Post on 16-Dec-2015
Name of work: Electrification & Allied works
S.NO. BSR Ref DESCRIPTION QTY. UNIT RATE (Nu.)
A WIRING
1
Providing Wiring for the light point with 2x1.5sq. mmPVC insulated multistrand copper conductor cable in
recessed 25mm dia HDPE pipe I/c all accessories as required for light point . Including providing accessories,
Platinum brand switches 6A 1-gang / 2gang White colour Code CQ000501/02 for front cover. 6A 1 gang
switch Code CQAT0006, Outer Plate for 1 module Code CQAT0501 for 2 module Code CQAT0502. Inner
Plate for 1 module Code CQAT1501 for 2 module Code CQAT1502. Platinum brand switches 6A 4-gang
White colour Code CQ000504 for front cover. 6A 1 gang switch Code CQAT0006, Outer Plate for 4 module
Code CQAT0504. Inner Plate for 4 module Code CQAT1504 Havells make. Use maximum 3 CFL fixture by
1 switch. Maximum 2single tube light fitting by 1 switch and double tube light fitting by 1 switch.
1a WC0300 Short Point 36 Point
1b WC0301 Medium Point 64 Point
1c WC0302 Long Point 54 Point
2
Providing Wiring for the 2-way light point with 2x1.5sq. mm PVC insulated multistrand copper conductor
cable in recessed 25mm dia HDPE pipe I/c all accessories as required for twin control light point.
2a WC0371 Medium point 4 Point
2b WC0372 Long point 4 Point
3WC0391
Providing Wiring for the light point with 2x2.5sq. mm PVC insulated multistrand copper conductor cable in
recessed 25mm dia HDPE pipe I/c all accessories as required for light circuit wiring .395 M
4WC0400
Providing Wiring for the power point with 2x4sq. mm PVC insulated multistrand copper conductor cable in
recessed 25mm dia HDPE pipe I/c all accessories as required for power wiring . 1150 M
SUB-TOTAL FOR WIRING
B FITTING & ACCESSORIES
1IL0170
Supplying of Tubelight fitting surface mounted 1x36w/40w fluorscent. Code No.LHIF 71104011 White -
Havells/Equivalent. 42 Each
ROYAL AUDIT AUTHORITY TRAINING CENTRE, TSIRANG
Royal Audit Authority
Sub Title: General Hostel
Page 1 of 12
S.NO. BSR Ref DESCRIPTION QTY. UNIT RATE (Nu.)
2
AR1
Supplying of Surface mounted ceiling fitting square decorative downlighter with HF electronic ballast and
translucent diffuser, pre-fitted with flat profile, for 1x25W CFL lamp LONON SQUARE White Code
No.LHDC70125670 - Havells/Equivalent
32 Each
3AR3
Supplying of decorative wall light fixture foe 1x15W CFL White Code No.LHDL 06160099
Havells/Equivalent.64 Each
4FN0002
Supplying of ceiling fan 240volt AC 1200rpm with all accessories such as down rod, sweep 3nos. Canopy
2nos. Condenser, fan body & regulator etc. complete as required. - 1200mm sweep.20 Each
5SS0205
Supplying and fixing 6 Amp 3pin Switch Socket Combined shuttered having rectangle edge (Crabtree/
equivalent).20 Each
6SS0220
Supplying and fixing 16 Amp 6pin Switch Socket Combined shuttered having rectangle edge (Crabtree/
equivalent). 60 Each
7 LS0127TLF lamp 36/40W 42 Each
8 AR6CFL Lamp 15W 64 Each
9 AR7CFL Lamp 25W 32 Each
SUB-TOTAL FOR FITTING & ACCESSORIES
C SOLAR LIGHT
1 ARSL01 Supplying and fixing of 50watt solar panel including all required accessories (TATA BP solar/equivalent). 8.00 Each
2 ARSL02 Supplying and fixing of 12v 100AH Battery for the solar panel. 8.00 Each
3 ARSL03 Supplying of Controller CAT CI10 (TATA BP solar/equivalent). 8.00 Each
4 ARSL04 Supplying of luminaire 9w 12v (TATA BP solar/equivalent). 22.00 Each
5 LS Supplying and fixing of mounting station for the solar panel on roof top. 8.00 LS
6 EI0002 Erection of solar lights / controller / etc. I/c fixing of lamp connection, testing etc. as required. 30 Each
7 ARSL05
Supplying and wiring the solar luminaire from solar panel to a single point in each room ground floor and
first floor by 2core 2.5sq.mm copper wire. (10point in 1x10rooms & 1point in corridor for G/F & 10point in
1x10rooms & 1point in corridor for F/F).
290.00 m
SUB-TOTAL FOR SOLAR LIGHT
Page 2 of 12
S.NO. BSR Ref DESCRIPTION QTY. UNIT RATE (Nu.)
D ERECTION OF FITTING & ACCESS.
1EI0041
Installation, testing & commissioning of prewired fluorscent fittings of all types complete with all accessories
and tubes etc. directly on wall / ceiling surface /recess mounted etc. as required.42 Each
2EI0002
Erection of compact fluorscent fitting/wall brackets /ceiling fitting/ outdoor fittings/ Solar light/Batten holder
/musical call bell etc. I/c fixing of lamp connection, testing etc. as required.118 Each
3EI0096
Installation, testing and commissioning of all size ceiling fan and regulator including wiring the down rod of
standard length upto 300mm with 1.5sq.mm PVC insulated copper conductor20 Each
4EI0110
Supplying extra down rod of G.I pipe (heavy duty) 15mm dia, 100mm long with 2x1.5sq.mm PVC insulated
single core copper conductor cable, painting, cutting and threading etc. as required.20 Each
SUB-TOTAL FOR ERECTION of FITT & ACCE
E SUBMAIN & CONTROL GEAR
1
Supplying of following sizes of 1.1 KV grade aluminium conductor PVC insulated and PVC sheathed
armoured power cable.
1aPC0150
3-1/2Cx25mm2 PVC Insulated UG cable Armoured AYFY from MCPB (Main control panel board) to SDB
(Sub distribution board). Actual length will be as per site condition.45 M
2GB0541
8way TP&N Distribution board (DIN type) with metal door, 415 volts AC complete for SDB-1 (Ground
Floor) (SQCA Appd)1 Each
GB0355 63Amp TP&N MCB, 415volt. (SQCA Appd) 2 Each
GB0270 6Amp SPMCB 6 Each
GB0272 16Amp SPMCB 18 Each
3GB0541
8way TP&N Distribution board (DIN type) with metal door, 415 volts AC complete for SDB-2 (Ground
Floor) (SQCA Appd)1 Each
GB0355 63Amp TP&N MCB, 415volt. (SQCA Appd) 2 Each
GB0270 6Amp SPMCB 6 Each
GB0272 16Amp SPMCB 18 Each
4GB0541
8way TP&N Distribution board (DIN type) with metal door, 415 volts AC complete for SDB-3 (First Floor)
(SQCA Appd)1 Each
GB0355 63Amp TP&N MCB, 415volt. (SQCA Appd) 2 Each
GB0270 6Amp SPMCB 6 Each
Page 3 of 12
S.NO. BSR Ref DESCRIPTION QTY. UNIT RATE (Nu.)
GB0272 16Amp SPMCB 18 Each
5GB0541
8way TP&N Distribution board (DIN type) with metal door, 415 volts AC complete for SDB-4 (First Floor)
(SQCA Appd)1 Each
GB0355 63Amp TP&N MCB, 415volt. (SQCA Appd) 2 Each
GB0270 6Amp SPMCB 6 Each
GB0272 16Amp SPMCB 18 Each
6GB0227
Supplying of 250A Moulded case circuit breaker (MCCB) with electronic release, breaking capacity 36kA,
4pole 415volt, A.C complete with all accessories etc. as required.1 Each
7 GB0009Copper busbar chamber of size 300Amp 4x600mm including all accessories etc. at the Generator MCPB. 1 Set
8AR9
Providing and fixing electrical measuring instruments at the Main control panel board as per contract
document specification - Voltmeter 0-500V - 1no.1 Set
- Ammeter 0- 400A - 1no.
- Ammeter selector switch - 1no.
- Voltmeter selector switch - 1no.
- CT's and PT's
- Indicating lamps - 4no.
- HRC fuse 2A rating for avove-4no.
9AR17
Providing and fixing 300A 3-Phase 4 wire system Energy Meter at the apprppriate location in consultation
with BPCL.1 Set
SUB-TOTAL FOR SUBMAIN & CONTRL GEAR
F CABLE TERMINATION WITH COMPRESSION GLAND
1
Installation, testing and commissioning of end termination with single/double compresion gland for PVC
insulated and sheathed aluminium conductor cable of 1.1kV grade including connections etc. as required.
1a CL0110 6/10/16/25mm dia 8 each
SUB-TOTAL FOR CABLE TERMINATION WITH COMPRESSION GLAND
G INSTALLATION of SWITCH GEARS
1
Installation, testing and commissioning of TP switch fuse unit front drive four/miniature circuit breaker (DIN
type) / Moulded case circuit breaker (MCCB) complete with all accessories to accommodate on/in
prefabricated MS surface/Cubical control panel board including drilling holes, connections etc. as required.
Page 4 of 12
S.NO. BSR Ref DESCRIPTION QTY. UNIT RATE (Nu.)
1a EI0340 63A TP&N MCB,415V 8 each
1b EI0450 250A TP&N MCCB,415V 1 each
SUB-TOTAL FOR INSTALN. of SWITCH GEARS
H INSTALLATION of DISTRIBUTION BOARD
1
Installation, testing and commissioning of TPN DB (DIN type) single/double door complete with all
accessories to accommodate incoming MCB/MCCB/RCCB 4pole 32/40/63A sensitivity 30/100/300mA and
outgoing SPMCB 6A/16A in prefabricated MS surface /MS cubical panel board including drilling holes,
connections etc. as required.
1a EI0545 8way TPN DB 4 each
SUB-TOTAL FOR INSTALN. of DISTRIBUTION BOARD
I METAL PANEL BOARD
1
Providing and fixing of prefabricated panel board with minimum 50x50x6mm angle iron framework with
horizontal and vertical intermediate members of flat iron 40x6mm and 24swg sheet cover for mounting of
switchgears incoming/outgoing busbar chambers including driling holes, insulator, painting, denting, grouting
etc. as required. for MCPB.
1a EI0600 Floor mounted cubical control panel board of welded construction 0.8 cu.m
2MR
Providing & fixing Wooden board of size 2' x 2-1/2' to mount the switchgears on the wall with locking
arrangement.4 each
3
Providing and fixing medium volt danger notice plate made of mild steel and painted with viterous enamelled
white paint on both sides, and with inscription in signal red colour written as 440V/1100V in
Dzongkha/English on front side as required on prefabricated MS surface/MS cubical control panel board on
surface including drilling holes etc. as required.
3a EI0610 200mmx150mmx2mm 5 each
SUB-TOTAL FOR METAL PANEL BOARD
J EARTHING & LIGHTNING PROTEC.
1ET0075
P/F of G.I. earth conductor of size 25mmx4mm for loop earthing as required. Including horizontal and four
vertical drops for Lightning arrestor Loop connection for earthings etc.375 M
2 ET0121Supplying & drawing 14SWG copper wire for loop earthing / earthing for electrical equipments. 760 M
Page 5 of 12
S.NO. BSR Ref DESCRIPTION QTY. UNIT RATE (Nu.)
3LG0002
P/F of lightning arrestor final made of 25mm dia 900mm long GI tube having five prong at top with 85mm
dia 6mm thick copper plate I/c holes and spring washer etc. as required. 2 M
4
ET0001
Earthing with G.I earth plate 600mmx600mm x6mm thick I/c accessories & providing masonry enclosure
with cover plate having locking arrangement & watering pipe. (For Lightning Arrestor) NOTE: This
earthing shall be independently looped to each other and not to be interconnected with the electrical
earthing.
2 Each
5ET0001
Earthing with G.I earth plate 600mmx600mm x6mm thick I/c accessories & providing masonry enclosure
with cover plate having locking arrangement & watering pipe. (For General electrical earthing)2 Each
SUB-TOTAL FOR EARTNG & LIGHTNING PROTEC.
K HDPE PIPE
1 Providing and Laying HDPE Pipe including trenching and refilling.
1a PO0018 50mm dia for service cable, incoming main telephone cable if required. 10 M
1b PO0022 110mm dia for service cable connection to shaft. 10 M
SUBTOTAL FOR HDPE PIPE
Sub-Total for General Hostel for 1 No. (Nu.)
Total for General Hostel A&B - 2 Nos (Nu.)
In Words:
.
Page 6 of 12
AMOUNT (Nu.)
ROYAL AUDIT AUTHORITY TRAINING CENTRE, TSIRANG
Royal Audit Authority
Page 7 of 12
AMOUNT (Nu.)
Page 8 of 12
AMOUNT (Nu.)
Page 9 of 12
AMOUNT (Nu.)
Page 10 of 12
AMOUNT (Nu.)
Page 11 of 12
AMOUNT (Nu.)
Page 12 of 12