Sensors ATEX Sensors - Explosion Proof Enclosures Controllers Warning Devices.

16
Sensors ATEX Sensors - Explosion Proof Enclosures Controllers Warning Devices

Transcript of Sensors ATEX Sensors - Explosion Proof Enclosures Controllers Warning Devices.

Page 1: Sensors ATEX Sensors - Explosion Proof Enclosures Controllers Warning Devices.

Sensors

ATEX Sensors - Explosion Proof

Enclosures

Controllers

Warning Devices

Page 2: Sensors ATEX Sensors - Explosion Proof Enclosures Controllers Warning Devices.

Gas Sensors/Transmitters:•Plug-in sensor and PCB (easy service)•Short circuit and reverse polarity protection•For CO, NO2 monitoring in car-parks•For Ex-Hydrocarbon (flammables gases) in 0-100% LELOther gases: Cl2, H2S, NH3, SO2 and others•24 VAC/DC•0-20mA output, 4-20mA, 0-10VDC 2-10 VDC•RS485, MODBUS, LON, BACnet (with Gateway)

Housing Options:Stainless Steel (vandal proof)IP-65 with splash guardsMetalIP 65 (standard – as pictured)ATEX Hazardous Area Certified (Ex-Proof)

Page 3: Sensors ATEX Sensors - Explosion Proof Enclosures Controllers Warning Devices.

CO SensorsThree different models stocked by Siemens.

• AT-02-1110 (0-300PPM, 4-20mA)• ADT-03-1110 (0-300PPM, multi-output)• ADT-03-1110-LED (0-150PPM, multi-output, 3x LEDs, metal enclosure)

NO2 Sensor• ADT-53-1130(0-25PPM, multi-output)

NO Sensor• ADT-53-1129 (0-25PPM, multi-output)

Page 4: Sensors ATEX Sensors - Explosion Proof Enclosures Controllers Warning Devices.

Freon Sensors• AT-42-20xx (0-2000PPM, 4-20mA)• AT-42-20xx (0-300PPM, 4-20mA) – special order• ADT-D3-20xx (0-2000PPM, multi-output, Infra-red cell)

NH3 Sensor• ADT-53-1120 (0-300/1000PPM, multi-output, -10oC - +40oC)• ADT-63-1125 (0-300/1000PPM, multi-output, -40oC - +10oC)

CO2 Sensor• ADT-D3-1164 (0-50,000PPM, multi-output, Infra-red cell)

Page 5: Sensors ATEX Sensors - Explosion Proof Enclosures Controllers Warning Devices.

O2 Sensor• ADT-93-1195 (0-25%VOL, multi-output)

Ex Sensor• ADT-23-34xx (0-100%LEL, multi-output)• Calibrated for all Explosive gases, Methane, Propane,Ethylene, Benzene etc)

ATEX Sensors (Explosion proof)• Available for Zone 1 & Zone 2• For all gases (O2, Methane, Ethylene, CO, CO2, H2S, CL2, NO, NO2 etc)•With or without LC Display

•For monitoring in ambient air, ground water contamination / soil contamination to meet EPA guidelines•For Oil/Gas, Petro-chemicals, Dangerous goods, Laboratories, Mining, Tunnels

Page 6: Sensors ATEX Sensors - Explosion Proof Enclosures Controllers Warning Devices.

Hazardous Area Installations:

America: Div 1, Zone 0 (Cont. hazard), Zone 1 (Intermittent Hazard), Div 2 or Zone 2 (Hazard under abnormal conditions)

CENELEC (Europe): Zone 0 (continuous), Zone 1 (Intermittent), Zone 2 (abnormal conditions)

Australia: Follows both (depends on the consultants – but mainly European)

Page 7: Sensors ATEX Sensors - Explosion Proof Enclosures Controllers Warning Devices.

Plastic IP65 (standard)

For low cost, buildings

Stainless Steel

(Vandal proof)

For corrosive places

IP 65 with splash guard

For out-doors, water splash

Duct Mount For Ducts

Heater For freezing temp.

Page 8: Sensors ATEX Sensors - Explosion Proof Enclosures Controllers Warning Devices.

• IP 65 ABS housing, Averaging, Mean-Value calculations• Option of 1 hour emergency back up with batteries, integral buzzer, integral A-V Alarm•Fully Modular to build from 4 upto 24 Channel System

– Clear hinged door with option of lock– password protected– LON Gateway– MODBUS Gateway– BACnet Gateway

Page 9: Sensors ATEX Sensors - Explosion Proof Enclosures Controllers Warning Devices.

PolyGard® Gas Controller MGC 03MGC03-02-02 -2 Measuring Point - 2 Alarm

relay

Page 10: Sensors ATEX Sensors - Explosion Proof Enclosures Controllers Warning Devices.

Stand Alone Gas Alarms (Car parks, LPG, Natural Gas, O2, CO2 and many other gases)

•Integral Gas Sensors (Remote Gas Sensors)Gases: CO, NH3, Explosive, NO2, CO2 (for DCV)

•Integral display

•4-20 mA Ouput

•Integral Relays

•Stand alone operation for fan logic control or alarms

•For small car parks, garages, labs, uni, schools (Single channel controller)

Page 11: Sensors ATEX Sensors - Explosion Proof Enclosures Controllers Warning Devices.

PolyGard® Gas Controller MGC 04MGC04-04-04 -4 Measuring Point - 4 Alarm

relay

Page 12: Sensors ATEX Sensors - Explosion Proof Enclosures Controllers Warning Devices.

MGC_04_08_088 Measuring Point -- 8 Alarm relay

Page 13: Sensors ATEX Sensors - Explosion Proof Enclosures Controllers Warning Devices.

MGC_04_16_16 -16 Measuring Point - 16 Alarm relay

Page 14: Sensors ATEX Sensors - Explosion Proof Enclosures Controllers Warning Devices.

MGC_04_24_24 -24 Measuring Point -- 16 Alarm relay

Page 15: Sensors ATEX Sensors - Explosion Proof Enclosures Controllers Warning Devices.

MLD-95A 24VDC Combo siren/strobe

Lo Alarm: Flasher (Red)

Hi-Alarm: Siren (105dB)

Text Legend Type, flashing, also audio

240 VAC, 24 VDC

E2S combination A-V Alarm, 24 VDC

Lo-Alarm: Flasher (Red)

Hi-Alarm: Audio (95 dB)

Page 16: Sensors ATEX Sensors - Explosion Proof Enclosures Controllers Warning Devices.

Australian Exposure Standards for Atmospheric Contaminants in the Occupational Environment NOHSC: 3008 (1995) has set some TWA standards which are followed by various OH&S Statutory Bodies as well as referred by Standards (AS 1668.2 etc) – some typical TWA (for others refer to USA-ACGIH, OSHA, NIOSH)

NH3: TWA – 25 ppm, STEL – 35 ppmCO2: TWA – 5000 ppm, STEL – 30000 ppmCO: TWA – 30 ppm, STEL- 200 ppmH2S: TWA – 10 ppm, STEL- 15 ppmNO2: TWA – 3 ppm, STEL – 5 ppmNO (Nitric Oxide): TWA - 25 ppmN2O3 (Nitrous Oxide): TWA - 25 PPM (hospitals)Cl2 (Chlorine): TWA – 1 ppmO2 (Oxygen): 19 % Vol (minimum), Air has 20.9 % O2O3 (Ozone): TWA – 0.1 ppm