PiiGAB Processinformation i Göteborg AB • Anders Carlssons gata 7 • SE-417 55 Göteborg • Sweden Tel: +46(0)31-55 99 77 • Fax: +46(31)-22 70 71 • www.piigab.com • email: [email protected] Troubleshooting M-Bus meters M-Bus meters PiiGAB M-Bus Setup Wizard Find PiiGAB’s M-Bus gateways on the network. Set IP-address of PiiGAB’s M-Bus gateways on the network. Test M-Bus meters. Set primary address of M-Bus meters. Set communication speed M-Bus meters. See the raw data sent to and from the M-Bus meters. Search M-Bus meters. PiiGAB M-Bus Explorer Assumes you have an established connection with the M-Bus gateways and the M-Bus meters. See what objects are possible to read from an M-Bus meter: o Objects data types o Objects physical quantities o Objects scaling o Objects values See what telegram contains the M-Bus meter’s objects.

Transcript of Troubleshooting M-Bus meters · client2 Modbus client3 Modbus client4 Modbus client M-Bus meters...

Page 1: Troubleshooting M-Bus meters · client2 Modbus client3 Modbus client4 Modbus client M-Bus meters Possibilities Allowing any Modbus clients to read the M-Bus meters. Up to four Modbus

PiiGAB Processinformation i Göteborg AB • Anders Carlssons gata 7 • SE-417 55 Göteborg • Sweden Tel: +46(0)31-55 99 77 • Fax: +46(31)-22 70 71 • www.piigab.com • email: [email protected]

Troubleshooting M-Bus meters

M-Busmeters

PiiGAB M-Bus Setup Wizard Find PiiGAB’s M-Bus gateways on the network.

Set IP-address of PiiGAB’s M-Bus gateways on the network.

Test M-Bus meters.

Set primary address of M-Bus meters.

Set communication speed M-Bus meters.

See the raw data sent to and from the M-Bus meters.

Search M-Bus meters.

PiiGAB M-Bus Explorer Assumes you have an established connection with the M-Bus gateways and the M-Bus

meters.

See what objects are possible to read from an M-Bus meter:

o Objects data types

o Objects physical quantities

o Objects scaling

o Objects values

See what telegram contains the M-Bus meter’s objects.

Page 2: Troubleshooting M-Bus meters · client2 Modbus client3 Modbus client4 Modbus client M-Bus meters Possibilities Allowing any Modbus clients to read the M-Bus meters. Up to four Modbus

PiiGAB Processinformation i Göteborg AB • Anders Carlssons gata 7 • SE-417 55 Göteborg • Sweden Tel: +46(0)31-55 99 77 • Fax: +46(31)-22 70 71 • www.piigab.com • email: [email protected]

MBus2MBus

M-Busmeters

M-Busclient1

M-Busclient2

M-Busclient3

M-Busclient4

M-Busclient2

M-Busclient1

M-Busmeters

Possibilities Transparent M-Bus traffic between the M-Bus meter and the M-Bus client. PiiGAB M-Bus 900

will not affect the requests and responses in any way.

Up to four M-Bus clients can read the M-Bus meters independently.

The M-Bus client can communicate UDP/IP, TCP/IP, RS232 or RS485 with PiiGAB M-Bus 900.

A separate M-Bus master can also be used and will be regarded as an M-Bus client.

Internal switching function with queue that selects what M-Bus client has access to the M-

Bus meters.

Limitations Half duplex on the M-Bus loop. Not possible to read the M-Bus meters in parallel.

Slow readout time of M-Bus meters. Normally there is about a 1 second readout time (2400

baud). It may vary depending on the baud rate from 0,5 seconds to 10 seconds.

The more M-Bus clients the more each client has to take into consideration that the readout

time will increase. Time = Readout time for one M-Bus meter x Number of clients.

Page 3: Troubleshooting M-Bus meters · client2 Modbus client3 Modbus client4 Modbus client M-Bus meters Possibilities Allowing any Modbus clients to read the M-Bus meters. Up to four Modbus

PiiGAB Processinformation i Göteborg AB • Anders Carlssons gata 7 • SE-417 55 Göteborg • Sweden Tel: +46(0)31-55 99 77 • Fax: +46(31)-22 70 71 • www.piigab.com • email: [email protected]

MBus2Modbus

M-Busmeters

Modbusclient1

Modbusclient2

Modbusclient3

Modbusclient4

Modbusclient

M-Busmeters

Possibilities Allowing any Modbus clients to read the M-Bus meters.

Up to four Modbus clients can read the M-Bus meters independently.

Modbus TCP or Modbus RTU over UDP/IP, TCP/IP, RS232 or RS485.

Modbus function 3 or function 4.

Use the PiiGAB M-Bus Explorer to specify which register corresponds to particular objects in

the M-Bus meters.

Use the Modbus client in PiiGAB M-Bus Setup Wizard to test the MBus2Modbus

configuration.

Limitations Half duplex on M-Bus loop. Not possible to read M-Bus meters in parallel.

Slow readout time of M-Bus meters. Normally there is about a 1 second readout time (2400

baud). It may vary depending on the baud rate from 0,5 seconds to 10 seconds.

The more M-Bus clients the more each client has to take into consideration that the readout

time will increase. Time = Readout time for one M-Bus meter x Number of clients.

Beware of multi-telegram M-Bus meters as they might cause long read-out times.

Page 4: Troubleshooting M-Bus meters · client2 Modbus client3 Modbus client4 Modbus client M-Bus meters Possibilities Allowing any Modbus clients to read the M-Bus meters. Up to four Modbus

PiiGAB Processinformation i Göteborg AB • Anders Carlssons gata 7 • SE-417 55 Göteborg • Sweden Tel: +46(0)31-55 99 77 • Fax: +46(31)-22 70 71 • www.piigab.com • email: [email protected]

MBus2MBusASCII

M-Busmeters

MBusASCIIclient1

MBusASCIIclient2

MBusASCIIclient3

MBusASCIIclient4

MBusASCII client

M-Busmeters

Possibilities Allowing any M-Bus ASCII clients to read the M-Bus meters.

Up to four M-Bus ASCII clients can read the M-Bus meters independently.

Allowing the QuickPost in PiiGAB M-Bus 900 to read the M-Bus meters.

M-Bus ASCII over UDP/IP, TCP/IP, RS232 or RS485.

Use the PiiGAB M-Bus Explorer to specify what objects to read from the M-Bus meters.

Use the M-Bus ASCII client in PiiGAB M-Bus Setup Wizard to test the MBus2MBusASCII

configuration.

M-Bus ASCII is PiiGAB’s open data protocol.

Limitations Half duplex on M-Bus loop. Not possible to read M-Bus meters in parallel.

Slow readout time of M-Bus meters. Normally there is about a 1 second readout time (2400

baud). It may vary depending on the baud rate from 0,5 seconds to 10 seconds.

The more M-Bus clients the more each client has to take into consideration that the readout

time will increase. Time = Readout time for one M-Bus meter x Number of clients.

Beware of multi-telegram M-Bus meters as they might cause long read-out times.

Page 5: Troubleshooting M-Bus meters · client2 Modbus client3 Modbus client4 Modbus client M-Bus meters Possibilities Allowing any Modbus clients to read the M-Bus meters. Up to four Modbus

PiiGAB Processinformation i Göteborg AB • Anders Carlssons gata 7 • SE-417 55 Göteborg • Sweden Tel: +46(0)31-55 99 77 • Fax: +46(31)-22 70 71 • www.piigab.com • email: [email protected]

MBus2Clients

M-Busmeters

M-Busclient

Modbusclient

MBusASCIIclient

Possibilities Allowing M-Bus, M-Bus gateways, Modbus or M-Bus ASCII clients to read the M-Bus meters.

Up to four clients can read the M-Bus meters independently.

Communication over UDP/IP, TCP/IP, RS232, RS485 or as M-Bus slave.

Limitations Half duplex on M-Bus loop. Not possible to read M-Bus meters in parallel.

Slow readout time of M-Bus meters. Normally there is about 1 a second readout time (2400

baud). It may vary depending on the baud rate from 0,5seconds to 10 seconds.

The more M-Bus clients the more each client has to take into consideration that the readout

time will increase. Time = Readout time for one M-Bus meter x Number of clients.

Beware of multi-telegram M-Bus meters as they might cause long read-out times.

Page 6: Troubleshooting M-Bus meters · client2 Modbus client3 Modbus client4 Modbus client M-Bus meters Possibilities Allowing any Modbus clients to read the M-Bus meters. Up to four Modbus

PiiGAB Processinformation i Göteborg AB • Anders Carlssons gata 7 • SE-417 55 Göteborg • Sweden Tel: +46(0)31-55 99 77 • Fax: +46(31)-22 70 71 • www.piigab.com • email: [email protected]

Modbus2MBus

M-Busclient

Modbus RTUmeters/slaves

M-Busmeters

Modbus RTUmeters/slaves

Possibilities Allowing Modbus meters/slaves to be converted to M-Bus.

Extend an M-Bus loop with Modbus meters/slaves.

Modbus RTU over RS485, RS232, UDP/IP or TCP/IP.

Modbus function 3 and function 4.

Virtual M-Bus meters will represent the Modbus meters/slaves.

Use primary or secondary addresses.

Limitations Only Modbus RTU meters/slaves.

Page 7: Troubleshooting M-Bus meters · client2 Modbus client3 Modbus client4 Modbus client M-Bus meters Possibilities Allowing any Modbus clients to read the M-Bus meters. Up to four Modbus

PiiGAB Processinformation i Göteborg AB • Anders Carlssons gata 7 • SE-417 55 Göteborg • Sweden Tel: +46(0)31-55 99 77 • Fax: +46(31)-22 70 71 • www.piigab.com • email: [email protected]

QuickPost (MBus2MBusASCII for FTP- or HttpPost-servers)

FTP-serverHttpPost-server

FTP-serverHttpPost-server

M-Busmeters

WWW

Possibilities Reads M-Bus meters with the MBus2MBusASCII principle.

QuickPost uses an internal MBusASCII client.

Specify when to read the M-Bus meters.

All read-out is stored in files.

Specify a FTP-server or an HttpPost-server as the remote server.

Specify when to send the files to the remote server.

Limitations Half duplex on M-Bus loop. Not possible to read M-Bus meters in parallel.

Slow readout time of M-Bus meters. Normally there is about 1 a second readout time (2400

baud). It may vary depending on the baud rate from 0,5seconds to 10 seconds.

The more M-Bus clients the more each client has to take into consideration that the readout

time will increase. Time = Readout time for one M-Bus meter x Number of clients.

Beware of multi-telegram M-Bus meters as they might cause long read-out times.

Page 8: Troubleshooting M-Bus meters · client2 Modbus client3 Modbus client4 Modbus client M-Bus meters Possibilities Allowing any Modbus clients to read the M-Bus meters. Up to four Modbus

PiiGAB Processinformation i Göteborg AB • Anders Carlssons gata 7 • SE-417 55 Göteborg • Sweden Tel: +46(0)31-55 99 77 • Fax: +46(31)-22 70 71 • www.piigab.com • email: [email protected]

Port forward

Client(M-Bus,Modbus,

MBusASCII)

WWW

Meters(M-Bus,

Modbus)

Possibilities No setup needed for port forward in the PiiGAB M-Bus 900. Setup the port forward in the

router.

Read the M-Bus meters or Modbus meters (Modbus2MBus) from the remote clients.

Up to four remote clients.

Remote access for UDP/IP or TCP/IP.

Limitations Half duplex on M-Bus loop. Not possible to read M-Bus meters in parallel.

Slow readout time of M-Bus meters. Normally there is about 1 a second readout time (2400

baud). It may vary depending on the baud rate from 0,5seconds to 10 seconds.

The more M-Bus clients the more each client has to take into consideration that the readout

time will increase. Time = Readout time for one M-Bus meter x Number of clients.

Beware of multi-telegram M-Bus meters as they might cause long read-out times.

Page 9: Troubleshooting M-Bus meters · client2 Modbus client3 Modbus client4 Modbus client M-Bus meters Possibilities Allowing any Modbus clients to read the M-Bus meters. Up to four Modbus

PiiGAB Processinformation i Göteborg AB • Anders Carlssons gata 7 • SE-417 55 Göteborg • Sweden Tel: +46(0)31-55 99 77 • Fax: +46(31)-22 70 71 • www.piigab.com • email: [email protected]

MBus2OPC - General

OPC client 1

OPC client N

M-Busmeters

M-Busmeters

M-Bus client

OPC-server

Possibilities Read any M-Bus meters with primary or secondary addresses.

Communicate with any M-Bus gateways through UDP/IP, TCP/IP or serial.

Handles both single-telegram and multi-telegram M-Bus meters.

Any OPC-clients may connect to the OPC-server to read the M-Bus meters.

Page 10: Troubleshooting M-Bus meters · client2 Modbus client3 Modbus client4 Modbus client M-Bus meters Possibilities Allowing any Modbus clients to read the M-Bus meters. Up to four Modbus

PiiGAB Processinformation i Göteborg AB • Anders Carlssons gata 7 • SE-417 55 Göteborg • Sweden Tel: +46(0)31-55 99 77 • Fax: +46(31)-22 70 71 • www.piigab.com • email: [email protected]

MBus2OPC – Extended

OPC client 1

OPC client N

M-Busmeters

M-Busmeters

M-Bus client

OPC-server

OPC client 1

OPC client N

M-Bus client

OPC-server

M-Busmeters

Possibilities Use the multiple clients feature in the PiiGAB M-Bus 900 to read the M-Bus meters from

several OPC-servers.

Page 11: Troubleshooting M-Bus meters · client2 Modbus client3 Modbus client4 Modbus client M-Bus meters Possibilities Allowing any Modbus clients to read the M-Bus meters. Up to four Modbus

PiiGAB Processinformation i Göteborg AB • Anders Carlssons gata 7 • SE-417 55 Göteborg • Sweden Tel: +46(0)31-55 99 77 • Fax: +46(31)-22 70 71 • www.piigab.com • email: [email protected]

QuickLoop

DatabaseDatabase

OPC-server A

FTPFTP

OPC-server B

M-Busmeters

M-Bus client

OPC-server

OPC-client

Possibilities Use the internal OPC-client in QuickLoop to read any OPC-server.

Specify how often to read the OPC-tags.

Specify how to export the read OPC-tags.

o Export to text-file.

o Export to XML-file.

o Export to Microsoft SQL-server.

o Export to any SQL-server through an ODBC-connection.

Send exported file to a remote FTP-server.

Limitations Beware of how much time it will take for the OPC-servers to read the OPC-tags. Change the

sample period time accordingly.

Page 12: Troubleshooting M-Bus meters · client2 Modbus client3 Modbus client4 Modbus client M-Bus meters Possibilities Allowing any Modbus clients to read the M-Bus meters. Up to four Modbus

PiiGAB Processinformation i Göteborg AB • Anders Carlssons gata 7 • SE-417 55 Göteborg • Sweden Tel: +46(0)31-55 99 77 • Fax: +46(31)-22 70 71 • www.piigab.com • email: [email protected]

Total solution all inclusive

DatabaseDatabase FTPFTP

OPC client 1

cPC client n

Modbus RTUmeters/slaves

M-Busmeters

Modbusclient

M-Busclient

FTP-serverHttpPost-server

FTP-serverHttpPost-server

WWW

Read M-Bus meters

Modbus meters/slaves

Read M-Bus meters from M-Bus-clients

PiiGAB M-Bus Explorer / M-Bus OPC-server

Modbus TCP or Modbus RTU clients

MBusASCII clients, to use the QuickPost application

Convert Modbus meters/slaves to Read the Modbus meters as virtual M-Bus meters with the Modbsu2MBus application.

The virtual M-Bus meters can be used as normal M-Bus meters.

Page 13: Troubleshooting M-Bus meters · client2 Modbus client3 Modbus client4 Modbus client M-Bus meters Possibilities Allowing any Modbus clients to read the M-Bus meters. Up to four Modbus

PiiGAB Processinformation i Göteborg AB • Anders Carlssons gata 7 • SE-417 55 Göteborg • Sweden Tel: +46(0)31-55 99 77 • Fax: +46(31)-22 70 71 • www.piigab.com • email: [email protected]

Contacts

PiiGAB Processinformation Anders Carlssons gata 7

417 55 Göteborg Sweden

Phone + 46 31 55 99 77

www.piigab.com

Distributors Please contact our distributors in respective countries:

Germany Relay GmbH Stettiner Str. 38 33106 Paderborn Germany Phone +49 5251 17670 www.relay.de

Norway Autic Systems AS Stoltenbergs gate 48 3110 Tønsberg Norway Phone +47 33 30 09 50 www.autic.no

Czech Republic Papouch s.r.o. Strasnicka 3164/1a 102 00 PRAGUE 10 Czech Republic Phone +420 267 314 267 www.papouch.com