Summer_Training_HTPP-libre (1).pdf

download Summer_Training_HTPP-libre (1).pdf

of 20

Transcript of Summer_Training_HTPP-libre (1).pdf

  • 8/11/2019 Summer_Training_HTPP-libre (1).pdf

    1/20

    0

    Summer Training

    REPORTHarduaganj Thermal Power Plant

    Uttar Pradesh Rajya Vidyut Utpadan

    Nagar Limited (UPRVUNL)

    1

    st

    July 2013 1

    st

    August 2013

    Ali Shazan Gulrez

    B-Tech (Electrical) II Year

    Aligarh Muslim University

    Verified By: Checked By:

  • 8/11/2019 Summer_Training_HTPP-libre (1).pdf

    2/20

    1

    Harduaganj Thermal Power Plant

    UNIT 1 to 4 & 6 DeletedUNIT 5 60 MW

    UNIT: 7(R&M) 120 MWExtension (UNIT: 8 &9) 2 x 250 MW

    Proposed 1 x 660 MW

    Harduaganj Thermal Power Plant, Kasimpur

  • 8/11/2019 Summer_Training_HTPP-libre (1).pdf

    3/20

    2

    Contents

    S.No Topic Page No.

    1 Thermal Power Plant: An Overview 42 Electrical System Layout 53 System Components 5

    3.1 Switchyard 53.2 Isolator 63.3 Circuit Breaker 63.4 Generator 73.5 Generator Transformer 7

    3.6 Neutral Grounding Transformer 73.7 Station Transformer 73.8 Unit Auxiliary Transformer 83.9 Switchgear 8

    3.10 Double Bus System with Transfer Bus 83.11 Bays 93.12 Instrument Transformers 9

    4 Electrical Protection System 104.1 Fuse 104.2 Relays 104.3 Circuit Breakers 10

    4.4 Lightning Arrestor 104.5 Isolators 105 Generator Protection 11

    5.1 Class A Trip 115.2 Class B Trip 115.3 Class C Trip 115.4 Differential Protection 125.5 Earth Fault Protection 125.6 Negative Phase Sequence 125.7 Over Voltage Protection 12

    5.8 Backup Impedance 125.9 Reverse Power Protection 13

    5.10 Low Forward Power Protection 135.11 Pole Splitting Protection 135.12 Over-Current Protection 135.13 Under Frequency Protection 135.14 Generator Relay Protection Panels 145.15 GRP 8A 145.16 GRP 8B 145.17 GRP 8C 145.18 BCU Panel 14

  • 8/11/2019 Summer_Training_HTPP-libre (1).pdf

    4/20

    3

    6 Transformer Protection 156.1 Buchholz Protection 156.2 PRV Protection 156.3 OSR Protection 156.4 Temperature Protection 157 Ratings 16

    7.1 Generator Rating 167.2 Generator Transformer Rating 17

    7.3 Station Transformer Rating 177.4 Unit Auxiliary Transformer Rating 18

  • 8/11/2019 Summer_Training_HTPP-libre (1).pdf

    5/20

    4

    (1) Thermal Power Plant: An Overview

    In a coal based power plant coal is transported from coal mines to the power plant by

    railway in wagons. Coal is unloaded from the wagons to a moving underground

    conveyor belt. This coal from the mines is of no uniform size. So it is taken to the

    Crusher house and crushed to a size of 20mm. It is then stored in coal bunkers. Raw

    coal from the raw coal bunker is supplied to the Coal Mills by a Raw Coal Feeder.

    The Coal Mills or pulverizer pulverizes the coal to 200 mesh size. The powdered coal

    from the coal mills is carried to the boiler in coal pipes by high pressure hot air. The

    pulverized coal air mixture is burnt in the boiler in the combustion zone. The boiler is

    a water tube boiler hanging from the top. Water is converted to steam in the boiler

    and steam is separated from water in the boiler Drum. The saturated steam from the

    boiler drum is taken to the Low Temperature Superheater, Platen Superheater and

    Final Superheater respectively for superheating. The superheated steam from the

    final superheater is taken to the High Pressure Steam Turbine (HPT). In the HPT thesteam pressure is utilized to rotate the turbine and the resultant is rotational energy.

    From the HPT the out coming steam is taken to the Reheater in the boiler to

    increase its temperature as the steam becomes wet at the HPT outlet. After

    reheating this steam is taken to the Intermediate Pressure Turbine (IPT) and then to

    the Low Pressure Turbine (LPT). The outlet of the LPT is sent to the condenser for

    condensing back to water by a cooling water system. This condensed water is

    collected in the Hotwell and is again sent to the boiler in a closed cycle. The

    rotational energy imparted to the turbine by high pressure steam is converted to

    electrical energy in the Generator.

  • 8/11/2019 Summer_Training_HTPP-libre (1).pdf

    6/20

    5

    (2) Electrical System Layout

    (3) System Components

    3.1 Switchyard

    A switchyard is essentially a hub for electrical power sources. For instance, a

    switchyard will exist at a generating station to coordinate the exchange of

    power between the generators and the transmission lines in the area. A

    switchyard will also exist when high voltage lines need to be converted to

    lower voltage for distribution to consumers.

    The function of electrical switch yard is to delivered the generated power from

    power plant at desired voltage level to the nearest grid. or In Another way we

    can say Simply switching the received power supply from various generatingstations to various locations with respect to their requirement. Therefore a

    switchyard will contain; current carrying conductors, grounding wires and

  • 8/11/2019 Summer_Training_HTPP-libre (1).pdf

    7/20

    6

    switches, transformers, disconnects,isolators, remotely controlled arc snuffing

    breakers, metering devices, etc.

    Switchyard of Harduaganj Thermal Power Plant 220KV/132KV

    3.2 Isolator

    Isolators are used in electrical substations to allow isolation of apparatus

    such ascircuit breakers andtransformers, and transmission lines, formaintenance. Often the isolation switch is not intended for normal control of

    the circuit and is used only for isolation.

    3.3 Circuit Breakers

    A circuit breaker is an automatically operatedelectricalswitch designed to

    protect anelectrical circuit from damage caused byoverload orshort circuit.

    Its basic function is to detect a fault condition and interrupt current flow. Unlike

    afuse,which operates once and then must be replaced, a circuit breaker canbe reset (either manually or automatically) to resume normal operation. Circuit

    breakers are made in varying sizes, from small devices that protect an

    http://en.wikipedia.org/wiki/Circuit_breakerhttp://en.wikipedia.org/wiki/Transformerhttp://en.wikipedia.org/wiki/Electricityhttp://en.wikipedia.org/wiki/Switchhttp://en.wikipedia.org/wiki/Electrical_networkhttp://en.wikipedia.org/wiki/Overcurrenthttp://en.wikipedia.org/wiki/Short_circuithttp://en.wikipedia.org/wiki/Fuse_(electrical)http://en.wikipedia.org/wiki/Fuse_(electrical)http://en.wikipedia.org/wiki/Short_circuithttp://en.wikipedia.org/wiki/Overcurrenthttp://en.wikipedia.org/wiki/Electrical_networkhttp://en.wikipedia.org/wiki/Switchhttp://en.wikipedia.org/wiki/Electricityhttp://en.wikipedia.org/wiki/Transformerhttp://en.wikipedia.org/wiki/Circuit_breaker
  • 8/11/2019 Summer_Training_HTPP-libre (1).pdf

    8/20

    7

    individual household appliance up to largeswitchgear designed to protect

    high-voltage circuits feeding an entire city.

    3.4 Generator

    The Generator is 250MW, 16.5KV, 10KA hydrogen cooled generator. The

    generator operate typically at 3000 rpm. When Generator is in operating

    Condition a part of Power delivered is diverted to run the auxiliaries which is

    about 8-10% of total power developed. It produces power at 0.85 power

    factor.

    3.5 Generator Transformer (16.5KV/220KV)

    This is a type of Power Transformer of 315 MVA where the LV winding isconnected to the generator through the bus duct and HV winding to the

    transmission system. In addition to the features of Power Transformer, our

    Generator Transformer is designed to withstand over voltage caused by

    sudden load throw off from the generator. It is built as a single or three phase

    unit and located in power stations.

    3.6 Neutral Grounding Transformer (NGT)

    Neutral grounding transformers are used to derive a neutral-to-earthconnection for systems that do not otherwise have one.The transformerprimary terminals (wye side) are connected to the power system, and itsneutral is connected to earth, perhaps through a controlled impedance. Noother load is connected to the delta of the transformer.These transformersprovide a high impedance to normal currents (positive & negative sequence),but allow ground fault currents (zero sequence) to flow, thereby allowingprotective devices to operate if a ground fault occurs.

    3.7 Station Transformer

    This transformer 220KV/6.6KV 50MVA is used in sub stations to transfer theincoming voltage to the next voltage level. It can be system or autotransformer with two/three windings. In general it is equipped with On load tapchangers and are connected to transmission grids by bushings and cables.The system/auto transformer is built in core form. HV/LV windings aregalvanically separated for system transformer while they are Auto connectedfor auto transformer.

    http://en.wikipedia.org/wiki/Switchgearhttp://en.wikipedia.org/wiki/Switchgear
  • 8/11/2019 Summer_Training_HTPP-libre (1).pdf

    9/20

    8

    3.8 Unit Auxiliary Transformer UAT

    The Unit Auxiliary Transformer is the Power Transformer that provides power

    to the auxiliary equipment of a power generating station during its normal

    operation. This transformer is connected directly to the generator out-put by atap-off of the isolated phase bus duct and thus becomes cheapest source of

    power to the generating station. It is generally a three-winding transformer i.e.

    one primary and two separate secondary windings. Primary winding of UAT is

    equal to the main generator voltage rating. The secondary windings can have

    same or different voltages. In power plant at Harduaganj it is rated as

    16.5KV/6.6KV 31.5MVA.

    3.9 Switchgear

    In an electric power system, switchgear is the combination of electrical

    disconnect switches, fuses or circuit breakers used to control, protect and

    isolate electrical equipment. Switchgear is used both to de-energize

    equipment to allow work to be done and to clearfaults downstream. This type

    of equipment is important because it is directly linked to the reliability of the

    electricity supply. It is rated as 6.6KV and 0.4KV switchgear in the Power plant

    Switchgear of Harduaganj Thermal Power Plant

    3.10 Double Bus System with Transfer Bus

    In double bus bar system two identical bus bars are used in such a way that

    any outgoing or incoming feeder can be taken from any of the bus.Actually

    http://en.wikipedia.org/wiki/Electric_power_systemhttp://en.wikipedia.org/wiki/Fuse_%28electrical%29http://en.wikipedia.org/wiki/Circuit_breakerhttp://en.wikipedia.org/wiki/Fault_%28power_engineering%29http://en.wikipedia.org/wiki/Electricityhttp://en.wikipedia.org/wiki/Electricityhttp://en.wikipedia.org/wiki/Fault_%28power_engineering%29http://en.wikipedia.org/wiki/Circuit_breakerhttp://en.wikipedia.org/wiki/Fuse_%28electrical%29http://en.wikipedia.org/wiki/Electric_power_system
  • 8/11/2019 Summer_Training_HTPP-libre (1).pdf

    10/20

    9

    every feeder is connected to both of the buses in parallel through individual

    isolator. By closing any of the isolators one can put the feeder to associated

    bus. Both of the buses are energized and total feeders are divided into two

    groups, one group is fed from one bus and other from other bus. But any

    feeder at any time can be transferred from one bus to other. If necessary thetransfer bus can be energized by main bus power by closing the transfer bus

    coupler isolators and then breaker. Then the power in transfer bus can directly

    be fed to the feeder line by closing the bypass isolator.

    3.11 Bays

    In switchyard electrical bays usually consists of Circuit Breakers , earth

    switches, Instrument transformers and protection equipments. A substation

    comprise of number of bays connected to busbars.

    A Bay has following equipments

    1. Line isolator with e/s and bus isolator

    2. Lightning arrestor

    3. Potential transformer

    4. Current transformer

    5. Circuit Breaker and

    6. Carrier communication equipments

    The following are the type of Bays1. Incoming feeder bay

    2. Outgoing feeder bay and

    3. Transformer bay

    3.12 Instrument Transformers

    Potential Transformer: Potential transformers (PT) (also called voltage

    transformers (VT)) are a parallel connected type of instrument transformer.

    They are designed to present negligible load to the supply being measured

    and have an accurate voltage ratio and phase relationship to enable accurate

    secondary connected metering.

    Current transformer: A current transformer also isolates the measuring

    instruments from what may be very high voltage in the monitored circuit.

    Current transformers are commonly used in metering and protective

    relays in theelectrical power industry

    http://en.wikipedia.org/wiki/Protective_relayhttp://en.wikipedia.org/wiki/Protective_relayhttp://en.wikipedia.org/wiki/Electrical_power_industryhttp://en.wikipedia.org/wiki/Electrical_power_industryhttp://en.wikipedia.org/wiki/Electrical_power_industryhttp://en.wikipedia.org/wiki/Protective_relayhttp://en.wikipedia.org/wiki/Protective_relay
  • 8/11/2019 Summer_Training_HTPP-libre (1).pdf

    11/20

    10

    (4) Electrical Protection System

    4.1 Fuse

    It is a type of low resistanceresistor that acts as asacrificial device to provide

    overcurrent protection, of either the load or source circuit. Its essential

    component is a metal wire or strip that melts when too much current flows,

    which interrupts thecircuit in which it is connected. Short circuit,overloading,

    mismatched loads or device failure are the prime reasons for excessive

    current.

    4.2 Relays

    A relay is anelectrically operatedswitch.Many relays use anelectromagnet to

    operate a switching mechanism mechanically, but other operating principles

    are also used. Relays are used where it is necessary to control a circuit by a

    low-power signal (with complete electrical isolation between control and

    controlled circuits), or where several circuits must be controlled by one signal.

    The first relays were used in long distance telegraph circuits, repeating the

    signal coming in from one circuit and re-transmitting it to another. Relays were

    used extensively in telephone exchanges and early computers to perform

    logical operations.

    4.3 Circuit Breakers

    They are used to isolate the faulty circuits, and are capable of carrying these

    fault currents until the fault currents are totally cleared. Circuit Breakers are

    the main isolating devices and which can be said to directly protect the

    system.

    4.4 Lightning Arrestor

    It is a device used in electric power system to protect the insulation and

    conductors from the damaging effect of lightning. It has a high voltage terminal

    and a ground terminal.When a lightning surge travels along the line to

    arrester, current from the surge is diverted to the earth.

    4.5 Isolators

    Isolators are used in electrical substations to allow isolation of apparatus such

    ascircuit breakers andtransformers,and transmission lines, for maintenance.

    Often the isolation switch is not intended for normal control of the circuit and is

    used only for isolation

    https://en.wikipedia.org/wiki/Resistorhttps://en.wikipedia.org/wiki/Sacrificial_devicehttps://en.wikipedia.org/wiki/Overcurrenthttps://en.wikipedia.org/wiki/Electrical_networkhttps://en.wikipedia.org/wiki/Short_circuithttp://en.wikipedia.org/wiki/Electrichttp://en.wikipedia.org/wiki/Switchhttp://en.wikipedia.org/wiki/Electromagnethttp://en.wikipedia.org/wiki/Circuit_breakerhttp://en.wikipedia.org/wiki/Transformerhttp://en.wikipedia.org/wiki/Transformerhttp://en.wikipedia.org/wiki/Circuit_breakerhttp://en.wikipedia.org/wiki/Electromagnethttp://en.wikipedia.org/wiki/Switchhttp://en.wikipedia.org/wiki/Electrichttps://en.wikipedia.org/wiki/Short_circuithttps://en.wikipedia.org/wiki/Electrical_networkhttps://en.wikipedia.org/wiki/Overcurrenthttps://en.wikipedia.org/wiki/Sacrificial_devicehttps://en.wikipedia.org/wiki/Resistor
  • 8/11/2019 Summer_Training_HTPP-libre (1).pdf

    12/20

    11

    (5) Generator Protection

    5.1 Class A Trip:

    This is applied to those protections which operate for severe electrical faults within

    the machine or associated equipments (Generator Differential,Overall

    Differential,Stator E/F,GT/UAT REF,Rotor E/F,Back up Impedance or Overcurrentprotection). It is used only in emergencies where continuation in service ,for any

    length of time, is not permitted.

    5.2 Class B Trip:

    This is applied to such of those protections for which electrical isolation of the

    generator can be delayed without any significant damage to the machine, in this

    mode, the turbine is tripped immediately, but tripping of GT/UAT/Field circuit breakers

    is interlocked through a low forward power relay, thereby delaying electrical isolation

    until the power output of the generator has been substantially reduced. This avoids

    over speeding of generator.

    5.3 Class C Trip:

    The Turbine-Generator (TG) unit is isolated from the grid by opening the transmission

    lines, and allowed to continue service with station load. This is applied to those

    protections, which operate for conditions external to the Generators and its

    associated equipments. This enables quick restoration by re-synchronizing the

    machine with the systems

  • 8/11/2019 Summer_Training_HTPP-libre (1).pdf

    13/20

    12

    5.4 Differential Protection

    87GT : GENERATOR+UT+ GT OVERALL PROTECTION

    87G : GENERATOR PROTECTION (EXCLUSIVE)

    87HV : GENERATOR TRANSFORMER HV WINDING

    87UAT: UNIT TRANSFORMER PROTECTION

    5.5 Earth Fault Protection

    64G2: PROTECTION OF GENERATOR STATOR WINDING

    64UAT: UNIT TRANSFORMER LV WINDING E/F PROTECTION

    51NGT BACK-UP EARTH FAULT RELAY FOR GT

    64G1: 100% PROTECTION OF GENERATOR STATOR WINDING

    95G: STATOR PHASE INTER-TURN PROTECTION

    5.6 Negative Phase Sequence Protection

    Connected on Generator Phase side CTs.

    Provided to prevent rotor Over heating in case of Unbalanced loading. Relay has Inverse Current Vs timecharacteristics with two stages

    Voltage induced in the rotor at double frequency.

    5.7 Over-Voltage Protection

    Overvoltage may be caused by the following contingencies:

    Defective operation of AVR.

    Operation under manual control with AVR out of service.

    Sudden loss of load (due to line tripping).

    5.8 Backup Impedance Protection

    Employed for the protection of the Generator against the uncleared system

    line to line faults.

    Relay has Reach setting and time delay setting

    Relay reach Setting for trip is decided based on System conditions;

    Reach should be limited and time to be more than the highest line backup

    protection time setting.

  • 8/11/2019 Summer_Training_HTPP-libre (1).pdf

    14/20

    13

    5.9 Reverse Power Protection

    This protection acts under the following conditions of operation:

    Turbine tripped and reverse power detected for 2 seconds

    Reverse Power detected for 15 seconds.

    5.10 Low Forward Power Protection

    This protection acts under the following conditions of operation:

    Turbine tripped and reverse power detected for 2 seconds

    Reverse Power detected for 15 seconds.

    5.11 Pole Slipping Protection

    During system disturbance, Generator rotor oscillates with consequent

    variation of Voltage, Current and Power factor. This leads to variation in speed

    of rotor from synchronous speed leading to slip of Pole pitch.

    Causes:

    System Faults(delayed uncleared faults)

    Power Swings

    Weak field conditions

    Effects:

    Causes rotor oscillations with cyclic variation in voltage, current,

    active/reactive power.

    5.12 Over-Current Protection

    It is usual to provide overcurrent relays of IDMT pattern to generators as ageneral back up feature. These are in no way related to the thermal

    characteristics of the generator and are intended to operate only under fault

    conditions.

    5.13 Under frequency Protection

    Results due to overloading of the generator beyond the corrective limits of

    governor. This protection is employed for the system disturbances such as

    tripping of multiple units of power stations.

  • 8/11/2019 Summer_Training_HTPP-libre (1).pdf

    15/20

    14

    5.14 Generator Relay Protection Panels

    There are 4 nos. of Generator Relay Protection Panel comprising the following

    relays having the integrated functions of the Generator Protection.

    1. GRP 8A

    2. GRP 8B

    3. GRP 8C

    4. BCU(Bay Control Unit) Panel

    5.15 GRP 8A

    It comprises the following relays:

    Overall Differential relay

    GT Overhang Differential Relay Generator Relay- 1(GR-1): It incorporates Generator Back up Impedance

    protection,Negative Phase sequence,Overvoltage,Field Failure, Undervoltage,

    Low Forward Power,Reverse Power,Stator 95% E/f Protection,

    Underfrequency / Overfrequency,Overfluxing,Generator Overload Protection)

    5.16 GRP 8B

    UAT Differential Relay

    GT Overcurrent/Earth Fault Relay Generator Relay -2(GR-2): It incorporates Generator Back up Impedance

    protection,Negative Phase sequence,Overvoltage,Pole Slipping,Field

    Failure,Undervoltage,Low Forward Power,Reverse Power,100% Stator E/f

    ,Underfrequency/Overfrequency,Overfluxing,Generator Overload Protection,

    Dead Machine Protection,Rotor E/F,Generator Differential Protection

    5.17 GRP 8C

    UAT Overcurrent/Earth fault Relay

    Energy Meter-Main

    Energy MeterCheck

    5.18 BCU Panel

    BCU relays serve the function of controlling the remote operation(opening/closing) of

    the isolators in the 220 kV Switchyard.

  • 8/11/2019 Summer_Training_HTPP-libre (1).pdf

    16/20

    15

    (6) Transformer Protection

    6.1 Buchholz Protection

    A gas operated protection with capability of detecting and warning early about an

    incipient fault. Most useful for winding inter turn faults.

    6.2 PRV Protection

    The relay detects a sudden rise in pressure and it is used to evacuate any over

    pressure due to extreme heating, to avoid explosion of the transformer tank.

    6.3 OSR Protection

    The relay detects the rate of change of pressure

    6.4 Temperature Protection

    OTI Alarm/Trip : 90/100 deg

    WTI Alarm/Trip : 95/105 deg

  • 8/11/2019 Summer_Training_HTPP-libre (1).pdf

    17/20

    16

    (7) Ratings

    7.1 Generator Rating:

    Stator:

    Active Power 250000kW

    Power Factor 0.85(lagging)

    Volt Ampere 294100kVA

    Generated Voltage 16.5kV

    Current 10291A

    Rotor:

    DC voltage 299VCurrent 2497A

    R.P.M 3000

    Frequency 50

    Connection YY

    Coolant Hydrogen

    Insulation Class F

    PM Generator (Pilot Exciter)

    Active Power 35kW

    Voltage 220V

    R.P.M 3000

    Coolant Air

    Connection YYYY

    YYYY

    Volt Ampere 35kVA

    Current 105A

    Phase 3Power Factor 1

    Frequency 400

    BRUSHLESS EXCITER

    Active Power 1350kW

    Excitation Voltage 106(DC)

    R.P.M 3000

    Insulation Class F

    Excitation Current 36.5A

    Coolant Air

  • 8/11/2019 Summer_Training_HTPP-libre (1).pdf

    18/20

    17

    Voltage 420V

    Current 3200A

    7.2 Generator Transformer rating:

    Type of cooling OFAF

    Rated Power HV-315000kVALV-315000kVA

    Rated voltage at HV-230kVno load LV-16.5kV

    Rated Line current HV-760.72ALV-11022.14A

    Maximum temperature Oil-50oCrise Winding-55oC

    Phase 3

    Frequency 50 Hz

    7.3 Station Transformer Rating:

    Type of cooling ONAN/ONAF

    Rated Power HV - 30000kVA 50000kVALV1-15000kVA 25000kVALV2-15000kVA 25000kVA

    Rated voltage at HV -220kV 220kVno load LV1- 6.9kV 6.9kV

    LV2- 6.9kV 6.9kV

    Rated Line current HV - 78.73A 131.22ALV1-1255.11A 2091.85ALV2-1255.11A 2091.85A

    Maximum temperature Oil-50oCrise Winding-55oC

    Phase 3

    Frequency 50Hz

  • 8/11/2019 Summer_Training_HTPP-libre (1).pdf

    19/20

    18

    7.4 Unit Auxiliary Transformer Rating:

    Type of cooling ONAN/ONAF

    Rated Power HV - 30000kVA 50000kVALV1-15000kVA 25000kVALV2-15000kVA 25000kVA

    Rated voltage at HV -220kV 220kVno load LV1- 6.9kV 6.9kV

    LV2- 6.9kV 6.9kV

    Rated Line current HV - 78.73A 131.22A

    LV1-1255.11A 2091.85ALV2-1255.11A 2091.85A

    Maximum temperature Oil-50oCrise Winding-55oC

    Phase 3

    Frequency 50Hz

  • 8/11/2019 Summer_Training_HTPP-libre (1).pdf

    20/20

    19