IQ422, IQ4NC/00, IQ4NC/12 Controllers Installation Instructions - Configuring TG201265 Issue 12, 24-Jul-2018 1 Installation Instructions - Configuring IQ422, IQ4NC/00, IQ4NC/12 Controllers Important: Retain these instructions These instructions shall be used by trained service personnel only. If the equipment is used in a manner not specified by these instructions, the protection provided by the equipment may be impaired. https://partners.trendcontrols.com 1 Isolate All Power (including any I/O supplies) 1 BEFORE STARTING CONFIGURATION CONTENTS 1 Before Starting Configuration .......................................1 2 Configuration .................................................................1 3 Connect to IQ4xx ........................................................10 4 Reset to Defaults .........................................................12 2 CONFIGURATION Read & Agree to End User Licence Agreement Additional Documentation Required SET Manual (TE200147) IP Tool Manual (TE200638) IQTool Monitor Applet Manual (TE201298) IQTool Addresser Applet Manual (TE201299) IQ4 Configuration Manual (TE201263) Note: PDF copies are included with SET installation in the following folder: C:\...\Trend Control Systems\Documentation IQ422, IQ4NC/00, IQ4NC/12 Installation Instructions - Mounting (TG201264) SET Manual (TE200147) Prepare Ethernet Network (if using Ethernet) Install DHCP Server If the IP address settings (IP address, subnet mask, default router, WINS and DNS servers’ addresses) are to be supplied by a DHCP server, ensure one is installed on the Ethernet segment to which the IQ422, IQ4NC/00, IQ4NC/12 is connected. Install WINS Server If host names are being used for IP addressing across a router, a WINS server must be installed. Install DNS Server If email alarms are being sent, and the email server address is identified by internet domain name, a DNS server must be installed. IQ422, IQ4NC/00, IQ4NC/12 Installation Instructions - Mounting (TG201264) PSU PSU O I O I O I Install the IQ422, IQ4NC/00, IQ4NC/12 Install SET on PC / Laptop WARNING Connecting leads may be connected to power supplies. Isolate before touching.

Transcript of Installation Instructions - Confi guring IQ422 ... - Honeywell

Page 1: Installation Instructions - Confi guring IQ422 ... - Honeywell

IQ422,IQ4NC/00,IQ4NC/12ControllersInstallationInstructions-ConfiguringTG201265Issue12,24-Jul-2018 1

Installation�Instructions�-�Confi�guring

IQ422, IQ4NC/00, IQ4NC/12Controllers

Important: Retain these instructions

These instructions shall be used by trained service personnel only. If the equipment is used in a manner not specifiedbytheseinstructions,theprotectionprovidedbytheequipmentmaybeimpaired. https://partners.trendcontrols.com

1 Isolate All Power (includinganyI/Osupplies)

1 BEFORE STARTING CONFIGURATION

CONTENTS1 BeforeStartingConfiguration.......................................12 Configuration.................................................................1

3 Connect to IQ4xx........................................................104 Reset to Defaults.........................................................12

2 CONFIGURATION

Read�&�Agree�to�End�User�Licence�Agreement

Additional Documentation Required

▪ SETManual(TE200147) ▪ IPToolManual(TE200638) ▪ IQToolMonitorAppletManual(TE201298) ▪ IQToolAddresserAppletManual(TE201299) ▪ IQ4ConfigurationManual(TE201263)

Note: PDF copies are included with SET installation in the following folder: C:\...\Trend Control Systems\Documentation

IQ422, IQ4NC/00, IQ4NC/12 Installation Instructions-Mounting(TG201264) SETManual(TE200147)

Prepare Ethernet Network (ifusingEthernet)

Install DHCP ServerIftheIPaddresssettings(IPaddress,subnetmask,defaultrouter,WINSandDNSservers’addresses)aretobesuppliedbyaDHCPserver,ensureone is installedon theEthernetsegment to which the IQ422, IQ4NC/00, IQ4NC/12 isconnected.

Install WINS ServerIf host names are being used for IP addressing across arouter,aWINSservermustbeinstalled.

Install DNS ServerIfemailalarmsarebeingsent,andtheemailserveraddressisidentifiedbyinternetdomainname,aDNSservermustbeinstalled.

IQ422, IQ4NC/00, IQ4NC/12 Installation Instructions-Mounting(TG201264)

PSU

PSU

O

I

O

I

O

I

Install the IQ422, IQ4NC/00, IQ4NC/12 Install�SET�on�PC�/�Laptop

WARNING Connecting leadsmay be connectedtopowersupplies.Isolatebeforetouching.

Page 2: Installation Instructions - Confi guring IQ422 ... - Honeywell

2 IQ422,IQ4NC/00,IQ4NC/12ControllersInstallationInstructions-ConfiguringTG201265Issue12,24-Jul-2018.

IQ422, IQ4NC/00, IQ4NC/12� Installation�Instructions�-�Confi�guring

6 Select Terminator Switch Position (IQ4NCusingMS/TPnetworkonly)

3 Peel�Off��Top�Serial�Label�&�Retain

5 Disconnect All I/O4 Open�Rotating�Covers

2 Open Panel / Enclosure

2 CONFIGURATION (continued)

Serial

Number

n q 4 e y e c p 4 1 2 3 4 5

Q422B_V53440388 O/S

Q422B_V53440388

n q 4 e y e c p 4 1 2 3 4 5

00:10:70:0D:1E:92MAC Addr

IQ411-1010U5000Part No:

LAN

422

MAC

Addr

IP

Addr

LAN

Location

S/No:

MAC Addr 00.10.70.00.UD.BBS/No:

Q3B____X73010003

IP Addr Location

TerminatoroutofcircuitTerminatorincircuit

IQ422, IQ4NC/00, IQ4NC/12 Installation Instructions - Mounting (TG201264) fordetailsofterminatoruse.

Leave Power, Ethernet, Current loop LAN, USB, RS232,andMS/TPconnected(whereappropriate).

WARNING Opening the panel may exposedangerousvoltages.

Page 3: Installation Instructions - Confi guring IQ422 ... - Honeywell

IQ422,IQ4NC/00,IQ4NC/12ControllersInstallationInstructions-ConfiguringTG201265Issue12,24-Jul-2018 3

Installation�Instructions�-�Confi�guring IQ422, IQ4NC/00, IQ4NC/12

8 Close�Rotating�Covers

10 Check�Power�&�Watchdog�Indicators

9 Switch On Power to IQ4xx

7 Connect�PC�/�Laptop

11 Check Ethernet Indicators (ifEthernetisconnected)

2 CONFIGURATION (continued)

O

I

Either:viaEthernetHub/Switch Or:usingdirectconnection

Note: To connect with SET a vCNC is required (see step 14). SET can connect when on a diff erent subnet.

Note: Other methods of connection are available see ‘Connect to IQ4xx’ on page 10.

Normal operation indicationPower

Watchdog

Fault indicationsPower Checkinputpowersupply

Watchdog Devicefault.TryresettingtheIQ4xxtodefaultsettings(seepage12).

10s

Normal operation indicationOK RX or

Fault indicationsOK CheckEthernet

RJ45 StandardEthernetcable(Cat5etwistedpair)max100m(109yds)

StandardEthernetcable(Cat5etwistedpair)max100m(109yds)

RJ45

Hub/SwitchRouter

Note: All LEDs illuminate for several seconds after switch on.

Watchdog(red)

Power(green)

OK(green)

RX(yellow)

Page 4: Installation Instructions - Confi guring IQ422 ... - Honeywell

4 IQ422,IQ4NC/00,IQ4NC/12ControllersInstallationInstructions-ConfiguringTG201265Issue12,24-Jul-2018.

IQ422, IQ4NC/00, IQ4NC/12� Installation�Instructions�-�Configuring

12 Connect to the IQ4xx

13 Set�up�IP�Addressing�Details�(ifusingEthernet)

2 CONFIGURATION (continued)

n q 4 e y e c p 4 1 2 3 4 5

Q422B_V53440388 O/S

00:10:70:0D:1E:92MAC Addr

IQ422-1010U5000Part No:

LAN

IP

Addr

422

Thenfind the IQ4NC, IQ422by itsMACaddressasshownonseriallabel

SETManual(TE200147)IPToolManual(TE200638)

UseIPTool–seestep12–tochooseeitherstatic(fixed)ordynamic(DHCP)addressing:

Dynamic�(DHCP)�Addressing�(default)

Parameter ValueDeviceMode

Static�(Fixed)�Addressing

Parameter ValueDeviceMode

IPAddressEnterrequiredvalueinformat:

xxx.xxx.xxx.xxxSubnetMaskDefault RouterWINSServer

Whensettodynamic(DHCP)addressingtheunitautomaticalobtains its IP addressing details (IP address, subnetmask,default router, WINS server and DNS server) from thenetwork’s DHCP (Dynamic Host Configuration Protocol)server. IfnoDHCPserver is found, theunitdefaults to link/localmodewhereitautonegotiatesitsIPaddresswithotherdevicesonitsEthernetsegment,

Note:  It  is  recommended  that  link/local  only  be  used  on  a single segment system.

When set to static (fixed) addresssing the IP addressingdetailsmustbeconfiguredmanually.

Note:  If  email  alarms  are  being  sent,  and  the  email  server address  is  identified  by  internet  domain  name,  then  a DNS server must also be specified using Text Comms.

IPToolManual(TE200638)

UsingthePC/laptop(seestep7)runSET/IPTool

14 Set up Virtual CNCs (ifrequired)

Bydefault,IQ4NCshave4enabledvCNCs(4,5,6,and7)andIQ422shave3disabledvCNCs.AvCNCmustbeenabledif connection to a supervisor, tool or display is required. Ifnecessarydisable/configurethemtoavoidaddressconflicts.

Use IPTool–seestep12– tosetup theaddressandportnumberofeachvCNC.

Parameter RangeAddress 0(disabled),1,4to9,11to119PortNumber 1to32767

Default = 10000 plus the address(e.g.address23setsportto10023)

OncethevCNCsetupinIPTooliscomplete,useIQSETtoconfigurethevCNCs.

▪ UsingIQSETconnecttooneofthecontroller’svCNCs. ▪ Youwillbeprompted topress theservicebuttonon the

controller.OncepressedtheSecure�Site�Configuration dialogueboxisdisplayed.

▪ Configure the vCNCs as required, and enter thecredentialsfortheCNCUsermodule.

Note: configuring the vCNCs require physical access to the controller ensure this is done before leaving site.

SETManual(TE200147)IPToolManual(TE200638)

Page 5: Installation Instructions - Confi guring IQ422 ... - Honeywell

IQ422,IQ4NC/00,IQ4NC/12ControllersInstallationInstructions-ConfiguringTG201265Issue12,24-Jul-2018 5

Installation�Instructions�-�Configuring IQ422, IQ4NC/00, IQ4NC/12

15 Set up IQ4NC Communication Mode (ifusingIQ4NC)

16 Check�Trend�Current�Loop�Network�Indicators�(ifcurrentloopnetworkbeingused)

17 Check MS/TP Network Indicators (IfIQ4NCusingMS/TPnetwork)

▪ ConnectaPCdirectlytotheIQ4usinganEthernetcable,see‘ConnecttoIQ4’onpage10.

▪ Usingawebbrowser,e.g. InternetExplorer,access thecontroller’swebpagesandselectModules>Networks to displaytheNC�Configuration�Wizard.

▪ Click required mode, and if necessary specify anyparameterse.g.LANnumber.

▪ Click ;thecontrollerwillrestart.

EthernetInternetworktotoMS/TPLAN(default)

Parameter NotesLANnumber 1,4to9,11to119BACnetIP Canbedisabled

CurrentLoopInternetworktoMS/TPLAN

Parameter NotesLANnumber 1,4to9,11to119BACnetIP Canbedisabled

EthernetInternetworktoCurrentLoopLAN

Parameter NotesLANnumber 1,4to9,11to119BACnetIP CanbedisabledBACnetMSTP

Can be enabled e.g. forconnectionofPEHAdevices

Ethernet Internetwork to Current loopInternetwork

Note: Address no longer needs to be > 100.

Parameter NotesLANnumber 1,4to9,11to119BACnetIP CanbedisabledBACnetMSTP

Can be enabled e.g. forconnectionofPEHAdevices.

ManualconfigurationE.g. Ethernet Internetwork to Current loopInternetworkplusMS/TPLan

2 CONFIGURATION (continued)

IQ4WebUserGuide(TC201256).

Note: The IQ4NC always has a LAN to connect to the internetwork so cannot join another LAN on the internetwork.

Normal operation indicationTX RX

Fault indicationsTX Checkconnectiontodownstreamdevice

RX Checkconnectiontoupstreamdevice

Normal operation indicationRX TX

Fault indicationsRX Signal not reaching RX on downstream

deviceonnetwork–checkdevice/wiringTX No TX signal from upstream device on

network–checkdevice/wiring

TX(yellow)

RX(yellow)

TX(yellow)

RX(yellow)

Page 6: Installation Instructions - Confi guring IQ422 ... - Honeywell

6 IQ422,IQ4NC/00,IQ4NC/12ControllersInstallationInstructions-ConfiguringTG201265Issue12,24-Jul-2018.

IQ422, IQ4NC/00, IQ4NC/12� Installation�Instructions�-�Configuring

19 Set�up�Trend�Addressing

18 Set up Ethernet Access Across Routers (ifrequired)

20 Write�Address�Details�on�Label

2 CONFIGURATION (continued)

IftheLANistobebuiltacrossarouter(s)detailsofdevices(on each subnet) must be specified to enable cross-routercommunications.

UseIPTool–seestep12–tospecifyIPsettingsforupto20devicesintheRemoteTrendDeviceslist:

Parameter ValueIPAddress If using dynamic (DHCP) addressing:

Enterthehostnameoftheremotedevice.

If using static (fixed) addressing:EntertheIPAddressoftheremotedevice,intheformat:xxx.xxx.xxx.xxx

SubnetMask Thesubnetmaskfortheremotedevice,intheformat:xxx.xxx.xxx.xxx

IPToolManual(TE200638)

It is recommended that atleasttwodevicesfromeachsubnetare specified. For increased reliability details of additionaldevicesshouldbespecified.

IfstaticIPaddressingisbeingusedthelistshouldcontainthedeviceswiththelowestIPaddresses.

ThesamelistmustbecopiedtootherEINCtypedevicesonthenetwork.

Hint: Ticking the check box next to the Remote Trend Devices list retains the list in IP Tool, allowing it to be easily copied to other devices:

n q 4 e y e c p 4 1 2 3 4 5

Q422B_V53440388 O/S

00:10:70:0D:1E:92MAC Addr

IQ422-1010U5000Part No:

LAN

IP

Addr

422

IPToolManual(TE200638)IQTool Addresser Applet Manual(TE201299)

If�connecting�to�a�LAN�on�Ethernet�(or�standalone�mode): ▪ UseIPTool–seestep12–tosetthedeviceaddressand

LANnumber.

IQ4xx controllers are given a default device address andLANnumberinthefactory.Thedeviceaddressissetintherange11to119onarollingbasiswiththeLANnumbersetto20. Therefore itmay be necessary to set the address/LANnumberasrequired.

Parameter ValueLocalAddress 1,4to9,11to119

(mustbeuniqueonLAN)LocalLAN 1,4to9,11to119

(must be the same for all devicesrequiredtoformaLAN).

Note: Changing the LAN number and/or device address will cause the controller to reboot.

If�connecting�to�a�LAN�on�current�loop�(with�only�IQ4�type�controllers): ▪ Use SET’s IQTool Addresser Applet, and run the

DiscoveryWizard. ▪ Select either ‘Automatic Discovery’ (recommended) or

‘Manual Discovery’. If ‘Automatic Discovery’ is chosenyoushouldthenselect‘DuplicateAddressResolution’.

Automatic Discovery: Thetoolwilldiscoverthedevices,andattempttoresolveanyduplicateaddresses.

Manual Discovery: Either scan the bar code, or presstheServiceButtonforeachcontroller.

WARNING For /230 variants hazardousvoltagesexistwhentheunitispowered.Takesuitableprecautionsifpressingservicebutton.

Note: If the LAN is not as expected after discovery it could be because of installation related reasons, e.g. wiring faults, power failure, etc. Check the devices are operating correctly and repeat discovery. If there are duplicate addresses add the devices to the grid manually, using network address and serial number. If necessary use SET’s System View to set the LAN number, and IQTool to set the address.

If� connecting� to� a� LAN� on� current� loop� (with� pre� IQ4�controllers): ▪ UseSET’sIQToolAddresserApplettomanuallyaddthe

IQ4tothegridusingtheserialnumberandaddress. ▪ UseSET’sSystemViewtosettheLANnumber.

Deviceaddress(O/S)LANnumberFixedIPAddressorHostname(ifDCHP)

Page 7: Installation Instructions - Confi guring IQ422 ... - Honeywell

IQ422,IQ4NC/00,IQ4NC/12ControllersInstallationInstructions-ConfiguringTG201265Issue12,24-Jul-2018 7

Installation�Instructions�-�Configuring IQ422, IQ4NC/00, IQ4NC/12

21 Set�Current�Loop�Baud�Rate�(IQ4NCor../LANvariantsonly,ifcurrentloopnetworkbeingused)

22 Set�up�RS232�/�USB�Port�Addressing�(ifrequired)

23 Check�LAN�OK�Indicator�(notIQ4NC)

2 CONFIGURATION (continued)

IQToolMonitorAppletManual(TE201298)SETManual(TE200147)IQ4ConfigurationManual(TE201263)

Parameter RangeSupervisorport 0,4to9,11to119

Default=0localaccessonlyUSBEngineeringport

0,4to9,11to119Default=0temporarilytakesaddress125

UseSET’sIQToolMonitorApplettosettheSupervisorPortorUSBEngineeringPortasrequired.

IQToolMonitorAppletManual(TE201298)SETManual(TE200147)IQ4ConfigurationManual(TE201263)

If the IQ4xx is to provide connection to the network forsupervisors and tools it is necessary to setup the RS232SupervisorPortorUSBEngineeringPortasrequired.

Normal operation indication

LANbuiltOK

AttemptingtobuildLAN

Note: It is normal behaviour for LAN OK indicator to extinguish for up to 1 min after detecting baud rate, then illuminate.

Fault indication (EthernetLAN)

UnabletocommunicateonLAN.Note: Only applies if current loop is disabled or is not fitted.

Fault indication (CurrentLoopLAN)

every15s Longerthan2minutesindicatesLAN/internetworkcannotbebuilt.

▪ Checkbaudsettingsofalldevicesoncurrentloop–seestep21,andcheckalldeviceconnections.

▪ Ifstillflashing,fitloopback:

8584 86 87

RX- RX+TX- TX+

IfindicatorturnsOFF,deviceisfaulty.IfON,reconnectnetworkandswitchoffallotherdevicesonthenetwork.

▪ IfstillOFF,checknetworkcablingforshortcircuitswithamultimeter(NOTMegger).

▪ IfONswitchonotherdevicesinturnuntilfaultydevicefound (i.e.LANOKgoesOFF), inspect thatdevice todetermineandandcorrectthefault.

BydefaulttheIQ4xxwillautodetectthebaudrateinuseonthecurrentloop.Ifalldevicesaresettoautodetectthebaudratechosencannotbeguaranteed, inwhichcase itmaybenecessarytomanuallysetonedevicetoaknownrate.

Use SET’s IQTool Monitor Applet to disable autobaud andspecifythebaudrate.

Module Parameter RangeIQ Lan network

Autobaud 0(disabled)or1(enabled)Baud Rate 1k2,4k8,9k6,19k2,38k4

LAN�OK(green)

Page 8: Installation Instructions - Confi guring IQ422 ... - Honeywell

8 IQ422,IQ4NC/00,IQ4NC/12ControllersInstallationInstructions-ConfiguringTG201265Issue12,24-Jul-2018.

IQ422, IQ4NC/00, IQ4NC/12� Installation�Instructions�-�Confi�guring

24 Download�Strategy

25 Check IQ422 or IQ4NC on BACnet (If/BACorIQ4NCandBACnetprotocolcommunicationsrequired)

26 Test Inputs (NotIQ4NC/.../00)

2 CONFIGURATION (continued)

SETManual(TE200147)IQ4ConfigurationManual(TE201263)

SETManual(TE200147)

O

I

Switchoff Re-connect inputsOpencovers Closecovers

O

I

Switchon

Note:  An  Ethernet  connection  is  required  to  download  both strategy and backdrop fi les. Other connection types only allow download of strategy fi les.

Note: strategy download is not recommended over current loop with baud rate <9k6.

Note: SET will set up the controller’s date and time to that of the PC during download. However, they may be set up from a controller confi gured as timemaster.

ConfiguretheIQ4xxstrategyusingSET,andtestusingSET’ssimulationmode.

Use SET to download the strategy and backdrop file (ifrequired).

Use SET to check that the IQ4 BACnet functionality isoperatingbycheckingitappearscorrectlyintheSystemViewonitsBACnetnetwork.

S

Checkdigitalinputs Checkanalogueinputs

LED(yellow)

Page 9: Installation Instructions - Confi guring IQ422 ... - Honeywell

IQ422,IQ4NC/00,IQ4NC/12ControllersInstallationInstructions-ConfiguringTG201265Issue12,24-Jul-2018 9

Installation�Instructions�-�Confi�guring IQ422, IQ4NC/00, IQ4NC/12

28 Test Outputs (NotIQ4NC/.../00)

29 Connect Supervisors/Tools/DisplayPanels (ifrequired)

31 Backup�Strategy

33 Close Panel / Enclosure 32 Close�Rotating�Covers

30 Confi�gure�Web�Server

2 CONFIGURATION (continued)

Connect PCs (e.g. for supervisors/tools) and displays asdescribedin‘ConnecttoIQ4xx’onpage10.

Connectionofsupervisors,tools,displaypanelsetccanbemadedirectlytocontrollerviatheRS232LocalsupervisorPort,USBLocalEngineeringPort,WallbusPort,orEthernetport.ConnectioncanalsobemadeovertheTrendnetworkoverEthernetorthecurrentloop.

Use SET to upload the strategy and compare it with thestrategyheldbySET.

Note: An Ethernet connection is required to upload strategy and backdrop fi les. Other connection types only allow upload of strategy fi les.

SETManual(TE200147)

O

I

Switchoff Re-connect outputsOpencovers Closecovers

O

I

Switchon Checkdigitaloutputs Checkanalogueoutputs

LED(yellow)

LOAD

LED(yellow)

LOAD

ConnectiontotheIQ4webservercanbemadeviaHTTPand/or HTTPS protocol.Where HTTPS is used it will benecessarytoconfigureSSLcertificates.

Ifwebaccessisnotrequireditisrecommendedthatthewebserverisdisabledforsecurity.

IQ4ConfigurationManual(TE201263)SETManual(TE200147)

Page 10: Installation Instructions - Confi guring IQ422 ... - Honeywell

10 IQ422,IQ4NC/00,IQ4NC/12ControllersInstallationInstructions-ConfiguringTG201265Issue12,24-Jul-2018.

IQ422, IQ4NC/00, IQ4NC/12� Installation�Instructions�-�Confi�guring

1 Switch�Off��Power�to�IQ4xx 2 Open Top Cover (ifrequired)

3 Make Connection

O

I

PCviaLocalEngineeringPort(USB)Connect Directly to ControllerPCviaEthernetPort

RJ45 StandardEthernetcable(Cat5etwistedpair)max100m(109yds)

Connection use NotesIPTool ü

SET ü RequiresvCNCWebBrowser ü

Supervisor ü RequiresvCNC

PCviaLocalSupervisorPort(RS232)

CABLE/EJ101442

9wayfemaleDtype

RJ11

PC

ConnectiontotheIQ4xxcanbemadedirectlyviatheRS232LocalSupervisorPort,USBLocalEngineeringPort,orEthernetPort.Connectioncanalsobemadeoveranetwork(Ethernet).

Connection use NotesIPTool

SET ü

WebBrowser

Supervisor

Connection use NotesIPTool

SET ü

WebBrowser

Supervisor ü

IQView8viaLocalSupervisorPort(RS232)IQView8 requires its own power supply.

Note:  If  local  supervisor  port  address  is  ‘0’  (default) communication is limited to the IQ4xx.  If  non-zero, communication is possible over the entire network. 

RJ11 RJ11

RD/SDU-IQ2COMMSCABLE3M

USBcable

MicroBUSBconnector

3 CONNECT TO IQ4XX

IQView8

Page 11: Installation Instructions - Confi guring IQ422 ... - Honeywell

IQ422,IQ4NC/00,IQ4NC/12ControllersInstallationInstructions-ConfiguringTG201265Issue12,24-Jul-2018 11

Installation�Instructions�-�Configuring IQ422, IQ4NC/00, IQ4NC/12

3 Make Connection (continued)

3 CONNECT TO IQ4XX (continued)

RJ11

RJ11

24VdcSupply

XW/R/IQ

Mustuseexternal24Vsupply

Connect Directly to ControllerRD-IQ, SDU-xcite, IQView4 via Local Supervisor Port(RS232)

Connect via Ethernet Network ▪ EnsuretheIQ4xxisconnectedtotheEthernetnetwork.

▪ Connecttheotherdevice(e.g.networkdisplayorPC)tosameEthernetnetworkandensurean IPconnection isavailablebetweenitandtheIQ4xx.

▪ TomakeaconnectionwithSET,asupervisorordisplayensureavCNCisavailableinaTrenddeviceonthesameEthernet Trend network and connect to the vCNC asdescribedinthesupplieddocumentation.

Note: If connecting with IP Tool, the PC should be on the same Ethernet segment as the IQ4xx.

▪ To make a connection with a web browser run a webbrowseronthePCandaccesstheIQ4xxIPaddressorhostname.

XW/R/IQwirelesssensorreceiverviaLocalSupervisorPort(RS232)

PC Connection use NotesIPTool ü

SET ü RequiresvCNCWebBrowser ü

Supervisor ü RequiresvCNC

Note:  Set  local  supervisor  port  address  to  ‘0’  (default)  as communication is limited to the IQ422, IQ4NC/00, IQ4NC/12.

IQView4  requires  its  own  power supply.

RJ11RJ11

RD/SDU-IQ2COMMSCABLE3M

RJ11

RJ11

IQView4

RD-IQ

SDU-xcite

StandardEthernetcable (Cat5etwistedpair) max100m(109yds)

Hub/SwitchRouter

RJ45

RD-WMBviaWallbusPort

RD-WMB

TwistedPairCablemaximumlength60m(200ft)

IQView8

PC

Page 12: Installation Instructions - Confi guring IQ422 ... - Honeywell

12 IQ422,IQ4NC/00,IQ4NC/12ControllersInstallationInstructions-ConfiguringTG201265Issue12,24-Jul-2018.

IQ422, IQ4NC/00, IQ4NC/12� Installation�Instructions�-�Confi�guring

Please send any comments about this or any other Trend [email protected]

© 2018 HoneywellProductsandSolutionsSARL,ConnectedBuildingDivision.Allrightsreserved.ManufacturedforandonbehalfoftheConnectedBuildingDivisionofHoneywellProductsandSolutionsSARL,Z.A.LaPièce,16,1180Rolle,SwitzerlandbyitsAuthorizedRepresentative,TrendControlSystemsLimited.

TrendControlSystemsLimitedreservestherighttorevisethispublicationfromtimetotimeandmakechangestothecontenthereofwithoutobligationtonotifyanypersonofsuchrevisionsorchanges.

Trend�Control�Systems�LimitedSt.Mark’sCourt,NorthStreet,Horsham,WestSussex,RH121BW,UK.Tel:+44(0)1403211888,www.trendcontrols.com

2 Reset Controller

1 Isolate Power and Disconnect All I/O

3 Re-confi�gure�Controller

The factory reset will erase the strategy and reboot thecontroller into its original configuration.While the controlleriserasingthestrategy,theWatchdogandLANOKindicatorswill flashalternately.During the reboot all indicatorswill beON. Once this process has completed the Watchdog andLANOK indicatorswillgoOFF, leaving thePower indicatorON.Thisprocessmay takeup to10minutesdependingoncontrollertype.

Do� not� switch� off�� the� controller� until� the� process� has�completed.

�4� RESET�TO�DEFAULTS

Gotostep1onpage1.

Unplug the Ethernet cable and press and hold down theservice button. While continuing to hold down the button,switchonthecontroller.Ensurethebuttonremainspressedfor2to5safterpowerisswitchedon.

WARNING FOR /230 versions: Hazardousvoltages exist in this area when the unit ispowered.Thisoperationshouldonlybeperformedaftertakingsuitableprecautions

Thestrategy,usermodules(passwords,PINsetc),alarmlogs,andplotsarecleareddownandthefollowingparameterssettodefaults:

LANnumberoutstation addressIPaddressingmodeIP addresssubnetmaskUDPportidentifierRouter 1remoteTrenddevicesVirtualvCNCs.

Timeanddateareleftattheircurrentsettings.

O

I

2to5s

22 23 24 25

RX+

28 29

WMBRX- TX+ TX-

RX OK

4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 1 2 3

230V

19

4 510

24V0V 0V 0V 0V 0V 0V986 7

1 2 3

Press

22 23 24 25

RX+

28 29

WMBRX- TX+ TX-

RX OK

4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 1 2 3

230V

19

4 510

24V0V 0V 0V 0V 0V 0V986 7

1 2 3

Release

Followsteps1,2,4,5and8(onpages1to3)to:

▪ IsolatePower, ▪ OpenPanel, ▪ OpenRotatingCovers, ▪ DisconnectAllI/O, ▪ CloseRotatingCovers.