SAMPLE Thermography Inspection Report of ABC...

10
SAMPLE Thermography Inspection Report of ABC PLAZA ABC Street, Auckland - XX November 20XX Report Prepared for: Inspection and Report by: ABC Property Eric Hammond c/-Abc Management Thermographer ABC Street Registered Electrician PO Box XXX

Transcript of SAMPLE Thermography Inspection Report of ABC...

SAMPLE Thermography Inspection Report

of ABC PLAZA

ABC Street, Auckland - XX November 20XX

Report Prepared for: Inspection and Report by:

ABC Property Eric Hammond c/-Abc Management Thermographer ABC Street Registered Electrician PO Box XXX

Thermography Report

Scope of Works

To perform quantitative thermography inspections of the electrical distribution equipment for the purpose of ongoing risk management at the following location(s):

Concept

Conventional techniques such as impedance testing and torque checking have a relatively low effectiveness in detecting and preventing electrical component failure. Thermal imaging is the technique for making invisible infrared radiation visible and is the non-contact on-line mapping and analysis of thermal patterns from the surface of an object that can be employed to detect temperature rises as "hot spots". Identification of hot spots can be used to trigger remedial works, reducing the number of defects and improving reliability. The infrared element of the radiation is measured and constructed from a multitude of point measurements taken in sequence whilst scanning the field of view representing the point temperature values.

The temperature of electrical components and connections are indicative of their health. Excessive heat due to increased electrical resistance will be generated by faulty components and by loose or deteriorated connections, short-circuit, overload, mismatched or improperly installed components. Equipment running hot can also be related to load imbalance, failure of cooling, missing or deteriorated materials, improper installation or insufficient amounts of material usually cause anomalies in insulation system.

A regular thermal imaging program can assist to identify potential problems before the component fails allowing repairs to be conveniently scheduled as apposed to costly and unexpected breakdowns or failures.

Disclaimer

Due to the dynamic nature of both operating and ambient conditions of electrical equipment, the images recorded in this report are only valid for the specific moment in time when they were recorded. Many external forces can immediately change the operating condition of a piece of equipment , therefore the thermographer Eric Hammond, and Replacement Lamp Services Limited are not responsible for any action, inaction or consequences which arise from this report.

Privacy Policy

We have the duty to protect any information we collect from you. We do not pass on your details to any third party unless you give us permission to do so.

Further Information

Please address any comments or questions you may have to: Replacement Lamp Services Limited 220a Bush Road, Albany, Auckland 0632 P O Box 300059, Albany 0752Tel. 09 414 0300 email: [email protected] page: http://www.lamp.co.nz

Building Name ABC PLAZA

Site Address ABC PROPERTY

Sample

Thermography Report

Inspection Methodology

(A) Inspection Conditions:

The inspection shall be performed when the site is operating under normal conditions. This ensures thebest conditions for the detection of temperature anomalies.

(B) Equipment Used:

Infrared Camera: Fluke i450

Mobile Phone (for recording of notes and reference images)

Basic Hand Tools

(C) Method Statements:

Assess of electrical cupboard condition: Check cupboard doors and locks. Check for rubbish or area being used for storage. Report on any anomalies.

Assess electrical panel condition: Check condition of electrical panel doors, locks and protective covers. Check for missing fuse carriers, missing fuse plugs, missing MCB blanks or gaps in the panels. Report any anomalies. Minor repairs to be made at time of inspection or quote provided.

Perform Thermography Inspection: Report on any hotspots or anomalies visible at time of inspection. Add comments, references and location notes to image file.

The inspection shall include but is not limited to the following panels:

Main Switch Boards; Power Factor Correction Units. Metering and Link Boxes; Distribution & Sub-Distribution Boards; Fuse panels. Bus Bar and Cable Zones. Mechanical Services Switch Boards (MSSBs); Motor Control Centres (MCCs); Air Conditioning / Ventilation / AHU Panels. PLC control panels; Pump Panels.

The inspection of these panels shall include but is not limited to the following components:

Incoming Supply; Main & Sub-Main Switches. Bus bars and cabling. Isolators, Circuit Breakers, RCDs/ELCB's; Fuses and connections. Contactors & Overloads. Active, neutral, earth links and terminals. Relays and PLC I/O blocks. Control Voltage Transformers. Capacitors and shunt transformers in Power Factor Panels. Various other components and circuit wiring within the panels.

On the completion of inspection ensure that all panels are fixed back into place, panel doors closed and locked(where required), cupboard doors closed and locked.

Sample

Thermography Report

Report and Analysis

Each distribution panel and thermographic image shall be assessed on a case by case basis. Recommendations to investigate or perform corrective action shall be made with consideration to the type of panel and/or component being assessed.

The thermographer may use the below Delta-T(temperature difference) criteria to evaluate the temperature and categorise the severity of an exception. These criteria are reported as the temperature rise of the exception above the temperature of a defined reference, which is typically the ambient air temperature, a similar component under the same conditions or the maximum allowable temperature of the component.

Other anomalies such as gaps in the panels, missing fuse carriers, exposed terminals, missing fuse plugs, electrical cupboards accumulating rubbish or being used as storage areas will also be noted in the report and may also be categorised as below at the discretion of the thermographer.

Repair Priority and Fault Severity Classifications

Image Page Recommendations

Recommendations are made based on information analysed from images and notes taken onsite however final corrective action to be determined by Registered Electrician undertaking the repairs.

Repair Priority

Temperature Rise

Severity Rating Recommendation

A >40°C Critical Corrective measures required immediately

B >20°C - 40°C Serious Corrective measures required as soon as possible

C >10°C - 20°C Alert Corrective measures required as scheduling permits

D 1°C - 10°C Minor Corrective measures should be taken at the next maintenance period

Sample

Thermography Report

Report Summary

We have performed thermographic inspections of the electrical distribution equipment and in general, results of inspected electrical infrastructure was classified to be in Normal Condition, not requiring corrective action.

In addition to the above classification, there are Five exception items where anomalies have been detected and further investigation or corrective action is recommended. Detailed analysis and rectification recommendations have been provided in the thermal image pages of the report.

Exception Items

Location Fault Repair Priority

ABC PLAZA Overheating Contactor C

ABC PLAZA Incorrectly Terminated Wiring C

ABC PLAZA Parts Exposed C

ABC PLAZA Missing Pole Fillers C

ABC PLAZA Overheating Connection D

Sample

Thermography Inspection Report

Replacement Lamp Services Ltd

58.7 °C

47.8

40.6

33.3

22.5 °C

IR_00513.IS2Tuesday, 1 November 2016 at 9:59:14 AM NZDT

Image InfoImage Time Tuesday, 1 November 2016 at 9:59:14 A…Camera Serial Number Ti450-16080109Camera Manufacturer Fluke Thermography

Main Image AnnotationsLocation Eden 3, Basement, Main Switch RoomPanel Name ControlsAnalysis Fault Spot (Sp01) overheating at above

satisfactory temperaturesRating CRecommendation Replace component

Main Image MarkersName Max

Hotpoint 58.1 °C

Sp01: 58.1ºC

Text

Repaired By:

Repair Details:

Date:

DB-1, Basement, Controls

Repair Priority: C

ABC PLAZASample

Thermography Inspection Report

Replacement Lamp Services Ltd

60.0 °C

49.1

41.8

34.6

23.6 °C

IR_00522.IS2Tuesday, 1 November 2016 at 12:35:13 PM NZDT

Image InfoImage Time Tuesday, 1 November 2016 at 12:35:13…Camera Serial Number Ti450-16080109Camera Manufacturer Fluke Thermography

Main Image AnnotationsLocation Eden 4 North, Level 1, AC PanelAnalysis Wires not terminated correctlyRating CRecommendation Check and clean both connecting

surfaces. Remake and tighten with the correct level of torque loading.

Main Image MarkersName Max

DB-2, L1, AC

Repaired By:

Repair Details:

Date:

Repair Priority: C

ABC PLAZASample

Thermography Inspection Report

Replacement Lamp Services Ltd

42.4 °C

35.7

31.3

26.8

20.2 °C

IR_00521.IS2Tuesday, 1 November 2016 at 12:08:17 PM NZDT

Image InfoImage Time Tuesday, 1 November 2016 at 12:08:17…Camera Serial Number Ti450-16080109Camera Manufacturer Fluke Thermography

Main Image AnnotationsLocation Eden 4 North, Level 3(5), Aircon PanelAnalysis Fuse plug missing leaving exposed partsRating CRecommendation Install new fuse carrier

Main Image MarkersName Max

DB-3, PLAZA 3

Repaired By:

Repair Details:

Date:

Repair Priority: C

ABC PLAZASample

Thermography Inspection Report

Replacement Lamp Services Ltd

25.1 °C

23.4

22.3

21.2

19.5 °C

IR_00520.IS2Tuesday, 1 November 2016 at 12:04:46 PM NZDT

Image InfoImage Time Tuesday, 1 November 2016 at 12:04:46…Camera Serial Number Ti450-16080109Camera Manufacturer Fluke Thermography

Main Image AnnotationsLocation Eden 4 North, L3(5)Analysis Pole filler(s) missing leaving live parts

exposedRating CRecommendation Sleeve live parts in switchboard if possible,

install pole fillers

Main Image MarkersName Max

Hotpoint 24.9 °C

DB-4, North, L3(5)

Repaired By:

Repair Details:

Date:

Repair Priority:C

ABC PLAZASample

Thermography Inspection Report

Replacement Lamp Services Ltd

49.8 °C

42.2

37.1

32.0

24.4 °C

Eden 4, DB-C, R3.IS2Tuesday, 1 November 2016 at 8:53:17 AM NZDT

Image InfoImage Time Tuesday, 1 November 2016 at 8:53:17 A…Camera Serial Number Ti450-16080109Camera Manufacturer Fluke Thermography

Main Image AnnotationsLocation Eden 4, Basement, Main Switch RoomPanel Name DB CommunityAnalysis Fault Spot (Sp01) overheating against

Satisfactory Spot (Sp02.) Temperature Rise of 12.5 degrees.

Rating DRecommendation Check and clean both connecting

surfaces. Remake and tighten with the correct level of torque loading.

Main Image MarkersName Max

Hotpoint 44.0 °CReference Point 32.5 °C

Repaired By: Eric Hammond

Repair Details: As per recommendation

Date: At time of inspection

Sp02: 32.5ºC

Sp01: 44ºC

DB-5, Basement, Community DB

B1

Repair Priority: D

ABC PLAZASample