enclosures to ATEX and enclosures for special custom ... · Worldwide availability without delays....
Transcript of enclosures to ATEX and enclosures for special custom ... · Worldwide availability without delays....
R
enclosures to ATEX and enclosures
for special custom design (EEx p and NEMA cabinets)
S t a i n l e s s s t e e l a n d
p l a s t i c e n c l o s u r e s f o r u s e
i n p o t e n t i a l l y e x p l o s i v e
e n v i r o n m e n t s
Rittal – system partnersPerfect comprehensive solutions
2 Rittal Ex enclosures to ATEX
The demands placed on Ex enclosures are particularly
high. For this reason, Rittal accepts no compromises, and
adapts tried and tested enclosure concepts to meet the
specific requirements of potentially explosive environments.
The result is a series of Ex enclosures providing ideal
conditions for applications in the chemicals and petro-
chemicals industries, in the offshore sector and in the foods
industry.
The added value of our integral solutionsEnclosures for every application in numerous sizes and designs.
Fast, cost-effective system integration through comprehensive accessories.
High product quality ensuring reliability.
Worldwide availability without delays.
International approvals and certification.
Faster + better + cost-effective: That is the formula for a modular configuration concept and individual Rittal solutions. Ex enclosures to ATEX
satisfy approval criteria to the fullZone 1 and 2 to EN 50 014 and EN 50 019.
Zone 21 and 22 to EN 50 281.
Partial certification to ATEX 100a (EC Directive 94/9/EC).
Ambient operating temperature: Maximum: +80 °C Minimum: –20 °C (–40 °C on request)
Protection category: With IP 56 or IP 66 to EN 60 529, the required level of protection is reliably exceeded.
Constantly high quality is guaranteed by production and routine testing procedures with ISO 9001 certification.
Perfect response to special demandsWorldwide implementation of explosion protection is based essentially on the European standards.
Special approvals for the American market – to Class I, Zone I acc. to NEC – upon request.
Practically all Rittal enclosure systems can also be prepared for pressurisation to EN 50 016 upon request.
Further dimensions and versions upon request, also to meet individual certification requirements.(NEMA 4, NEMA 4x, IP65)
Ex enclosures
Rittal Ex enclosures to ATEX 3
Plastic Ex enclosure with hinged door Type Examination Certificate No. PTB 03 ATEX 1011U (for empty enclosures KEL)PTB 03 ATEX 1012 (for terminal enclosures KE)
For wall mounting: 4 press-fit screw bushes M8.
Double seal at top and bottom edges of the door through additional integrated rain protection strip.
Enclosure can be rotated to switch door hinging to the other side.
Door opening angle 180°.
Double-bit insert in the lock, exchangeable for other lock inserts.
Manufactured in fibre-glass-reinforced, unsaturated polyester with a high graphite content: Surface resistance: < 109 Ohm.
Stainless steel Ex enclosure with hinged door Type Examination Certificate No. PTB 02 ATEX 1082U (for empty enclosures KEL)PTB 02 ATEX 1083(for terminal enclosures KE)
For wall mounting: 4 blind rivet nuts M8.
To discharge possible static charges: Blind rivet nut M8 on the outside.
Door is simple to remove when open.
Double-bit insert in the cam lock, exchangeable for other lock inserts.
Mounting plate both sides with pitch pattern for easier configuration.
PE conductor connection in enclosure and door.
Stainless steel Ex enclosure with screw fastened lid Type Examination Certificate No. PTB 03 ATEX 1013U (for empty enclosures KEL)PTB 03 ATEX 1014 (for terminal enclosures KE)
For wall mounting: 4 blind rivet nuts M8.
To discharge possible static charges: Blind rivet nut M8 on the outside.
For simple attachment of support rails or mounting plates in the enclosure: Profile strips with mounting holes on both sides.
PE conductor connection in enclosure and cover.
Captive-mounted cover attachment.
Three enclosure types to meet differing demandsThe enclosures in this brochure are approved for use in potentially explosive atmospheres attributable to gases and/or dusts.
Our own accredited laboratories and the latest manufacturing technologies, paired with comprehensive quality management, guarantee constantly high standards worldwide.
Stainless steel Ex enclosures
4 Rittal Ex enclosures to ATEX
With screw fastened lid
Material:Stainless steel 1.4301/1.4404 (304/316L)
Surface finish:Brushed
Protection category:IP 66 to EN 60 529/10.91
Certificates: PTB 03 ATEX 1013U (for empty enclosures KEL)PTB 03 ATEX 1014 (for terminal enclosures KE)
Supply includes:Enclosure, lid with all-round foamed-in PU seal.
With hinged door
Material:Stainless steel 1.4301/1.4404(304/316L)Mounting plate: Sheet steel
Surface finish:Brushed Mounting plate: Zinc-plated
Protection category:IP 66 to EN 60 529/10.91
Certificates: PTB 02 ATEX 1082U (for empty enclosures KEL)PTB 02 ATEX 1083 (for terminal enclosures KE)
Supply includes:Enclosure, door with all-round foamed-in PU seal, mounting plate.
Wall brackets for enclosure attachment of the series KE/KEL 9301.600 – 9306.600.
Material:Stainless steel 1.4301/1.4404*
Wall brackets for enclosure attachment of the series KE/KEL 9401.600 – 9409.600.
Material:Stainless steel 1.4301/1.4404*
Packs of Model No. KL
4 1594.000
4 on request*
Packs of Model No. SZ
4 2433.000
4 2433.500*
EMC concept on request.
5Rittal Ex enclosures to ATEX
B4
B6
B3
M8
x 20
50B5
H1
B1
20
44
20
79.515.5H
4
H3
H2
15
120
44
H3
H2
H4
15
80
39.5
15.5
2020
2.5
B3
B5
2.5
100
B6
B1
50
32
100
37.
5
H1
20
2020
H4
T1
H2
2.5
H3
2.5
30
50
Ø 9
138
225
6.5
275
260
162
122
122
9
12.5
F1
18.5
23.
5
F2
8.2
6.6
G1
42.
5
F2
14.
5
1
KEL 9301.000 – KEL 9306.000: with screw fastened lid
KEL 9301.000 – KEL 9306.000: with screw fastened lid
KEL 9401.600 – KEL 9409.600: with hinged door
B1 Width mm
H1 Height mm
T1 Depth mm
Packs of B3 B4 B5 B6 H2 H3 H4
Dimensions of mounting plate Weight
(kg)Model No.
KEL
Accessories: Mounting plates KLG1 F1 F2
150 150 80 1 132 109 125 148 148 132 100 135 125 – 1.3 9301.000 1560.700
200 200 80 1 182 159 175 198 198 182 150 185 175 50 1.8 9303.000 1562.700
300 150 80 1 282 259 275 298 148 132 100 285 125 – 1.8 9302.000 1561.700
300 200 80 1 282 259 275 298 198 182 150 285 175 50 2.4 9304.000 1563.700
300 300 120 1 282 259 275 298 298 282 250 285 275 50 3.9 9306.000 1567.700
400 200 120 1 382 359 375 398 198 182 150 385 175 50 3.6 9305.000 1564.700
To order Ex enclosures in 1.4404 (AISI 316L), change the last three digits of the Model No. to .500.
B1 Width mm
H1 Height mm
T1 Depth mm
Packs of B3 B5 B6 H2 H3 H4
Dimensions of mounting plate No. of fasteners
Weight (kg)
Model No. KELG1 G2 F1 F2
200 300 155 1 167 122 – 295 274 260 – – – – 1 3.8 9401.600
300 380 210 1 260 250 175 375 340 295 275 250 334 295 1 7.7 9409.600
380 300 155 1 340 295 255 295 260 250 275 250 334 295 1 7.4 9402.600
380 380 210 1 340 295 255 375 340 330 355 330 334 295 1 9.7 9403.600
380 600 210 1 340 295 255 595 560 545 570 545 334 295 2 13.3 9404.600
600 600 210 1 560 510 475 595 560 545 570 545 549 510 2 15.6 9405.600
600 760 210 1 560 510 475 755 720 705 730 705 549 510 2 22.3 9406.600
760 760 300 1 720 665 635 755 720 705 730 705 704 665 2 30.5 9407.600
800 1000 300 1 760 700 675 995 960 930 955 930 739 700 2 36.3 9408.600
To order Ex enclosures in 1.4404 (AISI 316L), change the last three digits of the Model No. to .500.
1
2
G2
10
90
F1
F2
G1
Mounting plate
= only attaching in the centre for 125 mm wide plates
1
KEL 9401.600 – KEL 9409.600: with hinged door Mounting plate KEL 9401.600
Mounting plate KEL 9402.600 – KEL 9408.600
= Only for KEL 9408.6001 = 20 for KEL 9409.6002
Installation position of the mounting plate is rotated through 90° for KEL 9409.600.
Ex enclosuresStainless steel enclosures with screw fastened lid
6 Rittal Ex enclosures to ATEX
KEL 9301.000 empty enclosuresEx II 2 G EEx e II
KE 9301.000 terminal enclosuresEx II 2 G EEx e ia II C T6 or T5
Wall mountingSee page 4.
Max. number of screwed cable glands
Equipment of terminal enclosure KE 9301.000Max. number of cables depending on the cross-section and the permissible permanent current.
KEL 9302.000 empty enclosuresEx II 2 G EEx e II
KE 9302.000 terminal enclosuresEx II 2 G EEx e ia II C T6 or T5
Wall mountingSee page 4.
Max. number of screwed cable glands
Equipment of terminal enclosure KE 9302.000Max. number of cables depending on the cross-section and the permissible permanent current.
KEL 9303.000 empty enclosuresEx II 2 G EEx e II
KE 9303.000 terminal enclosuresEx II 2 G EEx e ia II C T6 or T5
Wall mountingSee page 4.
Max. number of screwed cable glands
Equipment of terminal enclosure KE 9303.000Max. number of cables depending on the cross-section and the permissible permanent current.
Size A B C D
M12 x 1.5 4 2 4 4
M16 x 1.5 3 1 3 3
M20 x 1.5 3 1 3 3
M25 x 1.5 – – 2 2
M32 x 1.5 – – 2 2
M40 x 1.5 – – – –
M50 x 1.5 – – – –
M63 x 1.5 – – – –
Current in A
Cross-section in mm2
1.5 2.5 4 6 10
10 43
16 15 29 112
20 6 17 32
25 8 18 35
35 5 14 34
50 2 11
63 3
80
100
125
Max. number of terminals 18 18 18 13 11
Size A B C D
M12 x 1.5 4 2 11 11
M16 x 1.5 3 1 10 10
M20 x 1.5 3 1 8 8
M25 x 1.5 – – 7 7
M32 x 1.5 – – 5 5
M40 x 1.5 – – – –
M50 x 1.5 – – – –
M63 x 1.5 – – – –
Current in A
Cross-section in mm2
1.5 2.5 4 6 10
10 48
16 16 32 124
20 6 18 36
25 8 20 39
35 6 15 38
50 2 12
63 4
80
100
125
Max. number of terminals 47 47 44 33 27
Size A B C D
M12 x 1.5 6 4 6 6
M16 x 1.5 5 3 5 5
M20 x 1.5 4 2 4 4
M25 x 1.5 – – 4 4
M32 x 1.5 – – 3 3
M40 x 1.5 – – – –
M50 x 1.5 – – – –
M63 x 1.5 – – – –
Current in A
Cross-section in mm2
1.5 2.5 4 6 10
10 50
16 17 33 131
20 7 19 38
25 9 21 41
35 6 16 40
50 2 13
63 4
80
100
125
Max. number of terminals 57 57 28 21 17
Stainless steel enclosures with screw fastened lid
Ex enclosures
7Rittal Ex enclosures to ATEX
KEL 9304.000 empty enclosuresEx II 2 G EEx e II
KE 9304.000 terminal enclosuresEx II 2 G EEx e ia II C T6 or T5
Wall mountingSee page 4.
Max. number of screwed cable glands
Equipment of terminal enclosure KE 9304.000Max. number of cables depending on the cross-section and the permissible permanent current.
KEL 9305.000 empty enclosuresEx II 2 G EEx e II
KE 9305.000 terminal enclosuresEx II 2 G EEx e ia II C T6 or T5
Wall mountingSee page 4.
Max. number of screwed cable glands
Equipment of terminal enclosure KE 9305.000Max. number of cables depending on the cross-section and the permissible permanent current.
KEL 9306.000 empty enclosuresEx II 2 G EEx e II
KE 9306.000 terminal enclosuresEx II 2 G EEx e ia II C T6 or T5
Wall mountingSee page 4.
Max. number of screwed cable glands
Equipment of terminal enclosure KE 9306.000Max. number of cables depending on the cross-section and the permissible permanent current.
Size A B C D
M12 x 1.5 6 4 11 11
M16 x 1.5 5 3 10 10
M20 x 1.5 4 2 8 8
M25 x 1.5 – – 7 7
M32 x 1.5 – – 5 5
M40 x 1.5 – – – –
M50 x 1.5 – – – –
M63 x 1.5 – – – –
Current in A
Cross-section in mm2
1.5 2.5 4 6 10
10 55
16 19 36 143
20 7 21 41
25 10 23 45
35 6 17 44
50 2 14
63 4
80
100
125
Max. number of terminals 89 89 48 36 29
Size A B C D
M12 x 1.5 18 16 48 48
M16 x 1.5 9 7 41 41
M20 x 1.5 8 6 22 22
M25 x 1.5 7 5 19 19
M32 x 1.5 3 1 13 13
M40 x 1.5 2 – 6 6
M50 x 1.5 2 – 5 5
M63 x 1.5 – – – –
Current in A
Cross-section in mm2
1.5 2.5 4 6 10 16 25 35
10 68
16 23 45 175
20 9 26 51
25 12 29 55
35 8 21 54
50 3 17 44
63 6 20 73
80 8 23 82
100 10 21
125 8
Max. number of terminals 118 118 59 44 35 30 24 24
Size A B C D
M12 x 1.5 33 31 33 33
M16 x 1.5 19 17 29 29
M20 x 1.5 16 14 16 16
M25 x 1.5 13 11 13 13
M32 x 1.5 4 2 9 9
M40 x 1.5 3 1 3 3
M50 x 1.5 2 1 2 2
M63 x 1.5 – – – –
Current in A
Cross-section in mm2
1.5 2.5 4 6 10 16 25 35
10 76
16 26 50 197
20 10 29 57
25 14 32 62
35 9 24 60
50 3 19 50
63 6 23 82
80 9 26 92
100 11 24
125 9
Max. number of terminals 129 129 43 32 26 21 17 17
Ex enclosuresStainless steel enclosures with hinged door
8 Rittal Ex enclosures to ATEX
KEL 9401.600 empty enclosuresEx II 2 G EEx e II
KE 9401.600 terminal enclosuresEx II 2 G EEx e ia II C T6 or T5
Wall mountingSee page 4.
Max. number of screwed cable glands
Equipment of terminal enclosure KE 9401.600Max. number of cables depending on the cross-section and the permissible permanent current.
KEL 9402.600 empty enclosuresEx II 2 G EEx e II
KE 9402.600 terminal enclosuresEx II 2 G EEx e ia II C T6 or T5
Wall mountingSee page 4.
Max. number of screwed cable glands
Equipment of terminal enclosure KE 9402.600Max. number of cables depending on the cross-section and the permissible permanent current.
KEL 9409.600 empty enclosuresEx II 2 G EEx e II
KE 9409.600 terminal enclosuresEx II 2 G EEx e ia II C T6 or T5
Wall mountingSee page 4.
Max. number of screwed cable glands
Equipment of terminal enclosure KE 9409.600Max. number of cables depending on the cross-section and the permissible permanent current.
Size A B C D
M12 x 1.5 60 54 40 40
M16 x 1.5 44 40 28 28
M20 x 1.5 36 32 24 24
M25 x 1.5 23 20 14 14
M32 x 1.5 11 10 7 7
M40 x 1.5 10 8 6 6
M50 x 1.5 8 7 6 6
M63 x 1.5 – – – –
Current in A
Cross-section in mm2
1.5 2.5 4 6 10 16
10 77
16 26 51 198
20 11 30 57
25 14 32 62
35 9 24 61
50 3 20 50
63 6 23
80 9
100
125
Max. number of terminals 40 40 40 30 24 20
Size A B C D
M12 x 1.5 60 54 80 80
M16 x 1.5 44 41 60 60
M20 x 1.5 36 32 48 48
M25 x 1.5 24 21 30 30
M32 x 1.5 12 10 16 16
M40 x 1.5 10 8 12 12
M50 x 1.5 8 6 9 9
M63 x 1.5 3 2 4 4
Current in A
Cross-section in mm2
1.5 2.5 4 6 10 16 25 35
10 91
16 31 60 236
20 13 35 68
25 16 38 74
35 11 29 72
50 4 23 60
63 8 28 99
80 10 31 111
100 13 29
125 11
Max. number of terminals 77 77 77 58 46 39 31 31
Size A B C D
M12 x 1.5 128 124 96 96
M16 x 1.5 102 99 77 77
M20 x 1.5 72 68 54 54
M25 x 1.5 50 48 40 40
M32 x 1.5 32 30 24 24
M40 x 1.5 18 17 15 15
M50 x 1.5 10 9 8 8
M63 x 1.5 8 7 6 6
Current in A
Cross-section in mm2
1.5 2.5 4 6 10 16 25 35
10 107
16 36 71 276
20 15 41 80
25 19 45 87
35 13 34 85
50 5 27 70
63 9 32 116
80 12 36 130
100 15 34
125 13
Max. number of terminals 77 77 77 58 46 39 31 31
Stainless steel enclosures with hinged door
Ex enclosures
9Rittal Ex enclosures to ATEX
KEL 9403.600 empty enclosuresEx II 2 G EEx e II
KE 9403.600 terminal enclosuresEx II 2 G EEx e ia II C T6 or T5
Wall mountingSee page 4.
Max. number of screwed cable glands
Equipment of terminal enclosure KE 9403.600Max. number of cables depending on the cross-section and the permissible permanent current.
KEL 9404.600 empty enclosuresEx II 2 G EEx e II
KE 9404.600 terminal enclosuresEx II 2 G EEx e ia II C T6 or T5
Wall mountingSee page 4.
Max. number of screwed cable glands
Equipment of terminal enclosure KE 9404.600Max. number of cables depending on the cross-section and the permissible permanent current.
KEL 9405.600 empty enclosuresEx II 2 G EEx e II
KE 9405.600 terminal enclosuresEx II 2 G EEx e ia II C T6 or T5
Wall mountingSee page 4.
Max. number of screwed cable glands
Equipment of terminal enclosure KE 9405.600Max. number of cables depending on the cross-section and the permissible permanent current.
Size A B C D
M12 x 1.5 128 122 128 128
M16 x 1.5 105 101 105 105
M20 x 1.5 72 67 72 72
M25 x 1.5 48 46 48 48
M32 x 1.5 30 28 30 30
M40 x 1.5 18 15 18 18
M50 x 1.5 10 8 10 10
M63 x 1.5 8 7 8 8
Current in A
Cross-section in mm2
1.5 2.5 4 6 10 16 25 35
10 114
16 39 76 294
20 16 44 85
25 21 48 93
35 14 36 90
50 5 29 75
63 10 35 123
80 13 38 138
100 16 36
125 16
Max. number of terminals 102 102 102 77 62 52 41 41
Size A B C D
M12 x 1.5 216 208 128 128
M16 x 1.5 161 156 98 98
M20 x 1.5 114 108 72 72
M25 x 1.5 80 77 50 50
M32 x 1.5 48 46 32 32
M40 x 1.5 30 28 18 18
M50 x 1.5 16 14 10 10
M63 x 1.5 14 12 8 8
Current in A
Cross-section in mm2
1.5 2.5 4 6 10 16 25 35
10 123
16 42 82 318
20 17 48 92
25 22 52 100
35 15 39 98
50 5 32 81
63 10 37 133
80 14 42 149
100 18 39
125 16
Max. number of terminals 172 172 172 130 104 87 70 70
Size A B C D
M12 x 1.5 216 208 216 216
M16 x 1.5 161 155 161 161
M20 x 1.5 114 108 114 114
M25 x 1.5 80 77 80 80
M32 x 1.5 48 46 48 48
M40 x 1.5 30 28 30 30
M50 x 1.5 16 14 16 16
M63 x 1.5 14 12 14 14
Current in A
Cross-section in mm2
1.5 2.5 4 6 10 16 25 35
10 145
16 50 97 375
20 20 56 109
25 27 62 119
35 18 46 115
50 6 37 95
63 12 44 157
80 17 49 176
100 21 46
125 2 19
Max. number of terminals 258 258 258 195 157 131 105 105
Ex enclosuresStainless steel enclosures with hinged door
10 Rittal Ex enclosures to ATEX
KEL 9406.600 empty enclosuresEx II 2 G EEx e II
KE 9406.600 terminal enclosuresEx II 2 G EEx e ia II C T6 or T5
Wall mountingSee page 4.
Max. number of screwed cable glands
Equipment of terminal enclosure KE 9406.600Max. number of cables depending on the cross-section and the permissible permanent current.
KEL 9407.600 empty enclosuresEx II 2 G EEx e II
KE 9407.600 terminal enclosuresEx II 2 G EEx e ia II C T6 or T5
Wall mountingSee page 4.
Max. number of screwed cable glands
Equipment of terminal enclosure KE 9407.600Max. number of cables depending on the cross-section and the permissible permanent current.
KEL 9408.600 empty enclosuresEx II 2 G EEx e II
KE 9408.600 terminal enclosuresEx II 2 G EEx e ia II C T6 or T5
Wall mountingSee page 4.
Max. number of screwed cable glands
Equipment of terminal enclosure KE 9408.600Max. number of cables depending on the cross-section and the permissible permanent current.
Size A B C D
M12 x 1.5 272 264 216 216
M16 x 1.5 210 205 161 161
M20 x 1.5 150 144 114 114
M25 x 1.5 100 97 80 80
M32 x 1.5 64 62 48 48
M40 x 1.5 39 37 30 30
M50 x 1.5 22 20 16 16
M63 x 1.5 18 16 14 14
Current in A
Cross-section in mm2
1.5 2.5 4 6 10 16 25 35
10 154
16 53 103 399
20 22 60 116
25 28 65 126
35 19 49 123
50 7 40 101
63 13 47 167
80 18 52 187
100 22 49
125 2 20
Max. number of terminals 335 335 335 253 204 170 136 136
Size A B C D
M12 x 1.5 408 402 408 408
M16 x 1.5 330 324 330 330
M20 x 1.5 225 219 225 225
M25 x 1.5 156 151 156 156
M32 x 1.5 94 91 94 94
M40 x 1.5 76 73 76 76
M50 x 1.5 44 42 44 44
M63 x 1.5 27 25 27 27
Current in A
Cross-section in mm2
1.5 2.5 4 6 10 16 25 35
10 194
16 66 129 501
20 27 75 145
25 36 82 158
35 24 62 154
50 9 50 127
63 7 59 210
80 23 66 235
100 28 62
125 3 25
Max. number of terminals 335 335 335 253 204 170 136 136
Size A B C D
M12 x 1.5 552 544 432 432
M16 x 1.5 429 423 341 341
M20 x 1.5 324 320 252 252
M25 x 1.5 189 189 154 154
M32 x 1.5 126 124 108 108
M40 x 1.5 83 81 68 68
M50 x 1.5 56 54 44 44
M63 x 1.5 35 34 27 27
Current in A
Cross-section in mm2
1.5 2.5 4 6 10 16 25 35
10 211
16 72 140 545
20 30 82 158
25 39 90 172
35 26 67 168
50 10 55 139
63 18 64 229
80 25 71 256
100 31 67
125 3 27
Max. number of terminals 444 444 444 336 270 225 181 181
Plastic Ex enclosures with hinged door
11Rittal Ex enclosures to ATEX
KS 1423.600 and KS 1432.600 with only one cam lock in the centreModel No. B1 B2 B3 B4 B5 B7 B8 H1 H2 H3 H5 H6 H7 T1 T3 T4 m1 m2 m3 F1 G1
KEL 9201.600 200 140 150 – 100 150 25 300 280 256 200 245 250 150 80 – 110/117 119 2,0 3,0 3,0 145 250
KEL 9202.600 250 190 200 75 150 200 50 350 330 306 250 295 300 150 80 – 110/117 119 2,0 3,0 3,0 195 300
KEL 9203.600 300 240 249 100 200 250 50 400 380 355 300 345 350 200 80 – 160/167 169 2,0 3,0 3,0 245 350
KEL 9204.600 400 340 348 200 300 350 100 400 380 354 300 345 350 200 80 – 159/166 168,5 2,5 3,2 3,2 345 350
KEL 9205.600 400 340 348 200 300 350 100 600 580 554 500 545 550 200 80 – 158/165 168 2,5 3,5 3,5 345 550
KEL 9206.600 600 540 548 400 500 550 200 600 580 554 500 545 550 200 80 – 158/165 168 2,5 3,5 3,5 545 550
KEL 9207.600 500 440 434 300 400 450 150 500 480 454 400 445 450 300 80 – 258/265 268 2,5 3,5 3,5 417 450
Model No. B1 B2 B3 B4 B5 B7 H1 H2 H3 H5 H6 H7 m2 m3 G1 F1
KEL 9208.600 600 485 533 400 500 550 800 780 753 700 740 750 3,7 3,7 750 517
KEL 9209.600 800 685 733 600 700 750 1000 980 953 900 940 950 3,7 4,0 950 717
B452
B2
B7
B1
B3
B5
H3
100
H6
H5
4.5
H2
H1
H7
25
T1
m1
m2
3
T4
T3
12.5
42.5
42.5
12.5
12.5G
1
10
50
10.
5
F1
16
60
10.5
8.5
B8
3
m3
17.5 B7 = Separation width for wall mounting holeH7 = Separation height for wall mounting hole
Mounting plate
Inside view of door
Only KEL 9201.600
and KEL 9202.600
Material:Enclosure: Fibre-glass-reinforced unsaturated polyesterSurface resistance: < 103 ΩMounting plate: Sheet steel, zinc-plated, passivated
Colour:RAL 9011
Protection category:IP 66 to EN 60 529/10.91KEL 9209.600:IP 56 to EN 60 529/10.91
Certificates: PTB 03 ATEX 1011U (for empty enclosures KEL)PTB 03 ATEX 102 (for terminal enclosures KE)
Supply includes:Enclosure, door with all-round foamed-in PU seal, mounting plate.
Wall brackets for safe enclosure attachment of the series KE/KEL 9201.600 – 9209.600. Colour similar to RAL 9011.
Material:Durethan
Packs of Model No. KE
4 9266.000
Ex enclosuresPlastic enclosures with hinged door
12 Rittal Ex enclosures to ATEX
KEL 9201.600 empty enclosuresEx II 2 G EEx e II
KE 9201.600 terminal enclosuresEx II 2 G EEx e ia II C T6 or T5
Wall mountingSee page 11.
Max. number of screwed cable glands
Equipment of terminal enclosure KE 9201.600Max. number of cables depending on the cross-section and the permissible permanent current.
KEL 9202.600 empty enclosuresEx II 2 G EEx e II
KE 9202.600 terminal enclosuresEx II 2 G EEx e ia II C T6 or T5
Wall mountingSee page 11.
Max. number of screwed cable glands
Equipment of terminal enclosure KE 9202.600Max. number of cables depending on the cross-section and the permissible permanent current.
KEL 9203.600 empty enclosuresEx II 2 G EEx e II
KE 9203.600 terminal enclosuresEx II 2 G EEx e ia II C T6 or T5
Wall mountingSee page 11.
Max. number of screwed cable glands
Equipment of terminal enclosure KE 9203.600Max. number of cables depending on the cross-section and the permissible permanent current.
Size A B C D
M12 x 1.5 24 24 24 24
M16 x 1.5 16 16 16 16
M20 x 1.5 4 4 8 8
M25 x 1.5 2 2 6 6
M32 x 1.5 2 2 2 2
M40 x 1.5 – – 2 2
M50 x 1.5 – – – –
M63 x 1.5 – – – –
Current in A
Cross-section in mm2
1.5 2.5 4 6 10 16
10 75
16 26 50 195
20 10 29 56
25 14 32 61
35 9 24 60
50 3 19 49
63 6 23
80 8
100
125
Max. number of terminals 40 40 40 30 24 20
Size A B C D
M12 x 1.5 32 32 32 32
M16 x 1.5 22 22 22 22
M20 x 1.5 8 8 12 12
M25 x 1.5 8 8 10 10
M32 x 1.5 2 2 4 4
M40 x 1.5 2 2 2 2
M50 x 1.5 2 2 2 2
M63 x 1.5 – – – –
Current in A
Cross-section in mm2
1.5 2.5 4 6 10 16 25 35
10 83
16 28 55 215
20 11 32 62
25 15 35 68
35 10 26 66
50 4 21 54
63 7 25 90
80 9 28 101
100 12 26
125 10
Max. number of terminals 44 44 44 33 27 22 18 18
Size A B C D
M12 x 1.5 60 60 60 60
M16 x 1.5 46 46 46 46
M20 x 1.5 24 24 32 32
M25 x 1.5 22 22 24 24
M32 x 1.5 12 12 12 12
M40 x 1.5 4 4 8 8
M50 x 1.5 4 4 4 4
M63 x 1.5 2 2 2 2
Current in A
Cross-section in mm2
1.5 2.5 4 6 10 16 25 35
10 105
16 36 69 270
20 15 40 78
25 19 44 85
35 13 33 83
50 5 27 69
63 9 32 113
80 12 35 127
100 15 33
125 13
Max. number of terminals 60 60 60 46 37 30 24 24
Plastic enclosures with hinged door
Ex enclosures
13Rittal Ex enclosures to ATEX
KEL 9204.600 empty enclosuresEx II 2 G EEx e II
KE 9204.600 terminal enclosuresEx II 2 G EEx e ia II C T6 or T5
Wall mountingSee page 11.
Max. number of screwed cable glands
Equipment of terminal enclosure KE 9204.600Max. number of cables depending on the cross-section and the permissible permanent current.
KEL 9205.600 empty enclosuresEx II 2 G EEx e II
KE 9205.600 terminal enclosuresEx II 2 G EEx e ia II C T6 or T5
Wall mountingSee page 11.
Max. number of screwed cable glands
Equipment of terminal enclosure KE 9205.600Max. number of cables depending on the cross-section and the permissible permanent current.
KEL 9206.600 empty enclosuresEx II 2 G EEx e II
KE 9206.600 terminal enclosuresEx II 2 G EEx e ia II C T6 or T5
Wall mountingSee page 11.
Max. number of screwed cable glands
Equipment of terminal enclosure KE 9206.600Max. number of cables depending on the cross-section and the permissible permanent current.
Size A B C D
M12 x 1.5 60 60 96 96
M16 x 1.5 46 46 66 66
M20 x 1.5 24 24 40 40
M25 x 1.5 22 22 36 36
M32 x 1.5 12 12 24 24
M40 x 1.5 4 4 12 12
M50 x 1.5 4 4 8 8
M63 x 1.5 2 2 4 4
Current in A
Cross-section in mm2
1.5 2.5 4 6 10 16 25 35
10 114
16 39 76 294
20 16 44 85
25 21 48 93
35 14 36 90
50 5 29 75
63 10 35 123
80 13 38 138
100 16 36
125 14
Max. number of terminals 99 99 99 75 60 50 40 40
Size A B C D
M12 x 1.5 120 120 96 96
M16 x 1.5 82 82 62 62
M20 x 1.5 52 52 40 40
M25 x 1.5 39 39 35 35
M32 x 1.5 20 20 20 20
M40 x 1.5 10 10 10 10
M50 x 1.5 10 10 8 8
M63 x 1.5 4 4 4 4
Current in A
Cross-section in mm2
1.5 2.5 4 6 10 16 25 35
10 123
16 42 82 317
20 17 48 92
25 22 52 100
35 15 39 98
50 5 32 81
63 10 37 133
80 14 41 149
100 18 39
125 16
Max. number of terminals 172 172 172 130 104 87 70 70
Size A B C D
M12 x 1.5 120 120 156 156
M16 x 1.5 82 82 109 109
M20 x 1.5 52 52 72 72
M25 x 1.5 38 38 58 58
M32 x 1.5 18 18 32 32
M40 x 1.5 9 9 16 16
M50 x 1.5 9 9 12 12
M63 x 1.5 4 4 6 6
Current in A
Cross-section in mm2
1.5 2.5 4 6 10 16 25 35
10 142
16 49 95 368
20 20 55 107
25 26 60 116
35 18 45 113
50 6 37 94
63 12 43 154
80 16 48 173
100 20 45
125 2 18
Max. number of terminals 258 258 258 195 157 131 105 105
Ex enclosuresPlastic enclosures with hinged door
14 Rittal Ex enclosures to ATEX
KEL 9207.600 empty enclosuresEx II 2 G EEx e II
KE 9207.600 terminal enclosuresEx II 2 G EEx e ia II C T6 or T5
Wall mountingSee page 11.
Max. number of screwed cable glands
Equipment of terminal enclosure KE 9207.600Max. number of cables depending on the cross-section and the permissible permanent current.
KEL 9208.600 empty enclosuresEx II 2 G EEx e II
KE 9208.600 terminal enclosuresEx II 2 G EEx e ia II C T6 or T5
Wall mountingSee page 11.
Max. number of screwed cable glands
Equipment of terminal enclosure KE 9208.600Max. number of cables depending on the cross-section and the permissible permanent current.
KEL 9209.600 empty enclosuresEx II 2 G EEx e II
KE 9209.600 terminal enclosuresEx II 2 G EEx e ia II C T6 or T5
Wall mountingSee page 11.
Max. number of screwed cable glands
Equipment of terminal enclosure KE 9209.600Max. number of cables depending on the cross-section and the permissible permanent current.
Size A B C D
M12 x 1.5 165 165 220 220
M16 x 1.5 120 120 152 152
M20 x 1.5 72 72 112 112
M25 x 1.5 55 55 91 91
M32 x 1.5 25 25 45 45
M40 x 1.5 15 15 32 32
M50 x 1.5 10 10 16 16
M63 x 1.5 7 7 10 10
Current in A
Cross-section in mm2
1.5 2.5 4 6 10 16 25 35
10 157
16 54 104 405
20 22 61 117
25 29 66 128
35 19 50 124
50 7 40 103
63 13 48 170
80 18 53 190
100 23 50
125 2 20
Max. number of terminals 197 197 197 149 120 100 80 80
Size A B C D
M12 x 1.5 308 308 286 286
M16 x 1.5 232 232 187 187
M20 x 1.5 152 152 144 144
M25 x 1.5 102 102 102 102
M32 x 1.5 54 54 54 54
M40 x 1.5 31 31 35 35
M50 x 1.5 17 17 21 21
M63 x 1.5 17 17 16 16
Current in A
Cross-section in mm2
1.5 2.5 4 6 10 16 25 35
10 181
16 62 121 468
20 26 70 136
25 33 77 148
35 22 58 144
50 8 47 119
63 16 55 197
80 21 61 220
100 26 58
125 2 23
Max. number of terminals 343 343 343 259 208 174 139 139
Size A B C D
M12 x 1.5 418 418 308 308
M16 x 1.5 290 290 222 222
M20 x 1.5 200 200 144 144
M25 x 1.5 144 144 102 102
M32 x 1.5 82 82 54 54
M40 x 1.5 46 46 36 36
M50 x 1.5 27 27 20 20
M63 x 1.5 22 22 16 16
Current in A
Cross-section in mm2
1.5 2.5 4 6 10 16 25 35
10 211
16 72 140 545
20 30 82 158
25 39 90 172
35 26 67 168
50 10 55 139
63 18 64 229
80 25 71 256
100 31 67
125 3 27
Max. number of terminals 444 444 444 336 270 225 181 181
Prepared for Ex pressurisation or indoor and outdoor solutions
Baying systems TS 8 with side panel
15Rittal Ex enclosures to ATEX
Prepared for Ex pressurisation
Prepared for NEMA 4x, NEMA 4
Width mm 600 800 600 800 600 800 1000 600 800 600 –
Height mm 1400 1400 1600 1600 1800 1800 1800 1800 1800 1800 –
Depth mm 500 500 500 500 400 400 400 500 500 600 –
Model No. TS sheet steel 8645.660 8845.660 8665.660 8865.660 8684.660 8884.660 8084.660 8685.660 8885.660 8686.660 –
Width mm 800 600 800 600 800 600 800 600 800 600 800
Height mm 1800 2000 2000 2000 2000 2000 2000 2000 2000 2200 2200
Depth mm 600 400 400 500 500 600 600 800 800 600 600
Model No. TS sheet steel 8886.660 8604.660 8804.660 8605.660 8805.660 8606.660 8806.660 8608.660 8808.660 8626.660 8826.660
Width mm 800 1000 600 800 600 600 800 800 – – –
Height mm 1800 1800 1800 1800 1800 2000 2000 2000 – – –
Depth mm 400 400 500 500 600 600 600 800 – – –
Model No. TS stainless steel 8454.660 8461.660 8457.660 8455.660 8458.660 8452.660 8450.660 8460.660 – – –
Packs of NEMA 4x, stainless steel NEMA 4, sheet steel
Width mm 600 800 600 800 600 800 600 800
Height mm 1800 1800 2000 2000 1800 1800 2000 2000
Depth mm 600 600 600 600 600 600 600 600
Clearance width mm 512 712 512 712 512 712 512 712
Clearance height mm 1712 1712 1912 1912 1712 1712 1912 1912
Clearance depth mm 512 512 512 512 512 512 512 512
Door clearance available for installation 455 655 455 655 455 655 455 655
Door clearance available for installation 1630 1630 1830 1830 1630 1630 1830 1830
Mounting plate width 499 699 499 699 499 699 499 699
Mounting plate height 1696 1696 1896 1896 1696 1696 1896 1896
Model No. TS 1 8458.640 8459.640 8452.640 8450.640 8686.640 8886.640 8606.640 8806.640
Door 1 1 1 1 1 1 1 1
Design: Base as for roof Door with additional cams top
and bottom (only EEx p models)
Door r/h or l/h hinged on request
Front and back door on request
3 mm zinc-plated mounting plate (sheet steel)
Customer-specific design and solutions on request
Price and delivery times on request
Protection category:Complies with Nema 4, Nema 4x, IP 65
Material:Sheet steel, dipcoat primed and powder-coated on the outside in textured RAL 7035or stainless steel 1.4301 (AISI 304)or stainless steel 1.4401 (AISI 316L)
R
Switch to perfection
Small enclosures Compact enclosures Large enclosuresPC enclosure and case systems Console systems Industrial Workstations Command Panel systems Support arm systems Stainless steel enclosures EMC-shielded enclosures Ex enclosures
All in all – solutions from Rittal
Rittal has one of the largest ranges of enclosures available for immediate delivery. However, Rittal also supplies integrated solutions – up to Level 4. This comprises mechanical installation, power supply, electronic components, climate control and central monitoring. For all
of your requirements. Fully assembled and functional. Wherever in the world you develop and implement solutions for yourself and your customers, we are close at hand. The global alliance between production, distribution and service guarantees closeness to the customer. Worldwide!
10/0
4 E
145
Electronic packaging
IT solutions
Communication systems
System climate control
Power distribution
Industrial enclosures