DIGSI read me files

6
DIGSI V4.83 Hotfix 2 Readme Readme / Installation Instructions for DIGSI V4.83 Hotfix 2 Die deutsche Version finden Sie im Anschluss an die englische Version. New Features and Modifications This hotfix eliminates the following problems: ERR_48226 Some wrong AppIDs (GOOSE) after updating DIGSI from V 4.71 to V 4.83 The GOOSE AppIDs are correctly updated now. To ensure compatibility of the GOOSE AppIDs during the update all AppIDs are changed. Therefore mixed device configurations (devices parameterized using DIGSI 4.71 and DIGSI 4.83 HF2) can communicate via GOOSE without problems. ERR_47593 DIGSI crash if you have more than 8 IP-addresses on your PC DIGSI 4 works correctly with up to 20 IP addresses on a PC. ERR_48779 Errors in Parameter Set Comparison When comparing the device parameter set online / offline the correct language and character set is used. When a device is opened online and PC device language and device operating language are different, the correct language and character set is used. When display images are compared, the comparison result is correct. ERR_48498 Parameter Set Comparison shows German text When DIGSI parameter set comparison is used in Russian, the text “Line … is different” is translated cor- rectly to Russian. ERR_49088 Traces will be shifted in case of a comma in the name of the trace If a fault record is transferred via IEC 61850, commas in the names of analog tracks will not affect displaying the fault record anymore. Please note: If user defined annunciations shall be displayed in the binary tracks of a fault record that is downloaded via IEC 61850, you need to avoid using commas in the names. CR_758 Extension of IEC 61850 IED-names to 13 characters IEC 61850 IED names can have up to 13 characters Please note: it is recommended to set definitive IED names before configuring GOOSE connections. If the IED name of a device that communicates via GOOSE is changed, don’t forget to force an update of all devices that take part in GOOSE communications of the changed device. In order to do this you might need to issue a pseudo change (i.e. just an interim change of a setting and changing it back after DIGSI 4 recog- nizes the need for an update) in the other devices to recognize the change of the device name. System Requirements See DIGSI V4.83. Comments to usage / restrictions DIGSI 4.83 must be installed on your PC. Siemens Aktiengesellschaft 1 Copyrights © Siemens AG 2010 All Rights Reserved

Transcript of DIGSI read me files

Page 1: DIGSI read me files

DIGSI V4.83 Hotfix 2 Readme

Readme / Installation Instructions for DIGSI V4.83 Hotfix 2

Die deutsche Version finden Sie im Anschluss an die englische Version.

New Features and Modifications

This hotfix eliminates the following problems:

ERR_48226 Some wrong AppIDs (GOOSE) after updating DIGSI from V 4.71 to V 4.83

The GOOSE AppIDs are correctly updated now. To ensure compatibility of the GOOSE AppIDs during the update all AppIDs are changed. Therefore mixed device configurations (devices parameterized using DIGSI 4.71 and DIGSI 4.83 HF2) can communicate via GOOSE without problems.

ERR_47593 DIGSI crash if you have more than 8 IP-addresses on your PC

DIGSI 4 works correctly with up to 20 IP addresses on a PC.

ERR_48779 Errors in Parameter Set Comparison

When comparing the device parameter set online / offline the correct language and character set is used. When a device is opened online and PC device language and device operating language are different, the correct language and character set is used. When display images are compared, the comparison result is correct.

ERR_48498 Parameter Set Comparison shows German text

When DIGSI parameter set comparison is used in Russian, the text “Line … is different” is translated cor-rectly to Russian.

ERR_49088 Traces will be shifted in case of a comma in the name of the trace

If a fault record is transferred via IEC 61850, commas in the names of analog tracks will not affect displaying the fault record anymore. Please note: If user defined annunciations shall be displayed in the binary tracks of a fault record that is downloaded via IEC 61850, you need to avoid using commas in the names.

CR_758 Extension of IEC 61850 IED-names to 13 characters

IEC 61850 IED names can have up to 13 characters Please note: it is recommended to set definitive IED names before configuring GOOSE connections. If the IED name of a device that communicates via GOOSE is changed, don’t forget to force an update of all devices that take part in GOOSE communications of the changed device. In order to do this you might need to issue a pseudo change (i.e. just an interim change of a setting and changing it back after DIGSI 4 recog-nizes the need for an update) in the other devices to recognize the change of the device name.

System Requirements

See DIGSI V4.83.

Comments to usage / restrictions

DIGSI 4.83 must be installed on your PC.

Siemens Aktiengesellschaft 1 Copyrights © Siemens AG 2010 All Rights Reserved

Page 2: DIGSI read me files

DIGSI V4.83 Hotfix 2 Readme

Compatibility

DIGSI V4.83 Hotfix 2 can only be used to update DIGSI V4.83. It doesn't matter if the Patch 1 oder Patch 2 for DIGSI V4.83 has been applied to the system prior to installing this hotfix. This hotfix does not include Patch 1, Patch2 or Hotfix1 for DIGSI V4.83.

Contents of the Consignment / Installation

DIGSI V4.83 Hotfix 2 contains the following files:

| GNL_DIGSI-V4.83_HF2_ReadMe.pdf | HotFixInstall.bat | +---DIGSI4 | | dig4resf.dll V 4.83.21 | | DIntAPI.dll V 4.83.21 | | DIntComp.dll V 4.83.21 | | DIntText.dll V 4.83.21 | | Iec2Map.dll V 2.11.05 | | UpgradeX.dll V 4.83.21 | | | \---Syskon | IEC61850Logic.dll V 4.83.21 | \---MANAGER | \---S7BIN P7Di618x.dll p7dierra.dll V 4.83.21 p7dierrb.dll V 4.83.21 p7dierrc.dll V 4.83.21 p7dierrd.dl V 4.83.21 p7dierre.dll V 4.83.21 p7dierrF.dll V 4.83.21 p7dierrK.dll V 4.83.21 p7dierrL.dll V 4.83.21 p7diiedx.dll V 4.83.21

Installation:

1. Make sure, that DIGSI V4.83 is installed on your PC. 2. Close DIGSI V4.83 before you install the DIGSI V4.83 Hotfix 2. 3. Unzip the files in a local folder of your PC. Keep the folder structure as it is in the ZIP archive,

see “Contents of the Consignment / Installation”. 4. Execute the installation script HotFixInstall.bat. This will install the hotfix into your local DIGSI 4 installa-

tion. 5. Now you can delete the unzipped files.

Remarks to Installation

How to recognize that DIGSI V4.83 Hotfix 2 has been installed: Open the "Properties" of the installed files in MS Windows-Explorer, open the "Version" tab and check if it shows the version that is listed in “Contents of the Consignment / Installation”, see above.

Siemens Aktiengesellschaft 2 Copyrights © Siemens AG 2010 All Rights Reserved

Page 3: DIGSI read me files

DIGSI V4.83 Hotfix 2 Readme

Uninstallation

It is neither possible nor necessary to uninstall DIGSI V4.83 Hotfix 2.

Hotline

To get help with installation and usage of this hotfix, please ask our hotline.

Phone: +49 - 180 - 524 7000

Fax: +49 - 180 - 524 2471

eMail: [email protected]

Siemens Aktiengesellschaft 3 Copyrights © Siemens AG 2010 All Rights Reserved

Page 4: DIGSI read me files

DIGSI V4.83 Hotfix 2 Readme

Readme / Installationsanleitung für DIGSI V4.83 Hotfix 2

Neuerungen und Änderungen

Folgende Fehler werden mit diesem Hotfix behoben:

ERR_48226 Nach der DIGSI-Aktualisierung von V4.71 auf V4.83 sind manche AppIDs (GOOSE) falsch

Die GOOSE AppIDs werden jetzt korrekt aktualisiert. Um die Kompatibilität der GOOSE AppIDs beim Up-date sicherzustellen, werden alle AppIDs automatisch angepasst. Deshalb können gemischte Gerätekonfi-gurationen (Geräte parametriert mit DIGSI 4.71 und DIGSI 4.83 HF2) über GOOSE problemlos kommunizie-ren.

ERR_47593 DIGSI stürzt ab, wenn der PC mehr als 8 IP-Adressen hat

DIGSI 4 funktioniert einwandfrei mit bis zu 20 IP-Adressen auf dem PC.

ERR_48779 Fehler im Parametersatzvergleich

Für den Parametersatzvergleich Online / Offline wird die richtige Sprache und der richtige Zeichensatz ver-wendet. Wenn ein Gerät Online geöffnet wird und PC-Gerätesprache und Gerätebediensprache sind unter-schiedlich, wird die richtige Sprache und der richtige Zeichensatz verwendet. Wenn Displaybilder verglichen werden, ist das Vergleichsergebnis korrekt.

ERR_48498 Parametersatzvergleich zeigt deutsche Texte

Wenn der Parametersatzvergleich in russischer Sprache verwendet wird, ist der Text „Zeile … ist unter-schiedlich“ richtig ins russische übersetzt.

ERR_49088 Störschriebe sind verschoben, wenn einer der Bezeichner ein Komma enthält

Wenn ein Störschrieb über IEC 61850 übertragen wird, wird die Darstellung des Störschriebs durch ein Komma im Bezeichner einer Analogspur nicht mehr beeinträchtigt. Hinweis: Wenn benutzerdefinierte Meldungen als Binärspur eines Störschriebs, der über IEC 61850 über-tragen wird, dargestellt werden sollen, müssen Sie Kommas in den Meldungsnamen vermeiden.

CR_758 Erweiterung des IEC 61850 IED-Namen auf 13 Zeichen

IEC 61850 IED-Namen können bis zu 13 Zeichen lang sein. Hinweis: Es ist ratsam, die endgültigen IED-Namen festzulegen, bevor GOOSE-Verbindungen parametriert werden. Wenn der IED-Name eines Geräts, das über GOOSE kommuniziert, geändert wird, muss bei allen Geräten, die an einer GOOSE-Verbindung des geänderten Geräts teilnehmen, die Aktualisierung erzwun-gen werden. Dazu müssen Sie möglicherweise bei den anderen Geräten eine Pseudoänderung durchführen (z.B. eine Einstellung vorübergehend ändern und, nachdem DIGSI erkannt hat, dass eine Aktualisierung notwendig ist, wieder zurückstellen) damit die Änderung des IED-Namen erkannt wird.

Systemvoraussetzungen

Siehe DIGSI V4.83.

Hinweise zur Benutzung / Einschränkungen

Für die Installation des Hotfix muss DIGSI V4.83 auf Ihrem PC installiert sein.

Siemens Aktiengesellschaft 4 Copyrights © Siemens AG 2010 All Rights Reserved

Page 5: DIGSI read me files

DIGSI V4.83 Hotfix 2 Readme

Kompatibilität

DIGSI V4.83 Hotfix 2 darf nur mit DIGSI V4.83 eingesetzt werden. Ob der bereits verfügbare Patch 1 oder Patch 2 für DIGSI V4.83 vor Installation dieses Hotfixes ausgeführt wurde, spielt keine Rolle. Dieser Hotfix beinhaltet NICHT den Patch 1, Patch 2 oder Hotfix1 für DIGSI V4.83.

Lieferumfang / Installation

DIGSI V4.83 Hotfix 2 beinhaltet folgende Dateien:

| GNL_DIGSI-V4.83_HF2_ReadMe.pdf | HotFixInstall.bat | +---DIGSI4 | | dig4resf.dll V 4.83.21 | | DIntAPI.dll V 4.83.21 | | DIntComp.dll V 4.83.21 | | DIntText.dll V 4.83.21 | | Iec2Map.dll V 2.11.05 | | UpgradeX.dll V 4.83.21 | | | \---Syskon | IEC61850Logic.dll V 4.83.21 | \---MANAGER | \---S7BIN P7Di618x.dll p7dierra.dll V 4.83.21 p7dierrb.dll V 4.83.21 p7dierrc.dll V 4.83.21 p7dierrd.dl V 4.83.21 p7dierre.dll V 4.83.21 p7dierrF.dll V 4.83.21 p7dierrK.dll V 4.83.21 p7dierrL.dll V 4.83.21 p7diiedx.dll V 4.83.21

Installation:

1. Stellen Sie sicher, dass DIGSI V4.83 auf dem PC installiert ist. 2. Schließen Sie DIGSI V4.83, bevor Sie das DIGSI V4.83 Hotfix 2 installieren. 3. Entpacken Sie die Datei in ein lokales Verzeichnis auf ihrem PC. Behalten Sie dabei die Unterverzeich-

nisse bei, siehe „Lieferumfang / Installation“. 4. Starten Sie das Installationsscript HotFixInstall.bat. Dies installiert den Hotfix in Ihre lokale DIGSI 4

Installation. 5. Jetzt können Sie die entpackten Dateien wieder löschen.

Hinweise zur Installation

So erkennen Sie, dass das DIGSI V4.83 Hotfix 2 installiert ist: Öffnen Sie den "Eigenschaften"-Dialog der installierten Dateien mit dem MS Windows-Explorer, öffnen Sie die Registerkarte "Version" und überprüfen Sie, ob die Version angezeigt wird, die in „Lieferumfang / Instal-lation“ angegeben ist, siehe oben.

Siemens Aktiengesellschaft 5 Copyrights © Siemens AG 2010 All Rights Reserved

Page 6: DIGSI read me files

DIGSI V4.83 Hotfix 2 Readme

Siemens Aktiengesellschaft 6 Copyrights © Siemens AG 2010 All Rights Reserved

Deinstallation

Es ist weder möglich noch nötig, das DIGSI V4.83 Hotfix 2 zu deinstallieren.

Hotline-Kontakt

Um Unterstützung bei der Installation und Benutzung dieses Hotfixes zu bekommen, wenden Sie sich bitte an unsere Hotline.

Fon: +49 - 180 - 524 7000

Fax: +49 - 180 - 524 2471

eMail: [email protected]