TRANSORANJE SCHOOL FOR THE DEAF, MECHANICAL BOQ
DEPARTMENT OF INFRASTRUCTURE DEVELOPMENT
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
FIRE PROTECTION INSTALLATIONS-M1
(a) This part of the BoQ must be priced by a specialist
fire protection sub-contractors to reduce failure due
to financial risk.
(b) The main contractor shall provide a CV or brochure
for a specialist fire protection sub-contractor before
work starts for approval by engineer.
( c) Allow for the specialist fire protection sub-contractor
to visit the site and take measurements Sum 1
(d) Allow for production of factory shop drawings Sum 1
( e) Allow for submission of brochures & datasheets for
equipment to be supplied before equipment is
purchased
(f) Contractor must carefully study the Gauteng
Province Department of Infrastructure Standard
Quality Specifications ,project specification SANS
standards and the site before submitting
tenders.Contractors will be expected to submit
SABS Mark samples and SABS certificates before
purchasing all materials.
CD available from DID offices
(g) The fire protection installations should comply with
fire requirements of SANS (NBR) with special
reference to Part O, T and W in relation to
mechanical installation. Notwithstanding the
regulation and or the rational fire design
the requirements are to be met
(h) All work should comform to requirements of the
Standard Quality Specification for Fire Protection-
DID-E/M1 and Standard Quality Specification for
Ventilation and Air Conditioning- DID-E/M6
Carried to Collection
MECHANICAL SERVICES
OCTOBER 2016 1
TRANSORANJE SCHOOL FOR THE DEAF, MECHANICAL BOQ
DEPARTMENT OF INFRASTRUCTURE DEVELOPMENT
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
Fire Hydrants
All Fire Hydrants shall comply with the
requirements of SANS 1128-1.
1.0 Supply, install, test and commission Ø65mm Twin
Fire Booster connection complete with Plastic
material dust covers and connecting chain, 65mm
Pressure Gauge Adaptor with Ball Valve. Twin
booster shall be installaed at site entrance or in a
suitable position for access by the Fire Brigade. No. 1
1.1 Supply, install, test and commission Ø100mm
suction hydrant complete with Storz couplings and
plastic cover.
1.2 Supply No. 1
1.3 Install No. 1
1.4 Supply, install, test and commission 80mm x 65mm
Right Angled Tamperproof Hydrant with single lug
outlet and supplied complete with Tee key for
opening valve
1.5 Supply No. 12
1.6 Install No. 12
Fire Hose Reels
All Fire Hose Reels shall comply with the
requirements of SANS 543, and shall be in
installed accordance with SANS 10105-1 and
SANS 10400-W and the Department's Document
GP/M1 Rev 1.
2.0 Supply, install, test and commission SABS approved
fire hose reel fitted with 30m length of 20mm hose
mountedon wall bracket bolted to wall behind. The FHR to be
installed complete with 25mm chromium shut-off
valve, valve and a ø7mm aluminium nozzle and hose guide
FHR to be in red painted steel enclosures with
breakable glass and key.
2.1 Supply No. 342.2 Install No. 34
2.3 Supply ,install steel cabinets large enough to house 10kg hand held unit Fire extinguishers below the hose hose reels and should be with a break glass units
2.4 Supply No. 342.5 Install No. 34
Carried to Collection
MECHANICAL SERVICES
OCTOBER 2016 2
TRANSORANJE SCHOOL FOR THE DEAF, MECHANICAL BOQ
DEPARTMENT OF INFRASTRUCTURE DEVELOPMENT
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
Portable Fire extinguishers
All Portable Fire Extinguishers shall comply with the
requirements of SANS 1910, and the Department's requirements of SANS 1910, and the Department's
Document GP/M1 Rev 1
3.0 Supply and install 10kg Carbon Dioxide (CO2) type
fire extingusher
3.1 Supply No. 20
3.2 Supply and install a tamper proof translucent
polycarbonate enclosure for the 10 kg Carbon Dioxide
(CO2) Fire Extinguisher
3.3 Supply No. 203.4 Install No. 20
3.5 Supply 4.5kg Dry Chemical Powder (DCP) type fire
extingusher. One for each classroom and HOD
offices.3.6 Supply No. 130
Install No. 130
3.7 Supply and install a tamper proof translucent
polycarbonate enclosure for the 4,5 Dry Chemical
Powder (DCP) Fire Extinguisher. One for each
classroom and HOD offices.
3.8 Supply No. 1303.9 Install No. 130
Fire Signage
Photoluminescent fire signage and direction
location signage and warning notices in accordance
with SANS 1186-1: 2008, and incorporating the
pictographs in the standard size 190 x 190mm,
securely fixed to wall, door, ceiling or soffit as
required and as may be indicated on drawings and
architectural specifications.
4.0 Supply and install Photoliminescent fire fighting
equipmentdesignation, location and general escape symbolic
signsin accordance with SANS 1186-1: 2008.
4.1 Supply Sum 300
4.2 Install Sum 300
,
5 Fire Water Storage Tank
Supply and install 4.88m L x 2.44m W x 2.44m H (30kL)
sectional steel panel fire water storage tank to be
mounted on a purpose-made 1 x 5 metre elevated
steel structure stand. Or approved
5.01 Supply Sum 1
5.02 Install sum 1
5.03 Delivery to site Sum 1
5.03b Allow for builders works for tank and pump room as Sum lot
shown on fire protection site reticulation drawing
LXWXH=12000mmX8000mmX3500mm or to fit the
approved tank size and pumps
Carried to Collection
MECHANICAL SERVICES
OCTOBER 2016 3
TRANSORANJE SCHOOL FOR THE DEAF, MECHANICAL BOQ
DEPARTMENT OF INFRASTRUCTURE DEVELOPMENT
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
5.04 Supply, install test and commision, a 1 x electric fire and 1 standby Diesel water booster pump complete
with electricmono block jockey pump equipped
with an EP8 pressure switch operated auto start
arrangement equipped with pressure gauges.The
system to be equipped with isolating ball valves,
strainers,non-return valves IP54 electrical control
panel c/w alarm, galvanised inletand outlet
manifolds all on a base pre-piped, pre-wiredand
tested.
5.05 Hydrant & Hosereel Diesel Driven Pumpset
- Pressure head: - 10.7 bars
- Flow rate: - 42 litres per second
Supply No. 1
Install No. 1
5.06 Hydrant & Hosereel Electric Driven Pumpset
- Pressure head: - 10.7 bars
- Flow rate: - 42 litres per second
Supply No. 1
Install No. 1
5.07 Hydrant & Hosereel Jockey Pump
Duty: 4.2 litres per second @ 11.7bar
Supply No. 1
Install No. 1
6.0 TANK AND BOOSTER PUMPS PIPEWORK
Supply and install galvanised pipework c/w fittings
and pipe supports within pump house
6.01 100mm diameter m 6
6.02 80mm diameter m 6
6.03 50mm diameter m
6.04 Supply and Install isolation Valves on pump pipeworks
6.05 100mm diameter No 2
6.06 80mm diameter No 4
6.07 Suppy and install non return valves as shown on the
drawings on pump pipeworks
6.08 100mm diameter No 2
6.09 80mm diameter No 1
Carried to Collection
MECHANICAL SERVICES
OCTOBER 2016 4
TRANSORANJE SCHOOL FOR THE DEAF, MECHANICAL BOQ
DEPARTMENT OF INFRASTRUCTURE DEVELOPMENT
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
6.10 Suppy and install strainers as shown on the
drawings on pump pipeworks
6.11 100mm diameter No 2
6.12 80mm diameter No 2
6.13 Suppy and install bends as shown on the
drawings on pump pipeworks
6.14 100mm diameter No 4
6.15 80mm diameter No 4
6.16 Suppy and install Tees as shown on the
drawings on pump pipeworks
6.17 80mm-100mm-80mm diameter No 2
6.18 100mm -100mm-100mm diameter No 2
6.19 80mm -80mm-80mm diameter No 2
6.2 Suppy and install Reducers as shown on the
drawings on pump pipeworks
6.21 100mm-80mm diameter No 2
6.22 80mm-50mm diameter No 2
6.23 Suppy and install Drain Valves as shown on the
drawings on pump pipeworks
6.24 100mm diameter No 2
6..25 80mm diameter No 2
6.26 Suppy and install Flexibles as shown on the
drawings on pump pipeworks
6.27 100mm diameter No 2
6.28 80mm diameter No 2
6.29 Allow for pump mounting and tank mounting base lot 1
6.30 Suppy and install pressure gauge as shown on the No 2
drawings on pump pipeworks
6.31 Suppy and install flow switch No 1
6.32 Allow for all other valves and fittings not specified
but needed for successful installation of Tank and
pumps lot 1
Carried to Collection
MECHANICAL SERVICES
OCTOBER 2016 5
TRANSORANJE SCHOOL FOR THE DEAF, MECHANICAL BOQ
DEPARTMENT OF INFRASTRUCTURE DEVELOPMENT
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
to protect pumps against fire engine boosters
Supply No 2
install No 2
6.34 CONTROL PANELS
Supply, install and connect weatherproof control
panels for the booster pump sets complete with
alarms and other accessories
Supply No. 1
Install No. 1
HDPE Pipework
All underground pipework shall be High Pressure
Class16 type IV HDPE used in conjunction with
compressionfittings.
7 150mm diameter High pressure class 16 HDPE pipes
laid in ground not more than 1000mm deep m 1700
7.01 110mm diameter High pressure class 16 HDPE pipes
laid in ground not more than 1000mm deep m 1300
7.1 50mm diameter High pressure class 16 HDPE pipes
laid in ground not more than 1000mm deep m 300
7.2 32mm diameter High pressure class 16 HDPE pipes
laid in ground not more than 1000mm deep
m 0
Extra over HDPE pipework for fittings, as shown on
the drawings:
Tees
7.3 150mm-110mm-150mm No. 12
7.4 110mm-50mm-110m No 6
7.5 110mm-110mm-110mm No. 3
Bends
7.7 150mm diameter No. 4
7.8 110mm diameter No. 16
7.9 25mm diameter No. 0
Carried to Collection
MECHANICAL SERVICES
OCTOBER 2016 6
TRANSORANJE SCHOOL FOR THE DEAF, MECHANICAL BOQ
DEPARTMENT OF INFRASTRUCTURE DEVELOPMENT
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
Adapters
7.10 150mm to 110mm HDPE to iron adaptors No. 15
7.11 110mm to 50mm HDPE to iron adaptors No. 13
7.12 75mm to 50mm HDPE to iron adaptors No. 0
7.13 32mm to 25mm HDPE to iron adaptors No. 15
7.14 50mm to 32mm HDPE to iron adaptors No. 0
Galvanised Mild Steel Pipework
Medium class galvanised mild steel (GMS)
screwed all necessary supports, fixing, brackets, saddles,
holderbats, etc, and pained red in accordance
with SANS 10140-3:2003: in the running length, and all
necessary supports, fixing, brackets, saddles, holderbats,
etc, and pained red in accordance with SANS 10140-
3:2003:
7.15 75mm diameter pipes m 0
7.16 50mm diameter pipes m 0
7.17 32mm diameter pipes m 0
7.18 25mm diameter pipes m 300
Extra over GMS pipework for fittings, as shown on the
drawings:
Tees
7.19 110mm diameter No. 0
7.20 25mm diameter No. 0
Bends
7.21 110mm diameter No. 0
7.22 25mm diameter No. 140
Carried to Collection
MECHANICAL SERVICES
OCTOBER 2016 7
TRANSORANJE SCHOOL FOR THE DEAF, MECHANICAL BOQ
DEPARTMENT OF INFRASTRUCTURE DEVELOPMENT
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
Operating and Maintenance Procedures
8.0 Compilation and submission of 4 No. Operation &
installation. No 4
Test and Commissioning
8.1 Allow for testing of entire fire protection installation
after completion Sum 1
8.2 Test again in the presence of and to entire
satisfation the consulting engineer
8.3 Testing and commission of the completed fire
protection installation Item 1
8.5 Attendance and profits on tests Item 1
8.6 Credit for redundant materials and equipment
8.7 Allow for inspections and measurements as
required for the shop drawings and detailed design
of installation 1
8.8 Allow for monthly site meetings and managing of
8.10 Allow for record drawings and operating instructions 1
8.11 Allow for transportation/travelling charges 1Allow for maintenance and specialist maintenance as
specified
8.12 Allow for 12 months guarantee in terms of the
Document 1
8.13 Allow for all transport and rigging, lifting gear, cranes
etc. that may be required for moving of plant
and equipment setting out works 1
8.14 Allow for attendance on main contractor and for
switching off, removing all redundant items and
earthing to make supply safe and re-energise after 1
installation
AS-BUILT INFORMATION AND OPERATING AND
MAINTENANCE MANUALS
8.15 Obtaining of all available information, compiling,
eproducing and finalising three sets of as-built and
Operating and Maintenance manuals 3
Carried to Collection
MECHANICAL SERVICES
OCTOBER 2016 8
TRANSORANJE SCHOOL FOR THE DEAF, MECHANICAL BOQ
DEPARTMENT OF INFRASTRUCTURE DEVELOPMENT
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
SHOP AND "AS BUILT" DRAWINGS
drawings and 'as built" drawings to the entire works
and all its components include for 3 copies of all
drawings or approval carring out corrections as
required by engineer No. 3
TRAINING
8.17 Presenting a training course for operators 1
8.18 Presenting training course for maintenance staff 1
EQUIPMENT SELECTIONS
8.20 Provide detailed selections and samples as
required for approval before installing Sum 4
OPERATION AND MAINTENANCE MANUALS
8.21 Provide Operating and Maintenance Manuals:
including "as built" drawings and equpment
selection information No. 3
Other
8.24 Any other items required for the successful
completion of the work but not included in this
bill of quantities. Please specify :
Carried to Collection
CARRIED TO SUMMARY PAGE
SUB-TOTAL FOR FIRE PROTECTION
MECHANICAL SERVICES
OCTOBER 2016 9
TRANSORANJE SCHOOL FOR THE DEAF, MECHANICAL BOQ
DEPARTMENT OF INFRASTRUCTURE DEVELOPMENT
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
WET SERVICES INSTALLATIONS-M2
(a) This part of the BoQ must be priced by a specialist
plumber and solar sub-contractors to reduce failure
due financial risk.
(b) The main contractor shall provide a CV or brochure
for a specialist plumber and Solar sub-contractor
before work starts for approval by engineer.
( c) Allow for the specialist plumber and solar sub-
contractor to visit the site and take measurements Sum 1
(d) Allow for production of factory shop drawings Sum 1
( e) Allow for submission of brochures for equipment to
be purchased before equipment is purchased
(f) Contractor must study carefully the DID, GP SQS
specifications, project specification, SANS
standards and the site before submitting
tenders.Contractors will be expected to submit
SABS Mark samples and SABS certificates before
purchasing all materials.
(g) All work should conform to the requirements of the
Standard Quality Specification for Wet Services-
DID-E/M2
(h) All domesttic Water installations shall comply with
SANS 105252-1;2012
(i) COLD WATER SUPPLY RETICULATION
All rates supplied in this bill of quantities will be
deemed to include scaffolding to any height and
fixing of cold and hot water pipes up to and
including roof height.
All cold water supply pipes are to be chased into
walls except where pipes are to be surface-
mounted on wall face and fixed with standard type
pipe saddles and brackets.
(j) Copper Pipework
Half hard drawn copper pipes to SANS 460 Class
1 and SANS 1067 with capillary type soldered
joints done in accordance with the manufacturer's
specifications, and installed in accordance with
SANS 10400:2011 and SANS 10252-1:2004,
including couplers in the running length, and all
necessary supports, fixing, brackets,saddles,
holderbats, etc, and colour-coded in accordance
with SANS 10140-3:2003:
Carried to Collection
MECHANICAL SERVICES
OCTOBER 2016 10
TRANSORANJE SCHOOL FOR THE DEAF, MECHANICAL BOQ
DEPARTMENT OF INFRASTRUCTURE DEVELOPMENT
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
All rates supplied in this bill of quantities will be
deemed to include scaffolding to any height and
fixing of cold and hotwater pipes up to and including
roof height.
All pipes suspended from concrete slabs, roof,
ceiling, etc, shall be deemed to include in the rates
all necessary hanger brackets, threaded rod
(irrespective of the suspension length), nuts,
washers, anchors and drilling of holes in the
concrete slab.
All hot water pipes are to be chased into walls
except where pipes are to be surface-mounted on
wall face or run in ceiling voids or inside ducts, and
fixed with standard type pipe saddles and brackets
at 1000mm maximum.
(l) Copper Pipework
Hard drawn copper pipes to SANS 460 and SANS
1067 with capillary type soldered joints done in
accordance with the manufacturer's specifications,
and installed in accordance with SANS 10400:2010
and SANS 10252-1:2004, including couplers in the
running length, and all necessary supports, fixing,
brackets, saddles, holderbats, etc, and colour-coded
in accordance with SANS 10140-3:2003. Installation
to comply with the Department's document GP/M2
Rev 1.
(m) Hot Water Supply
Straight copper piping not chased in walls but
surface-mounted fixed to walls, or in celing voids or
in service ducts are to be insulated with 25mm thick
pre-formed fibreglass sections (lagging) in
accordance with SANS 612:2007. The insulation
is to be clad in galvanised muffs secured with
10mm galvanised strapping and seal. Water proof
material and paint to be applied where the pipes run
below slab.Bends to be insulated with fibreglass
with 'Insulpro' hardsetting plaster protected with
gauze reinforced mastic.
Valves, strainers and flanges will not be insulated.
All materials and equipment, etc, are to be supplied
by the Contractor.
Carried to Collection
MECHANICAL SERVICES
OCTOBER 2016 11
TRANSORANJE SCHOOL FOR THE DEAF, MECHANICAL BOQ
DEPARTMENT OF INFRASTRUCTURE DEVELOPMENT
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
PRE SCHOOL HOSTEL
REMOVALS
1.0 Disconnect and make safe existing electric water
hot geyser No. 0
1.1 Remove from site existing hot water geyser and
cold water piping No. 0
1.2 Cutting of walls to remove pipes in the wall No. 0
1.3 Safe keeping all the accessories associated with
pipes, eg basins, shower heads, baths etc No. o
NEW INSTALLATIONS
Cold Water Supply
2.0 15mm diameter pipes. m 24
2.1 22mm diameter pipes. m 70
2.2 28mm diameter insulated pipes. m 0
2.3 35mm diameter insulated pipes. m 0
2.4 42mm diameter pipes. m 0
2.5 54mm diameter pipes. m 0
2.6 67mm diameter pipes. m 0
Extra over copper pipework for fittings, as shown on
the Hot and Cold Water Plumbing Layout drawings:
Bends
2.7 15mm diameter No 20
2.8 22mm diameter No 40
2.9 28mm diameter No 0
2.10 35mm diameter No 0
2.11 42mm diameter No 0
2.12 54mm diameter No 0
2.13 67mm diameter No 0
Carried to Collection
MECHANICAL SERVICES
OCTOBER 2016 12
TRANSORANJE SCHOOL FOR THE DEAF, MECHANICAL BOQ
DEPARTMENT OF INFRASTRUCTURE DEVELOPMENT
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
2.15 32mm-22mm-32mm diameter No 2
2.16 22mm-22mm-22mm diameter No 10
2.17 22mm-15mm-22mm diameter No 12
2.18 54mm diameter No 0
2.19 67mm diameter No 0
Reducers
2.20 50mm-32mm diameter No 4
2.21 32mm -22mm diameter No 4
2.22 32mm-15mm diameter No 4
2.23 22mm-15mm diameter No 0
2.24 42mm diameter No 0
2.25 54mm diameter No 0
2.26 67mm diameter No 0
Adapters
2.27 25mm Plastic to Male Iron adapter No 4
2.28 65mm Plastic to Male Iron adapter No 0
SOLAR WATER HEATERS
3.0 Supply, install, test and commission a double
jacketed, direct thermosiphon circulation type 200
litre solar water heater, complete with 3kW
electrical heater back-up element and 2 x 2m flat
plate solar collectors, 10m of copper piping,
insulation, 2-off 20mm vacuum breakers, 15mm
expansion relief valve, lever ball valves, mixing
valve, temperature differential controller, hot water
pipe insulation and truss strengthening where
required. Installation to comply with the
Department's document GP/M 2 Rev 1. Units to be
SABS Mark with SABS certificate.
Carried to Collection
MECHANICAL SERVICES
OCTOBER 2016 13
TRANSORANJE SCHOOL FOR THE DEAF, MECHANICAL BOQ
DEPARTMENT OF INFRASTRUCTURE DEVELOPMENT
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
Cylinder (mounted on roof)
Cylinder Capacity: 200 litres
Cylinder Material: SS 441;
Cylinder Material Thickness: 1.5mm
Design Working Pressure: 400kPa
Glazing Material: 3.2mm tampered low iron.
Absorber Material: Steel
Absorber Surface: Black Chrome selective surface
Solar Collector Mounting: North Facing
No. of Solar collectors: 2
Collector Aperture: 1.86m2
Full Weight of System incl. frame: 500kg
Solar Collector Mounting: North Facing
3.1 Supply No. 6
3.2 Install No. 6
3.4 Installation of Solar Controller No. 1
3.5 Installation of timer No. 1
Copper pipe work
3.6 15mm diameter insulated pipes m 24
3.7 22mm diameter insulated pipes m 20
3.8 28mm diameter insulated pipes m 36
Extra over copper pipework for fittings, as shown on
Hot and Cold Water Plumbing Layout drawings:
Bends
3.9 15mm diameter No 15
3.10 22mm diameter No 25
3.11 28mm diameter No 0
3.12 35mm diameter No 0
Equal Tees
3.13 15mm diameter No 15
3.14 22mm diameter No 25
3.15 38mm diameter No 0
3.16 42mm diameter No 0
Carried to Collection
MECHANICAL SERVICES
OCTOBER 2016 14
TRANSORANJE SCHOOL FOR THE DEAF, MECHANICAL BOQ
DEPARTMENT OF INFRASTRUCTURE DEVELOPMENT
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
Reducers
3.17 28mm-22mm diameter No 4
3.18 22mm-15mm diameter No 4
3.19 35mm diameter No 0
Valves
5mm diameter stopcock/angle valve on cold and
3.20 hot water pipes to sanitary appliances. No 20
3.21 20mm diameter isolation ballvalve on cold water
pipes No 0
3.22 25mm diameter isolation ballvalve on cold water
pipe. No 0
3.23 65mm diameter isolation ballvalve on cold water
pipes. No 0
Carried to Collection
,
MECHANICAL SERVICES
OCTOBER 2016 15
TRANSORANJE SCHOOL FOR THE DEAF, MECHANICAL BOQ
DEPARTMENT OF INFRASTRUCTURE DEVELOPMENT
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
HALL
REMOVALS
1.0 Disconnect and make safe existing hot water
geyser No. 1
1.1 Remove from site existing hot water geyser and
cold water piping No. 1
1.2 Cutting of walls to remove pipes in the wall No. 1
1.3 Safe keeping all the associated with pipes, eg
basins, shower heads, baths etc No. 1
NEW INSTALLATIONS
Cold Water Supply
2.0 15mm diameter pipes. m 30
2.1 22mm diameter pipes. m 40
2.2 28mm diameter insulated pipes. m 0
2.3 35mm diameter insulated pipes. m 0
2.4 42mm diameter pipes. m 0
2.5 54mm diameter pipes. m 0
2.6 67mm diameter pipes. m 0
Extra over copper pipework for fittings, the as
shown on Hot and Cold Water Plumbing:
Bends
2.7 15mm diameter No 20
2.8 22mm diameter No 10
2.9 28mm diameter No 0
2.10 35mm diameter No 0
2.11 42mm diameter No 0
2.12 54mm diameter No 0
2.13 67mm diameter No 0
Carried to Collection
MECHANICAL SERVICES
OCTOBER 2016 16
TRANSORANJE SCHOOL FOR THE DEAF, MECHANICAL BOQ
DEPARTMENT OF INFRASTRUCTURE DEVELOPMENT
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
Tees
2.14 50mm-32mm-50mm diameter No 2
2.15 32mm-22mm-32mm diameter No 0
2.16 22mm-22mm-22mm diameter No 10
2.17 22mm-15mm-22mm diameter No 20
2.18 54mm diameter No 0
Reducers
2.20 50mm-32mm diameter No 2
2.21 32mm -22mm diameter No 0
2.22 32mm-15mm diameter No 0
2.23 22mm-15mm diameter No 2
2.24 42mm diameter No 0
2.25 54mm diameter No 0
2.26 67mm diameter No 0
Adapters
2.27 25mm Plastic to Male Iron adapter No 0
2.28 65mm Plastic to Male Iron adapter No 0
SOLAR WATER HEATERS
3.0 Supply, install, test and commission a double
jacketed, direct thermosiphon circulation type 200
litre solar water heater, complete with 3kW
electrical heater back-up element and 2 x 2m flat
plate solar collectors, 10m of copper piping,
insulation, 2-off 20mm vacuum breakers, 15mm
expansion relief valve, lever ball valves, mixing
valve, temperature differential controller, hot water
pipe insulation and truss strengthening where
required. Installation to comply with the
Department's document GP/M 2 Rev 1. Units to be
SABS Mark with SABS certificate.
Carried to Collection
MECHANICAL SERVICES
OCTOBER 2016 17
TRANSORANJE SCHOOL FOR THE DEAF, MECHANICAL BOQ
DEPARTMENT OF INFRASTRUCTURE DEVELOPMENT
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
Cylinder (mounted on roof)
Cylinder Capacity: 200 litres
Cylinder Material: SS 441;
Cylinder Material Thickness: 1.5mm
SABS Pressure Rating: 600kPa
Design Working Pressure: 400kPa
Glazing Material: 3.2mm tampered low iron.
Absorber Material: Steel
Absorber Surface: Black Chrome selective surface
Solar Collector Mounting: North Facing
No. of Solar collectors: 2
Full Weight of System incl. frame: 500kg
Solar Collector Mounting: North Facing
3.1 Supply No. 4
3.2 Install No. 4
3.4 Installation of Solar Controller No. 1
3.5 Installation of timer No. 1
Copper pipe work
3.6 15mm diameter insulated pipes m 15
3.7 22mm diameter insulated pipes m 30
3.8 28mm diameter insulated pipes m
Extra over copper pipework for fittings, as shown on
the Hot and Cold Water Plumbing Layout drawings:
Bends
3.9 15mm diameter No 20
3.10 22mm diameter No 10
3.11 28mm diameter No 0
3.12 35mm diameter No 0
Equal Tees
3.13 15mm diameter No 20
3.14 22mm diameter No 10
3.15 38mm diameter No 0
3.16 42mm diameter No 0
Carried to Collection
MECHANICAL SERVICES
OCTOBER 2016 18
TRANSORANJE SCHOOL FOR THE DEAF, MECHANICAL BOQ
DEPARTMENT OF INFRASTRUCTURE DEVELOPMENT
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
Reducers
3.17 28mm-22mm diameter No 2
3.18 22mm-15mm diameter No 2
3.19 35mm diameter No 0
Valves
5mm diameter stopcock/angle valve on cold and
3.20 hot water pipes to sanitary appliances. No 14
3.21 20mm diameter isolation ballvalve on cold water
pipes No 0
3.22 25mm diameter isolation ballvalve on cold water
pipe. No 0
3.23 65mm diameter isolation ballvalve on cold water
pipes. No 0
Carried to Collection
,
MECHANICAL SERVICES
OCTOBER 2016 19
TRANSORANJE SCHOOL FOR THE DEAF, MECHANICAL BOQ
DEPARTMENT OF INFRASTRUCTURE DEVELOPMENT
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
LAUNDRY
REMOVALS
1.0 Disconnect and make safe existing hot water
geyser No. 1
1.1 Remove from site existing hot water geyser and
cold water piping No. 1
1.2 Cutting of walls to remove pipes in the wall No. 1
1.3 Safe keeping all the associated with pipes, eg
basins, shower heads, baths etc No. 1
NEW INSTALLATIONS
Cold Water Supply
2.0 15mm diameter pipes. m 18
2.1 22mm diameter pipes. m 50
2.2 28mm diameter insulated pipes. m 0
2.3 35mm diameter insulated pipes. m 0
2.4 42mm diameter pipes. m 0
2.5 54mm diameter pipes. m 0
2.6 67mm diameter pipes. m 0
Extra over copper pipework for fittings, as shown on
the Hot and Cold Water Plumbing Layout drawings:
Bends
2.7 15mm diameter No 15
2.8 22mm diameter No 18
2.9 28mm diameter No 0
2.10 35mm diameter No 0
2.11 42mm diameter No 0
2.12 54mm diameter No 0
2.13 67mm diameter No 0
Carried to Collection
MECHANICAL SERVICES
OCTOBER 2016 20
TRANSORANJE SCHOOL FOR THE DEAF, MECHANICAL BOQ
DEPARTMENT OF INFRASTRUCTURE DEVELOPMENT
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
Tees
2.14 50mm-32mm-50mm diameter No 0
2.15 32mm-22mm-32mm diameter No 0
2.16 22mm-22mm-22mm diameter No 2
2.17 22mm-15mm-22mm diameter No 12
2.18 54mm diameter No 0
2.19 67mm diameter No 0
Reducers
2.20 50mm-32mm diameter No 2
2.21 32mm -22mm diameter No 2
2.22 32mm-15mm diameter No 0
2.23 22mm-15mm diameter No 2
2.24 42mm diameter No 0
2.25 54mm diameter No 0
2.26 67mm diameter No 0
Adapters
2.27 25mm Plastic to Male Iron adapter No 4
2.28 65mm Plastic to Male Iron adapter No 0
SOLAR WATER HEATERS
3.0 Supply, install, test and commission a double
jacketed, direct thermosiphon circulation type 200
litre solar water heater, complete with 3kW
electrical heater back-up element and 2 x 2m flat
plate solar collectors, 10m of copper piping,
insulation, 2-off 20mm vacuum breakers, 15mm
expansion relief valve, lever ball valves, mixing
valve, temperature differential controller, hot water
pipe insulation and truss strengthening where
required. Installation to comply with the
Department's document GP/M 2 Rev 1. Units to be
SABS Mark with SABS certificate.
Carried to Collection
MECHANICAL SERVICES
OCTOBER 2016 21
TRANSORANJE SCHOOL FOR THE DEAF, MECHANICAL BOQ
DEPARTMENT OF INFRASTRUCTURE DEVELOPMENT
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
Cylinder (mounted on roof)
Cylinder Capacity: 200 litres
Cylinder Material: SS 441;
Cylinder Material Thickness: 1.5mm
SABS Pressure Rating: 600kPa
Design Working Pressure: 400kPa
Glazing Material: 3.2mm tampered low iron.
Absorber Material: Steel
Absorber Surface: Black Chrome selective surface
Solar Collector Mounting: North Facing
No. of Solar collectors: 2
Collector Aperture: 1.86m2
Full Weight of System incl. frame: 500kg
Solar Collector Mounting: North Facing
3.1 Supply No. 1
3.2 Install No. 1
3.4 Installation of Solar Controller No. 1
3.5 Installation of timer No. 1
Copper pipe work
3.6 15mm diameter insulated pipes m 20
3.7 22mm diameter insulated pipes m 55
3.8 28mm diameter insulated pipes m 0
Extra over copper pipework for fittings, as shown on
the Hot and Cold Water Plumbing Layout drawings:
Bends
3.9 15mm diameter No 18
3.10 22mm diameter No 10
3.11 28mm diameter No 0
3.12 35mm diameter No 0
Equal Tees
3.13 15mm diameter No 10
3.14 22mm diameter No 8
3.15 38mm diameter No 0
3.16 42mm diameter No 0
Carried to Collection
MECHANICAL SERVICES
OCTOBER 2016 22
TRANSORANJE SCHOOL FOR THE DEAF, MECHANICAL BOQ
DEPARTMENT OF INFRASTRUCTURE DEVELOPMENT
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
Reducers
3.17 28mm-22mm diameter No 4
3.18 22mm-15mm diameter No 4
3.19 35mm diameter No 0
Valves
5mm diameter stopcock/angle valve on cold and
3.20 hot water pipes to sanitary appliances. No 14
3.21 20mm diameter isolation ballvalve on cold water
pipes No 0
3.22 25mm diameter isolation ballvalve on cold water
pipe. No 0
3.23 65mm diameter isolation ballvalve on cold water
pipes. No 0
Carried to Collection
,
MECHANICAL SERVICES
OCTOBER 2016 23
TRANSORANJE SCHOOL FOR THE DEAF, MECHANICAL BOQ
DEPARTMENT OF INFRASTRUCTURE DEVELOPMENT
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
PRE SCHOOL TOILETS
REMOVALS
1.0 Disconnect and make safe existing hot water
geyser No. 1
1.1 Remove from site existing hot water geyser and
cold water piping No. 1
1.2 Cutting of walls to remove pipes in the wall No. 1
1.3 Safe keeping all the associated with pipes, eg
basins, shower heads, baths etc No. 1
NEW INSTALLATIONS
Cold Water Supply
2.0 15mm diameter pipes. m 15
2.1 22mm diameter pipes. m 40
2.2 28mm diameter insulated pipes. m 0
2.3 35mm diameter insulated pipes. m 0
2.4 42mm diameter pipes. m 0
2.5 54mm diameter pipes. m 0
2.6 67mm diameter pipes. m 0
Extra over copper pipework for fittings, as shown on
the Hot and Cold Water Plumbing Layout drawings:
Bends
2.7 15mm diameter No 15
2.8 22mm diameter No 10
2.9 28mm diameter No 0
2.10 35mm diameter No 0
2.11 42mm diameter No 0
2.12 54mm diameter No 0
2.13 67mm diameter No 0
Carried to Collection
MECHANICAL SERVICES
OCTOBER 2016 24
TRANSORANJE SCHOOL FOR THE DEAF, MECHANICAL BOQ
DEPARTMENT OF INFRASTRUCTURE DEVELOPMENT
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
Tees
2.14 50mm-32mm-50mm diameter No 1
2.15 32mm-22mm-32mm diameter No 1
2.16 22mm-22mm-22mm diameter No 2
2.17 22mm-15mm-22mm diameter No 15
2.18 54mm diameter No 0
2.19 67mm diameter No 0
Reducers
2.20 50mm-32mm diameter No 4
2.21 32mm -22mm diameter No 4
2.22 32mm-15mm diameter No 4
2.23 22mm-15mm diameter No 0
2.24 42mm diameter No 0
2.25 54mm diameter No 0
2.26 67mm diameter No 0
Adapters
2.27 22mm Plastic to Male Iron adapter No 0
2.28 65mm Plastic to Male Iron adapter No 0
SOLAR WATER HEATERS
3.0 Supply, install, test and commission a double
jacketed, direct thermosiphon circulation type 200
litre solar water heater, complete with 3kW
electrical heater back-up element and 2 x 2m flat
plate solar collectors, 10m of copper piping,
insulation, 2-off 20mm vacuum breakers, 15mm
expansion relief valve, lever ball valves, mixing
valve, temperature differential controller, hot water
pipe insulation and truss strengthening where
required. Installation to comply with the
Department's document GP/M 2 Rev 1. Units to be
SABS Mark with SABS certificate.
Carried to Collection
MECHANICAL SERVICES
OCTOBER 2016 25
TRANSORANJE SCHOOL FOR THE DEAF, MECHANICAL BOQ
DEPARTMENT OF INFRASTRUCTURE DEVELOPMENT
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
Cylinder (mounted on roof)
Cylinder Capacity: 200 litres
Cylinder Material: SS 441;
Cylinder Material Thickness: 1.5mm
SABS Pressure Rating: 600kPa
Design Working Pressure: 400kPa
Glazing Material: 3.2mm tampered low iron.
Absorber Material: Steel
Absorber Surface: Black Chrome selective surface
Solar Collector Mounting: North Facing
No. of Solar collectors: 2
Collector Aperture: 1.86m2
Full Weight of System incl. frame: 500kg
Solar Collector Mounting: North Facing
3.1 Supply No. 4
3.2 Install No. 4
3.4 Installation of Solar Controller No. 1
3.5 Installation of timer No. 1
Copper pipe work
3.6 15mm diameter insulated pipes m 26
3.7 22mm diameter insulated pipes m 15
3.8 28mm diameter insulated pipes m 36
Extra over copper pipework for fittings, as shown on
the Hot and Cold Water Plumbing Layout drawings:
Bends
3.9 15mm diameter No 18
3.10 22mm diameter No 28
3.11 28mm diameter No 0
3.12 35mm diameter No 0
Equal Tees
3.13 15mm diameter No 15
3.14 22mm diameter No 25
3.15 38mm diameter No 0
3.16 42mm diameter No 0
Carried to Collection
MECHANICAL SERVICES
OCTOBER 2016 26
TRANSORANJE SCHOOL FOR THE DEAF, MECHANICAL BOQ
DEPARTMENT OF INFRASTRUCTURE DEVELOPMENT
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
Reducers
3.17 28mm-22mm diameter No 4
3.18 22mm-15mm diameter No 4
3.19 35mm diameter No 0
Valves
5mm diameter stopcock/angle valve on cold and
3.20 hot water pipes to sanitary appliances. No 15
3.21 20mm diameter isolation ballvalve on cold water
pipes No 0
3.22 25mm diameter isolation ballvalve on cold water
pipe. No 0
3.23 65mm diameter isolation ballvalve on cold water
pipes. No 0
Carried to Collection
,
MECHANICAL SERVICES
OCTOBER 2016 27
TRANSORANJE SCHOOL FOR THE DEAF, MECHANICAL BOQ
DEPARTMENT OF INFRASTRUCTURE DEVELOPMENT
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
STAFF ROOM
REMOVALS
1.0 Disconnect and make safe existing hot water
geyser No. 1
1.1 Remove from site existing hot water geyser and
cold water piping No. 1
1.2 Cutting of walls to remove pipes in the wall No. 1
1.3 Safe keeping all the associated with pipes, eg
basins, shower heads, baths etc No. 1
NEW INSTALLATIONS
Cold Water Supply
2.0 15mm diameter pipes. m 20
2.1 22mm diameter pipes. m 60
2.2 28mm diameter insulated pipes. m 0
2.3 35mm diameter insulated pipes. m 0
2.4 42mm diameter pipes. m 0
2.5 54mm diameter pipes. m 0
2.6 67mm diameter pipes. m 0
Extra over copper pipework for fittings, as shown on
the Hot and Cold Water Plumbing Layout drawings:
Bends
2.7 15mm diameter No 15
2.8 22mm diameter No 30
2.9 28mm diameter No 0
2.10 35mm diameter No 0
2.11 42mm diameter No 0
2.12 54mm diameter No 0
2.13 67mm diameter No 0
Carried to Collection
MECHANICAL SERVICES
OCTOBER 2016 28
TRANSORANJE SCHOOL FOR THE DEAF, MECHANICAL BOQ
DEPARTMENT OF INFRASTRUCTURE DEVELOPMENT
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
Tees
2.14 50mm-32mm-50mm diameter No 2
2.15 32mm-22mm-32mm diameter No 2
2.16 22mm-22mm-22mm diameter No 5
2.17 22mm-15mm-22mm diameter No 12
2.18 54mm diameter No 0
2.19 67mm diameter No 0
Reducers
2.20 50mm-32mm diameter No 4
2.21 32mm -22mm diameter No 4
2.22 32mm-15mm diameter No 4
2.23 22mm-15mm diameter No 0
2.24 42mm diameter No 0
2.25 54mm diameter No 0
2.26 67mm diameter No 0
Adapters
2.27 25mm Plastic to Male Iron adapter No 0
2.28 65mm Plastic to Male Iron adapter No 0
SOLAR WATER HEATERS
3.0 Supply, install, test and commission a double
jacketed, direct thermosiphon circulation type 200
litre solar water heater, complete with 3kW
electrical heater back-up element and 2 x 2m flat
plate solar collectors, 10m of copper piping,
insulation, 2-off 20mm vacuum breakers, 15mm
expansion relief valve, lever ball valves, mixing
valve, temperature differential controller, hot water
pipe insulation and truss strengthening where
required. Installation to comply with the
Department's document GP/M 2 Rev 1. Units to be
SABS Mark with SABS certificate.
Carried to Collection
MECHANICAL SERVICES
OCTOBER 2016 29
TRANSORANJE SCHOOL FOR THE DEAF, MECHANICAL BOQ
DEPARTMENT OF INFRASTRUCTURE DEVELOPMENT
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
Cylinder (mounted on roof)
Cylinder Capacity: 200 litres
Cylinder Material: SS 441;
Cylinder Material Thickness: 1.5mm
SABS Pressure Rating: 600kPa
Design Working Pressure: 400kPa
Glazing Material: 3.2mm tampered low iron.
Absorber Material: Steel
Absorber Surface: Black Chrome selective surface
Solar Collector Mounting: North Facing
No. of Solar collectors: 2
Collector Aperture: 1.86m2
Full Weight of System incl. frame: 500kg
Solar Collector Mounting: North Facing
3.1 Supply No. 1
3.2 Install No. 1
3.4 Installation of Solar Controller No. 1
3.5 Installation of timer No. 1
Copper pipe work
3.6 15mm diameter insulated pipes m 40
3.7 22mm diameter insulated pipes m 20
3.8 28mm diameter insulated pipes m 0
Extra over copper pipework for fittings, as shown
on Hot and Cold Water Plumbing layout drawings
Bends
3.9 15mm diameter No 14
3.10 22mm diameter No 30
3.11 28mm diameter No 0
3.12 35mm diameter No 0
Equal Tees
3.13 15mm diameter No 5
3.14 22mm diameter No 4
3.15 38mm diameter No 0
3.16 42mm diameter No 0
Carried to Collection
MECHANICAL SERVICES
OCTOBER 2016 30
TRANSORANJE SCHOOL FOR THE DEAF, MECHANICAL BOQ
DEPARTMENT OF INFRASTRUCTURE DEVELOPMENT
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
Reducers
3.17 28mm-22mm diameter No 4
3.18 22mm-15mm diameter No 4
3.19 35mm diameter No 0
Valves
15mm diameter stopcock/angle valve on cold and
3.20 hot water pipes to sanitary appliances. No 14
3.21 20mm diameter isolation ballvalve on cold water
pipes No 0
3.22 25mm diameter isolation ballvalve on cold water
pipe. No 0
3.23 65mm diameter isolation ballvalve on cold water
pipes. No 0
Carried to Collection
,
MECHANICAL SERVICES
OCTOBER 2016 31
TRANSORANJE SCHOOL FOR THE DEAF, MECHANICAL BOQ
DEPARTMENT OF INFRASTRUCTURE DEVELOPMENT
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
HOUSE 2
REMOVALS
1.0 Disconnect and make safe existing hot water
geyser No. 1
1.1 Remove from site existing hot water geyser and
cold water piping No. 1
1.2 Cutting of walls to remove pipes in the wall No. 1
1.3 Safe keeping all the associated with pipes, eg
basins, shower heads, baths etc No. 1
NEW INSTALLATIONS
Cold Water Supply
2.0 15mm diameter pipes. m 30
2.1 22mm diameter pipes. m 20
2.2 28mm diameter insulated pipes. m 0
2.3 35mm diameter insulated pipes. m 0
2.4 42mm diameter pipes. m 0
2.5 54mm diameter pipes. m 0
2.6 67mm diameter pipes. m 0
Extra over copper pipework for fittings, as shown on
the Hot and Cold Water Plumbing Layout drawings:
Bends
2.7 15mm diameter No 10
2.8 22mm diameter No 15
2.9 28mm diameter No 0
2.10 35mm diameter No 0
2.11 42mm diameter No 0
2.12 54mm diameter No 0
2.13 67mm diameter No 0
Carried to Collection
MECHANICAL SERVICES
OCTOBER 2016 32
TRANSORANJE SCHOOL FOR THE DEAF, MECHANICAL BOQ
DEPARTMENT OF INFRASTRUCTURE DEVELOPMENT
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
Tees
2.14 50mm-32mm-50mm diameter No 2
2.15 32mm-22mm-32mm diameter No 2
2.16 22mm-22mm-22mm diameter No 5
2.17 22mm-15mm-22mm diameter No 6
2.18 54mm diameter No 0
2.19 67mm diameter No 0
Reducers
2.20 50mm-32mm diameter No 4
2.21 32mm -22mm diameter No 4
2.22 32mm-15mm diameter No 4
2.23 22mm-15mm diameter No 0
2.24 42mm diameter No 0
2.25 54mm diameter No 0
2.26 67mm diameter No 0
Adapters
2.27 25mm Plastic to Male Iron adapter No 4
2.28 65mm Plastic to Male Iron adapter No 0
SOLAR WATER HEATERS
3.0 Supply, install, test and commission a double
jacketed, direct thermosiphon circulation type 200
litre solar water heater, complete with 3kW
electrical heater back-up element and 2 x 2m flat
plate solar collectors, 10m of copper piping,
insulation, 2-off 20mm vacuum breakers, 15mm
expansion relief valve, lever ball valves, mixing
valve, temperature differential controller, hot water
pipe insulation and truss strengthening where
required. Installation to comply with the
Department's document GP/M 2 Rev 1. Units to be
SABS Mark with SABS certificate.
Carried to Collection
MECHANICAL SERVICES
OCTOBER 2016 33
TRANSORANJE SCHOOL FOR THE DEAF, MECHANICAL BOQ
DEPARTMENT OF INFRASTRUCTURE DEVELOPMENT
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
Cylinder (mounted on roof)
Cylinder Capacity: 200 litres
Cylinder Material: SS 441;
Cylinder Material Thickness: 1.5mm
SABS Pressure Rating: 600kPa
Design Working Pressure: 400kPa
Glazing Material: 3.2mm tampered low iron.
Absorber Material: Steel
Absorber Surface: Black Chrome selective surface
Solar Collector Mounting: North Facing
No. of Solar collectors: 2
Collector Aperture: 1.86m2
Full Weight of System incl. frame: 500kg
Solar Collector Mounting: North Facing
3.1 Supply No. 1
3.2 Install No. 1
3.4 Installation of Solar Controller No. 1
3.5 Installation of timer No. 1
Copper pipe work
3.6 15mm diameter insulated pipes m 30
3.7 22mm diameter insulated pipes m 25
3.8 28mm diameter insulated pipes m 0
Extra over copper pipework for fittings as shown on
Hot and Cold Water Plumbing Layout drawings:
Bends
3.9 15mm diameter No 14
3.10 22mm diameter No 20
3.11 28mm diameter No 0
3.12 35mm diameter No 0
Equal Tees
3.13 15mm diameter No 6
3.14 22mm diameter No 10
3.15 38mm diameter No 0
3.16 42mm diameter No 0
Carried to Collection
MECHANICAL SERVICES
OCTOBER 2016 34
TRANSORANJE SCHOOL FOR THE DEAF, MECHANICAL BOQ
DEPARTMENT OF INFRASTRUCTURE DEVELOPMENT
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
Reducers
3.17 28mm-22mm diameter No 5
3.18 22mm-15mm diameter No 5
3.19 35mm diameter No 0
Valves
15mm diameter stopcock/angle valve on cold and
3.20 hot water pipes to sanitary appliances. No 15
3.21 20mm diameter isolation ballvalve on cold water
pipes No 0
3.22 25mm diameter isolation ballvalve on cold water
pipe. No 0
3.23 65mm diameter isolation ballvalve on cold water
pipes. No 0
Carried to Collection
,
MECHANICAL SERVICES
OCTOBER 2016 35
TRANSORANJE SCHOOL FOR THE DEAF, MECHANICAL BOQ
DEPARTMENT OF INFRASTRUCTURE DEVELOPMENT
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
WORHSHOP 100
REMOVALS
1.0 Disconnect and make safe existing hot water
geyser No. 1
1.1 Remove from site existing hot water geyser and
cold water piping No. 1
1.2 Cutting of walls to remove pipes in the wall No. 1
1.3 Safe keeping all the associated with pipes, eg
basins, shower heads, baths etc No. 1
NEW INSTALLATIONS
Cold Water Supply
2.0 15mm diameter pipes. m 30
2.1 22mm diameter pipes. m 50
2.2 28mm diameter insulated pipes. m 0
2.3 35mm diameter insulated pipes. m 0
2.4 42mm diameter pipes. m 0
2.5 54mm diameter pipes. m 0
2.6 67mm diameter pipes. m 0
Extra over copper pipework for fittings, as shown on
the Hot and Cold Water Plumbing Layout drawings:
Bends
2.7 15mm diameter No 25
2.8 22mm diameter No 45
2.9 28mm diameter No 0
2.10 35mm diameter No 0
2.11 42mm diameter No 0
2.12 54mm diameter No 0
2.13 67mm diameter No 0
Carried to Collection
MECHANICAL SERVICES
OCTOBER 2016 36
TRANSORANJE SCHOOL FOR THE DEAF, MECHANICAL BOQ
DEPARTMENT OF INFRASTRUCTURE DEVELOPMENT
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
Tees
2.14 50mm-32mm-50mm diameter No 2
2.15 32mm-22mm-32mm diameter No 2
2.16 22mm-22mm-22mm diameter No 5
2.17 22mm-15mm-22mm diameter No 18
2.18 54mm diameter No 0
2.19 67mm diameter No 0
Reducers
2.20 50mm-32mm diameter No 4
2.21 32mm -22mm diameter No 4
2.22 32mm-15mm diameter No 4
2.23 22mm-15mm diameter No 0
2.24 42mm diameter No 0
2.25 54mm diameter No 0
2.26 67mm diameter No 0
Adapters
2.27 25mm Plastic to Male Iron adapter No 4
2.28 65mm Plastic to Male Iron adapter No 0
SOLAR WATER HEATERS
3.0 Supply, install, test and commission a double
jacketed, direct thermosiphon circulation type 200
litre solar water heater, complete with 3kW
electrical heater back-up element and 2 x 2m flat
plate solar collectors, 10m of copper piping,
insulation, 2-off 20mm vacuum breakers, 15mm
expansion relief valve, lever ball valves, mixing
valve, temperature differential controller, hot water
pipe insulation and truss strengthening where
required. Installation to comply with the
Department's document GP/M 2 Rev 1. Units to be
SABS Mark with SABS certificate.
Carried to Collection
MECHANICAL SERVICES
OCTOBER 2016 37
TRANSORANJE SCHOOL FOR THE DEAF, MECHANICAL BOQ
DEPARTMENT OF INFRASTRUCTURE DEVELOPMENT
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
Cylinder (mounted on roof)
Cylinder Capacity: 200 litres
Cylinder Material: SS 441;
Cylinder Material Thickness: 1.5mm
SABS Pressure Rating: 600kPa
Design Working Pressure: 400kPa
Glazing Material: 3.2mm tampered low iron.
Absorber Material: Steel
Absorber Surface: Black Chrome selective surface
Solar Collector Mounting: North Facing
No. of Solar collectors: 2
Collector Aperture: 1.86m2
Full Weight of System incl. frame: 500kg
Solar Collector Mounting: North Facing
3.1 Supply No. 1
3.2 Install No. 1
3.4 Installation of Solar Controller No. 1
3.5 Installation of timer No. 1
Copper pipe work
3.6 15mm diameter insulated pipes m 30
3.7 22mm diameter insulated pipes m 25
3.8 28mm diameter insulated pipes m 0
Extra over copper pipework for fittings, as shown on
the Hot and Cold Water Plumbing Layout drawings:
Bends
3.9 15mm diameter No 18
3.10 22mm diameter No 30
3.11 28mm diameter No 0
3.12 35mm diameter No 0
Equal Tees
3.13 15mm diameter No 18
3.14 22mm diameter No 25
3.15 38mm diameter No 0
3.16 42mm diameter No 0
Carried to Collection
MECHANICAL SERVICES
OCTOBER 2016 38
TRANSORANJE SCHOOL FOR THE DEAF, MECHANICAL BOQ
DEPARTMENT OF INFRASTRUCTURE DEVELOPMENT
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
Reducers
3.17 28mm-22mm diameter No 4
3.18 22mm-15mm diameter No 4
3.19 35mm diameter No 0
Valves
15mm diameter stopcock/angle valve on cold and
3.20 hot water pipes to sanitary appliances. No 14
3.21 20mm diameter isolation ballvalve on cold water
pipes No 0
3.22 25mm diameter isolation ballvalve on cold water
pipe. No 0
3.23 65mm diameter isolation ballvalve on cold water
pipes. No 0
Carried to Collection
,
MECHANICAL SERVICES
OCTOBER 2016 39
TRANSORANJE SCHOOL FOR THE DEAF, MECHANICAL BOQ
DEPARTMENT OF INFRASTRUCTURE DEVELOPMENT
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
WORKSHOP 200
REMOVALS
1.0 Disconnect and make safe existing hot water
geyser No. 1
1.1 Remove from site existing hot water geyser and
cold water piping No. 1
1.2 Cutting of walls to remove pipes in the wall No. 1
1.3 Safe keeping all the associated with pipes, eg
basins, shower heads, baths etc No. 1
NEW INSTALLATIONS
Cold Water Supply
2.0 15mm diameter pipes. m 20
2.1 22mm diameter pipes. m 40
2.2 28mm diameter insulated pipes. m 0
2.3 35mm diameter insulated pipes. m 0
2.4 42mm diameter pipes. m 0
2.5 54mm diameter pipes. m 0
2.6 67mm diameter pipes. m 0
Extra over copper pipework for fittings, as shown on
the Hot and Cold Water Plumbing Layout drawings:
Bends
2.7 15mm diameter No 15
2.8 22mm diameter No 10
2.9 28mm diameter No 0
2.10 35mm diameter No 0
2.11 42mm diameter No 0
2.12 54mm diameter No 0
2.13 67mm diameter No 0
Carried to Collection
MECHANICAL SERVICES
OCTOBER 2016 40
TRANSORANJE SCHOOL FOR THE DEAF, MECHANICAL BOQ
DEPARTMENT OF INFRASTRUCTURE DEVELOPMENT
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
Tees
2.14 50mm-32mm-50mm diameter No 2
2.15 32mm-22mm-32mm diameter No 2
2.16 22mm-22mm-22mm diameter No 12
2.17 22mm-15mm-22mm diameter No 12
2.18 54mm diameter No 0
2.19 67mm diameter No 0
Reducers
2.20 50mm-32mm diameter No 4
2.21 32mm -22mm diameter No 4
2.22 32mm-15mm diameter No 4
2.23 22mm-15mm diameter No 0
2.24 42mm diameter No 0
2.25 54mm diameter No 0
2.26 67mm diameter No 0
Adapters
2.27 25mm Plastic to Male Iron adapter No 4
2.28 65mm Plastic to Male Iron adapter No 0
SOLAR WATER HEATERS
3.0 Supply, install, test and commission a double
jacketed, direct thermosiphon circulation type 200
litre solar water heater, complete with 3kW
electrical heater back-up element and 2 x 2m flat
plate solar collectors, 10m of copper piping,
insulation, 2-off 20mm vacuum breakers, 15mm
expansion relief valve, lever ball valves, mixing
valve, temperature differential controller, hot water
pipe insulation and truss strengthening where
required. Installation to comply with the
Department's document GP/M 2 Rev 1. Units to be
SABS Mark with SABS certificate.
Carried to Collection
MECHANICAL SERVICES
OCTOBER 2016 41
TRANSORANJE SCHOOL FOR THE DEAF, MECHANICAL BOQ
DEPARTMENT OF INFRASTRUCTURE DEVELOPMENT
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
Cylinder (mounted on roof)
Cylinder Capacity: 200 litres
Cylinder Material: SS 441;
Cylinder Material Thickness: 1.5mm
SABS Pressure Rating: 600kPa
Design Working Pressure: 400kPa
Glazing Material: 3.2mm tampered low iron.
Absorber Material: Steel
Absorber Surface: Black Chrome selective surface
Solar Collector Mounting: North Facing
No. of Solar collectors: 2
Collector Aperture: 1.86m2
Full Weight of System incl. frame: 500kg
Solar Collector Mounting: North Facing
3.1 Supply No. 1
3.2 Install No. 1
3.4 Installation of Solar Controller No. 1
3.5 Installation of timer No. 1
Copper pipe work
3.6 15mm diameter insulated pipes m 20
3.7 22mm diameter insulated pipes m 40
3.8 28mm diameter insulated pipes m 0
Extra over copper pipework for fittingsas shown on
Hot and Cold Water Plumbing Layout drawings:
Bends
3.9 15mm diameter No 20
3.10 22mm diameter No 22
3.11 28mm diameter No 0
3.12 35mm diameter No 0
Equal Tees
3.13 15mm diameter No 4
3.14 22mm diameter No 8
3.15 38mm diameter No 0
3.16 42mm diameter No 0
Carried to Collection
MECHANICAL SERVICES
OCTOBER 2016 42
TRANSORANJE SCHOOL FOR THE DEAF, MECHANICAL BOQ
DEPARTMENT OF INFRASTRUCTURE DEVELOPMENT
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
Reducers
3.17 28mm-22mm diameter No 4
3.18 22mm-15mm diameter No 4
3.19 35mm diameter No 0
Valves
15mm diameter stopcock/angle valve on cold and
3.20 hot water pipes to sanitary appliances. No 15
3.21 20mm diameter isolation ballvalve on cold water
pipes No 0
3.22 25mm diameter isolation ballvalve on cold water
pipe. No 0
3.23 65mm diameter isolation ballvalve on cold water
pipes. No 0
Carried to Collection
,
MECHANICAL SERVICES
OCTOBER 2016 43
TRANSORANJE SCHOOL FOR THE DEAF, MECHANICAL BOQ
DEPARTMENT OF INFRASTRUCTURE DEVELOPMENT
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
WORKSHOP 300
REMOVALS
1.0 Disconnect and make safe existing hot water
geyser No. 1
1.1 Remove from site existing hot water geyser and
cold water piping No. 1
1.2 Cutting of walls to remove pipes in the wall No. 1
1.3 Safe keeping all the associated with pipes, eg
basins, shower heads, baths etc No. 1
NEW INSTALLATIONS
Cold Water Supply
2.0 15mm diameter pipes. m 20
2.1 22mm diameter pipes. m 40
2.2 28mm diameter insulated pipes. m 0
2.3 35mm diameter insulated pipes. m 0
2.4 42mm diameter pipes. m 0
2.5 54mm diameter pipes. m 0
2.6 67mm diameter pipes. m 0
Extra over copper pipework for fittings, as shown on
Hot and Cold Water Plumbing Layout drawings:
Bends
2.7 15mm diameter No 24
2.8 22mm diameter No 10
2.9 28mm diameter No 0
2.10 35mm diameter No 0
2.11 42mm diameter No 0
2.12 54mm diameter No 0
2.13 67mm diameter No 0
Carried to Collection
MECHANICAL SERVICES
OCTOBER 2016 44
TRANSORANJE SCHOOL FOR THE DEAF, MECHANICAL BOQ
DEPARTMENT OF INFRASTRUCTURE DEVELOPMENT
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
Tees
2.14 50mm-32mm-50mm diameter No 2
2.15 32mm-22mm-32mm diameter No 2
2.16 22mm-22mm-22mm diameter No 5
2.17 22mm-15mm-22mm diameter No 12
2.18 54mm diameter No 0
2.19 67mm diameter No 0
Reducers
2.20 50mm-32mm diameter No 4
2.21 32mm -22mm diameter No 4
2.22 32mm-15mm diameter No 4
2.23 22mm-15mm diameter No 0
2.24 42mm diameter No 0
2.25 54mm diameter No 0
2.26 67mm diameter No 0
Adapters
2.27 25mm Plastic to Male Iron adapter No 4
2.28 65mm Plastic to Male Iron adapter No 0
SOLAR WATER HEATERS
3.0 Supply, install, test and commission a double
jacketed, direct thermosiphon circulation type 200
litre solar water heater, complete with 3kW
electrical heater back-up element and 2 x 2m flat
plate solar collectors, 10m of copper piping,
insulation, 2-off 20mm vacuum breakers, 15mm
expansion relief valve, lever ball valves, mixing
valve, temperature differential controller, hot water
pipe insulation and truss strengthening where
required. Installation to comply with the
Department's document GP/M 2 Rev 1. Units to be
SABS Mark with SABS certificate.
Carried to Collection
MECHANICAL SERVICES
OCTOBER 2016 45
TRANSORANJE SCHOOL FOR THE DEAF, MECHANICAL BOQ
DEPARTMENT OF INFRASTRUCTURE DEVELOPMENT
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
Cylinder (mounted on roof)
Cylinder Capacity: 200 litres
Cylinder Material: SS 441;
Cylinder Material Thickness: 1.5mm
SABS Pressure Rating: 600kPa
Design Working Pressure: 400kPa
Glazing Material: 3.2mm tampered low iron.
Absorber Material: Steel
Absorber Surface: Black Chrome selective surface
Solar Collector Mounting: North Facing
No. of Solar collectors: 2
Collector Aperture: 1.86m2
Full Weight of System incl. frame: 500kg
Solar Collector Mounting: North Facing
3.1 Supply No. 1
3.2 Install No. 1
3.4 Installation of Solar Controller No. 1
3.5 Installation of timer No. 1
Copper pipe work
3.6 15mm diameter insulated pipes m 30
3.7 22mm diameter insulated pipes m 25
3.8 28mm diameter insulated pipes m 0
Extra over copper pipework for fittings, as shown on
Hot and Cold Water Plumbing Layout drawings:
Bends
3.9 15mm diameter No 12
3.10 22mm diameter No 10
3.11 28mm diameter No 0
3.12 35mm diameter No 0
Equal Tees
3.13 15mm diameter No 12
3.14 22mm diameter No 10
3.15 38mm diameter No 0
3.16 42mm diameter No 0
Carried to Collection
MECHANICAL SERVICES
OCTOBER 2016 46
TRANSORANJE SCHOOL FOR THE DEAF, MECHANICAL BOQ
DEPARTMENT OF INFRASTRUCTURE DEVELOPMENT
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
Reducers
3.17 28mm-22mm diameter No 4
3.18 22mm-15mm diameter No 4
3.19 35mm diameter No 0
Valves
15mm diameter stopcock/angle valve on cold and
3.20 hot water pipes to sanitary appliances. No 14
3.21 20mm diameter isolation ballvalve on cold water
pipes No 0
3.22 25mm diameter isolation ballvalve on cold water
pipe. No 0
3.23 65mm diameter isolation ballvalve on cold water
pipes. No 0
Carried to Collection
,
MECHANICAL SERVICES
OCTOBER 2016 47
TRANSORANJE SCHOOL FOR THE DEAF, MECHANICAL BOQ
DEPARTMENT OF INFRASTRUCTURE DEVELOPMENT
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
PRE SCHOOL CLASSES
REMOVALS
1.0 Disconnect and make safe existing hot water
geyser No. 1
1.1 Remove from site existing hot water geyser and
cold water piping No. 1
1.2 Cutting of walls to remove pipes in the wall No. 1
1.3 Safe keeping all the associated with pipes, eg
basins, shower heads, baths etc No. 1
NEW INSTALLATIONS
Cold Water Supply
2.0 15mm diameter pipes. m 30
2.1 22mm diameter pipes. m 55
2.2 28mm diameter insulated pipes. m 0
2.3 35mm diameter insulated pipes. m 0
2.4 42mm diameter pipes. m 0
2.5 54mm diameter pipes. m 0
2.6 67mm diameter pipes. m 0
Extra over copper pipework for fittings, as shown on
Hot and Cold Water Plumbing Layout drawings:
Bends
2.7 15mm diameter No 25
2.8 22mm diameter No 35
2.9 28mm diameter No 0
2.10 35mm diameter No 0
2.11 42mm diameter No 0
2.12 54mm diameter No 0
2.13 67mm diameter No 0
Carried to Collection
MECHANICAL SERVICES
OCTOBER 2016 48
TRANSORANJE SCHOOL FOR THE DEAF, MECHANICAL BOQ
DEPARTMENT OF INFRASTRUCTURE DEVELOPMENT
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
Tees
2.14 50mm-32mm-50mm diameter No 2
2.15 32mm-22mm-32mm diameter No 2
2.16 22mm-22mm-22mm diameter No 10
2.17 22mm-15mm-22mm diameter No 12
2.18 54mm diameter No 0
2.19 67mm diameter No 0
Reducers
2.20 50mm-32mm diameter No 4
2.21 32mm -22mm diameter No 4
2.22 32mm-15mm diameter No 4
2.23 22mm-15mm diameter No 0
2.24 42mm diameter No 0
2.25 54mm diameter No 0
2.26 67mm diameter No 0
Adapters
2.27 25mm Plastic to Male Iron adapter No 4
2.28 65mm Plastic to Male Iron adapter No 0
SOLAR WATER HEATERS
3.0 Supply, install, test and commission a double
jacketed, direct thermosiphon circulation type 200
litre solar water heater, complete with 3kW
electrical heater back-up element and 2 x 2m flat
plate solar collectors, 10m of copper piping,
insulation, 2-off 20mm vacuum breakers, 15mm
expansion relief valve, lever ball valves, mixing
valve, temperature differential controller, hot water
pipe insulation and truss strengthening where
required. Installation to comply with the
Department's document GP/M 2 Rev 1. Units to be
SABS Mark with SABS certificate.
Carried to Collection
MECHANICAL SERVICES
OCTOBER 2016 49
TRANSORANJE SCHOOL FOR THE DEAF, MECHANICAL BOQ
DEPARTMENT OF INFRASTRUCTURE DEVELOPMENT
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
Cylinder (mounted on roof)
Cylinder Capacity: 200 litres
Cylinder Material: SS 441;
Cylinder Material Thickness: 1.5mm
SABS Pressure Rating: 600kPa
Design Working Pressure: 400kPa
Glazing Material: 3.2mm tampered low iron.
Absorber Material: Steel
Absorber Surface: Black Chrome selective surface
Solar Collector Mounting: North Facing
No. of Solar collectors: 2
Collector Aperture: 1.86m2
Full Weight of System incl. frame: 500kg
Solar Collector Mounting: North Facing
3.1 Supply No. 1
3.2 Install No. 1
3.4 Installation of Solar Controller No. 1
3.5 Installation of timer No. 1
Copper pipe work
3.6 15mm diameter insulated pipes m 30
3.7 22mm diameter insulated pipes m 25
3.8 28mm diameter insulated pipes m 36
Extra over copper pipework for fittings, as shown on
Hot and Cold Water Plumbing Layout drawings:
Bends
3.9 15mm diameter No 10
3.10 22mm diameter No 12
3.11 28mm diameter No 0
3.12 35mm diameter No 0
Equal Tees
3.13 15mm diameter No 10
3.14 22mm diameter No 12
3.15 38mm diameter No 0
3.16 42mm diameter No 0
Carried to Collection
MECHANICAL SERVICES
OCTOBER 2016 50
TRANSORANJE SCHOOL FOR THE DEAF, MECHANICAL BOQ
DEPARTMENT OF INFRASTRUCTURE DEVELOPMENT
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
Reducers
3.17 28mm-22mm diameter No 4
3.18 22mm-15mm diameter No 4
3.19 35mm diameter No 0
Valves
15mm diameter stopcock/angle valve on cold and
3.20 hot water pipes to sanitary appliances. No 12
3.21 20mm diameter isolation ballvalve on cold water
pipes No 0
3.22 25mm diameter isolation ballvalve on cold water
pipe. No 0
3.23 65mm diameter isolation ballvalve on cold water
pipes. No 0
Carried to Collection
,
SUB-TOTAL FOR BILL WET SERVICES
CARRIED TO SUMMARY PAGE
MECHANICAL SERVICES
OCTOBER 2016 51
TRANSORANJE SCHOOL FOR THE DEAF, MECHANICAL BOQ
DEPARTMENT OF INFRASTRUCTURE DEVELOPMENT
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
GIRLS HOSTEL E&G
REMOVALS
1.0 Disconnect and make safe existing hot water
geyser No. 1
1.1 Remove from site existing hot water geyser and
cold water piping No. 1
1.2 Cutting of walls to remove pipes in the wall No. 1
1.3 Safe keeping all the associated with pipes, eg
basins, shower heads, baths etc No. 1
NEW INSTALLATIONS
Cold Water Supply
2.0 15mm diameter pipes. m 30
2.1 22mm diameter pipes. m 66
2.2 28mm diameter insulated pipes. m 0
2.3 35mm diameter insulated pipes. m 0
2.4 42mm diameter pipes. m 0
2.5 54mm diameter pipes. m 0
2.6 67mm diameter pipes. m 0
Extra over copper pipework for fittings, as shown on
the Hot and Cold Water Plumbing Layout drawings:
Bends
2.7 15mm diameter No 15
2.8 22mm diameter No 20
2.9 28mm diameter No 0
2.10 35mm diameter No 0
2.11 42mm diameter No 0
2.12 54mm diameter No 0
2.13 67mm diameter No 0
Carried to Collection
MECHANICAL SERVICES
OCTOBER 2016 52
TRANSORANJE SCHOOL FOR THE DEAF, MECHANICAL BOQ
DEPARTMENT OF INFRASTRUCTURE DEVELOPMENT
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
Tees
2.14 50mm-32mm-50mm diameter No 2
2.15 32mm-22mm-32mm diameter No 2
2.16 22mm-22mm-22mm diameter No 5
2.17 22mm-15mm-22mm diameter No 12
2.18 54mm diameter No 0
2.19 67mm diameter No 0
Reducers
2.20 50mm-32mm diameter No 4
2.21 32mm -22mm diameter No 4
2.22 32mm-15mm diameter No 4
2.23 22mm-15mm diameter No 0
2.24 42mm diameter No 0
2.25 54mm diameter No 0
2.26 67mm diameter No 0
Adapters
2.27 25mm Plastic to Male Iron adapter No 0
2.28 65mm Plastic to Male Iron adapter No 0
SOLAR WATER HEATERS
3.0 Supply, install, test and commission a double
jacketed, direct thermosiphon circulation type 200
litre solar water heater, complete with 3kW
electrical heater back-up element and 2 x 2m flat
plate solar collectors, 10m of copper piping,
insulation, 2-off 20mm vacuum breakers, 15mm
expansion relief valve, lever ball valves, mixing
valve, temperature differential controller, hot water
pipe insulation and truss strengthening where
required. Installation to comply with the
Department's document GP/M 2 Rev 1. Units to be
SABS Mark with SABS certificate.
Carried to Collection
MECHANICAL SERVICES
OCTOBER 2016 53
TRANSORANJE SCHOOL FOR THE DEAF, MECHANICAL BOQ
DEPARTMENT OF INFRASTRUCTURE DEVELOPMENT
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
Cylinder (mounted on roof)
Cylinder Capacity: 200 litres
Cylinder Material: SS 441;
Cylinder Material Thickness: 1.5mm
SABS Pressure Rating: 600kPa
Design Working Pressure: 400kPa
Glazing Material: 3.2mm tampered low iron.
Absorber Material: Steel
Absorber Surface: Black Chrome selective surface
Solar Collector Mounting: North Facing
No. of Solar collectors: 2
Collector Aperture: 1.86m2
Full Weight of System incl. frame: 500kg
Solar Collector Mounting: North Facing
3.1 Supply No. 6
3.2 Install No. 6
3.4 Installation of Solar Controller No. 1
3.5 Installation of timer No. 1
Copper pipe work
3.6 15mm diameter insulated pipes m 30
3.7 22mm diameter insulated pipes m 70
3.8 28mm diameter insulated pipes m 0
Extra over copper pipework for fittings, as shown on
Hot and Cold Water Plumbing Layout drawings:
Bends
3.9 15mm diameter No 20
3.10 22mm diameter No 10
3.11 28mm diameter No 0
3.12 35mm diameter No 0
Equal Tees
3.13 15mm diameter No 15
3.14 22mm diameter No 25
3.15 38mm diameter No 0
3.16 42mm diameter No 0
Carried to Collection
MECHANICAL SERVICES
OCTOBER 2016 54
TRANSORANJE SCHOOL FOR THE DEAF, MECHANICAL BOQ
DEPARTMENT OF INFRASTRUCTURE DEVELOPMENT
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
Reducers
3.17 28mm-22mm diameter No 4
3.18 22mm-15mm diameter No 4
3.19 35mm diameter No 0
Valves
15mm diameter stopcock/angle valve on cold and
3.20 hot water pipes to sanitary appliances. No 15
3.21 20mm diameter isolation ballvalve on cold water
pipes No 0
3.22 25mm diameter isolation ballvalve on cold water
pipe. No 0
3.23 65mm diameter isolation ballvalve on cold water
pipes. No 0
Carried to Collection
MECHANICAL SERVICES
OCTOBER 2016 55
TRANSORANJE SCHOOL FOR THE DEAF, MECHANICAL BOQ
DEPARTMENT OF INFRASTRUCTURE DEVELOPMENT
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
GIRLS HOSTEL F
REMOVALS
1.0 Disconnect and make safe existing hot water
geyser No. 1
1.1 Remove from site existing hot water geyser and
cold water piping No. 1
1.2 Cutting of walls to remove pipes in the wall No. 1
1.3 Safe keeping all the associated with pipes, eg
basins, shower heads, baths etc No. 1
NEW INSTALLATIONS
Cold Water Supply
2.0 15mm diameter pipes. m 30
2.1 22mm diameter pipes. m 75
2.2 28mm diameter insulated pipes. m 0
2.3 35mm diameter insulated pipes. m 0
2.4 42mm diameter pipes. m 0
2.5 54mm diameter pipes. m 0
2.6 67mm diameter pipes. m 0
Extra over copper pipework for fittings, as shown on
Hot and Cold Water Plumbing Layout drawings:
Bends
2.7 15mm diameter No 15
2.8 22mm diameter No 10
2.9 28mm diameter No 0
2.10 35mm diameter No 0
2.11 42mm diameter No 0
2.12 54mm diameter No 0
2.13 67mm diameter No 0
Carried to Collection
MECHANICAL SERVICES
OCTOBER 2016 56
TRANSORANJE SCHOOL FOR THE DEAF, MECHANICAL BOQ
DEPARTMENT OF INFRASTRUCTURE DEVELOPMENT
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
Tees
2.14 50mm-32mm-50mm diameter No 2
2.15 32mm-22mm-32mm diameter No 2
2.16 22mm-22mm-22mm diameter No 12
2.17 22mm-15mm-22mm diameter No 12
2.18 54mm diameter No 0
2.19 67mm diameter No 0
Reducers
2.20 50mm-32mm diameter No 4
2.21 32mm -22mm diameter No 4
2.22 32mm-15mm diameter No 4
2.23 22mm-15mm diameter No 0
2.24 42mm diameter No 0
2.25 54mm diameter No 0
2.26 67mm diameter No 0
Adapters
2.27 25mm Plastic to Male Iron adapter No 0
2.28 65mm Plastic to Male Iron adapter No 0
SOLAR WATER HEATERS
3.0 Supply, install, test and commission a double
jacketed, direct thermosiphon circulation type 200
litre solar water heater, complete with 3kW
electrical heater back-up element and 2 x 2m flat
plate solar collectors, 10m of copper piping,
insulation, 2-off 20mm vacuum breakers, 15mm
expansion relief valve, lever ball valves, mixing
valve, temperature differential controller, hot water
pipe insulation and truss strengthening where
required. Installation to comply with the
Department's document GP/M 2 Rev 1. Units to be
SABS Mark with SABS certificate.
Carried to Collection
MECHANICAL SERVICES
OCTOBER 2016 57
TRANSORANJE SCHOOL FOR THE DEAF, MECHANICAL BOQ
DEPARTMENT OF INFRASTRUCTURE DEVELOPMENT
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
Cylinder (mounted on roof)
Cylinder Capacity: 200 litres
Cylinder Material: SS 441;
Cylinder Material Thickness: 1.5mm
SABS Pressure Rating: 600kPa
Design Working Pressure: 400kPa
Glazing Material: 3.2mm tampered low iron.
Absorber Material: Steel
Absorber Surface: Black Chrome selective surface
Solar Collector Mounting: North Facing
No. of Solar collectors: 2
Collector Aperture: 1.86m2
Full Weight of System incl. frame: 500kg
Solar Collector Mounting: North Facing
3.1 Supply No. 6
3.2 Install No. 6
3.4 Installation of Solar Controller No. 1
3.5 Installation of timer No. 1
Copper pipe work
3.6 15mm diameter insulated pipes m 40
3.7 22mm diameter insulated pipes m 80
3.8 28mm diameter insulated pipes m 36
Extra over copper pipework for fittings, as shown on
Hot and Cold Water Plumbing Layout drawings:
Bends
3.9 15mm diameter No 30
3.10 22mm diameter No 25
3.11 28mm diameter No 0
3.12 35mm diameter No 0
Equal Tees
3.13 15mm diameter No 10
3.14 22mm diameter No 8
3.15 38mm diameter No 0
3.16 42mm diameter No 0
Carried to Collection
MECHANICAL SERVICES
OCTOBER 2016 58
TRANSORANJE SCHOOL FOR THE DEAF, MECHANICAL BOQ
DEPARTMENT OF INFRASTRUCTURE DEVELOPMENT
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
Reducers
3.17 28mm-22mm diameter No 4
3.18 22mm-15mm diameter No 4
3.19 35mm diameter No 0
Valves
15mm diameter stopcock/angle valve on cold and
3.20 hot water pipes to sanitary appliances. No 25
3.21 20mm diameter isolation ballvalve on cold water
pipes No 0
3.22 25mm diameter isolation ballvalve on cold water
pipe. No 0
3.23 65mm diameter isolation ballvalve on cold water
pipes. No 0
Carried to Collection
MECHANICAL SERVICES
OCTOBER 2016 59
TRANSORANJE SCHOOL FOR THE DEAF, MECHANICAL BOQ
DEPARTMENT OF INFRASTRUCTURE DEVELOPMENT
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
KITCHEN
REMOVALS
1.0 Disconnect and make safe existing hot water
geyser No. 1
1.1 Remove from site existing hot water geyser and
cold water piping No. 1
1.2 Cutting of walls to remove pipes in the wall No. 1
1.3 Safe keeping all the associated with pipes, eg
basins, shower heads, baths etc No. 1
NEW INSTALLATIONS
Cold Water Supply
2.0 15mm diameter pipes. m 40
2.1 22mm diameter pipes. m 80
2.2 28mm diameter insulated pipes. m 0
2.3 35mm diameter insulated pipes. m 0
2.4 42mm diameter pipes. m 0
2.5 54mm diameter pipes. m 0
2.6 67mm diameter pipes. m 0
Extra over copper pipework for fittings, as shown on
Hot and Cold Water Plumbing Layout drawings:
Bends
2.7 15mm diameter No 30
2.8 22mm diameter No 45
2.9 28mm diameter No 0
2.10 35mm diameter No 0
2.11 42mm diameter No 0
2.12 54mm diameter No 0
2.13 67mm diameter No 0
Carried to Collection
MECHANICAL SERVICES
OCTOBER 2016 60
TRANSORANJE SCHOOL FOR THE DEAF, MECHANICAL BOQ
DEPARTMENT OF INFRASTRUCTURE DEVELOPMENT
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
Tees
2.14 50mm-32mm-50mm diameter No 2
2.15 32mm-22mm-32mm diameter No 2
2.16 22mm-22mm-22mm diameter No 5
2.17 22mm-15mm-22mm diameter No 12
2.18 54mm diameter No 0
2.19 67mm diameter No 0
Reducers
2.20 50mm-32mm diameter No 4
2.21 32mm -22mm diameter No 4
2.22 32mm-15mm diameter No 4
2.23 22mm-15mm diameter No 0
2.24 42mm diameter No 0
2.25 54mm diameter No 0
2.26 67mm diameter No 0
Adapters
2.27 25mm Plastic to Male Iron adapter No 4
2.28 65mm Plastic to Male Iron adapter No 0
SOLAR WATER HEATERS
3.0 Supply, install, test and commission a double
jacketed, direct thermosiphon circulation type 200
litre solar water heater, complete with 3kW
electrical heater back-up element and 2 x 2m flat
plate solar collectors, 10m of copper piping,
insulation, 2-off 20mm vacuum breakers, 15mm
expansion relief valve, lever ball valves, mixing
valve, temperature differential controller, hot water
pipe insulation and truss strengthening where
required. Installation to comply with the
Department's document GP/M 2 Rev 1. Units to be
SABS Mark with SABS certificate.
Carried to Collection
MECHANICAL SERVICES
OCTOBER 2016 61
TRANSORANJE SCHOOL FOR THE DEAF, MECHANICAL BOQ
DEPARTMENT OF INFRASTRUCTURE DEVELOPMENT
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
Cylinder (mounted on roof)
Cylinder Capacity: 200 litres
Cylinder Material: SS 441;
Cylinder Material Thickness: 1.5mm
SABS Pressure Rating: 600kPa
Design Working Pressure: 400kPa
Glazing Material: 3.2mm tampered low iron.
Absorber Material: Steel
Absorber Surface: Black Chrome selective surface
Solar Collector Mounting: North Facing
No. of Solar collectors: 2
Collector Aperture: 1.86m2
Full Weight of System incl. frame: 500kg
Solar Collector Mounting: North Facing
3.1 Supply No. 3
3.2 Install No. 3
3.4 Installation of Solar Controller No. 1
3.5 Installation of timer No. 1
Copper pipe work
3.6 15mm diameter insulated pipes m 20
3.7 22mm diameter insulated pipes m 40
3.8 28mm diameter insulated pipes m 0
Extra over copper pipework for fittings, as shown on
Hot and Cold Water Plumbing Layout drawings:
Bends
3.9 15mm diameter No 20
3.10 22mm diameter No 10
3.11 28mm diameter No 0
3.12 35mm diameter No 0
Equal Tees
3.13 15mm diameter No 10
3.14 22mm diameter No 8
3.15 38mm diameter No 0
3.16 42mm diameter No 0
Carried to Collection
MECHANICAL SERVICES
OCTOBER 2016 62
TRANSORANJE SCHOOL FOR THE DEAF, MECHANICAL BOQ
DEPARTMENT OF INFRASTRUCTURE DEVELOPMENT
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
Reducers
3.17 28mm-22mm diameter No 4
3.18 22mm-15mm diameter No 4
3.19 35mm diameter No 0
Valves
15mm diameter stopcock/angle valve on cold and
3.20 hot water pipes to sanitary appliances. No 25
3.21 20mm diameter isolation ballvalve on cold water
pipes No 0
3.22 25mm diameter isolation ballvalve on cold water
pipe. No 0
3.23 65mm diameter isolation ballvalve on cold water
pipes. No 0
Carried to Collection
MECHANICAL SERVICES
OCTOBER 2016 63
TRANSORANJE SCHOOL FOR THE DEAF, MECHANICAL BOQ
DEPARTMENT OF INFRASTRUCTURE DEVELOPMENT
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
ADMIN
REMOVALS
1.0 Disconnect and make safe existing hot water
geyser No. 1
1.1 Remove from site existing hot water geyser and
cold water piping No. 1
1.2 Cutting of walls to remove pipes in the wall No. 1
1.3 Safe keeping all the associated with pipes, eg
basins, shower heads, baths etc No. 1
NEW INSTALLATIONS
Cold Water Supply
2.0 15mm diameter pipes. m 20
2.1 22mm diameter pipes. m 50
2.2 28mm diameter insulated pipes. m 0
2.3 35mm diameter insulated pipes. m 0
2.4 42mm diameter pipes. m 0
2.5 54mm diameter pipes. m 0
2.6 67mm diameter pipes. m 0
Extra over copper pipework for fittings, as shown on
Hot and Cold Water Plumbing Layout drawings:
Bends
2.7 15mm diameter No 14
2.8 22mm diameter No 10
2.9 28mm diameter No 0
2.10 35mm diameter No 0
2.11 42mm diameter No 0
2.12 54mm diameter No 0
2.13 67mm diameter No 0
Carried to Collection
MECHANICAL SERVICES
OCTOBER 2016 64
TRANSORANJE SCHOOL FOR THE DEAF, MECHANICAL BOQ
DEPARTMENT OF INFRASTRUCTURE DEVELOPMENT
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
Tees
2.14 50mm-32mm-50mm diameter No 2
2.15 32mm-22mm-32mm diameter No 2
2.16 22mm-22mm-22mm diameter No 5
2.17 22mm-15mm-22mm diameter No 12
2.18 54mm diameter No 0
2.19 67mm diameter No 0
Reducers
2.20 50mm-32mm diameter No 4
2.21 32mm -22mm diameter No 4
2.22 32mm-15mm diameter No 4
2.23 22mm-15mm diameter No 0
2.24 42mm diameter No 0
2.25 54mm diameter No 0
2.26 67mm diameter No 0
Adapters
2.27 25mm Plastic to Male Iron adapter No 0
2.28 65mm Plastic to Male Iron adapter No 0
SOLAR WATER HEATERS
3.0 Supply, install, test and commission a double
jacketed, direct thermosiphon circulation type 200
litre solar water heater, complete with 3kW
electrical heater back-up element and 2 x 2m flat
plate solar collectors, 10m of copper piping,
insulation, 2-off 20mm vacuum breakers, 15mm
expansion relief valve, lever ball valves, mixing
valve, temperature differential controller, hot water
pipe insulation and truss strengthening where
required. Installation to comply with the
Department's document GP/M 2 Rev 1. Units to be
SABS Mark with SABS certificate.
Carried to Collection
MECHANICAL SERVICES
OCTOBER 2016 65
TRANSORANJE SCHOOL FOR THE DEAF, MECHANICAL BOQ
DEPARTMENT OF INFRASTRUCTURE DEVELOPMENT
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
Cylinder (mounted on roof)
Cylinder Capacity: 200 litres
Cylinder Material: SS 441;
Cylinder Material Thickness: 1.5mm
SABS Pressure Rating: 600kPa
Design Working Pressure: 400kPa
Glazing Material: 3.2mm tampered low iron.
Absorber Material: Steel
Absorber Surface: Black Chrome selective surface
Solar Collector Mounting: North Facing
No. of Solar collectors: 2
Collector Aperture: 1.86m2
Full Weight of System incl. frame: 500kg
Solar Collector Mounting: North Facing
3.1 Supply No. 1
3.2 Install No. 1
3.4 Installation of Solar Controller No. 1
3.5 Installation of timer No. 1
Copper pipe work
3.6 15mm diameter insulated pipes m 20
3.7 22mm diameter insulated pipes m 25
3.8 28mm diameter insulated pipes m 0
Extra over copper pipework for fittings, as shown on
Hot and Cold Water Plumbing Layout drawings:
Bends
3.9 15mm diameter No 10
3.10 22mm diameter No 15
3.11 28mm diameter No 0
3.12 35mm diameter No 0
Equal Tees
3.13 15mm diameter No 15
3.14 22mm diameter No 10
3.15 38mm diameter No 0
3.16 42mm diameter No 0
Carried to Collection
MECHANICAL SERVICES
OCTOBER 2016 66
TRANSORANJE SCHOOL FOR THE DEAF, MECHANICAL BOQ
DEPARTMENT OF INFRASTRUCTURE DEVELOPMENT
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
Reducers
3.17 28mm-22mm diameter No 4
3.18 22mm-15mm diameter No 4
3.19 35mm diameter No 0
Valves
15mm diameter stopcock/angle valve on cold and
3.20 hot water pipes to sanitary appliances. No 15
3.21 20mm diameter isolation ballvalve on cold water
pipes No 0
3.22 25mm diameter isolation ballvalve on cold water
pipe. No 0
3.23 65mm diameter isolation ballvalve on cold water
pipes. No 0
Carried to Collection
MECHANICAL SERVICES
OCTOBER 2016 67
TRANSORANJE SCHOOL FOR THE DEAF, MECHANICAL BOQ
DEPARTMENT OF INFRASTRUCTURE DEVELOPMENT
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
MEDIA CENTRE
REMOVALS
1.0 Disconnect and make safe existing hot water
geyser No. 0
1.1 Remove from site existing hot water geyser and
cold water piping No. 1
1.2 Cutting of walls to remove pipes in the wall No. 1
1.3 Safe keeping all the associated with pipes, eg
basins, shower heads, baths etc No. 1
NEW INSTALLATIONS
Cold Water Supply
2.0 15mm diameter pipes. m 30
2.1 22mm diameter pipes. m 50
2.2 28mm diameter insulated pipes. m 0
2.3 35mm diameter insulated pipes. m 0
2.4 42mm diameter pipes. m 0
2.5 54mm diameter pipes. m 0
2.6 67mm diameter pipes. m 0
Extra over copper pipework for fittings, as shown on
Hot and Cold Water Plumbing Layout drawings:
Bends
2.7 15mm diameter No 20
2.8 22mm diameter No 40
2.9 28mm diameter No 0
2.10 35mm diameter No 0
2.11 42mm diameter No 0
2.12 54mm diameter No 0
2.13 67mm diameter No 0
Carried to Collection
MECHANICAL SERVICES
OCTOBER 2016 68
TRANSORANJE SCHOOL FOR THE DEAF, MECHANICAL BOQ
DEPARTMENT OF INFRASTRUCTURE DEVELOPMENT
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
Tees
2.14 50mm-32mm-50mm diameter No 2
2.15 32mm-22mm-32mm diameter No 2
2.16 22mm-22mm-22mm diameter No 10
2.17 22mm-15mm-22mm diameter No 12
2.18 54mm diameter No 0
2.19 67mm diameter No 0
Reducers
2.20 50mm-32mm diameter No 4
2.21 32mm -22mm diameter No 4
2.22 32mm-15mm diameter No 4
2.23 22mm-15mm diameter No 0
2.24 42mm diameter No 0
2.25 54mm diameter No 0
2.26 67mm diameter No 0
Adapters
2.27 25mm Plastic to Male Iron adapter No 4
2.28 65mm Plastic to Male Iron adapter No 0
Carried to Collection
MECHANICAL SERVICES
OCTOBER 2016 69
TRANSORANJE SCHOOL FOR THE DEAF, MECHANICAL BOQ
DEPARTMENT OF INFRASTRUCTURE DEVELOPMENT
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
CLASSROOM 200
REMOVALS
1.0 Disconnect and make safe existing hot water
geyser No. 0
1.1 Remove from site existing hot water geyser and
cold water piping No. 1
1.2 Cutting of walls to remove pipes in the wall No. 1
1.3 Safe keeping all the associated with pipes, eg
basins, shower heads, baths etc No. 1
NEW INSTALLATIONS
Cold Water Supply
2.0 15mm diameter pipes. m 30
2.1 22mm diameter pipes. m 100
2.2 28mm diameter insulated pipes. m 0
2.3 35mm diameter insulated pipes. m 0
2.4 42mm diameter pipes. m 0
2.5 54mm diameter pipes. m 0
2.6 67mm diameter pipes. m 0
Extra over copper pipework for fittings, as shown on
Hot and Cold Water Plumbing Layout drawings:
Bends
2.7 15mm diameter No 25
2.8 22mm diameter No 20
2.9 28mm diameter No 0
2.10 35mm diameter No 0
2.11 42mm diameter No 0
2.12 54mm diameter No 0
2.13 67mm diameter No 0
Carried to Collection
MECHANICAL SERVICES
OCTOBER 2016 70
TRANSORANJE SCHOOL FOR THE DEAF, MECHANICAL BOQ
DEPARTMENT OF INFRASTRUCTURE DEVELOPMENT
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
Tees
2.14 50mm-32mm-50mm diameter No 2
2.15 32mm-22mm-32mm diameter No 2
2.16 22mm-22mm-22mm diameter No 5
2.17 22mm-15mm-22mm diameter No 12
2.18 54mm diameter No 0
2.19 67mm diameter No 0
Reducers
2.20 50mm-32mm diameter No 4
2.21 32mm -22mm diameter No 4
2.22 32mm-15mm diameter No 4
2.23 22mm-15mm diameter No 0
2.24 42mm diameter No 0
2.25 54mm diameter No 0
2.26 67mm diameter No 0
Adapters
2.27 25mm Plastic to Male Iron adapter No 0
2.28 65mm Plastic to Male Iron adapter No 0
Carried to Collection
MECHANICAL SERVICES
OCTOBER 2016 71
TRANSORANJE SCHOOL FOR THE DEAF, MECHANICAL BOQ
DEPARTMENT OF INFRASTRUCTURE DEVELOPMENT
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
CLASSROOM 400
REMOVALS
1.0 Disconnect and make safe existing hot water
geyser No. 0
1.1 Remove from site existing hot water geyser and
cold water piping No. 1
1.2 Cutting of walls to remove pipes in the wall No. 1
1.3 Safe keeping all the associated with pipes, eg
basins, shower heads, baths etc No. 1
NEW INSTALLATIONS
Cold Water Supply
2.0 15mm diameter pipes. m 35
2.1 22mm diameter pipes. m 105
2.2 28mm diameter insulated pipes. m 0
2.3 35mm diameter insulated pipes. m 0
2.4 42mm diameter pipes. m 0
2.5 54mm diameter pipes. m 0
2.6 67mm diameter pipes. m 0
Extra over copper pipework for fittings, as shown on
Hot and Cold Water Plumbing Layout drawings:
Bends
2.7 15mm diameter No 20
2.8 22mm diameter No 10
2.9 28mm diameter No 0
2.10 35mm diameter No 0
2.11 42mm diameter No 0
2.12 54mm diameter No 0
2.13 67mm diameter No 0
Carried to Collection
MECHANICAL SERVICES
OCTOBER 2016 72
TRANSORANJE SCHOOL FOR THE DEAF, MECHANICAL BOQ
DEPARTMENT OF INFRASTRUCTURE DEVELOPMENT
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
Tees
2.14 50mm-32mm-50mm diameter No 2
2.15 32mm-22mm-32mm diameter No 2
2.16 22mm-22mm-22mm diameter No 8
2.17 22mm-15mm-22mm diameter No 12
2.18 54mm diameter No 0
2.19 67mm diameter No 0
Reducers
2.20 50mm-32mm diameter No 4
2.21 32mm -22mm diameter No 4
2.22 32mm-15mm diameter No 4
2.23 22mm-15mm diameter No 0
2.24 42mm diameter No 0
2.25 54mm diameter No 0
2.26 67mm diameter No 0
Adapters
2.27 25mm Plastic to Male Iron adapter No 0
2.28 65mm Plastic to Male Iron adapter No 0
Carried to Collection
MECHANICAL SERVICES
OCTOBER 2016 73
TRANSORANJE SCHOOL FOR THE DEAF, MECHANICAL BOQ
DEPARTMENT OF INFRASTRUCTURE DEVELOPMENT
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
OFFICES
REMOVALS
1.0 Disconnect and make safe existing hot water
geyser No. 1
1.1 Remove from site existing hot water geyser and
cold water piping No. 1
1.2 Cutting of walls to remove pipes in the wall No. 1
1.3 Safe keeping all the associated with pipes, eg
basins, shower heads, baths etc No. 1
NEW INSTALLATIONS
Cold Water Supply
2.0 15mm diameter pipes. m 30
2.1 22mm diameter pipes. m 80
2.2 28mm diameter insulated pipes. m 0
2.3 35mm diameter insulated pipes. m 0
2.4 42mm diameter pipes. m 0
2.5 54mm diameter pipes. m 0
2.6 67mm diameter pipes. m 0
Extra over copper pipework for fittings, as shown on
Hot and Cold Water Plumbing Layout drawings:
Bends
2.7 15mm diameter No 25
2.8 22mm diameter No 18
2.9 28mm diameter No 0
2.10 35mm diameter No 0
2.11 42mm diameter No 0
2.12 54mm diameter No 0
2.13 67mm diameter No 0
Carried to Collection
MECHANICAL SERVICES
OCTOBER 2016 74
TRANSORANJE SCHOOL FOR THE DEAF, MECHANICAL BOQ
DEPARTMENT OF INFRASTRUCTURE DEVELOPMENT
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
Tees
2.14 50mm-32mm-50mm diameter No 2
2.15 32mm-22mm-32mm diameter No 2
2.16 22mm-22mm-22mm diameter No 10
2.17 22mm-15mm-22mm diameter No 12
2.18 54mm diameter No 0
2.19 67mm diameter No 0
Reducers
2.20 50mm-32mm diameter No 4
2.21 32mm -22mm diameter No 4
2.22 32mm-15mm diameter No 4
2.23 22mm-15mm diameter No 0
2.24 42mm diameter No 0
2.25 54mm diameter No 0
2.26 67mm diameter No 0
Adapters
2.27 25mm Plastic to Male Iron adapter No 4
2.28 65mm Plastic to Male Iron adapter No 0
SOLAR WATER HEATERS
3.0 Supply, install, test and commission a double
jacketed, direct thermosiphon circulation type 100
litre solar water heater, complete with 3kW
electrical heater back-up element and 2 x 2m flat
plate solar collectors, 10m of copper piping,
insulation, 2-off 20mm vacuum breakers, 15mm
expansion relief valve, lever ball valves, mixing
valve, temperature differential controller, hot water
pipe insulation and truss strengthening where
required. Installation to comply with the
Department's document GP/M 2 Rev 1. Units to be
SABS Mark with SABS certificate.
Carried to Collection
MECHANICAL SERVICES
OCTOBER 2016 75
TRANSORANJE SCHOOL FOR THE DEAF, MECHANICAL BOQ
DEPARTMENT OF INFRASTRUCTURE DEVELOPMENT
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
Cylinder (mounted on roof)
Cylinder Capacity: 100 litres
Cylinder Material: SS 441;
Cylinder Material Thickness: 1.5mm
SABS Pressure Rating: 600kPa
Design Working Pressure: 400kPa
Glazing Material: 3.2mm tampered low iron.
Absorber Material: Steel
Absorber Surface: Black Chrome selective surface
Solar Collector Mounting: North Facing
No. of Solar collectors: 2
Collector Aperture: 1.86m2
Full Weight of System incl. frame: 500kg
Solar Collector Mounting: North Facing
3.1 Supply No. 1
3.2 Install No. 1
3.4 Installation of Solar Controller No. 1
3.5 Installation of timer No. 1
Copper pipe work
3.6 15mm diameter insulated pipes m 30
3.7 22mm diameter insulated pipes m 20
3.8 28mm diameter insulated pipes m 0
Extra over copper pipework for fittings, as shown on
Hot and Cold Water Plumbing Layout drawings:
Bends
3.9 15mm diameter No 15
3.10 22mm diameter No 25
3.11 28mm diameter No 0
3.12 35mm diameter No 0
Equal Tees
3.13 15mm diameter No 15
3.14 22mm diameter No 25
3.15 38mm diameter No 0
3.16 42mm diameter No 0
Carried to Collection
MECHANICAL SERVICES
OCTOBER 2016 76
TRANSORANJE SCHOOL FOR THE DEAF, MECHANICAL BOQ
DEPARTMENT OF INFRASTRUCTURE DEVELOPMENT
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
Reducers
3.17 28mm-22mm diameter No 4
3.18 22mm-15mm diameter No 4
3.19 35mm diameter No 0
Valves
15mm diameter stopcock/angle valve on cold and
3.20 hot water pipes to sanitary appliances. No 20
3.21 20mm diameter isolation ballvalve on cold water
pipes No 0
3.22 25mm diameter isolation ballvalve on cold water
pipe. No 0
3.23 65mm diameter isolation ballvalve on cold water
pipes. No 0
Carried to Collection
MECHANICAL SERVICES
OCTOBER 2016 77
TRANSORANJE SCHOOL FOR THE DEAF, MECHANICAL BOQ
DEPARTMENT OF INFRASTRUCTURE DEVELOPMENT
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
FLATS
REMOVALS
1.0 Disconnect and make safe existing hot water
geyser No. 1
1.1 Remove from site existing hot water geyser and
cold water piping No. 1
1.2 Cutting of walls to remove pipes in the wall No. 1
1.3 Safe keeping all the associated with pipes, eg
basins, shower heads, baths etc No. 1
NEW INSTALLATIONS
Cold Water Supply
2.0 15mm diameter pipes. m 50
2.1 22mm diameter pipes. m 180
2.2 28mm diameter insulated pipes. m 0
2.3 35mm diameter insulated pipes. m 0
2.4 42mm diameter pipes. m 0
2.5 54mm diameter pipes. m 0
2.6 67mm diameter pipes. m 0
Extra over copper pipework for fittings, as shown on
Hot and Cold Water Plumbing Layout drawings:
Bends
2.7 15mm diameter No 20
2.8 22mm diameter No 40
2.9 28mm diameter No 0
2.10 35mm diameter No 0
2.11 42mm diameter No 0
2.12 54mm diameter No 0
2.13 67mm diameter No 0
Carried to Collection
MECHANICAL SERVICES
OCTOBER 2016 78
TRANSORANJE SCHOOL FOR THE DEAF, MECHANICAL BOQ
DEPARTMENT OF INFRASTRUCTURE DEVELOPMENT
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
Tees
2.14 50mm-32mm-50mm diameter No 2
2.15 32mm-22mm-32mm diameter No 2
2.16 22mm-22mm-22mm diameter No 10
2.17 22mm-15mm-22mm diameter No 12
2.18 54mm diameter No 0
2.19 67mm diameter No 0
Reducers
2.20 50mm-32mm diameter No 4
2.21 32mm -22mm diameter No 4
2.22 32mm-15mm diameter No 4
2.23 22mm-15mm diameter No 0
2.24 42mm diameter No 0
2.25 54mm diameter No 0
2.26 67mm diameter No 0
Adapters
2.27 25mm Plastic to Male Iron adapter No 4
2.28 65mm Plastic to Male Iron adapter No 0
SOLAR WATER HEATERS
3.0 Supply, install, test and commission a double
jacketed, direct thermosiphon circulation type 200
litre solar water heater, complete with 3kW
electrical heater back-up element and 2 x 2m flat
plate solar collectors, 10m of copper piping,
insulation, 2-off 20mm vacuum breakers, 15mm
expansion relief valve, lever ball valves, mixing
valve, temperature differential controller, hot water
pipe insulation and truss strengthening where
required. Installation to comply with the
Department's document GP/M 2 Rev 1. Units to be
SABS Mark with SABS certificate.
Carried to Collection
MECHANICAL SERVICES
OCTOBER 2016 79
TRANSORANJE SCHOOL FOR THE DEAF, MECHANICAL BOQ
DEPARTMENT OF INFRASTRUCTURE DEVELOPMENT
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
Cylinder (mounted on roof)
Cylinder Capacity: 200 litres
Cylinder Material: SS 441;
Cylinder Material Thickness: 1.5mm
SABS Pressure Rating: 600kPa
Design Working Pressure: 400kPa
Glazing Material: 3.2mm tampered low iron.
Absorber Material: Steel
Absorber Surface: Black Chrome selective surface
Solar Collector Mounting: North Facing
No. of Solar collectors: 2
Collector Aperture: 1.86m2
Full Weight of System incl. frame: 500kg
Solar Collector Mounting: North Facing
3.1 Supply No. 20
3.2 Install No. 20
3.4 Installation of Solar Controller No. 20
3.5 Installation of timer No. 20
Copper pipe work
3.6 15mm diameter insulated pipes m 80
3.7 22mm diameter insulated pipes m 120
3.8 28mm diameter insulated pipes m 36
Extra over copper pipework for fittings, as shown on
the Hot and Cold Water Plumbing Layout drawings:
Bends
3.9 15mm diameter No 40
3.10 22mm diameter No 10
3.11 28mm diameter No 0
3.12 35mm diameter No 0
Equal Tees
3.13 15mm diameter No 10
3.14 22mm diameter No 14
3.15 38mm diameter No 0
3.16 42mm diameter No 0
Carried to Collection
MECHANICAL SERVICES
OCTOBER 2016 80
TRANSORANJE SCHOOL FOR THE DEAF, MECHANICAL BOQ
DEPARTMENT OF INFRASTRUCTURE DEVELOPMENT
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
Reducers
3.17 28mm-22mm diameter No 4
3.18 22mm-15mm diameter No 4
3.19 35mm diameter No 0
Valves
15mm diameter stopcock/angle valve on cold and
3.20 hot water pipes to sanitary appliances. No 30
3.21 20mm diameter isolation ballvalve on cold water
pipes No 0
3.22 25mm diameter isolation ballvalve on cold water
pipe. No 0
3.23 65mm diameter isolation ballvalve on cold water
pipes. No 0
Carried to Collection
SUB-TOTAL FOR BILL WET SERVICES
MECHANICAL SERVICES
OCTOBER 2016 81
TRANSORANJE SCHOOL FOR THE DEAF, MECHANICAL BOQ
DEPARTMENT OF INFRASTRUCTURE DEVELOPMENT
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
BOYS HOSTEL A
REMOVALS
1.0 Disconnect and make safe existing hot water
geyser No. 1
1.1 Remove from site existing hot water geyser and
cold water piping No. 1
1.2 Cutting of walls to remove pipes in the wall No. 1
1.3 Safe keeping all the associated with pipes, eg
basins, shower heads, baths etc No. 1
NEW INSTALLATIONS
Cold Water Supply
2.0 15mm diameter pipes. m 40
2.1 22mm diameter pipes. m 120
2.2 28mm diameter insulated pipes. m 0
2.3 35mm diameter insulated pipes. m 0
2.4 42mm diameter pipes. m 0
2.5 54mm diameter pipes. m 0
2.6 67mm diameter pipes. m 0
Extra over copper pipework for fittings, as shown on
Hot and Cold Water Plumbing Layout drawings:
Bends
2.7 15mm diameter No 20
2.8 22mm diameter No 40
2.9 28mm diameter No 0
2.10 35mm diameter No 0
2.11 42mm diameter No 0
2.12 54mm diameter No 0
2.13 67mm diameter No 0
Carried to Collection
MECHANICAL SERVICES
OCTOBER 2016 82
TRANSORANJE SCHOOL FOR THE DEAF, MECHANICAL BOQ
DEPARTMENT OF INFRASTRUCTURE DEVELOPMENT
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
Tees
2.14 50mm-32mm-50mm diameter No 2
2.15 32mm-22mm-32mm diameter No 2
2.16 22mm-22mm-22mm diameter No 10
2.17 22mm-15mm-22mm diameter No 12
2.18 54mm diameter No 0
2.19 67mm diameter No 0
Reducers
2.20 50mm-32mm diameter No 4
2.21 32mm -22mm diameter No 4
2.22 32mm-15mm diameter No 4
2.23 22mm-15mm diameter No 0
2.24 42mm diameter No 0
2.25 54mm diameter No 0
2.26 67mm diameter No 0
Adapters
2.27 25mm Plastic to Male Iron adapter No 4
2.28 65mm Plastic to Male Iron adapter No 0
SOLAR WATER HEATERS
3.0 Supply, install, test and commission a double
jacketed, direct thermosiphon circulation type 200
litre solar water heater, complete with 3kW
electrical heater back-up element and 2 x 2m flat
plate solar collectors, 10m of copper piping,
insulation, 2-off 20mm vacuum breakers, 15mm
expansion relief valve, lever ball valves, mixing
valve, temperature differential controller, hot water
pipe insulation and truss strengthening where
required. Installation to comply with the
Department's document GP/M 2 Rev 1. Units to be
SABS Mark with SABS certificate.
Carried to Collection
MECHANICAL SERVICES
OCTOBER 2016 83
TRANSORANJE SCHOOL FOR THE DEAF, MECHANICAL BOQ
DEPARTMENT OF INFRASTRUCTURE DEVELOPMENT
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
Cylinder (mounted on roof)
Cylinder Capacity: 200 litres
Cylinder Material: SS 441;
Cylinder Material Thickness: 1.5mm
SABS Pressure Rating: 600kPa
Design Working Pressure: 400kPa
Glazing Material: 3.2mm tampered low iron.
Absorber Material: Steel
Absorber Surface: Black Chrome selective surface
Solar Collector Mounting: North Facing
No. of Solar collectors: 2
Collector Aperture: 1.86m2
Full Weight of System incl. frame: 500kg
Solar Collector Mounting: North Facing
3.1 Supply No. 6
3.2 Install No. 6
3.4 Installation of Solar Controller No. 1
3.5 Installation of timer No. 1
Copper pipe work
3.6 15mm diameter insulated pipes m 35
3.7 22mm diameter insulated pipes m 120
3.8 28mm diameter insulated pipes m 36
Extra over copper pipework for fittings, as shown on
Hot and Cold Water Plumbing Layout drawings:
Bends
3.9 15mm diameter No 18
3.10 22mm diameter No 26
3.11 28mm diameter No 0
3.12 35mm diameter No 0
Equal Tees
3.13 15mm diameter No 40
3.14 22mm diameter No 10
3.15 38mm diameter No 0
3.16 42mm diameter No 0
Carried to Collection
MECHANICAL SERVICES
OCTOBER 2016 84
TRANSORANJE SCHOOL FOR THE DEAF, MECHANICAL BOQ
DEPARTMENT OF INFRASTRUCTURE DEVELOPMENT
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
Reducers
3.17 28mm-22mm diameter No 4
3.18 22mm-15mm diameter No 4
3.19 35mm diameter No 0
Valves
15mm diameter stopcock/angle valve on cold and
3.20 hot water pipes to sanitary appliances. No 30
3.21 20mm diameter isolation ballvalve on cold water
pipes No 0
3.22 25mm diameter isolation ballvalve on cold water
pipe. No 0
3.23 65mm diameter isolation ballvalve on cold water
pipes. No 0
Carried to Collection
MECHANICAL SERVICES
OCTOBER 2016 85
TRANSORANJE SCHOOL FOR THE DEAF, MECHANICAL BOQ
DEPARTMENT OF INFRASTRUCTURE DEVELOPMENT
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
BOYS HOSTEL B
REMOVALS
1.0 Disconnect and make safe existing hot water
geyser No. 1
1.1 Remove from site existing hot water geyser and
cold water piping No. 1
1.2 Cutting of walls to remove pipes in the wall No. 1
1.3 Safe keeping all the associated with pipes, eg
basins, shower heads, baths etc No. 1
NEW INSTALLATIONS
Cold Water Supply
2.0 15mm diameter pipes. m 35
2.1 22mm diameter pipes. m 120
2.2 28mm diameter insulated pipes. m 0
2.3 35mm diameter insulated pipes. m 0
2.4 42mm diameter pipes. m 0
2.5 54mm diameter pipes. m 0
2.6 67mm diameter pipes. m 0
Extra over copper pipework for fittings, as shown on
Hot and Cold Water Plumbing Layout drawings:
Bends
2.7 15mm diameter No 30
2.8 22mm diameter No 15
2.9 28mm diameter No 0
2.10 35mm diameter No 0
2.11 42mm diameter No 0
2.12 54mm diameter No 0
2.13 67mm diameter No 0
Carried to Collection
MECHANICAL SERVICES
OCTOBER 2016 86
TRANSORANJE SCHOOL FOR THE DEAF, MECHANICAL BOQ
DEPARTMENT OF INFRASTRUCTURE DEVELOPMENT
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
Tees
2.14 50mm-32mm-50mm diameter No 2
2.15 32mm-22mm-32mm diameter No 2
2.16 22mm-22mm-22mm diameter No 10
2.17 22mm-15mm-22mm diameter No 12
2.18 54mm diameter No 0
2.19 67mm diameter No 0
Reducers
2.20 50mm-32mm diameter No 4
2.21 32mm -22mm diameter No 4
2.22 32mm-15mm diameter No 4
2.23 22mm-15mm diameter No 0
2.24 42mm diameter No 0
2.25 54mm diameter No 0
2.26 67mm diameter No 0
Adapters
2.27 25mm Plastic to Male Iron adapter No 4
2.28 65mm Plastic to Male Iron adapter No 0
SOLAR WATER HEATERS
3.0 Supply, install, test and commission a double
jacketed, direct thermosiphon circulation type 200
litre solar water heater, complete with 3kW
electrical heater back-up element and 2 x 2m flat
plate solar collectors, 10m of copper piping,
insulation, 2-off 20mm vacuum breakers, 15mm
expansion relief valve, lever ball valves, mixing
valve, temperature differential controller, hot water
pipe insulation and truss strengthening where
required. Installation to comply with the
Department's document GP/M 2 Rev 1. Units to be
SABS Mark with SABS certificate.
Carried to Collection
MECHANICAL SERVICES
OCTOBER 2016 87
TRANSORANJE SCHOOL FOR THE DEAF, MECHANICAL BOQ
DEPARTMENT OF INFRASTRUCTURE DEVELOPMENT
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
Cylinder (mounted on roof)
Cylinder Capacity: 200 litres
Cylinder Material: SS 441;
Cylinder Material Thickness: 1.5mm
SABS Pressure Rating: 600kPa
Design Working Pressure: 400kPa
Glazing Material: 3.2mm tampered low iron.
Absorber Material: Steel
Absorber Surface: Black Chrome selective surface
Solar Collector Mounting: North Facing
No. of Solar collectors: 2
Collector Aperture: 1.86m2
Full Weight of System incl. frame: 500kg
Solar Collector Mounting: North Facing
3.1 Supply No. 6
3.2 Install No. 6
3.4 Installation of Solar Controller No. 1
3.5 Installation of timer No. 1
Copper pipe work
3.6 15mm diameter insulated pipes m 35
3.7 22mm diameter insulated pipes m 120
3.8 28mm diameter insulated pipes m 36
Extra over copper pipework for fittings, as shown on
Hot and Cold Water Plumbing Layout drawings:
Bends
3.9 15mm diameter No 30
3.10 22mm diameter No 20
3.11 28mm diameter No 0
3.12 35mm diameter No 0
Equal Tees
3.13 15mm diameter No 30
3.14 22mm diameter No 10
3.15 38mm diameter No 0
3.16 42mm diameter No 0
Carried to Collection
MECHANICAL SERVICES
OCTOBER 2016 88
TRANSORANJE SCHOOL FOR THE DEAF, MECHANICAL BOQ
DEPARTMENT OF INFRASTRUCTURE DEVELOPMENT
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
Reducers
3.17 28mm-22mm diameter No 4
3.18 22mm-15mm diameter No 4
3.19 35mm diameter No 0
Valves
15mm diameter stopcock/angle valve on cold and
3.20 hot water pipes to sanitary appliances. No 30
3.21 20mm diameter isolation ballvalve on cold water
pipes No 0
3.22 25mm diameter isolation ballvalve on cold water
pipe. No 0
3.23 65mm diameter isolation ballvalve on cold water
pipes. No 0
Carried to Collection
MECHANICAL SERVICES
OCTOBER 2016 89
TRANSORANJE SCHOOL FOR THE DEAF, MECHANICAL BOQ
DEPARTMENT OF INFRASTRUCTURE DEVELOPMENT
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
BOYS HOSTEL C
REMOVALS
1.0 Disconnect and make safe existing hot water
geyser No. 1
1.1 Remove from site existing hot water geyser and
cold water piping No. 1
1.2 Cutting of walls to remove pipes in the wall No. 1
1.3 Safe keeping all the associated with pipes, eg
basins, shower heads, baths etc No. 1
NEW INSTALLATIONS
Cold Water Supply
2.0 15mm diameter pipes. m 35
2.1 22mm diameter pipes. m 120
2.2 28mm diameter insulated pipes. m 0
2.3 35mm diameter insulated pipes. m 0
2.4 42mm diameter pipes. m 0
2.5 54mm diameter pipes. m 0
2.6 67mm diameter pipes. m 0
Extra over copper pipework for fittings, as shown on
Hot and Cold Water Plumbing Layout drawings:
Bends
2.7 15mm diameter No 30
2.8 22mm diameter No 45
2.9 28mm diameter No 0
2.10 35mm diameter No 0
2.11 42mm diameter No 0
2.12 54mm diameter No 0
2.13 67mm diameter No 0
Carried to Collection
MECHANICAL SERVICES
OCTOBER 2016 90
TRANSORANJE SCHOOL FOR THE DEAF, MECHANICAL BOQ
DEPARTMENT OF INFRASTRUCTURE DEVELOPMENT
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
Tees
2.14 50mm-32mm-50mm diameter No 2
2.15 32mm-22mm-32mm diameter No 2
2.16 22mm-22mm-22mm diameter No 8
2.17 22mm-15mm-22mm diameter No 12
2.18 54mm diameter No 0
2.19 67mm diameter No 0
Reducers
2.20 50mm-32mm diameter No 4
2.21 32mm -22mm diameter No 4
2.22 32mm-15mm diameter No 4
2.23 22mm-15mm diameter No 0
2.24 42mm diameter No 0
2.25 54mm diameter No 0
2.26 67mm diameter No 0
Adapters
2.27 25mm Plastic to Male Iron adapter No 4
2.28 65mm Plastic to Male Iron adapter No 0
SOLAR WATER HEATERS
3.0 Supply, install, test and commission a double
jacketed, direct thermosiphon circulation type 200
litre solar water heater, complete with 3kW
electrical heater back-up element and 2 x 2m flat
plate solar collectors, 10m of copper piping,
insulation, 2-off 20mm vacuum breakers, 15mm
expansion relief valve, lever ball valves, mixing
valve, temperature differential controller, hot water
pipe insulation and truss strengthening where
required. Installation to comply with the
Department's document GP/M 2 Rev 1. Units to be
SABS Mark with SABS certificate.
Carried to Collection
MECHANICAL SERVICES
OCTOBER 2016 91
TRANSORANJE SCHOOL FOR THE DEAF, MECHANICAL BOQ
DEPARTMENT OF INFRASTRUCTURE DEVELOPMENT
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
Cylinder (mounted on roof)
Cylinder Capacity: 200 litres
Cylinder Material: SS 441;
Cylinder Material Thickness: 1.5mm
SABS Pressure Rating: 600kPa
Design Working Pressure: 400kPa
Glazing Material: 3.2mm tampered low iron.
Absorber Material: Steel
Absorber Surface: Black Chrome selective surface
Solar Collector Mounting: North Facing
No. of Solar collectors: 2
Collector Aperture: 1.86m2
Full Weight of System incl. frame: 500kg
Solar Collector Mounting: North Facing
3.1 Supply No. 6
3.2 Install No. 6
3.4 Installation of Solar Controller No. 1
3.5 Installation of timer No. 1
Copper pipe work
3.6 15mm diameter insulated pipes m 35
3.7 22mm diameter insulated pipes m 120
3.8 28mm diameter insulated pipes m 0
Extra over copper pipework for fittings, as shown on
Hot and Cold Water Plumbing Layout drawings:
Bends
3.9 15mm diameter No 30
3.10 22mm diameter No 20
3.11 28mm diameter No 0
3.12 35mm diameter No 0
Equal Tees
3.13 15mm diameter No 30
3.14 22mm diameter No 10
3.15 38mm diameter No 0
3.16 42mm diameter No 0
Carried to Collection
MECHANICAL SERVICES
OCTOBER 2016 92
TRANSORANJE SCHOOL FOR THE DEAF, MECHANICAL BOQ
DEPARTMENT OF INFRASTRUCTURE DEVELOPMENT
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
Reducers
3.17 28mm-22mm diameter No 4
3.18 22mm-15mm diameter No 4
3.19 35mm diameter No 0
Valves
15mm diameter stopcock/angle valve on cold and
3.20 hot water pipes to sanitary appliances. No 30
3.21 20mm diameter isolation ballvalve on cold water
pipes No 0
3.22 25mm diameter isolation ballvalve on cold water
pipe. No 0
3.23 65mm diameter isolation ballvalve on cold water
pipes. No 0
Carried to Collection
MECHANICAL SERVICES
OCTOBER 2016 93
TRANSORANJE SCHOOL FOR THE DEAF, MECHANICAL BOQ
DEPARTMENT OF INFRASTRUCTURE DEVELOPMENT
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
ABLUTIONS
REMOVALS
1.0 Disconnect and make safe existing hot water
geyser No. 0
1.1 Remove from site existing hot water geyser and
cold water piping No. 1
1.2 Cutting of walls to remove pipes in the wall No. 1
1.3 Safe keeping all the associated with pipes, eg
basins, shower heads, baths etc No. 1
NEW INSTALLATIONS
Cold Water Supply
2.0 15mm diameter pipes. m 30
2.1 22mm diameter pipes. m 80
2.2 28mm diameter insulated pipes. m 0
2.3 35mm diameter insulated pipes. m 0
2.4 42mm diameter pipes. m 0
2.5 54mm diameter pipes. m 0
2.6 67mm diameter pipes. m 0
Extra over copper pipework for fittings, as shown on
Hot and Cold Water Plumbing Layout drawings:
Bends
2.7 15mm diameter No 20
2.8 22mm diameter No 40
2.9 28mm diameter No 0
2.10 35mm diameter No 0
2.11 42mm diameter No 0
2.12 54mm diameter No 0
2.13 67mm diameter No 0
Carried to Collection
MECHANICAL SERVICES
OCTOBER 2016 94
TRANSORANJE SCHOOL FOR THE DEAF, MECHANICAL BOQ
DEPARTMENT OF INFRASTRUCTURE DEVELOPMENT
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
Tees
2.14 50mm-32mm-50mm diameter No 2
2.15 32mm-22mm-32mm diameter No 2
2.16 22mm-22mm-22mm diameter No 10
2.17 22mm-15mm-22mm diameter No 12
2.18 54mm diameter No 0
2.19 67mm diameter No 0
Reducers
2.20 50mm-32mm diameter No 4
2.21 32mm -22mm diameter No 4
2.22 32mm-15mm diameter No 4
2.23 22mm-15mm diameter No 0
2.24 42mm diameter No 0
2.25 54mm diameter No 0
2.26 67mm diameter No 0
Adapters
2.27 25mm Plastic to Male Iron adapter No 0
2.28 65mm Plastic to Male Iron adapter No 0
Carried to Collection
MECHANICAL SERVICES
OCTOBER 2016 95
TRANSORANJE SCHOOL FOR THE DEAF, MECHANICAL BOQ
DEPARTMENT OF INFRASTRUCTURE DEVELOPMENT
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
BOYS HOSTEL D
REMOVALS
1.0 Disconnect and make safe existing hot water
geyser No. 1
1.1 Remove from site existing hot water geyser and
cold water piping No. 1
1.2 Cutting of walls to remove pipes in the wall No. 1
1.3 Safe keeping all the associated with pipes, eg
basins, shower heads, baths etc No. 1
NEW INSTALLATIONS
Cold Water Supply
2.0 15mm diameter pipes. m 35
2.1 22mm diameter pipes. m 110
2.2 28mm diameter insulated pipes. m 0
2.3 35mm diameter insulated pipes. m 0
2.4 42mm diameter pipes. m 0
2.5 54mm diameter pipes. m 0
2.6 67mm diameter pipes. m 0
Extra over copper pipework for fittings, as shown on
Hot and Cold Water Plumbing Layout drawings:
Bends
2.7 15mm diameter No 30
2.8 22mm diameter No 10
2.9 28mm diameter No 0
2.10 35mm diameter No 0
2.11 42mm diameter No 0
2.12 54mm diameter No 0
2.13 67mm diameter No 0
Carried to Collection
MECHANICAL SERVICES
OCTOBER 2016 96
TRANSORANJE SCHOOL FOR THE DEAF, MECHANICAL BOQ
DEPARTMENT OF INFRASTRUCTURE DEVELOPMENT
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
Tees
2.14 50mm-32mm-50mm diameter No 2
2.15 32mm-22mm-32mm diameter No 2
2.16 22mm-22mm-22mm diameter No 8
2.17 22mm-15mm-22mm diameter No 12
2.18 54mm diameter No 0
2.19 67mm diameter No 0
Reducers
2.20 50mm-32mm diameter No 4
2.21 32mm -22mm diameter No 4
2.22 32mm-15mm diameter No 4
2.23 22mm-15mm diameter No 0
2.24 42mm diameter No 0
2.25 54mm diameter No 0
2.26 67mm diameter No 0
Adapters
2.27 25mm Plastic to Male Iron adapter No 4
2.28 65mm Plastic to Male Iron adapter No 0
SOLAR WATER HEATERS
3.0 Supply, install, test and commission a double
jacketed, direct thermosiphon circulation type 200
litre solar water heater, complete with 3kW
electrical heater back-up element and 2 x 2m flat
plate solar collectors, 10m of copper piping,
insulation, 2-off 20mm vacuum breakers, 15mm
expansion relief valve, lever ball valves, mixing
valve, temperature differential controller, hot water
pipe insulation and truss strengthening where
required. Installation to comply with the
Department's document GP/M 2 Rev 1. Units to be
SABS Mark with SABS certificate.
Carried to Collection
MECHANICAL SERVICES
OCTOBER 2016 97
TRANSORANJE SCHOOL FOR THE DEAF, MECHANICAL BOQ
DEPARTMENT OF INFRASTRUCTURE DEVELOPMENT
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
Cylinder (mounted on roof)
Cylinder Capacity: 200 litres
Cylinder Material: SS 441;
Cylinder Material Thickness: 1.5mm
SABS Pressure Rating: 600kPa
Design Working Pressure: 400kPa
Glazing Material: 3.2mm tampered low iron.
Absorber Material: Steel
Absorber Surface: Black Chrome selective surface
Solar Collector Mounting: North Facing
No. of Solar collectors: 2
Collector Aperture: 1.86m2
Full Weight of System incl. frame: 500kg
Solar Collector Mounting: North Facing
3.1 Supply No. 6
3.2 Install No. 6
3.4 Installation of Solar Controller No. 1
3.5 Installation of timer No. 1
Copper pipe work
3.6 15mm diameter insulated pipes m 40
3.7 22mm diameter insulated pipes m 120
3.8 28mm diameter insulated pipes m 36
Extra over copper pipework for fittings, as shown on
Hot and Cold Water Plumbing Layout drawings:
Bends
3.9 15mm diameter No 30
3.10 22mm diameter No 20
3.11 28mm diameter No 0
3.12 35mm diameter No 0
Equal Tees
3.13 15mm diameter No 14
3.14 22mm diameter No 16
3.15 38mm diameter No 0
3.16 42mm diameter No 0
Carried to Collection
MECHANICAL SERVICES
OCTOBER 2016 98
TRANSORANJE SCHOOL FOR THE DEAF, MECHANICAL BOQ
DEPARTMENT OF INFRASTRUCTURE DEVELOPMENT
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
Reducers
3.17 28mm-22mm diameter No 4
3.18 22mm-15mm diameter No 4
3.19 35mm diameter No 0
Valves
15mm diameter stopcock/angle valve on cold and
3.20 hot water pipes to sanitary appliances. No 30
3.21 20mm diameter isolation ballvalve on cold water
pipes No 0
3.22 25mm diameter isolation ballvalve on cold water
pipe. No 0
3.23 65mm diameter isolation ballvalve on cold water
pipes. No 0
Carried to Collection
MECHANICAL SERVICES
OCTOBER 2016 99
TRANSORANJE SCHOOL FOR THE DEAF, MECHANICAL BOQ
DEPARTMENT OF INFRASTRUCTURE DEVELOPMENT
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
KITCHEN
REMOVALS
1.0 Disconnect and make safe existing hot water
geyser No. 1
1.1 Remove from site existing hot water geyser and
cold water piping No. 1
1.2 Cutting of walls to remove pipes in the wall No. 1
1.3 Safe keeping all the associated with pipes, eg
basins, shower heads, baths etc No. 1
NEW INSTALLATIONS
Cold Water Supply
2.0 15mm diameter pipes. m 40
2.1 22mm diameter pipes. m 90
2.2 28mm diameter insulated pipes. m 0
2.3 35mm diameter insulated pipes. m 0
2.4 42mm diameter pipes. m 0
2.5 54mm diameter pipes. m 0
2.6 67mm diameter pipes. m 0
Extra over copper pipework for fittings, as shown on
Hot and Cold Water Plumbing Layout drawings:
Bends
2.7 15mm diameter No 30
2.8 22mm diameter No 10
2.9 28mm diameter No 0
2.10 35mm diameter No 0
2.11 42mm diameter No 0
2.12 54mm diameter No 0
2.13 67mm diameter No 0
Carried to Collection
MECHANICAL SERVICES
OCTOBER 2016 100
TRANSORANJE SCHOOL FOR THE DEAF, MECHANICAL BOQ
DEPARTMENT OF INFRASTRUCTURE DEVELOPMENT
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
Tees
2.14 50mm-32mm-50mm diameter No 2
2.15 32mm-22mm-32mm diameter No 2
2.16 22mm-22mm-22mm diameter No 8
2.17 22mm-15mm-22mm diameter No 12
2.18 54mm diameter No 0
2.19 67mm diameter No 0
Reducers
2.20 50mm-32mm diameter No 4
2.21 32mm -22mm diameter No 4
2.22 32mm-15mm diameter No 4
2.23 22mm-15mm diameter No 0
2.24 42mm diameter No 0
2.25 54mm diameter No 0
2.26 67mm diameter No 0
Adapters
2.27 25mm Plastic to Male Iron adapter No 4
2.28 65mm Plastic to Male Iron adapter No 0
SOLAR WATER HEATERS
3.0 Supply, install, test and commission a double
jacketed, direct thermosiphon circulation type 200
litre solar water heater, complete with 3kW
electrical heater back-up element and 2 x 2m flat
plate solar collectors, 10m of copper piping,
insulation, 2-off 20mm vacuum breakers, 15mm
expansion relief valve, lever ball valves, mixing
valve, temperature differential controller, hot water
pipe insulation and truss strengthening where
required. Installation to comply with the
Department's document GP/M 2 Rev 1. Units to be
SABS Mark with SABS certificate.
Carried to Collection
MECHANICAL SERVICES
OCTOBER 2016 101
TRANSORANJE SCHOOL FOR THE DEAF, MECHANICAL BOQ
DEPARTMENT OF INFRASTRUCTURE DEVELOPMENT
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
Cylinder (mounted on roof)
Cylinder Capacity: 200 litres
Cylinder Material: SS 441;
Cylinder Material Thickness: 1.5mm
SABS Pressure Rating: 600kPa
Design Working Pressure: 400kPa
Glazing Material: 3.2mm tampered low iron.
Absorber Material: Steel
Absorber Surface: Black Chrome selective surface
Solar Collector Mounting: North Facing
No. of Solar collectors: 2
Collector Aperture: 1.86m2
Full Weight of System incl. frame: 500kg
Solar Collector Mounting: North Facing
3.1 Supply No. 2
3.2 Install No. 2
3.4 Installation of Solar Controller No. 1
3.5 Installation of timer No. 1
Copper pipe work
3.6 15mm diameter insulated pipes m 48
3.7 22mm diameter insulated pipes m 30
3.8 28mm diameter insulated pipes m 36
Extra over copper pipework for fittings, as shown on
the Hot and Cold Water Plumbing Layout drawings:
Bends
3.9 15mm diameter No 30
3.10 22mm diameter No 10
3.11 28mm diameter No 0
3.12 35mm diameter No 0
Equal Tees
3.13 15mm diameter No 10
3.14 22mm diameter No 4
3.15 38mm diameter No 0
3.16 42mm diameter No 0
Carried to Collection
MECHANICAL SERVICES
OCTOBER 2016 102
TRANSORANJE SCHOOL FOR THE DEAF, MECHANICAL BOQ
DEPARTMENT OF INFRASTRUCTURE DEVELOPMENT
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
Reducers
3.17 28mm-22mm diameter No 4
3.18 22mm-15mm diameter No 4
3.19 35mm diameter No 0
Valves
15mm diameter stopcock/angle valve on cold and
3.20 hot water pipes to sanitary appliances. No 15
3.21 20mm diameter isolation ballvalve on cold water
pipes No 0
3.22 25mm diameter isolation ballvalve on cold water
pipe. No 0
3.23 65mm diameter isolation ballvalve on cold water
pipes. No 0
Carried to Collection
MECHANICAL SERVICES
OCTOBER 2016 103
TRANSORANJE SCHOOL FOR THE DEAF, MECHANICAL BOQ
DEPARTMENT OF INFRASTRUCTURE DEVELOPMENT
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
CLASSROOM 100
REMOVALS
1.0 Disconnect and make safe existing hot water
geyser No. 0
1.1 Remove from site existing hot water geyser and
cold water piping No. 1
1.2 Cutting of walls to remove pipes in the wall No. 1
1.3 Safe keeping all the associated with pipes, eg
basins, shower heads, baths etc No. 1
NEW INSTALLATIONS
Cold Water Supply
2.0 15mm diameter pipes. m 40
2.1 22mm diameter pipes. m 120
2.2 28mm diameter insulated pipes. m 0
2.3 35mm diameter insulated pipes. m 0
2.4 42mm diameter pipes. m 0
2.5 54mm diameter pipes. m 0
2.6 67mm diameter pipes. m 0
Extra over copper pipework for fittings, as shown on
Hot and Cold Water Plumbing Layout drawings:
Bends
2.7 15mm diameter No 20
2.8 22mm diameter No 40
2.9 28mm diameter No 0
2.10 35mm diameter No 0
2.11 42mm diameter No 0
2.12 54mm diameter No 0
2.13 67mm diameter No 0
Carried to Collection
MECHANICAL SERVICES
OCTOBER 2016 104
TRANSORANJE SCHOOL FOR THE DEAF, MECHANICAL BOQ
DEPARTMENT OF INFRASTRUCTURE DEVELOPMENT
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
Tees
2.14 50mm-32mm-50mm diameter No 2
2.15 32mm-22mm-32mm diameter No 2
2.16 22mm-22mm-22mm diameter No 10
2.17 22mm-15mm-22mm diameter No 12
2.18 54mm diameter No 0
2.19 67mm diameter No 0
Reducers
2.20 50mm-32mm diameter No 4
2.21 32mm -22mm diameter No 4
2.22 32mm-15mm diameter No 4
2.23 22mm-15mm diameter No 0
2.24 42mm diameter No 0
2.25 54mm diameter No 0
2.26 67mm diameter No 0
Adapters
2.27 25mm Plastic to Male Iron adapter No 4
2.28 65mm Plastic to Male Iron adapter No 0
Carried to Collection
MECHANICAL SERVICES
OCTOBER 2016 105
TRANSORANJE SCHOOL FOR THE DEAF, MECHANICAL BOQ
DEPARTMENT OF INFRASTRUCTURE DEVELOPMENT
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
CLASSROOM 300
REMOVALS
1.0 Disconnect and make safe existing hot water
geyser No. 0
1.1 Remove from site existing hot water geyser and
cold water piping No. 1
1.2 Cutting of walls to remove pipes in the wall No. 1
1.3 Safe keeping all the associated with pipes, eg
basins, shower heads, baths etc No. 1
NEW INSTALLATIONS
Cold Water Supply
2.0 15mm diameter pipes. m 44
2.1 22mm diameter pipes. m 100
2.2 28mm diameter insulated pipes. m 0
2.3 35mm diameter insulated pipes. m 0
2.4 42mm diameter pipes. m 0
2.5 54mm diameter pipes. m 0
2.6 67mm diameter pipes. m 0
Extra over copper pipework for fittings, as shown on
Hot and Cold Water Plumbing Layout drawings:
Bends
2.7 15mm diameter No 30
2.8 22mm diameter No 10
2.9 28mm diameter No 0
2.10 35mm diameter No 0
2.11 42mm diameter No 0
2.12 54mm diameter No 0
2.13 67mm diameter No 0
Carried to Collection
MECHANICAL SERVICES
OCTOBER 2016 106
TRANSORANJE SCHOOL FOR THE DEAF, MECHANICAL BOQ
DEPARTMENT OF INFRASTRUCTURE DEVELOPMENT
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
Tees
2.14 50mm-32mm-50mm diameter No 2
2.15 32mm-22mm-32mm diameter No 2
2.16 22mm-22mm-22mm diameter No 10
2.17 22mm-15mm-22mm diameter No 12
2.18 54mm diameter No 0
2.19 67mm diameter No 0
Reducers
2.20 50mm-32mm diameter No 4
2.21 32mm -22mm diameter No 4
2.22 32mm-15mm diameter No 4
2.23 22mm-15mm diameter No 0
2.24 42mm diameter No 0
2.25 54mm diameter No 0
2.26 67mm diameter No 0
Adapters
2.27 25mm Plastic to Male Iron adapter No 0
2.28 65mm Plastic to Male Iron adapter No 0
Carried to Collection
MECHANICAL SERVICES
OCTOBER 2016 107
TRANSORANJE SCHOOL FOR THE DEAF, MECHANICAL BOQ
DEPARTMENT OF INFRASTRUCTURE DEVELOPMENT
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
CLASSROOM 500
REMOVALS
1.0 Disconnect and make safe existing hot water
geyser No. 1
1.1 Remove from site existing hot water geyser and
cold water piping No. 1
1.2 Cutting of walls to remove pipes in the wall No. 1
1.3 Safe keeping all the associated with pipes, eg
basins, shower heads, baths etc No. 1
NEW INSTALLATIONS
Cold Water Supply
2.0 15mm diameter pipes. m 50
2.1 22mm diameter pipes. m 100
2.2 28mm diameter insulated pipes. m 0
2.3 35mm diameter insulated pipes. m 0
2.4 42mm diameter pipes. m 0
2.5 54mm diameter pipes. m 0
2.6 67mm diameter pipes. m 0
Extra over copper pipework for fittings, as shown on
Hot and Cold Water Plumbing Layout drawings:
Bends
2.7 15mm diameter No 24
2.8 22mm diameter No 20
2.9 28mm diameter No 0
2.10 35mm diameter No 0
2.11 42mm diameter No 0
2.12 54mm diameter No 0
2.13 67mm diameter No 0
Carried to Collection
MECHANICAL SERVICES
OCTOBER 2016 108
TRANSORANJE SCHOOL FOR THE DEAF, MECHANICAL BOQ
DEPARTMENT OF INFRASTRUCTURE DEVELOPMENT
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
Tees
2.14 50mm-32mm-50mm diameter No 2
2.15 32mm-22mm-32mm diameter No 2
2.16 22mm-22mm-22mm diameter No 8
2.17 22mm-15mm-22mm diameter No 12
2.18 54mm diameter No 0
2.19 67mm diameter No 0
Reducers
2.20 50mm-32mm diameter No 4
2.21 32mm -22mm diameter No 4
2.22 32mm-15mm diameter No 4
2.23 22mm-15mm diameter No 0
2.24 42mm diameter No 0
2.25 54mm diameter No 0
2.26 67mm diameter No 0
Adapters
2.27 25mm Plastic to Male Iron adapter No 4
2.28 65mm Plastic to Male Iron adapter No 0
Carried to Collection
MECHANICAL SERVICES
OCTOBER 2016 109
TRANSORANJE SCHOOL FOR THE DEAF, MECHANICAL BOQ
DEPARTMENT OF INFRASTRUCTURE DEVELOPMENT
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
PLAYROOMS
REMOVALS
1.0 Disconnect and make safe existing hot water
geyser No. 1
1.1 Remove from site existing hot water geyser and
cold water piping No. 1
1.2 Cutting of walls to remove pipes in the wall No. 1
1.3 Safe keeping all the associated with pipes, eg
basins, shower heads, baths etc No. 1
NEW INSTALLATIONS
Cold Water Supply
2.0 15mm diameter pipes. m 30
2.1 22mm diameter pipes. m 60
2.2 28mm diameter insulated pipes. m 0
2.3 35mm diameter insulated pipes. m 0
2.4 42mm diameter pipes. m 0
2.5 54mm diameter pipes. m 0
2.6 67mm diameter pipes. m 0
Extra over copper pipework for fittings, as shown on
Hot and Cold Water Plumbing Layout drawings:
Bends
2.7 15mm diameter No 30
2.8 22mm diameter No 25
2.9 28mm diameter No 0
2.10 35mm diameter No 0
2.11 42mm diameter No 0
2.12 54mm diameter No 0
2.13 67mm diameter No 0
Carried to Collection
MECHANICAL SERVICES
OCTOBER 2016 110
TRANSORANJE SCHOOL FOR THE DEAF, MECHANICAL BOQ
DEPARTMENT OF INFRASTRUCTURE DEVELOPMENT
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
Tees
2.14 50mm-32mm-50mm diameter No 2
2.15 32mm-22mm-32mm diameter No 2
2.16 22mm-22mm-22mm diameter No 8
2.17 22mm-15mm-22mm diameter No 12
2.18 54mm diameter No 0
2.19 67mm diameter No 0
Reducers
2.20 50mm-32mm diameter No 4
2.21 32mm -22mm diameter No 4
2.22 32mm-15mm diameter No 4
2.23 22mm-15mm diameter No 0
2.24 42mm diameter No 0
2.25 54mm diameter No 0
2.26 67mm diameter No 0
Adapters
2.27 25mm Plastic to Male Iron adapter No 4
2.28 65mm Plastic to Male Iron adapter No 0
Carried to Collection
MECHANICAL SERVICES
OCTOBER 2016 111
TRANSORANJE SCHOOL FOR THE DEAF, MECHANICAL BOQ
DEPARTMENT OF INFRASTRUCTURE DEVELOPMENT
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
HOUSE 1
REMOVALS
1.0 Disconnect and make safe existing hot water
geyser No. 1
1.1 Remove from site existing hot water geyser and
cold water piping No. 1
1.2 Cutting of walls to remove pipes in the wall No. 1
1.3 Safe keeping all the associated with pipes, eg
basins, shower heads, baths etc No. 1
NEW INSTALLATIONS
Cold Water Supply
2.0 15mm diameter pipes. m 20
2.1 22mm diameter pipes. m 40
2.2 28mm diameter insulated pipes. m 0
2.3 35mm diameter insulated pipes. m 0
2.4 42mm diameter pipes. m 0
2.5 54mm diameter pipes. m 0
2.6 67mm diameter pipes. m 0
Extra over copper pipework for fittings, as shown on
Hot and Cold Water Plumbing Layout drawings:
Bends
2.7 15mm diameter No 18
2.8 22mm diameter No 15
2.9 28mm diameter No 0
2.10 35mm diameter No 0
2.11 42mm diameter No 0
2.12 54mm diameter No 0
2.13 67mm diameter No 0
Carried to Collection
MECHANICAL SERVICES
OCTOBER 2016 112
TRANSORANJE SCHOOL FOR THE DEAF, MECHANICAL BOQ
DEPARTMENT OF INFRASTRUCTURE DEVELOPMENT
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
Tees
2.14 50mm-32mm-50mm diameter No 2
2.15 32mm-22mm-32mm diameter No 2
2.16 22mm-22mm-22mm diameter No 8
2.17 22mm-15mm-22mm diameter No 12
2.18 54mm diameter No 0
2.19 67mm diameter No 0
Reducers
2.20 50mm-32mm diameter No 4
2.21 32mm -22mm diameter No 4
2.22 32mm-15mm diameter No 4
2.23 22mm-15mm diameter No 0
2.24 42mm diameter No 0
2.25 54mm diameter No 0
2.26 67mm diameter No 0
Adapters
2.27 25mm Plastic to Male Iron adapter No 4
2.28 65mm Plastic to Male Iron adapter No 0
SOLAR WATER HEATERS
3.0 Supply, install, test and commission a double
jacketed, direct thermosiphon circulation type 200
litre solar water heater, complete with 3kW
electrical heater back-up element and 2 x 2m flat
plate solar collectors, 10m of copper piping,
insulation, 2-off 20mm vacuum breakers, 15mm
expansion relief valve, lever ball valves, mixing
valve, temperature differential controller, hot water
pipe insulation and truss strengthening where
required. Installation to comply with the
Department's document GP/M 2 Rev 1. Units to be
SABS Mark with SABS certificate.
Carried to Collection
MECHANICAL SERVICES
OCTOBER 2016 113
TRANSORANJE SCHOOL FOR THE DEAF, MECHANICAL BOQ
DEPARTMENT OF INFRASTRUCTURE DEVELOPMENT
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
Cylinder (mounted on roof)
Cylinder Capacity: 200 litres
Cylinder Material: SS 441;
Cylinder Material Thickness: 1.5mm
SABS Pressure Rating: 600kPa
Design Working Pressure: 400kPa
Glazing Material: 3.2mm tampered low iron.
Absorber Material: Steel
Absorber Surface: Black Chrome selective surface
Solar Collector Mounting: North Facing
No. of Solar collectors: 2
Collector Aperture: 1.86m2
Full Weight of System incl. frame: 500kg
Solar Collector Mounting: North Facing
3.1 Supply No. 1
3.2 Install No. 1
3.4 Installation of Solar Controller No. 1
3.5 Installation of timer No. 1
Copper pipe work
3.6 15mm diameter insulated pipes m 24
3.7 22mm diameter insulated pipes m 20
3.8 28mm diameter insulated pipes m 36
Extra over copper pipework for fittings, as shown on
the Hot and Cold Water Plumbing Layout drawings:
Bends
3.9 15mm diameter No 18
3.10 22mm diameter No 25
3.11 28mm diameter No 0
3.12 35mm diameter No 0
Equal Tees
3.13 15mm diameter No 15
3.14 22mm diameter No 25
3.15 38mm diameter No 0
3.16 42mm diameter No 0
Carried to Collection
MECHANICAL SERVICES
OCTOBER 2016 114
TRANSORANJE SCHOOL FOR THE DEAF, MECHANICAL BOQ
DEPARTMENT OF INFRASTRUCTURE DEVELOPMENT
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
Reducers
3.17 28mm-22mm diameter No 4
3.18 22mm-15mm diameter No 4
3.19 35mm diameter No 0
Valves
15mm diameter stopcock/angle valve on cold and
3.20 hot water pipes to sanitary appliances. No 4
3.21 20mm diameter isolation ballvalve on cold water
pipes No 0
3.22 25mm diameter isolation ballvalve on cold water
pipe. No 0
3.23 65mm diameter isolation ballvalve on cold water
pipes. No 0
Carried to Collection
MECHANICAL SERVICES
OCTOBER 2016 115
TRANSORANJE SCHOOL FOR THE DEAF, MECHANICAL BOQ
DEPARTMENT OF INFRASTRUCTURE DEVELOPMENT
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
HOUSE 3
REMOVALS
1.0 Disconnect and make safe existing hot water
geyser No. 1
1.1 Remove from site existing hot water geyser and
cold water piping No. 1
1.2 Cutting of walls to remove pipes in the wall No. 1
1.3 Safe keeping all the associated with pipes, eg
basins, shower heads, baths etc No. 1
NEW INSTALLATIONS
Cold Water Supply
2.0 15mm diameter pipes. m 18
2.1 22mm diameter pipes. m 25
2.2 28mm diameter insulated pipes. m 0
2.3 35mm diameter insulated pipes. m 0
2.4 42mm diameter pipes. m 0
2.5 54mm diameter pipes. m 0
2.6 67mm diameter pipes. m 0
Extra over copper pipework for fittings, as shown on
Hot and Cold Water Plumbing Layout drawings:
Bends
2.7 15mm diameter No 10
2.8 22mm diameter No 4
2.9 28mm diameter No 0
2.10 35mm diameter No 0
2.11 42mm diameter No 0
2.12 54mm diameter No 0
2.13 67mm diameter No 0
Carried to Collection
MECHANICAL SERVICES
OCTOBER 2016 116
TRANSORANJE SCHOOL FOR THE DEAF, MECHANICAL BOQ
DEPARTMENT OF INFRASTRUCTURE DEVELOPMENT
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
Tees
2.14 50mm-32mm-50mm diameter No 2
2.15 32mm-22mm-32mm diameter No 2
2.16 22mm-22mm-22mm diameter No 4
2.17 22mm-15mm-22mm diameter No 12
2.18 54mm diameter No 0
2.19 67mm diameter No 0
Reducers
2.20 50mm-32mm diameter No 4
2.21 32mm -22mm diameter No 4
2.22 32mm-15mm diameter No 4
2.23 22mm-15mm diameter No 0
2.24 42mm diameter No 0
2.25 54mm diameter No 0
2.26 67mm diameter No 0
Adapters
2.27 25mm Plastic to Male Iron adapter No 4
2.28 65mm Plastic to Male Iron adapter No 0
SOLAR WATER HEATERS
3.0 Supply, install, test and commission a double
jacketed, direct thermosiphon circulation type 200
litre solar water heater, complete with 3kW
electrical heater back-up element and 2 x 2m flat
plate solar collectors, 10m of copper piping,
insulation, 2-off 20mm vacuum breakers, 15mm
expansion relief valve, lever ball valves, mixing
valve, temperature differential controller, hot water
pipe insulation and truss strengthening where
required. Installation to comply with the
Department's document GP/M 2 Rev 1. Units to be
SABS Mark with SABS certificate.
Carried to Collection
MECHANICAL SERVICES
OCTOBER 2016 117
TRANSORANJE SCHOOL FOR THE DEAF, MECHANICAL BOQ
DEPARTMENT OF INFRASTRUCTURE DEVELOPMENT
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
Cylinder (mounted on roof)
Cylinder Capacity: 200 litres
Cylinder Material: SS 441;
Cylinder Material Thickness: 1.5mm
SABS Pressure Rating: 600kPa
Design Working Pressure: 400kPa
Glazing Material: 3.2mm tampered low iron.
Absorber Material: Steel
Absorber Surface: Black Chrome selective surface
Solar Collector Mounting: North Facing
No. of Solar collectors: 2
Collector Aperture: 1.86m2
Full Weight of System incl. frame: 500kg
Solar Collector Mounting: North Facing
3.1 Supply No. 1
3.2 Install No. 1
3.4 Installation of Solar Controller No. 1
3.5 Installation of timer No. 1
Copper pipe work
3.6 15mm diameter insulated pipes m 20
3.7 22mm diameter insulated pipes m 25
3.8 28mm diameter insulated pipes m 0
Extra over copper pipework for fittings, as shown on
the Hot and Cold Water Plumbing Layout drawings:
Bends
3.9 15mm diameter No 18
3.10 22mm diameter No 15
3.11 28mm diameter No 0
3.12 35mm diameter No 0
Equal Tees
3.13 15mm diameter No 18
3.14 22mm diameter No 15
3.15 38mm diameter No 0
3.16 42mm diameter No 0
Carried to Collection
MECHANICAL SERVICES
OCTOBER 2016 118
TRANSORANJE SCHOOL FOR THE DEAF, MECHANICAL BOQ
DEPARTMENT OF INFRASTRUCTURE DEVELOPMENT
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
Reducers
3.17 28mm-22mm diameter No 4
3.18 22mm-15mm diameter No 4
3.19 35mm diameter No 0
Valves
15mm diameter stopcock/angle valve on cold and
3.20 hot water pipes to sanitary appliances. No 4
3.21 20mm diameter isolation ballvalve on cold water
pipes No 0
3.22 25mm diameter isolation ballvalve on cold water
pipe. No 0
3.23 65mm diameter isolation ballvalve on cold water
pipes. No 0
Carried to Collection
MECHANICAL SERVICES
OCTOBER 2016 119
TRANSORANJE SCHOOL FOR THE DEAF, MECHANICAL BOQ
DEPARTMENT OF INFRASTRUCTURE DEVELOPMENT
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
HOUSE 4
REMOVALS
1.0 Disconnect and make safe existing hot water
geyser No. 1
1.1 Remove from site existing hot water geyser and
cold water piping No. 1
1.2 Cutting of walls to remove pipes in the wall No. 1
1.3 Safe keeping all the associated with pipes, eg
basins, shower heads, baths etc No. 1
NEW INSTALLATIONS
Cold Water Supply
2.0 15mm diameter pipes. m 20
2.1 22mm diameter pipes. m 25
2.2 28mm diameter insulated pipes. m 0
2.3 35mm diameter insulated pipes. m 0
2.4 42mm diameter pipes. m 0
2.5 54mm diameter pipes. m 0
2.6 67mm diameter pipes. m 0
Extra over copper pipework for fittings, as shown on
Hot and Cold Water Plumbing Layout drawings:
Bends
2.7 15mm diameter No 10
2.8 22mm diameter No 8
2.9 28mm diameter No 0
2.10 35mm diameter No 0
2.11 42mm diameter No 0
2.12 54mm diameter No 0
2.13 67mm diameter No 0
Carried to Collection
MECHANICAL SERVICES
OCTOBER 2016 120
TRANSORANJE SCHOOL FOR THE DEAF, MECHANICAL BOQ
DEPARTMENT OF INFRASTRUCTURE DEVELOPMENT
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
Tees
2.14 50mm-32mm-50mm diameter No 2
2.15 32mm-22mm-32mm diameter No 2
2.16 22mm-22mm-22mm diameter No 4
2.17 22mm-15mm-22mm diameter No 12
2.18 54mm diameter No 0
2.19 67mm diameter No 0
Reducers
2.20 50mm-32mm diameter No 4
2.21 32mm -22mm diameter No 4
2.22 32mm-15mm diameter No 4
2.23 22mm-15mm diameter No 0
2.24 42mm diameter No 0
2.25 54mm diameter No 0
2.26 67mm diameter No 0
Adapters
2.27 25mm Plastic to Male Iron adapter No 0
2.28 65mm Plastic to Male Iron adapter No 0
SOLAR WATER HEATERS
3.0 Supply, install, test and commission a double
jacketed, direct thermosiphon circulation type 200
litre solar water heater, complete with 3kW
electrical heater back-up element and 2 x 2m flat
plate solar collectors, 10m of copper piping,
insulation, 2-off 20mm vacuum breakers, 15mm
expansion relief valve, lever ball valves, mixing
valve, temperature differential controller, hot water
pipe insulation and truss strengthening where
required. Installation to comply with the
Department's document GP/M 2 Rev 1. Units to be
SABS Mark with SABS certificate.
Carried to Collection
MECHANICAL SERVICES
OCTOBER 2016 121
TRANSORANJE SCHOOL FOR THE DEAF, MECHANICAL BOQ
DEPARTMENT OF INFRASTRUCTURE DEVELOPMENT
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
Cylinder (mounted on roof)
Cylinder Capacity: 200 litres
Cylinder Material: SS 441;
Cylinder Material Thickness: 1.5mm
SABS Pressure Rating: 600kPa
Design Working Pressure: 400kPa
Glazing Material: 3.2mm tampered low iron.
Absorber Material: Steel
Absorber Surface: Black Chrome selective surface
Solar Collector Mounting: North Facing
No. of Solar collectors: 2
Collector Aperture: 1.86m2
Full Weight of System incl. frame: 500kg
Solar Collector Mounting: North Facing
3.1 Supply No. 1
3.2 Install No. 1
3.4 Installation of Solar Controller No. 1
3.5 Installation of timer No. 1
Copper pipe work
3.6 15mm diameter insulated pipes m 18
3.7 22mm diameter insulated pipes m 25
3.8 28mm diameter insulated pipes m 0
Extra over copper pipework for fittings, as shown on
the Hot and Cold Water Plumbing Layout drawings:
Bends
3.9 15mm diameter No 10
3.10 22mm diameter No 25
3.11 28mm diameter No 0
3.12 35mm diameter No 0
Equal Tees
3.13 15mm diameter No 15
3.14 22mm diameter No 25
3.15 38mm diameter No 0
3.16 42mm diameter No 0
Carried to Collection
MECHANICAL SERVICES
OCTOBER 2016 122
TRANSORANJE SCHOOL FOR THE DEAF, MECHANICAL BOQ
DEPARTMENT OF INFRASTRUCTURE DEVELOPMENT
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
Reducers
3.17 28mm-22mm diameter No 4
3.18 22mm-15mm diameter No 4
3.19 35mm diameter No 0
Valves
15mm diameter stopcock/angle valve on cold and
3.20 hot water pipes to sanitary appliances. No 4
3.21 20mm diameter isolation ballvalve on cold water
pipes No 0
3.22 25mm diameter isolation ballvalve on cold water
pipe. No 0
3.23 65mm diameter isolation ballvalve on cold water
pipes. No 0
Carried to Collection
MECHANICAL SERVICES
OCTOBER 2016 123
TRANSORANJE SCHOOL FOR THE DEAF, MECHANICAL BOQ
DEPARTMENT OF INFRASTRUCTURE DEVELOPMENT
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
GUARD HOUSE
REMOVALS
1.0 Disconnect and make safe existing hot water
geyser No. 1
1.1 Remove from site existing hot water geyser and
cold water piping No. 1
1.2 Cutting of walls to remove pipes in the wall No. 1
1.3 Safe keeping all the associated with pipes, eg
basins, shower heads, baths etc No. 1
NEW INSTALLATIONS
Cold Water Supply
2.0 15mm diameter pipes. m 10
2.1 22mm diameter pipes. m 30
2.2 28mm diameter insulated pipes. m 0
2.3 35mm diameter insulated pipes. m 0
2.4 42mm diameter pipes. m 0
2.5 54mm diameter pipes. m 0
2.6 67mm diameter pipes. m 0
Extra over copper pipework for fittings, as shown on
Hot and Cold Water Plumbing Layout drawings:
Bends
2.7 15mm diameter No 8
2.8 22mm diameter No 6
2.9 28mm diameter No 0
2.10 35mm diameter No 0
2.11 42mm diameter No 0
2.12 54mm diameter No 0
2.13 67mm diameter No 0
Carried to Collection
MECHANICAL SERVICES
OCTOBER 2016 124
TRANSORANJE SCHOOL FOR THE DEAF, MECHANICAL BOQ
DEPARTMENT OF INFRASTRUCTURE DEVELOPMENT
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
Tees
2.14 50mm-32mm-50mm diameter No 2
2.15 32mm-22mm-32mm diameter No 2
2.16 22mm-22mm-22mm diameter No 5
2.17 22mm-15mm-22mm diameter No 6
2.18 54mm diameter No 0
2.19 67mm diameter No 0
Reducers
2.20 50mm-32mm diameter No 4
2.21 32mm -22mm diameter No 4
2.22 32mm-15mm diameter No 4
2.23 22mm-15mm diameter No 0
2.24 42mm diameter No 0
2.25 54mm diameter No 0
2.26 67mm diameter No 0
Adapters
2.27 25mm Plastic to Male Iron adapter No 4
2.28 65mm Plastic to Male Iron adapter No 0
Carried to Collection
MECHANICAL SERVICES
OCTOBER 2016 125
TRANSORANJE SCHOOL FOR THE DEAF, MECHANICAL BOQ
DEPARTMENT OF INFRASTRUCTURE DEVELOPMENT
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
4.0 Testing and commission of the completed
installation Item 1
4.1 Attendance and profits on tests
4.2 Credit for redundant materials and equipment 1
4.3 Allow for inspections and measurements as
of installation required for the shop drawings
and detailed design 1
4.4 Allow for monthly site meetings and managing of
project and for senior supervision by a qualified
person
4.5 Allow for samples and technical information 1
4.6 Allow for record drawings and operating instructions 1
4.7 Allow for transportation/travelling charges 1
4.8 Allow for 12 months guarantee in terms of the 1
Document
4.9 Allow for all transport and rigging, lifting gear,
cranes, that may be required for moving of plant and
equipment setting out works 1
4.10 Allow for attendance on main contractor and for
switching off, removing all redundant items and
earthing to make supply safe and re-energise after
installation 1
AS-BUILT INFORMATION AND OPERATING AND
MAINTENANCE MANUALS
4.11 0btaining of all available information, compiling,
eproducing and finalising three sets of as-built and
Operating and Maintenance manuals as specified
Sb 05,01 and FF 03 and handing over to the
Engineer 3
Carried to Collection
MECHANICAL SERVICES
OCTOBER 2016 126
TRANSORANJE SCHOOL FOR THE DEAF, MECHANICAL BOQ
DEPARTMENT OF INFRASTRUCTURE DEVELOPMENT
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
SHOP AND "AS BUILT" DRAWINGS
4.12 Allow for preparation of detailed, dimensioned shop
drawings and 'as built" drawings to the entire works
and all its components include for 3 copies of all
drawings or approval carring out corrections as
required by engineer No. 3
TRAINING
18.23 Presenting a training course for operators 1
18.24 Presenting training course for maintenance staff 1
INSPECTION OF SITE AND SITE MEASUREMENT
18.25 Allow for detailed inspection of the site, site
measurement and setting out as necessary to carry
out the contract and to provide detailed dimensioned
shop drawings of all works Sum 1
EQUIPMENT SELECTIONS
18.26 Provide detailed selections and samples as
required for approval before installing Sum 1
OPERATION AND MAINTENANCE MANUALS
18.27 Provide Operating and Maintenance Manuals:
including "as built" drawings and equpment
selection information No. 3
SERVICE INSTALLATIONS AND CONNECTIONS
18.28 Electrical work: carry out complete connection from
local isolator, connect and gland off with water
proofed pvc sheathed copex and test electrical
installation to SANS 10142 and issue COC
certificates No. 3
Other
18.29 Any other items required for the successful
completion of the work but not included in this
bill of quantities. Please specify :
Carried to Collection
SUBTOTAL
SUB-TOTAL FOR BILL WET SERVICES
MECHANICAL SERVICES
OCTOBER 2016 127
TRANSORANJE SCHOOL FOR THE DEAF, MECHANICAL BOQ
DEPARTMENT OF INFRASTRUCTURE DEVELOPMENT
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
SPACE HEATING INSTALLATIONS-M2(2)
(a) This part of the BoQ must be priced by a specialist
HVAC sub-contractors to reduce failure
due financial risk.
(b) The main contractor shall provide a CV or brochure
for a specialist HVAC sub-contractor before
work starts for approval by engineer.
( c) Allow for the specialist HVAC sub-contractor
to visit the site and take measurements Sum 1
(d) Allow for production of factory shop drawings Sum 1
( e) Allow for submission of brochures and Data Sheet
for equipment to be supplied before equipment is
purchased Pricing of this BOQ must be done by
hvac specialist to reduce failure due to financial
risk
(f) Specialist to produce shop floor drawings to be
approved by the engineer
(g) Contractor must carefully study the DID, GP SQS
specifications, project specification, SANS
standards and the site before submitting
tenders.Contractors will be expected to submit
SABS Mark samples and SABS certificates before
purchasing all materials.
Carried to Collection
SPACE HEATING
JULY 2016 128
TRANSORANJE SCHOOL FOR THE DEAF, MECHANICAL BOQ
DEPARTMENT OF INFRASTRUCTURE DEVELOPMENT
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
1.0 3000l Hot Water Storage Tank with insulation c/w
cladding to DID SQS standards specification
and Heating Element 36kW as backup or approved
Working Pressure -400kPa
Supply No 1
Install No 1
2.0 Hot Water Pumps
Variable speed Circulating Pump
Liquid temperature Range -Upto 100 degrees
Working Pressure -TBC
Flow rate-64l/min or approved
2.1 Supply No 2
2.2 Install No 2
3.0 Solar Panels:Thermal Solar Collectors
Type ;Evacuated Tubes
Capacity: 3000litres/6hour to 100 deg C including
Mounting stands or approved
3.1 Supply Sum lot
3.2 Install Sum lot
3.3 Allow for a plinth and palisade fencing for storage Sum 1
tank and pumps ;Size-3000X2000x300mm
4.0 Space Heating ;Fan Coil Units
2.7 Kw
4.1 Supply No 4
4.2 Install No 4
3.9 Kw
4.3 Supply No 2
4.4 Install No 2
1.8Kw
4.5 Supply No 1
4.6 Install No 1
5.5 Kw
4.7 Supply No 1
4.8 Install No 1
4.8 Kw
4.9 Supply No 2
4.10 Install No 2
25mm Isolation Valves
5.1 Supply No 20
5.2 Install No 20
54mm Isolation Valves
5.3 Supply No 2
5.4 Install No 2
Carried to Collection
SPACE HEATING
JULY 2016 129
TRANSORANJE SCHOOL FOR THE DEAF, MECHANICAL BOQ
DEPARTMENT OF INFRASTRUCTURE DEVELOPMENT
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
6.0 On/off 220v Motorized Actuator
6.1 Supply No 10
6.2 Install No 10
Control Panels c/w sensors and timers
6.3 Supply Sum lot
6.4 Install Sum lot
7.0 Pipes
InsulationType -Superlon or approved by Engineer
Insulation Working Temperature- Upto 105 Degrees
7.1 Supply and install
7.2 25mm Copper Pipe superlon insulated m 140
7.3 54mm Copper Pipe superlon insulated m 200
8.0 Bends
8.1 Supply and install Superlon Insulated
8.2 25mm 90 deg bend no. 16
8.4 54mm 90 deg bend no. 6
9.0 Reducers
9.1 Supply and install Superlon Insulated
9.5 54 to 25mm no. 2
9 Pipe hangers
Supply Sum lot
Install Sum lot
9.1 54mm Strainers
Supply No 2
Install No 2
9.2 Thermostatic mixing valve maintain temperature
at 83-85 degree celcius
Supply No 10
Install No 10
9.3 Central programmer to provide overall on/off control
Supply No 1
Install No 1
9.4 Programmable Room thermostats
Supply No 10
Install No 10
Carried to Collection
SPACE HEATING
JULY 2016 130
TRANSORANJE SCHOOL FOR THE DEAF, MECHANICAL BOQ
DEPARTMENT OF INFRASTRUCTURE DEVELOPMENT
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
BLOCK B
1.0 3000l Hot Water Storage Tank with insulation c/w
cladding to DID SQS standards specification
and a Heating Element 36kW as backup or approved
Working Pressure -400kPa
Supply No 1
Install No 1
2.0 Hot Water Pumps
Variable speed Circulating Pump
Working Pressure -TBC
Flow rate-80l/min or approved
2.1 Supply No 2
2.2 Install No 2
3.0 Solar Panels:Thermal Solar Collectors
Type ;Evacuated Tubes
Capacity: 3000litres/6hour to 100 deg C including
Mounting stands or approved
3.1 Supply Sum lot
3.2 Install Sum lot
3.3 Allow for a plinth and palisade fencing for storage Sum 1
tank and pumps ;Size-3000X2000x300mm
4.0 Space Heating :Fan Coil Units
3.1 Kw
4.1 Supply No 7
4.2 Install No 7
1.9 Kw
4.3 Supply No 2
4.4 Install No 2
4.8Kw
4.5 Supply No 2
4.6 Install No 2
10Kw
4.7 Supply No 1
4.8 Install No 1
25mm Isolation Valves
4.9 Supply No 22
4.10 Install No 22
54mm isolation Valves
5.1 Supply No 2
5.2 Install No 2
On/off 220v Motorized Actuator
5.3 Supply No 11
5.4 Install No 11
6.0 Control Panels c/w sensors and timers
6.1 Supply Sum lot
6.2 Install Sum lot
Carried to Collection
SPACE HEATING
JULY 2016 131
TRANSORANJE SCHOOL FOR THE DEAF, MECHANICAL BOQ
DEPARTMENT OF INFRASTRUCTURE DEVELOPMENT
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
7.0 Pipes
InsulationType -Superlon or approved by Engineer
Insulation Working Temperature- Upto 105 Degrees
7.1 Supply and install
7.2 25mm Copper Pipe superlon insulated m 200
7.3 54mm Copper Pipe superlon insulated m 160
8.1 Supply and install Superlon Insulated
8.2 25mm 90 deg bend superlon insulated no. 24
8.4 54mm 90 deg bend superlon insulated no. 8
8.5 Reducers
8.6 Supply and install Superlon Insulated
8.7 54 to 25mm superlon insulated no. 2
9 Pipe hangers
Supply Sum lot
Install Sum lot
9.1 54mm Strainers
Supply No 2
Install No 2
9.2 Thermostatic mixing valve maintain temperature
at 83-85 degree celcius
Supply No 11
Install No 11
9.3Central programmer to provide overall on/off control
Supply No 1
Install No 1
9.4 Programmable Room thermostats
Supply No 11
Install No 11
Carried to Collection
SPACE HEATING
JULY 2016 132
TRANSORANJE SCHOOL FOR THE DEAF, MECHANICAL BOQ
DEPARTMENT OF INFRASTRUCTURE DEVELOPMENT
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
BLOCK C
1.0 2800l Hot Water Storage Tank with insulation c/w
cladding to DID SQS standards specification
and a Heating element 36kw as backup or approved
Working Pressure -400kPa
Supply No 1
Install No 1
2.0 Hot Water Pumps
Variable speed Circulating Pump
Liquid temperature Range -Upto 100 degrees
Working Pressure -TBC
Flow rate-22l/min or approved
2.1 Supply No 2
2.2 Install No 2
3.0 Solar Panels:Thermal Solar Collectors
Type ;Evacuated Tubes
Capacity: 2800litres/6hour to 100 deg C including
Mounting stands or approved
3.1 Supply Sum lot
3.2 Install Sum lot
3.3 Allow for a plinth and palisade fencing for storage Sum 1
tank and pumps ;Size-3000X2000x300mm
4.0
Space Heating ;Fan Coil Units
4.1 3 Kw
4.2 Supply No 4
Install No 4
4.7 25mm Isolation Valves
4.8 Supply No 8
Install No 8
4.9 54mm Isolation Valves
4.10 Supply No 2
Install No 2
5.1 On/off 220v Motorized Actuator
5.2 Supply No 4
Install No 4
Control Panels c/w sensors and timers
5.3 Supply Sum lot
5.4 Install Sum lot
Carried to Collection
SPACE HEATING
JULY 2016 133
TRANSORANJE SCHOOL FOR THE DEAF, MECHANICAL BOQ
DEPARTMENT OF INFRASTRUCTURE DEVELOPMENT
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
6.0 Pipes
InsulationType -Superlon or approved by Engineer
Insulation Working Temperature- Upto 105 Degrees6.1 Supply and install
6.3 25mm Copper Pipe insulated pipes m 60
6.4 54mm Copper Pipe insulated pipes m 60
7.0 Bends
7.1 Supply and install Superlon insulated
7.2 25mm 90 deg bend insulated no. 32
7.4 54mm 90 deg bend insulated no. 6
8.0 Reducers
8.1 Supply and install Superlon insulated
8.2 54 to 25mm insulated no. 2
9 Pipe hangers
Supply Sum lot
Install Sum lot
9.1 54mm Strainers
Supply No 2
Install No 2
9.2 Thermostatic mixing valve maintain temperature
at 83-85 degree celcius
Supply No 4
Install No 4
9.3 Central programmer to provide overall on/off control
Supply No 1
Install No 1
9.4 Programmable Room thermostats
Supply No 4
Install No 4
Carried to Collection
SPACE HEATING
JULY 2016 134
TRANSORANJE SCHOOL FOR THE DEAF, MECHANICAL BOQ
DEPARTMENT OF INFRASTRUCTURE DEVELOPMENT
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
BLOCK D
1.0 2800l Hot Water Storage Tank with insulation c/w
cladding to DID SQS standards specification
and a Heating element 36kW as backup or approved
Working Pressure -400kPa
Supply No 1
Install No 1
2.0 Hot Water Pumps
Variable speed Circulating Pump
Liquid temperature Range -Upto 100 degrees
Working Pressure -TBC
Flow rate-23l/min or approved
2.1 Supply No 2
2.2 Install No 2
3.0 Solar Panels:Thermal Solar Collectors
Type ;Evacuated Tubes
Capacity: 2800l/6hour to 100 deg C including
Mounting stands or approved
3.1 Supply Sum lot
3.2 Install Sum lot
3.3 Allow for a plinth and palisade fencing for storage Sum lot
tank and pumps ;Size-3000X2000x300mm
4.0 Space Heating ;Fan Coil Unit
5.2 Kw
4.1 Supply No 1
4.2 Install No 1
3.8 Kw
4.3 Supply No 2
4.4 Install No 2
15mm isolation Valves
4.5 Supply No 6
4.6 Install No 6
54mm isolation Valves
4.7 Supply No 2
4.8 Install No 2
On/off 220v Motorized Actuator
4.9 Supply No 3
4.10 Install No 3
Control Panels c/w sensors and timers
5.1 Supply Sum lot
5.2 Install Sum lot
Pipes
InsulationType -Superlon or approved by Engineer
Insulation Working Temperature- Upto 105 Degrees
6.0 Supply and install
6.1 25mm Copper Pipe Superlon insulated m 50
6.2 54mm Copper Pipe Superlon insulated m 50
Carried to Collection
SPACE HEATING
JULY 2016 135
TRANSORANJE SCHOOL FOR THE DEAF, MECHANICAL BOQ
DEPARTMENT OF INFRASTRUCTURE DEVELOPMENT
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
7.0 Bends
7.1 Supply and install Superlon insulated
7.2 25mm 90 deg bend insulated no. 80
7.3 54mm 90 deg bend insulated no. 10
8.0 Reducers
8.1 Supply and install Superlon insulated
8.2 54 to 25mm insulated no. 6
9 Pipe hangers
Supply Sum lot
Install Sum lot
9.1 54mm Strainers
Supply No 2
Install No 2
9.2 Thermostatic mixing valve maintain temperature
at 83-85 degree celcius
Supply No 3
9.3Central programmer to provide overall on/off control
Supply No 1
Install No 1
9.4 Programmable Room thermostats
Supply No 3
Install No 3
Carried to Collection
SPACE HEATING
JULY 2016 136
TRANSORANJE SCHOOL FOR THE DEAF, MECHANICAL BOQ
DEPARTMENT OF INFRASTRUCTURE DEVELOPMENT
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
BLOCK E-GIRLS HOSTEL
1.0 2800l Hot Water Storage Tank with insulation c/w
cladding to DID SQS standards specification
and Heating element 36kW as backup or approved
Working Presure -400kPa
Install No 1
Install No 1
2.0 Hot Water Pumps
Variable speed Circulating Pump
Liquid temperature Range -Upto 100 degrees
Working Pressure -TBC
Flow rate-70l/min or approved
2.1 Supply No 2
2.2 Install No 2
3.0 Solar Panels:Thermal Solar Collectors
Type ;Evacuated Tubes
Capacity: 2800litres /6hour to 100 deg C including
Mounting stands or approved
3.1 Supply No
3.2 Install No
3.3 Allow for a plinth and palisade fencing for storage Sum lot
tank and pumps ;Size-3000X2000x300mm
4.0 Space Heating Radiators
6.6Kw
4.1 Supply No 4
4.2 Install No 4
12.5 Kw
4.3 Supply No 4
4.4 Install No 4
25mm Valves
4.7 Supply No 16
4.8 Install No 16
54mm Valves
4.9 Supply No 2
4.10 Install No 2
On/off 220v Motorized Actuator
5.1 Supply No 8
5.2 Install No 8
Control Panels c/w sensors and timers
5.3 Supply Sum lot
5.4 Install Sum lot
Carried to Collection
SPACE HEATING
JULY 2016 137
TRANSORANJE SCHOOL FOR THE DEAF, MECHANICAL BOQ
DEPARTMENT OF INFRASTRUCTURE DEVELOPMENT
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
6.0 Pipes
InsulationType -Superlon or approved by Engineer
Insulation Working Temperature- Upto 105 Degrees6.1 Supply and install
6.2 25mm Copper Pipe superlon insulated m 160
6.3 54mm Copper Pipe superlon insulated m 160
7.0 Bends
7.1 Supply and install superlon insulated
7.2 25mm 90 deg bend no. 16
7.3 54mm 90 deg bend no. 6
8.0 Reducers
8.1 Supply and install superlon insulated
8.6 54 to 25mm no. 6
9 Pipe hangers
Supply Sum lot
Install Sum lot
9.2 54mm Strainers
Supply No 2
Install No 2
9.3 Thermostatic mixing valve maintain temperature
at 83-85 degree celcius
Supply No 8
Install No 8
9.4Central programmer to provide overall on/off control
Supply No 1
Install No 1
9.5 Programmable Room thermostats
Supply No 8
Install No 8
Carried to Collection
SPACE HEATING
JULY 2016 138
TRANSORANJE SCHOOL FOR THE DEAF, MECHANICAL BOQ
DEPARTMENT OF INFRASTRUCTURE DEVELOPMENT
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
BLOCK F
1.0 2800l Hot Water Storage Tank with insulation c/w
cladding to DID SQS standards specification
and a Heating element 36kW as backupor approved
working Pressure -400kPa
Supply No 1
Install No 1
2.0 Hot Water Pumps
Variable speed Circulating Pump
Liquid temperature Range -Upto 100 degrees
Working Pressure -TBC
Flow rate-23l/min or approved
2.1 Supply No 2
2.2 Install No 2
3.0 Solar Panels:Thermal Solar Collectors
Type ;Evacuated Tubes
Capacity: 2800litres/6hour to 100 deg C including
Mounting stands or approved
3.1 Supply Sum lot
3.2 Install Sum lot
3.3 Allow for a plinth and palisade fencing for storage No 1
tank and pumps ;Size-3000X2000x300mm
4.0 Space Heating Radiators:
3.1 Kw
4.1 Supply No 4
4.2 Install No 4
25mm Valves
4.3 Supply No 8
4.4 Install No 8
54mm Valves
4.5 Supply No 2
4.6 Install No 2
On/off 220v Motorized Actuator
4.7 Supply No 4
4.8 Install No 4
Control Panels c/w sensors and timers
4.9 Supply Sum lot
4.10 Install Sum lot
5.0 Pipes
InsulationType -Superlon or approved by Engineer
Insulation Working Temperature- Upto 105 Degrees
5.1 Supply and install
5.2 25mm Copper Pipe Superlon insulated m 60
5.3 54mm Copper Pipe Superlon insulated m 120
Carried to Collection
SPACE HEATING
JULY 2016 139
TRANSORANJE SCHOOL FOR THE DEAF, MECHANICAL BOQ
DEPARTMENT OF INFRASTRUCTURE DEVELOPMENT
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
6.0 Bends
6.1 Supply and install Superlon insulated
6.2 25mm 90 deg bend insulated no. 16
6.3 54mm 90 deg bend insulated no. 6
6.4
Reducers
7.0 Supply and install Superlon insulated
7.5 54 to 25mm insulated no. 2
9 Pipe hangers
Supply sum lot
Install sum lot
9.1 54mm Strainers
Supply No 2
Install No 2
9.2 Thermostatic mixing valve maintain temperature
at 83-85 degree celcius
Supply No 4
Install No 4
9.3Central programmer to provide overall on/off control
Supply No 1
Install No 1
9.4 Programmable Room thermostats
Supply No 4
Install No 4
Carried to Collection
SPACE HEATING
JULY 2016 140
TRANSORANJE SCHOOL FOR THE DEAF, MECHANICAL BOQ
DEPARTMENT OF INFRASTRUCTURE DEVELOPMENT
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
BLOCK G
1.0 2800l Hot Water Storage Tank with insulation c/w
cladding to DID SQS standards specification
and Heating element 36kW as backup or approved
Working Pressure -400kPa
Supply No 1
Install No 1
2.0 Hot Water Pumps
Variable speed Circulating Pump
Liquid temperature Range -Upto 100 degrees
Working Pressure -TBC
Flow rate-23l/min
2.1 Supply No 2
2.2 Install No 2
3.0 Solar Panels:Thermal Solar Collectors
Type ;Evacuated Tubes
Capacity: 2800litres/6hour to 100 deg C including
Mounting stands or approved
3.1 Supply sum lot
3.2 Install sum lot
3.3 Allow for a plinth and palisade fencing for storage No 1
tank and pumps ;Size-3000X2000x300mm
4.0 Space Heating :Fan Coil Units
3.1 Kw
4.1 Supply No 4
4.2 Install No 4
25mm Isolation Valves
4.3 Supply No 8
4.4 Install No 8
54mm isolation Valves
4.5 Supply No 2
4.6 Install No 2
On/off 220v Motorized Actuator
4.7 Supply No 8
4.8 Install No 8
Control Panels c/w sensors and timers
4.9 Supply Sum lot
4.10 Install Sum lot
5.0 Pipes
InsulationType -Superlon or approved by Engineer
Insulation Working Temperature- Upto 105 Degrees
5.1 Supply and install
5.2 25mm Copper Pipe Superlon insulated m 60
5.3 54mm Copper Pipe Superlon insulated m 120
Carried to Collection
SPACE HEATING
JULY 2016 141
TRANSORANJE SCHOOL FOR THE DEAF, MECHANICAL BOQ
DEPARTMENT OF INFRASTRUCTURE DEVELOPMENT
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
6.0 Bends
6.1 Supply and install Superlon insulated
6.2 22mm 90 deg bend no. 16
6.3 54mm 90 deg bend no. 6
7.0 Reducers
7.1 Supply and install Superlon insulated
7.2 54 to 32mm no. 4
9 Pipe hangers
Supply Sum lot
Install Sum lot
9.1 54mm Strainers
Supply No 2
Install No 2
9.2 Thermostatic mixing valve maintain temperature
at 83-85 degree celcius
Supply No 4
Install No 4
9.3Central programmer to provide overall on/off control
Supply No 1
Install No 1
9.4 Programmable Room thermostats
Supply No 4
Install No 4
Carried to Collection
SPACE HEATING
JULY 2016 142
TRANSORANJE SCHOOL FOR THE DEAF, MECHANICAL BOQ
DEPARTMENT OF INFRASTRUCTURE DEVELOPMENT
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
CR 200
1.0 2800l Hot Water Storage Tank with insulation c/w
cladding to DID SQS standards specification and
a Heating element 36kW as backup or approved
Working Pressure -400kPa
Supply No 1
Install No 1
2.0 Hot Water Pumps
Variable speed Circulating Pump
Liquid temperature Range -Upto 100 degrees
Working Pressure -TBC
Flow rate-45l/min
2.1 Supply No 2
2.2 Install No 2
3.0 Solar Panels:Thermal Solar Collectors
Type ;Evacuated Tubes
Capacity: 2800litres/6hour to 100 deg C including
Mounting stands or approved
3.1 Supply sum lot
3.2 Install sum lot
3.3 Allow for a plinth and palisade fencing for storage No 1
tank and pumps ;Size-3000X2000x300mm
4.0 Space Heating Radiator
1.17 Kw
4.1 Supply No 2
4.2 Install No 2
1.338 Kw
4.3 Supply No 2
4.4 Install No 2
2.64Kw
Supply No 2
Install No 2
3.036Kw
Supply No 2
Install No 2
3.6Kw
Supply No 2
Install No 2
4.068Kw
Supply No 2
Install No 2
4.5Kw
Supply No 2
Install No 2
Carried to Collection
SPACE HEATING
JULY 2016 143
TRANSORANJE SCHOOL FOR THE DEAF, MECHANICAL BOQ
DEPARTMENT OF INFRASTRUCTURE DEVELOPMENT
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
5.7Kw
Supply No 2
Install No 2
25mm Isolation Valves
4.5 Supply No 32
4.6 Install No 32
54mm isolation Valves
4.7 Supply No 2
4.8 Install No 2
On/off 220v Motorized Actuator
4.9 Supply No 16
4.10 Install No 16
Control Panels c/w sensors and timers
5.1 Supply Sum lot
5.2 Install Sum lot
6.0 Pipes
InsulationType -Superlon or approved by Engineer
Insulation Working Temperature- Upto 105 Degrees
6.1 Supply and install
6.3 25mm Copper Pipe Superlon insulated m 80
6.2 54mm Copper Pipe Superlon insulated m 180
6.0 Bends
6.1 Supply and install Superlon insulated
6.2 25mm 90 deg bend no. 16
6.3 54mm 90 deg bend no. 6
7.0 Reducers
7.1 Supply and install Superlon insulated
7.6 54 to 25mm no. 4
9 Pipe hangers
Supply sum lot
Install sum lot
9.1 25mm Strainers
Supply No 2
Install No 2
9.2 Thermostatic mixing valve maintain temperature
at 83-85 degree celcius
Supply No 16
Install No 16
Carried to Collection
SPACE HEATING
JULY 2016 144
TRANSORANJE SCHOOL FOR THE DEAF, MECHANICAL BOQ
DEPARTMENT OF INFRASTRUCTURE DEVELOPMENT
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
9.3 Central programmer to provide overall on/off control
Supply No 1
Install No 1
9.4 Programmable Room thermostats
Supply No 16
Install No 16
Carried to Collection
SPACE HEATING
JULY 2016 145
TRANSORANJE SCHOOL FOR THE DEAF, MECHANICAL BOQ
DEPARTMENT OF INFRASTRUCTURE DEVELOPMENT
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
CR 100
1.0 2800l Hot Water Storage Tank with insulation c/w
cladding to DID SQS standards specification
and Heating element 36Kw as backup or approved
Working Pressure -400kPa
Supply No 1
Install No 1
2.0 Hot Water Pumps
Variable speed Circulating Pump
Liquid temperature Range -Upto 100 degrees
Working Pressure -TBC
Flow rate-130l/min
2.1 Supply No 2
2.2 Install No 2
3.0 Solar Panels:Thermal Solar Collectors
Type ;Evacuated Tubes
Capacity: 2800litres/6hour to 100 deg C including
Mounting stands or approved
3.1 Supply Sum Lot
3.2 Install sum lot
3.3 Allow for a plinth and palisade fencing for storage No 1
tank and pumps ;Size-3000X2000x300mm
4.0 Space Heating ;Radiators
2.52 Kw
4.1 Supply No 24
4.2 Install No 24
4.3 25mm isolation Valves
Supply No 56
Install No 56
54mm isolation Valves
5.3 Supply No 2
5.4 Install No 2
6.0 On/off 220v Motorized Actuator
6.1 Supply No 18
6.2 Install No 18
Control Panels c/w sensors and timers
6.3 Supply Sum lot
6.4 Install Sum lot
Carried to Collection
SPACE HEATING
JULY 2016 146
TRANSORANJE SCHOOL FOR THE DEAF, MECHANICAL BOQ
DEPARTMENT OF INFRASTRUCTURE DEVELOPMENT
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
7.0 Pipes
InsulationType -Superlon or approved by Engineer
Insulation Working Temperature- Upto 105 Degrees
7.1 Supply and install
7.2 25mm Copper Pipe Superlon insulated m 200
7.3 54mm Copper Pipe Superlon insulated m 180
8.0 Bends
8.1 Supply and install Superlon insulated
8.2 25mm 90 deg bend no. 32
8.4 54mm 90 deg bend no. 10
9.0 Reducers
9.1 Supply and install Superlon insulated
9.2 54 to 25mm no. 2
9.3 Pipe hangers
Supply Sum lot
Install Sum lot
9.4 54mm Strainers
Supply No 2
Install No 2
9.5 Thermostatic mixing valve maintain temperature
at 83-85 degree celcius
Supply No 18
Install No 18
9.6 Central programmer to provide overall on/off control
Supply No 1
Install No 1
9.7 Programmable Room thermostats
Supply No 18
Install No 18
Carried to Collection
SPACE HEATING
JULY 2016 147
TRANSORANJE SCHOOL FOR THE DEAF, MECHANICAL BOQ
DEPARTMENT OF INFRASTRUCTURE DEVELOPMENT
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
CR300
1.0 2800l Hot Water Storage Tank with insulation c/w
cladding to DID SQS standards specification
with Heating element 36Kw as backup or approved
Working Pressure -400kPa
Supply No 1
Install No 1
2.0 Hot Water Pumps
Variable speed Circulating Pump
Liquid temperature Range -Upto 100 degrees
Working Pressure -TBC
Flow rate-90l/min
2.1 Supply No 2
2.2 Install No 2
3.0 Solar Panels:Thermal Solar Collectors
Type ;Evacuated Tubes
Capacity: 2800litres/6hour to 100 deg C including
Mounting stands or approved
3.1 Supply sum lot
3.2 Install sum lot
3.3 Allow for a plinth and palisade fencing for storage No 1
tank and pumps ;Size-3000X2000x300mm
4.0 Space Heating ;Fan Coil Units
2.25 Kw
4.1 Supply No 8
4.2 Install No 8
1.86 Kw
4.3 Supply No 6
4.4 Install No 6
25mm isolation Valves
4.5 Supply No 28
4.6 Install No 28
54mm isolation Valves
4.7 Supply No 2
4.8 Install No 2
On/off 220v Motorized Actuator
4.9 Supply No 14
4.10 Install No 14
Control Panels c/w sensors and timers
5.1 Supply Sum lot
5.2 Install Sum lot
6.0 Pipes
InsulationType -Superlon or approved by Engineer
Insulation Working Temperature- Upto 105 Degrees
6.1 Supply and install
6.2 25mm Copper Pipe Superlon insulated m 140
6.3 54mm Copper Pipe Superlon insulated m 140
Carried to Collection
SPACE HEATING
JULY 2016 148
TRANSORANJE SCHOOL FOR THE DEAF, MECHANICAL BOQ
DEPARTMENT OF INFRASTRUCTURE DEVELOPMENT
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
7.0 Bends
7.1 Supply and install Superlon insulated
7.2 25mm 90 deg bend no. 20
7.3 54mm 90 deg bend no. 2
8.0 Reducers
8.1 Supply and install Superlon insulated
8.6 54 to 25mm insulated no. 4
9 Pipe hangers
Supply Sum lot
Install Sum lot
9.1 54mm Strainers
Supply No 2
Install No 2
9.2 Thermostatic mixing valve maintain temperature
at 83-85 degree celcius
Supply No 28
Install No 28
9.3Central programmer to provide overall on/off control
Supply No 1
Install No 1
9.4 Programmable Room thermostats
Supply No 28
Install No 28
Carried to Collection
SPACE HEATING
JULY 2016 149
TRANSORANJE SCHOOL FOR THE DEAF, MECHANICAL BOQ
DEPARTMENT OF INFRASTRUCTURE DEVELOPMENT
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
CR400
1.0 2800l Hot Water Storage Tank with insulation c/w
cladding to DID SQS standards specification
and Heating element 36kW as backup or approved
Working Pressure-400kPa
Supply No 1
Install No 1
2.0 Hot Water Pumps
Variable speed Circulating Pump
Liquid temperature Range -Upto 100 degrees
Working Pressure -TBC
Flow rate-62l/min
2.1 Supply No 2
2.2 Install No 2
3.0 Solar Panels:Thermal Solar Collectors
Type ;Evacuated Tubes
Capacity: 2800litres/6hour to 100 deg C including
Mounting stands or approved
3.1 Supply sum lot
3.2 Install sum lot
3.3 Allow for a plinth and palisade fencing for storage No 1
tank and pumps ;Size-3000X2000x300mm
4.0 Space Heating:Fan Coil Units
4.3Kw
4.1 Supply No 2
4.2 Install No 2
3.3Kw
Supply No 4
Install No 4
25mm isolation Valves
4.3 Supply No 12
4.4 Install No 12
54mm isolation Valves
4.5 Supply No 2
4.6 Install No 2
On/off 220v Motorized Actuator
4.7 Supply No 6
4.8 Install No 6
Control Panels c/w sensors and timers
4.9 Supply Sum lot
4.10 Install Sum lot
Carried to Collection
SPACE HEATING
JULY 2016 150
TRANSORANJE SCHOOL FOR THE DEAF, MECHANICAL BOQ
DEPARTMENT OF INFRASTRUCTURE DEVELOPMENT
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
5 Pipes
InsulationType -Superlon or approved by Engineer
Insulation Working Temperature- Upto 105 Degrees
5.1 Supply and install
5.2 25mm Copper Pipe Superlon insulated m 140
5.3 54mm Copper Pipe Superlon insulated m 160
6.0 Bends
6.1 Supply and install Superlon insulated
6.2 22mm 90 deg bend no. 12
6.3 54mm 90 deg bend no. 6
7.0 Reducers
7.1 Supply and install Superlon insulated
7.6 54 to 25mm no. 2
9.51 Pipe hangers
Supply Sum lot
Install Sum lot
9.6 54mm Strainers
Supply No 2
Install No 2
9.7 Thermostatic mixing valve maintain temperature
at 83-85 degree celcius
Supply No 6
Install No 6
9.8Central programmer to provide overall on/off control
Supply No 1
Install No 1
9.9 Programmable Room thermostats
Supply No 6
Install No 6
Carried to Collection
SPACE HEATING
JULY 2016 151
TRANSORANJE SCHOOL FOR THE DEAF, MECHANICAL BOQ
DEPARTMENT OF INFRASTRUCTURE DEVELOPMENT
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
CR500
1.0 2800l Hot Water Storage Tank with insulation c/w
cladding to DID SQS standards specification
and Heating element 36kW as backup or approved
Working Pressure -400kPa
Supply No 1
Install No 1
2.0 Hot Water Pumps
Variable speed Circulating Pump
Liquid temperature Range -Upto 100 degrees
Working Pressure -TBC
Flow rate-203l/min
2.1 Supply No 2
2.2 Install No 2
3.0 Solar Panels:Thermal Solar Collectors
Type ;Evacuated Tubes
Capacity: 2800l/6hour to 100 deg C including
Mounting stands or approved
3.1 Supply Sum lot
3.2 Install Sum lot
3.3 Allow for a plinth and palisade fencing for storage No 1
tank and pumps ;Size-3000X2000x300mm
4.0 Space Heating Radiators
2.52Kw
4.1 Supply No 10
4.2 Install No 10
1.86Kw
Supply No 8
Install No 8
25mm isolation Valves
4.3 Supply No 36
4.4 Install No 36
54mm Isolation Valves
4.5 Supply No 2
4.6 Install No 2
On/off 220v Motorized Actuator
4.7 Supply No 18
4.8 Install No 18
Control Panels c/w sensors and timers
4.9 Supply Sum lot
4.10 Install Sum lot
Carried to Collection
SPACE HEATING
JULY 2016 152
TRANSORANJE SCHOOL FOR THE DEAF, MECHANICAL BOQ
DEPARTMENT OF INFRASTRUCTURE DEVELOPMENT
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
5.0 Pipes
InsulationType -Superlon or approved by Engineer
Insulation Working Temperature- Upto 105 Degrees
5.1 Supply and install
5.2 25mm Copper Pipe Superlon insulated m 180
5.3 54mm Copper Pipe Superlon insulated m 180
6.0 Bends
6.1 Supply and install Superlon insulated
6.2 25mm 90 deg bend no. 16
6.3 54mm 90 deg bend no. 6
7.0 Reducers
7.1 Supply and install Superlon insulated
7.2 54 to 25mm no. 4
8 Pipe hangers
Supply sum lot
Install sum lot
8.1 54mm Strainers
Supply No 2
Install No 2
8.2 Thermostatic mixing valve maintain temperature
at 83-85 degree celcius
Supply No 18
Install No 18
8.3 Central programmer to provide overall on/off control
Supply No 1
Install No 1
8.4 Programmable Room thermostats
Supply No 18
Install No 18
Carried to Collection
SPACE HEATING
JULY 2016 153
TRANSORANJE SCHOOL FOR THE DEAF, MECHANICAL BOQ
DEPARTMENT OF INFRASTRUCTURE DEVELOPMENT
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
DINNING HALL
1.0 2800l Hot Water Storage Tank with insulation c/w
cladding to DID SQS standards specification
and Heating element 36kW as a backup or approved
Working Pressure -400kPa
Supply No 1
Install No 1
2.0 Hot Water Pumps
Variable speed Circulating Pump
Liquid temperature Range -Upto 100 degrees
Working Pressure -TBC
Flow rate-86l/min
2.1 Supply No 2
2.2 Install No 2
3.0 Solar Panels:Thermal Solar Collectors
Type ;Evacuated Tubes
Capacity: 3000litres/6hour to 100 deg C including
Mounting stands or approved
3.1 Supply Sum lot
3.2 Install Sum lot
3.3 Allow for a plinth and palisade fencing for storage No 1
tank and pumps ;Size-3000X2000x300mm
4.0 Space Heating ;Radiators
4.1 3.0Kw
4.2 Supply No 10
Install No 10
4.3 25mm Isolation Valves
4.4 Supply No 24
Install No 24
4.5 54mm IsolationValves
4.6 Supply No 2
Install No 2
4.7 On/off 220v Motorized Actuator
4.8 Supply No 16
Install No 16
4.9 Control Panels c/w sensors and timers
4.10 Supply Sum lot
Install Sum lot
Carried to Collection
SPACE HEATING
JULY 2016 154
TRANSORANJE SCHOOL FOR THE DEAF, MECHANICAL BOQ
DEPARTMENT OF INFRASTRUCTURE DEVELOPMENT
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
5.0 Pipes
InsulationType -Superlon or approved by Engineer
Insulation Working Temperature- Upto 105 Degrees
5.1 Supply and Install
5.2 25mm Copper Pipe Superlon insulated m 100
5.3 54mm Copper Pipe Superlon insulated m 100
6.0 Bends
6.1 Supply and Install Superlon insulated
6.2 25mm 90 deg bend no. 24
6.3 54mm 90 deg bend no. 6
7.0 Reducers
7.1 Supply and Install Superlon insulated
7.6 54 to 25mm no. 2
8 Pipe hangers
Supply Sum lot
Install Sum lot
8.1 54mm Strainers
Supply No 2
Install No 2
8.2 Thermostatic mixing valve to maintain temperature
at 83-85 degree celcius
Supply No 1
Install No 1
8.3Central programmer to provide overall on/off control
Supply No 1
Install No 1
8.4 Programmable Room thermostats
Supply No 16
Install No 16
Carried to Collection
SPACE HEATING
JULY 2016 155
TRANSORANJE SCHOOL FOR THE DEAF, MECHANICAL BOQ
DEPARTMENT OF INFRASTRUCTURE DEVELOPMENT
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
MEDIA CENTER
1.0 2400l Hot Water Storage Tank with insulation &
cladding to DID SQS standards specification
with Heating element 36kW as backup or approved
Working Pressure-400kpa
Supply No 1
Install No 1
2.0 Hot Water Pumps
Variable speed Circulating Pump
Liquid temperature Range -Upto 100 degrees
Working Pressure -TBC
Flow rate-20l/min
2.1 Supply No 2
2.2 Install No 2
3.0 Solar Panels:Thermal Solar Collectors
Type ;Evacuated Tubes
Capacity: 2400Litres /6hour to 60 deg C including
Mounting stands or approved
3.1 Supply Sum lot
3.2 Install Sum lot
3.3 Allow for a plinth and palisade fencing for storage No 1
tank and pumps ;Size-3000X2000x300mm
4.0 Underfloor Space Heating
4.1 Pipes
4.2 Supply and install
4.3 12mm Pex or Multilayer or PTFE pipes m 1232
4.4 25mm Pex or Multilayer or PTFE pipes m 8
4.1 Bends
4.2 Supply and install
4.3 15mm 90 deg bend no. 210
4.4 25mm 90 deg bend no. 0
no. 6
6.0 Reducers
6.1 Supply and install
6.2 25mm to 12mm no. 4
7 Pipe Fixing
Steel Mesh
Area-220 sqm
Supply Sum lot
Install Sum lot
7.1 Staples ,Clips,Wire
Supply Sum lot
Install Sum lot
Carried to Collection
SPACE HEATING
JULY 2016 156
TRANSORANJE SCHOOL FOR THE DEAF, MECHANICAL BOQ
DEPARTMENT OF INFRASTRUCTURE DEVELOPMENT
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
7.2 Manifold
Supply No 1
Install No 1
7.3 Floor Insulation
Supply Sum lot
Install Sum lot
7.4 Edge strip Insulation
Supply Sum lot
Install Sum lot
7.5 Temperature Mixing Valve to maintain temperature
of water @ 40-55 degrees celcius
Supply No 2
Install No 2
7.8 Actuactors
Supply No 2
Install No 2
7.9 Underfloor Pump
Supply No 2
Install No 2
8 Central Programmer for overall on/off control
Supply No 1
Install No 1
8.1 Zoned area Thermostats
Supply No 3
Install No 3
8.2 15mm Isolation Valves
8.4 Supply No 8
8.5 Install No 8
8.6 25mm Isolation Valves
8.7 Supply No 2
8.8 Install No 2
7.111 Injection Valves to inject water @ 40 -55 degrees
celcuis
Supply No 1
Install No 1
8.9 Allow for Removal of wooden floor panels Sum lot
9 Keep wooden floor panels in storeroom Sum lot
9.11 Transport back for reinstallation Sum lot
Carried to Collection
SPACE HEATING
JULY 2016 157
TRANSORANJE SCHOOL FOR THE DEAF, MECHANICAL BOQ
DEPARTMENT OF INFRASTRUCTURE DEVELOPMENT
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
9.12 Reinstate wooden floor as was before Sum lot
9.13 Sanding and sealing Sum lot
9.14 Allow for a cement additive Sum lot
9.15 Allow for feasibility study by hvac specilists lot Sum
9.17 Allow for specilist installation drawings lot sum
9.17b Allow for glycol as a heat transfer medium lot sum
Testing and Commissioning
9.18
Allow for testing of equipments and training of the end
user on all the equipment installation after completion.
Sum 1
Gurantee and Maintenance
9.19Provision of Guarantee of equipment and 12-month
maintenance period.
Sum 1
Operating and Maintenance Procedures
9.2Compilation and submission of Operation &
Maintenance procedures for all the Equipments.
No 4
9.3 completion of the work but not included in this bill of
quantities. Please specify: Sum 1
9.4 Testing and commission of the completed
installation Item 1
9.5 Attendance and profits on tests
9.6 Allow for inspections and measurements as
9.7 required for the shop drawings and detailed
9.8 design of installation 1
9.9 Allow for monthly site meetings and managing of
10 project and for senior supervision by a qualified
10.11 person 1
10.12 Allow for samples and technical information 1
10.13
Allow for record drawings and operating instructions 1
10.14 Allow for transportation/travelling charges 1
10.15 Allow for maintenance and specialist maintenance
10.16 as specified 1
10.17 Allow for 12 months guarantee in terms of the
Document 1
Carried to Collection
SPACE HEATING
JULY 2016 158
TRANSORANJE SCHOOL FOR THE DEAF, MECHANICAL BOQ
DEPARTMENT OF INFRASTRUCTURE DEVELOPMENT
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
10.18
Allow for all transport and rigging, lifting gear, cranes
etc, that may be required for moving of plant and
equipment setting out works 1
10.19 Allow for attendance on main contractor and for
switching off, removing all redundant items and
earthing to make supply safe and re-energise after
installation 1
AS-BUILT INFORMATION AND OPERATING AND
MAINTENANCE MANUALS
10.2 Obtaining of all available information, compiling,
reproducing and finalising three sets of as-built and
Operating and Maintenance manuals as specified in
Sb 05,01 and FF 03 and handing over to the Engineer 3
SHOP AND "AS BUILT" DRAWINGS
10.21 Allow for preparation of detailed, dimensioned shop
drawings and 'as built" drawings to the entire works
and all its components include for 3 copies of all
drawings for approval carring out corrections as
required by engineer No. 3
TRAINING
10.22 Presenting a training course for operators 1
10.23 Presenting training course for maintenance staff 1
INSPECTION OF SITE AND SITE MEASUREMENT
10.24 Allow for detailed inspection of the site,
site measurement and setting out as necessary to
carryout the contract and to provide detailed
dimensioned shop drawings of all works 1
EQUIPMENT SELECTIONS
10.25 Provide detailed selections and samples as
required for approval before installing
OPERATION AND MAINTENANCE MANUALS
10.26 Provide Operating and Maintenance Manuals:
including "as built" drawings and equpment
selection information No. 3
SERVICE INSTALLATIONS AND CONNECTIONS
10.27 Electrical work: carry out complete connection from
local isolator, connect and gland off with water
proofed pvc sheathed copex and test electrical
installation to SANS 10142 and issue COC
certificates No. 0
Carried to Collection
SPACE HEATING
JULY 2016 159
TRANSORANJE SCHOOL FOR THE DEAF, MECHANICAL BOQ
DEPARTMENT OF INFRASTRUCTURE DEVELOPMENT
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
10.28 Plumbing and drainage work: carry out complete
connection to water services and to drains, connect
SS flexible 15mm water connection installation and
with compression fitting for easy access- use
stainless steel for isolation of the ball valves(and
balls with viton seats)supply at each equipment item 0
10.29 Test the complete installation at full load and in
cooking mode and all associated components of
the installation in phases as the work proses as
work proceeds, demostrate and hand over to the
user; sign off at hand over as beingfully operational
and satisfactory Sum 1
Other
10.3 Any other items required for the successful
completion of the work but not included in this
bill of quantities. Please specify :
Carried to Collection
SUB-TOTAL FOR SPACE HEATING
CARRIED TO SUMMARY PAGE
SPACE HEATING
JULY 2016 160
TRANSORANJE SCHOOL FOR THE DEAF, MECHANICAL BOQ
DEPARTMENT OF INFRASTRUCTURE DEVELOMENT
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
LG GAS INSTALLATIONS-M5
(a) This part of the BoQ must be priced by a specialist
LP Gas sub-contractors to reduce failure due
financial risk.
(b) The main contractor shall provide a CV or brochure
for a specialist LP gas sub-contractor before
work starts for approval by engineer.
( c) Allow for the specialist LP gas sub-contractor
to visit the site and take measurements Sum 1
(d) Allow for production of factory shop drawings Sum 1
( e) Allow for submission of brochures and datsheets for
equipment to before it is purchased
(f) Contractor must study carefully the DID, GP SQS
specifications, project specification, SANS
standards and the site before submitting
tenders.Contractors will be expected to submit
SABS Mark samples and SABS certificates before
purchasing all materials.
(g) All work should conform to the requirements of the
Standard Quality Specification for Liquefied
Petroleum Gas(LPG)-DID-E/M5 latest revision
LP Gas Installation
(h) All materials and workmanship for the LP Gas
installation shall be in accordance with SANS
10087:2008, SANS 1237:2007 and SANS 1156:2007
and is to be carried out by an approved, qualified and
registered LP Gas contractor.
Carried to Collection
LPG INSTALLATION
JULY 2016 161
TRANSORANJE SCHOOL FOR THE DEAF, MECHANICAL BOQ
DEPARTMENT OF INFRASTRUCTURE DEVELOMENT
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
KITCHEN
Purpose-Made Gas Cylinder Cage
1.0 Allow for the supply and fixing of approved
lockable,purpose-made prefabricated,vandal proof
and robust steel cage enclosure for the LP Gas
cylinder containers capable of housing a maximum
of 4-off standard 48kg Gas cylinder containers,
manifold and associated valves, pigtails, piping
and fittings.
Supply No 1
Install No 1
LP Gas Pipe Manifold
1.1 Allow for fixing of LP Gas pipe mainifold support
brackets to wall in LP Gas containers enclosure,
including flexible hose connections to 4 No LP gas
containers, support chains and clamps, etc,
for containers. Sum 1
Regulator
1.2 Low pressure first stage gas regulator. No 1
Valves
1.3 Shut-off valves in LP Gas cage enclosure. No 4
1.4 Changeover valve in LP Gas container enclosure. No 1
1.5 Isolating valves to kitchen appliances. No 1
1.6 Allow for emergency shut-off valve in kitchen. No 1
Carried to Collection
LPG INSTALLATION
JULY 2016 162
TRANSORANJE SCHOOL FOR THE DEAF, MECHANICAL BOQ
DEPARTMENT OF INFRASTRUCTURE DEVELOMENT
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
2.0 Pipework
Copper Piping
LP Gas grade Class 1 minimum copper pipes to
SANS 460 and SANS 1067 with capillary type
soldered joints done in accordance with the
manufacturer's specifications, and installed in
accordance with SANS 10400:2011 and SANS
10252-1:2004, including couplers in the running
length, and all necessary supports, fixing, brackets,
saddles, holderbats, etc, and colour-coded in
accordance with SANS 10140-3:2003. Installation
to comply with the Department's document GP/M2
Rev 1.
2.1 15mm diameter pipe fixed to walls. m 40
Extra over LP Gas copper pipework for fittings, as
shown on the LP Gas drawing:
2.2 22mm diameter tees, reducers, plugs, bends, etc. Sum 1
Composite Piping
2.3 2025mm composite LP Gas piping fixed to external
walls. m 40
Extra over LP Gas copper pipework for fittings,
as shown on the LP Gas drawing:
2.4 2025mm diameter bends, tees, reducers, plugs,
etc. Sum 1
2.5 Muti-layer / Composite to copper pipe connector. No 1
Fire Extinguisher
3.0 Supply and install 10kg Carbon Dioxide (CO2) type
fire extingusher
3.1 Supply No. 1
Install No. 1
3.2 Supply and install a tamper proof translucent
polycarbonate enclosure for the 10 kg Carbon Dioxide
(CO2) Fire Extinguisher
3.3 Supply No. 13.4 Install No. 1
Carried to Collection
LPG INSTALLATION
JULY 2016 163
TRANSORANJE SCHOOL FOR THE DEAF, MECHANICAL BOQ
DEPARTMENT OF INFRASTRUCTURE DEVELOMENT
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
Photoluminescent signage and warning notices in
accordance with SANS 1186-1:2008, and
incorporating the pictographs in the standard,
size 150 x 150mm, securely fixed to wall or gate at
the LP Gas cylinders enclosure:
4.1 Type F13 red figure on white background with 4mm
red border line: Fire extinguisher. No 1
4.2 Type PV1, black figure on white background with
4mm red circular border line: Smoking prohibited. No 1
4.3 Type PV2, black figure on white background with
4mm red circular border line: Fire and open flames
prohibited. No 1
4.4 Type PV27, black figure on white background with
4mm red circular border line: Cellphone prohibited. No 1
Carried to Collection
LPG INSTALLATION
JULY 2016 164
TRANSORANJE SCHOOL FOR THE DEAF, MECHANICAL BOQ
DEPARTMENT OF INFRASTRUCTURE DEVELOMENT
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
HOME ECONOMICS
1.0 Allow for the supply and fixing of approved
lockable,purpose-made prefabricated,vandal proof
and robust Steel Cage enclosure for the LP Gas
Cylinder containers capable of housing a maximum
of 6-off standard 48kg Gas cylinder containers,
manifold and associated valves, pigtails, piping
and fittings. No 1
LP Gas Pipe Manifold
1.1 Allow for fixing of LP Gas pipe mainifold support
brackets to wall in LP Gas containers enclosure,
including flexible hose connections to 6 No LP gas
containers, support chains and clamps, etc,
for containers. Sum 1
Regulator
1.2 Low pressure first stage gas regulator. No 1
Valves
1.3 Shut-off valves in LP Gas cage enclosure. No 6
1.4 Changeover valve in LP Gas container enclosure. No 1
1.5 Isolating valves to Kitchen appliances. No 1
1.6 Allow for emergency shut-off valve in Kitchen. No 1
Carried to Collection
LPG INSTALLATION
JULY 2016 165
TRANSORANJE SCHOOL FOR THE DEAF, MECHANICAL BOQ
DEPARTMENT OF INFRASTRUCTURE DEVELOMENT
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
2.0 Pipework
Copper Piping
LP Gas grade Class 1 minimum copper pipes to
soldered joints done in accordance with the
manufacturer's specifications, and installed in
accordance with SANS 10400:2011 and SANS
10252-1:2004, including couplers in the running
length, and all necessary supports, fixing, brackets,
saddles, holderbats, etc, and colour-coded in
accordance with SANS 10140-3:2003. Installation
to comply with the Department's document GP/M2
Rev 1.
2.1 15mm diameter pipe fixed to walls. m 90
Extra over LP Gas copper pipework for fittings, as
shown on the LP Gas drawing:
2.2 22mm diameter tees, reducers, plugs, bends, etc. Sum 1
Composite Piping
2.3 2025mm composite LP Gas piping fixed to external
walls. m 90
Extra over LP Gas copper pipework for fittings,
as shown on the LP Gas drawing:
2.4 2025mm diameter bends, tees, reducers, plugs,
etc. Sum 1
2.5 Muti-layer / Composite to copper pipe connector. No 1
Fire Extinguisher
3.0 Supply and install 10kg Carbon Dioxide (CO2) type
fire extingusher
3.1 Supply No. 1
3.2 Supply and install a tamper proof translucent
polycarbonate enclosure for the 10 kg Carbon Dioxide
(CO2) Fire Extinguisher
3.3 Supply No. 13.4 Install No. 1
Carried to Collection
LPG INSTALLATION
JULY 2016 166
TRANSORANJE SCHOOL FOR THE DEAF, MECHANICAL BOQ
DEPARTMENT OF INFRASTRUCTURE DEVELOMENT
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
4.0 Signage
Photoluminescent signage and warning notices in
accordance with SANS 1186-1:2008, and
incorporating the pictographs in the standard,
size 150 x 150mm, securely fixed to wall or gate at
the LP Gas cylinders enclosure:
4.1 Type F13 red figure on white background with 4mm
red border line: Fire extinguisher. No 1
4.2 Type PV1, black figure on white background with
4mm red circular border line: Smoking prohibited. No 1
4.3 Type PV2, black figure on white background with
4mm red circular border line: Fire and open flames
prohibited. No 1
4.4 Type PV27, black figure on white background with
4mm red circular border line: Cellphone prohibited. No 1
Testing and Commissioning
5.0 Allow for testing of entire LP Gas installation after
completion and provide a signed certificate in an
aluminium frame with transparent protective
material in front. Sum 1
Operating and Maintenance Procedures
Compilation and submission of 4 No. Operation &
Maintenance procedures for the LP Gas
installation. No 4
Carried to Collection
LPG INSTALLATION
JULY 2016 167
TRANSORANJE SCHOOL FOR THE DEAF, MECHANICAL BOQ
DEPARTMENT OF INFRASTRUCTURE DEVELOMENT
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
5.01 Any other items required for the successful
completion of the work but not included in this bill of
quantities. Please specify: Sum 1
5.03 Attendance and profits on tests
5.04 Allow for inspections and measurements as
5.05 required for the shop drawings and detailed
design of installation 1
5.06 Allow for monthly site meetings and managing of
project and for senior supervision by a qualified
person 1
5.07 Allow for samples and technical information 1
5.08 Allow for record drawings and operating instructions 1
5.09 Allow for transportation/travelling charges 1
5.10 Allow for maintenance and specialist maintenance
as specified 1
5.11 Allow for 12 months guarantee in terms of the
Document 1
5.12 Allow for all transport and rigging, lifting gear, cranes
etc, that may be required for moving of plant and
equipment setting out works 1
5.13 Allow for attendance on main contractor and for
switching off, removing all redundant items and
earthing to make supply safe and re-energise after
installation 1
AS-BUILT INFORMATION AND OPERATING AND
MAINTENANCE MANUALS
5.14 Obtaining of all available information, compiling,
reproducing and finalising three sets of as-built and
Operating and Maintenance manuals as specified in
Sb 05,01 and FF 03 and handing over to the Engineer 3
SHOP AND "AS BUILT" DRAWINGS
5.15 Allow for preparation of detailed, dimensioned shop
drawings and 'as built" drawings to the entire works
and all its components include for 3 copies of all
drawings for approval carring out corrections as
required by engineer No. 3
TRAINING
5.16 Presenting a training course for operators 1
5.17 Presenting training course for maintenance staff 1
Carried to Collection
LPG INSTALLATION
JULY 2016 168
TRANSORANJE SCHOOL FOR THE DEAF, MECHANICAL BOQ
DEPARTMENT OF INFRASTRUCTURE DEVELOMENT
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
INSPECTION OF SITE AND SITE MEASUREMENT
5.18 Allow for detailed inspection of the site,
site measurement and setting out as necessary to
carryout the contract and to provide detailed
dimensioned shop drawings of all works 1
EQUIPMENT SELECTIONS
required for approval before installing
OPERATION AND MAINTENANCE MANUALS
5.20, Provide Operating and Maintenance Manuals:
including "as built" drawings and equpment
selection information No. 3
SERVICE INSTALLATIONS AND CONNECTIONS
5.21 Electrical work: carry out complete connection from
local isolator, connect and gland off with water
proofed pvc sheathed copex and test electrical
installation to SANS 10142 and issue COC
certificates No. 0
5.22 Plumbing and drainage work: carry out complete
connection to water services and to drains, connect
SS flexible 15mm water connection installation and
with compression fitting for easy access- use
stainless steel for isolation of the ball valves(and
balls with viton seats)supply at each equipment item 0
5.23 Test the complete installation at full load and in
cooking mode and all associated components of
the installation in phases as the work proses as
work proceeds, demostrate and hand over to the
user; sign off at hand over as beingfully operational
and satisfactory Sum 1
Other
5.24 Any other items required for the successful
completion of the work but not included in this
bill of quantities. Please specify :
Carried to CollectionSUB-
TOTA SUB-TOTAL FOR LPG
CARRIED TO SUMMARY PAGE
LPG INSTALLATION
JULY 2016 169
TRANSORANJE SCHOOL FOR THE DEAF, MECHANICAL BOQ
DEAPARTMENT OF INFRASTRUCTURE DEVELOPMENT
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
HVAC INSTALLATIONS-M6
(a) This part of the BoQ must be priced by a specialist
HVAC sub-contractors to reduce failure due
financial risk.
(b) The main contractor shall provide a CV or brochure
for a specialist hvac sub-contractor before
work starts for approval by engineer.
( c) Allow for the specialist hvac sub-contractor
to visit the site and take measurements Sum 1
(d) Allow for production of factory shop drawings Sum 1
( e) Allow for submission of brochures for equipment to
be purchased before equipment is purchased
(f) Contractor must study carefully the DID, GP SQS
specifications, project specification, SANS
standards and the site before submitting
tenders.Contractors will be expected to submit
SABS Mark samples and SABS certificates before
purchasing all materials.
(g) All work should conform to the requirements of the
Standard Quality Specification for Ventilation
and Air Conditioning -DID-E/M6 latest revision
1 HVAC INSTALLATION
Space Heating -Air Conditioning GP/M6
Contractor must study the DID, GP SQS specifications,
ADMIN BUILDING
(Removals)
AB 100 (all mechanical equipment to be removed within
a Disconnect Wall mounted heaters No. 6
b Disconnect Air conditioning Units (Midwall Unit
Console Unit and any AC of any other type
including all piping and any other equipment related
c to such exiting installation. No. 3
d Disconnect Existing Ceiling Fans No. 3
e Disconnect electric geyser, piping and all the
existing associated accessories. No. 1
Carried to Collection
HVAC
JULY 2016 170
TRANSORANJE SCHOOL FOR THE DEAF, MECHANICAL BOQ
DEAPARTMENT OF INFRASTRUCTURE DEVELOPMENT
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
f Removal of Wall mounted heaters No. 6
g Removal of Air conditioning Units (Midwall Unit
Console Unit and any AC of any other type
including all piping and any other equipment related
h to such exiting installation. No. 3
i Removal of Existing Ceiling Fans No. 3
j Removal of electric geyser, piping and all the
existing associated accessories. No. 1
l Transport Wall mounted heaters to storage No. 6
m Transport Air conditioning Units (Midwall Unit
Console Unit and any AC of any other type
including all piping and any other equipment related
n to such exiting installation to storage No. 3
o Transport Existing Ceiling Fans to storage No. 3
l Transportelectric geyser, piping and all the
existing associated accessories to storage No. 1
2 (New Installations)
Supply, install, test and commission a VRV heat
recovery type air cooled air conditioning system,
including refrigerant piping, insulation and all other
necessary accessories to ensure a functional AC
All pipes to be run within trunking
Outdoor Units
2.01 20 kW Heating and Cooling Capacity
Supply No. 2
Install No. 2
2.02 Isolator at Condenser -Electrician to bring
power to isolator
Supply No. 1
install No. 1
2.03 1.1 kW Midwall Unit
Supply No. 1
Install No. 1
2.04 2.1 kW Midwall Unit
Supply No. 6
Install No. 6
2.05 2.3 kW Midwall Unit
Supply No. 2
Install No. 2
Carried to Collection
HVAC
JULY 2016 171
TRANSORANJE SCHOOL FOR THE DEAF, MECHANICAL BOQ
DEAPARTMENT OF INFRASTRUCTURE DEVELOPMENT
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
2.06 2.5 kW Midwall Unit
Supply No. 1
Install No. 1
2.07 4.0kW Midwall Unit
Supply No. 1
Install No. 1
2.08 4.5 kW Midwall Unit
Supply No. 2
Install No. 2
2.09 4.2 kW Ceiling Cassette
Supply No. 2
Install No. 2
2.1 8 Port BC Box
Supply No. 2
Install No. 2
2.11 REFRIGERATION PIPEWORK
Copper pipework
Supply m 250
Install m 250
PVC Draining Pipe φ 25
Supply m 100
Install m 100
Extra over for pipe fittings
Supply lot 1
Install lot 1
2.12 COMMUNICATION
Interconnecting cables
Brackets
Supply lot lot
Install lot lot
2.13 SUPPORT & PROTECTION
Cable tray for refrigerant piping and wiring
complete with all support,clamps,brackets etc
Supply lot lot
Install lot lot
2.14 POWER SUPPLY
Supply lot lot
Install lot lot
Carried to Collection
HVAC
JULY 2016 172
TRANSORANJE SCHOOL FOR THE DEAF, MECHANICAL BOQ
DEAPARTMENT OF INFRASTRUCTURE DEVELOPMENT
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
3 OFFICES
(Removals)
OFF 100 (all mechanical equipment to be removed within
3.01 STAFF ROOM
SR 100 (all mechanical equipment to be removed within
3.02 Disconnect Wall mounted heaters No. 6
3.03 Disconnect Air conditioning Units (Midwall Unit
3.04 Console Unit and any AC of any other type
including all piping and any other equipment related
to such exiting installation. No. 3
3.05 Disconnect Existing Ceiling Fans No. 3
3.06 Disconnect electric geyser, piping and all the
existing associated accessories. No. 1
3.07 Removal of Wall mounted heaters No. 6
3.08 Removal of Air conditioning Units (Midwall Unit
3.09 Console Unit and any AC of any other type
including all piping and any other equipment related
to such exiting installation. No. 3
3.1 Removal of Existing Ceiling Fans No. 3
3.11 Removal of electric geyser, piping and all the
existing associated accessories. No. 1
3.12 Transport Wall mounted heaters to storage No. 6
3.13 Transport Air conditioning Units (Midwall Unit
3.14 Console Unit and any AC of any other type
including all piping and any other equipment related
to such exiting installation to storage No. 3
3.15 Transport Existing Ceiling Fans to storage No. 3
3.16 Transportelectric geyser, piping and all the
existing associated accessories to storage No. 1
4 MEDIA CENTRE
MC 100 (all mechanical equipment to be removed within
4.01 Disconnect Air conditioning Units (Midwall Unit
Console Unit and any AC of any other type
including all piping and any other equipment related
to such exiting installation. No. 3
4.02 Disconnect Existing Ceiling Fans
existing associated accessories. No. 1
4.03 Removal of Air conditioning Units (Midwall Unit
4.04 Console Unit and any AC of any other type
including all piping and any other equipment related
to such exiting installation. No. 3
4.05 Removal of Existing Ceiling Fans No. 3
Carried to Collection
HVAC
JULY 2016 173
TRANSORANJE SCHOOL FOR THE DEAF, MECHANICAL BOQ
DEAPARTMENT OF INFRASTRUCTURE DEVELOPMENT
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
4.06 Transport Wall mounted heaters to storage No. 6
4.07 Transport Air conditioning Units (Midwall Unit
4.08 Console Unit and any AC of any other type
including all piping and any other equipment related
to such exiting installation to storage No. 3
4.09 Transport Existing Ceiling Fans to storage No. 3
OFFICES
(New Installations)
5 Supply, install, test and commission a VRV units
heat recovery type air cooled air conditioning system,
including refrigerant piping, insulation and all other
necessary accessories to ensure a functional AC
All pipes to be run within trunking
Outdoor Units
5.01 25 kW Heating and Cooling Capacity or approved
Supply No. 1
Install No. 1
5.02 15 kW Heating and Cooling Capacity or approved
Supply No. 1
Install No. 1
Indoor Units
5.03 2.6 kW Midwall Unit
Supply No. 5
Install No. 5
5.04 2.2 kW Midwall Unit
Supply No. 1
Install No. 1
5.05 1.7 kW Midwall Unit
Supply No. 1
Install No. 1
5.06 2.7 kW Midwall Unit
Supply No. 1
Install No. 1
5.07 3.4 kW Midwall Unit
Supply No. 2
Install No. 2
5.08 4.0kW Ceiling Cassette
Supply No. 1
Install No. 1
5.09 4.38kW Ceiling Cassette
Supply No. 1
Install No. 1
5.1 4.3 kW Midwall Unit
Supply No. 1
Install No. 1
Carried to Collection
HVAC
JULY 2016 174
TRANSORANJE SCHOOL FOR THE DEAF, MECHANICAL BOQ
DEAPARTMENT OF INFRASTRUCTURE DEVELOPMENT
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
5.11 8 Port BC Box
Supply No. 2
Install No. 2
REFRIGERATION PIPEWORK
5.12 Copper pipework
Supply m 250
Install m 250
5.13 PVC Draining Pipe φ 25
Supply m 100
Install m 100
5.14 Extra over for pipe fittings
Supply lot 1
Install lot 1
COMMUNICATION
5.15 Interconnecting cables
Brackets
Supply lot lot
Install lot lot
SUPPORT & PROTECTION
5.16 Cable tray for refrigerant piping and wiring
complete with all support,clamps,brackets etc
Supply lot lot
Install lot lot
5.17 POWER SUPPLY
Supply lot lot
Install lot lot
Carried to Collection
HVAC
JULY 2016 175
TRANSORANJE SCHOOL FOR THE DEAF, MECHANICAL BOQ
DEAPARTMENT OF INFRASTRUCTURE DEVELOPMENT
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
KITCHEN VENTILATION
6 KITCHEN CANOPY
(Removals)
All mechanical equipment to be removed including
all electrical wiring6.01 Disconnect and Remove extraction fans No. 6
6.02 Transport removed extraction fans to storage No. 6
200m away
6.03 Disconnect and Remove Kitchen Canopy No. 3
6.04 Transport removed kitchen Canopy to storage No. 3
200m away
6.05 Disconnect and Remove canopy ductwork No. 3
6.06 Transport removed Canopy ductwork to No. 3
storage 200m away
New Installations
6.07 Supply and install canopy 6400 x 2400 with roof fan,
attenuators and S/S 304 ductwork through roof.
installed complete with roof pod, weather skirt, GMS
steel support work and roof discharge to
atomsphere c/w start-stop control panel for fans
supply No. 1
install No. 1
EXTRACTION FANS
6.08 Supply, install, test and commission axial flow .
kitchen canopy air extract fan c/w mating flange
,mounting feet,antivibration mounts,P1.5D Silencer
flexible connection
Air quantity: 2300l/s
supply No 2
install No 2
MAKE UP AIR SUPPLY FANS
6.09 Supply, install, test and commission axial flow .
make up air supply fan c/w mating flange
,mounting feet,antivibration mounts,P1.5D Silencer
flexible connection
Air quantity: 3680l/s
supply No 1
install No 1
Carried to Collection
HVAC
JULY 2016 176
TRANSORANJE SCHOOL FOR THE DEAF, MECHANICAL BOQ
DEAPARTMENT OF INFRASTRUCTURE DEVELOPMENT
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
Ducting
6.1 Supply and install Circular black steel sheetmetal
ductwork for Kitchen canopy air extract system,
including transformation pieces, bends, tees,
spigots, etc installed on the Kitchen roof and in the
Kitchen,and make up air ducting, manufactured in
accordance with SANS1238:2005 & SANS 10173:2003 `
as amended, including all necessary supports,fixing,
brackets, flexible connections, etc, all as may be
shown on the mechanical ventilation drawing.
304SS ducting, all transforms, fittings, flanges fixing to
fans and canopy c/w discharge cowls, supports,
weather proofing etc
6.11 1240X 550mm
Supply m 5
install m 5
6.12 900x400mm
Supply m 12
install m 12
6.13 580X 350mm
Supply m 4
install m 4
6.14 650X 550mm
Supply m 6
install m 6
6.15 650X450mm
Supply m 6
install m 6
6.16 650X350mm
Supply m 3
install m 3
6.16 550X450mm
Supply m 4
install m 4
6.16 350X350mm
Supply m 6
install m 6
Duct Reducers
6.17 900X400mm to 840X350mm
Supply No 1
Carried to Collection
HVAC
JULY 2016 177
TRANSORANJE SCHOOL FOR THE DEAF, MECHANICAL BOQ
DEAPARTMENT OF INFRASTRUCTURE DEVELOPMENT
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
6.18 840x350mm -600x350mm
Supply No 1
install No 1
6.19 600x350mm-350x350mm
Supply No 1
install No 1
6.2 1240x550mm-750x550mm
Supply No 1
install No 1
6.2 750x550mm-650x550mm
Supply No 1
install No 1
6.2 650x550-650x450
Supply No 1
install No 1
6.2 650x450mm-550x450mm
Supply No 1
install No 1
6.2 550x450mm-350x350mm
Supply No 1
install No 1
Supply Air Grilles
6.21 Supply and Install drum louvers
Flow -400l/s
Supply No 9
install No 9
6.21b Allow for demolition of walls and making right for new lot sum
installations
Carried to Collection
HVAC
JULY 2016 178
TRANSORANJE SCHOOL FOR THE DEAF, MECHANICAL BOQ
DEAPARTMENT OF INFRASTRUCTURE DEVELOPMENT
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
LAUNDRY EXTRACTION
Removal of existing extraction fan and transporting
to storage No 1
6.22 Supply and install wall mounted extraction fan
Flow rate =550l/s
Supply No 1
6.23 install No 1
WORKSHOP 105 EXTRACTION
Removal of existing extraction fans and transporting
to storage No 4
6.24 Replacement of dust extraction fan and with same
Duty as existing dust extraction fan
DCE Unimaster MT100L28-2 or equivalent
6.25 3.3kW 4.3HP
Rev - 3179 rev/min
Supply No 1
install No 1
Dust Extraction system ductwork
Diameter 150mm
Supply m 45
6.26 install m 45
WORKSHOP 206 EXTRACTION
Replacement of Extract fan
Flow rate =240 l/s
6.27 Supply No 2
install No 2
6.28 HOSPITALITY CLASSROOM
600mm CHIMNEY EXTRACTOR STAINLESS
STEEL
Supply new a domestic extraction canopy for the
hotplate installed in the work room in Block E-
Library complete with ducting to above roof height,
grease filters light, upper chimney, lower chimney,
fan and light switches
flow rate- 600m3/h
Input Power- 0.16KW
Width-600mm
Depth- 480mm
Minimum Height- 1040mm
Maximum Height-6800mm
supply No. 6
install No. 6
Carried to Collection
HVAC
JULY 2016 179
TRANSORANJE SCHOOL FOR THE DEAF, MECHANICAL BOQ
DEAPARTMENT OF INFRASTRUCTURE DEVELOPMENT
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
6.29 BAKERY
Supply and install canopy 6400 x 2400 with roof fan,
attenuators and S/S 304 ductwork through roof.
installed complete with roof pod, weather skirt, GMS
steel support work and roof discharge to
atomsphere c/w start-stop control panel for fans
supply No. 1
install No. 1
6.3 EXTRACTION FANS
Supply, install, test and commission axial flow .
kitchen canopy air extract fan c/w mating flange
,mounting feet,antivibration mounts,P1.5D Silencer
flexible connection
Air quantity: 2300l/s
supply No 2
install No 2
TRAINING
Presenting a training course for operators 1
Presenting training course for maintenance staff 1
7.08
INSPECTION OF SITE AND SITE MEASUREMENT
Allow for detailed inspection of the site,site
measurement and setting out as necessary to carry
7.09 out the contract and to provide detailed dimensioned
shop drawings of all works 1
EQUIPMENT SELECTIONS
Provide detailed selections and samples as
required for approval before installing Sum 1
7.1
OPERATION AND MAINTENANCE MANUALS
Provide Operating and Maintenance Manuals:
including "as built" drawings and equpment
7.11 selection information No. 3
Carried to Collection
HVAC
JULY 2016 180
TRANSORANJE SCHOOL FOR THE DEAF, MECHANICAL BOQ
DEAPARTMENT OF INFRASTRUCTURE DEVELOPMENT
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
SERVICE INSTALLATIONS AND CONNECTIONS
Electrical work: carry out complete connection from
local isolator, connect and gland off with water
7.12 proofed pvc sheathed copex and test electrical
installation to SANS 10142 and issue COC
certificates No. 6
Plumbing and drainage work: carry out complete
connection to water services and to drains, connect
SS flexible 15mm water connection installation and
with compression fitting for easy access- use
stainless steel for isolation of the ball valves(and
balls with viton seats)supply at each equipment item 3
Carried to Collection
Other
Any other items required for the successful
completion of the work but not included in this
bill of quantities. Please specify :
SUB-TOTAL FOR HVAC
CARRIED TO SUMMARY PAGE
HVAC
JULY 2016 181
TRANSORANJE SCHOOL FOR THE DEAF, MECHANICAL BOQ
DEPARTMENT OF INFRASTRUCTURE DEVELOPMENT
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
REFRIGERATION INSTALLATIONS-M7
(a) This part of the BoQ must be priced by a specialist
refrigeration sub-contractors to reduce failure due
financial risk.
(b) The main contractor shall provide a CV or brochure
for a specialist refrigeration sub-contractor before
work starts for approval by engineer.
( c) Allow for the specialist refrigeration sub-contractor
to visit the site and take measurements Sum 1
(d) Allow for production of factory shop drawings Sum 1
( e) Allow for submission of brochures and datasheets
for equipment to be purchased before purchasing
Contractor must study carefully the DID, GP SQS
specifications, project specification, SANS
standards and the site before submitting
tenders.Contractors will be expected to submit
SABS Mark samples and SABS certificates before
purchasing all materials.
All work should conform to the requirements of the
Standard Quality Specification for Refrigeration
Installations -DID-E/M7 latest revision
Refrigeration; GP/M7
New Cold Room Complete
1.0 Cold room 2950W refrigeration package plant
and evaporator installation complete or approved
1.1 Supply and install cold room chromadeck enclosure
3060x 2290x 2400 high complete as specified with
lights, swing door, fully sealed and vapour proof c/w
condensate drains
1.2 The cold room should be complete with shelving
Set temperature should be between 1 and 4 deg
Estimated design capacity is 1000kg fruit and
vegetable
1.3 Supply No. 1
1.4 Install No. 1
1.5 Supply and install blower coil
1.6 Supply No. 1
1.7 Install No. 1
1.8 Supply and install cold room vapour proof light
fittings (2 x 28W vapour)
1.9 Supply No. 4
1.10 Install No. 4
Carried to Collection
REFRIGERATION
JULY 2016 182
TRANSORANJE SCHOOL FOR THE DEAF, MECHANICAL BOQ
DEPARTMENT OF INFRASTRUCTURE DEVELOPMENT
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
2.0 Supply and install complete electrical installation
and control DB for cold room
2.1 Supply No. 1
2.2 Install No. 1
3.0 Supply and install temperature gauge and high
temperature flashing allarm
3.1 Supply No. 2
3.2 Install No. 2
4.0 Supply and install cambro shelving 1220(L)
x 460(W) No. 6
4.2 Supply and install cambro shelving 960(L)
x 460(W) No. 2
5.0 Traveling cost of technicians Sum 1
5.1 Test and commission entire system Sum 1
6.0 New Freezer room Complete
Cold room 4200W refrigeration package plant
and evaporator installation complete or approved
Freezer room -150mm Polystyrene
Size -3060x 2290x 2400
Door: STD Hinge Door
Finish: White Chromadeck with alum angles
6.1 Supply No 1
6.2 Install No 1
6.3 Energy Saving ZX Refrigeration Pack &
Blower Coil
6.4 Supply No 1
6.5 Install No 1
6.6 Copper pipe, spares & gas
6.7 Supply No Sum
6.8 Install No Sum
6.9 Electrical
6.10 Supply No Sum
6.11 Install No Sum
Allow for Freezer room and Cold room hire during
decommissioning period of existing ones Lot Sum
Carried to Collection
REFRIGERATION
JULY 2016 183
TRANSORANJE SCHOOL FOR THE DEAF, MECHANICAL BOQ
DEPARTMENT OF INFRASTRUCTURE DEVELOPMENT
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
TRAINING
7.0 Development of syllabus for training of
maintenance staff Sum Sum
7.1 Presenting a training course for maintenace staff No. 1
7.2 Testing and commission of the completed
installation Item 1
7.3 Attendance and profits on tests
7.4 Credit for redundant materials and equipment
7.5 Allow for inspections and measurements required
for shop drawings and detailed design of installation 1
7.6 Allow for record drawings and operating instructions
7.7 Allow for transportation/travelling charges 1
7.8Allow for maintenance and specialist maintenance as
specified
7.1 Allow for 12 months guarantee in terms of the
Document 1
7.12 Allow for all transport and rigging, lifting gear, cranes
etc. that may be required for moving of plant and
equipment setting out works Sum 1
7.13 Allow for attendance on main contractor and for
switchingoff, removing all redundant items and
earthing to make supply safe and re-energise
after installation 1
AS-BUILT INFORMATION AND OPERATING AND
MAINTENANCE MANUALS
7.14 SHOP AND "AS BUILT" DRAWINGS
Allow for preparation of detailed, dimensioned shop
drawings and 'as built" drawings to the entire works
and all its components include for 3 copies of all
drawings for approval carring out corrections as
required by engineer No. 3
Carried to Collection
REFRIGERATION
JULY 2016 184
TRANSORANJE SCHOOL FOR THE DEAF, MECHANICAL BOQ
DEPARTMENT OF INFRASTRUCTURE DEVELOPMENT
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
TRAINING
7.16 Presenting a training course for operators No 1
7.17 Presenting training course for maintenance staff No 1
INSPECTION OF SITE AND SITE MEASUREMENT
7.18 Allow for detailed inspection of the site,site
measurement and setting out as necessary to carry
out the contract and to provide detailed dimensioned
shop drawings of all works 1
EQUIPMENT SELECTIONS
7.19 Provide detailed selections and samples as
required for approval before installing Sum 1
including "as built" drawings and equpment
OPERATION AND MAINTENANCE MANUALS
7.20 Provide Operating and Maintenance Manuals:
including "as built" drawings and equpment
selection information No. 3
SERVICE INSTALLATIONS AND CONNECTIONS
7.21 Electrical work: carry out complete connection from
local isolator, connect and gland off with water
proofed pvc sheathed copex and test electrical
installation to SANS 10142 and issue COC
certificates No. 1
7.22 Plumbing and drainage work: carry out complete
connection to water services and to drains, connect
SS flexible 15mm water connection installation and
with compression fitting for easy access- use
stainless steel for isolation of the ball valves(and
balls with viton seats)supply at each equipment item 2
Other
7.23 Any other items required for the successful
completion of the work but not included in this
bill of quantities. Please specify :
Carried to Collection
CARRIED TO SUMMARY PAGE
SUB-TOTAL FOR REFRIGERATION
REFRIGERATION
JULY 2016 185
TRANSORANJE SCHOOL FOR THE DEAF, MECHANICAL BOQ
DEPARTMENT OF INFRASTRUCTURE DEVELOPMENT
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
KITCHEN EQUIPMENT INSTALLATIONS-M8
(a) This part of the BoQ must be priced by a specialist
Commercial kitchen sub-contractors to reduce failure
due
financial risk.
(b) The main contractor shall provide a CV or brochure
for a specialist commercial kitchen sub-contractor
before
work starts for approval by engineer.
( c)Allow for the specialist commercial kitchen sub-
contractor
to visit the site and take measurements Sum 1
(d) Allow for production of factory shop drawings Sum 1
( e) Allow for submission of brochures and datasheet for
equipment to be purchased before purchasing
Contractor must study carefully the DID, GP SQS
specifications, project specification, SANS
standards and the site before submitting
tenders.Contractors will be expected to submit
SABS Mark samples and SABS certificates before
purchasing all materials.CD available in DID offices
EQUIPMENT; GP/M8 (1)
1.0 Supply and installation of kitchen equipment is to be
carried out in conjuction with the main contractor.
The contractor is to present a detailed programe for
the scheduled installation of new equipment
1.1 The specialist kitchen contractor shall submit
detailed shop drawings depicting the proposed
layout of all new equipment associated services for
approval before ordering any new equipment for
services installation by others
Carried to Collection
EQUIPMENT- KITCHEN
JULY 2016
TRANSORANJE SCHOOL FOR THE DEAF, MECHANICAL BOQ
DEPARTMENT OF INFRASTRUCTURE DEVELOPMENT
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
Main Kitchen
Removals (kitchen)
Old redundant kitchen Equipment must remain
2.0 Disconnect power and existing Hydroboils No. 2
2.1 Disconnect power to existing Boiling Pan No. 1
2.2 Disconnect Gas Stove No. 1
2.3 Disconnect Tilting Pan No. 1
2.4 Disconnect power to solid Top Stove with Oven No. 1
2.5 Disconnect power to Wall Mounted Heaters No. 14
2.6 Disconnect All Existing LP Gas infrastructure No. 1
2.7 Disconnect existing Extraction Fans No. 2
3.0 Removal of existing Hydroboils No. 2
3.1 Removal of existing Boiling Pan No. 1
3.2 Removal of existing Gas Stove No. 1
3.3 Removal of existing Tilting Pan No. 1
3.4 Removal of existing solid Top Stove with Oven No. 1
3.5 Removal of existing Wall Mounted Heaters No. 14
3.6 Removal of existing All Existing LP Gas
infrastructure No. 1
3.7 Removal of existing Extraction Fans No. 2
4.0 Transport existing Hydroboils to storage No. 2
4.1 Transport existing Boiling Pan to storage No. 1
4.2 Transport existing Gas Stove to storage No. 1
4.3 Transport existing Tilting Pan to storage No. 1
4.4 Transport existing solid Top Stove with Oven to
storage No. 1
4.5Transport existing Wall Mounted Heaters to storage
No. 14
4.6 Transport existing All Existing LP Gas
infrastructure to storage No. 1
4.7 Transport existing Extraction Fans to storage No. 2
Carried to Collection
EQUIPMENT- KITCHEN
JULY 2016
TRANSORANJE SCHOOL FOR THE DEAF, MECHANICAL BOQ
DEPARTMENT OF INFRASTRUCTURE DEVELOPMENT
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
NEW INSTALLATION KITCHEN
installed complete, connected to water, drainage
requirements, and power complete to manufactures
operating requirements
Dish washer Hood Type(12,5 kW, 380 V, 3ph)
5.0 Supply No. 1
5.1 Install No. 1
5.2Double Stainless Dirties Table with Scraphole
(1650x650)
5.3 Supply No. 1
5.4 Install No. 1
5.5 Stainless Steel Table (1800x650x915)
5.6 Supply No. 2
5.7 Install No. 2
5.8 Stainless Steel Table no SBR (1800x650x915)
5.9 Supply No. 5
5.10 Install No. 5
5.11 Stainless Steel Table with SBR (1400x650x915)
5.12 Supply No. 3
5.13 Install No. 3
5.14 S/Steel Bain Marie with Hot Closet
5.15 (6kW, 380V, 3ph)
Supply No. 2
5.16 Install No. 2
5.17 Double Bowl Pot Sink(2300x 650 x915)
5.18 Supply No. 2
5.19 Install No. 2
5.20 3 Solid Top Range with Oven (18KW, 400, 3ph)
5.21 Supply No. 1
5.22 Install No. 1
5.23 Mobile Food Warmer ( Low Height) (1kW, 220V)
5.24 Supply No. 2
5.25 Install No. 2
5.26 40L Tilting Frying Pan(Electrical)(7.5kW, 3ph)
5.27 Supply No. 1
5.28 Install No. 1
5.29 80L Tilting Frying Pan(Gas)(72000KJ/hr)
5.30 Supply No. 1
5.31 Install No. 1
5.32 Pot Rack(1790x600) Tier
5.33 Supply No. 3
5.34 Install No. 3
5.35 2 Tier Stainless Steel Wall Mounted Shelfing
5.36 (1800x350)
Supply No. 3
5.37 Install No. 3
5.38 Turbo Fryer(Electrical)
5.39 Supply No. 2
5.40 Install No. 2
5.41
Carried to Collection
EQUIPMENT- KITCHEN
JULY 2016
TRANSORANJE SCHOOL FOR THE DEAF, MECHANICAL BOQ
DEPARTMENT OF INFRASTRUCTURE DEVELOPMENT
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
Turbo Fryer(Gas)(10000kJ/H) 10L
5.42 Supply No. 1
5.43 Install No. 1
5.44 Imperial 6 Burner (203 kJ/H)
5.45 Supply No. 1
5.46 Install No. 1
5.47 225 Boiling Pan (106KJ/H)
Supply No. 1
5.49 Install No. 1
5.50 Confectionary Mixer (1.5 KW, 400V, 3ph)
5.51 Supply No. 1
5.52 Install No. 1
5.53 10 Pan Convection Oven (Electric)
5.54 (10.6 KW, 400V, 3ph)
Supply No. 1
5.55 Install No. 1
5.56 50 liter Hydroboil water heater (3x2,4 KW, 380V)
5.57 Supply No. 2
5.58 Install No. 2
5.59
Stainless Steel Grease Traps
6.0 Herbish' HB GT 700' stainless steel grease trap
6.1 including handles, lids, perforated plates and baskets. No.
Supply No. 2
6.2 Install No. 2
6.3
'Herbish' HB GT 500' stainless steel grease trap
6.4
including handles, lids, perforated plates and baskets.
Supply No. 2
6.5 Install No. 2
6.6
Schedule of new staffroom kitchen equipment,
supplied,installed complete, connected to water,
drainagerequirements, and power complete to
manufactures
10 liter Hydroboil water heater (2,4 KW, 220V)
7.0 Supply No. 1
7.1 Install No. 1
7.2
Industrial type three burner gas cookers
7.3 It must be of a steel construction with good
corrosion protection. Each burner must have
regulating valves.
Supply No. 2
7.4 Install No. 2
7.5
Carried to Collection
EQUIPMENT- KITCHEN
JULY 2016
TRANSORANJE SCHOOL FOR THE DEAF, MECHANICAL BOQ
DEPARTMENT OF INFRASTRUCTURE DEVELOPMENT
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
HOME ECONOMICS
Supply and install 21 of 4 plates gas cooker hobs
7.6 Supply No. 21
7.7 Install No. 21
7.8
Testing and commission of the completed
8.0 installation Item 1
8.6 Allow for transportation/travelling charges 1
8.7 Allow for maintenance and specialist maintenance
as specified
8.9 Allow for all transport and rigging, lifting gear, cranes
etc. that may be required for moving of plant and
equipment setting out works Sum 1
Allow for attendance on main contractor and for
8.10 switching off, removing all redundant items and
earthing to make supply safe and re-energise
after installation 1
AS-BUILT INFORMATION AND OPERATING AND
MAINTENANCE MANUALS
Obtaining of all available information, compiling,
Carried to Collection
EQUIPMENT- KITCHEN
JULY 2016
TRANSORANJE SCHOOL FOR THE DEAF, MECHANICAL BOQ
DEPARTMENT OF INFRASTRUCTURE DEVELOPMENT
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
SHOP AND "AS BUILT" DRAWINGS
8.12
Allow for preparation of detailed, dimensioned shop
drawings and 'as built" drawings to the entire works
and all its components include for 3 copies of all
drawings for approval carring out corrections as
required by engineer No. 3
TRAINING
Presenting a training course for operators Sum 1
8.13 Presenting training course for maintenance staff Sum 1
8.14
INSPECTION OF SITE AND SITE MEASUREMENT
Allow for detailed inspection of the site, site
8.15 measurement and setting out as necessary to carry
out the contract and to provide detailed dimensioned
shop drawings of all the works 1
EQUIPMENT SELECTIONS
Provide detailed selections and samples as
8.17 required for approval before installing Sum 3
Carried to Collection
EQUIPMENT- KITCHEN
JULY 2016
TRANSORANJE SCHOOL FOR THE DEAF, MECHANICAL BOQ
DEPARTMENT OF INFRASTRUCTURE DEVELOPMENT
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
Other
Any other items required for the successful
7.23 completion of the work but not included in this
bill of quantities. Please specify :
Carried to Collection
SUB-TOTAL FOR EQUIPMENT
CARRIED TO SUMMARY PAGE
EQUIPMENT- KITCHEN
JULY 2016
TRANSORANJE SCHOOL FOR THE DEAF, MECHANICAL BOQ
DEPARTMENT OF INFRASTRUCTURE DEVELOPMENT
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
LAUNDRY EQUIPMENT INSTALLATIONS-M8
(a) This part of the BoQ must be priced by a specialist
Laundry equipment sub-contractors to reduce failure
due financial risk.
(b) The main contractor shall provide a CV or brochure
for a specialist laundry equipment sub-contractor
before work starts for approval by engineer.
( c) Allow for the specialist laundry sub-contractor
to visit the site and take measurements Sum 1
(d) Allow for production of factory shop drawings Sum 1
( e) Allow for submission of brochures and Datasheets for
equipment to be purchased before purchasing
Contractor must carefully study the DID, GP SQS
specifications, project specification, SANS
standards and the site before submitting
tenders.Contractors will be expected to submit
SABS Mark samples and SABS certificates before
purchasing all materials.
LAUNDRY EQUIPMENT GP/M8(2)
Contractor must study the DID, GP SQS specifications,
project specification, SANS standards and the site carefully
before submitting tenders. Contractors will be expected to
submit SABS Mark samples and SABS certificates before
purchasing all materials.
(Removals)
LH (all mechanical equipment to be removed within these
Disconnect electric geyser, piping and all the existing associated accessories. No. 1
Disconnect Existing Washing Machine No. 1
Disconnect Existing Industrial Spinner/Drier No. 3
Disconnect Existing Industrial Washing Machine No. 2
Disconnect Existing Extraction Fan No. 1
Removal of electric geyser, piping and all the existing
associated accessories. No. 1
Removal of Existing Washing Machine No. 1
Removal of an Existing Industrial Spinner/Drier No. 3
Removal of Existing Industrial Washing Machine No. 2
Removal of Existing Extraction Fan No. 1
Carried to Collection
EQUIPMENT-LAUNDRY
JULY 2016 193
TRANSORANJE SCHOOL FOR THE DEAF, MECHANICAL BOQ
DEPARTMENT OF INFRASTRUCTURE DEVELOPMENT
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
Transport of electric geyser, piping and all the existing
associated accessories to storage No. 1
Transport Existing Washing Machine to storage No. 1
Transport Existing Industrial Spinner/Drier to storage No. 3
Transport Existing Industrial Washing Machine to storage No. 2
Transport Existing Extraction Fan to storage No. 1
Supply, install, test and commission including rigging
1.0 Fixed Iron Board Omega 2000
Supply No. 6
install No. 6
Roller Iron 3ph/60A 11kW
Supply No. 1
install No. 1
Top Loader 35 kg
Supply No. 2
install No. 2
Folding Table 1650x750
Supply No. 2
install No. 2
Slow/Medium Speed Washer 30 kg
Supply No. 2
install No. 2
12 Tumble Drier 40 kg
Supply No. 1
install No. 1
13 Portable Iron 1ph/380V 2000W
Supply No. 7
14 Concrete Plinth
Strength: 250kpa/m2
Size: 2500x2000
Supply No. 1
install No. 1
Testing and Commissioning
15 Allow for testing of equipments and training of the end Sum 1
Carried to Collection
EQUIPMENT-LAUNDRY
JULY 2016 194
TRANSORANJE SCHOOL FOR THE DEAF, MECHANICAL BOQ
DEPARTMENT OF INFRASTRUCTURE DEVELOPMENT
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
Gurantee and Maintenance
16 Provision of Guarantee of equipment and 12-month Sum 1
Operating and Maintenance Procedures
17 Compilation and submission of Operation & Maintenance No 4
Other
18 Any other items required for the successful completion of Sum
5.1 Any other items required for the successful
completion of the work but not included in this bill of
quantities. Please specify: Sum 1
5.2 Testing and commission of the completed laundry
installation Item 1
5.3 Attendance and profits on tests
5.4 Allow for inspections and measurements as
5.5 required for the shop drawings and detailed
design of installation 1
5.6 Allow for monthly site meetings and managing of
project and for senior supervision by a qualified
person 1
5.7 Allow for samples and technical information 1
5.8 Allow for record drawings and operating instructions 1
5.9 Allow for transportation/travelling charges 1
5.10 Allow for maintenance and specialist maintenance
as specified 1
5.11 Allow for 12 months guarantee in terms of the
Document 1
5.12 Allow for all transport and rigging, lifting gear, cranes
etc, that may be required for moving of plant and
equipment setting out works 1
5.13 Allow for attendance on main contractor and for
switching off, removing all redundant items and
earthing to make supply safe and re-energise after
installation 1
AS-BUILT INFORMATION AND OPERATING AND
MAINTENANCE MANUALS
5.14 Obtaining of all available information, compiling,
reproducing and finalising three sets of as-built and
Operating and Maintenance manuals as specified in
Sb 05,01 and FF 03 and handing over to the Engineer 3
Carried to Collection
EQUIPMENT-LAUNDRY
JULY 2016 195
TRANSORANJE SCHOOL FOR THE DEAF, MECHANICAL BOQ
DEPARTMENT OF INFRASTRUCTURE DEVELOPMENT
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
SHOP AND "AS BUILT" DRAWINGS
5.15 Allow for preparation of detailed, dimensioned shop
drawings and 'as built" drawings to the entire works
and all its components include for 3 copies of all
drawings for approval carring out corrections as
required by engineer No. 3
TRAINING
5.16 Presenting a training course for operators 1
5.17 Presenting training course for maintenance staff 1
INSPECTION OF SITE AND SITE MEASUREMENT
5.18 Allow for detailed inspection of the site,
site measurement and setting out as necessary to
carryout the contract and to provide detailed
dimensioned shop drawings of all works 1
EQUIPMENT SELECTIONS
5.19 Provide detailed selections and samples as
required for approval before installing
OPERATION AND MAINTENANCE MANUALS
5.20, Provide Operating and Maintenance Manuals:
selection information No. 3
SERVICE INSTALLATIONS AND CONNECTIONS
5.21 Electrical work: carry out complete connection from
local isolator, connect and gland off with water
proofed pvc sheathed copex and test electrical
installation to SANS 10142 and issue COC
certificates
5.23 Test the complete installation at full load and in
cooking mode and all associated components of
the installation in phases as the work proses as
work proceeds, demostrate and hand over to the
user; sign off at hand over as beingfully operational
and satisfactory Sum 1
Carried to Collection
EQUIPMENT-LAUNDRY
JULY 2016 196
TRANSORANJE SCHOOL FOR THE DEAF, MECHANICAL BOQ
DEPARTMENT OF INFRASTRUCTURE DEVELOPMENT
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
Other
5.24 Any other items required for the successful
completion of the work but not included in this
bill of quantities. Please specify :
Carried to CollectionSUB-
TOTA SUB-TOTAL FOR LAUNDRY EQUIPMENT
EQUIPMENT-LAUNDRY
JULY 2016 197
TRANSORANJE SCHOOL FOR THE DEAF, MECHANICAL BOQ
DEPARTMENT OF INFRASTRUCTURE DEVELOPMENT
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
WORKSHOP INSTALLATIONS-M8
(a) This part of the BoQ must be priced by a specialist
sub-contractors to reduce failure due financial risk
(b) The main contractor shall provide a CV or brochure
for a specialist sub-contractor before work starts
for approval by engineer.
( c) Allow for the specialist sub-contractor to visit the site
and take measurements Sum 1
(d) Allow for production of factory shop drawings Sum 1
( e) Allow for submission of brochures and datasheets for
equipment to be purchased before purchasing
Contractor must study carefully the DID, GP SQS
specifications, project specification, SANS
standards and the site before submitting
tenders.Contractors will be expected to submit
SABS Mark samples and SABS certificates before
purchasing all materials.
LAUNDRY EQUIPMENT GP/M8(2)
Contractor must study the DID, GP SQS specifications,
project specification, SANS standards and the site carefully
before submitting tenders. Contractors will be expected to
submit SABS Mark samples and SABS certificates before
purchasing all materials.
(Removals)
LH (all mechanical equipment to be removed within these
area are excluding striping of electrical wiring). The details
of the equipments to be removed are to be clarified at
Compulsory Site Inspection and the pricing must include all
the necessary work to be done. (All Machine Weights to be
taken into consideration)
Carried to Collection
EQUIPMENT- OTHER
JULY 2016 198
TRANSORANJE SCHOOL FOR THE DEAF, MECHANICAL BOQ
DEPARTMENT OF INFRASTRUCTURE DEVELOPMENT
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
WORKSHOP 100
Disconnect electric geyser, piping and all the existing
associated accessories. No. 1
Disconnect Existing Wall Mounted Heaters No. 6
Disconnect Existing Pedestal Drilling Machings No. 4
Disconnect Existing work benches No. 6
Disconnect Existing Pedestal Saw No. 2
Disconnect Existing Pedestal Grinder No. 1
Disconnect Existing Saw Benches No. 4
Disconnect all other machines No. 3
Disconnect all extraction system including ducting
geyser No. 1
Removal of electric geyser, piping and all the
existing associated accessories. No. 1
Removal of Existing Wall Mounted Heaters No. 6
Removal of Existing Pedestal Drilling Machings No. 4
Removal of Existing work benches No. 6
Removal of Existing Pedestal Saw No. 2
Removal of Existing Pedestal Grinder No. 1
Removal of Existing Saw Benches No. 4
Removal of all other machines No. 3
removal of all extraction system including ducting
and all other related equipment No. 1
Transport of electric geyser, piping and all the
existing associated accessories to storage No. 1
Transport of Existing Wall Mounted Heaters to
storage No. 6
Transport Existing Pedestal Drilling Machings
to storage No. 4
Transport Existing work benches to storage No. 6
Transport Existing Pedestal Saw to storage No. 2
Transport Existing Pedestal Grinder to storage No. 1
Transport Existing Saw Benches to storage No. 4
Transport all other machines to storage No. 3
Transport of all extraction system including ducting
and all other related equipment to storage No. 1
Carried to Collection
EQUIPMENT- OTHER
JULY 2016 199
TRANSORANJE SCHOOL FOR THE DEAF, MECHANICAL BOQ
DEPARTMENT OF INFRASTRUCTURE DEVELOPMENT
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
Transport Existing Pedestal Drilling Machings
to workshop No. 4
Transport Existing work benches to workshop No. 6
Transport Existing Pedestal Saw to workshop No. 2
Transport Existing Pedestal Grinder to workshop No. 1
Transport Existing Saw Benches to workshop No. 4
Transport all other machines to workshop No. 3
Reconnect Existing Pedestal Drilling Machings No. 4
Reconnect Existing work benches No. 6
Reconnect Existing Pedestal Saw No. 2
Reconnect Existing Pedestal Grinder No. 1
Reconnect Existing Saw Benches No. 4
Reconnect all other machines No. 3
Carried to Collection
EQUIPMENT- OTHER
JULY 2016 200
TRANSORANJE SCHOOL FOR THE DEAF, MECHANICAL BOQ
DEPARTMENT OF INFRASTRUCTURE DEVELOPMENT
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
WORKSHOP 200
Disconnect electric geyser, piping and all the existing
associated accessories. No. 1
Disconnect Existing Arc Welding Maching No. 6
Disconnect Existing Other Welding Machines No. 2
Disconnect Existing Centre Lathe No. 2
Disconnect Existing Drilling Machines No. 3
Disconnect Existing galentine Machines No. 1
Disconnect all other machines No. 1
Disconnect all extraction system including ducting
and all other related equipment No. 6
Disconnect and make safe existing hot water
geyser No. 1
Removal of electric geyser, piping and all the
existing associated accessories. No. 1
Removal of Existing Arc Welding Machines No. 6
Removal of Existing Other Welding Machines No. 2
Removal of Existing Centre Lathe No. 2
Removal of Existing Pedestal Drilling Machines No. 3
Removal of Existing Gilantine Machines No. 1
Removal of all other machines No. 1
removal of all extraction system including ducting
and all other related equipment No. 1
existing associated accessories to storage No. 1
Transport of Existing arc welding machine to
storage No. 6
Transport Existing other welding machine
to storage No. 2
Transport Existing Centre Lathe to storage No. 2
Transport Existing Pedestal Drilling Machine to
storage No. 3
Transport Existing Gilantine Machine to storage No. 1
Transport Existing Saw Benches to storage No. 1
Transport all other machines to storage No. 1
Transport of all extraction system including ducting
and all other related equipment to storage No. 6
Carried to Collection
EQUIPMENT- OTHER
JULY 2016 201
TRANSORANJE SCHOOL FOR THE DEAF, MECHANICAL BOQ
DEPARTMENT OF INFRASTRUCTURE DEVELOPMENT
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
Transport Existing Pedestal Drilling Machinge
to workshop No. 3
Transport existing arc welding machine to workshop No. 6
Transport other arc welding machine to workshop No. 2
Transport Existing centre lather to workshop No. 2
Transport Existing Gilantine to workshop No. 1
Transport all other machines to workshop No. 1
Reconnect Existing Arc Welding Maching No. 6
Reconnect Existing Other Welding Machines No. 2
Reconnect Existing Centre Lathe No. 2
Reconnect Existing Drilling Machines No. 3
Reconnect Existing galentine Machines No. 1
Reconnect all other machines No. 1
Carried to Collection
EQUIPMENT- OTHER
JULY 2016 202
TRANSORANJE SCHOOL FOR THE DEAF, MECHANICAL BOQ
DEPARTMENT OF INFRASTRUCTURE DEVELOPMENT
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
WORKSHOP 300
Disconnect all other machines No. 1
Removal of all other machines No. 1
Transport all other machines to storage No. 1
Transport all other machines to workshop No. 1
Reconnect all other machines No. 1
CLASSROOM
Classroom 100- Classroom 500
Disconnect LPG infrastructure ( First floor CR 100) No. 6
Disconnect Existing Wall Mounted Heaters No. 2
Disconnect Existing Extraction Fans (CR200-
201) No. 2
DiSsonnect Existing Ceiling Fans (CR 200-CR207) No. 3
Disconnect electric geyser, piping and all the existing
associated accessories. No. 1
Removal of LPG infrastructure ( First floor CR 100) No. 6
Removal of Existing Wall Mounted Heaters No. 2
Removal of Existing Extraction Fans (CR200-
201) No. 2
Removal of Existing Ceiling Fans (CR 200-CR207) No. 3
Removal of electric geyser, piping and all the
existing associated accessories. No. 1
Transport LPG infrastructure to storage No. 6
Transport Existing Wall Mounted Heaters to
storage No. 2
Transport Existing Extraction Fans (CR200-
201) to storage No. 2
Transport Existing Ceiling Fans (CR 200-CR207) No. 3
to storage
Transport electric geyser, piping and all the
existing associated accessories to storage No. 1
Carried to Collection
EQUIPMENT- OTHER
JULY 2016 203
TRANSORANJE SCHOOL FOR THE DEAF, MECHANICAL BOQ
DEPARTMENT OF INFRASTRUCTURE DEVELOPMENT
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
Testing and Commissioning
15 Allow for testing of equipments and training of the end Sum 1
Gurantee and Maintenance
16 Provision of Guarantee of equipment and 12-month Sum 1
Operating and Maintenance Procedures
17 Compilation and submission of Operation & Maintenance No 4
Other
18 Any other items required for the successful completion of Sum
5.1 Any other items required for the successful
completion of the work but not included in this bill of
quantities. Please specify: Sum 1
5.2 Testing and commission of the completed machine
installations Item 1
5.3 Attendance and profits on tests
5.4 Allow for inspections and measurements as
5.5 required for the shop drawings and detailed
design of installation 1
5.6 Allow for record drawings and operating instructions 1
5.7 Allow for transportation/travelling charges 1
5.8 Allow for maintenance and specialist maintenance
as specified 1
5.11 Allow for 12 months guarantee in terms of the
Document 1
5.12 Allow for all transport and rigging, lifting gear, cranes
etc, that may be required for moving of plant and
equipment setting out works 1
5.13 Allow for attendance on main contractor and for
switching off, removing all redundant items and
earthing to make supply safe and re-energise after
installation 1
Carried to Collection
EQUIPMENT- OTHER
JULY 2016 204
TRANSORANJE SCHOOL FOR THE DEAF, MECHANICAL BOQ
DEPARTMENT OF INFRASTRUCTURE DEVELOPMENT
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
SHOP AND "AS BUILT" DRAWINGS
5.15 Allow for preparation of detailed, dimensioned shop
drawings and 'as built" drawings to the entire works
and all its components include for 3 copies of all
drawings for approval carring out corrections as
required by engineer No. 3
TRAINING
5.16 Presenting a training course for operators 1
5.17 Presenting training course for maintenance staff 1
INSPECTION OF SITE AND SITE MEASUREMENT
5.18 Allow for detailed inspection of the site,
site measurement and setting out as necessary to
carryout the contract and to provide detailed
dimensioned shop drawings of all works 1
EQUIPMENT SELECTIONS
5.19 Provide detailed selections and samples as
required for approval before installing
OPERATION AND MAINTENANCE MANUALS
5.20, Provide Operating and Maintenance Manuals:
including "as built" drawings and equpment
selection information No. 3
SERVICE INSTALLATIONS AND CONNECTIONS
5.21 Electrical work: carry out complete connection from
local isolator, connect and gland off with water
proofed pvc sheathed copex and test electrical
installation to SANS 10142 and issue COC
certificates No. 0
5.22 Plumbing and drainage work: carry out complete
connection to water services and to drains, connect
SS flexible 15mm water connection installation and
with compression fitting for easy access- use
stainless steel for isolation of the ball valves(and
balls with viton seats)supply at each equipment item 0
5.23 Test the complete installation at full load and in
cooking mode and all associated components of
the installation in phases as the work proses as
work proceeds, demostrate and hand over to the
user; sign off at hand over as beingfully operational
and satisfactory Sum 1
Carried to Collection
EQUIPMENT- OTHER
JULY 2016 205
TRANSORANJE SCHOOL FOR THE DEAF, MECHANICAL BOQ
DEPARTMENT OF INFRASTRUCTURE DEVELOPMENT
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
Other
5.24 Any other items required for the successful
completion of the work but not included in this
bill of quantities. Please specify :
Carried to CollectionSUB-
TOTA SUB-TOTAL FOR LAUNDRY EQUIPMENT
CARRIED TO SUMMARY PAGE
EQUIPMENT- OTHER
JULY 2016 206
Transoranje School for the Deaf - Mechanical Installations BoQs
TOTAL
Bill No. 1 FIRE PRTOTECTION
Bill No. 2 WET SERVICES
Bill No. 3 SPACE HEATING
Bill No. 4 LP GAS INSTALLATION
Bill No. 5 HVAC
Bill No. 6 REFRIGERATION
Bill No. 7 EQUIPMENT -KITCHEN
Bill No. 8 EQUIPMENT -LAUNDRY
Bill No. 9 EQUIPMENT -WORKSHOPS
GRAND TOTAL EXCLUDING VAT
MECHANICAL INSTALLATIONS BILL SUMMARY
TransOranje School for the Deaf - Mechanical Installations Bills of Quantities
July 2016