Room Controller - Semi-Private Patient Room w/Daylight ... · w/Daylight Dimming and Pillow Speaker...

4
www.coopercontrol.com 1 1. Toggle Load 1 2. Toggle Load 2 3. Toggle Load 3 4. Raise Dimmer 5% 5. Lower Dimmer 5% 6. Load 1, 2, 3 Off General Exam Reading Raise Lower All Off General Exam Reading All Off Access to daylight and personal control of electric light improves the health and well being of patients, reduces anxiety and increases overall patient satisfaction. Simple to use, labeled controls allow hospital staff to provide quality care. Including energy saving strategies such as daylighting, which provides up to 30% savings, and code requirements like integral UL 924 relays qualifies the Room Controller as an outstanding solution for the private patient room. The Room Controller QuicKit is shipped preconfigured to work out-of-the-box, minimizing installation and setup time, while ensuring maximum energy savings. Using this design guide to specify your room with a Room Controller QuicKit catalog number will guarantee that after installation the lighting control system will work immediately as defined on this application guide. SUMMARY Room Controller - Semi-Private Patient Room w/Daylight Dimming and Pillow Speaker Integration ROOM CONTROLLER SAMPLE PLACEMENT LAYOUT (12X 16’) Normal power connection RC3DEHC For Patient Rooms (3 Relay + 3 Dimmer + 1 Emergency) Emergency power connection RC-6TSB-HC2-* Patient Station Daylight sensor (DSRC-FMOIR) Exam Load (2) General Emergency (Tracks with Load (1) General Load (1) General Load (1) General Load (1) General Load (1) General Emergency (Tracks with Load (1) Exam Load (2) Daylight sensor (DSRC-FMOIR) RC-4TSB-HC1-* Patient Station Emergency power connection RC3DEHC For Patient Rooms (3 Relay + 3 Dimmer + 1 Emergency) Normal power connection RC-6TSB-HC2-* Patient Station RC-4TSB-HC1-* Patient Station RC-6TSB-HC2-* Patient Station RC-6TSB-HC2-* Patient Station Nurse Call System and Entertainment System (by others) Reading - Load (3) GPCS-3Z-DIM Greengate Patient Control Station 3 switch zones 3 dimming zones w/ All Zone button RC3DEHC GPCS-3Z-DIM Greengate Patient Control Station 3 switch zones 3 dimming zones w/ All Zone button Nurse Call System and Entertainment System (by others) Reading - Load (3) RC3DEHC INTEGRATED CAPABILITIES COOPER LIGHTING GUARANTEED COMPATIBLE FIXTURES Refer to these Cooper Lighting data sheets for lighting layouts and illuminance value information. RC-4TSB-HC1 RC-6TSB-HC2 Daylighting Control Manual Control Integration Room Controller QuicKit RCQK-HC3E-HC1-HC2-HC2-3ZD-D1-P-W Manual On Patient personal control from pillow speaker, 3 relay On/Off and 3 dimming zones Direct integration with most major Nurse Call Systems Providing users with wall-based dimming controls to adjust the lighting levels to meet their needs Automatic multi-zone daylight dimming out-of-the-box High-end trim/tuning to define target light levels guarantees energy savings BMS integration for HVAC control based on Occupancy CONTROL SEQUENCE 1. Toggle Load 1 2. Toggle Load 2 3. Toggle Load 3 4. Load 1, 2, 3 Off Fail-Safe Room Controller Patient Room Lighting Layouts Product Legend (per patient bed) QTY1: RC3DEHC 3 RELAY + 3 DIMMER + 1 EMERGENCY RELAY QTY1: RC-4TSB-HC1-W GENERAL, EXAM, READING, ALL OFF QTY1: RC-6TSB-HC2-W GENERAL, EXAM, READING, RAISE, LOWER, ALL OFF QTY1: GPCS-3Z-DIM 3 ON/OFF & 3 ZONE DIMMING PATIENT CONTROLS QTY1: GG37P 37PIN CONNECTOR FOR GPCS-3Z-DIM MOUNTED ON HEADWALL QTY1: DSRC-FMOIR DAYLIGHT SENSOR QTY1: GGRJ45-10-G QUICKCONNECT CABLE 10’ QTY1: GGRJ45-50-G QUICKCONNECT CABLE 50’ SINGLE BOX PACKAGING WITH WIRING DETAIL AND INSTALLATION DOWNLIGHT FIXTURES RECESSED FIXTURES FOR GUARANTEED COMPATIBILITY REFER TO PREFERRED COOPER LIGHTING FIXTURE INFORMATION BELOW. RC3DE UL924 Emergency

Transcript of Room Controller - Semi-Private Patient Room w/Daylight ... · w/Daylight Dimming and Pillow Speaker...

Page 1: Room Controller - Semi-Private Patient Room w/Daylight ... · w/Daylight Dimming and Pillow Speaker Integration room Controller Sample plaCement layout (12’ x 16’) Normal power

www.coopercontrol.com

1

1. Toggle Load 1

2. Toggle Load 2

3. Toggle Load 3

4. Raise Dimmer 5%

5. Lower Dimmer 5%

6. Load 1, 2, 3 Off

General

Exam

Reading

Raise

Lower

All Off

General

Exam

Reading

All Off

Access to daylight and personal control of electric light improves the health and well being of patients, reduces anxiety and increases overall patient satisfaction. Simple to use, labeled controls allow hospital staff to provide quality care. Including energy saving strategies such as daylighting, which provides up to 30% savings, and code requirements like integral UL 924 relays qualifies the Room Controller as an outstanding solution for the private patient room.

The Room Controller QuicKit is shipped preconfigured to work out-of-the-box, minimizing installation and setup time, while ensuring maximum energy savings. Using this design guide to specify your room with a Room Controller QuicKit catalog number will guarantee that after installation the lighting control system will work immediately as defined on this application guide.

Summary

Room Controller - Semi-Private Patient Room w/Daylight Dimming and Pillow Speaker Integration

room Controller Sample plaCement layout (12’ x 16’)

Nor

mal

pow

er

conn

ectio

nR

C3D

EH

CFo

r Pat

ient

Roo

ms

(3 R

elay

+ 3

Dim

mer

+ 1

Em

erge

ncy)

Low

er

All

Off

Rai

se

Rea

ding

Exa

m

Gen

eral

Em

erge

ncy

pow

er

conn

ectio

n

RC-6TSB-HC2-*Patient Station

Day

light

sen

sor

(DS

RC

-FM

OIR

)

Exa

mLo

ad (2

)

Gen

eral

Em

erge

ncy

(Tra

cks

with

Loa

d (1

)

Gen

eral

Load

(1)

Gen

eral

Load

(1)

Gen

eral

Load

(1)

Gen

eral

Load

(1)

Gen

eral

Em

erge

ncy

(Tra

cks

with

Loa

d (1

)

Exa

mLo

ad (2

)

Day

light

sen

sor

(DS

RC

-FM

OIR

)

RC-4TSB-HC1-*Patient Station

Em

erge

ncy

pow

er

conn

ectio

n

All Off

Reading

Exam

General

Gen

eral

Exa

m

Rea

ding

Rai

se

All

Off

Low

er

Gen

eral

Exa

m

Rea

ding

Rai

se

All

Off

Low

er

RC

3DE

HC

For P

atie

nt R

oom

s(3

Rel

ay +

3 D

imm

er +

1 E

mer

genc

y)N

orm

al p

ower

co

nnec

tion

RC-6TSB-HC2-*Patient Station

General

Exam

Reading

All Off RC-4TSB-HC1-*Patient Station

RC-6TSB-HC2-*Patient Station

Gen

eral

Exa

m

Rea

ding

Rai

se

All

Off

Low

er

RC-6TSB-HC2-*Patient Station

Nur

se C

all S

yste

m a

nd

Ent

erta

inm

ent S

yste

m(b

y ot

hers

)

ccTV

12

3

45

67

89

PREV

0

13

ALL

ON

/OFF2

MU

TE

SLEE

PO

PTIO

N

CH

AN

NEL

VOLU

MEVO

LUM

EC

HA

NN

EL

OPTIO

NSLEEP

MU

TE

2

ALL

ON

/OFF

31

0PR

EV

98

76

54

32

1

TVcc

Rea

ding

- Lo

ad (3

)

GP

CS

-3Z-

DIM

Gre

enga

te P

atie

nt C

ontro

l Sta

tion

3 sw

itch

zone

s 3

dim

min

g zo

nes

w/ A

ll Zo

ne b

utto

n

RC

3DE

HC

GP

CS

-3Z-

DIM

Gre

enga

te P

atie

nt C

ontro

l Sta

tion

3 sw

itch

zone

s 3

dim

min

g zo

nes

w/ A

ll Zo

ne b

utto

n

Nur

se C

all S

yste

m a

nd

Ent

erta

inm

ent S

yste

m(b

y ot

hers

)

Rea

ding

- Lo

ad (3

)

RC

3DE

HC

Integrated CapabIlItIeS Cooper lIghtIng guaranteed CompatIble FIxtureS

Refer to these Cooper Lighting data sheets for lighting layouts and illuminance value information.

RC-4TSB-HC1 RC-6TSB-HC2

UL924

DaylightingControl

UL924

ManualControl

UL924

Integration

Room Controller QuicKitRCQK-HC3E-HC1-HC2-HC2-3ZD-D1-P-W

• Manual On

• Patient personal control from pillow speaker, 3 relay On/Off and 3 dimming zones

• Direct integration with most major Nurse Call Systems

• Providing users with wall-based dimming controls to adjust the lighting levels to meet their needs

• Automatic multi-zone daylight dimming out-of-the-box

• High-end trim/tuning to define target light levels guarantees energy savings

• BMS integration for HVAC control based on Occupancy

Control SequenCe

1. Toggle Load 1

2. Toggle Load 2

3. Toggle Load 3

4. Load 1, 2, 3 Off

Fail-Safe Room Controller Patient Room Lighting Layouts

Product Legend (per patient bed)

Qty1: RC3DEhC3 relay + 3 DImmer + 1 emergency relay

Qty1: RC-4tSB-hC1-Wgeneral, eXam, reaDIng, all off

Qty1: RC-6tSB-hC2-Wgeneral, eXam, reaDIng, raISe, lower, all off

Qty1: GPCS-3Z-DIM3 on/off & 3 Zone DImmIng PaTIenT conTrolS

Qty1: GG37P37PIn connecTor for gPcS-3Z-DIm moUnTeD on HeaDwall

Qty1: DSRC-FMOIRDaylIgHT SenSor

Qty1: GGRJ45-10-GqUIcKconnecT caBle 10’

Qty1: GGRJ45-50-GqUIcKconnecT caBle 50’

Single box packaging with wiring detail and inStallation

DOWNLIGht FIXtURES

RECESSED FIXtURES

for gUaranTeeD comPaTIBIlITy refer To PreferreD cooPer lIgHTIng fIXTUre InformaTIon Below.

Half Lights

All Off

Full Lights

Raise

Lower

RC3DE

Entry Lighting

All Off

RC3D

General

Exam

Reading

All Off

cc

TV

1 2 3

4 5 67 8 9

PREV 0

1 3ALLON/OFF

2

MUTE

SLEEP OPTION

CHANNEL VOLUME

General

Whiteboard

Quiet Time •

A/V Mode

Raise

Lower

Half Lights

All Off

Full Lights

Raise

Lower

RC3DE

Entry Lighting

All Off

RC3D

General

Exam

Reading

All Off

cc

TV

1 2 3

4 5 67 8 9

PREV 0

1 3ALLON/OFF

2

MUTE

SLEEP OPTION

CHANNEL VOLUME

General

Whiteboard

Quiet Time •

A/V Mode

Raise

Lower

Half Lights

All Off

Full Lights

Raise

Lower

RC3DE

Entry Lighting

All Off

RC3D

General

Exam

Reading

All Off

cc

TV

1 2 3

4 5 67 8 9

PREV 0

1 3ALLON/OFF

2

MUTE

SLEEP OPTION

CHANNEL VOLUME

General

Whiteboard

Quiet Time •

A/V Mode

Raise

Lower

Half Lights

All Off

Full Lights

Raise

Lower

RC3DE

Entry Lighting

All Off

RC3D

General

Exam

Reading

All Off

cc

TV

1 2 3

4 5 67 8 9

PREV 0

1 3ALLON/OFF

2

MUTE

SLEEP OPTION

CHANNEL VOLUME

General

Whiteboard

Quiet Time •

A/V Mode

Raise

Lower

Half Lights

All Off

Full Lights

Raise

Lower

RC3DE

Entry Lighting

All Off

RC3D

General

Exam

Reading

All Off

cc

TV

1 2 3

4 5 67 8 9

PREV 0

1 3ALLON/OFF

2

MUTE

SLEEP OPTION

CHANNEL VOLUME

General

Whiteboard

Quiet Time •

A/V Mode

Raise

Lower

Half Lights

All Off

Full Lights

Raise

Lower

RC3DE

Entry Lighting

All Off

RC3D

General

Exam

Reading

All Off

cc

TV

1 2 3

4 5 67 8 9

PREV 0

1 3ALLON/OFF

2

MUTE

SLEEP OPTION

CHANNEL VOLUME

General

Whiteboard

Quiet Time •

A/V Mode

Raise

Lower

Half Lights

All Off

Full Lights

Raise

Lower

RC3DE

Entry Lighting

All Off

RC3D

General

Exam

Reading

All Off

cc

TV

1 2 3

4 5 67 8 9

PREV 0

1 3ALLON/OFF

2

MUTE

SLEEP OPTION

CHANNEL VOLUME

General

Whiteboard

Quiet Time •

A/V Mode

Raise

Lower

Half Lights

All Off

Full Lights

Raise

Lower

RC3DE

Entry Lighting

All Off

RC3D

General

Exam

Reading

All Off

cc

TV

1 2 3

4 5 67 8 9

PREV 0

1 3ALLON/OFF

2

MUTE

SLEEP OPTION

CHANNEL VOLUME

General

Whiteboard

Quiet Time •

A/V Mode

Raise

Lower

Half Lights

All Off

Full Lights

Raise

Lower

RC3DE

Entry Lighting

All Off

RC3D

General

Exam

Reading

All Off

cc

TV

1 2 3

4 5 67 8 9

PREV 0

1 3ALLON/OFF

2

MUTE

SLEEP OPTION

CHANNEL VOLUME

General

Whiteboard

Quiet Time •

A/V Mode

Raise

Lower

UL924

Emergency

Page 2: Room Controller - Semi-Private Patient Room w/Daylight ... · w/Daylight Dimming and Pillow Speaker Integration room Controller Sample plaCement layout (12’ x 16’) Normal power

www.coopercontrol.com

2

In developing a patient room lighting control solution, Cooper Controls found existing methods for providing patients control over natural and electric lighting levels to be inadequate. Control solutions that rely on existing off-the-shelf pillow speakers and nurse call station interfaces are severely limited in functionality. On/Off only control of a limited number of lighting zones is typical for these systems.

To adress this issue, Cooper Controls developed a line of proprietary pillow speakers designed specifically to support the control of natural and electric light.

These units offer the following features:• Support for up to three zones of electric lighting control• An all zones On/all zones Off function• Independent Raise/Lower control of each zone• Shade Raise/Lower function• Standard pillow speaker functionality including nurse call and television control• Sealed design reduces potential risk of infectious fluids or solids settling into the unit, even in the speaker area• High-impact case material is designed to withstand over 100 drops onto a concrete floor without impacting its functionality• Standard interface to leading nurse call stations

These exceptionally functional control devices interface with a state of art, small form factor lighting control panel. This panel is capable of supporting a digital switch network. Multiple digital switch stations maybe used in conjunction with the pillow speaker to provide additional control points for staff and visitors.

pIllow Speaker Control FunCtIonalIty

RC-6TSB-HC2-*Wallstation

Lower

Raise

RC-4TSB-HC1-*Wallstation

QuickConnect coupler (GGRC-COUPLER)

Adjustable daylight sensor dome

Daylight sensor(DSRC-FMOIR)

BLACK - Hot(120/277 VAC)

WHT/ORG or WHT/BLKNeutral

BLUE - Relay In(120/277 VAC)

Lighting Load (1)

Lighting Load (2)

Lighting Load (3)

YELLOW

RED

Violet - Dimmer 1

Requires 0-10V dimming ballasts

Connect up to four wallstations per Room

Controller

Quick connect cables are pre-terminated and included in the Room Controller QuicKit and measured to fit typical room layouts

Gray - Dimmer 1

Gray - Dimmer 2Violet - Dimmer 2

Violet - Dimmer 3Gray - Dimmer 3

Cooper Controls 203 Cooper Circle Peachtree City, GA 30269. USA

Tel: +1-800-553-3879 Fax: +1-800-954-7016 Email: [email protected]: www.coopercontrol.com

Room Controller - RC3DEHCThree Relay + Three Dimmers Wiring Diagram + One Emergency Relay

Drawing Name: RC3DEHC-PatientRoomWiring.dwg

PURPLE

Drawing Date: 1/10/2013

Button 5: Press and hold decrease zone 5%Button 4: Press and hold increase zone 5%

Button 2: Toggle Load (2)Button 1: Toggle Load (1)

*Immediately provides multi-zone daylight dimming upon powerup

BLUE - Emergency Power In(120/277 VAC)

YELLOWEmergency Power OUT

Emergency Lighting Load(Tracks with normal lighting YELLOW load)

EMERGENCY NEUTRAL

All Off

Reading

Exam

General General

Exam

Reading

All Off

Button 3: Toggle Load (3)

Button 6: Load (1), (2), (3) Off

Button 3: Toggle Load (3)

Button 1: Toggle Load (1)Button 2: Toggle Load (2)

Button 4: Load (1),(2),(3) Off

General

Exam

Reading

GG37PGreengate 37 Pin ReceptacleProvided by Cooper Controls for pillow speaker connection

GPCSGreengate Patient Control StationProvided by Cooper Controls

Note:Use only wiring supplied with the GG37P receptacle.Only the Greengate Patient Control Station sall be connected to a GG37P Receptacle

Eight conductors of the 37 conductor healthcare cable.

To Nurse Call System and Entertainment System (by others)

0-10V Dimming Zone Note: The 0-10V dimming zones within the Room Controller can be wired and controlled independent of the connected loads. This allows a each load to have a dedicated 0-10V dimming zone or a single load to have up to three 0-10V dimming zones.

Emergency Note: Emergency load tracks with normal lighting YELLOW load for On/OFF. If dimming it will be adjusted with the dimming zone it is connected to. Upon loss of normal power to the RC3DE, the emergency load will be forced On and full bright to 100%.

In room ladderless testing is done by pressing the "All Off" button four times, within 3 seconds.

The RC3DE is UL 924 listed.

VOLU

ME

CHAN

NEL

OPTI

ON

SLEE

PM

UTE

2AL

LON

/OFF

3

10

PREV

98

76

54

32

1

TVcc

Room Controller - Semi-Private Patient Room w/Daylight Dimming and Pillow Speaker Integration

Page 3: Room Controller - Semi-Private Patient Room w/Daylight ... · w/Daylight Dimming and Pillow Speaker Integration room Controller Sample plaCement layout (12’ x 16’) Normal power

www.coopercontrol.com

3

mountIng the room Controller

wIrIng dIagram

ConneCtIonS

daylIght SenSor CeIlIng loCatIon

Sample load Zoning(for example purposes only)

Sample placement diagram(for example purposes only)

room Controller 0-10V dimming ConnectionsDimmer 1: Near the WindowDimmer 2: Middle of RoomDimmer 3: Far from Window

The daylight sensor will automaticallyprovide multi-zone daylight dimming based on this wiring configuration.

room Controller and Smart devices use Click & go Connections1. Wallstations (up to four)2. Slider Station Connection (one)3. Occupancy Sensors (up to two)4. Daylight Sensor (one)5. Receptacle Control or BMS Output6. Switchpack (controlled with Load 1 for

alternate voltage)

WindowLoad 1

Dim

mer 1

ExamLighting

Load 3D

imm

er 3

Reading Light

Load 2D

imm

er 2 General Lighting

Window

Load 1D

imm

er 1

ExamLighting

Load 3D

imm

er 3R

eading Light

Load 2D

imm

er 2General Lighting

Window

Room Controller(above ceiling over headwall)

Patient Wallstation

DaylightSensor

GPC

SG

reengate Patient C

ontrol Station

GG

37P

General

Exam

Reading

Raise

All Off

Lower

All O

ff

Reading

Exam

General

General

Exam

Reading

All O

ff

GG

37P

GPC

SG

reengate Patient C

ontrol Station

Room Controller(above ceiling over headwall)

Window

DaylightSensor

Patient Wallstation

Patient Wallstation

Patient Wallstation

Lower

All Off

Raise

Reading

Exam

General

cc TV

12

3

45

67

89

PREV

0

13

ALL

ON

/OFF

2

MU

TE

SLEEPO

PTION

CH

AN

NEL

VOLU

ME VO

LUM

EC

HA

NN

EL

OPT

ION

SLEE

P

MU

TE

2 ALL

ON

/OFF

31

0PR

EV

98

76

54

32

1

TV cc

For semi-private rooms where you would need multiple Room Controllers, each would mount above the ceiling in the space it is controlling, typically above the headwall so it can be easily wired to the 37pin connector and Nurse Call System. The Room Controller includes breakouts for direct conduit connection limiting the need for additional junction boxes. Mount the Room Controller using the keyhole slots at the top and secure to the wall using the holes at the bottom of the Room Controller

Connect conduit to the line voltage breakout connections and connect the line and load wires. Connect low voltage cables either through the low voltage breakout openings or by connecting low voltage conduit to the breakouts on the low voltage side of the Room Controller.

Dimmer 3 Dimmer 2 Dimmer 1+ - -+ + -

0-10V Dimming

0-10V Violet (+)0-10V Gray (-)

4325 6

1

Room Controller - Semi-Private Patient Room w/Daylight Dimming and Pillow Speaker Integration

DSRC-FMOIR(Multi-zone

daylight sensor)

Wallstation

Room Controller(Above Ceiling Over Headwall)Normal Power

(Line In & Load Out)

Emergency Power(Line In & Load Out)

0-10V Dimmer Wiring(low voltage, class 2)

Lower

All Off

Raise

Reading

Exam

General General

Exam

Reading

All Off

GPCS(Greengate Patient

Control Station)

GG37P(Greengate 37 Pin Receptacle

for GPCS control station connection)

Connections to Nurse Call Stations and Entertainment System

Connections to Room Controller

Wallstation

ccTV

12

34

56

78

9PREV

01

3ALL

ON/OFF

2M

UTESLEEP

OPTION

CHANNEL

VOLUME

1. Mount the daylight sensor one to two times the window height from the window wall.

2. Position the sensor so its arrow is pointed toward the nearest window.3. Ensure the daylight sensor is not obstructed or looking directly at electric

light.4. For narrow spaces mount the daylight sensor near the window facing into

the space.

60°

Area viewed bydaylight sensor

Page 4: Room Controller - Semi-Private Patient Room w/Daylight ... · w/Daylight Dimming and Pillow Speaker Integration room Controller Sample plaCement layout (12’ x 16’) Normal power

www.coopercontrol.com

4

orderIng (per patIent bed)

healthCare applICatIon button FunCtIonalIty

pre-deFIned wallStatIonS and pIllow Speaker model numberS

rC-4tSb-hC1 rC-6tSb-hC2

room ControllerQuicKit

types of Space and ControlHC3E - Healthcare Patient Room (RC3DEHC) pillow Speaker

3Z - 3 Relay On/Off control

3ZD - 3 Relay On/Off, 3 zone dimming control

2Z - 2 Relay On/Off control

2ZD - 2 Relay On/Off, 2 zone dimming conrtol

daylightD1 - Multi-zone Daylight Sensor

DH - Multi-zone Daylight Sensor w/

Handheld Remote optionsP - Plug Load

B - BMS/Egress

Station ColorW - White

G - Gray

V - Ivory

B - Black

patient Stations (Choose up to 4)HC1 - General, Exam, Reading, All Off

HC2 - General, Exam, Reading, Raise, Lower, All Off

programno.

button textControl

type

Function(unless a target level is indicated, the dimmer output will default to daylight sensor control)

1 General Toggle Load 1 (yellow) ON and OFF

2 Exam Toggle Load 2 (red) ON and OFF

3 Reading Toggle Load 3 (purple) ON and OFF

6 Raise Raise Raise All Dimmers†

7 Lower Lower Lower All Dimmers†

16 All On PresetLoad 1 (yellow) ON, Load 2 (red) ON, Load 3 (purple) ON

8 All Off PresetLoad 1 (yellow) OFF, Load 2 (red) OFF, Load 3 (purple) OFF

†Final dimmer output level is determined by the fol lowing combination:• High end trim level• Daylighting contribution

If enough natural l ight is entering the space and either of these features has been implemented, raise commands from pushbuttons or the Greengate Patient Control Station wil l not override or raise the l ighting above the target threshold implemented by these advanced energy savings methods.

additional Information:Emergency relay wil l always work under normal conditions with Load 1 (yellow lead).

Alternate Voltage Switchpack: Click & Go connected alternate voltage switchpacks wil l always track with Load 1 (yellow lead).

General

Exam

Reading

All Off

General

Exam

Reading

Raise

Lower

All Off

Catalog #

Project

Comments

Prepared by

Type

Date

Room Controller - Semi-Private Patient Room w/Daylight Dimming and Pillow Speaker Integration

ACC130085

gpCS-2Z gpCS-2Z-dIm gpCS-3Z gpCS-3Z-dIm

7

4

1

8

5

2 3

6

9

TVPOWER

CHANNEL VOLUME

Gen4

OPTION

MUTEPREV

SLEEP

0

ALLON/OFF

LIGHTS1 3

7

4

1

8

5

2 3

6

9

TVPOWER

CHANNEL VOLUME

Gen4

OPTION

MUTEPREV

SLEEP

0

ALLON/OFF

LIGHTS1 3

LIGHTDIM

7

4

1

8

5

2 3

6

9

TVPOWER

CHANNEL VOLUME

Gen4

OPTION

MUTEPREV

SLEEP

0

ALLON/OFF

LIGHTS1 3

2

7

4

1

8

5

2 3

6

9

TVPOWER

CHANNEL VOLUME

Gen4

OPTION

MUTEPREV

SLEEP

0

ALLON/OFF

LIGHTS1 3

2

LIGHTDIM

Input button IconControl

type

Function(unless a target level is indicated, the dimmer output will default to daylight sensor control)

1 (General)

1

2

ALLON/OFF

3

ToggleLoad 1 (yellow) ON and OFF, Sets Raise/Lower control action to control Dimmer 1

2 (Exam)

1

2

ALLON/OFF

3

ToggleLoad 2 (red) ON and OFF, Sets Raise/Lower control action to control Dimmer 2

3 (Reading)

1

2

ALLON/OFF

3 ToggleLoad 3 (purple) ON and OFF, Sets Raise/Lower control action to control Dimmer 3

6 (All)

1

2

ALLON/OFF

3

ToggleLoad 1 (yellow), Load 2 (red), Load 3 (purple) ON and OFF, Sets Raise/Lower control action to control dimmers 1, 2 and 3

Raise

1

2

ALLON/OFF

3

Raise

Raise the selected dimmer zone.† Zone controlled is based on last GPCS button that was pressed. To control all zones together, ensure that the ALL button is pressed prior to raising the zones.

Lower

1

2

ALLON/OFF

3

Lower

Lower the selected dimmer zone. Zone controlled is based on last GPCS button that was pressed. To control all zones together, ensure that the ALL button is pressed prior to raising the zones.

†Final dimmer output level is determined by the fol lowing combination:• High end trim level• Daylighting contribution

If enough natural l ight is entering the space and either of these features has been implemented, raise commands from pushbuttons or the Greengate Patient Control Station wil l not override or raise the l ighting above the target threshold implemented by these advanced energy savings methods.

additional Information:Emergency relay wil l always work under normal conditions with Load 1 (yellow lead).

Alternate Voltage Switchpack: Click & Go connected alternate voltage switchpacks wil l always track with Load 1 (yellow lead).

RCQK - HC3E - HC1-HC2 - 3ZD - D1 - P - W

*Catalog number automatically includes low voltage connection cable, wallplates and connectors based on room type and configuration.

*For site specific engraving, please see the Room Controller Wallstation custom engraving form on the Cooper Controls website

† These dimming wallstations can only be used with dimming Room Controllers (RC3D, RC3D2, RC3DE)

†† Slider stations can not be used if a wallstation with Raise/Lower buttons are used

pIllow Speaker FunCtIonalIty