07b Busbar Differential
Transcript of 07b Busbar Differential
-
8/13/2019 07b Busbar Differential
1/50
Protection EngineeringAnd Research Laboratories
Session VII :
Busbar Protection
Dr. G. Pradeep Kumar
Training on Power System Element Protection,
9th
& 17th
March, 2007 at L&T Manappakam, Chennai.
-
8/13/2019 07b Busbar Differential
2/50
2007 Protection Engineering And Research Laboratories
2
17thMarch 2007
Contents
Introduction
Frame leakage protection
High impedance bus differential
Low impedance bus differential
Busbar configurations
Breaker failure protection
-
8/13/2019 07b Busbar Differential
3/50
2007 Protection Engineering And Research Laboratories
3
17thMarch 2007
Introduction
-
8/13/2019 07b Busbar Differential
4/50
2007 Protection Engineering And Research Laboratories
4
17thMarch 2007
Busbar Protection
Busbar faults are very rare.
Busbar protection not provided always
Without busbar protection
No dislocation of system due to accidental operation of
busbar protection.
Slow fault clearance.
Busbar faults are cleared by remote time delayed
protection on circuits feeding the faults:
Time delayed over current or
Time delayed distance protection
-
8/13/2019 07b Busbar Differential
5/50
2007 Protection Engineering And Research Laboratories
5
17thMarch 2007
Busbar Faults Are UsuallyPermanent
CAUSES :
Insulation failures
Circuit breaker failures
Falling debris
Isolators operated outside their ratings
Safety earths left connected
Current transformer failures
THEREFORE :
Circuit breakers should be tripped and locked out by busbar
protection
-
8/13/2019 07b Busbar Differential
6/50
2007 Protection Engineering And Research Laboratories
6
17thMarch 2007
Busbar Protection
BUSBARZONE
F2F1
WITH BUSBAR PROTECTION
Fast clearance by breakers at the busbars
Where busbars are sectionalised, protection can limit the
amount of system disruption for a busbar fault
-
8/13/2019 07b Busbar Differential
7/50
2007 Protection Engineering And Research Laboratories
7
17thMarch 2007
Busbar Protection
RELIABILITY Failure could cause widespread damage to the substation
STABILITY
False tripping can cause widespread interruption of supplies
to customers
DISCRIMINATION
Should trip the minimum number of breakers to clear the
fault
SPEED
To limit damage and possible power system instability
-
8/13/2019 07b Busbar Differential
8/50
2007 Protection Engineering And Research Laboratories
8
17thMarch 2007
Methods of Providing BusbarProtection
Frame to Earth (Leakage) Protection
Directional Comparison Protection
Differential Protection : High Impedance
Low Impedance
-
8/13/2019 07b Busbar Differential
9/50
2007 Protection Engineering And Research Laboratories
9
17thMarch 2007
Frame LeakageProtection
-
8/13/2019 07b Busbar Differential
10/50
2007 Protection Engineering And Research Laboratories
10
17thMarch 2007
Can only detect an earth fault
Involves measuring fault current from switchgear frame
to earth
Switchgear insulated by standing on concrete plinth
Only one earthing point allowed on switchgear
C.T. mounted on single earth conductor used to energiseinstantaneous relay
All cable glands must be insulated
Frame Earth Protection Scheme
-
8/13/2019 07b Busbar Differential
11/50
2007 Protection Engineering And Research Laboratories
11
17thMarch 2007
Current Distribution for ExternalFault
Outgoing feeder
Switchgear frameSwitchgear framebonding bar
Generator
SystemearthingresistorEarth bar
Frame-leakage currenttransformer
Earthing electroderesistance (< 1)
Frame insulationresistance to earth(> 10)
IF = I1+ I2
I1+ I2
I1I2
I1
-
8/13/2019 07b Busbar Differential
12/50
2007 Protection Engineering And Research Laboratories
12
17thMarch 2007
Frame Leakage Busbar Protection
Simple, economical.
Suitable for phase segregated indoor metal-clad
switchgear. Only E/F protection required.
Setting of instantaneous E/F relay (64)
= < 0.3 IF(min)
Disadvantages
Insulation of switchgear frame and between sections.
Insulation of cable glands to prevent spurious currents
during through faults.
-
8/13/2019 07b Busbar Differential
13/50
-
8/13/2019 07b Busbar Differential
14/50
2007 Protection Engineering And Research Laboratories
14
17thMarch 2007
Frame Leakage Protection
Check Feature
To differentiate between a genuine busbar fault and a
fault in the secondary winding of a c.t.
The check feature provides a second line of defence.
The check relays pick up for both internal and external
faults.
Both check and discriminating relays must operate
before tripping can occur.
-
8/13/2019 07b Busbar Differential
15/50
2007 Protection Engineering And Research Laboratories
15
17thMarch 2007
Frame Leakage Protection
Check Feature
The various methods of obtaining the check feature are,
Neutral check provided by a relay energised from a single
c.t. in the power system neutral.
Residual check provided by a relay energized from a
residually connected c.t. on the busbar incomers.
Residual voltage check provided by a voltage relay
energized from a broken delta v.t. supply.
Check relays are normally self-reset in order to avoid
having to reset the relay after each external fault.
-
8/13/2019 07b Busbar Differential
16/50
2007 Protection Engineering And Research Laboratories
16
17thMarch 2007
Single Zone Frame - EarthProtection with Neutral Check
Switchgear frame
Neutral check relay
Trip all breakerscircuit
Frame-earthfault relay
G H J K
64
64
CH
+
-
8/13/2019 07b Busbar Differential
17/50
2007 Protection Engineering And Research Laboratories
17
17thMarch 2007
High Impedance BusDifferential
-
8/13/2019 07b Busbar Differential
18/50
2007 Protection Engineering And Research Laboratories
18
17thMarch 2007
G H
AB
CN
Differential relay
87A 87A 87A
Circulating CurrentDifferential Scheme
-
8/13/2019 07b Busbar Differential
19/50
2007 Protection Engineering And Research Laboratories
19
17thMarch 2007
High Impedance Protection
This is a versatile and reliable protection
system applied to many different busbar
configurations.
Simple system to apply and extend.
High sensitivity for phase and earth faults.
Extremely stable for external faults.
-
8/13/2019 07b Busbar Differential
20/50
2007 Protection Engineering And Research Laboratories
20
17thMarch 2007
High Impedance Protection
CT requirements:
Equal ratios
Class X
Requires stabilising resistors, RST
May require non-linear resistors (Metrosils)
If CT requirements are met, scheme
performance may be predicted by calculation
without heavy current conjunctive tests
-
8/13/2019 07b Busbar Differential
21/50
2007 Protection Engineering And Research Laboratories
21
17thMarch 2007
High Impedance BusbarProtection
RST
METROSIL
87
-
8/13/2019 07b Busbar Differential
22/50
2007 Protection Engineering And Research Laboratories22
17thMarch 2007
Effective Setting
Since in each zone of protection there are several CTs inparallel with the relay and each other, the combined CT
magnetising currents will increase the primary operating
current (P.O.C).
P.O.C. = CT ratio (IR + INLR + nIM)where :-
IR = Relay setting current
IM = CT magnetising current (one CT at relay
setting voltage)n = Number of paralleled CTs
INLR= Non linear resistor current at relay setting
voltage
-
8/13/2019 07b Busbar Differential
23/50
2007 Protection Engineering And Research Laboratories23
17thMarch 2007
Primary Operating Current(P.O.C)
The value of primary operating current should be
around 30% of minimum fault current available.
This ensures sufficient relay current during internal
fault conditions for high speed operation.
-
8/13/2019 07b Busbar Differential
24/50
2007 Protection Engineering And Research Laboratories24
17th
March 2007
Through Fault Stability
Busbar protection stability limit is based on maximum
through fault current.
Generally this value is derived from the rating of the
associated switchgear irrespective of existing fault
level, since it can be expected that system can growup to limit of rating.
-
8/13/2019 07b Busbar Differential
25/50
2007 Protection Engineering And Research Laboratories25
17th
March 2007
Check Feature
Provided by duplication of primary protection using second setof CTs on all circuits other than bus section and coupler units.
Check system forms one zone only, covering whole of busbar
systems and not discriminating between faults on various
sections.
Check zone
Zone A Zone B87A
87A
87A
-
8/13/2019 07b Busbar Differential
26/50
2007 Protection Engineering And Research Laboratories26
17th
March 2007
CT Wiring Supervision
Open circuit connections between CTs and relay circuit
result in unbalance currents which may operate the
protection.
Supervision is applied by a voltage relay across
differential relay circuit.
Supervision relay is time delayed, gives alarm and also
shorts out bus wires to protect differential relay circuit.
Typical effective setting is 25 primary amps or 10% of
lowest circuit rating, whichever is greater.
-
8/13/2019 07b Busbar Differential
27/50
2007 Protection Engineering And Research Laboratories27
17th
March 2007
M3
SP
M3
SP
M2
SPSP
SP
M4M3M21
Z
V
Z
V
Z
V
R
V
relaynsupervisiotheoperatecurrent tobalance-of-OutVsettingrelaynsupervisioIf
)Z||Z||Z||(RV
relaynsupervisiobymeasuredVoltage
CT1
Supervisionrelay
V
RST
RR
RZM2 ZM3 ZM4
I1
I1
I2 I3 I4
CT Wiring Supervision
-
8/13/2019 07b Busbar Differential
28/50
2007 Protection Engineering And Research Laboratories28
17th
March 2007
Differential Relay CircuitA
B
C
N
Zone bus wires
95X
95X
95X
Bus wire short
contacts
Supervision
relay
95
Stabilizingresistors
87 87 87
v v v
Non-linearresistors
-
8/13/2019 07b Busbar Differential
29/50
2007 Protection Engineering And Research Laboratories29
17th
March 2007
Current Transformer Wiring
Lead burdens between various sets of CTs must be kept
low. Usually bus wires are run in closed ring between
breaker control panels.
Typical route is :-
CTs to marshalling kiosk
Marshalling kiosk to isolator auxiliaries
Loop between marshalling kiosks
Normal conductor size is 2.5mm2
-
8/13/2019 07b Busbar Differential
30/50
2007 Protection Engineering And Research Laboratories30
17th
March 2007
Low Impedance BusDifferential
-
8/13/2019 07b Busbar Differential
31/50
2007 Protection Engineering And Research Laboratories31
17th
March 2007
Low Impedance Busbar Protection
Biased differential characteristics provides stability forthrough fault.
Modular scheme design allows relays to relate to each
circuit and function of the protection.
Optic inter module communication in numerical relays
High sensitivity for phase and earth faults. Protection for
each phase can be relatively independent.
Earlier schemes were less stable than high impedance
schemes. Modern schemes incorporate saturation
detectors and are extremely stable.
-
8/13/2019 07b Busbar Differential
32/50
2007 Protection Engineering And Research Laboratories32
17th
March 2007
Low Impedance Busbar Protection
Current transformers can be :
of different ratio
of relatively small output
shared with other protections
Current transformer secondary circuits are not
switched.
CT burden reduced in distributed architecture
Continuous supervision of CT circuits and constant
monitoring of vital circuits are included.
-
8/13/2019 07b Busbar Differential
33/50
2007 Protection Engineering And Research Laboratories33
17th
March 2007
Modular Low Impedance RelaySingle Bus Protection
F1 F2 F3 F4
Z2Z1
BS
FM1
FM2
FM3
FM4BSM
Z1ZCK Z2ZCK
ZCKZ1 Z2
-
8/13/2019 07b Busbar Differential
34/50
2007 Protection Engineering And Research Laboratories34
17th
March 2007
Modular Low Impedance RelayDouble Bus Protection
Z1
BCM1
Z3
Z2
Z4
BS
BC1 BC2F1 F2 F3 F4
BCM2
FM1
FM2
FM3
FM4BSM
Z1
Z3ZCK
Z2
Z4ZCK
Z1 Z2 Z4Z3 ZCK
-
8/13/2019 07b Busbar Differential
35/50
2007 Protection Engineering And Research Laboratories35
17th
March 2007
Bus Arrangements
-
8/13/2019 07b Busbar Differential
36/50
2007 Protection Engineering And Research Laboratories36
17th
March 2007
Effect of C.T. Location on BusbarProtection Performance
Circuitprotection
Busbar
protection
Overlapping C.T.s
Circuitprotection
Busbarprotection
Interlocked
over currentrelay
All C.T.s on line sideof circuit breaker
All C.T.s on Busbar sideof circuit breaker
Busbarprotection
Circuit
protection
Interlockedover currentrelay
-
8/13/2019 07b Busbar Differential
37/50
2007 Protection Engineering And Research Laboratories37
17th
March 2007
Typical Double BusbarArrangement
60MW
Generators
75MVA132/13.8kVTransformers
132kV
-
8/13/2019 07b Busbar Differential
38/50
2007 Protection Engineering And Research Laboratories38
17th
March 2007
Zones of Protection forDouble Bus Station
Zone G Zone H
Zone J
BC BC
BS
Typical Feeder Circuits
-
8/13/2019 07b Busbar Differential
39/50
2007 Protection Engineering And Research Laboratories39
17th
March 2007
Isolator Auxiliary Switches
R
M
A B C D
a b c d
r
Buswires
In order to maintain stability
on switching, auxiliary switches
should :
1) Close before the isolator
closes
2) Open after the isolator
opens
m
-
8/13/2019 07b Busbar Differential
40/50
2007 Protection Engineering And Research Laboratories40
17th
March 2007
Tripping Circuits
One trip relay is required for each feeder breaker
Two trip relays for each bus section or bus coupler
breakers.
The trip relays have to be lock-out type (hand reset)
Both main and check relays must be energized for the
tripping relays to trip all breakers associated with that
zone.
-
8/13/2019 07b Busbar Differential
41/50
2007 Protection Engineering And Research Laboratories41
17th
March 2007
Double Busbar with TransferFacilities
Main
Reserve / Transfer
By-passIsolator
By-passIsolator
-
8/13/2019 07b Busbar Differential
42/50
2007 Protection Engineering And Research Laboratories42
17th
March 2007
Triple Busbar
Main
TransferCB
Transfer
Reserve
TransferCB
-
8/13/2019 07b Busbar Differential
43/50
2007 Protection Engineering And Research Laboratories43
17th
March 2007
1 Breaker Scheme
Bus 1
Bus 2
-
8/13/2019 07b Busbar Differential
44/50
2007 Protection Engineering And Research Laboratories44
17
th
March 2007
1 Breaker Bus Protection
87
87
-
8/13/2019 07b Busbar Differential
45/50
2007 Protection Engineering And Research Laboratories45
17
th
March 2007
Mesh Busbar
T1
F1 F3
T4
T3
T2
F4 F2
-
8/13/2019 07b Busbar Differential
46/50
2007 Protection Engineering And Research Laboratories46
17
th
March 2007
Mesh Busbar Protection
T1
F1 F3
T4
T3
T2
F4 F2
87
R1
87
R3
87R4
87R2
-
8/13/2019 07b Busbar Differential
47/50
2007 Protection Engineering And Research Laboratories47
17thMarch 2007
Breaker Failure Protection
-
8/13/2019 07b Busbar Differential
48/50
2007 Protection Engineering And Research Laboratories
48
17thMarch 2007
Breaker Fail Protection
Detects failure of a circuit breaker to interrupt the fault
current even after the protection relay issues a trip
command
Where breaker fail protection is applied to a system,
back tripping of associated breakers is required in the
event of a breaker failure.
Often, breaker fail protection is arranged in conjunction
with busbar protection tripping circuits to initiate trippingof breakers on a busbar zone associated with the failed
breaker.
-
8/13/2019 07b Busbar Differential
49/50
2007 Protection Engineering And Research Laboratories
49
17thMarch 2007
Breaker Fail Protection
Inst.O/CEnable
Td
Breaker FailureTrip Initiation
+ -
PR Trip
-
8/13/2019 07b Busbar Differential
50/50
2007 Protection Engineering And Research Laboratories 17th March 2007
Thank you