09/24/2010 40655422.xlsHVAC Page 1of15
BILLS OF QUANTITIESPROJECT NAME SAK ENGINEERING CONSULTANTS
LOCATION Bill No. - 00 (Rev. 0) BUILDIONG NAME DIVISION - 15 - Mech. Works (HVAC)
Amount Ref. DESCRIPTION Unit SR SR
1.0
Refrigerant : R- HFC 134 A1.1 ACWC-01 capacity 00 ton / 00 GPM No. - 1.2 ACWC-02 capacity 00 ton /00 GPM (STD BY) No. -
2.0 Chilled Water AHU
2.1 AHU-1 capacity 25 ton No. - 2.2 AHU-2 capacity 30 ton No. -
3.0 Chilled Water Pump Set
3.1 No. -
3.2 No. -
To Bill Summary
Unit Price Quantit
y
Packaged Air Cooled Rotary Screw Water ChillersSupply, Installation and setting to work including all required field wiring in rigid metal conduit from Chiller panel to local isolators, condenser anti corrosion coatings, spring vibration isolators, electrical isolators temperature controllers, testing and commissioning etc. as per equipment schedule
Supply, Installation and setting to work including all required field wiring in rigid metal conduit from AHU panel to local isolators, condenser anti corrosion coatings, spring vibration isolators, electrical isolators temperature controllers, testing and commissioning etc. Complete (modulating 3 way valve temperature controls) as per equipment schedule
Supply, installation and setting to work including all required field wiring, galvanized rigid metal conduit from Pump panel to local isolator & from Pump to Pump panel, electrical isolator, pump control panel, controls, spring type vibration isolators testing and commissioning etc., as per equipment schedule
CWPP-01 to 00 capacity 00 GPM @ 00 meter head (00 duty + 01 std by)
CWSP-01 to 00 capacity 00 GPM @ 00 meter head (00 duty + 01 std by)
09/24/2010 40655422.xlsHVAC Page 2of15
BILLS OF QUANTITIESPROJECT NAME SAK ENGINEERING CONSULTANTS
LOCATION Bill No. - 00 (Rev. 0) BUILDIONG NAME DIVISION - 15 - Mech. Works (HVAC)
Amount Ref. DESCRIPTION Unit SR SR
Unit Price Quantit
y
4.0 Roof Top Package Units:
4.1 Capacity 30 ton / 12000 CFM No. 820,000.00 - 4.2 Capacity 25 ton / 10000 CFM No. 73,000.00 - 4.3 Capacity 20 ton / 8000 CFM No. 60,000.00 - 4.4 Capacity 15 ton / 6000 CFM No. 45,500.00 - 4.5 Capacity 10 ton / 4000 CFM No. 30,000.00 -
5.0 DX Type Air Conditioning Unit
5.1 Ducted Split Air Conditioning Unit5.1.1 Capacity 5 ton No. 22,500.00 - 5.1.2 Capacity 4 ton No. 18,600.00 - 5.1.3 Capacity 3 ton No. 14,500.00 - 5.1.4 Capacity 2.5 ton No. 12,000.00 - 5.1.5 Capacity 2.0 ton No. 9,500.00 - 5.1.6 Capacity 1.5 ton No. 7,300.00 -
Supply, lift into position, install, test, set to work, and commission weatherproof Package Units, Units shall be complete with internal & external. Anti vibration mounts, and a spare set of filters shall be installed after commissioning. Installation shall include all required field wiring, power wiring from an adjacent disconnect switch (supplied and installed by others), weatherproof cables, galvanized rigid metal conduits, condensate drain, complete. operating at 380/3/60 Hz power supply including thermostat and as specified in the equipment schedule. Package unit time delay to be adjusted by the contractor.
Supply, lift into position, install, test, set to work, and commission DX type (mini-split A/C unit & ducted-split A/C unit) complete with thermostat with ACU outside, Installation shall include all required field control wiring, power wiring from an adjacent disconnect switch (supplied and installed by others), weatherproof cables, galvanized rigid metal conduits, refrigerant pipes and insulation, support for ACCU, etc, complete to set to work (as specified in the drawing). Out door refrigerant pipe shall have canvas with two coats of foster paint and supported by cable trays. All units to be suitable for externally locating and Nominal capacities indicated.
09/24/2010 40655422.xlsHVAC Page 3of15
BILLS OF QUANTITIESPROJECT NAME SAK ENGINEERING CONSULTANTS
LOCATION Bill No. - 00 (Rev. 0) BUILDIONG NAME DIVISION - 15 - Mech. Works (HVAC)
Amount Ref. DESCRIPTION Unit SR SR
Unit Price Quantit
y
To Bill Summary
5.2 Ducted Split Air Conditioning Unit5.2.1 Capacity 2.0 ton No. 6,000.00 - 5.2.2 Capacity 1.5 ton No. 5,000.00 -
No.5.3 Window AC No.
5.3.1 1.5 Tons No. 3,500.00 -
6.0 Extract Air Fans
6.1 EF-01 capacity 00 CFM @ 00" static (Roof top) No. - 6.2 EF-02 capacity 00 CFM @ 00" static (Inline) No. - 6.3 EF-03 capacity 100 CFM (wall mounted) No. -
7.0 Air curtains No. -
8.0 Duct Works8.1
8.1.1 20 GAUGE 185.00 -
8.1.2 22 GAUGE 160.00 -
8.1.3 24 GAUGE 145.00 -
8.1.4 26 GAUGE 140.00 -
8.2 125 -
Supply, lift into position, install, test, set to work and commission Extract Air Fans. The Fan Units shall have Anti-back draught shutters & internal Anti vibration mounts. Installation shall include all required power wiring from an adjacent disconnect switch weatherproof cables, galvanized rigid metal conduits, etc., complete. All fans are centrifugal and roof mounted and wall fans are wall mounted.
Supply, lift into position, install, test, set to work and commission air curtains operating at 230/1/60 Hz power supply, capacity 00 CFM as per equipment schedule, from Mars or equal manufacturer
Supply, installation and setting to work ductwork as per SMACNA Standards including full sealing of all joints, Rectangular volume control dampers, galvanized hangers and supports, leak testing, air balancing and testing and commissioning etc., complete For Air Conditioned Air & Exhaust air.
m2
m2
m2
m2
Supply and installation Aluminum cladding 0.6 mm thickness to exposed supply & return ducts including full sealing of all joints
m2
09/24/2010 40655422.xlsHVAC Page 4of15
BILLS OF QUANTITIESPROJECT NAME SAK ENGINEERING CONSULTANTS
LOCATION Bill No. - 00 (Rev. 0) BUILDIONG NAME DIVISION - 15 - Mech. Works (HVAC)
Amount Ref. DESCRIPTION Unit SR SR
Unit Price Quantit
y
To Bill Summary
09/24/2010 40655422.xlsHVAC Page 5of15
BILLS OF QUANTITIESPROJECT NAME SAK ENGINEERING CONSULTANTS
LOCATION Bill No. - 00 (Rev. 0) BUILDIONG NAME DIVISION - 15 - Mech. Works (HVAC)
Amount Ref. DESCRIPTION Unit SR SR
Unit Price Quantit
y
8.3 50 -
8.4 65 -
8.5 40 -
8.6
8.6.1 250 mm (10 Inch) diameter No. 135 - 8.6.2 200 mm (8 Inch) diameter No. 125 - 8.6.3 150 mm (6 Inch) diameter No. 115 -
9.0 Air Distributing Equipment
9.1
9.1.1 600 x 600 mm (24 x 24) Inch No. 650 - 9.1.2 450 x 450 mm (18 x 18) Inch No. 500 - 9.1.3 300 x 300 mm (12 x 12) Inch No. 350 - 9.1.4 225 x 225 mm (9 x 9) Inch No. 300 - 9.1.5 150 x 150 mm (6 x 6) Inch No. 250 -
9.2
9.2.1 600 x 600 mm (24 x 24) Inch No. 450 - 9.2.2 450 x 450 mm (18 x 18) Inch No. 350 - 9.2.3 300 x 300 mm (12 x 12) Inch No. 225 - 9.2.4 225 x 225 mm (9 x 9) Inch No. 175 - 9.2.5 150 x 150 mm (6 x 6) Inch No. 150 -
To Bill Summary
Supply and installation Supply and installation Acoustic lining fiber glass 25mm thick to supply and return duct up to 5 meter length and of density 24 kg / m3 from AFICO or equal
m2
Supply and installation Fiber glass Insulation 50mm thick 48 kg / m3 density from AFICO or equal to exposed supply & return ducts
m2
Supply and installation Fiber glass Insulation 25mm thick 24 kg / m3 density from AFICO or equal to indoor supply & return duct
m2
Supply, installation and setting to work Flexible duct1.2m long as per SMACNA Standards including full sealing of all joints, Round volume control dampers, galvanized hangers and supports, leak testing, air balancing and testing and commissioning etc., complete For Air Conditioned Air & Exhaust air. as per drawings. from SAFID or equal manufacturer
Supply and install Supply air Ceiling Diffuser SCD with internally insulated plenum boxes as per drawings. from GGC or equal
Supply and install Return air Ceiling Diffuser RCD, with internally insulated plenum boxes unless it is not connected to return duct, as per drawings. from GGC or equal
09/24/2010 40655422.xlsHVAC Page 6of15
BILLS OF QUANTITIESPROJECT NAME SAK ENGINEERING CONSULTANTS
LOCATION Bill No. - 00 (Rev. 0) BUILDIONG NAME DIVISION - 15 - Mech. Works (HVAC)
Amount Ref. DESCRIPTION Unit SR SR
Unit Price Quantit
y
09/24/2010 40655422.xlsHVAC Page 7of15
BILLS OF QUANTITIESPROJECT NAME SAK ENGINEERING CONSULTANTS
LOCATION Bill No. - 00 (Rev. 0) BUILDIONG NAME DIVISION - 15 - Mech. Works (HVAC)
Amount Ref. DESCRIPTION Unit SR SR
Unit Price Quantit
y
9.3
9.3.1 225 x 225 mm (9 x 9) Inch No. 275 - 9.3.2 150 x 150 mm (6 x 6) Inch No. 210 -
9.4
9.4.1 2 slot x 1 m No. - 9.4.2 3 slot x 1 m No. -
9.5
9.5.1 1000 x 150 mm No. - 9.5.2 1500 x 200 mm No. -
9.6
9.6.1 2 slot x 1 m No. - 9.6.2 3 slot x 1 m No. -
9.7
9.7.1 1000 x 150 mm No. - 9.7.2 1500 x 200 mm No. -
9.8
9.8.1 2000 x 600 mm No. -
9.8
9.8.1 2000 x 600 mm No. -
To Bill Summary
Supply and install Exhaust air Ceiling Diffusers ECD with plenum boxes internally insulated, as per drawings. from GGC or equal
Supply and install Supply Linear Slot Diffusers LSD including plenum boxes with internally insulation, as per drawings. from GGC or equal
Supply and install Linear Bar air Supply Grill LBSG including plenum boxes with internally insulation as per drawings. from GGC or equal
Supply and install Return Linear Slot Diffusers RLSD including plenum boxes with internally insulation unless it is not connected to a return duct, as per drawings. from GGC or equal
Supply and install Linear Bar air Return Grill LBRG including plenum boxes with internally insulation unless it is not connected to a return duct, as per drawings. from GGC or equal
Supply and install Intake air Sand Trap Louver STL as per drawings. from GGC or equal
Supply and install Exhaust air Sand Trap Louver ESTL as per drawings. from GGC or equal
09/24/2010 40655422.xlsHVAC Page 8of15
BILLS OF QUANTITIESPROJECT NAME SAK ENGINEERING CONSULTANTS
LOCATION Bill No. - 00 (Rev. 0) BUILDIONG NAME DIVISION - 15 - Mech. Works (HVAC)
Amount Ref. DESCRIPTION Unit SR SR
Unit Price Quantit
y
09/24/2010 40655422.xlsHVAC Page 9of15
BILLS OF QUANTITIESPROJECT NAME SAK ENGINEERING CONSULTANTS
LOCATION Bill No. - 00 (Rev. 0) BUILDIONG NAME DIVISION - 15 - Mech. Works (HVAC)
Amount Ref. DESCRIPTION Unit SR SR
Unit Price Quantit
y
10.0 Chilled Water Pipe works10.1
10.1.1 300 mm (12 Inch) dia. black steel sch. 40 ERW m - 10.1.2 250 mm (10 Inch) dia. black steel sch. 40 ERW m - 10.1.3 200 mm (8 Inch) dia. black steel sch. 40 ERW m - 10.1.4 150 mm (6 Inch) dia. black steel sch. 40 ERW m - 10.1.5 100 mm (4 Inch) dia. black steel sch. 40 ERW m - 10.1.6 75 mm (3 Inch) dia. black steel sch. 40 ERW m - 10.1.7 65 mm (2 ½ Inch) dia. black steel sch. 40 ERW m - 10.1.8 50 mm (2 Inch) dia. black steel sch. 40 ERW m - 10.1.9 40 mm (1 ½ Inch) dia. black steel sch. 40 ERW m -
32 mm (1¼ Inch) dia. black steel sch. 40 ERW m - 25 mm (1 Inch) dia. black steel sch. 40 ERW m -
10.2
10.2.1 300 mm (12 Inch) dia. black steel sch. 40 ERW m - 10.2.2 250 mm (10 Inch) dia. black steel sch. 40 ERW m - 10.2.3 200 mm (8 Inch) dia. black steel sch. 40 ERW m - 10.2.4 150 mm (6 Inch) dia. black steel sch. 40 ERW m - 10.2.5 100 mm (4 Inch) dia. black steel sch. 40 ERW m - 10.2.6 75 mm (3 Inch) dia. black steel sch. 40 ERW m - 10.2.7 65 mm (2 ½ Inch) dia. black steel sch. 40 ERW m - 10.2.8 50 mm (2 Inch) dia. black steel sch. 40 ERW m - 10.2.9 40 mm (1 ½ Inch) dia. black steel sch. 40 ERW m -
32 mm (1¼ Inch) dia. black steel sch. 40 ERW m - 25 mm (1 Inch) dia. black steel sch. 40 ERW m -
To Bill Summary
Supply, installation and setting to work chilled water pipes and fittings including galvanized hangers and supports, vibration isolators, expansion joints, thrust block, pressure testing, system testing and commissioning all necessary accessories to finalize work
10.1.1010.1.11
Supply, installation and setting to work exposed chilled water pipes and fittings including galvanized hangers and supports, vibration isolators, expansion joints, thrust block, pressure testing, system testing and commissioning and all necessary accessories to finalize work
10.2.1010.2.11
09/24/2010 40655422.xlsHVAC Page 10of15
BILLS OF QUANTITIESPROJECT NAME SAK ENGINEERING CONSULTANTS
LOCATION Bill No. - 00 (Rev. 0) BUILDIONG NAME DIVISION - 15 - Mech. Works (HVAC)
Amount Ref. DESCRIPTION Unit SR SR
Unit Price Quantit
y
09/24/2010 40655422.xlsHVAC Page 11of15
BILLS OF QUANTITIESPROJECT NAME SAK ENGINEERING CONSULTANTS
LOCATION Bill No. - 00 (Rev. 0) BUILDIONG NAME DIVISION - 15 - Mech. Works (HVAC)
Amount Ref. DESCRIPTION Unit SR SR
Unit Price Quantit
y
10.3
10.3.1 300 mm (12 Inch) dia. black steel sch. 40 ERW m - 10.3.2 250 mm (10 Inch) dia. black steel sch. 40 ERW m - 10.3.3 200 mm (8 Inch) dia. black steel sch. 40 ERW m - 10.3.4 150 mm (6 Inch) dia. black steel sch. 40 ERW m - 10.3.5 100 mm (4 Inch) dia. black steel sch. 40 ERW m - 10.3.6 75 mm (3 Inch) dia. black steel sch. 40 ERW m - 10.3.7 65 mm (2 ½ Inch) dia. black steel sch. 40 ERW m - 10.3.8 50 mm (2 Inch) dia. black steel sch. 40 ERW m - 10.3.9 40 mm (1 ½ Inch) dia. black steel sch. 40 ERW m - 10.3.10 32 mm (1 ¼ Inch) dia. black steel sch. 40 ERW m -
11.0 Chilled Water Valves and Accessories11.1 Item -
11.2 Item -
11.3
11.3.1 250 mm dia inlet/outlet connection No. - 11.3.2 No. -
11.4 Valves and Pipeline Ancillaries11.4.1 1 Item -
11.5 No. -
11.6 25 mm dia. Isolating gate valves - for dosing pot No. - 11.7 15 mm dia. drain valve for dosing pot No. -
To Bill Summary
Supply and install Thermal insulation to chilled water pipework. minimum density 64 kg/m3 pre-formed rigid fiber glass Thermal Insulation with factory applied foil reinforced Kraft laminate facing & 0.6 mm thick aluminium cladding for the external pipes
Supply, install, set to work and commission all necessary sundries, supports, etc., complete
Supply, install, set to work and commission chemical dosing pot assembly (00 litres) including 1" dia. ball valves for filling, inlet line, outlet line, and drain. Filling funnel with cap, automatic air vent with cock, and all other accessories needed to finalise the work as per drawings. From METITO or equal
Air Separator including gate valves for inlet, outlet and by-pass, automatic air vent with cock, drain valve, and othe accessories needed to finalise the work as per drawings. From TACO or equal
Expansion tank 00 liters, bladder type similar or equal to TACO
Supply, install, set to work and commission all valves and pipeline ancillaries etc. complete. From Nibco/Crane/Bell & Gossette
32 mm dia. water supply isolation valve for make-up water
09/24/2010 40655422.xlsHVAC Page 12of15
BILLS OF QUANTITIESPROJECT NAME SAK ENGINEERING CONSULTANTS
LOCATION Bill No. - 00 (Rev. 0) BUILDIONG NAME DIVISION - 15 - Mech. Works (HVAC)
Amount Ref. DESCRIPTION Unit SR SR
Unit Price Quantit
y
09/24/2010 40655422.xlsHVAC Page 13of15
BILLS OF QUANTITIESPROJECT NAME SAK ENGINEERING CONSULTANTS
LOCATION Bill No. - 00 (Rev. 0) BUILDIONG NAME DIVISION - 15 - Mech. Works (HVAC)
Amount Ref. DESCRIPTION Unit SR SR
Unit Price Quantit
y
11.8 25 mm dia. drain valve No. - 11.9 100 mm dia. check valves No. - 11.10 100 mm dia. butterfly valve No. - 11.11 50 mm dia. pressure relief valve No. - 11.12 150 mm dia. facia pressure gauge & gauge ports No. - 11.13 100 mm dia. pipeline Y - Strainer No. - 11.14 15 mm dia. Automatic air vent No. - 11.15 No. -
12.0 Chilled water pump valves and accessories12.1 15 mm dia. drain valve No. - 12.2 150 mm dia. triple duty valve No. - 12.3 50 mm dia. pressure relief valve No. - 12.4 150 mm dia. butterfly valve No. - 12.5 100 mm dia. check valves No. - 12.6 150 mm dia. Y-Strainer No. - 12.7 150 mm dia. fascia pressure gauge No. - 12.8 No. -
13.0 Flushing and Water Treatment ChemicalsItem -
14.0 item -
AA Mechanical Identification:item -
BB Civil Worksjob -
To Bill Summary
100 mm dia. flexible connectors for the pump (to be pump connection size)
100 mm dia. flexible connectors for the pump (to be pump connection size)
Supply, installation and setting to work including all necessary sundries, water requirement and proper waste water disposal, laboratory test, etc., complete. From Metito or equal
Supply, installation, test and setting to work condensate drain piping of AC machines connected to nearest drain point with fittings and accessories completely
Supply and install approved services identification tags, markings and flow direction arrows.
Provide for associated civil works required for the Mechanical Services Installation as described and listed in this B of Q and as shown on the drawings. The works shall include the formation of all holes for the services to pass through etc., and the sealing of the holes once the services have been installed. Provide structural supports / framing for the WU, EU & ACU, EF at height such as to allow for the installation of P- trap for condensate drain lines.
09/24/2010 40655422.xlsHVAC Page 14of15
BILLS OF QUANTITIESPROJECT NAME SAK ENGINEERING CONSULTANTS
LOCATION Bill No. - 00 (Rev. 0) BUILDIONG NAME DIVISION - 15 - Mech. Works (HVAC)
Amount Ref. DESCRIPTION Unit SR SR
Unit Price Quantit
y
BILL SUMMARY
00 -Bill #00 -Div.15 -HVAC -Rev.0 -Page 1 of 8
00 -Bill #00 -Div.15 -HVAC -Rev.0 -Page 2 of 8
00 -Bill #00 -Div.15 -HVAC -Rev.0 -Page 3 of 8
00 -Bill #00 -Div.15 -HVAC -Rev.0 -Page 4 of 8
00 -Bill #00 -Div.15 -HVAC -Rev.0 -Page 5 of 8
00 -Bill #00 -Div.15 -HVAC -Rev.0 -Page 6 of 8
00 -Bill #00 -Div.15 -HVAC -Rev.0 -Page 7 of 8
00 -Bill #00 -Div.15 -HVAC -Rev.0 -Page 8 of 8
09/24/2010 40655422.xlsHVAC Page 15of15
BILLS OF QUANTITIESPROJECT NAME SAK ENGINEERING CONSULTANTS
LOCATION Bill No. - 00 (Rev. 0) BUILDIONG NAME DIVISION - 15 - Mech. Works (HVAC)
Amount Ref. DESCRIPTION Unit SR SR
Unit Price Quantit
y
To General Summary