Topic 3 Industrial Energy Management
description
Transcript of Topic 3 Industrial Energy Management
26/10/2014
1
BEF 44903 IndustrialIndustrial
Power Systems
Topic 3
BEF44903
Topic 3Topic 3Topic 3Topic 3
INDUSTRIAL ENERGY MANAGEMENT
1
BEF 44903 Industrial
Outline
Power Losses in Industrial Power SystemsIndustrial
Power Systems
Topic 3 Loss Reduction Methods Energy Efficiency in Industrial Power
Systems Battery Application in Industrial Power
SystemsSystems Application of Uninterruptible Power Supplies
(UPS)
2
26/10/2014
2
BEF 44903 Industrial
Power Losses in IPS
• Losses occurred in the electrical
• Losses due to theft of energyIndustrial
Power Systems
Topic 3
in the electrical elements mainly comprises of ohmic and iron losses
• Mostly depends on electrical
theft of energy and unrecovered billed amount
• Also called as commercial Losses
loading
Technical losses
Non-technical losses
3
BEF 44903 Industrial
Power Losses in IPS
TECHNICALIndustrial Power Systems
Topic 3
TECHNICAL LOSSES
Current dependent
Voltage dependent
Series Losses
Shunt Lossesdependent
Copper Losses
dependent
Iron Losses
Dielectric Losses
Corona Losses
Losses Losses
4
26/10/2014
3
BEF 44903 Industrial
Power Losses in IPS
TX
I2R
FD
Industrial Power Systems
Topic 3
I2R
I2R I2R I2R
Power Transformer
Power CableFeeder
I2R
Power Cable
I2R I2R I2R
Lighting L Motor Loads M Heating Elements H5
BEF 44903 Industrial
Power Losses in IPS
Line Losses are a result of passing current through an imperfect conductor such as
Industrial Power Systems
Topic 3
copper. The line losses can be calculated based on
the measured current load as:Ploss = I * (I * r/l * L) = I2RWhere,,I is currentr/l is resistance / KilometreL is length of cable in Kilometres
6
26/10/2014
4
BEF 44903 Industrial
Power Losses in IPS
For a 3-phase system, the losses for each phase are calculated separately according to h dIndustrial
Power Systems
Topic 3
the measured current as:Ploss total = Ploss-a + Ploss-b + Ploss-c
Assumptions made: All load currents maintain a constant ratio to
ccbbaa RIRIRI 222
the total current The voltage at every source bus remain
constant in magnitude Power factor remains constant
7
BEF 44903 Industrial
Power Losses in IPS
It is not possible to measure the distribution losses incurred by individual customers due
d l f hIndustrial Power Systems
Topic 3
to many unexpected losses factors such as network utilisation, network configuration, the shape of the load profile and the level of reactive power support.
Thus, an estimated losses calculation app oach sing Load Facto (LF) and Loadapproach using Load Factor (LF) and Load Loss Factor (LLF) is introduced.
8
26/10/2014
5
BEF 44903 Industrial
Power Losses in IPS
Load Factor – Ratio of average demand over maximum demand.
Industrial Power Systems
Topic 3
Load Loss Factor – Ratio of average power loss over power loss at maximum demand
demandMaximum
kW)(in demandAverage LF
periodduring(kWh)lossActualLLF
Relationship between LF and LLF:LLF = k * LF + (1 - k) * LF2
(kWh)current maximumat Loss
pg( ) LLF
9
BEF 44903 Industrial
Power Losses in IPS
where k = a constant, typically 0.1, 0.2 or 0.3
Industrial Power Systems
Topic 3
Typically, k = 0.3 for subtransmission systems k = 0.2 for medium voltage feeders and
distribution substations k = Sample sections of the network can be
analysed to produce an estimate of the k factoranalysed to produce an estimate of the k factor applicable for the rest of the system
10
26/10/2014
6
BEF 44903 Industrial
Power Losses in IPS
Loss in a feeder for a given period (which is one month in this case) is given by:
Industrial Power Systems
Topic 3
Technical loss in MU = I2 × R × L × LLF ×24 × 30 × 10−9
Where,I = Load in ampereR = Resistance of the conductor in ohms/ kilometreL = Length of the feeder in kilometresLLF = Load loss factor
Yearly technical loss for 3- feeder in MU,= 3 x I2 x R x L x LLF x 8760 / 10911
BEF 44903 Industrial
Power Losses in IPS
Example 3.1 Calculate LF, LLF,
Industrial Power Systems
Topic 3
and k. Calculate technical
losses per month. Consider following parameters: 300mm2 = 0.1173/km 240mm2 = 0.1267 /km 120mm2 = 0.2176 /km L1 = 1.2 km, L2 =
0.5km, L3 = 2.4km12
26/10/2014
7
BEF 44903 Industrial
Power Losses in IPS
Technical loss of Transformer in MU for year = {No load loss + [(% loading in p.u.)2
* d C l * ]} * 2 * 36 / 06Industrial Power Systems
Topic 3
* rated Cu. loss * LLF]} * 24 * 365 / 106
Example 3.2: What is the total MU loss?
13
BEF 44903 Industrial
Loss Reduction Methods
Proper Sizing Regular MaintenanceIndustrial
Power Systems
Topic 3
p g Maintenance
Convert LV to HV Lines
MinimiseOverload
Improve Power Factor
14
26/10/2014
8
BEF 44903 Industrial
Energy Efficiency in Industrial Power Systems
Reduce iIndustrial
Power Systems
Topic 3
Energy efficiency
consumption
Reduce CO2emission
Optimisecost
Improve reliability
15
BEF 44903 Industrial
Energy Efficiency in Industrial Power Systems
Transport – 27%Industrial
Power Systems
Topic 3
Residential – 16%
Commercial – 8%
Industrial – 49%
16
26/10/2014
9
BEF 44903 Industrial
Energy Efficiency in Industrial Power Systems
Save energy
• Proper production planning to avoid peak hour charges
• Use automation systemIndustrial Power Systems
Topic 3
Reduce energy
use
energy cost
Energy reliability
Use automation system in the plant
U How to increase energy
efficiency?
• Avoid energy losses• Proper maintenance• Treat PQ properly
• Use energy efficient devices/ equipment
• Proper control and monitoring
• Use variable speed drives17
BEF 44903 Industrial
Energy Efficiency in Industrial Power Systems Some of energy efficiency classes for LV
motors:Industrial
Power Systems
Topic 3
18
26/10/2014
10
BEF 44903 Industrial
Energy Efficiency in Industrial Power Systems Energy savings based on reducing fan speed
by half:Industrial
Power Systems
Topic 3
19
BEF 44903 Industrial
Energy Efficiency in Industrial Power Systems Load management strategy:
Industrial Power Systems
Topic 3
20
26/10/2014
11
BEF 44903 Industrial
Energy Efficiency in Industrial Power Systems Monitoring architecture for a small site:
Industrial Power Systems
Topic 3
21
BEF 44903 Industrial
Battery Application in Industrial Power Systems
UPSIndustrial
Power Systems
Topic 3
Solar power systemVoltage support
Battery Applications
22
Tele-communication
Emergency Control/lighting
26/10/2014
12
BEF 44903 Industrial
Battery Application in Industrial Power Systems
Lead acid (Mostly used in
• Most economical• Not much sensitive to
temperature• 5-7 Years lifespanIndustrial
Power Systems
Topic 3
IPS)p
• Needs special battery room
Nickel Cadmium
• Most expensive • 20 years lifespan• Large size as
compared to same Ah
Sealed Mainte-nanceFree
• No maintenance• User friendly• Very sensitive to
temperature• Lowest lifespan23
BEF 44903 Industrial
Battery Application in Industrial Power Systems Why battery sizing?
Ensure the loads being supplied or the powerIndustrial Power Systems
Topic 3
Ensure the loads being supplied or the power system being supported are adequately provided by the battery for the period of time (i.e. autonomy) for which it is designed.
Improper battery sizing can lead to poor autonomy times, permanent damage to battery cells from over-discharge low load voltages etccells from over discharge, low load voltages, etc.
Methodology – Normal industry practice and technical standards: IEEE Std 485 (Lead-Acid) and IEEE Std 1115 (Nickel-Cadmium), based on the ampere-hour method.
24
26/10/2014
13
BEF 44903 Industrial
Battery Application in Industrial Power Systems Steps to be considered in battery sizing:
Step 1 – Collect load data to be supported byIndustrial Power Systems
Topic 3
Step 1 Collect load data to be supported by the battery
Step 2 – Construct load profile and calculate the design load (VA) and design energy (VAh)
Step 3 – Select battery type and determine the characteristics of the cellSt 4 S l t b f b tt ll t b Step 4 – Select number of battery cells to be connected in series
Step 5 – Calculate required Ampere-hour (Ah) capacity of the battery
25
BEF 44903 Industrial
Battery Application in Industrial Power Systems Design load (VA) (Step 2):
Cgpd kkSS 11Industrial
Power Systems
Topic 3 Design energy demand (VAh) (Step 2):
where, Sp is the peak load apparent power (VA)
gp
Cgtd kkEE 11
Et is the total load energy (VAh) kg is a contingency for future load growth (%)
(10%) kc is a design margin (%) (10%)
26
26/10/2014
14
BEF 44903 Industrial
Battery Application in Industrial Power Systems Factors to be considered for battery type
selection (Step 3):Industrial
Power Systems
Topic 3 Physical characteristics Expected life of cell Frequency and depth of discharge Ambient temperature Charging characteristicsg g Maintenance requirements Ventilation requirements Seismic factors (vibration and shock)
27
BEF 44903 Industrial
Battery Application in Industrial Power Systems Most common number of cells (Step 4):
Rated Voltage Lead-Acid Ni-CdIndustrial Power Systems
Topic 3
g
12 V 6 9 – 10
24 V 12 18 – 20
48 V 24 36 – 40
125 V 60 92 – 100
250 V 120 184 – 200
28
26/10/2014
15
BEF 44903 Industrial
Battery Application in Industrial Power Systems Number of cells calculation (Step 4):
lDC VVN max,1 lDC VV
N min,1Industrial
Power Systems
Topic 3
where,
Nmax/ Nmin is the max. or min. of cells VDC is the nominal battery voltage
V i th l d lt t l (%)
c
lC
VN a,
max
eod
lC
VN ,
min
Vl,max is the max. load voltage tolerance (%) Vl,min is the min. load voltage tolerance (%) VC is the cell charging voltage (charge cycle) Veod is the cell end of discharge voltage
29
BEF 44903 Industrial
Battery Application in Industrial Power Systems Min. battery capacity required (Step 5):
tcad kkkEC
)1()1(Industrial
Power Systems
Topic 3
where,
Cmin is the min. battery capacity (Ah) Ed is the design energy over autonomy time (VAh) V is the nominal battery voltage
dodDC
tcad
kVC
)()(min
VDC is the nominal battery voltage ka is a battery ageing factor (%) (25%) kc is a capacity rating factor (%) (10%) kt is a temperature correction factor kdod is the max. depth of discharge (%) (80%)30
26/10/2014
16
BEF 44903 Industrial
Battery Application in Industrial Power Systems IEEE Std 485-1997
reIndustrial Power Systems
Topic 3
acto
rs fo
r te
mpe
ratu
Cell
corr
ectio
n fa
31
BEF 44903 Industrial
Design of Uninterruptible Power Supplies (UPS) The primary function of uninterruptible
power supplies is to ensure continuity of l l dIndustrial
Power Systems
Topic 3
electrical power during power outage or contingencies.
UPS can be used to improve PQ especially voltage quality in IPS.
Static transfer switches can be used to supply power to a load via two independent power sources. In the event of a fault, they automatically transfer the loads from one source to the other.
32
26/10/2014
17
BEF 44903 Industrial
Design of Uninterruptible Power Supplies (UPS)
Industrial Power Systems
Topic 3
Line-interactive
OnlineOffline
33
BEF 44903 Industrial
Design of Uninterruptible Power Supplies (UPS)Online or Double conversion UPS In normal operation, the load is supplied with power
l hIndustrial Power Systems
Topic 3
permanently via the inverter. Bypass channel can be used to increase the
availability of the power supply in the event of an overload or if the inverter shuts down following a fault or for maintenance purposes.
34
26/10/2014
18
BEF 44903 Industrial
Design of Uninterruptible Power Supplies (UPS)Line-interactive UPS The load is supplied from power supply via power
f h h d ll l h hIndustrial Power Systems
Topic 3
interface in which connected in parallel with the inverter. Can improve voltage quality/ harmonics.
35
BEF 44903 Industrial
Design of Uninterruptible Power Supplies (UPS)Offline or passive stand-by UPS In normal operation, the load is supplied with power
d l h lIndustrial Power Systems
Topic 3
directly via the line. If the line voltage strays outside the permissible
load tolerance limits, the inverter takes place. This configuration is designed for low-sensitivity
loads such as personal computers.
36
26/10/2014
19
BEF 44903 Industrial
Design of Uninterruptible Power Supplies (UPS) Steps in UPS sizing:
Step 1 – Prepare load list Consider apparentIndustrial Power Systems
Topic 3
Step 1 Prepare load list. Consider apparent power and autonomy hour:
Step 2 – Construct load profile Step 3 – Calculate peak design load (in kVA) and
cos
PS
design energy demand (kVAH)
cgpd kkSS 11
cgtd kkEE 11
kg – future load growth (10%)kc – design margin (10%)Sp – peak loadEt – total load energy (VAh)
37
BEF 44903 Industrial
Design of Uninterruptible Power Supplies (UPS)
Step 4 – Battery sizing Step 5 – Rectifier/ Charger sizing. The design
DC load current:Industrial Power Systems
Topic 3
DC load current:
The maximum charging current:DC
DCL V
SI ,
lC t
kCI
C is the selected battery capacity (Ah)kl is the battery recharge efficiency/ loss
S is the selected UPS rating (kVA)VDC is the nominal battery/ DC link voltage
The total min. DC rectifier/ charger current:
Ct factor (pu) (1.1)tc is the min. battery recharge time (hrs)
CDCLDC III ,38
26/10/2014
20
BEF 44903 Industrial
Design of Uninterruptible Power Supplies (UPS)
Step 6 – Inverter/ Static switch sizing.For a three-phase UPS:
Industrial Power Systems
Topic 3
For a single-phase UPS:
where
03 V
SIL
0V
SIL
where,S is the selected UPS rating (kVA)V0 is the nominal AC voltage
39
BEF 44903 Industrial
Design of Uninterruptible Power Supplies (UPS) Example 3.3
An inverter based UPS is installed in a Industrial
Power Systems
Topic 3
factory to run 10 Nos of 250 VA ESD cabinets for at least 3 hours during blackout period. The battery bank output voltage is 120 VDC. The future growth contingency and the design margin are both considered as 10%10%.
40
26/10/2014
21
BEF 44903 Industrial
Design of Uninterruptible Power Supplies (UPS) Example 3.3a) The cell charging voltage is 2.25 VDC/cell, the end-
f d h l 8 / ll d hIndustrial Power Systems
Topic 3
of-discharge voltage is 1.8 VDC/cell, and the minimum and maximum load voltage tolerance are 10% and 20%, respectively. Decide the number of cells in series.
b) Given a depth of discharge is 80%, battery ageing factor is 20%, temperature correction factor for
t d ll t 30C i 0 956 d th it tivented cell at 30C is 0.956 and the capacity rating factor is 10%. Compute the minimum battery size (in AH).
41
BEF 44903 Industrial
Design of Uninterruptible Power Supplies (UPS)a)
cells 64
252
2.011201 max,max
lDC
V
VVN
Industrial Power Systems
Topic 3
The selected n mbe of cells in se ies is 62
25.2acV
cells 60
8.1
1.011201 min,min
eod
lDC
V
VVN
The selected number of cells in series is 62 cells.
42
26/10/2014
22
BEF 44903 Industrial
Design of Uninterruptible Power Supplies (UPS)b)
VAHEd 90751.011.01325010 Industrial
Power Systems
Topic 3
The minimum battery size,
d
AHkV
kkkEC
dodDC
tcad 29.1198.0120
956.01.12.19075)1()1(min
43
BEF 44903 Industrial
Design of Uninterruptible Power Supplies (UPS) Example 3.4
Table E3.4 shows the critical loads for a Industrial
Power Systems
Topic 3
plastic packaging plant that to be supplied by UPS during power outage period. Figure E3.4 depicts the connection diagram of the proposed UPS and its main configurations.
44
26/10/2014
23
BEF 44903 Industrial
Design of Uninterruptible Power Supplies (UPS)a) Construct the load profile (VA versus period
in hour) for the UPS loading Industrial
Power Systems
Topic 3
b) Compute the peak design load and design energy demand if the future growth contingency and the design margin are both considered as 10%
c) Design the UPS based on the ratings of the battery bank, the rectifier system, the static switch and the inverter system
45
BEF 44903 Industrial
Design of Uninterruptible Power Supplies (UPS) Table E3.4
Rating Nos Autonomy Industrial
Power Systems
Topic 3
Load Description (VA) (Unit) Time (Hours)
Distributed Control System Cabinet
350 10 4
Electrostatic Discharge Cabinet
400 10 6
Telecommunications Cabinet
180 3 8
46
CabinetComputer Console 120 5 2HMI Units 150 10 4
26/10/2014
24
BEF 44903 Industrial
Design of Uninterruptible Power Supplies (UPS) Figure E3.4
Static Switch
Bypass AC Input Supply
415V ACIndustrial Power Systems
Topic 3Rectifier Inverter
Battery Bank
Main AC Input Supply
415V AC Output
Output voltage is 120 VDC
Depth of discharge is 85%
f
47
Battery ageing factor is 25%
Temperature correction factor for vented cell at 30C is 0.956
Capacity rating factor is 8%
Recharge efficiency factor is 1.1
Minimum recharge time is 3 hours
BEF 44903 Industrial
Design of Uninterruptible Power Supplies (UPS)a) Load profile of the UPS loading:
VAIndustrial
Power Systems
Topic 3
6000
8000
10000
12000
48
2000
4000
4 6 8 Operating hour
2
26/10/2014
25
BEF 44903 Industrial
Design of Uninterruptible Power Supplies (UPS)b) The peak design load = 540 + 4000 + 3500
+ 1500 + 600 = 10,140 VAIndustrial
Power Systems
Topic 3
Total energy demand,= 540(8) + 4000(6) + 3500(4) + 1500(4) + 600(2) = 49,520 VAH
The design energy demand,
49
VAHEd 2.919,591.011.01520,49
BEF 44903 Industrial
Design of Uninterruptible Power Supplies (UPS)c) Battery bank sizing,
AHkkkE
C tcad 15758956.008.125.12.919,59)1()1(
Industrial Power Systems
Topic 3
A battery bank capacity of 800 AH is selected.
Rectifier sizing
AHkV
CdodDC
15.75885.0120min
Rectifier sizing,Design load = 10140 (1.1)(1.1) = 12,269.4 VAThe 15,000 VA of design load is considered.
50
26/10/2014
26
BEF 44903 Industrial
Design of Uninterruptible Power Supplies (UPS)c) Design DC load current,
AVA
I 125000,15
Industrial Power Systems
Topic 3
Maximum battery charging current,
Total minim m DC ectifie and cha ging
AV
I DCL 125120,
AIC 3.293
3
1.1800
Total minimum DC rectifier and charging currents,IDC = IL,DC + IC = 125A + 293.3A = 418.3AA DC rectifier rating of 420A is selected.51
BEF 44903 Industrial
Design of Uninterruptible Power Supplies (UPS)
Inverter and static switch sizing,
Industrial Power Systems
Topic 3Output AC voltage is 415V,
Design AC load current,
AV
VAI ACL 87.20
4153
000,15,
An inverter and static switch rating of 30A is selected.52
V4153