  • 8/18/2019 Siemens PXL Operation Installation Manual

    1/83

    Technical Manuals Online! - http://www.tech-man.com

  • 8/18/2019 Siemens PXL Operation Installation Manual

    2/83

    WARNING

    ALL WIRINGMUST BE DONE

    AS DESCRIBED BELOWTO OBTAIN SAFE AND PROPER SYSTEM OPERATION.

    1. Earth ground the PXL enclosureproperly; see the latest edition of theNational Electrical Code for approvedmethods. Conduit ground is notrecommended as the primary

    means of grounding.

    2. Separate all wiring for initiating devicecircuits (i.e., detectors, manualstations, etc.) from all other wiring inthe PXL enclosure. To wire theSystem in compliance with UL 864,

    refer to the Power Limited Wiring Instructions for the PSE-1 Enclosure,P/N 315-094154.

    3. INSULATE ALL CABLE DRAIN

    WIRES from any conduit or earthgrounded electrical box, includingthose in the PXL enclosure.

    4. Connect shield cable drain wireONLY inside the PXL enclosure.

    CAUTIONS AND WARNINGS

    This caution symbol appears periodically throughout this manual. Itidentifies important safety instructions. Read these instructions care-fully. Failure to follow these instructions may result in damage to theequipment.

    This warning symbol appears periodically throughout this manual. Itidentifies important safety instructions. Read these instructions care-fully. Failure to follow these instructions may result in serious or fatalpersonal injury or costly property damage.

    Technical Manuals Online! - http://www.tech-man.com

  • 8/18/2019 Siemens PXL Operation Installation Manual

    3/83

    Contents PXL Conventional Fire Alarm Control Panel 

    i

     

     

     

     

     

     

     

     

     

     

     

     

     

     

     

     

     

     

    Technical Manuals Online! - http://www.tech-man.com

  • 8/18/2019 Siemens PXL Operation Installation Manual

    4/83

    PXL Conventional Fire Alarm Control Panel  Contents 

    ii

     

     

     

     

     

     

     

     

     

       

     

     

     

     

     

     

     

        

     

     

     

     

    Technical Manuals Online! - http://www.tech-man.com

  • 8/18/2019 Siemens PXL Operation Installation Manual

    5/83

    Contents PXL Conventional Fire Alarm Control Panel 

    iii

     

     

     

    Technical Manuals Online! - http://www.tech-man.com

  • 8/18/2019 Siemens PXL Operation Installation Manual

    6/83

    PXL Conventional Fire Alarm Control Panel  Contents 

    iv

    Technical Manuals Online! - http://www.tech-man.com

  • 8/18/2019 Siemens PXL Operation Installation Manual

    7/83

    Introduction PXL Conventional Fire Alarm Control Panel 

    1

     

     

       

    Technical Manuals Online! - http://www.tech-man.com

  • 8/18/2019 Siemens PXL Operation Installation Manual

    8/83

    PXL Conventional Fire Alarm Control Panel  Introduction 

    2

    C E R B E R U S P Y R O T R O N I C S

    P X L S Y S T E M N O R M A L

    < M E N U

    1 2 : 0 0 : 0 0

    POWER

    ALARM

    SUPERVISORY

    TROUBLE

    AUDIBLESSILENCED

    PARTIALDISABLE

    CERBERUS PYROTRONICS

    Figure 1Basic PXL System

    Exterior View 

    Interior View 

    Technical Manuals Online! - http://www.tech-man.com

  • 8/18/2019 Siemens PXL Operation Installation Manual

    9/83

    Introduction PXL Conventional Fire Alarm Control Panel 

    3

     

     

       

     

    Technical Manuals Online! - http://www.tech-man.com

  • 8/18/2019 Siemens PXL Operation Installation Manual

    10/83

    PXL Conventional Fire Alarm Control Panel  Introduction 

    4Technical Manuals Online! - http://www.tech-man.com

  • 8/18/2019 Siemens PXL Operation Installation Manual

    11/83

    Installation PXL Conventional Fire Alarm Control Panel 

    5

     

    Technical Manuals Online! - http://www.tech-man.com

  • 8/18/2019 Siemens PXL Operation Installation Manual

    12/83

    PXL Conventional Fire Alarm Control Panel  Installation 

    6

     

     

     

    Technical Manuals Online! - http://www.tech-man.com

  • 8/18/2019 Siemens PXL Operation Installation Manual

    13/83

    Installation PXL Conventional Fire Alarm Control Panel 

    7

     

     

    Figure 2The PSE-1 Enclosure

    Technical Manuals Online! - http://www.tech-man.com

  • 8/18/2019 Siemens PXL Operation Installation Manual

    14/83

    PXL Conventional Fire Alarm Control Panel  Installation 

    8

     

       

    Figure 3Removing the PMK-1 Bracket from the PSE-1

    Technical Manuals Online! - http://www.tech-man.com

  • 8/18/2019 Siemens PXL Operation Installation Manual

    15/83

    Installation PXL Conventional Fire Alarm Control Panel 

    9

     

     

           

     

     

    TABLE 1SETTING THE ADDRESS ON THE PPS-10M

    Module

    Number

    NAC

    Range

    Switch Setting

     1 2 3 4 5*

    1 1-4 X O O O O

    2 5-8 O X O O O

    X = SWITCH CLOSED OR ON , O = SWITCH OPEN OR OFF 

    * Refer to Appendix C, Figure 25, for Canadian Automatic Battery Disconnect setting.

    Technical Manuals Online! - http://www.tech-man.com

  • 8/18/2019 Siemens PXL Operation Installation Manual

    16/83

    PXL Conventional Fire Alarm Control Panel  Installation 

    10

     

     

    Figure 4PPS-10M Module Board

       

    Technical Manuals Online! - http://www.tech-man.com

  • 8/18/2019 Siemens PXL Operation Installation Manual

    17/83

    Installation PXL Conventional Fire Alarm Control Panel 

    11

    Figure 5Sliding the PPS-10M into the PMK-1 Bracket

    Figure 6Mounting the PPS-10M on the PMK-1 Bracket

    Technical Manuals Online! - http://www.tech-man.com

  • 8/18/2019 Siemens PXL Operation Installation Manual

    18/83

    PXL Conventional Fire Alarm Control Panel  Installation 

    12

     

         

       

    TABLE 2SETTING THE ADDRESS ON THE PRM-4

    Module

    Number

    Relay

    Range

    Switch Setting

    1 2 3 4 5

    1 1-4 X O O O O

    2 5-8 O X O O O

    3 9-12 X X O O O

    4 13-16 O O X O O

    5 17-20 X O X O O

    6 21-24 O X X O O

    7 25-28 X X X O O

    8 29-32 O O O X O

    X = SWITCH CLOSED OR ON , O = SWITCH OPEN OR OFF 

    Figure 7PRM-4 Module Board

    Technical Manuals Online! - http://www.tech-man.com

  • 8/18/2019 Siemens PXL Operation Installation Manual

    19/83

    Installation PXL Conventional Fire Alarm Control Panel 

    13

     

    Figure 8Mounting the PRM-4 on the PMK-1 Bracket

    Technical Manuals Online! - http://www.tech-man.com

  • 8/18/2019 Siemens PXL Operation Installation Manual

    20/83

    PXL Conventional Fire Alarm Control Panel  Installation 

    14

     

     

         

     

    X = SWITCH CLOSED OR ON , O = SWITCH OPEN OR OFF 

    Figure 9PNC-2Z Module Board

    TABLE 3

    SETTING THE ADDRESS ON THEPNC-2Z

    ModuleNumber

    NACRange

    Switch Setting1 2 3 4 5

    1 9-10 X O O O O

    2 11-12 O X O O O

    3 13-14 X X O O O

    4 15-16 O O X O O

    Technical Manuals Online! - http://www.tech-man.com

  • 8/18/2019 Siemens PXL Operation Installation Manual

    21/83

    Installation PXL Conventional Fire Alarm Control Panel 

    15

     

     

    Figure 10Mounting the PNC-2Z on the PMK-1 Bracket

    Technical Manuals Online! - http://www.tech-man.com

  • 8/18/2019 Siemens PXL Operation Installation Manual

    22/83

    PXL Conventional Fire Alarm Control Panel  Installation 

    16

     

     

     

     

     

     

     

    Technical Manuals Online! - http://www.tech-man.com

  • 8/18/2019 Siemens PXL Operation Installation Manual

    23/83

    Installation PXL Conventional Fire Alarm Control Panel 

    17

     

     

     

     

     

     

     

    Technical Manuals Online! - http://www.tech-man.com

  • 8/18/2019 Siemens PXL Operation Installation Manual

    24/83

    PXL Conventional Fire Alarm Control Panel  Installation 

    18

    Figure 11Mounting the PCM-1 on the PMK-1 Bracket

    Figure 12Labeling the Zones and Terminal Blocks on the PCM-1

    Technical Manuals Online! - http://www.tech-man.com

  • 8/18/2019 Siemens PXL Operation Installation Manual

    25/83

    Installation PXL Conventional Fire Alarm Control Panel 

    19

     

     

     

           

    TABLE 4

    SETTING THE ADDRESS ON THE PZE-4B

    PZE-4B

    Module

    IDC

    Range

    Switch Setting

    1 2 3 4 5

    1 13-16 X O O O O

    2 17-20 O X O O O

    3 21-24 X X O O O

    4 25-28 O O X O O

    5 29-32 X O X O O

    6 33-36 O X X O O

         

     

    Technical Manuals Online! - http://www.tech-man.com

  • 8/18/2019 Siemens PXL Operation Installation Manual

    26/83

    PXL Conventional Fire Alarm Control Panel  Installation 

    20

    Figure 13PZE-4B Module Board

    Figure 14Mounting the PZE-4B

    Figure 15Labeling the Zones and Terminal Blocks

    on the PZE-4B

    Technical Manuals Online! - http://www.tech-man.com

  • 8/18/2019 Siemens PXL Operation Installation Manual

    27/83

    Installation PXL Conventional Fire Alarm Control Panel 

    21

     

     

     

     

     

     

    Technical Manuals Online! - http://www.tech-man.com

  • 8/18/2019 Siemens PXL Operation Installation Manual

    28/83

    PXL Conventional Fire Alarm Control Panel  Installation 

    22

     

     

    Figure 16Installing the PMK-1 Bracket in the PSE-1

    Technical Manuals Online! - http://www.tech-man.com

  • 8/18/2019 Siemens PXL Operation Installation Manual

    29/83

    Installation PXL Conventional Fire Alarm Control Panel 

    23

     

     

    Figure 17Mounting the PTX-12

    Technical Manuals Online! - http://www.tech-man.com

  • 8/18/2019 Siemens PXL Operation Installation Manual

    30/83

    PXL Conventional Fire Alarm Control Panel  Installation 

    24

     

     

    Figure 18Installing the Grounding Strap with Two Lugs

    Technical Manuals Online! - http://www.tech-man.com

  • 8/18/2019 Siemens PXL Operation Installation Manual

    31/83

    Installation PXL Conventional Fire Alarm Control Panel 

    25

     

    Figure 19Installing the Grounding Strap with One Lug

    Technical Manuals Online! - http://www.tech-man.com

  • 8/18/2019 Siemens PXL Operation Installation Manual

    32/83

    PXL Conventional Fire Alarm Control Panel  Installation 

    26

     

     

     

     

     

     

       

       

     

     

       

    Technical Manuals Online! - http://www.tech-man.com

  • 8/18/2019 Siemens PXL Operation Installation Manual

    33/83

    Installation PXL Conventional Fire Alarm Control Panel 

    27

     

     

     

     

     

       

    Technical Manuals Online! - http://www.tech-man.com

  • 8/18/2019 Siemens PXL Operation Installation Manual

    34/83

    2   8  

    Figure 20PXL Power Limited Wiring

    i

    lM

    l

    O

    li

    !  

    h t  t  

    /  /  

    t  

  • 8/18/2019 Siemens PXL Operation Installation Manual

    35/83

    Installation PXL Conventional Fire Alarm Control Panel 

    29

    TABLE 6

    NON-POWER LIMITED WIRING

      Module Termination

    Enclosure

    Knockout

      PPS-10M

      PRM-4

      TB1 (3 positions)

      TB6 (All 9 positions)

      TB1 (6 positions)  TB2 (6 positions)

    7

    4

    44

     

     

     

     

     

     

    TABLE 7

    POWER LIMITED WIRING

      Module Termination

    Enclosure

    Knockout

      PCM-1

      PNC-2Z

      PPS-10M

      PZE-4B

     All Zone Wiring

     TB2 (All positions) TB3 (All positions)

     TB3 (2 positions) TB4 (All 16 positions)

     TB5 (1-4) All Zone Wiring

    1 and 2

    33

    66

    61 and 2

    Technical Manuals Online! - http://www.tech-man.com

  • 8/18/2019 Siemens PXL Operation Installation Manual

    36/83

    PXL Conventional Fire Alarm Control Panel  Installation 

    30

       

     

       

     

     

     

     

     

     

       

     

     

       

     

     

     

     

    Technical Manuals Online! - http://www.tech-man.com

  • 8/18/2019 Siemens PXL Operation Installation Manual

    37/83

    Installation PXL Conventional Fire Alarm Control Panel 

    31

     

       

       

     

     

    Technical Manuals Online! - http://www.tech-man.com

  • 8/18/2019 Siemens PXL Operation Installation Manual

    38/83

    PXL Conventional Fire Alarm Control Panel  Installation 

    32

     

     

     

     

     

     

       

     

     

    Technical Manuals Online! - http://www.tech-man.com

  • 8/18/2019 Siemens PXL Operation Installation Manual

    39/83

    Installation PXL Conventional Fire Alarm Control Panel 

    33

     

     

     

       

     

    Technical Manuals Online! - http://www.tech-man.com

  • 8/18/2019 Siemens PXL Operation Installation Manual

    40/83

    PXL Conventional Fire Alarm Control Panel  Installation 

    34

     

     

       

         

    Technical Manuals Online! - http://www.tech-man.com

  • 8/18/2019 Siemens PXL Operation Installation Manual

    41/83

    Operation PXL Conventional Fire Alarm Control Panel 

    35

    Figure 21The PCM-1 User Interface

         

     

     

     

    Technical Manuals Online! - http://www.tech-man.com

  • 8/18/2019 Siemens PXL Operation Installation Manual

    42/83

    PXL Conventional Fire Alarm Control Panel  Operation 

    36

     ALARM 1 OF 1:

    LOCATION 

     ACKNOWLEDGE ALARMS>

     

    Supervisory

     

    SUPV 1 OF 1:

    LOCATION 

     ACKNOWLEDGE SUPV’S>

    Trouble

     

     

    TROUBLE 1 OF 1:

    LOCATION 

     ACKNOWLEDGE TRBL’S>

    Normal  

     

     

    Technical Manuals Online! - http://www.tech-man.com

  • 8/18/2019 Siemens PXL Operation Installation Manual

    43/83

    Operation PXL Conventional Fire Alarm Control Panel 

    37

     

    TIME 

    COMPANY NAME 

    PXL SYSTEM NORMAL

  • 8/18/2019 Siemens PXL Operation Installation Manual

    44/83

    PXL Conventional Fire Alarm Control Panel  Operation 

    38

     

     

     

       

     

     

    Technical Manuals Online! - http://www.tech-man.com

  • 8/18/2019 Siemens PXL Operation Installation Manual

    45/83

    Programming PXL Conventional Fire Alarm Control Panel 

    39

    Technical Manuals Online! - http://www.tech-man.com

  • 8/18/2019 Siemens PXL Operation Installation Manual

    46/83

    PXL Conventional Fire Alarm Control Panel  Programming 

    40

    Figure 22PXL Automatic System Configuration Mode

     

    DO YOU WANT TO

    CONFIGURE THE

    SYSTEM NOW ?

       

     

    Technical Manuals Online! - http://www.tech-man.com

  • 8/18/2019 Siemens PXL Operation Installation Manual

    47/83

    Programming PXL Conventional Fire Alarm Control Panel 

    41

     

     

     

     

       

         

     

     

     

     

    Technical Manuals Online! - http://www.tech-man.com

  • 8/18/2019 Siemens PXL Operation Installation Manual

    48/83

    PXL Conventional Fire Alarm Control Panel  Programming 

    42

    Figure 23PXL Normal Operating Mode

    Technical Manuals Online! - http://www.tech-man.com

  • 8/18/2019 Siemens PXL Operation Installation Manual

    49/83

    Programming PXL Conventional Fire Alarm Control Panel 

    43

     

     

     

       

       

     

       

         

     

       

    Technical Manuals Online! - http://www.tech-man.com

  • 8/18/2019 Siemens PXL Operation Installation Manual

    50/83

    PXL Conventional Fire Alarm Control Panel  Programming 

    44

     

     

     

     

     

    Technical Manuals Online! - http://www.tech-man.com

  • 8/18/2019 Siemens PXL Operation Installation Manual

    51/83

    Programming PXL Conventional Fire Alarm Control Panel 

    45

     

       

     

    KEYASSIGNED

    CHARACTERS KEYASSIGNED

    CHARACTERS

    12

    34

    5

    6

    A, B, C, 1D, E, F, 2

    G, H, I, 3J, K, L, 4

    M, N, O, 5

    P, Q, R, 6

    78

    90

    *

    #

    S, T, U, 7V, W, X, 8

    Y, Z, _, 90

    Future Use

    Future Use

     

     

     

     

    Technical Manuals Online! - http://www.tech-man.com

  • 8/18/2019 Siemens PXL Operation Installation Manual

    52/83

    PXL Conventional Fire Alarm Control Panel  Programming 

    46

     

    rotceteDputratSyaleD

    )sdnoceS(

    H3 / 3-ID 5

    H3A / 3A-ID 5

    H3B / 3B-ID 5

    1911-ABP 1

    T3 / 3-EP 03

    T11 / 11-EP 05

     

     

     

     

     

     

         

    Technical Manuals Online! - http://www.tech-man.com

  • 8/18/2019 Siemens PXL Operation Installation Manual

    53/83

    Programming PXL Conventional Fire Alarm Control Panel 

    47

       

       

    CERBERUS PYROTRONICS

    < INSERT DELETE >

    < LEFT RIGHT >

    < MORE DONE >

     

       

     

       

     

       

         

     

     

    Technical Manuals Online! - http://www.tech-man.com

  • 8/18/2019 Siemens PXL Operation Installation Manual

    54/83

    PXL Conventional Fire Alarm Control Panel  Programming 

    48

     

     

     

     

     

       

       

     

     

    Technical Manuals Online! - http://www.tech-man.com

  • 8/18/2019 Siemens PXL Operation Installation Manual

    55/83

  • 8/18/2019 Siemens PXL Operation Installation Manual

    56/83

    PXL Conventional Fire Alarm Control Panel  Programming 

    50Technical Manuals Online! - http://www.tech-man.com

  • 8/18/2019 Siemens PXL Operation Installation Manual

    57/83

    CUSTOM MESSAGES

    NOTIFICATION APPLIANCE CIRCUITSON POWER SUPPLIES (PPS-10M)ON BELL MODULES (PNC-2Z)

    STEADY

    TEMPORAL

    MARCH TIME

     ADDRESSING

    NON - SILENCEABLE

    1615141312

    1110

    987

    6543

    21

      B

    B

    B

    B

    E

    E

    E

    E

    L

    L

    L

    L

    L

    L

    L

    L

     

    2

    3

    4

     

    INITIATING DEVICE CIRCUITSGENERAL ALARM

    SUPERVISORYVERIFIED ALARM

    RESET ZONE

    GENERIC ZONE

     

    CUSTOM MESSAGES

    Z

    Z

    Z

    Z

    Z

    Z

    Z

    Z

    Z

    Z

    Z

    Z

    O

    O

    O

    O

    O

    O

    O

    O

    O

    O

    O

    O

    N

    N

    N

    N

    N

    N

    N

    N

    N

    N

    N

    N

    E

    E

    E

    E

    E

    E

    E

    E

    E

    E

    E

    E

     

    2

    3

    4

    5

    6

    7

    8

    9

     

    2

    1516171819

    202122232425

    2627

    2829

    33

    30

    34

    31

    35

    32

    36

    14

    13

    1211

    10987

    65

    43

    21

    CUSTOM MESSAGES

    PROGRAMMABLE RELAYS

    12

    345

    6

    78

    910

    1112

    13141516

    17181920

    212223

    2425

    2627

    2829

    303132

     ADDRESSING

    1

    1

    1

    1

    1

    1

    1

    1

    1

    1

    1

    1

    1

    1

    2

    2

    2

    2

    2

    2

    2

    2

    2

    2

    2

    2

    2

    2

    3

    3

    3

    3

    3

    3

    3

    3

    3

    3

    3

    3

    3

    3

    4

    4

    4

    4

    4

    4

    4

    4

    4

    4

    4

    4

    4

    4

    5

    5

    5

    5

    5

    5

    5

    5

    5

    5

    5

    5

    5

    5

    1

    1

    1

    1

    1

    1

    2

    2

    2

    2

    2

    2

    3

    3

    3

    3

    3

    3

    4

    4

    4

    4

    4

    4

    5

    5

    5

    5

    5

    5

    NOTE : All installed IDCS defaultto GENERAL ALARM.

    NOTE :  All grayed text indicates default programming.

    NOTE : All installed NACS

    default to STEADY.MODULE

    MODULE ADDRESSING

    MODULE

    PCM

    PZENo. 1

    PZENo. 2

    PZENo. 3

    PZENo. 4

    PZENo. 5

    PZENo. 6

    PPSNo.1

    PPSNo. 2

    PNCNo. 1

    PNCNo. 2

    PNCNo. 3PNCNo. 4

    PRMNo. 1

    PRM

    No. 2

    PRMNo. 3

    PRMNo. 4

    PRMNo. 5

    PRMNo. 6

    PRMNo. 7

    PRMNo. 8

  • 8/18/2019 Siemens PXL Operation Installation Manual

    58/83

                    

       T  e  c   h  n   i  c  a   l   M  a  n  u  a   l  s   O  n   l   i  n  e   !  -   h   t   t  p  :   /   /  w  w  w .   t  e  c   h  -  m  a  n .  c  o  m

  • 8/18/2019 Siemens PXL Operation Installation Manual

    59/83

    Testing and Troubleshooting PXL Conventional Fire Alarm Control Panel 

    53

     

     

    Technical Manuals Online! - http://www.tech-man.com

  • 8/18/2019 Siemens PXL Operation Installation Manual

    60/83

    PXL Conventional Fire Alarm Control Panel  Testing and Troubleshooting 

    54

     

     

     

       

     

       

     

       

    Technical Manuals Online! - http://www.tech-man.com

  • 8/18/2019 Siemens PXL Operation Installation Manual

    61/83

    Testing and Troubleshooting PXL Conventional Fire Alarm Control Panel 

    55

     

    TABLE 14

    PXL FUSE REPLACEMENT

    FUSE DESCRIPTION VALUE

    F1F2F3

    F4

    XFORM SECBATTERYAUX POWER

    +24 VDC

    20.0A, 250V, Normal Blow20.0A, 250V, Normal Blow1.50A, 250V, Normal Blow

    1.00A, 250V, Normal Blow

    Technical Manuals Online! - http://www.tech-man.com

  • 8/18/2019 Siemens PXL Operation Installation Manual

    62/83

    PXL Conventional Fire Alarm Control Panel  Testing and Troubleshooting 

    56

    TROUBLE MESSAGES

    Trouble Message Text Condition Possible Cause

    System powers up normally butnothing shows on LCD display

    Contrast not adjusted properly

    AC POWER FAULT AC power off/low Loss of AC mains• AC brownout• Blown secondary fuse

    • Open transformer primary/secondary

    BELL XX NAC trouble NAC open

    NAC shorted

    BELL XX BYPASSED NAC bypassed NAC bypassed

    GROUND FAULT Ground fault • +24 shorted to earth ground

    • -V shorted to earth ground

    • F+, R+, R-, F- of an NAC shorted  to earth ground

    • IDC+ or IDC- of an IDC zone

      shorted to earth ground

    INCORRECT PZE PIC Firmware error for CANADA

    country selection

    PCM-1 and/or PZE-4B module has Rev. 1.0

    firmware. Upgrade to Rev. 3.x or higher

    LED MOD X MULTI/UNKN LED-3/4 not responding and ASCroutine will not run

    Two or more LED-3/4s installed with samedipswitch address

    LED-3/4 MOD X NO

    RESPONSE

    LED-3/4 not responding • Module removed from system*• Module failed

    • Module address changed

    LED-3/4 MOD X NOT SPEC’D LED-3/4 responding but not inconfiguration

    • LED module added but system not  reconfigured

    • LED module address changed

    MULTI RESP LED-3/4 MOD X Multiple Response at LED-3/4address

    • Two LED modules set to same address• LED set to address out of range

    MULTI RESP PCM MOD O Multiple Response at PCM

    address

    Module failed

    MULTI RESP PNC MOD X Multiple Response at PNC

    address

    • Two PNC modules set to same address

    • PNC set to address out of range

    MULTI RESP PPS MOD X Multiple Response at PPSaddress

    • Two PPS modules set to same address• PPS set to address out of range

    MULTI RESP PRM MOD X Multiple Response at PRMaddress

    • Two PRM modules set to same address• PRM set to address out of range

    MULTI RESP PZE MOD X Multiple Response at PZEaddress • Two PZE modules set to same address• PZE set to address out of range

    MULTI RESP RSA MOD X Multiple Response at RSAaddress

    • Two RSA modules set to same address• RSA set to address out of range

    * Modules purposely removed from the system may be removed from the configuration using  the "Delete Module Option" in the Program menu.

    X = Module number

    Technical Manuals Online! - http://www.tech-man.com

  • 8/18/2019 Siemens PXL Operation Installation Manual

    63/83

    Testing and Troubleshooting PXL Conventional Fire Alarm Control Panel 

    57

    TROUBLE MESSAGES (Cont.)

    Trouble Message Text Condition Possible Cause

    PCM MOD O WATCHDOG PCM module watchdog Module locked up; reset the panel

    PNC MOD X MULTI/UNKN PNC not responding and ASC

    routine will not run

    Two or more PNC modules installed with

    same dipswitch address

    PNC MOD X NO RESPONSE PNC not responding • Module removed from system*• Module failed

    • Module address changed

    PNC MOD X NOT SPEC’D PNC responding but not inconfiguration

    • PNC module added but system not  reconfigured

    • PNC module address changed

    PNC MOD X WATCHDOG PNC module watchdog Module locked up; reset the panel

    PNC MOD X COMM ERR PNC communication error • Data transmission failure

    • Module failed

    PPS MOD X COMM ERR PPS communication error • Data transmission failure• Module failed

    PPS MOD X NO RESPONSE PPS not responding • Module removed from system*

    • Module failed• Module address changed

    PPS MOD X NOT SPEC’D PPS responding but not in

    configuration

    • PPS module added but system not

      reconfigured• PPS module address changed

    PPS MOD X WATCHDOG PPS module watchdog Module locked up; reset the panel

    PPS1 AUX PWR FAULT Auxiliary power trouble on first

    PPS-10M in PXL System

    Aux power fuse blown

    PPS1 BATTERY FAULT Battery trouble on first PPS-10M inPXL System

    • Battery missing/not connected• Battery high

    • Battery low• Battery fuse blown

    • Battery connected backwards

    PPS2 AUX PWR FAULT Auxiliary power trouble on second

    PPS-10M in PXL System

    Aux power fuse blown

    PPS2 BATTERY FAULT Battery trouble on second

    PPS-10M in PXL System

    • Battery missing/not connected

    • Battery high• Battery low

    • Battery fuse blown

    • Battery connected backwards

    PRM MOD X COMM ERR PRM communication error • Data transmission failure• Module failed

    PRM MOD X MULTI/UNKN PRM not responding and ASCroutine will not run

    Two or more PRM modules installed withsame dipswitch address

    * Modules purposely removed from the system may be removed from the configuration using

      the "Delete Module Option" in the Program menu.

    X = Module number

    Technical Manuals Online! - http://www.tech-man.com

  • 8/18/2019 Siemens PXL Operation Installation Manual

    64/83

    PXL Conventional Fire Alarm Control Panel  Testing and Troubleshooting 

    58

    TROUBLE MESSAGES (Cont.)

    Trouble Message Text Condition Possible Cause

    PRM MOD X NO RESPONSE PRM not responding • Module removed from system*• Module failed

    • Module address changed

    PRM MOD X NOT SPEC’D PRM responding but not in

    configuration

    • PRM module added but system

      not reconfigured• PRM module address changed

    PRM MOD X WATCHDOG PRM module watchdog Module locked up; reset the panel

    PZE MOD X MULTI/UNKN PZE not responding and ASC

    routine will not run

    Two or more PZEs installed with same

    dipswitch address

    PZE MOD X NOT SPEC’D PZE responding but not inconfiguration

    • PZE module added but system  not reconfigured

    • PZE module address changed

    PZE MOD X WATCHDOG PZE module watchdog Module locked up; reset the panel

    PZE NEEDS NEWFIRMWARE

    Firmware error for CANADAcountry selection occurs during

    reset

    PCM-1 and/or PZE-4B module has Rev.1.0 firmware. Upgrade to Rev. 3.x or

    higher

    RELAY XX BYPASSED Relay bypassed Relay bypassed

    RSA MOD X MULTI/UNKN RSA not responding and ASCroutine will not run

    Two or more RSAs installed with samedipswitch address

    RSA MOD X NO RESPONSE RSA not responding • Module removed from system*

    • Module failed• Module address changed

    RSA MOD X NOT SPEC’D RSA responding but not inconfiguration

    • RSA module added but system  not reconfigured

    • RSA module address changed

    SYSTEM WATCHDOG System watchdog Panel locked up; reset the panel

    ZONE X COMM ERR PCM/PZE communication error • Data transmission failure• Module failed

    ZONE XX IDC zone trouble IDC zone open

    ZONE XX BYPASSED IDC zone bypassed IDC zone bypassed

    ZONE XX NO RESPONSE PCM/PZE not responding • Module removed from system*

    • Module failed• Module address changed

    *Modules purposely removed from the system may be removed from the configuration using

     the "Delete Module Option" in the Program menu.

    X = Module number

    Technical Manuals Online! - http://www.tech-man.com

  • 8/18/2019 Siemens PXL Operation Installation Manual

    65/83

    Appendix APXL Conventional Fire Alarm Control Panel 

    59

       

    Technical Manuals Online! - http://www.tech-man.com

  • 8/18/2019 Siemens PXL Operation Installation Manual

    66/83

  • 8/18/2019 Siemens PXL Operation Installation Manual

    67/83

    Appendix APXL Conventional Fire Alarm Control Panel 

    61

    CUSTOM MESSAGES

    NOTIFICATION APPLIANCE CIRCUITSON POWER SUPPLIES (PPS-10M)ON BELL MODULES (PNC-2Z)

    STEADY

    TEMPORAL

    MARCH TIME

     ADDRESSING

    NON - SILENCEABLE

    16

    15

    14

    1312

    11

    10

    9

    8

    7

    65

    4

    3

    2

    1  B

    B

    B

    B

    E

    E

    E

    E

    L

    L

    L

    L

    L

    L

    L

    L

     

    3

    4

     

    1

    1

    1

    1

    1

    1

    2

    2

    2

    2

    2

    2

    3

    3

    3

    3

    3

    3

    4

    4

    4

    4

    4

    4

    5

    5

    5

    5

    5

    5

    NOTE : All installed NACSdefault to STEADY.

    MODULE

    PPSNo.1

    PPSNo. 2

    PNCNo. 1

    PNCNo. 2

    PNCNo. 3PNCNo. 4

    Technical Manuals Online! - http://www.tech-man.com

  • 8/18/2019 Siemens PXL Operation Installation Manual

    68/83

    PXL Conventional Fire Alarm Control Panel  Appendix A

    62

    CUSTOM MESSAGES

    PROGRAMMABLE RELAYS

    1

    23

    4

    56

    78

    910

    1112

    1314

    1516

    1718

    1920

    2122

    23

    2425

    2627

    2829

    303132

     ADDRESSING

    1

    1

    1

    1

    1

    1

    1

    1

    2

    2

    2

    2

    2

    2

    2

    2

    3

    3

    3

    3

    3

    3

    3

    3

    4

    4

    4

    4

    4

    4

    4

    4

    5

    5

    5

    5

    5

    5

    5

    5

    MODULE

    PRMNo. 1

    PRMNo. 2

    PRMNo. 3

    PRMNo. 4

    PRMNo. 5

    PRMNo. 6

    PRMNo. 7

    PRMNo. 8

    Technical Manuals Online! - http://www.tech-man.com

  • 8/18/2019 Siemens PXL Operation Installation Manual

    69/83

    Appendix APXL Conventional Fire Alarm Control Panel 

    63Technical Manuals Online! - http://www.tech-man.com

  • 8/18/2019 Siemens PXL Operation Installation Manual

    70/83

    PXL Conventional Fire Alarm Control Panel  Appendix A

    64Technical Manuals Online! - http://www.tech-man.com

  • 8/18/2019 Siemens PXL Operation Installation Manual

    71/83

  • 8/18/2019 Siemens PXL Operation Installation Manual

    72/83

    PXL Conventional Fire Alarm Control Panel  Appendix B 

    66

    ELECTRICAL REQUIREMENTS FOR BATTERY CALCULATIONS

    Standby

    Current

    Alarm

    Current

    PCM-1 Module 0.147A 0.147A

    PPS-10M Module 0.088A 0.118A

    PZE-4B Module(s) Standby Current 0.039A  Alarm Current 0.039A

      Number of modules x current  ________ x 0.039A = ______A ______A

    PNC-2Z Module(s) Standby Current 0.012A  Alarm Current 0.012A

      Number of modules x current  ________ x 0.012A = ______A ______A

    PRM-4 Module(s) Standby Current 0.007A  Alarm Current 0.067A  Number of modules x current

      ________ x 0.007A (Standby) =  ________ x 0.067A (Alarm) = ______A ______A

    IDC Current:

      Alarm Current = .180/zone

      4 x .180 = 0.72A 0A 0.72A

    NAC/Aux Port Current: Current

  • 8/18/2019 Siemens PXL Operation Installation Manual

    73/83

    Appendix C PXL Conventional Fire Alarm Control Panel 

    67

     

     

     

     

     

    Technical Manuals Online! - http://www.tech-man.com

  • 8/18/2019 Siemens PXL Operation Installation Manual

    74/83

    PXL Conventional Fire Alarm Control Panel  Appendix C 

    68

    AUTOMATIC BATTERY DISCONNECT

    Canadian systems require automatic battery disconnect. In order to select this option, setSwitch 5 on S1 of the PPS-10M to the ON  position. Connect the battery to the PPS-10Mthrough the supervisory relay.

    Connect the NO contact to Battery+ terminal and Common to Bat+ terminal of the PPS-10M.• Connect Battery- terminal to Bat- of the PPS-10M.

    • If a supervisory relay is required, use a PRM-4 and configure the relay as a global supervisory.

    Figure 25PPS-10M Wiring for Canadian Automatic Battery Disconnect

    Technical Manuals Online! - http://www.tech-man.com

  • 8/18/2019 Siemens PXL Operation Installation Manual

    75/83

       

     

     

         

     

    Technical Manuals Online! - http://www.tech-man.com

  • 8/18/2019 Siemens PXL Operation Installation Manual

    76/83

       

     

    Technical Manuals Online! - http://www.tech-man.com

  • 8/18/2019 Siemens PXL Operation Installation Manual

    77/83

       

    Technical Manuals Online! - http://www.tech-man.com

  • 8/18/2019 Siemens PXL Operation Installation Manual

    78/83

       

       

        

     

          

       

     

     

       

     

     

     

     

     

     

     

     

     

    Technical Manuals Online! - http://www.tech-man.com

  • 8/18/2019 Siemens PXL Operation Installation Manual

    79/83

    Appendix E PXL Conventional Fire Alarm Control Panel 

    73

    Figure 28Cabling Connections in a PSE-2 Enclosure with Full Module Capacity

    (Batteries Removed to BB-55/-55R)

     

    PPS-10M

    PPS-10M

    PNC-2Z

    or 

    PRM-4

    JP2

    JP2

    PNC-2Zor 

    PRM-4

    PNC-2Z

    or 

    PRM-4

    PNC-2Z

    or 

    PRM-4

    JP2

    JP2 JP2

    JP1JP1

    JP1

    JP1   JP2

    JP2 JP2JP1

    PZE-4B

    PZE-4B

    JP7

    = Components areunderneath the board

    1   1

    1 111

    JP7JP6   JP6

    PZE-4B

    JP1JP1

    1

    1

    1

    1

    1

    1

    1 1 1

    1 1 1 1

    PNC-2Z

    or 

    PRM-4

    PNC-2Z

    or 

    PRM-4

    PNC-2Z

    or 

    PRM-4

    PNC-2Z

    or 

    PRM-4

    PNC-2Z

    or 

    PRM-4

    PNC-2Z

    or 

    PRM-4

    PNC-2Z

    or 

    PRM-4

    PNC-2Z

    or 

    PRM-4

    15" CABLE FROMPCK-1 KIT (P/N 500-695066)WITH RED CONDUCTORSCUT AND REMOVED

    MOUNTED ONFIRST PMK-1

    BRACKET

    MOUNTED ONSECOND PMK-1

    BRACKET

    MOUNTEDON PMK-2

    BRACKET

    PTX-12TRANSFORMER

    15" CABLE FROMPCK-1 KIT (P/N 500-695066)WITH ALL CONDUCTORS

    CABLE P/N555-194066(Provided withthe modules)

    -

    JP1

    JP1 JP1 JP1 JP1

    JP1 JP1 JP1JP2

    JP2 JP2 JP2 JP2

    JP2 JP2 JP2

    P ZE -4 B P ZE -4 B

    JP7   JP6JP7   JP6JP7   JP6JP7   JP6

    PCM-1

    1 1 1 1 1 1

    11111111

    1 1   1   1   1   1   1 1

    PTX-12TRANSFORMER

    Technical Manuals Online! - http://www.tech-man.com

  • 8/18/2019 Siemens PXL Operation Installation Manual

    80/83

    PXL Conventional Fire Alarm Control Panel  Appendix E 

    74

    Figure 29Cabling Connections in a PSE-2 Enclosure with Full Zone and Relay Capacity

    JP2 JP2JP1

    1

    PRM-4PRM-4

    JP1 JP1JP2 JP2

    1 1   1   1

    PPS-10M   PRM-4JP2

    PRM-4

    PRM-4

    PRM-4

    JP2

    JP2 JP2

    JP1JP1

    JP1

    JP1 JP2

    PZE-4B

    PZE-4B

    JP7

    = Components areunderneath the board

    1   1

    1 111

    JP7JP6   JP6

    PZE-4B

    JP1JP1

    1

    1

    1   1   1 1 1

    1 1   1   1

    MOUNTED ONFIRST PMK-1

    BRACKET

    MOUNTED ONSECOND PMK-1

    BRACKET

    15" CABLE FROMPCK-1 KIT (P/N 500-695066)WITH ALL CONDUCTORS

    P ZE -4 B P ZE -4 B

    JP7   JP6JP7   JP6JP7   JP6JP7   JP6

    PCM-1

    1 1 1 1 1 1

    PTX-12TRANSFORMER

    JP2 JP2JP1

    1

    PRM-4PRM-4

    JP1 JP1JP2 JP2

    1 1   1   1

    BP-6115AH BATTERY

    +  _ 

    Technical Manuals Online! - http://www.tech-man.com

  • 8/18/2019 Siemens PXL Operation Installation Manual

    81/83

     

    PXL FUSE REPLACEMENT

    FUSE DESCRIPTION VALUE

    F1F2F3F4

    XFORM SECBATTERYAUX POWER+24 VDC

    20.0A, 250V, Normal Blow20.0A, 250V, Normal Blow1.50A, 250V, Normal Blow1.00A, 250V, Normal Blow

     

     

     

    ELECTRICAL RATINGS

    Supervisory Alarm

    PCM-1 (IDC) 20.0-26.4 VDC8.5mA max

    20.0-26.4 VDC180mA max

    PZE-4B (IDC)Class B

    20.0-26.4 VDC8.5mA max

    20.0-26.4 VDC180mA max

    PNC-2Z (NAC) 24 VDC Nominal2.4mA max

    24 VDC Nominal2A max

    PPS-10M (NAC) 24 VDC Nominal2.4mA max

    24 VDC Nominal2A max

    PPS-10M (Relays) 30 VDC / 120 VAC5A max resistive

    30 VDC / 120 VAC5A max resistive

    PPS-10M (Serial Bus) 400mA, 24V 400mA, 24V

    PRM-4 30 VDC / 120 VAC5A max resistive

    30 VDC / 120 VAC5A max resistive

    LED-3/-4 24 VDC10mA max

    24 VDC10mA + 2mAper LED max

    RSA-16 24 VDC20mA max

    24 VDC20mA + 13mAper LED max

       

     

    COMPATIBLE DETECTORS*

    Detector

    Quantityper

    Loop Base

    InstallationInstructions

    Part No.

    DI-3/3H 30 DB-3S 315-081943-16

    DI-A3/A3H 30 DB-3S 315-081943-16

    DI-B3/B3H 30 AD-3I 315-093234-5

    DT-11 30 DB-11DB-3S with DB-ADPT

     315-095429-2 315-095429-2

    PBA-1191*** 1 PBB-1191 315-095424-3

    PE-3 30 DB-3SAD-3ILP

     315-081943-16 315-093234-5

    PE-11/11T 30 DB-11DB-3S with DB-ADPT

    AD-11P/11PR

     315-094198-7 315-094198-7 315-095659-6

     

     

     

       

     

     

    ical Manuals Online! - http://www.tech-man.com

  • 8/18/2019 Siemens PXL Operation Installation Manual

    82/83

    WARNING: This equipment generates, uses, and can radiate radiofrequency energy and if not installed and used in accordance with theinstructions manual, may cause interference to radio communica-tions. It has been tested and found to comply with the limits for a ClassA computing device pursuant to Part 15 of FCC Rules, which are

    designed to provide reasonable protection against such interferencewhen operated in a commercial environment. Operation of thisequipment in a residential area is likely to cause interference in which

    case the user at his own expense will be required to take whatevermeasures may be required to correct the interference.