Temp Scanner-Modbus Details

35
SCANNER 85XX masibus Operational manual - 1 of 33 – Issue No : 01A/600787 Ref. No. : m83/om/403/1 OPERATIONAL MANUAL FOR 85XX INDEX No Subject Page No. 1. Technical details 2. 2. Specifications 3 3. User guide 4 4. Run mode 6 5. Manual mode 6 6. Program mode 6 7. Configuration mode 8 8. Verify Configuration mode 13 9. Verify program mode 13 10. Calibration mode 14 11. Back plate detail 15 12. Relay logic table detail 16 13. Trouble shooting 18 14. Modbus Detail (optional) 20

Transcript of Temp Scanner-Modbus Details

Page 1: Temp Scanner-Modbus Details

SCANNER 85XX masibus

Operational manual - 1 of 33 –

Issue No : 01A/600787

Ref. No. : m83/om/403/1

OPERATIONAL MANUAL FOR 85XX

INDEX No Subject Page

No. 1. Technical details 2. 2. Specifications 3 3. User guide 4 4. Run mode 6 5. Manual mode 6 6. Program mode 6 7. Configuration mode 8 8. Verify Configuration mode 13 9. Verify program mode 13 10. Calibration mode 14 11. Back plate detail 15 12. Relay logic table detail 16 13. Trouble shooting 18 14. Modbus Detail (optional) 20

Page 2: Temp Scanner-Modbus Details

SCANNER 85XX masibus

Operational manual - 2 of 33 –

Issue No : 01A/600787

1. TECHNICAL DETAILS This is a versatile micro-controller based Scanner with a very high performance to price ratio. The features offered in this product are better than any other Scanner available in similar price range. The instrument is made in 96x192x208 mm size with standard cut out of 92x188 mm. Front is sealed membrane type to withstand dusty environment. On back plate PCB soldered 37 pin D type terminals of very good quality are used. The programming and calibration operation of the instrument is by nine simple keys with two independent displays for channel no and data value for that channel. Channel display is of two digit to differentiate it from data display of four digit, each of 0.56" seven segment LED. Status of Run/ Program/Verify mode, Fault, Auto/Manual mode Operation of the instrument is menu driven with user understandable prompts. Provision for PASS WORD is kept for unauthorized access to critical configuration and program parameters. The product is made to accept Linear voltage inputs. The type of input can be changed in field also. The calibration of the unit is done without trim-pots. The unit can be calibrated in installed condition itself by front panel keys at any given point i.e. user do not required to feed a fixed signal. No. of Groups as well as no. of channels within the group are programmable. Set point type ( LL, hL or hh ), abnormal status ( Alarm or Trip ) for alarm limit1 and alarm limit 2 as well as Relay action type ( ON or OFF ) for alarm limit 1 and alarm limit 2 are programmable. For each group two relays are given for one alarm limit 1 and second alarm limit 2. Scan time is programmable up to 99 seconds with + 30% error.. Relay on time is programmable up to from 0 to 5 minutes with + 30% error.. Provision for zero and span setting is made to restrict range of usage and programming. This restricts accidental wrong setting of set point beyond the range of interest. This zero and span setting is more useful for linear inputs for setting the range between -1999 to 9999 counts. Serial Communication with RS 232 / RS 485 is also provided for using the scanner as backend for Supervisory Control or for P.C. connectivity. Standard protocol for communication used is “MODBUS-RTU”.

Page 3: Temp Scanner-Modbus Details

SCANNER 85XX masibus

Operational manual - 3 of 33 –

Issue No : 01A/600787

2. SPECIFICATIONS 2.1. DISPLAY 2 digit 0.56" Red seven segment LEDs for channel no. 4 digit 0.56" Red seven segment LEDs for data of current channel. mode selection discrete Red LEDs.

2.2. INPUT

0-10 V DC linear Other types on request Accuracy +/- 0.1% of span +/- 1 Count Input open protection – upscale /downscale programmable Digital I/P (Optional)

2.3. RANGE

0-10 V - Field scaleable -1999 to 9999

2.4. ALARM/TRIP OUTPUT

Up to 3 Groups with two individual relay output for each group relay. One relay for each alarm limit (i.e. AL1 and AL2) for a group rated for 2A @ 230 VAC., selectable for alarm or trip. Common Hysteresis setting 0 to 100 value will be treated as display count. Relay status configurable as normally ON or OFF. Set point type configurable as L, VL or L, H or H, VH. Relay on time is configurable from 0 to 5 minutes.

2.5. CALIBRATION

Ambient, Zero and span adjusted by digital calibration through front panel keys. No trim-pots.

2.6. CONTROLS

Vfy, Increase, Decrease, Auto/Man, Next, Skip/Self Check, Al1/Al2, Scan Time and Enter/ ACK keys for operation, programming & calibration.

2.7. GENERAL

power supply - 110V/230V AC 50 Hz. - user selectable 24 V DC, 110V DC, 220 VDC (optional)

Ambient - 0 to 55 deg C. Humidity - up to 95% RH (Non-condensing) Power consumption - Less than 20 VA Scanning time - 1) Linear - 300 mSec.

2.8. PHYSICAL

case - M.S. powder coated with ABS molded bezel

Page 4: Temp Scanner-Modbus Details

SCANNER 85XX masibus

Operational manual - 4 of 33 –

Issue No : 01A/600787

Terminals - Screw type, can accept up to 2.5 sq. mm wire Bezel size - 96 X 192 mm Depth behind panel - 208 mm / 250mm (with terminal plate) Panel cutout - 92 X 188 mm

3. USER GUIDE

3.1. INTRODUCTION This is a single chip micro-controller based scanner designed for 0 – 10V DC linear input type. Instrument is operated by nine user friendly keys. These keys are used for operation, programming and calibration. There are four levels of protections in the instrument. The four levels decide access to verify settings(operator level), access to set points & control parameters(supervisor level), configuration and calibration. The manual covers all aspects of operation of the instrument. Please read instructions carefully before altering any programming or configuration information.

3.2. OPERATION

3.2.1. POWER SUPPLY Always be sure that you are connecting right input supply voltage to right power terminal of the instrument. The instrument is having 4 terminals 110- 230V – Neutral and Earth for mains Supply. On application of proper power, the instrument will display Scanner type for 2 seconds and then configuration type for another two seconds. Now, if the input signal is connected, scanner will display value of input in DATA window and channel no. in channel window on display along with appropriate mode LED.

3.2.2. KEY BOARD

There are nine keys for operation of the instrument. For understanding the operation first let us see the operation of keys.

3.2.2.1. VFY This key is used to select desired parameter in configuration , program , verify configuration and verify program modes. On first press of this key, it will display

md CnFG

By pressing inc or dec key you can select the desired mode( CNFG, PRGM, VCFG, VPGM) of operation. Now if you again press the vfy key then the instrument will come in Run mode. The corresponding mode LED will glow on pressing this key.

3.2.2.2. ENTER/ACK

Page 5: Temp Scanner-Modbus Details

SCANNER 85XX masibus

Operational manual - 5 of 33 –

Issue No : 01A/600787

This key is used to enter the value of the selected parameter. After setting the data to proper value, if ENTER key is pressed, the data will be permanently stored in non-volatile memory. On pressing of ENTER key, the decimal point on last digit disappears to indicate that data is entered. Now, the data change is not allowed until ENTER key is pressed once again. On pressing of ENTER key once again, decimal point on last digit will glow and allow change in the data. This key when pressed during RUN MODE will be taken as a ACK key which is used to acknowledge the relays and LED status as per logic selected.

3.2.2.3. INC ( σ ) This key will increment the selected parameter value by one count in program ,configuration or calibration mode. if you keep pressed the key then value will be incremented by 10 times faster up to the maximum value of that particular parameter.

3.2.2.4. DEC ( τ )

This key will decrement the selected parameter value by one count in program or configuration mode. if you keep pressed the key then value will be decremented by 10 times faster up to the minimum value of that particular parameter.

3.2.2.5. NEXT This key is used to move into next parameter in a current mode. When pressed in Run mode, the next un-skipped channel will be displayed. Normally it is used in MAN mode to select next channel for fixed channel display.

3.2.2.6. AUTO/MAN This key is used to set the unit in either auto mode or manual mode. This is a toggle key. i.e. if it is pressed in auto mode, the unit is switched into MAN mode and channel display will become fixed. MAN LED will glow in MAN mode to indicate the same. This key is also used for individual zero/span, individual input type and individual decimal point position setting, for each channel.

3.2.2.7. SCN TIME This key is used to set the scan time for display of channels and its reading. It can be incremented up to 99 using INC key or decremented up to 1 using DEC key. This key is also used to enter in calibration mode from configuration mode and also to set the Relay time for setting on time of relay.

3.2.2.8. SKIP / SCHK KEY This key is used to skip / un-skip the channel in program mode. This is also a toggle key. i.e. if key is pressed while channel is skipped, it will un-skip the channel. On pressing this key in program mode, skip / un-skip message will be displayed in Data window and channel no. will be displayed in Channel window.

3.2.2.9. AL1 / AL2 This key is used to change from alarm limit 1 to alarm limit 2 and vice-versa. This is also a toggle key.

3.3. MODES OF OPERATIONS

3.3.1. There are seven modes of operations.

Page 6: Temp Scanner-Modbus Details

SCANNER 85XX masibus

Operational manual - 6 of 33 –

Issue No : 01A/600787

3.3.2. Run mode 3.3.3. Auto / manual mode 3.3.4. Verify program mode 3.3.5. Program mode 3.3.6. Configuration mode 3.3.7. Verify configuration mode 3.3.8. Calibration mode

Each are described in detail in individual chapter

4. RUN MODE This mode is indicated by RUN LED glowing. In this mode, channel window will display current channel number and DATA window will show its temperature. In AUTO mode, it will keep on displaying successive un-skipped channels at the programmed scan rate. In case of MAN mode, only one channel will be displayed continuously. For manual mode separate LED indication of mode is provided on front. The relay of that channel will be turned OFF, on acknowledging the alarm, if the alarm type is not configured for trip logic, where relay is not turned OFF until it actually comes within limit. The type of action and normal status of relay is programmable and described in Configuration mode. Also refer relay logic table For currently selected calibration channel decimal point on unit's digit of channel no. will glow.

5. MANUAL MODE Manual mode is same as normal run mode except for displaying only one channel continuously. The channel number can be changed by NEXT key. This mode is entered by pressing AUTO/MAN key in RUN/AUTO mode. Pressing this key once again brings back to AUTO mode.

6. PROGRAM MODE This mode is used to display / change alarm limits, scan time and skip status of channels. For entering in this mode, press VFY key in RUN mode and VFY LED will glow to indicate the mode selection and display will ask to select the mode. By pressing increment and decrement key select PRGM option and press ENTER key. By pressing the ENTER key it will ask for Password . Select your password by using “INC” and “DEC” keys.If the Password is correct then it will go in to Program mode and PRG LED will start glowing to indicate the current mode of operation. Then press NEXT key to enter in program mode. Pressing VFY key will take you out of this mode. Factory set password is '00'. If the user has programmed password in configuration mode, go to correct password using INC key and DEC keys and then press ENT key.

Page 7: Temp Scanner-Modbus Details

SCANNER 85XX masibus

Operational manual - 7 of 33 –

Issue No : 01A/600787

6.1. SET ALARM TRIP VALUE CHANNEL 1

01 500

First parameter is alarm limit 1 for channel 1. A decimal point on last digit of data will glow. Change the limit as per requirement by INC and DEC key and press ENTER.. For changing the entry once again, press ENTER key. The decimal point on last digit of data indicates, whether changing of data is allowed or not. If decimal point is off and LEDs are steady data changing is not allowed. Pressing NEXT key will bring display to 02 limit. CHANNEL 2

02 600

Alarm limit for 1 for channel 2. Its operations are identical to channel 1. Pressing NEXT key will bring display to 03 limit. CHANNEL 3

03 700

Its operations are identical to channel 1. Pressing NEXT key will bring display to 04 limit. Thus you can set AL1 limit for each individual channel. For programming AL2 limit for all channel s, press AL1/AL2 key to change to AL2 limits. Its operations are identical to AL1 programming. SCAN TIME For programming Scan Time, press SCN TIME key in program mode. Display will show:

St 001

Displays scan time for updating the channel on display. Maximum Scan Time is 99 Sec. Minimum Scan Time is 1 Sec. Change Scan Time by INC and DEC keys and press ENTER when correct value is set. This parameter is just for approximation it will not give exact timing. RELAY TIME For programming relay on time, press SCN TIME key in program mode and then NEXT key in program mode. Display will show:

Page 8: Temp Scanner-Modbus Details

SCANNER 85XX masibus

Operational manual - 8 of 33 –

Issue No : 01A/600787

rt 001

Displays Relay time is for setting the on time of relays. Maximum Relay on Time is 5 minutes. Minimum Relay on Time is 0 minute. Change Relay on Time by INC and DEC keys and press ENTER key when correct value is set. This parameter is just for approximation it will not give exact timing. Note:- The delay is provided only for relay on and no delay for relay off.

6.2. SKIPPING / UNSKIPPING OF CHANNEL For changing the skip status of channels, press SKIP key in program mode. The display will show channel skip status. If Ch-1 is skipped, display will be

1 S-ch

If Ch-1 is un-skipped, display will be

1 U-ch

Channel can be selected by pressing NEXT key. SKIP key works as a toggle key, i.e. if channel is skipped, by pressing SKIP key status will change to un-skip and vice-versa. After changing the skip status, press ENTER key to store the status. Skipping of all channels is not allowed. At least one channel has to be un-skipped for operation of unit. When user tries to skip the last un-skipped channel, it will not allow. In program mode, user can select any parameter by using NEXT, SKIP, AL1/AL2 and SCAN TIME keys and can abort from this mode by pressing VFY key. For Verify mode all the parameter sequences are same except for password entry and decimal point in last digit is 'off'.

7. CONFIGURATION MODE Configuration mode is used to change basic configuration of unit. The program is same for all options and all options are configurable from front only by using various keys. No hardware changes are necessary for changing input type. It can be changed by just using front keys. For entering Configuration mode, press VFY key in RUN mode and VFY LED will glow to indicate the mode selection and display will ask to select the mode. By pressing increment and decrement key select CNFG option and press ENTER key. Now it will ask for Password. After setting correct Password with the help of INC and DEC keys press ENTER. If the Password is correct then only you can enter in Configuration mode. PRG LED starts glowing

Page 9: Temp Scanner-Modbus Details

SCANNER 85XX masibus

Operational manual - 9 of 33 –

Issue No : 01A/600787

which indicates the mode of operation. Then press NEXT key to go ahead in Configuration mode. Pressing VFY key will take you out of this mode. By entering in Configuration mode, the scanner will display scanner type. The parameters in sequence are described below. User can go to next parameter in sequence by pressing NEXT key.

7.1. SCANNER TYPE

no OR no OR no OR no 8508 8516 8524 8532 There are three options 8508 or 8516 or 8524 for this parameter. Pressing INC and DEC key you can make it 8508 or 8516 or 8524 or 8532.

7.2. CONFIGURATION TYPE

MI OR FI CNty CNty

There are two options mix or fix for this parameter. Pressing INC and DEC key you can make it “mix” or “fix”. If configuration type is selected as fix then scanner will work as common I/P type. If configuration type is selected as mix then only you can change i/P for individual channel.

7.3. INPUT TYPE

Display will show as :

IP 0-10

By pressing NEXT key here you can go to next channel and similarly set the input type of other channels. From here you can go to the next parameters setting. If configuration type is selected is FIX then you can’t change individual I/P type for (i.e I/P type for each channel).

7.4. NO. OF GROUPS

03 no-G

No. of Groups are minimum 1. No. of Groups are maximum 6.

7.5. SETPOINT TYPE

Page 10: Temp Scanner-Modbus Details

SCANNER 85XX masibus

Operational manual - 10 of 33 –

Issue No : 01A/600787

hh OR hL OR LL SPtY

Where hh - high, very high AL1 - high AL2 - very high hL - high, Low AL1 - low AL2 - high LL - low, very low AL1 - very low AL2 - low This setting is common for all groups. For exact understanding of relay and LED operation, please refer the ‘relay logic table’ given at the end of manual.

7.6. ABNORMAL STATUS OF AL1

AL OR tr CAL1

Configuration of abnormal status for AL1 limit. It will toggle between ALRM and TRIP by INC and DEC keys. Open condition will be treated as normal condition in trip type. This is common for all groups.

7.7. ABNORMAL STATUS OF AL2

AL OR tr CAL2

This is for configuration of abnormal status for AL2. Other description is same as AL1.

7.8. RELAY STATUS OF AL1

OF OR on CrL1

Configures normal relay status as ON or OFF for AL1 Relay. This is common for all groups.

NOTE:

Page 11: Temp Scanner-Modbus Details

SCANNER 85XX masibus

Operational manual - 11 of 33 –

Issue No : 01A/600787

(1) Relay1 will be on when and only when both the channels configured in group1 and group4 will be in abnormal condition depending on the relay time settings.

(2) Relay2 will be on when and only when both the channels configured in group2 and group5 will be in abnormal condition depending on the relay time settings

(3) Relay3 will be on when and only when both the channels configured in group3 and group6 will be in abnormal condition depending on the relay time settings.

If Group1 channel comes in abnormal condition and if after some time the group4 channel is provided which is in abnormal condition, then the relay1 will be on after remaining time left from that particular relay on time settings. Similarly, this will be applicable for other groups operation.

Example:- If Group1 channel comes in abnormal condition and if after 20 seconds the group4 channel is provided which is in abnormal condition, then the relay1 will be on after 40 seconds left from relay on time settings.of 1 minute or after 100 seconds for relay on time settings of 2 minutes. Similarly, this will be applicable for other groups operation.

7.9. RELAY STATUS OF AL2

OF OR on CrL2

Configures normal relay status as ON or OFF for AL2 Relay. This is common for all groups. If it is configured as ON, relay will remain ON when all channels of that group are in clear status. This is useful for specific applications where Scanner ON is used for making a contact for failsafe operation, i.e. user wants to sound buzzer or annunciator when Scanner is turned OFF or it is not working. NOTE:

(1) Relay1 will be on when and only when both the channels configured in group1 and group4 will be in abnormal condition depending on the relay time settings.

(2) Relay2 will be on when and only when both the channels configured in group2 and group5 will be in abnormal condition depending on the relay time settings

(3) Relay3 will be on when and only when both the channels configured in group3 and group6 will be in abnormal condition depending on the relay time settings.

If Group1 channel comes in abnormal condition and if after some time the group4 channel is provided which is in abnormal condition, then the relay1 will be on after remaining time left from that particular relay on time settings. Similarly, this will be applicable for other groups operation.

Example:- If Group1 channel comes in abnormal condition and if after 20 seconds the group4 channel is provided which is in abnormal condition, then the relay1 will be on after 40 seconds left from relay on time settings.of 1 minute or after 100 seconds for relay on time settings of 2 minutes. Similarly, this will be applicable for other groups operation.

7.10. LATCHING OF ALARM

Y OR no

Page 12: Temp Scanner-Modbus Details

SCANNER 85XX masibus

Operational manual - 12 of 33 –

Issue No : 01A/600787

Ltch When CAL1 and CAL2 are of trip type, this parameter will be skipped from display.

7.11. NO. OF CHANNELS IN GROUP X

15 GrPX

Here, X indicates no. 1 to 6.(e.g. GrP1, GrP2, GrP3, GrP4, GrP5, GrP6). Up to 8 channels in group 1, if no. of groups is 1, if scanner type is 8508. Up to 16 channels in group 1, if no. of groups is 1, if scanner type is 8516. Up to 24 channels in group 1, if no. of groups is 1, if scanner type is 8524. Minimum no. of channels in a particular group is 1.

7.12. OPEN SENSOR UP/DOWN

UP OPEN

This is used to define the state of the alarms in open sensor condition. It can be configured as UP or DOWN by pressing INC and DEC keys. If it is configured as UP then Open condition will be treated as alarm / abnormal condition. If it is configured as DOWN then Open condition will be treated as normal condition.

7.13. HYSTERESIS

h 010

Hysteresis for relay operation an alarm limits. This parameter is common for all groups. Minimum value can be '0' and maximum value can be 100. Use INC or DEC keys for changing the value. Hysteresis is treated as per count basis depending on display value. For RTD Pt100,0.1 deg. resolution, maximum setting will be 10.0 deg.

7.14. ZERO

Z -1999

Zero value or minimum value for selected input. Minimum value is decided by input type. Maximum value will be span value. For linear inputs, this is the zero setting for range programming. This will be treated as common Zero value for all the channels.

Page 13: Temp Scanner-Modbus Details

SCANNER 85XX masibus

Operational manual - 13 of 33 –

Issue No : 01A/600787

If configuration type is mix OR for fix configuration i/p type is selected as linear(4 to 20 or 0 to 5) then only there is provision for setting zero/ span/ dp position ( dp position is zero for t/c’s ) for each channel individually. By pressing AUTO/MAN key here, you can enter individual zero value for all the channels. Display will show as :

01 100

Discrete LED 1 of AL1 will start flashing .By pressing INC/DEC keys, you can set the zero value for channel 1. If you press AUTO/MAN key here then Discrete LED 1 of AL2 will start flashing. Now display will show span of channel 1.By pressing INC/DEC keys, you can set the span value for channel 1. AUTO/MAN key here works as toggle key between AL1 & AL2 (i.e. Zero and Span). By pressing NEXT key here you can go to next channel and similarly set the zero and span values of other channels. If you want to come at channel 1 from any other channel then use SCN TIME key. VFY key will bring you back to the configuration mode ( i.e. One level up ) at common zero value setting. From here you can go to the next parameters setting.

7.15. SPAN

S 2000

Span value or maximum value for selected input. Maximum or minimum value is decided by input type. For linear inputs, this is the span setting for range programming. If configuration type is mix OR for fix configuration i/p type is selected as linear(4 to 20,0 to 5) then only by pressing AUTO/MAN key here, you can enter individual zero/ span values for all the channels. Display will show as :

01

1000 Discrete LED 1 of AL2 will start flashing. All the functions described in the previous description of zero value setting are applicable here. If I/P values goes below zero Configured Zero will be indicated on display. If I/P value goes above span Configured span will be indicated on display of process value.

7.16. DECIMAL POINT POSITION

dP 003

Decimal point position is applicable only to 4-20 mA or 0-5V i/p. It can be set between 0 to 3 as per requirement. If configuration type is mix OR for fix configuration i/p type is selected as linear (4 to 20,0 to 5) then only by pressing AUTO/MAN key here, you can enter individual dp position value for all the channels. If configuration type is selected as mix then you can enter in individual DP position setting but you can change DP position of channels only which has I/P type as 0-5V or 4 –20. Display will show as :

Page 14: Temp Scanner-Modbus Details

SCANNER 85XX masibus

Operational manual - 14 of 33 –

Issue No : 01A/600787

01 001

By pressing INC/DEC keys, you can set the dp position value for channel 1. By pressing NEXT key here you can go to next channel and similarly set the dp position values of other channels. If you want to come at channel 1 from any other channel then use SCN TIME key. VFY key will bring you back to the configuration mode ( ie. One level up ) at common DP value setting. From here you can go to the next parameters setting. For the channels having input types t/c and rtd, dp position value is fixed ( zero). If you are using the instrument with individual scaling of zero/span and dp then don’t press ENTER key at the main zero/span and dp parameters in the configuration mode after setting individual values. Main zero/span and dp values are common values for all the channels. After setting individual values if you will press ENTER key at main zero/span/dp then this will make zero, span and dp values same or common for all the channels.

7.17. PASSWORD

00 PASS

Password for entering to Program mode and Configuration mode. The value of password can be programmed anywhere between '0' to '99'. Factory set password is 00.

7.18. SERIAL NUMBER

1 Srno

This parameter is required while using the Serial Communication facility. It represents the serial number or the ID number of the Unit. It can be configured between 1 and 99 by using INC/DEC keys.

7.19. BAUD RATE

bd 9600

This parameter is used to set the BAUD RATE for serial communication. Different baud rates can be selected by using INC/DEC keys. Baud rate can be set from 2400,4800,9600 and 19.2KB.

7.20. OPEN COLLECTOR

n oC

If open collector outputs are used then select yes (y) otherwise select no (n).

Page 15: Temp Scanner-Modbus Details

SCANNER 85XX masibus

Operational manual - 15 of 33 –

Issue No : 01A/600787

If you select OC as n then it will show

y rtoP

This selection will give analog O/P of 4 to 20mA. If there is no relay card then two analog O/P will be on Relay 1 and relay 7. For 3-group scanner (i.e one relay card )take analog O/P at Relay no. 7. please refer legend print on back-plate. (if open collector is yes then Analog O/P is not available and vice versa.) Scanner will give analog O/P correspond to Max and Min channels value among all analog i/p channel values as per factory setting.

7.21. OPEN COLLECTOR TYPE

IN OCTY

This parameter is used to set the Open Collector Type. Open collector type can be selected by INC/DEC keys . Note : For, Open Collector type configuration is selected as “OR” then O/P will operate as below for different logic For hh (High, Very High) O/P will operate when Process value will be higher then very high set point i.e AL2. For LL (Low, Very Low) O/P will operate when Process value will be below very low set point i.e AL2. For HL (High, Low) O/P will operate when Process value will be either lower then low set point or higher then high set-points i.e process value is below AL1 or above AL2. For, Open Collector type configuration is selected as “IND” then O/P will operate as AL1 and AL2 alarms for respective channels.

8. VERIFY CONFIGURATION MODE This mode is to verify all the configuration parameters like scanner type, input type, no. of groups, no. of channels in each group, decimal point, zero, span etc. User can view the data but can’t change the data in this mode. For entering into verify configuration mode, press VFY key in RUN mode and VFY LED will glow to indicate the mode selection and display will ask to select the mode. By pressing increment and decrement key select VCFG option and press ENTER key. Then press NEXT key to enter in verify configuration mode. Pressing VFY key will take you out of this mode.

9. VERIFY PROGRAM MODE This mode is to verify the alarm limits, scan time, Relay on time and channel skip information. User can view the data but can not change it in this mode. For entering into verify program mode, press VFY key in RUN mode and VFY LED will glow to indicate the mode selection and display will ask to select the mode. By pressing increment and decrement key select VPGM option and press ENTER key. Then press NEXT key to enter in verify program mode. Pressing VFY key will take you out of this mode.

Page 16: Temp Scanner-Modbus Details

SCANNER 85XX masibus

Operational manual - 16 of 33 –

Issue No : 01A/600787

10. CALIBRATION MODE You can calibrate instrument after entering in configuration mode, press SCN TIME key to enter into Calibration mode. Here there are 4 groups of calibration. Group1 : 0-10V. Calibration can be done in any one channel only. Calibration done in any one channel will hold for all the channels. For the first group the calibration done is of I/P type 0-10V DC linear. In calibration mode following values are displayed and programmed as follows. When you press SCN TIME key display will be as follows:

1 CLch

Select your channel for calibration by using INC/DEC keys. After selecting calibration channel press enter to change calibration parameter.It is mandatory to press enter if you want to change calibration parameter of particular channel.

10.1. ZERO CALIBRATION

CZ 054

It will display current reading of calibration channel. Use INC or DEC key to bring it to desired value and press ENTER key to store zero calibration. On both sides 5% of total span is allowed for adjustment. To come out of calibration mode press VFY key.

10.2. SPAN CALIBRATION

CS 1200

It will display current reading of calibration channel. Use INC or DEC key to bring it to desired value and press ENTER key to store span calibration. On both sides 5% of total span is allowed for adjustment.

Page 17: Temp Scanner-Modbus Details

SCANNER 85XX masibus

Operational manual - 17 of 33 –

Issue No : 01A/600787

11. Back plate Detail.

Page 18: Temp Scanner-Modbus Details

SCANNER 85XX masibus

Operational manual - 18 of 33 –

Issue No : 01A/600787

12. Relay logic table

ALARM AL1 MOMEMTARY ALARM (when in abnormal condition ack not pressed) CONDITION NORMAL ABNORMAL UP (O/S) DOWN (O/S) ACK ** NORMAL * ACK ***

ALARM LATCH =

YES RELAY OFF ON ON OFF OFF OFF

HIGH ALARM LATCH =

NO RELAY OFF ON ON OFF OFF OFF

TRIP

RELAY OFF ON OFF OFF ON OFF ALARM LATCH =

YES RELAY OFF ON OFF ON OFF OFF

LOW ALARM LATCH = NO RELAY OFF ON OFF ON OFF OFF TRIP

RELAY OFF ON OFF OFF ON OFF ALARM LATCH =

YES RELAY OFF ON OFF ON OFF OFF

VLOW ALARM LATCH =

NO RELAY OFF ON OFF ON OFF OFF

TRIP

RELAY OFF ON OFF OFF ON OFF

ALARM AL2 MOMEMTARY ALARM (when in abnormal condition ack not pressed) CONDITION NORMAL ABNORMAL UP (O/S) DOWN (O/S) ACK ** NORMAL * ACK *** ALARM LATCH YES RELAY OFF ON ON OFF OFF OFF VHIGH ALARM LATCH NO RELAY OFF ON ON OFF OFF OFF TRIP RELAY OFF ON OFF OFF ON OFF ALARM LATCH YES RELAY OFF ON ON OFF OFF OFF HIGH ALARM LATCH NO RELAY OFF ON ON OFF OFF OFF TRIP RELAY OFF ON OFF OFF ON OFF ALARM LATCH YES RELAY OFF ON OFF ON OFF OFF LOW ALARM LATCH NO RELAY OFF ON OFF ON OFF OFF

Page 19: Temp Scanner-Modbus Details

SCANNER 85XX masibus

Operational manual - 19 of 33 –

Issue No : 01A/600787

TRIP RELAY OFF ON OFF OFF ON OFF

ALARM AL1 MAINTAINED ALARM (when in abnormal condition ack is pressed)

CONDITION NORMAL ABNORMAL UP (O/S) DOWN (O/S) ACK ** NORMAL * ACK ***

ALARM LATCH =

YES RELAY OFF ON ON OFF ON OFF OFF

HIGH ALARM LATCH =

NO RELAY OFF ON ON OFF OFF OFF OFF

TRIP

RELAY OFF ON OFF OFF ON ON OFF

ALARM LATCH =

YES RELAY OFF ON OFF ON ON OFF OFF

LOW ALARM LATCH =

NO RELAY OFF ON OFF ON OFF OFF OFF

TRIP

RELAY OFF ON OFF OFF ON ON OFF

ALARM LATCH =

YES RELAY OFF ON OFF ON ON OFF OFF

VLOW ALARM LATCH =

NO RELAY OFF ON OFF ON OFF OFF OFF

TRIP

RELAY OFF ON OFF OFF ON ON OFF

ALARM AL2 MAINTAINED ALARM (when in abnormal condition ack is pressed)

CONDITION NORMAL ABNORMAL UP (O/S) DOWN (O/S) ACK ** NORMAL * ACK ***

ALARM LATCH

YES RELAY OFF ON ON OFF ON OFF OFF

VHIGH ALARM LATCH

NO RELAY OFF ON ON OFF OFF OFF OFF

TRIP

RELAY OFF ON OFF OFF ON ON OFF

ALARM LATCH

YES RELAY OFF ON ON OFF ON OFF OFF

HIGH ALARM LATCH

NO RELAY OFF ON ON OFF OFF OFF OFF

TRIP

RELAY OFF ON OFF OFF ON ON OFF

ALARM LATCH

YES RELAY OFF ON OFF ON ON OFF OFF

LOW ALARM LATCH

NO RELAY OFF ON OFF ON OFF OFF OFF

TRIP

Page 20: Temp Scanner-Modbus Details

SCANNER 85XX masibus

Operational manual - 20 of 33 –

Issue No : 01A/600787

RELAY OFF ON OFF OFF ON ON OFF Notes : * means normal condition after abnormal has occurred ** means ack pressed in abnormal condition *** means ack pressed in normal condition after abnormal has already occurred.

13. Trouble shooting

Scanner does not Switch ON.

• Check the Mains Cord. • I/P power may be not present. Check power supply voltage is it proper as per order • Check fuse, if blown off replace it • Check the Power ON Indication LED.

Calibration of the unit is doubted to have drifted.

• Check the O/P of sensor is as per the chart supplied to you by sensor manufacturer. Measure it with

instrument with better then 0.1% accuracy. Standard multi-meter with 3½ digit display may have poor accuracy then scanner.

• Calibrate the unit as explained in the manual. Select the proper method according to your scanner input type.

In linear type input the unit shows false reading or ‘OVER’ or ‘UNDER’.

• Check for the polarity of the I/p connections. • Check for the proper range programmed in that channel.

Reading indicated by scanner is unstable, wrong or open.

• Check the process input and also check its connection are as per the back-plate supplied. • Ensure the perfect EARTHING to the unit & also check that neutral should not be floating. • Shielded cables should used for input. Shield should be EARTHED near the unit only. • Check any of the sensor is not getting EARTHED or having weak insulation with respect to earth. If so,

remove that sensor and check the cabling. • Check that Input cables are properly tighten with back-plate • Check that back-plate is not loose. • Take separate earth wires for separate instruments, avoid looping of earth wires. • If scanner is showing different reading in all channels for common I/P type and same Process vale then

please enter I/P type again. • Check for AC voltage pick up at the signal at scanner side • All low-level input and output such as T/C, Rtd, Linear I/P and control signal wires must be kept

separate from supply and relay output cabling. Communication Problem between the Unit and Host PC/Operator Terminal

• Check the cabling. • Check the serial No. and baud rate settings at PC side and scanner side. • Check the RS-485 to RS232 converter for 485 communication. • Check the serial port of the computer by shorting 2 and 3 no pin of PC comports with PROCOMM or

any other available application.

Page 21: Temp Scanner-Modbus Details

SCANNER 85XX masibus

Operational manual - 21 of 33 –

Issue No : 01A/600787

• Check RS 232 –RS 485 connection at PC and scanner side. • For RS 485 sometimes terminating resistor of 120Ω at scanner and converter side. In most of the cases

this is not required for scanner. Relay or open collector O/P Action problem

• Check power to the contactor operated by relay from scanner. • If relay card or open collector card burns out frequently check for the rating of the relay driven by open

collector card or rating of contactor driven by relay card.

General • It is mandatory to reset the Instrument by switching off the Power if the input type is changed. • In Configuration, Program, Verify Configuration, Verify Program and Calibration modes, 20 Sec time out is

provided i.e. if no key is pressed for 20 seconds, it will fall back into Run/Man mode. • While programming value, if the INC or DEC key is kept pressed for more than 10 counts, the

speed of change will be increased by 5 times. It is the dual speed concept for changing value at faster rate. • On power on scanner will first display model (8508/8516/8524), then configuration type for some time and

then it will come to actual Run mode display. • If there is any error in EEPROM data, it will display error message and halt.

10 -Err

• The upper two digit display will show no. of parameters having errors and lower 4 digit display will show -err message. To see the parameter having error, scan through parameters both in Program mode & Configuration mode. The decimal point of first digit of channel no. display will glow, if the parameter data in EEPROM is disturbed.

• If you change any individual I/P type or common I/P type then please also adjust your particular channel span value, Zero value and alarm-trip set-points.

SUPPLY VOLTAGE

• Supply voltage should be given through a good isolation transformer. This being a microprocessor based instrument, a massive voltage spike can damage it. A good isolation transformer shields the instrument from such voltage spikes and surges.

• All supply connections to final control devices such as contractors, solenoids etc. must be taken directly from the supply and not from the supply terminals of the instrument.

• An effective earth is mandatory for the instrument. I n absence of proper earthing instrument body will float at half some part of the supply voltage and this may give shock to user.

This is an electronics instrument it may have problem not listed above, in case of such fault while reporting to factory (Masibus area office or head office), mention exact nature of fault with sequence of events.

Page 22: Temp Scanner-Modbus Details

SCANNER 85XX masibus

Operational manual - 22 of 33 –

Issue No : 01A/600787

14. Modbus detail

14.1. INTRODUCTION

The scanner 85XX can be connected in RS-485 communication data link either in multi drop or repeat mode. Each scanner 85XX must have unique Serial Number. No two scanners may have the same address. Entire range of addresses ( 1 to 99 ) may be used. Before starting any communication, choose a baud rate and protocol compatible to the host computer. Only two-pass protocol is available on scanners and hence when using the scanners, only two-pass protocol is assumed. This speeds up the total throughput.

14.2. COMMUNICATION PROTOCOL The communication protocol is a HEX protocol. The host computer issues the commands to the scanners that in turn respond to each command. The entire protocol is based on the command/answer protocol.

14.2.1. How Characters are Transmitted Serially

When messages are transmitted on standard Modbus serial networks, each character or byte is sent in this order (left to right): Least Significant Bit (LSB) ... Most Significant Bit (MSB)With RTU character framing, the bit sequence is:

i.e. 1 start bit 1 stop bit No parity.

14.2.2. MESSAGE QUERY:

Page 23: Temp Scanner-Modbus Details

SCANNER 85XX masibus

Operational manual - 23 of 33 –

Issue No : 01A/600787

14.2.3. RTU Framing

14.2.4. START DELAY and ADDRESS:

Always contains the start of message with 3.5 null char delay followed by the address of the scanner to be addressed. The address is represented by a HEX character ranges from 00 to 99.

14.2.5. FUNCTION: When a message is sent from a master to a slave device the function code field tells the slave what kind of action to perform. In scanner 85XX the functions implemented are 01– READ COIL STATUS (REFERENCE - 0x). 05. – FORCE SINGLE COIL (REFERENCE - 0x). 03. – READ HOLDING REGISTERS (REFERENCE- 4x). 06. – PRESET SINGLE REGISTER (REFERENCE - 4x). Here Same Reference Functions are used for Reading and Writing a parameter, so only one Variable Tag is required for reading and writing a parameter.

14.2.6. DATA FIELD:

Read : The query message specifies the starting register and quantity of registers to be read. Registers are addressed starting at zero- registers 1 ... 12 are addressed as 0 ... 11. The quantity of channels must not exceed ( total no of channels – starting channel address). Write : The query message specifies the register address and the data to be written in that register. Registers are addressed starting at zero- register 1 is addressed as 0.

Page 24: Temp Scanner-Modbus Details

SCANNER 85XX masibus

Operational manual - 24 of 33 –

Issue No : 01A/600787

14.2.7. CHECKSUM COMPUTATION: The error checking field contains a 16-bit value implemented as two eight-bit bytes. The error check value is the result of a Cyclical Redundancy Check(CRC) calculation performed on the message contents.

14.2.8. CRC calculation: The CRC field checks the contents of the entire message. It is applied regardless of any parity check method used for the individual characters of the message. The CRC value is calculated by the transmitting device, which appends the CRC to the message. The receiving device recalculates a CRC during receipt of the message, and compares the calculated value to the actual value it received in the CRC field. If the two values are not equal, an error results. The CRC is started by first pre loading a 16-bit register to all 1's. Then a process begins of applying successive eight-bit bytes of the message to the current contents of the register. Only the eight bits of data in each character are used for generating the CRC. Start and stop bits, and the parity bit, do not apply to the CRC. During generation of the CRC, each eight-bit character is exclusive ORed with the register contents. Then the result is shifted in the direction of the least significant bit (LSB), with a zero filled into the most significant bit (MSB) position. The LSB is extracted and examined. If the LSB was a 1, the register is then exclusive ORed with a preset, fixed value. If the LSB was a 0, no exclusive OR takes place. This process is repeated until eight shifts have been performed. After the last (eighth) shift, the next eight-bit byte is exclusive ORed with the register's current value, and the process repeats for eight more shifts as described above. The final content of the register, after all the bytes of the message have been applied, is the CRC value. When the CRC is appended to the message, the low-order byte is appended first, followed by the high-order byte.

14.2.9. MESSAGE RESPONSE :

Page 25: Temp Scanner-Modbus Details

SCANNER 85XX masibus

Operational manual - 25 of 33 –

Issue No : 01A/600787

14.3. COMMUNICATION PROTOCOL IN SCANNER

14.3.1. Process Value read and Alarm – Trip Set-point value read write Data read Query = [0 x Sr.No.] , [0 x Fun Code], [0 x ADD. High], [0 x ADD. Low] , [0 x Data. High], [0 x Data. Low] [0 x CRC high] [0 x CRC low] Fun code = 0X03 Data word - Address word < 73. Response = [Sr.No.] , [0 x Fun Code], [Byte count], [Data High], [Data Low] …….., [Data. High], [Data. Low] [CRC high] [CRC low] Data write Query = [0 x Sr.No.] , [0 x Fun Code], [0 x ADD. High], [0 x ADD. Low] , [0 x Data. High], [0 x Data. Low] [0 x CRC high] [0 x CRC low] Fun code = 0X06 Data word - Address word < 73. Response = [Sr.No.] , [0 x Fun Code], [ADD High], [ADD Low] , [Data. High], [Data. Low] [CRC high] [CRC low]

14.3.1.1. Process value Addresses Sr.no Analog Parameters Absolute Address Type of Access Parameter Type Values Applicable1. CH1 40001 Read only Int NA 2. CH2 40002 Read only Int NA 3. CH3 40003 Read only Int NA 4. CH4 40004 Read only Int NA 5. CH5 40005 Read only Int NA 6. CH6 40006 Read only Int NA 7. CH7 40007 Read only Int NA 8. CH8 40008 Read only Int NA 9. CH9 40009 Read only Int NA 10. CH10 40010 Read only Int NA 11. CH11 40011 Read only Int NA 12. CH12 40012 Read only Int NA 13. CH13 40013 Read only Int NA 14. CH14 40014 Read only Int NA 15. CH15 40015 Read only Int NA 16. CH16 40016 Read only Int NA 17. CH17 40017 Read only Int NA

Page 26: Temp Scanner-Modbus Details

SCANNER 85XX masibus

Operational manual - 26 of 33 –

Issue No : 01A/600787

18. CH18 40018 Read only Int NA 19. CH19 40019 Read only Int NA 20. CH20 40020 Read only Int NA 21. CH21 40021 Read only Int NA 22. CH22 40022 Read only Int NA 23. CH23 40023 Read only Int NA 24. CH24 40024 Read only Int NA 25. CH25 40025 Read only Int NA 26. CH26 40026 Read only Int NA 27. CH27 40027 Read only Int NA 28. CH28 40028 Read only Int NA 29. CH29 40029 Read only Int NA 30. CH30 40030 Read only Int NA 31. CH31 40031 Read only Int NA 32. CH32 40032 Read only Int NA Note : If scanner process value is out of limit for particular I/P type then scanner will show ‘Open’ on display but it will send ‘10000’ to PC If scanner process value is out of limit for 5% for linear I/P type then scanner will show ‘ACT Zero ’ on display and it will send ‘ACT SPAN’ to PC If scanner process value is out of limit for 5% for linear I/P type then scanner will show ‘ACT Zero ’ on display and it will send ‘ACT Zero’ to PC

14.3.1.2. Alarm value addresses (AL1) Sr. No. Analog Parameters Absolute

Address Type of Access Parameter

Type Values Applicable

33. ALM1_1 40033 Read/ Write Int Ind. zero to Ind. Span 34. ALM2_1 40034 Read/ Write Int Ind. zero to Ind. Span 35. ALM3_1 40035 Read/ Write Int Ind. zero to Ind. Span 36. ALM4_1 40036 Read/ Write Int Ind. zero to Ind. Span 37. ALM5_1 40037 Read/ Write Int Ind. zero to Ind. Span 38. ALM6_1 40038 Read/ Write Int Ind. zero to Ind. Span 39. ALM7_1 40039 Read/ Write Int Ind. zero to Ind. Span 40. ALM8_1 40040 Read/ Write Int Ind. zero to Ind. Span 41. ALM9_1 40041 Read/ Write Int Ind. zero to Ind. Span 42. ALM10_1 40042 Read/ Write Int Ind. zero to Ind. Span 43. ALM11_1 40043 Read/ Write Int Ind. zero to Ind. Span 44. ALM12_1 40044 Read/Write Int Ind. zero to Ind. Span 45. ALM13_1 40045 Read/ Write Int Ind. zero to Ind. Span 46. ALM14_1 40046 Read/ Write Int Ind. zero to Ind. Span 47. ALM15_1 40047 Read/ Write Int Ind. zero to Ind. Span 48. ALM16_1 40048 Read/ Write Int Ind. zero to Ind. Span 49. ALM17_1 40049 Read/ Write Int Ind. zero to Ind. Span 50. ALM18_1 40050 Read/ Write Int Ind. zero to Ind. Span

Page 27: Temp Scanner-Modbus Details

SCANNER 85XX masibus

Operational manual - 27 of 33 –

Issue No : 01A/600787

51. ALM19_1 40051 Read/ Write Int Ind. zero to Ind. Span 52. ALM20_1 40052 Read/ Write Int Ind. zero to Ind. Span 53. ALM21_1 40053 Read/ Write Int Ind. zero to Ind. Span 54. ALM22_1 40054 Read/ Write Int Ind. zero to Ind. Span 55. ALM23_1 40055 Read/ Write Int Ind. zero to Ind. Span 56. ALM24_1 40056 Read/ Write Int Ind. zero to Ind. Span 57. ALM25_1 40057 Read/ Write Int Ind. zero to Ind. Span 58. ALM26_1 40058 Read/ Write Int Ind. zero to Ind. Span 59. ALM27_1 40059 Read/ Write Int Ind. zero to Ind. Span 60. ALM28_1 40060 Read/ Write Int Ind. zero to Ind. Span 61. ALM29_1 40061 Read/ Write Int Ind. zero to Ind. Span 62. ALM30_1 40062 Read/ Write Int Ind. zero to Ind. Span 63. ALM31_1 40063 Read/ Write Int Ind. zero to Ind. Span 64. ALM32_1 40064 Read/ Write Int Ind. Zero to Ind. Span

14.3.1.3. Trip Value Addresses (AL2) Sr. No. Analog Parameters Absolute Address Type of Access Parameter Type Values Applicable 65. TRIP1_1 40065 Read/ Write Int Ind. Zero to Ind. Span 66. TRIP2_1 40066 Read/ Write Int Ind. Zero to Ind. Span 67. TRIP3_1 40067 Read/ Write Int Ind. Zero to Ind. Span 68. TRIP4_1 40068 Read/ Write Int Ind. Zero to Ind. Span 69. TRIP5_1 40069 Read/ Write Int Ind. Zero to Ind. Span 70. TRIP6_1 40070 Read/ Write Int Ind. Zero to Ind. Span 71. TRIP7_1 40071 Read/ Write Int Ind. Zero to Ind. Span 72. TRIP8_1 40072 Read/ Write Int Ind. Zero to Ind. Span 73. TRIP9_1 40073 Read/ Write Int Ind. Zero to Ind. Span 74. TRIP10_1 40074 Read/ Write Int Ind. Zero to Ind. Span 75. TRIP11_1 40075 Read/ Write Int Ind. Zero to Ind. Span 76. TRIP12_1 40076 Read/ Write Int Ind. Zero to Ind. Span 77. TRIP13_1 40077 Read/ Write Int Ind. Zero to Ind. Span 78. TRIP14_1 40078 Read/ Write Int Ind. Zero to Ind. Span 79. TRIP15_1 40079 Read/ Write Int Ind. Zero to Ind. Span 80. TRIP16_1 40080 Read/ Write Int Ind. Zero to Ind. Span 81. TRIP17_1 40081 Read/ Write Int Ind. Zero to Ind. Span 82. TRIP18_1 40082 Read/ Write Int Ind. Zero to Ind. Span 83. TRIP19_1 40083 Read/ Write Int Ind. Zero to Ind. Span 84. TRIP20_1 40084 Read/ Write Int Ind. Zero to Ind. Span 85. TRIP21_1 40085 Read/ Write Int Ind. Zero to Ind. Span 86. TRIP22_1 40086 Read/ Write Int Ind. Zero to Ind. Span 87. TRIP23_1 40087 Read/ Write Int Ind. Zero to Ind. Span 88. TRIP24_1 40088 Read/ Write Int Ind. Zero to Ind. Span

Page 28: Temp Scanner-Modbus Details

SCANNER 85XX masibus

Operational manual - 28 of 33 –

Issue No : 01A/600787

89. TRIP25_1 40089 Read/ Write Int Ind. Zero to Ind. Span 90. TRIP26_1 40090 Read/ Write Int Ind. Zero to Ind. Span 91. TRIP27_1 40091 Read/ Write Int Ind. Zero to Ind. Span 92. TRIP28_1 40092 Read/ Write Int Ind. Zero to Ind. Span 93. TRIP29_1 40093 Read/ Write Int Ind. Zero to Ind. Span 94. TRIP30_1 40094 Read/ Write Int Ind. Zero to Ind. Span 95. TRIP31_1 40095 Read/ Write Int Ind. Zero to Ind. Span

96. TRIP32_1 40096 Read/ Write Int Ind. Zero to Ind. Span

14.3.1.4. Individual Scale Zero Addresses

Sr. No. Analog Parameters Absolute Address

Type of Access Parameter Type

Values Applicable

97. SCL_ZERO1_1 40097 Read/ Write Int Particular Ind. I/P type range 98. SCL_ZERO2_1 40098 Read/ Write Int Particular Ind. I/P type range 99. SCL_ZERO3_1 40099 Read/ Write Int Particular Ind. I/P type range 100. SCL_ZERO4_1 400100 Read/ Write Int Particular Ind. I/P type range 101. SCL_ZERO5_1 400101 Read/ Write Int Particular Ind. I/P type range 102. SCL_ZERO6_1 400102 Read/ Write Int Particular Ind. I/P type range 103. SCL_ZERO7_1 400103 Read/ Write Int Particular Ind. I/P type range 104. SCL_ZERO8_1 400104 Read/ Write Int Particular Ind. I/P type range 105. SCL_ZERO9_1 400105 Read/ Write Int Particular Ind. I/P type range 106. SCL_ZERO10_1 400106 Read/ Write Int Particular Ind. I/P type range 107. SCL_ZERO11_1 400107 Read/ Write Int Particular Ind. I/P type range 108. SCL_ZERO12_1 400108 Read/ Write Int Particular Ind. I/P type range 109. SCL_ZERO13_1 400109 Read/ Write Int Particular Ind. I/P type range 110. SCL_ZERO14_1 400110 Read/ Write Int Particular Ind. I/P type range 111. SCL_ZERO15_1 400111 Read/ Write Int Particular Ind. I/P type range 112. SCL_ZERO16_1 400112 Read/ Write Int Particular Ind. I/P type range 113. SCL_ZERO17_1 400113 Read/ Write Int Particular Ind. I/P type range 114. SCL_ZERO18_1 400114 Read/ Write Int Particular Ind. I/P type range 115. SCL_ZERO19_1 400115 Read/ Write Int Particular Ind. I/P type range 116. SCL_ZERO20_1 400116 Read/ Write Int Particular Ind. I/P type range 117. SCL_ZERO21_1 400117 Read/ Write Int Particular Ind. I/P type range 118. SCL_ZERO22_1 400118 Read/ Write Int Particular Ind. I/P type range 119. SCL_ZERO23_1 400119 Read/ Write Int Particular Ind. I/P type range 120. SCL_ZERO24_1 400120 Read/ Write Int Particular Ind. I/P type range 121. SCL_ZERO25_1 400121 Read/ Write Int Particular Ind. I/P type range 122. SCL_ZERO26_1 400122 Read/ Write Int Particular Ind. I/P type range 123. SCL_ZERO27_1 400123 Read/ Write Int Particular Ind. I/P type range 124. SCL_ZERO28_1 400124 Read/ Write Int Particular Ind. I/P type range 125. SCL_ZERO29_1 400125 Read/ Write Int Particular Ind. I/P type range 126. SCL_ZERO30_1 400126 Read/ Write Int Particular Ind. I/P type range 127. SCL_ZERO31_1 400127 Read/ Write Int Particular Ind. I/P type range 128. SCL_ZERO32_1 400128 Read/ Write Int Particular Ind. I/P type range

Page 29: Temp Scanner-Modbus Details

SCANNER 85XX masibus

Operational manual - 29 of 33 –

Issue No : 01A/600787

14.3.1.5. Individual Scale span Addresses Sr. No. Analog Parameters Absolute

Address Type of Access Parameter

Type Values Applicable

129. SCL_SPAN1_1 400129 Read/Write Int Particular Ind. I/P type Range 130. SCL_SPAN2_1 400130 Read/Write Int Particular Ind. I/P type Range 131. SCL_SPAN3_1 400131 Read/Write Int Particular Ind. I/P type Range 132. SCL_SPAN4_1 40132 Read/Write Int Particular Ind. I/P type Range 133. SCL_SPAN5_1 40133 Read/Write Int Particular Ind. I/P type Range 134. SCL_SPAN6_1 40134 Read/Write Int Particular Ind. I/P type Range 135. SCL_SPAN7_1 40135 Read/Write Int Particular Ind. I/P type Range 136. SCL_SPAN8_1 40136 Read/Write Int Particular Ind. I/P type Range 137. SCL_SPAN9_1 40137 Read/Write Int Particular Ind. I/P type Range 138. SCL_SPAN10_1 40138 Read/Write Int Particular Ind. I/P type Range 139. SCL_SPAN11_1 40139 Read/Write Int Particular Ind. I/P type Range 140. SCL_SPAN12_1 40140 Read/Write Int Particular Ind. I/P type Range 141. SCL_SPAN13_1 40141 Read/Write Int Particular Ind. I/P type Range 142. SCL_SPAN14_1 40142 Read/Write Int Particular Ind. I/P type Range 143. SCL_SPAN15_1 40143 Read/Write Int Particular Ind. I/P type Range 144. SCL_SPAN16_1 40144 Read/Write Int Particular Ind. I/P type Range 145. SCL_SPAN17_1 40145 Read/Write Int Particular Ind. I/P type Range 146. SCL_SPAN18_1 40146 Read/Write Int Particular Ind. I/P type Range 147. SCL_SPAN19_1 40147 Read/Write Int Particular Ind. I/P type Range 148. SCL_SPAN20_1 40148 Read/Write Int Particular Ind. I/P type Range 149. SCL_SPAN21_1 40149 Read/Write Int Particular Ind. I/P type Range 150. SCL_SPAN22_1 40150 Read/Write Int Particular Ind. I/P type Range 151. SCL_SPAN23_1 40151 Read/Write Int Particular Ind. I/P type Range 152. SCL_SPAN24_1 40152 Read/Write Int Particular Ind. I/P type Range 153. SCL_SPAN25_1 40153 Read/Write Int Particular Ind. I/P type Range 154. SCL_SPAN26_1 40154 Read/Write Int Particular Ind. I/P type Range 155. SCL_SPAN27_1 40155 Read/Write Int Particular Ind. I/P type Range 156. SCL_SPAN28_1 40156 Read/Write Int Particular Ind. I/P type Range 157. SCL_SPAN29_1 40157 Read/Write Int Particular Ind. I/P type Range 158. SCL_SPAN30_1 40158 Read/Write Int Particular Ind. I/P type Range 159. SCL_SPAN31_1 40159 Read/Write Int Particular Ind. I/P type Range 160. SCL_SPAN32_1 40160 Read/Write Int Particular Ind. I/P type Range

Page 30: Temp Scanner-Modbus Details

SCANNER 85XX masibus

Operational manual - 30 of 33 –

Issue No : 01A/600787

14.3.1.6. Individual DECIMAL POINT Addresses Sr. No. Analog Parameters Absolute

Address Type of Access Parameter

Type Values Applicable

161. IND_DP_POS1_1 40161 Read/Write Int Refer Note A. 162. IND_DP_POS2_1 40162 Read/Write Int Refer Note A. 163. IND_DP_POS3_1 40163 Read/Write Int Refer Note A. 164. IND_DP_POS4_1 40164 Read/Write Int Refer Note A. 165. IND_DP_POS5_1 40165 Read /Write Int Refer Note A. 166. IND_DP_POS6_1 40166 Read/Write Int Refer Note A. 167. IND_DP_POS7_1 40167 Read/Write Int Refer Note A. 168. IND_DP_POS8_1 40168 Read/Write Int Refer Note A. 169. IND_DP_POS9_1 40169 Read/write Int Refer Note A. 170. IND_DP_POS10_1 40170 Read/Write Int Refer Note A. 171. IND_DP_POS11_1 40171 Read/Write Int Refer Note A. 172. IND_DP_POS12_1 40172 Read/Write Int Refer Note A. 173. IND_DP_POS13_1 40173 Read/Write Int Refer Note A. 174. IND_DP_POS14_1 40174 Read/Write Int Refer Note A. 175. IND_DP_POS15_1 40175 Read/Write Int Refer Note A. 176. IND_DP_POS16_1 40176 Read/Write Int Refer Note A. 177. IND_DP_POS17_1 40177 Read/Write Int Refer Note A. 178. IND_DP_POS18_1 40178 Read/Write Int Refer Note A. 179. IND_DP_POS19_1 40179 Read/Write Int Refer Note A. 180. IND_DP_POS20_1 40180 Read/Write Int Refer Note A. 181. IND_DP_POS21_1 40181 Read/Write Int Refer Note A. 182. IND_DP_POS22_1 40182 Read/Write Int Refer Note A. 183. IND_DP_POS23_1 40183 Read/Write Int Refer Note A. 184. IND_DP_POS24_1 40184 Read/Write Int Refer Note A. 185. IND_DP_POS25_1 40185 Read/Write Int Refer Note A. 186. IND_DP_POS26_1 40186 Read/Write Int Refer Note A. 187. IND_DP_POS27_1 40187 Read/Write Int Refer Note A. 188. IND_DP_POS28_1 40188 Read/Write Int Refer Note A. 189. IND_DP_POS29_1 40189 Read/Write Int Refer Note A. 190. IND_DP_POS30_1 40190 Read/Write Int Refer Note A. 191. IND_DP_POS31_1 40191 Read/Write Int Refer Note A. 192. IND_DP_POS32_1 40192 Read/Write Int Refer Note A. Note A : For 4 to 20 mA and 0to 5V DP pos value should be 0-1-2-3. For other I/P Type it should be zero only.

Page 31: Temp Scanner-Modbus Details

SCANNER 85XX masibus

Operational manual - 31 of 33 –

Issue No : 01A/600787

14.3.1.7. Individual inp type Addresses Sr. No. Analog Parameters Absolute

Address Type of Access Parameter

Type Values Applicable

193. IND_INP_TYPE1_1 40193 Read/Write Int 0 to 11 194. IND_INP_TYPE2_1 40194 Read/Write Int 0 to 11 195. IND_INP_TYPE3_1 40195 Read/Write Int 0 to 11 196. IND_INP_TYPE4_1 40196 Read/Write Int 0 to 11 197. IND_INP_TYPE5_1 40197 Read/Write Int 0 to 11 198. IND_INP_TYPE6_1 40198 Read/Write Int 0 to 11 199. IND_INP_TYPE7_1 40199 Read/Write Int 0 to 11 200. IND_INP_TYPE8_1 40200 Read/Write Int 0 to 11 201. IND_INP_TYPE9_1 40201 Read/Write Int 0 to 11 202. IND_INP_TYPE10_1 40202 Read/Write Int 0 to 11 203. IND_INP_TYPE11_1 40203 Read/Write Int 0 to 11 204. IND_INP_TYPE12_1 40204 Read/Write Int 0 to 11 205. IND_INP_TYPE13_1 40205 Read/Write Int 0 to 11 206. IND_INP_TYPE14_1 40206 Read/Write Int 0 to 11 207. IND_INP_TYPE15_1 40207 Read/Write Int 0 to 11 208. IND_INP_TYPE16_1 40208 Read/Write Int 0 to 11 209. IND_INP_TYPE17_1 40209 Read/Write Int 0 to 11 210. IND_INP_TYPE18_1 40210 Read/Write Int 0 to 11 211. IND_INP_TYPE19_1 40211 Read/Write Int 0 to 11 212. IND_INP_TYPE20_1 40212 Read/Write Int 0 to 11 213. IND_INP_TYPE21_1 40213 Read/Write Int 0 to 11 214. IND_INP_TYPE22_1 40214 Read/Write Int 0 to 11 215. IND_INP_TYPE23_1 40215 Read/Write Int 0 to 11 216. IND_INP_TYPE24_1 40216 Read/Write Int 0 to 11 217. IND_INP_TYPE25_1 40217 Read/Write Int 0 to 11 218. IND_INP_TYPE26_1 40218 Read/Write Int 0 to 11 219. IND_INP_TYPE27_1 40219 Read/Write Int 0 to 11 220. IND_INP_TYPE28_1 40220 Read/Write Int 0 to 11 221. IND_INP_TYPE29_1 40221 Read/Write Int 0 to 11 222. IND_INP_TYPE30_1 40222 Read/Write Int 0 to 11 223. IND_INP_TYPE31_1 40223 Read/Write Int 0 to 11 224. IND_INP_TYPE32_1 40224 Read/Write Int 0 to 11

14.3.2. Skip – Unskip write and Alarm – Trip status Data read Data read Query = [0 x Sr.No.] , [0 x Fun Code], [0 x ADD. High], [0 x ADD. Low] , [0 x Data. High], [0 x Data. Low] [0 x CRC high] [0 x CRC low] Fun code = 0X01 Data word - Address word < 74. Response = [Sr.No.] , [0 x Fun Code], [Byte count], [Data High], [Data Low] …….., [Data. High], [Data. Low] [CRC high] [CRC low] Data read Query = [0 x Sr.No.] , [0 x 01], [0 x 00], [0 x 00] , [0 x 00], [0 x 48(h)] [0 x CRC high] [0 x CRC low] Fun code = 0X01 Data word - Address word < 74. Response = [Sr.No.] , [0 x 01], [9], [255], [255], [255], [254] [255], [255] [254] [255], [255] [CRC high] [CRC low] This is response of above query where First 3 words represent status of skip-unskip of 24 channels.(skip - 0,unskip - 1) Second 3 words represent status of AL1 (Alarm) of 24 channels. (LED on –1, LED off –0) Last 3 words represents status of AL2 (Trip) of 24 channels(LED on –1, LED off –0).

Page 32: Temp Scanner-Modbus Details

SCANNER 85XX masibus

Operational manual - 32 of 33 –

Issue No : 01A/600787

Data write Query = [0 x Sr.No.] , [0 x Fun Code], [0 x ADD. High], [0 x ADD. Low] , [0 x Data. High], [0 x Data. Low] [0 x CRC high] [0 x CRC low] Fun code = 0X05 Data word - Address word < 25. or = 73. To Skip channel Data high = 0X00. To Un- Skip channel Data high = 0XFF. Response = [Sr.No.] , [0 x Fun Code], [ADD High], [ADD Low] , [Data. High], [Data. Low] [CRC high] [CRC low]. For Example Query to skip channel 5 [0 x Sr.No.] , [0 x Fun Code], [0 x 00], [0 x 04] , [0 x 00], [0 x Data. Low] [0 x CRC high] [0 x CRC low] Response after data write [0 x Sr.No.] , [0 x Fun Code], [0 x 00], [0 x 04] , [0 x 00], [0 x Data. Low] [0 x CRC high] [0 x CRC low] Query to Un-skip channel 12 [0 x Sr.No.] , [0 x Fun Code], [0 x 00], [0 x 0B] , [0 x FF], [0 x Data. Low] [0 x CRC high] [0 x CRC low] Response after data write [0 x Sr.No.] , [0 x Fun Code], [0 x 00], [0 x 0B] , [0 x FF], [0 x Data. Low] [0 x CRC high] [0 x CRC low] Query to ACK [0 x Sr.No.] , [0 x Fun Code], [0 x 00], [0 x 48] , [0 x 00], [0 x Data. Low] [0 x CRC high] [0 x CRC low] Response after data write [0 x Sr.No.] , [0 x Fun Code], [0 x 00], [0 x 48] , [0 x 00], [0 x Data. Low] [0 x CRC high] [0 x CRC low] Query to ACK [0 x Sr.No.] , [0 x Fun Code], [0 x 00], [0 x 48] , [0 x 00], [0 x Data. Low] [0 x CRC high] [0 x CRC low] Response after data write [0 x Sr.No.] , [0 x Fun Code], [0 x 00], [0 x 48] , [0 x 00], [0 x Data. Low] [0 x CRC high] [0 x CRC low]

14.3.2.1. Skip/Unskip channel address Sr. No. Digital Parameters Absolute Address Type of Access Parameter Type Values Applicable1. SKIP1_1 00001 Read/Write Int 0 - 1 2. SKIP2_1 00002 Read/Write Int 0 - 1 3. SKIP3_1 00003 Read/Write Int 0 - 1

Page 33: Temp Scanner-Modbus Details

SCANNER 85XX masibus

Operational manual - 33 of 33 –

Issue No : 01A/600787

4. SKIP4_1 00004 Read/Write Int 0 - 1 5. SKIP5_1 00005 Read/Write Int 0 - 1 6. SKIP6_1 00006 Read/Write Int 0 - 1 7. SKIP7_1 00007 Read/Write Int 0 - 1 8. SKIP8_1 00008 Read/Write Int 0 - 1 9. SKIP9_1 00009 Read/Write Int 0 - 1 10. SKIP10_1 00010 Read/Write Int 0 - 1 11. SKIP11_1 00011 Read/Write Int 0 - 1 12. SKIP12_1 00012 Read/Write Int 0 - 1 13. SKIP13_1 00013 Read/Write Int 0 - 1 14. SKIP14_1 00014 Read/Write Int 0 - 1 15. SKIP15_1 00015 Read/Write Int 0 - 1 16. SKIP16_1 00016 Read/Write Int 0 - 1 17. SKIP17_1 00017 Read/Write Int 0 - 1 18. SKIP18_1 00018 Read/Write Int 0 - 1 19. SKIP19_1 00019 Read/Write Int 0 - 1 20. SKIP20_1 00020 Read/Write Int 0 - 1 21. SKIP21_1 00021 Read/Write Int 0 - 1 22. SKIP22_1 00022 Read/Write Int 0 - 1 23. SKIP23_1 00023 Read/Write Int 0 - 1 24. SKIP24_1 00024 Read/Write Int 0 - 1

14.3.2.2. Alarm (AL1) Status of individual channel Sr. No. Digital Parameters Absolute Address Type of Access Parameter Type Values Applicable25. DALM1_1 00025 Read only Int 0 - 1 26. DALM2_1 00026 Read only Int 0 - 1 27. DALM3_1 00027 Read only Int 0 - 1 28. DALM4_1 00028 Read only Int 0 - 1 29. DALM5_1 00029 Read only Int 0 - 1 30. DALM6_1 00030 Read only Int 0 - 1 31. DALM7_1 00031 Read only Int 0 - 1 32. DALM8_1 00032 Read only Int 0 - 1 33. DALM9_1 00033 Read only Int 0 - 1 34. DALM10_1 00034 Read only Int 0 - 1 35. DALM11_1 00035 Read only Int 0 - 1 36. DALM12_1 00036 Read only Int 0 - 1 37. DALM13_1 00037 Read only Int 0 - 1 38. DALM14_1 00038 Read only Int 0 - 1 39. DALM15_1 00039 Read only Int 0 - 1 40. DALM16_1 00040 Read only Int 0 - 1 41. DALM17_1 00041 Read only Int 0 - 1 42. DALM18_1 00042 Read only Int 0 - 1 43. DALM19_1 00043 Read only Int 0 - 1 44. DALM20_1 00044 Read only Int 0 - 1 45. DALM21_1 00045 Read only Int 0 - 1 46. DALM22_1 00046 Read only Int 0 - 1 47. DALM23_1 00047 Read only Int 0 - 1 48. DALM24_1 00048 Read only Int 0 - 1

14.3.2.3. Trip (AL2) Status of individual channel Sr. No. Digital Parameters Absolute Address Type of Access Parameter Type Values Applicable49. DTRIP1_1 00049 Read only Int 0 - 1 50. DTRIP2_1 00050 Read only Int 0 - 1 51. DTRIP3_1 00051 Read only Int 0 - 1

Page 34: Temp Scanner-Modbus Details

SCANNER 85XX masibus

Operational manual - 34 of 33 –

Issue No : 01A/600787

52. DTRIP4_1 00052 Read only Int 0 - 1 53. DTRIP5_1 00053 Read only Int 0 - 1 54. DTRIP6_1 00054 Read only Int 0 - 1 55. DTRIP7_1 00055 Read only Int 0 - 1 56. DTRIP8_1 00056 Read only Int 0 - 1 57. DTRIP9_1 00057 Read only Int 0 - 1 58. DTRIP10_1 00058 Read only Int 0 - 1 59. DTRIP11_1 00059 Read only Int 0 - 1 60. DTRIP12_1 00060 Read only Int 0 - 1 61. DTRIP13_1 00061 Read only Int 0 - 1 62. DTRIP14_1 00062 Read only Int 0 - 1 63. DTRIP15_1 00063 Read only Int 0 - 1 64. DTRIP16_1 00064 Read only Int 0 - 1 65. DTRIP17_1 00065 Read only Int 0 - 1 66. DTRIP18_1 00066 Read only Int 0 - 1 67. DTRIP19_1 00067 Read only Int 0 - 1 68. DTRIP20_1 00068 Read only Int 0 - 1 69. DTRIP21_1 00069 Read only Int 0 - 1 70. DTRIP22_1 00070 Read only Int 0 - 1 71. DTRIP23_1 00071 Read only Int 0 - 1 72. DTRIP24_1 00072 Read only Int 0 - 1 73. ACK 00073 Write only Int 0 - 1

Page 35: Temp Scanner-Modbus Details

SCANNER 85XX masibus

Operational manual - 35 of 33 –

Issue No : 01A/600787

14.3.3. Configuration parameter Read – write.

Data read Query = [0 x Sr.No.] , [0 x 03], [0 x 01], [0 x ADD. Low] , [0 x Data. High], [0 x Data. Low] [0 x CRC high] [0 x CRC low] Fun code = 0X03 Data word - Address word < . Response = [Sr.No.] , [Fun code], [Byte count], [Data High], [Data Low] …….., [Data. High], [Data. Low] [CRC high] [CRC low] Data write Query = [0 x Sr.No.] , [0 x 06], [0 x 01], [0 x ADD. Low] , [0 x Data. High], [0 x Data. Low] [0 x CRC high] [0 x CRC low] Fun code = 0X06 Data word - Address word < 24. Response = [Sr.No.] , [06], [ADD High] , [ADD Low] , [Data. High], [Data. Low] [CRC high] [CRC low] Sr.no Analog Parameters Absolute

Address Type of Access Parameter Type Values Applicae

1) I/P type 40001 Read/write Int 1 To 12 2) Scanner Type 40002 Read/write Int 8-16-24 3) Open Collector 40003 Read/write Int 0-1 4) No of group 40004 Read/write Int 0 To 6 5) Set Point Type 40005 Read/write Int 0-1-2 6) *Letch Led byte &

common DP 40006 Read/write

Int 0-1

7) CH in GRP1 40007 Read/write Int 1 To 19 8) CH in GRP2 40008 Read/write Int 1 To 19 9) CH in GRP3 40009 Read/write Int 1 To 19 10) CH in GRP4 40010 Read/write Int 1 To 19 11) CH in GRP5 40011 Read/write Int 1 To 19 12) CH in GRP6 40012 Read/write Int 1 To 19 13) Open Sensor 40013 Read/write Int 0-1 14) Hysteresis Byte 40014 Read/write Int 0 To 100 15) Scan Time 40015 Read/write Int 1 To 99 16) Abnormal Logic Al1 40016 Read/write Int 0-1 17) Abnormal Logic Al2 40017 Read/write Int 0-1 18) **Normal Relay status

AL1 and AL2 40018 Read/write Int 0-1

19) Password 40019 Read/write Int 0 To 99 20) Serial No. 40020 Read/write Int 0 To 99 21) Baud rate 40021 Read/write Int 0 To 6 22) Common Span 40022 Read/write Int Act zero to Act

Span 23) Common Zero 40023 Read/write Int Act zero to Act

Span 24) Open collector Type 40024 Read/write Int 0-1 25) Configuration Type 40025 Read only Int NA

latch LED Byte value is in least Significant Byte from bits 0-1-2-3. Common DP value is in most significant Byte 4-5-6-7. ** Normal relay status AL1 value is in least significant byte from bits 0-1-2-3. Normal relay status al2 value is in most significant byte 4-5-6-7.