5.-Electrical-Works-BoQ-RAATC21.pdf

Post on 16-Dec-2015

212 views 0 download

Transcript of 5.-Electrical-Works-BoQ-RAATC21.pdf

  • Name of work: Electrification & Allied works

    S.NO. BSR Ref DESCRIPTION QTY. UNIT RATE (Nu.)

    A WIRING

    1

    Providing Wiring for the light point with 2x1.5sq. mmPVC insulated multistrand copper conductor cable in

    recessed 25mm dia HDPE pipe I/c all accessories as required for light point . Including providing accessories,

    Platinum brand switches 6A 1-gang / 2gang White colour Code CQ000501/02 for front cover. 6A 1 gang

    switch Code CQAT0006, Outer Plate for 1 module Code CQAT0501 for 2 module Code CQAT0502. Inner

    Plate for 1 module Code CQAT1501 for 2 module Code CQAT1502. Platinum brand switches 6A 4-gang

    White colour Code CQ000504 for front cover. 6A 1 gang switch Code CQAT0006, Outer Plate for 4 module

    Code CQAT0504. Inner Plate for 4 module Code CQAT1504 Havells make. Use maximum 3 CFL fixture by

    1 switch. Maximum 2single tube light fitting by 1 switch and double tube light fitting by 1 switch.

    1a WC0300 Short Point 36 Point

    1b WC0301 Medium Point 64 Point

    1c WC0302 Long Point 54 Point

    2

    Providing Wiring for the 2-way light point with 2x1.5sq. mm PVC insulated multistrand copper conductor

    cable in recessed 25mm dia HDPE pipe I/c all accessories as required for twin control light point.

    2a WC0371 Medium point 4 Point

    2b WC0372 Long point 4 Point

    3WC0391

    Providing Wiring for the light point with 2x2.5sq. mm PVC insulated multistrand copper conductor cable in

    recessed 25mm dia HDPE pipe I/c all accessories as required for light circuit wiring .395 M

    4WC0400

    Providing Wiring for the power point with 2x4sq. mm PVC insulated multistrand copper conductor cable in

    recessed 25mm dia HDPE pipe I/c all accessories as required for power wiring . 1150 M

    SUB-TOTAL FOR WIRING

    B FITTING & ACCESSORIES

    1IL0170

    Supplying of Tubelight fitting surface mounted 1x36w/40w fluorscent. Code No.LHIF 71104011 White -

    Havells/Equivalent. 42 Each

    ROYAL AUDIT AUTHORITY TRAINING CENTRE, TSIRANG

    Royal Audit Authority

    Sub Title: General Hostel

    Page 1 of 12

  • S.NO. BSR Ref DESCRIPTION QTY. UNIT RATE (Nu.)

    2

    AR1

    Supplying of Surface mounted ceiling fitting square decorative downlighter with HF electronic ballast and

    translucent diffuser, pre-fitted with flat profile, for 1x25W CFL lamp LONON SQUARE White Code

    No.LHDC70125670 - Havells/Equivalent

    32 Each

    3AR3

    Supplying of decorative wall light fixture foe 1x15W CFL White Code No.LHDL 06160099

    Havells/Equivalent.64 Each

    4FN0002

    Supplying of ceiling fan 240volt AC 1200rpm with all accessories such as down rod, sweep 3nos. Canopy

    2nos. Condenser, fan body & regulator etc. complete as required. - 1200mm sweep.20 Each

    5SS0205

    Supplying and fixing 6 Amp 3pin Switch Socket Combined shuttered having rectangle edge (Crabtree/

    equivalent).20 Each

    6SS0220

    Supplying and fixing 16 Amp 6pin Switch Socket Combined shuttered having rectangle edge (Crabtree/

    equivalent). 60 Each

    7 LS0127TLF lamp 36/40W 42 Each

    8 AR6CFL Lamp 15W 64 Each

    9 AR7CFL Lamp 25W 32 Each

    SUB-TOTAL FOR FITTING & ACCESSORIES

    C SOLAR LIGHT

    1 ARSL01 Supplying and fixing of 50watt solar panel including all required accessories (TATA BP solar/equivalent). 8.00 Each

    2 ARSL02 Supplying and fixing of 12v 100AH Battery for the solar panel. 8.00 Each

    3 ARSL03 Supplying of Controller CAT CI10 (TATA BP solar/equivalent). 8.00 Each

    4 ARSL04 Supplying of luminaire 9w 12v (TATA BP solar/equivalent). 22.00 Each

    5 LS Supplying and fixing of mounting station for the solar panel on roof top. 8.00 LS

    6 EI0002 Erection of solar lights / controller / etc. I/c fixing of lamp connection, testing etc. as required. 30 Each

    7 ARSL05

    Supplying and wiring the solar luminaire from solar panel to a single point in each room ground floor and

    first floor by 2core 2.5sq.mm copper wire. (10point in 1x10rooms & 1point in corridor for G/F & 10point in

    1x10rooms & 1point in corridor for F/F).

    290.00 m

    SUB-TOTAL FOR SOLAR LIGHT

    Page 2 of 12

  • S.NO. BSR Ref DESCRIPTION QTY. UNIT RATE (Nu.)

    D ERECTION OF FITTING & ACCESS.

    1EI0041

    Installation, testing & commissioning of prewired fluorscent fittings of all types complete with all accessories

    and tubes etc. directly on wall / ceiling surface /recess mounted etc. as required.42 Each

    2EI0002

    Erection of compact fluorscent fitting/wall brackets /ceiling fitting/ outdoor fittings/ Solar light/Batten holder

    /musical call bell etc. I/c fixing of lamp connection, testing etc. as required.118 Each

    3EI0096

    Installation, testing and commissioning of all size ceiling fan and regulator including wiring the down rod of

    standard length upto 300mm with 1.5sq.mm PVC insulated copper conductor20 Each

    4EI0110

    Supplying extra down rod of G.I pipe (heavy duty) 15mm dia, 100mm long with 2x1.5sq.mm PVC insulated

    single core copper conductor cable, painting, cutting and threading etc. as required.20 Each

    SUB-TOTAL FOR ERECTION of FITT & ACCE

    E SUBMAIN & CONTROL GEAR

    1

    Supplying of following sizes of 1.1 KV grade aluminium conductor PVC insulated and PVC sheathed

    armoured power cable.

    1aPC0150

    3-1/2Cx25mm2 PVC Insulated UG cable Armoured AYFY from MCPB (Main control panel board) to SDB

    (Sub distribution board). Actual length will be as per site condition.45 M

    2GB0541

    8way TP&N Distribution board (DIN type) with metal door, 415 volts AC complete for SDB-1 (Ground

    Floor) (SQCA Appd)1 Each

    GB0355 63Amp TP&N MCB, 415volt. (SQCA Appd) 2 Each

    GB0270 6Amp SPMCB 6 Each

    GB0272 16Amp SPMCB 18 Each

    3GB0541

    8way TP&N Distribution board (DIN type) with metal door, 415 volts AC complete for SDB-2 (Ground

    Floor) (SQCA Appd)1 Each

    GB0355 63Amp TP&N MCB, 415volt. (SQCA Appd) 2 Each

    GB0270 6Amp SPMCB 6 Each

    GB0272 16Amp SPMCB 18 Each

    4GB0541

    8way TP&N Distribution board (DIN type) with metal door, 415 volts AC complete for SDB-3 (First Floor)

    (SQCA Appd)1 Each

    GB0355 63Amp TP&N MCB, 415volt. (SQCA Appd) 2 Each

    GB0270 6Amp SPMCB 6 Each

    Page 3 of 12

  • S.NO. BSR Ref DESCRIPTION QTY. UNIT RATE (Nu.)

    GB0272 16Amp SPMCB 18 Each

    5GB0541

    8way TP&N Distribution board (DIN type) with metal door, 415 volts AC complete for SDB-4 (First Floor)

    (SQCA Appd)1 Each

    GB0355 63Amp TP&N MCB, 415volt. (SQCA Appd) 2 Each

    GB0270 6Amp SPMCB 6 Each

    GB0272 16Amp SPMCB 18 Each

    6GB0227

    Supplying of 250A Moulded case circuit breaker (MCCB) with electronic release, breaking capacity 36kA,

    4pole 415volt, A.C complete with all accessories etc. as required.1 Each

    7 GB0009Copper busbar chamber of size 300Amp 4x600mm including all accessories etc. at the Generator MCPB. 1 Set

    8AR9

    Providing and fixing electrical measuring instruments at the Main control panel board as per contract

    document specification - Voltmeter 0-500V - 1no.1 Set

    - Ammeter 0- 400A - 1no.

    - Ammeter selector switch - 1no.

    - Voltmeter selector switch - 1no.

    - CT's and PT's

    - Indicating lamps - 4no.

    - HRC fuse 2A rating for avove-4no.

    9AR17

    Providing and fixing 300A 3-Phase 4 wire system Energy Meter at the apprppriate location in consultation

    with BPCL.1 Set

    SUB-TOTAL FOR SUBMAIN & CONTRL GEAR

    F CABLE TERMINATION WITH COMPRESSION GLAND

    1

    Installation, testing and commissioning of end termination with single/double compresion gland for PVC

    insulated and sheathed aluminium conductor cable of 1.1kV grade including connections etc. as required.

    1a CL0110 6/10/16/25mm dia 8 each

    SUB-TOTAL FOR CABLE TERMINATION WITH COMPRESSION GLAND

    G INSTALLATION of SWITCH GEARS

    1

    Installation, testing and commissioning of TP switch fuse unit front drive four/miniature circuit breaker (DIN

    type) / Moulded case circuit breaker (MCCB) complete with all accessories to accommodate on/in

    prefabricated MS surface/Cubical control panel board including drilling holes, connections etc. as required.

    Page 4 of 12

  • S.NO. BSR Ref DESCRIPTION QTY. UNIT RATE (Nu.)

    1a EI0340 63A TP&N MCB,415V 8 each

    1b EI0450 250A TP&N MCCB,415V 1 each

    SUB-TOTAL FOR INSTALN. of SWITCH GEARS

    H INSTALLATION of DISTRIBUTION BOARD

    1

    Installation, testing and commissioning of TPN DB (DIN type) single/double door complete with all

    accessories to accommodate incoming MCB/MCCB/RCCB 4pole 32/40/63A sensitivity 30/100/300mA and

    outgoing SPMCB 6A/16A in prefabricated MS surface /MS cubical panel board including drilling holes,

    connections etc. as required.

    1a EI0545 8way TPN DB 4 each

    SUB-TOTAL FOR INSTALN. of DISTRIBUTION BOARD

    I METAL PANEL BOARD

    1

    Providing and fixing of prefabricated panel board with minimum 50x50x6mm angle iron framework with

    horizontal and vertical intermediate members of flat iron 40x6mm and 24swg sheet cover for mounting of

    switchgears incoming/outgoing busbar chambers including driling holes, insulator, painting, denting, grouting

    etc. as required. for MCPB.

    1a EI0600 Floor mounted cubical control panel board of welded construction 0.8 cu.m

    2MR

    Providing & fixing Wooden board of size 2' x 2-1/2' to mount the switchgears on the wall with locking

    arrangement.4 each

    3

    Providing and fixing medium volt danger notice plate made of mild steel and painted with viterous enamelled

    white paint on both sides, and with inscription in signal red colour written as 440V/1100V in

    Dzongkha/English on front side as required on prefabricated MS surface/MS cubical control panel board on

    surface including drilling holes etc. as required.

    3a EI0610 200mmx150mmx2mm 5 each

    SUB-TOTAL FOR METAL PANEL BOARD

    J EARTHING & LIGHTNING PROTEC.

    1ET0075

    P/F of G.I. earth conductor of size 25mmx4mm for loop earthing as required. Including horizontal and four

    vertical drops for Lightning arrestor Loop connection for earthings etc.375 M

    2 ET0121Supplying & drawing 14SWG copper wire for loop earthing / earthing for electrical equipments. 760 M

    Page 5 of 12

  • S.NO. BSR Ref DESCRIPTION QTY. UNIT RATE (Nu.)

    3LG0002

    P/F of lightning arrestor final made of 25mm dia 900mm long GI tube having five prong at top with 85mm

    dia 6mm thick copper plate I/c holes and spring washer etc. as required. 2 M

    4

    ET0001

    Earthing with G.I earth plate 600mmx600mm x6mm thick I/c accessories & providing masonry enclosure

    with cover plate having locking arrangement & watering pipe. (For Lightning Arrestor) NOTE: This

    earthing shall be independently looped to each other and not to be interconnected with the electrical

    earthing.

    2 Each

    5ET0001

    Earthing with G.I earth plate 600mmx600mm x6mm thick I/c accessories & providing masonry enclosure

    with cover plate having locking arrangement & watering pipe. (For General electrical earthing)2 Each

    SUB-TOTAL FOR EARTNG & LIGHTNING PROTEC.

    K HDPE PIPE

    1 Providing and Laying HDPE Pipe including trenching and refilling.

    1a PO0018 50mm dia for service cable, incoming main telephone cable if required. 10 M

    1b PO0022 110mm dia for service cable connection to shaft. 10 M

    SUBTOTAL FOR HDPE PIPE

    Sub-Total for General Hostel for 1 No. (Nu.)

    Total for General Hostel A&B - 2 Nos (Nu.)

    In Words:

    .

    Page 6 of 12

  • AMOUNT (Nu.)

    ROYAL AUDIT AUTHORITY TRAINING CENTRE, TSIRANG

    Royal Audit Authority

    Page 7 of 12

  • AMOUNT (Nu.)

    Page 8 of 12

  • AMOUNT (Nu.)

    Page 9 of 12

  • AMOUNT (Nu.)

    Page 10 of 12

  • AMOUNT (Nu.)

    Page 11 of 12

  • AMOUNT (Nu.)

    Page 12 of 12