ROOM CONTROLLER 24 - Douglas Lighting Controls

48
by ® Product Overview & Reference Guide ROOM CONTROLLER ASHRAE 90.1-2010 C a lif o r n i a C o m p l i a n t 24 TITLE - - - - - - - - - - - - - - - - - - - - - - - - -

Transcript of ROOM CONTROLLER 24 - Douglas Lighting Controls

Page 1: ROOM CONTROLLER 24 - Douglas Lighting Controls

by

®

Product Overview & Reference GuideROOM CONTROLLER ASHRAE 90.1-2010

California

Compliant24TITLE

- - -

- -

- -

- - -

- - - - - - - - - - - - - - -

Page 2: ROOM CONTROLLER 24 - Douglas Lighting Controls

to provide the flexibility and cost savings needed in today’s competitive lighting controls market. It’s designed for stand-alone room applications, but can also be networked to a Dialog controller for centralized control of an entire floor or building.” Brad Stevenson - Vice President, Sales Douglas Lighting Controls

“The Dialog Room Controller* is the right product...

* Patent Pending1

Page 3: ROOM CONTROLLER 24 - Douglas Lighting Controls

Dialog Room Controller introduces specifiers and contractors to a versatile solution for stand-alone or networked lighting control applications. The Dialog Room Controller, manages classrooms, offices, conference rooms or small rooms to meet local and national lighting requirements such as ASHRAE 90.1-2010, California Title 24, and New York Local Law 48.

The Dialog Room Controller incorporates 2 sections – the Room Controller and the UL924 Relay Expansion Pack. The Room Controller is the main device and it includes 4 relays, 4 independent dimming

channels and the capability to connect to a Douglas Lighting Controls Dialog or BACnet network. When the need for emergency lighting control or additional relays arises because of room size or lighting requirements, the Room Controller UL924 / Relay Expansion Pack is easily added by clipping it to the bottom of the room controller and connecting to the appropriate loads. The expansion pack provides two additional relays that are certified for emergency lighting operation or can be used for additional lighting loads.

Dialog Room Controller is offered as in a packaged kit for specific room applications. Each kit is Plug ‘N ControlTM ready out of the box for fast installation. Kits can include the Room Controller, the UL924 Expansion Pack, occupancy sensors, switch stations, and daylight sensors depending on the application.

An added feature is the Dialog Room Controller can also be used in a centralized Dialog system to create a globally controlled network that is faster to install, requires less long wire/conduit runs, and provides room-by-room testing before complete system start-up.

ROOM CONTROLLER®

2

Page 4: ROOM CONTROLLER 24 - Douglas Lighting Controls

DIMENSIONS

2.1” (54mm)

6.1” (155mm)

4.3” (109mm)

5.7”(144mm)

6.3”(159mm) WEIGHT 1.15lbs (0.52kg)

3

Page 5: ROOM CONTROLLER 24 - Douglas Lighting Controls

FEATURES

CIRCUIT TEST BUTTONSRJ45 PORT FOR BACNET IP CONNECTIVITY

STATUS & LOCATOR LED LABELED LOW VOLTAGE WIRING COMPARTMENT

EASY BREAK WIRING KNOCKOUTS

& ACCESS TABS

PUSH-CONNECT DIMMING AND DATA

TERMINALSWIRE COLOR MATCHING RELAY LABELS WIRING INSTRUCTIONS½ INCH CHASE NIPPLES

½ INCH CHASE NIPPLES

COLOR CODED WIRESCLIP CONNECT RELAY

EXPANSION/UL924 EMERGENCY

LIGHTING PACK

4

Page 6: ROOM CONTROLLER 24 - Douglas Lighting Controls

ARCHITECTURE

In this example, Dialog Room Controller supports the requirements of a single classroom by taking commands from wall switches and sensors. The functionality of the lighting in this classroom is independent of lighting controls in other classrooms or across the facility. The Dialog Room Controller can be connected to a BMS/EMS via BACnet IP to receive demand response commands, share information on occupancy status, provide central time control, and allow for energy monitoring.

STAND-ALONE ARCHITECTURE

Entry Station

Teacher Station

Dialog Room Contoller

NATURAL LIGHT

Dialog Room Controller is designed for versatility. There are two common architectures for the Dialog Room Controller: Stand-alone or Networked

Occupancy/Vacancy Sensor

Daylight Sensor

5

Page 7: ROOM CONTROLLER 24 - Douglas Lighting Controls

ARCHITECTURE

In this example the Dialog Room Controller supports the requirements of one classroom by taking commands from wall switches and sensors in that classroom. Additionally, each Room Controller is networked to a centralized Dialog LCU (lighting control unit) through a low cost, polarity neutral, 2-wire data line. The LCU is programmed with schedules for controlling lights across the entire facility. Demand response functionality can also be initiated across the entire network.

NATURAL LIGHT

NATURAL LIGHT

DIALOG NETWORK CONTROLLERS

WLC-3150

Dialog Global Web Server for Master Level Control and/or Graphics Based User Experience

ROUTER LAN

LANDIALOG NETWORK

CONTROLLERSWLC-3150

NETWORKED ARCHITECTUREDialog Room Controller is designed for versatility. There are two common architectures for the Dialog Room Controller: Stand-alone or Networked

6

Page 8: ROOM CONTROLLER 24 - Douglas Lighting Controls

in identifying market challenges and then developing solutions that solve those challenges. We designed the Dialog Room Controller to eliminate wiring complications, ensure code compliance, simplify control systems, and improve the commissioning experience - common challenges that are found across our industry.” Rob Mahaffey, Director Product Market Development

“Douglas Lighting Controls continues to

provide leadership...

7

Page 9: ROOM CONTROLLER 24 - Douglas Lighting Controls

DRC 01 N S - - -1 S 1 2 1 2 N

01 = One Room System02 = Two Room System

1 = One 2-button Classroom Entry Station2 = Two 2-button Classroom Entry Stations3 = One 2-button Office Entry Station4 = Two 2-button Office Entry Stations

E = UL924 Relay Expansion PackN = None

1 = One 4-button Teacher Master Station2 = Two 4-button Teacher Master Stations3 = One 4-button Office Master Station4 = One 4-button Office Master Station + One 4-button Office Pre-set Station

1 = One Interior Daylight Sensor2 = Two Interior Daylight Sensors

1 = all relays Auto ON/Auto OFF3 = relays 1, 2, 3 Manual ON/Auto OFF. Relay 4 (receptacle) Auto ON/Auto OFF

N = No Teaching/Presentation WallO = Teaching/Presentation Wall Opposite WindowsP = Teaching/Presentation Wall Perpendicular to Windows

S = Single Daylight SourceM = Multiple Daylight Sources (Skylights)

1 = One Dual Tech Occupancy Sensor2 = Two Dual Tech Occupancy Sensors

S = standard range lensX = extended range lens

A key advantage of the Dialog Room Controller is the “kit” system. With many office and classrooms having common lighting control requirements, standardizing kits help make project design and installation easier. For extra cost and installation time saving, kits 9, 10, 15 are designed to control 2 similar rooms with only one Room Controller.

SENSOR ADDITIONSOccupancy sensors can be added to a total of 4 sensors per room controller.

SWITCH ADDITIONSDuplicate switches can be added to a total of 6 switch stations per

room controller

TITLE 24 DIMMING SWITCH ADDITIONS

For Title 24 requirements, dimming switches can be added to a total of

6 switch stations

1. Find a classroom or office layout that best suits your application on the following pages.2. Select the kit part number from the 4 options listed on the specific Kit page.

MODIFICATIONS:In some cases, specific applications may need kit modifications. For these instances, first find the kit that best suits your application, then review the modifications available below. Then call or email us.

DIALOG ROOM CONTROLLER KIT PART NUMBER OVERVIEW

LET US HELP YOU. [email protected] • 877-873-2797 ext. 607

• Removal of the Occupancy/ Vacancy Sensor• Removal of the Interior Daylight Sensor• Removal of the Entry Stations• Removal of the Teachers Station

• Addition of Occupancy/Vacancy Sensors, up to 4 per Dialog Room Controller

• Addition of duplicate wall switch stations (total of 6)

WRC-TS-1Teachers Stations

WRC-ES-1Entry Station

WRC-OF-PSPresent Station

WRC-OF-A1Entry Station

OF-TGLOffice Station

WRC-TS-8

Teaching General 50% R1 Toggle

General On Meeting 100% R2 ToggleGeneral On

A/V Presentation R3 Lights R3 ToggleAll Off

Quiet Mode All Off All Off All Off

WRC-DS-0

General

WRC-DS-F

Front

WRC-DS-R

Rear

WRC-DS-Z1

Zone 1

WRC-DS-Z2

Zone 2

WRC-DS-Z3

Zone 3

ORDERING

8

Page 10: ROOM CONTROLLER 24 - Douglas Lighting Controls

KIT #1

DimmingZone 1

Dimming Zone 3

Relay 3 White Board / Presentation Wall Lights

Window

D/S O/S

Relay 1

Dimmer 1

Dialog RoomController

Relay 1

Dimmer 2

Relay 1

Dimmer 2

Relay 1

Dimmer 1

Relay 2

Dimmer 4

Relay 2

Dimmer 4

Relay 2

Dimmer 4

Relay 2

Dimmer 4

Relay 2

Dimmer 3

Relay 2

Dimmer 3

EntryStation

EntryStation

TeacherStation

Relay 4Receptacle

Relay 1

Dimmer 2

Relay 1

Dimmer 2

DimmingZone 2

DimmingZone 4

Classroom• Windows Perpendicular to Teaching Wall• Occupancy Control (Auto ON /Auto OFF)• Daylight Control (2 zones)• Light Control (3 zones)• Receptacle Control• Dimming Control (4 zones)• Entry Station (General ON/ALL OFF)• Teacher Station (Teaching, General ON, A/V, Quiet Mode)

Options• Additional Occupancy Sensors (4 max.)• Vacancy Control (Manual ON / Auto OFF)• Extended Lens range: 54’ diameter (standard 28’)

Operation• Upon Entry Occupancy sensor switches lights and

receptacles ON• Daylight Sensor maintains light level based on light level

pre-set• Entry Station and Teacher Station provide manual control

of lights• Upon Exit and after Occupancy sensor times out, lights

and receptacles switched OFF• Lights can be switched OFF manually at Entry Station and

Teacher Station

Secondary Daylight ZonePrimary Daylight Zone

9

Page 11: ROOM CONTROLLER 24 - Douglas Lighting Controls

CLASSROOMPROJECT NAME: ___________________________________________________________________ DATE: __________________

Neutral not shown - these illustrations are for reference purposes only. For site installations, please review Kit wiring diagrams and follow local and national electrical codes.

Connection Schematic

Section 2 www.DouglasLightingControls.com

PURPLE

RED

YELLOW

BLUE

BLUE

WHITE

BLACK

PURPLE

RED

YELLOW

BLUE

BLUE

BLACK

WHITE

LIGHTING LOAD 1

LIGHTING LOAD 2

LIGHTING LOAD 3

SWITCHED RECEPTACLE(S) LOAD 4

RECEPTACLE(S) HOT

LIGHTING HOT

NEUTRAL

NEUTRAL

NEUTRALLighting120/277/347Vac

DistributionCabinet

(by Others)

Receptacle120Vac

DistributionCabinet

(by Others)

Receptacle(Relay 4)

N

N

N

N

DATALINE

DIM 1DIM 2

DIM 4DIM 3

Dim 1

0-10V Dimming(18/2 per channel)

Local Room Dataline (18/2)

Dim 2

Dim 4Dim 3

Occupancy Sensor(up to 4)

Daylight Sensor

Building Controlvia

BACnet IP or Dialog Network

RoomController(WRC-3160)

Teachers Station

Entry Station Entry Station

KIT#1

Kit Ordering Numbers:

DRC01PS-1S11-12-NDRC01PS-1X11-12-NDRC01PS-1S31-12-NDRC01PS-1X31-12-N

Primary Daylight Zone Secondary Daylight Zone

Classroom Front(Relay 1)

Classroom Rear(Relay 2)

Classroom Front(Relay 1)

Classroom Rear(Relay 2)

Whiteboard Light(Relay 3)

Options• Additional Occupancy Sensors (4 max.)• Vacancy Control (Manual ON / Auto OFF)• Extended Lens range: 54’ diameter (standard 28”)

Classroom• Windows Perpendicular to Teaching Wall• Occupancy Control (Auto ON /Auto OFF)• Daylight Control (2 zones)• Light Control (3 zones)• Receptacle Control• Dimming Control (4 zones)• Entry Station (General ON/ALL OFF)• Teacher Station (Teaching, General ON, A/V, Quiet Mode)

Operation• Upon Entry Occupancy sensor switches lights and

receptacles ON• Daylight Sensor maintains light level based on light

level pre-set• Entry Station and Teacher Station provide manual

control of lights• Upon Exit and after Occupancy sensor times out,

lights and receptacles switched OFF.• Lights can be switched OFF manually at Entry

Station and Teacher Station

Dialog Room Controller

10

Page 12: ROOM CONTROLLER 24 - Douglas Lighting Controls

KIT #2

DimmingZone 1

Dimming Zone 3

Relay 3 White Board / Presentation Wall Lights

Window

D/S O/S

Relay 1

Dimmer 1

Relay 1

Dimmer 2

Relay 1

Dimmer 2

Relay 5Dimmer 1

EMERGENCY

Relay 2

Dimmer 4

Relay 2

Dimmer 4

Relay 2

Dimmer 4

Relay 6Dimmer 4

EMERGENCY

Relay 2

Dimmer 3

Relay 2

Dimmer 3

EntryStation

EntryStation

TeacherStation

Relay 4Receptacle

Relay 1

Dimmer 2

Relay 1

Dimmer 2

DimmingZone 2

DimmingZone 4

Classroom with Emergency Lighting• Windows Perpendicular to Teaching Wall• Occupancy Control (Auto ON /Auto OFF)• Daylight Control (2 zones)• Light Control (3 zones)• Receptacle Control• Dimming Control (4 zones)• Entry Station (General ON/ALL OFF)• Teacher Station (Teaching, General ON, A/V, Quiet Mode)

Emergency Lighting Control (2 zones Orange & Grey)(Requires UL924 Relay Expansion Pack)

Options• Additional Occupancy Sensors (4 max.)• Vacancy Control (Manual ON / Auto OFF)• Extended Lens range: 54’ diameter (standard 28’)

Operation• Upon Entry Occupancy sensor switches lights and

receptacles ON• Daylight Sensor maintains light level based on light level

pre-set• Entry Station and Teacher Station provide manual control

of lights• Upon Exit and after Occupancy sensor times out, lights

and receptacles switched OFF• Lights can be switched OFF manually at Entry Station and

Teacher Station• During power failure UL924 listed relays are automatically

switched ON by back-up power source switching designated emergency lights ON and to full-bright. Emergency lights remain ON with all controls disabled until primary power is restored.

Dialog RoomController

Secondary Daylight ZonePrimary Daylight Zone

11

Page 13: ROOM CONTROLLER 24 - Douglas Lighting Controls

Neutral not shown - these illustrations are for reference purposes only. For site installations, please review Kit wiring diagrams and follow local and national electrical codes.

PROJECT NAME: ___________________________________________________________________ DATE: __________________

CLASSROOM + EMERGENCY

Connection Schematic

Section 2 www.DouglasLightingControls.com

PURPLE

RED

YELLOW

BLUE

BLUE

WHITE

BLACK

ORANGE

ORANGE

GREY

GREY

PURPLE

RED

YELLOW

BLUE

BLUE

BLACK

WHITE

ORANGE

ORANGE

GREY

GREY

LIGHTING LOAD 1

LIGHTING LOAD 2

LIGHTING LOAD 3

SWITCHED RECEPTACLE(S) LOAD 4

RECEPTACLE(S) HOT

LIGHTING HOT

NEUTRAL

(EM) LIGHTING LOAD 5

(EM) LIGHTING HOT

(EM) LIGHTING LOAD 6

(EM) LIGHTING HOT

NEUTRAL

NEUTRAL

Emergency120/277/347Vac

DistributionCabinet

(by Others)

NEUTRAL

Lighting120/277/347Vac

DistributionCabinet

(by Others)

Receptacle120Vac

DistributionCabinet

(by Others)

Receptacle(Relay 4)

Classroom Front(Relay 1)

N

N

Classroom Rear(Relay 2)N

N

Front EM Light(Relay 5)N

N

DATALINE

DIM 1DIM 2

DIM 4DIM 3

Classroom Front(Relay 1)

0-10V Dimming(18/2 per channel)

Local Room Dataline (18/2)

Dim 1

Dim 4

Occupancy Sensor(up to 4)

Daylight Sensor

Teachers Station

Building Controlvia

BACnet IP or Dialog Network

RoomController(WRC-3160)

EM Expansion(WUL-3924)

Entry Station

KIT#2

Kit Ordering Numbers:

DRC01PS-1S11-12-EDRC01PS-1X11-12-EDRC01PS-1S31-12-EDRC01PS-1X31-12-E

Entry Station

Classroom Rear(Relay 2)

Dim 1 Dim 2

Dim 4Dim 3

Primary Daylight Zone Secondary Daylight Zone

Rear EM Light(Relay 6)

Whiteboard Light(Relay 3)

Options• Additional Occupancy Sensors (4 max.)• Vacancy Control (Manual ON / Auto OFF)• Extended Lens range: 54’ diameter (standard 28”)

Classroom with Emergency Lighting• Windows Perpendicular to Teaching Wall• Occupancy Control (Auto ON /Auto OFF)• Daylight Control (2 zones)• Light Control (3 zones)• Receptacle Control• Dimming Control (4 zones)• Entry Station (General ON/ALL OFF)• Teacher Station (Teaching, General ON, A/V, Quiet Mode)

• Emergency Lighting Control (2 zones Orange & Grey)(Requires UL924 Relay Expansion Pack)

Operation• Upon Entry Occupancy sensor switches lights and

receptacles ON• Daylight Sensor maintains light level based on light

level pre-set• Entry Station and Teacher Station provide manual

control of lights• Upon Exit and after Occupancy sensor times out,

lights and receptacles switched OFF.• Lights can be switched OFF manually at Entry

Station and Teacher Station• During power failure UL924 listed relays are

automatically switched ON by back-up powersource switching designated emergency lights ONand to full-bright. Emergency lights remain ON withall controls disabled until primary power is restored.

Dialog Room Controller

12

Page 14: ROOM CONTROLLER 24 - Douglas Lighting Controls

KIT #3Primary Daylight Zone

Secondary Daylight Zone

Dimming Zone 1

Dimming Zone 2

Window

D/S

O/S

Relay 2

Dimmer 1

Relay 2

Dimmer 1

Relay 2

Dimmer 1

Relay 2

Dimmer 1

Relay 1

Dimmer 2

Relay 1

Dimmer 2

Relay 1

Dimmer 2

Relay 1

Dimmer 2

Relay 1

Dimmer 2

Relay 1

Dimmer 2

Relay 4Receptacle

Relay 2

Dimmer 1

Relay 2

Dimmer 1

Classroom• Windows Opposite to Teaching Wall• Occupancy Control (Auto ON /Auto OFF)• Daylight Control (2 zones)• Light Control (3 zones)• Receptacle Control• Dimming Control (3 zones)• Entry Station (General ON/ALL OFF)• Teacher Station (Teaching, General ON, A/V, Quiet Mode)

Options• Additional Occupancy Sensors (4 max.)• Vacancy Control (Manual ON / Auto OFF)• Extended Lens range: 54’ diameter (standard 28’)

Operation• Upon Entry Occupancy sensor switches lights and

receptacles ON• Daylight Sensor maintains light level based on light level

pre-set• Entry Station and Teacher Station provide manual control

of lights• Upon Exit and after Occupancy sensor times out, lights

and receptacles switched OFF• Lights can be switched OFF manually at Entry Station and

Teacher Station

Dimming Zone 3

Relay 3 White Board / Presentation Wall LightsEntry

StationEntry

StationTeacherStation

Dialog RoomController

13

Page 15: ROOM CONTROLLER 24 - Douglas Lighting Controls

Neutral not shown - these illustrations are for reference purposes only. For site installations, please review Kit wiring diagrams and follow local and national electrical codes.

PROJECT NAME: ___________________________________________________________________ DATE: __________________

CLASSROOM

Connection Schematic

Section 2 www.DouglasLightingControls.com

PURPLE

RED

YELLOW

BLUE

BLUE

WHITE

BLACK

PURPLE

RED

YELLOW

BLUE

BLUE

BLACK

WHITE

LIGHTING LOAD 1

LIGHTING LOAD 2

LIGHTING LOAD 3

SWITCHED RECEPTACLE(S) LOAD 4

RECEPTACLE(S) HOT

LIGHTING HOT

NEUTRAL

NEUTRAL

NEUTRALLighting120/277/347Vac

DistributionCabinet

(by Others)

Receptacle120Vac

DistributionCabinet

(by Others)

Receptacle(Relay 4)

N

N

N

Whiteboard LightRelay 3N

DATALINE

DIM 1DIM 2

DIM 4DIM 3

Dim 2

0-10V Dimming(18/2 per channel)

Local Room Dataline (18/2)

Dim 2

Dim 1Dim 1

Occupancy Sensor(up to 4)

Daylight Sensor

RoomController(WRC-3160)

Building Controlvia

BACnet IP or Dialog Network

Teachers Station

Entry Station Entry Station

KIT#3

Kit Ordering Numbers:

DRC01OS-1S11-12-NDRC01OS-1X11-12-NDRC01OS-1S31-12-NDRC01OS-1X31-12-N

Primary Daylight Zone Secondary Daylight Zone

Classroom Front(Relay 1)

Classroom RearRelay 2

Classroom Front(Relay 1)

Classroom RearRelay 2

Options• Additional Occupancy Sensors (4 max.)• Vacancy Control (Manual ON / Auto OFF)• Extended Lens range: 54’ diameter (standard 28”)

Classroom• Windows Opposite to Teaching Wall• Occupancy Control (Auto ON /Auto OFF)• Daylight Control (2 zones)• Light Control (3 zones)• Receptacle Control• Dimming Control (3 zones)• Entry Station (General ON/ALL OFF)• Teacher Station (Teaching, General ON, A/V, Quiet Mode)

Operation• Upon Entry Occupancy sensor switches lights and

receptacles ON• Daylight Sensor maintains light level based on light

level pre-set• Entry Station and Teacher Station provide manual

control of lights• Upon Exit and after Occupancy sensor times out,

lights and receptacles switched OFF.• Lights can be switched OFF manually at Entry

Station and Teacher Station.

Dialog Room Controller

14

Page 16: ROOM CONTROLLER 24 - Douglas Lighting Controls

KIT #4Classroom with Emergency Lighting• Windows Opposite to Teaching Wall• Occupancy Control (Auto ON /Auto OFF)• Daylight Control (2 zones)• Light Control zones (3 zones)• Receptacle Control• Dimming Control (3 zones)• Entry Station (General ON/ALL OFF)• Teacher Station (Teaching, General ON, A/V, Quiet Mode)

Emergency Lighting Control (2 zones Orange & Grey)(Requires UL924 Relay Expansion Pack)

Options• Additional Occupancy Sensors (4 max.)• Vacancy Control (Manual ON / Auto OFF)• Extended Lens range: 54’ diameter (standard 28’)

Operation• Upon Entry Occupancy sensor switches lights and

receptacles ON• Daylight Sensor maintains light level based on light level

pre-set• Entry Station and Teacher Station provide manual control

of lights• Upon Exit and after Occupancy sensor times out, lights

and receptacles switched OFF• Lights can be switched OFF manually at Entry Station and

Teacher Station• During power failure UL924 listed relays are automatically

switched ON by back-up power source switching designated emergency lights ON and to full-bright. Emergency lights remain ON with all controls disabled until primary power is restored.

Primary Daylight Zone

Secondary Daylight Zone

Dimming Zone 1

Dimming Zone 2

Window

D/S

O/S

Relay 2

Dimmer 1

Relay 2

Dimmer 1

Relay 2

Dimmer 1

Relay 6Dimmer 1

EMERGENCY

Relay 1

Dimmer 2

Relay 1

Dimmer 2

Relay 1

Dimmer 2

Relay 5Dimmer 2

EMERGENCY

Relay 1

Dimmer 2

Relay 1

Dimmer 2

Relay 4Receptacle

Relay 2

Dimmer 1

Relay 2

Dimmer 1

Dimming Zone 3

Relay 3 White Board / Presentation Wall LightsEntry

StationEntry

StationTeacherStation

Dialog RoomController

15

Page 17: ROOM CONTROLLER 24 - Douglas Lighting Controls

Neutral not shown - these illustrations are for reference purposes only. For site installations, please review Kit wiring diagrams and follow local and national electrical codes.

PROJECT NAME: ___________________________________________________________________ DATE: __________________

CLASSROOM + EMERGENCY

Connection Schematic

Section 2 www.DouglasLightingControls.com

PURPLE

RED

YELLOW

BLUE

BLUE

WHITE

BLACK

ORANGE

ORANGE

GREY

GREY

PURPLE

RED

YELLOW

BLUE

BLUE

BLACK

WHITE

ORANGE

ORANGE

GREY

GREY

LIGHTING LOAD 1

LIGHTING LOAD 2

LIGHTING LOAD 3

SWITCHED RECEPTACLE(S) LOAD 4

RECEPTACLE(S) HOT

LIGHTING HOT

NEUTRAL

(EM) LIGHTING LOAD 5

(EM) LIGHTING HOT

(EM) LIGHTING LOAD 6

(EM) LIGHTING HOT

NEUTRAL

NEUTRAL

Emergency120/277/347Vac

DistributionCabinet

(by Others)

NEUTRAL

Lighting120/277/347Vac

DistributionCabinet

(by Others)

Receptacle120Vac

DistributionCabinet

(by Others)

Receptacle(Relay 4)

N

N

N

N

N

N

DATALINE

DIM 1DIM 2

DIM 4DIM 3

Dim 2

0-10V Dimming(18/2 per channel)

Local Room Dataline (18/2)

Dim 2

Dim 1Dim 1

Dim 2

Dim 1

Occupancy Sensor(up to 4)

Daylight Sensor

Building Controlvia

BACnet IP or Dialog Network

RoomController(WRC-3160)

EM Expansion(WUL-3924)

Teachers Station

Entry Station Entry Station

KIT#4

Kit Ordering Numbers:

DRC01OS-1S11-12-EDRC01OS-1X11-12-EDRC01OS-1S31-12-EDRC01OS-1X31-12-E

Primary Daylight Zone Secondary Daylight Zone

Classroom Front(Relay 1)

Classroom Rear(Relay 2)

Classroom Front(Relay 1)

Classroom Rear(Relay 2)

Front EM Light(Relay 5)

Rear EM Light(Relay 6)

Whiteboard Light(Relay 3)

Options• Additional Occupancy Sensors (4 max.)• Vacancy Control (Manual ON / Auto OFF)• Extended Lens range: 54’ diameter (standard 28”)

Classroom with Emergency Lighting• Windows Opposite to Teaching Wall• Occupancy Control (Auto ON /Auto OFF)• Daylight Control (2 zones)• Light Control zones (3 zones)• Receptacle Control• Dimming Control (3 zones)• Entry Station (General ON/ALL OFF)• Teacher Station (Teaching, General ON, A/V, Quiet Mode)

• Emergency Lighting Control (2 zones Orange & Grey)(Requires UL924 Relay Expansion Pack)

Operation• Upon Entry Occupancy sensor switches lights and

receptacles ON• Daylight Sensor maintains light level based on light

level pre-set• Entry Station and Teacher Station provide manual

control of lights• Upon Exit and after Occupancy sensor times out,

lights and receptacles switched OFF.• Lights can be switched OFF manually at Entry

Station and Teacher Station• During power failure UL924 listed relays are

automatically switched ON by back-up powersource switching designated emergency lights ONand to full-bright. Emergency lights remain ON withall controls disabled until primary power is restored.

Dialog Room Controller

16

Page 18: ROOM CONTROLLER 24 - Douglas Lighting Controls

KIT #5

Secondary Daylight ZonePrimary Daylight Zone

DimmingZone 1

Dimming Zone 3

Relay 3 White Board / Presentation Wall Lights

Window

O/S

Relay 1

Dimmer 1

Relay 1

Dimmer 2

Relay 1

Dimmer 2

Relay 1

Dimmer 1

Relay 2

Dimmer 4

Relay 2

Dimmer 4

Relay 2

Dimmer 4

Relay 2

Dimmer 4

Relay 2

Dimmer 3

Relay 2

Dimmer 3

EntryStation

EntryStation

TeacherStation

Relay 4Receptacle

Relay 1

Dimmer 2

Relay 1

Dimmer 2

DimmingZone 2

DimmingZone 4

Classroom• Windows Perpendicular to Teaching Wall• Skylight• Occupancy Control (Auto ON /Auto OFF)• Daylight Control (2 zones)• Light Control (3 zones)• Receptacle Control• Dimming Control (4 zones)• Entry Station (General ON/ALL OFF)• Teacher Station (Teaching, General ON, A/V, Quiet Mode)

 

Options• Additional Occupancy Sensors (4 max.)• Vacancy Control (Manual ON / Auto OFF)• Extended Lens range: 54’ diameter (standard 28’)

Operation• Upon Entry Occupancy sensor switches lights and

receptacles ON• Daylight Sensor maintains light level based on light level

pre-set• Entry Station and Teacher Station provide manual control

of lights• Upon Exit and after Occupancy sensor times out, lights

and receptacles switched OFF• Lights can be switched OFF manually at Entry Station and

Teacher Station

D/SD/S Skylight

Dialog RoomController

17

Page 19: ROOM CONTROLLER 24 - Douglas Lighting Controls

Neutral not shown - these illustrations are for reference purposes only. For site installations, please review Kit wiring diagrams and follow local and national electrical codes.

PROJECT NAME: ___________________________________________________________________ DATE: __________________

CLASSROOM

Connection Schematic

Section 2 www.DouglasLightingControls.com

PURPLE

RED

YELLOW

BLUE

BLUE

WHITE

BLACK

PURPLE

RED

YELLOW

BLUE

BLUE

BLACK

WHITE

LIGHTING LOAD 1

LIGHTING LOAD 2

LIGHTING LOAD 3

SWITCHED RECEPTACLE(S) LOAD 4

RECEPTACLE(S) HOT

LIGHTING HOT

NEUTRAL

NEUTRAL

NEUTRALLighting120/277/347Vac

DistributionCabinet

(by Others)

Receptacle120Vac

DistributionCabinet

(by Others)

Receptacle(Relay 4)

N

N

N

N

DATALINE

DIM 1DIM 2

DIM 4DIM 3

Dim 1

0-10V Dimming(18/2 per channel)

Local Room Dataline (18/2)

Dim 2

Dim 4Dim 3

Daylight SensorZone 2

RoomController(WRC-3160)

Occupancy Sensor(up to 4)

Daylight SensorZone 1

Building Controlvia

BACnet IP or Dialog Network

Teachers Station

Entry Station Entry Station

KIT#5

Kit Ordering Numbers:

DRC01PM-1S12-12-NDRC01PM-1X12-12-NDRC01PM-1S32-12-NDRC01PM-1X32-12-N

Classroom Front(Relay 1)

Classroom Rear(Relay 2)

Classroom Front(Relay 1)

Classroom Rear(Relay 2)

Window Daylight Zone Skylight Daylight Zone

Whiteboard Light(Relay 3)

Options• Additional Occupancy Sensors (4 max.)• Vacancy Control (Manual ON / Auto OFF)• Extended Lens range: 54’ diameter (standard 28”)

Classroom• Windows Perpendicular to Teaching Wall• Skylight• Occupancy Control (Auto ON /Auto OFF)• Daylight Control (2 zones)• Light Control (3 zones)• Receptacle Control• Dimming Control (4 zones)• Entry Station (General ON/ALL OFF)• Teacher Station (Teaching, General ON, A/V, Quiet Mode)

Operation• Upon Entry Occupancy sensor switches lights and

receptacles ON• Daylight Sensor maintains light level based on light

level pre-set• Entry Station and Teacher Station provide manual

control of lights• Upon Exit and after Occupancy sensor times out,

lights and receptacles switched OFF.• Lights can be switched OFF manually at Entry

Station and Teacher Station

Dialog Room Controller

18

Page 20: ROOM CONTROLLER 24 - Douglas Lighting Controls

KIT #6

DimmingZone 1

Dimming Zone 3

Relay 3 White Board / Presentation Wall Lights

Window

O/S

Relay 1

Dimmer 1

Relay 1

Dimmer 2

Relay 1

Dimmer 2

Relay 5Dimmer 1

EMERGENCY

Relay 2

Dimmer 4

Relay 2

Dimmer 4

Relay 2

Dimmer 4

Relay 6Dimmer 4

EMERGENCY

Relay 2

Dimmer 3

Relay 2

Dimmer 3

EntryStation

EntryStation

TeacherStation

Relay 4Receptacle

Relay 1

Dimmer 2

Relay 1

Dimmer 2

DimmingZone 2

DimmingZone 4

Classroom with Emergency Power• Windows Perpendicular to Teaching Wall• Skylight• Occupancy Control (Auto ON /Auto OFF)• Daylight Control (2 zones)• Light Control (3 zones)• Receptacle Control• Dimming Control (4 zones)• Entry Station (General ON/ALL OFF)• Teacher Station (Teaching, General ON, A/V, Quiet Mode)

Emergency Lighting Control (2 zones Orange & Grey)(Requires UL924 Relay Expansion Pack)

Options• Additional Occupancy Sensors (4 max.)• Vacancy Control (Manual ON / Auto OFF)• Extended Lens range: 54’ diameter (standard 28’)

Operation• Upon Entry Occupancy sensor switches lights and

receptacles ON• Daylight Sensor maintains light level based on light level

pre-set• Entry Station and Teacher Station provide manual control

of lights• Upon Exit and after Occupancy sensor times out, lights

and receptacles switched OFF• Lights can be switched OFF manually at Entry Station and

Teacher Station• During power failure UL924 listed relays are automatically

switched ON by back-up power source switching designated emergency lights ON and to full-bright. Emergency lights remain ON with all controls disabled until primary power is restored.

D/SD/S

Secondary Daylight ZonePrimary Daylight Zone

Skylight

Dialog RoomController

19

Page 21: ROOM CONTROLLER 24 - Douglas Lighting Controls

Neutral not shown - these illustrations are for reference purposes only. For site installations, please review Kit wiring diagrams and follow local and national electrical codes.

PROJECT NAME: ___________________________________________________________________ DATE: __________________

CLASSROOM + EMERGENCY

Connection Schematic

Section 2 www.DouglasLightingControls.com

PURPLE

RED

YELLOW

BLUE

BLUE

WHITE

BLACK

ORANGE

ORANGE

GREY

GREY

PURPLE

RED

YELLOW

BLUE

BLUE

BLACK

WHITE

ORANGE

ORANGE

GREY

GREY

LIGHTING LOAD 1

LIGHTING LOAD 2

LIGHTING LOAD 3

SWITCHED RECEPTACLE(S) LOAD 4

RECEPTACLE(S) HOT

LIGHTING HOT

NEUTRAL

(EM) LIGHTING LOAD 5

(EM) LIGHTING HOT

(EM) LIGHTING LOAD 6

(EM) LIGHTING HOT

NEUTRAL

NEUTRAL

Emergency120/277/347Vac

DistributionCabinet

(by Others)

NEUTRAL

Lighting120/277/347Vac

DistributionCabinet

(by Others)

Receptacle120Vac

DistributionCabinet

(by Others)

Receptacle(Relay 4)

N

N

N

N

N

N

DATALINE

DIM 1DIM 2

DIM 4DIM 3

Dim 1

0-10V Dimming(18/2 per channel)

Local Room Dataline (18/2)

Dim 2

Dim 4Dim 3

Dim 1

Dim 4

Daylight SensorZone 2

Building Controlvia

BACnet IP or Dialog Network

RoomController(WRC-3160)

EM Expansion(WUL-3924)

Occupancy Sensor(up to 4)

Daylight SensorZone 1

Teachers Station

Entry Station Entry Station

KIT#6

Kit Ordering Numbers:

DRC01PM-1S12-12-EDRC01PM-1X12-12-EDRC01PM-1S32-12-EDRC01PM-1X32-12-E

Classroom Front(Relay 1)

Classroom Rear(Relay 2)

Front EM Light(Relay 5)

Classroom Front(Relay 1)

Classroom Rear(Relay 2)

Window Daylight Zone Skylight Daylight Zone

Rear EM Light(Relay 6)

Whiteboard Light(Relay 3)

Options• Additional Occupancy Sensors (4 max.)• Vacancy Control (Manual ON / Auto OFF)• Extended Lens range: 54’ diameter (standard 28”)

Classroom with Emergency Power• Windows Perpendicular to Teaching Wall• Skylight• Occupancy Control (Auto ON /Auto OFF)• Daylight Control (2 zones)• Light Control (3 zones)• Receptacle Control• Dimming Control (4 zones)• Entry Station (General ON/ALL OFF)• Teacher Station (Teaching, General ON, A/V, Quiet Mode)

• Emergency Lighting Control (2 zones Orange & Grey)(Requires UL924 Relay Expansion Pack)

Operation• Upon Entry Occupancy sensor switches lights and

receptacles ON• Daylight Sensor maintains light level based on light

level pre-set• Entry Station and Teacher Station provide manual

control of lights• Upon Exit and after Occupancy sensor times out,

lights and receptacles switched OFF.• Lights can be switched OFF manually at Entry

Station and Teacher Station• During power failure UL924 listed relays are

automatically switched ON by back-up powersource switching designated emergency lights ONand to full-bright. Emergency lights remain ON withall controls disabled until primary power is restored.

Dialog Room Controller

20

Page 22: ROOM CONTROLLER 24 - Douglas Lighting Controls

KIT #7Classroom• Windows Opposite to Teaching Wall• Skylight• Occupancy Control (Auto ON /Auto OFF)• Daylight Control (2 zones)• Light Control (3 zones)• Receptacle Control• Dimming Control (4 zones)• Entry Station (General ON/ALL OFF)• Teacher Station (Teaching, General ON, A/V, Quiet Mode) 

Options• Additional Occupancy Sensors (4 max.)• Vacancy Control (Manual ON / Auto OFF)• Extended Lens range: 54’ diameter (standard 28’)

Operation• Upon Entry Occupancy sensor switches lights and

receptacles ON• Daylight Sensor maintains light level based on light level

pre-set• Entry Station and Teacher Station provide manual control

of lights• Upon Exit and after Occupancy sensor times out, lights

and receptacles switched OFF• Lights can be switched OFF manually at Entry Station and

Teacher Station

Primary Daylight Zone

Secondary Daylight Zone

Dimming Zone 1

Dimming Zone 2

Dimming Zone 3

Relay 3 White Board / Presentation Wall Lights

Window

D/SA

D/SB

O/S

Relay 2

Dimmer 1

Relay 2

Dimmer 1

Relay 2

Dimmer 1

Relay 2

Dimmer 1

Relay 1

Dimmer 2

Relay 1

Dimmer 2

Relay 1

Dimmer 2

Relay 1

Dimmer 2

Relay 1

Dimmer 2

Relay 1

Dimmer 2

EntryStation

EntryStation

TeacherStation

Relay 4Receptacle

Relay 2

Dimmer 1

Relay 2

Dimmer 1

Skylight

Dialog RoomController

21

Page 23: ROOM CONTROLLER 24 - Douglas Lighting Controls

Neutral not shown - these illustrations are for reference purposes only. For site installations, please review Kit wiring diagrams and follow local and national electrical codes.

PROJECT NAME: ___________________________________________________________________ DATE: __________________

CLASSROOM

Connection Schematic

Section 2 www.DouglasLightingControls.com

PURPLE

RED

YELLOW

BLUE

BLUE

WHITE

BLACK

PURPLE

RED

YELLOW

BLUE

BLUE

BLACK

WHITE

LIGHTING LOAD 1

LIGHTING LOAD 2

LIGHTING LOAD 3

SWITCHED RECEPTACLE(S) LOAD 4

RECEPTACLE(S) HOT

LIGHTING HOT

NEUTRAL

NEUTRAL

NEUTRALLighting120/277/347Vac

DistributionCabinet

(by Others)

Receptacle120Vac

DistributionCabinet

(by Others)

Receptacle(Relay 4)

N

N

N

N

DATALINE

DIM 1DIM 2

DIM 4DIM 3

Dim 1

0-10V Dimming(18/2 per channel)

Local Room Dataline (18/2)

Dim 1

Dim 2Dim 2

RoomController(WRC-3160) Daylight Sensor

Zone 2

Occupancy Sensor(up to 4)

Daylight SensorZone 1

Building Controlvia

BACnet IP or Dialog Network

Teachers Station

Entry Station Entry Station

KIT#7

Kit Ordering Numbers:

DRC01OM-1S12-12-NDRC01OM-1X12-12-NDRC01OM-1S32-12-NDRC01OM-1X32-12-N

Classroom Front(Relay 1)

Classroom Rear(Relay 2)

Classroom Front(Relay 1)

Classroom Rear(Relay 2)

Whiteboard Light(Relay 3)

Window Daylight Zone Skylight Daylight Zone

Options• Additional Occupancy Sensors (4 max.)• Vacancy Control (Manual ON / Auto OFF)• Extended Lens range: 54’ diameter (standard 28”)

Classroom• Windows Opposite to Teaching Wall• Skylight• Occupancy Control (Auto ON /Auto OFF)• Daylight Control (2 zones)• Light Control (3 zones)• Receptacle Control• Dimming Control (4 zones)• Entry Station (General ON/ALL OFF)• Teacher Station (Teaching, General ON, A/V, Quiet Mode)

Operation• Upon Entry Occupancy sensor switches lights and

receptacles ON• Daylight Sensor maintains light level based on light

level pre-set• Entry Station and Teacher Station provide manual

control of lights• Upon Exit and after Occupancy sensor times out,

lights and receptacles switched OFF.• Lights can be switched OFF manually at Entry

Station and Teacher Station

Dialog Room Controller

22

Page 24: ROOM CONTROLLER 24 - Douglas Lighting Controls

KIT #8Classroom with Emergency Lighting• Windows Opposite to Teaching Wall• Skylight• Occupancy Control (Auto ON /Auto OFF)• Daylight Control (2 zones)• Light Control (3 zones)• Receptacle Control• Dimming Control (4 zones)• Entry Station (General ON/ALL OFF)• Teacher Station (Teaching, General ON, A/V, Quiet Mode)

Emergency Lighting Control (2 zones Orange & Grey)(Requires UL924 Relay Expansion Pack)

 

Options• Additional Occupancy Sensors (4 max.)• Vacancy Control (Manual ON / Auto OFF)• Extended Lens range: 54’ diameter (standard 28’)

Operation• Upon Entry Occupancy sensor switches lights and

receptacles ON• Daylight Sensor maintains light level based on light level

pre-set• Entry Station and Teacher Station provide manual control

of lights• Upon Exit and after Occupancy sensor times out, lights

and receptacles switched OFF• Lights can be switched OFF manually at Entry Station and

Teacher Station• During power failure UL924 listed relays are automatically

switched ON by back-up power source switching designated emergency lights ON and to full-bright. Emergency lights remain ON with all controls disabled until primary power is restored.

Primary Daylight Zone

Secondary Daylight Zone

Dimming Zone 1

Dimming Zone 2

Dimming Zone 3

Relay 3 White Board / Presentation Wall Lights

Window

D/SA

D/SB

O/S

Relay 2

Dimmer 1

Relay 2

Dimmer 1

Relay 2

Dimmer 1

Relay 6Dimmer 1

EMERGENCY

Relay 1

Dimmer 2

Relay 1

Dimmer 2

Relay 1

Dimmer 2

Relay 5Dimmer 2

EMERGENCY

Relay 1

Dimmer 2

Relay 1

Dimmer 2

EntryStation

EntryStation

TeacherStation

Relay 4Receptacle

Relay 2

Dimmer 1

Relay 2

Dimmer 1

Skylight

Dialog RoomController

23

Page 25: ROOM CONTROLLER 24 - Douglas Lighting Controls

Neutral not shown - these illustrations are for reference purposes only. For site installations, please review Kit wiring diagrams and follow local and national electrical codes.

PROJECT NAME: ___________________________________________________________________ DATE: __________________

CLASSROOM + EMERGENCY

Connection Schematic

Section 2 www.DouglasLightingControls.com

PURPLE

RED

YELLOW

BLUE

BLUE

WHITE

BLACK

ORANGE

ORANGE

GREY

GREY

PURPLE

RED

YELLOW

BLUE

BLUE

BLACK

WHITE

ORANGE

ORANGE

GREY

GREY

LIGHTING LOAD 1

LIGHTING LOAD 2

LIGHTING LOAD 3

SWITCHED RECEPTACLE(S) LOAD 4

RECEPTACLE(S) HOT

LIGHTING HOT

NEUTRAL

(EM) LIGHTING LOAD 5

(EM) LIGHTING HOT

(EM) LIGHTING LOAD 6

(EM) LIGHTING HOT

NEUTRAL

NEUTRAL

Emergency120/277/347Vac

DistributionCabinet

(by Others)

NEUTRAL

Lighting120/277/347Vac

DistributionCabinet

(by Others)

Receptacle120Vac

DistributionCabinet

(by Others)

Receptacle(Relay 4)

N

N

N

N

N

N

DATALINE

DIM 1DIM 2

DIM 4DIM 3

Dim 2

0-10V Dimming(18/2 per channel)

Local Room Dataline (18/2)

Dim 2

Dim 1Dim 1

Dim 2

Dim 1

Building Controlvia

BACnet IP or Dialog Network

RoomController(WRC-3160)

EM Expansion(WUL-3924)

Daylight SensorZone 2

Occupancy Sensor(up to 4)

Daylight SensorZone 1

Teachers Station

Entry Station Entry Station

KIT#8

Kit Ordering Numbers:

DRC01OM-1S12-12-EDRC01OM-1X12-12-EDRC01OM-1S32-12-EDRC01OM-1X32-12-E

Classroom Front(Relay 1)

Classroom Rear(Relay 2)

Classroom Front(Relay 1)

Classroom Rear(Relay 2)

Front EM Light(Relay 5)

Rear EM Light(Relay 6)

Whiteboard Light(Relay 3)

Window Daylight Zone Skylight Daylight Zone

Options• Additional Occupancy Sensors (4 max.)• Vacancy Control (Manual ON / Auto OFF)• Extended Lens range: 54’ diameter (standard 28”)

Classroom with Emergency Lighting• Windows Opposite to Teaching Wall• Skylight• Occupancy Control (Auto ON /Auto OFF)• Daylight Control (2 zones)• Light Control (3 zones)• Receptacle Control• Dimming Control (4 zones)• Entry Station (General ON/ALL OFF)• Teacher Station (Teaching, General ON, A/V, Quiet Mode)

• Emergency Lighting Control (2 zones Orange & Grey)(Requires UL924 Relay Expansion Pack)

Operation• Upon Entry Occupancy sensor switches lights and

receptacles ON• Daylight Sensor maintains light level based on light

level pre-set• Entry Station and Teacher Station provide manual

control of lights• Upon Exit and after Occupancy sensor times out,

lights and receptacles switched OFF.• Lights can be switched OFF manually at Entry

Station and Teacher Station• During power failure UL924 listed relays are

automatically switched ON by back-up powersource switching designated emergency lights ONand to full-bright. Emergency lights remain ON withall controls disabled until primary power is restored.

Dialog Room Controller

24

Page 26: ROOM CONTROLLER 24 - Douglas Lighting Controls

KIT #9Double Classroom• Windows Perpendicular to Teaching Wall• Occupancy Control (Auto ON /Auto OFF)• Daylight Control (2 zones per room)• Light Control (2 zones per room)• Dimming Control (2 zones per room)• Entry Station (General ON/ALL OFF)• Teacher Station (Teaching, General ON, A/V, Quiet Mode)

Options• Additional Occupancy Sensors (4 max.)• Vacancy Control (Manual ON / Auto OFF)• Extended Lens range: 54’ diameter (standard 28’)

Operation• Upon Entry Occupancy sensor switches lights and

receptacles ON• Daylight Sensor maintains light level based on light level

pre-set• Entry Station (ON/OFF) and Teacher Station (GENERAL,

TEACHING, A/V, ALL, DIMMING) provide manual control of lights

• Upon Exit and after Occupancy sensor times out, lights and receptacles switched OFF

• Lights can be switched OFF manually at Entry Station and Teacher Station

Primary Daylight Zone A Primary Daylight Zone B

Secondary Daylight Zone A Secondary Daylight Zone B

Dimming Zone 1 Dimming Zone 2

Dimming Zone 3 Dimming Zone 4

Window Window

D/SA

D/SB

O/SA

O/SB

Relay 1 Dimmer 1 Relay 2 Dimmer 2

Relay 1 Dimmer 3 Relay 2 Dimmer 4

EntryStation A

EntryStation B

TeacherStation A

TeacherStation B

Relay 3 W

hite Bo

ard / P

resentation W

all Lights

Dialog Room

Controller

Rel

ay 4

Whi

te B

oar

d /

Pre

sent

atio

n W

all L

ight

s25

Page 27: ROOM CONTROLLER 24 - Douglas Lighting Controls

Neutral not shown - these illustrations are for reference purposes only. For site installations, please review Kit wiring diagrams and follow local and national electrical codes.

PROJECT NAME: ___________________________________________________________________ DATE: __________________

DOUBLE CLASSROOM

Connection Schematic

Section 2 www.DouglasLightingControls.com

PURPLE

RED

YELLOW

BLUE

BLUE

WHITE

BLACK

PURPLE

RED

YELLOW

BLUE

BLUE

BLACK

WHITE

LIGHTING LOAD 1

LIGHTING LOAD 2

LIGHTING LOAD 3

LIGHTING LOAD 4

LIGHTING HOT LOAD 4

LIGHTING HOT

NEUTRAL

NEUTRALLighting120/277/347Vac

DistributionCabinet

(by Others)

N

N

N

DATALINE

DIM 1DIM 2

DIM 4DIM 3

Dim 1

0-10V Dimming(18/2 per channel)

Local Room Dataline (18/2)

Dim 2

Dim 4Dim 3

Daylight SensorClassroom B

RoomController(WRC-3160)

Occupancy SensorClassroom A

Daylight SensorClassroom A

N

N

N

Occupancy SensorClassroom B

Building Controlvia

BACnet IP or Dialog Network

Entry Station(s)Classroom B

Teachers StationClassroom B

Entry Station(s)Classroom A

Teachers StationClassroom A

KIT#9

Kit Ordering Numbers:

DRC02PS-2S12-22-NDRC02PS-2X12-22-NDRC02PS-2S32-22-NDRC02PS-2X32-22-N

Near Window(Relay 1)

Classroom B

Primary Daylight Zone Primary Daylight Zone

Near Window(Relay 2)

Secondary Daylight Zone Secondary Daylight Zone

Interior(Relay 1)

Interior(Relay 2)

Classroom A

Whiteboard Light(Relay 3)

Whiteboard Light((Relay 4))

Options• Additional Occupancy Sensors (4 max.)• Vacancy Control (Manual ON / Auto OFF)• Extended Lens range: 54’ diameter (standard 28”)

Double Classroom• Windows Perpendicular to Teaching Wall• Occupancy Control (Auto ON /Auto OFF)• Daylight Control (2 zones per room)• Light Control (2 zones per room)• Dimming Control (2 zones per room)• Entry Station (General ON/ALL OFF)• Teacher Station (Teaching, General ON, A/V, Quiet Mode)

Operation• Upon Entry Occupancy sensor switches lights and

receptacles ON• Daylight Sensor maintains light level based on light

level pre-set• Entry Station (ON/OFF) and Teacher Station

(GENERAL, TEACHING, A/V, ALL, DIMMING) providemanual control of lights

• Upon Exit and after Occupancy sensor times out,lights and receptacles switched OFF.

• Lights can be switched OFF manually at EntryStation and Teacher Station

Dialog Room Controller

26

Page 28: ROOM CONTROLLER 24 - Douglas Lighting Controls

KIT #10Double Classroom with Emergency Lighting(Requires UL924 Relay Expansion Pack)

• Windows Perpendicular to Teaching Wall• Occupancy Control (Auto ON /Auto OFF)• Daylight Control (2 zones per room)• Light Control (3 zones per room)• Dimming Control (2 per room)• Entry Station (General ON/ALL OFF)• Teacher Station (Teaching, General ON, A/V, Quiet Mode)

Options• Additional Occupancy Sensors (4 max.)• Vacancy Control (Manual ON / Auto OFF)• Extended Lens range: 54’ diameter (standard 28’)

Operation• Upon Entry Occupancy sensor switches lights and

receptacles ON• Daylight Sensor maintains light level based on light level

pre-set• Entry Station and Teacher Station provide manual control

of lights• Upon Exit and after Occupancy sensor times out, lights

and receptacles switched OFF• Lights can be switched OFF manually at Entry Station and

Teacher Station• During power failure UL924 listed relays are automatically

switched ON by back-up power source switching designated emergency lights ON and to full-bright. Emergency lights remain ON with all controls disabled until primary power is restored.

Primary Daylight Zone A Primary Daylight Zone B

Secondary Daylight Zone A Secondary Daylight Zone B

Dimming Zone 1 Dimming Zone 2

Dimming Zone 3 Dimming Zone 4

Relay 3 W

hite Bo

ard / P

resentation W

all Lights R

elay

4 W

hite

Bo

ard

/ P

rese

ntat

ion

Wal

l Lig

hts

Window Window

D/SA

D/SB

O/SA

O/SB

Relay 1 Dimmer 1 Relay 2 Dimmer 2

Relay 5 Dimmer 3 EMERGENCY Relay 6 Dimmer 4 EMERGENCY

EntryStation A

EntryStation B

TeacherStation A

TeacherStation B

Dialog Room

Controller

27

Page 29: ROOM CONTROLLER 24 - Douglas Lighting Controls

Neutral not shown - these illustrations are for reference purposes only. For site installations, please review Kit wiring diagrams and follow local and national electrical codes.

PROJECT NAME: ___________________________________________________________________ DATE: __________________

DOUBLE CLASSROOM + EMERGENCY

Connection Schematic

Section 2 www.DouglasLightingControls.com

PURPLE

RED

YELLOW

BLUE

BLUE

WHITE

BLACK

ORANGE

ORANGE

GREY

GREY

PURPLE

RED

YELLOW

BLUE

BLUE

BLACK

WHITE

ORANGE

ORANGE

GREY

GREY

LIGHTING LOAD 1

LIGHTING LOAD 2

LIGHTING LOAD 3

LIGHTING LOAD 4

LIGHTING HOT LOAD 4

LIGHTING HOT

NEUTRAL

(EM) LIGHTING LOAD 5

(EM) LIGHTING HOT

(EM) LIGHTING LOAD 6

(EM) LIGHTING HOT

NEUTRAL

Emergency120/277/347Vac

DistributionCabinet

(by Others)

NEUTRAL

Lighting120/277/347Vac

DistributionCabinet

(by Others)

Near Window(Relay 1)N

Interior(Relay 5)N

N

DATALINE

DIM 1DIM 2

DIM 4DIM 3

Dim 1

0-10V Dimming(18/2 per channel)

Local Room Dataline (18/2)

Dim 2

Dim 4Dim 3

Daylight SensorClassroom B

Entry Station(s)Classroom B

Building Controlvia

BACnet IP or Dialog Network

RoomController(WRC-3160)

EM Expansion(WUL-3924) Teachers Station

Classroom B

Occupancy SensorClassroom A

Daylight SensorClassroom A

N

N

N

Classroom A Classroom B

Occupancy SensorClassroom B

Entry Station(s)Classroom A

Teachers StationClassroom A

KIT#10

Kit Ordering Numbers:

DRC02PS-2S12-22-NDRC02PS-2X12-22-NDRC02PS-2S32-22-NDRC02PS-2X32-22-N

Primary Daylight Zone Primary Daylight Zone

Near Window(Relay 2)

Interior(Relay 6)

Secondary Daylight Zone Secondary Daylight Zone

Whiteboard Light(Relay 3)

Whiteboard Light((Relay 4))

Options• Additional Occupancy Sensors (4 max.)• Vacancy Control (Manual ON / Auto OFF)• Extended Lens range: 54’ diameter (standard 28”)

Double Classroom with Emergency Lighting• Windows Perpendicular to Teaching Wall• Occupancy Control (Auto ON /Auto OFF)• Daylight Control (2 zones per room)• Light Control (3 zones per room)• Dimming Control (2 per room)• Entry Station (General ON/ALL OFF)• Teacher Station (Teaching, General ON, A/V, Quiet Mode)

• Emergency Lighting Control (2 zones Orange & Grey)(Requires UL924 Relay Expansion Pack)

Operation• Upon Entry Occupancy sensor switches lights and

receptacles ON• Daylight Sensor maintains light level based on light

level pre-set• Entry Station and Teacher Station provide manual

control of lights• Upon Exit and after Occupancy sensor times out,

lights and receptacles switched OFF.• Lights can be switched OFF manually at Entry

Station and Teacher Station• During power failure UL924 listed relays are

automatically switched ON by back-up powersource switching designated emergency lights ONand to full-bright. Emergency lights remain ON withall controls disabled until primary power is restored.

Dialog Room Controller

28

DRC02PS-2S12-22-EDRC02PS-2X12-22-EDRC02PS-2S32-22-EDRC02PS-2X32-22-E

Page 30: ROOM CONTROLLER 24 - Douglas Lighting Controls

KIT #11Office• Occupancy Control (Auto ON /Auto OFF)• Daylight Control (2 zones)• Light Control (3 zones)• Receptacle Control• Dimming Control (3 zones)• Wall Station (General ON/ALL OFF)

Options• Additional Occupancy Sensors (4 max.)• Vacancy Control (Manual ON / Auto OFF)• Extended Lens range: 54’ diameter (standard 28’)

Operation• Upon Entry Occupancy sensor switches lights and

receptacles ON• Daylight Sensor maintains light level based on light level

pre-set• Office Wall Station provides manual control of lights• Upon Exit and after Occupancy sensor times out, lights

and receptacles switched OFF• Lights can be switched OFF manually at Office Wall

Station

Primary Daylight Zone

Secondary Daylight Zone

Dimming Zone 1

Dimming Zone 2

O/S

Relay 2

Dimmer 1

Relay 1

Dimmer 2

WallStation

Relay 4Receptacle

D/SDimming Zone 3

*Optional

Relay 3Dimmer 3

Relay 3Dimmer 3

Relay 3Dimmer 3

Relay 3Dimmer 3

Window

Dialog RoomController

29

Page 31: ROOM CONTROLLER 24 - Douglas Lighting Controls

Neutral not shown - these illustrations are for reference purposes only. For site installations, please review Kit wiring diagrams and follow local and national electrical codes.

PROJECT NAME: ___________________________________________________________________ DATE: __________________

OFFICE

Connection Schematic

Section 2 www.DouglasLightingControls.com

PURPLE

RED

YELLOW

BLUE

BLUE

WHITE

BLACK

NEUTRAL

NEUTRALLighting120/277/347Vac

DistributionCabinet

(by Others)

Receptacle120Vac

DistributionCabinet

(by Others)

Receptacle(Relay 4)

N

N

N

DATALINE

DIM 1DIM 2

DIM 4DIM 3

Dim 2

0-10V Dimming(18/2 per channel)

Dim 1

RoomController(WRC-3160)

Local Room Dataline (18/2)

Occupancy Sensor(up to 4)

Daylight Sensor

NDim 3

PURPLE

RED

YELLOW

BLUE

BLUE

BLACK

WHITE

LIGHTING LOAD 1

LIGHTING LOAD 2

LIGHTING LOAD 3

SWITCHED RECEPTACLE(S) LOAD 4

RECEPTACLE(S) HOT

LIGHTING HOT

NEUTRAL

Building Controlvia

BACnet IP or Dialog Network

Entry Station

KIT#11

Kit Ordering Numbers:

DRC01NS-1S11-03-NDRC01NS-1X11-03-NDRC01NS-1S31-03-NDRC01NS-1X31-03-N

Interior(Relay 1)

Secondary Daylight Zone

Display / Track(Relay 3)

Near Window(Relay 2)

Primary Daylight Zone

Options• Additional Occupancy Sensors (4 max.)• Vacancy Control (Manual ON / Auto OFF)• Extended Lens range: 54’ diameter (standard 28”)

Office• Occupancy Control (Auto ON /Auto OFF)• Daylight Control (2 zones)• Light Control (3 zones)• Receptacle Control• Dimming Control (3 zones)• Wall Station (General ON/ALL OFF)

Operation• Upon Entry Occupancy sensor switches lights and

receptacles ON• Daylight Sensor maintains light level based on light

level pre-set• Office Wall Station provides manual control of lights• Upon Exit and after Occupancy sensor times out,

lights and receptacles switched OFF.• Lights can be switched OFF manually at Office Wall

Station

Dialog Room Controller

30

Page 32: ROOM CONTROLLER 24 - Douglas Lighting Controls

KIT #12Office with Emergency Lighting• Occupancy Control (Auto ON /Auto OFF)• Daylight Control (2 zones)• Light Control (3 zones)• Receptacle Control• Dimming Control (3 zones)• Wall Station (General ON/ALL OFF) 

Emergency Lighting Control (EMRG)• UL924 Relay Expansion Pack Required• (1 zone - Orange)

Options• Additional Occupancy Sensors (4 max.)• Vacancy Control (Manual ON / Auto OFF)• Extended Lens range: 54’ diameter (standard 28’)

Operation• Upon Entry Occupancy sensor switches lights and

receptacles ON• Daylight Sensor maintains light level based on light level

pre-set• Office Wall Station provides manual control of lights• Upon Exit and after Occupancy sensor times out, lights

and receptacles switched OFF• Lights can be switched OFF manually at Office Wall

Station• During power failure UL924 listed relays are automatically

switched ON by back-up power source switching designated emergency lights ON and to full-bright. Emergency lights remain ON with all controls disabled until primary power is restored.

Primary Daylight Zone

Secondary Daylight Zone

Dimming Zone 1

Dimming Zone 2

O/S

Relay 2Dimmer 1

Relay 5Dimmer 2

EMERGENCY

WallStation

Relay 4Receptacle

D/S

Window

Dimming Zone 3

*Optional

Relay 3Dimmer 3

Relay 3Dimmer 3

Relay 3Dimmer 3

Relay 3Dimmer 3

Dialog RoomController

31

Page 33: ROOM CONTROLLER 24 - Douglas Lighting Controls

Neutral not shown - these illustrations are for reference purposes only. For site installations, please review Kit wiring diagrams and follow local and national electrical codes.

PROJECT NAME: ___________________________________________________________________ DATE: __________________

OFFICE + EMERGENCY

32

Connection Schematic

Section 2 www.DouglasLightingControls.com

PURPLE

RED

YELLOW

BLUE

BLUE

WHITE

BLACK

ORANGE

ORANGE

GREY

GREY

PURPLE

RED

YELLOW

BLUE

BLUE

BLACK

WHITE

ORANGE

ORANGE

GREY

GREY

LIGHTING LOAD 1

LIGHTING LOAD 2

LIGHTING LOAD 3

SWITCHED RECEPTACLE(S) LOAD 4

RECEPTACLE(S) HOT

LIGHTING HOT

NEUTRAL

(EM) LIGHTING LOAD 5

(EM) LIGHTING HOT

(EM) LIGHTING LOAD 6

(EM) LIGHTING HOT

NEUTRAL

NEUTRAL

Emergency120/277/347Vac

DistributionCabinet

(by Others)

NEUTRAL

Lighting120/277/347Vac

DistributionCabinet

(by Others)

Receptacle120Vac

DistributionCabinet

(by Others)

Receptacle(Relay 4)

N

N

DATALINE

DIM 1DIM 2

DIM 4DIM 3

0-10V Dimming(18/2 per channel)

Dim 1

Building Controlvia

BACnet IP or Dialog Network

RoomController(WRC-3160)

EM Expansion(WUL-3924)

Local Room Dataline (18/2)

Occupancy Sensor(up to 4)

Daylight Sensor

NDim 3

Interior EM(Relay 5)N

Dim 2

Entry Station

KIT#12

Kit Ordering Numbers:

DRC01NS-1S11-03-EDRC01NS-1X11-03-EDRC01NS-1S31-03-EDRC01NS-1X31-03-E

Near Window(Relay 2)

Primary Daylight Zone

Secondary Daylight Zone

Display / Track(Relay 3)

Options• Additional Occupancy Sensors (4 max.)• Vacancy Control (Manual ON / Auto OFF)• Extended Lens range: 54’ diameter (standard 28')

Office with Emergency Lighting• Occupancy Control (Auto ON /Auto OFF)• Daylight Control (2 zones)• Light Control (3 zones)• Receptacle Control• Dimming Control (3 zones)• Wall Station (General ON/ALL OFF)

• Emergency Lighting Control (1 zones Orange)(Requires UL924 Relay Expansion Pack)

Operation• Upon Entry Occupancy sensor switches lights and

receptacles ON• Daylight Sensor maintains light level based on light

level pre-set• Office Wall Station provides manual control of lights• Upon Exit and after Occupancy sensor times out,

lights and receptacles switched OFF.• Lights can be switched OFF manually at Office Wall

Station• During power failure UL924 listed relays are

automatically switched ON by back-up powersource switching designated emergency lights ONand to full-bright. Emergency lights remain ON withall controls disabled until primary power is restored.

Dialog Room Controller

DRC01NS-1S11-30-EDRC01NS-1X11-30-EDRC01NS-1S31-30-EDRC01NS-1X31-30-E

Connection Schematic

Section 2 www.DouglasLightingControls.com

PURPLE

RED

YELLOW

BLUE

BLUE

WHITE

BLACK

ORANGE

ORANGE

GREY

GREY

PURPLE

RED

YELLOW

BLUE

BLUE

BLACK

WHITE

ORANGE

ORANGE

GREY

GREY

LIGHTING LOAD 1

LIGHTING LOAD 2

LIGHTING LOAD 3

SWITCHED RECEPTACLE(S) LOAD 4

RECEPTACLE(S) HOT

LIGHTING HOT

NEUTRAL

(EM) LIGHTING LOAD 5

(EM) LIGHTING HOT

(EM) LIGHTING LOAD 6

(EM) LIGHTING HOT

NEUTRAL

NEUTRAL

Emergency120/277/347Vac

DistributionCabinet

(by Others)

NEUTRAL

Lighting120/277/347Vac

DistributionCabinet

(by Others)

Receptacle120Vac

DistributionCabinet

(by Others)

Receptacle(Relay 4)

N

N

DATALINE

DIM 1DIM 2

DIM 4DIM 3

0-10V Dimming(18/2 per channel)

Dim 1

Building Controlvia

BACnet IP or Dialog Network

RoomController(WRC-3160)

EM Expansion(WUL-3924)

Local Room Dataline (18/2)

Occupancy Sensor(up to 4)

Daylight Sensor

NDim 3

Interior EM(Relay 5)N

Dim 2

Entry Station

KIT#12

Kit Ordering Numbers:

DRC01NS-1S11-03-EDRC01NS-1X11-03-EDRC01NS-1S31-03-EDRC01NS-1X31-03-E

Near Window(Relay 2)

Primary Daylight Zone

Secondary Daylight Zone

Display / Track(Relay 3)

Options• Additional Occupancy Sensors (4 max.)• Vacancy Control (Manual ON / Auto OFF)• Extended Lens range: 54’ diameter (standard 28')

Office with Emergency Lighting• Occupancy Control (Auto ON /Auto OFF)• Daylight Control (2 zones)• Light Control (3 zones)• Receptacle Control• Dimming Control (3 zones)• Wall Station (General ON/ALL OFF)

• Emergency Lighting Control (1 zones Orange)(Requires UL924 Relay Expansion Pack)

Operation• Upon Entry Occupancy sensor switches lights and

receptacles ON• Daylight Sensor maintains light level based on light

level pre-set• Office Wall Station provides manual control of lights• Upon Exit and after Occupancy sensor times out,

lights and receptacles switched OFF.• Lights can be switched OFF manually at Office Wall

Station• During power failure UL924 listed relays are

automatically switched ON by back-up powersource switching designated emergency lights ONand to full-bright. Emergency lights remain ON withall controls disabled until primary power is restored.

Dialog Room Controller

Page 34: ROOM CONTROLLER 24 - Douglas Lighting Controls

KIT #13Office• Occupancy Control (Auto ON /Auto OFF)• Daylight Control (2 zones)• Light Control (3 zones)• Receptacle Control• Dimming Control (3 zones)• Wall Station (4-button toggle)

Options• Additional Occupancy Sensors (4 max.)• Vacancy Control (Manual ON / Auto OFF)• Extended Lens range: 54’ diameter (standard 28’)

• Operation• Upon Entry Occupancy sensor switches lights and

receptacles ON• Daylight Sensor maintains light level based on light level

pre-set• Office Wall Station provides manual control of lights• Upon Exit and after Occupancy sensor times out, lights

and receptacles switched OFF• Lights and receptacle can be switched OFF manually at

Wall Station 

Primary Daylight Zone &Dimmer Zone 1

Dimming Zone 1

Window

O/S

Relay 1

Dimmer 1

Relay 1

Dimmer 1

WallStation

Relay 4Receptacle

D/S

Relay 2 D

imm

er 2

Dimming Zone 3 Dimming Zone 2

*Optional *Optional

Relay 3Dimmer 3

Relay 3Dimmer 3

Relay 3Dimmer 3

Relay 3Dimmer 3

Dialog RoomController

33

Page 35: ROOM CONTROLLER 24 - Douglas Lighting Controls

Neutral not shown - these illustrations are for reference purposes only. For site installations, please review Kit wiring diagrams and follow local and national electrical codes.

PROJECT NAME: ___________________________________________________________________ DATE: __________________

OFFICE

Connection Schematic

Section 2 www.DouglasLightingControls.com

PURPLE

RED

YELLOW

BLUE

BLUE

WHITE

BLACK

NEUTRAL

NEUTRALLighting120/277/347Vac

DistributionCabinet

(by Others)

Receptacle120Vac

DistributionCabinet

(by Others)

Receptacle(Relay 4)

General Lighting(Relay 1)

N

N

N

DATALINE

DIM 1DIM 2

DIM 4DIM 3

Dim 1

0-10V Dimming(18/2 per channel)

Dim 2

RoomController(WRC-3160)

Local Room Dataline (18/2)

Occupancy Sensor(up to 4)

Daylight Sensor

Office Toggle Station

Preset Station(Optional)

NDim 3

PURPLE

RED

YELLOW

BLUE

BLUE

BLACK

WHITE

LIGHTING LOAD 1

LIGHTING LOAD 2

LIGHTING LOAD 3

SWITCHED RECEPTACLE(S) LOAD 4

RECEPTACLE(S) HOT

LIGHTING HOT

NEUTRAL

Building Controlvia

BACnet IP or Dialog Network

KIT#13

Kit Ordering Numbers:

DRC01PS-1S11-30-NDRC01PS-1X11-30-NDRC01PS-1S31-30-NDRC01PS-1X31-30-N

Primary Daylight Zone

Display / Track(Relay 2)

Display / Track(Relay 3)

Options• Additional Occupancy Sensors (4 max.)• Vacancy Control (Manual ON / Auto OFF)• Extended Lens range: 54’ diameter (standard 28”)

Office• Occupancy Control (Auto ON /Auto OFF)• Daylight Control (2 zones)• Light Control (3 zones)• Receptacle Control• Dimming Control (3 zones)• Wall Station (4-button toggle)

Operation• Upon Entry Occupancy sensor switches lights and

receptacles ON• Daylight Sensor maintains light level based on light

level pre-set• Office Wall Station provides manual control of lights• Upon Exit and after Occupancy sensor times out,

lights and receptacles switched OFF.• Lights and receptacle can be switched OFF

manually at Wall Station

Dialog Room Controller

34

DRC01NS-1S11-30-NDRC01NS-1X11-30-NDRC01NS-1S31-30-NDRC01NS-1X31-30-N

Page 36: ROOM CONTROLLER 24 - Douglas Lighting Controls

KIT #14Office with Emergency Lighting• Requires UL924 Relay Expansion Pack (orange)• Occupancy Control (Auto ON /Auto OFF)• Daylight Control (2 zones)• Light Control (3 zones)• Receptacle Control• Dimming Control (3 zones)• Wall Station (4-button)

Options• Additional Occupancy Sensors (4 max.)• Vacancy Control (Manual ON / Auto OFF)• Extended Lens range: 54’ diameter (standard 28’)

Operation• Upon Entry Occupancy sensor switches lights and

receptacles ON• Daylight Sensor maintains light level based on light level

pre-set• Office Wall Station provides manual control of lights• Upon Exit and after Occupancy sensor times out, lights

and receptacles switched OFF• Lights and receptacle can be switched OFF manually at

Wall Station• During power failure UL924 listed relays are automatically

switched ON by back-up power source switching designated emergency lights ON and to full-bright.

• Emergency lights remain ON with all controls disabled until primary power is restored.

Primary Daylight Zone &Dimmer Zone 1

Dimming Zone 1

Window

O/S

Relay 1

Dimmer 1

Relay 5Dimmer 1

EMERGENCY

WallStation

Relay 4Receptacle

D/S

Relay 2 D

imm

er 2

Dimming Zone 3 Dimming Zone 2

*Optional *Optional

Relay 3Dimmer 3

Relay 3Dimmer 3

Relay 3Dimmer 3

Relay 3Dimmer 3

Dialog RoomController

35

Page 37: ROOM CONTROLLER 24 - Douglas Lighting Controls

Neutral not shown - these illustrations are for reference purposes only. For site installations, please review Kit wiring diagrams and follow local and national electrical codes.

PROJECT NAME: ___________________________________________________________________ DATE: __________________

OFFICE + EMERGENCY

Connection Schematic

Section 2 www.DouglasLightingControls.com

PURPLE

RED

YELLOW

BLUE

BLUE

WHITE

BLACK

ORANGE

ORANGE

GREY

GREY

PURPLE

RED

YELLOW

BLUE

BLUE

BLACK

WHITE

ORANGE

ORANGE

GREY

GREY

LIGHTING LOAD 1

LIGHTING LOAD 2

LIGHTING LOAD 3

SWITCHED RECEPTACLE(S) LOAD 4

RECEPTACLE(S) HOT

LIGHTING HOT

NEUTRAL

(EM) LIGHTING LOAD 5

(EM) LIGHTING HOT

(EM) LIGHTING LOAD 6

(EM) LIGHTING HOT

NEUTRAL

NEUTRAL

Emergency120/277/347Vac

DistributionCabinet

(by Others)

NEUTRAL

Lighting120/277/347Vac

DistributionCabinet

(by Others)

Receptacle120Vac

DistributionCabinet

(by Others)

Receptacle(Relay 4)

N

N

N

DATALINE

DIM 1DIM 2

DIM 4DIM 3

Dim 1

0-10V Dimming(18/2 per channel)

Dim 2

Building Controlvia

BACnet IP or Dialog Network

RoomController(WRC-3160)

EM Expansion(WUL-3924)

Local Room Dataline (18/2)

Occupancy Sensor(up to 4)

Daylight Sensor

Office Toggle Station

Preset Station(Optional)

NDim 3

Genreal Ltg EM(Relay 5)N

Dim 1

KIT#14

Kit Ordering Numbers:

DRC01PS-1S11-30-EDRC01PS-1X11-30-EDRC01PS-1S31-30-EDRC01PS-1X31-30-E

General Lighting(Relay 1)

Primary Daylight Zone

Display / Track(Relay 2)

Display / Track(Relay 3)

Primary Daylight Zone

Options• Additional Occupancy Sensors (4 max.)• Vacancy Control (Manual ON / Auto OFF)• Extended Lens range: 54’ diameter (standard 28”)

Office with Emergency Lighting• Requires UL924 Relay Expansion Pack (orange)• Occupancy Control (Auto ON /Auto OFF)• Daylight Control (2 zones)• Light Control (3 zones)• Receptacle Control• Dimming Control (3 zones)• Wall Station (4-button)

• Emergency Lighting Control (1 zones Orange)(Requires UL924 Relay Expansion Pack)

Operation• Upon Entry Occupancy sensor switches lights and

receptacles ON• Daylight Sensor maintains light level based on light

level pre-set• Office Wall Station provides manual control of lights• Upon Exit and after Occupancy sensor times out,

lights and receptacles switched OFF.• Lights and receptacle can be switched OFF

manually at Wall Station

• During power failure UL924 listed relays areautomatically switched ON by back-up powersource switching designated emergency lights ONand to full-bright.

• Emergency lights remain ON with all controlsdisabled until primary power is restored.

Dialog Room Controller

36

DRC01NS-1S11-30-EDRC01NS-1X11-30-EDRC01NS-1S31-30-EDRC01NS-1X31-30-E

Page 38: ROOM CONTROLLER 24 - Douglas Lighting Controls

KIT #15Two Offices, One Dialog Room Controller• UL924 Relay Expansion Pack used for additional light

loads (not Emergency Lighting)• Occupancy Control (Auto ON /Auto OFF)• Daylight Control (1 zones per room)• Light Control (2 zones per room)• Receptacle Control• Dimming Control (1 zones per room)• Wall Station (ON/OFF)

Options• Additional Occupancy Sensors (Max. 4 per system)• Vacancy Control (Manual ON / Auto OFF)• Extended Lens range: 54’ diameter (standard 28’)

Operation• Upon Entry Occupancy sensor switches lights and

receptacles ON• Daylight Sensor maintains light level based on light level

pre-set• Office Wall Station provides manual control of lights• Upon Exit and after Occupancy sensor times out, lights

and receptacles switched OFF • Lights can be switched OFF manually at Wall Station

Primary Daylight Zone A Primary Daylight Zone B

Dimming Zone 1 Dimming Zone 2

Window Window

D/S D/S

O/S O/S

Relay 1 Dimmer 1 Relay 3 Dimmer 2

Relay 2 Dimmer 1 Relay 4 Dimmer 2

WallStation A

WallStation B

Relay 5Receptacle

Relay 6Receptacle

Dialog Room

Controller

37

Page 39: ROOM CONTROLLER 24 - Douglas Lighting Controls

Neutral not shown - these illustrations are for reference purposes only. For site installations, please review Kit wiring diagrams and follow local and national electrical codes.

PROJECT NAME: ___________________________________________________________________ DATE: __________________

TWO OFFICES, ONE DRC

Connection Schematic

Section 2 www.DouglasLightingControls.com

PURPLE

RED

YELLOW

BLUE

BLUE

WHITE

BLACK

ORANGE

ORANGE

GREY

GREY

PURPLE

RED

YELLOW

BLUE

BLUE

BLACK

WHITE

ORANGE

ORANGE

GREY

GREY

LIGHTING LOAD 1

LIGHTING LOAD 2

LIGHTING LOAD 3

LIGHTING LOAD 4

LIGHTING HOT LOAD 4

LIGHTING HOT

NEUTRAL

(EM) RECEPTACLE LOAD 5

(EM) RECEPTACLE HOT

(EM) RECEPTACLE LOAD 6

(EM) RECEPTACLE HOT

NEUTRAL

Receptacle120Vac

DistributionCabinet

(by Others)

NEUTRAL

Lighting120/277/347Vac

DistributionCabinet

(by Others)

Office A(Relay 3)N

DATALINE

DIM 1DIM 2

DIM 4DIM 3

Office B((Relay 4))

0-10V Dimming(18/2 per channel)

Local Room Dataline (18/2)

Dim 2Dim 1

Daylight SensorClassroom B

Entry Station(s)Office B

Building Controlvia

BACnet IP or Dialog Network

RoomController(WRC-3160)

EM Expansion(WUL-3924)

Occupancy SensorClassroom A

Daylight SensorClassroom A

N

Office A Office B

Occupancy SensorClassroom B

Entry Station(s)Office A

Receptacle(Relay 5)

N

Receptacle(Relay 6)

N

KIT#15

Kit Ordering Numbers:

DRC02NS-2S12-04-NDRC02NS-2X12-04-NDRC02NS-2S32-04-NDRC02NS-2X32-04-N

Primary Daylight Zone Primary Daylight Zone

Options• Additional Occupancy Sensors (4 max.)• Vacancy Control (Manual ON / Auto OFF)• Extended Lens range: 54’ diameter (standard 28”)

Two Offices, One Dialog Room Controller• Occupancy Control (Auto ON /Auto OFF)• Daylight Control (1 zones per room)• Light Control (2 zones per room)• Receptacle Control• Dimming Control (1 zones per room)• Wall Station (ON/OFF)

• UL924 Relay Expansion for additional light load(2 zones Orange & Grey)

Operation• Upon Entry Occupancy sensor switches lights and

receptacles ON• Daylight Sensor maintains light level based on light

level pre-set• Entry Station and Teacher Station provide manual

control of lights• Upon Exit and after Occupancy sensor times out,

lights and receptacles switched OFF.• Lights can be switched OFF manually at Entry

Station and Teacher Station

Dialog Room Controller

38

Page 40: ROOM CONTROLLER 24 - Douglas Lighting Controls

4

1

2

3

1.0 BASIC INSTALLATION 3.0 EMERGENCY INSTALLATION

4.0 EMERGENCY + RECEPTACLE INSTALLATION

2.0 RECEPTACLE

Loads Line Voltage (lights) Daylight Sensor

2-Wire Network

Occupancy Sensor Wall Switches

BASIC INSTALLATION

Dimming Zone 1

Dimming Zone 2

Dimming Zone 3

Dimming Zone 4

Neutral not shown - these illustrations are for reference purposes only. For site installations, please review Kit wiring diagrams and follow local and national electrical codes.

39

Line Voltage Passive Infrared (PIR) Occupancy / Vacancy Sensor Product Details Line Voltage Passive Infrared (PIR) Occupancy / Vacancy Sensor

www.DouglasLightingControls.comDiversa by Douglas Lighting Controls Passive Infrared (PIR) Occupancy / Vacancy Sensor Product Details

14040500-ALine Voltage Passive Infrared (PIR) Occupancy / Vacancy Sensor Product Details Line Voltage Passive Infrared (PIR) Occupancy / Vacancy Sensor

www.DouglasLightingControls.comDiversa by Douglas Lighting Controls Passive Infrared (PIR) Occupancy / Vacancy Sensor Product Details

14040500-A

Page 41: ROOM CONTROLLER 24 - Douglas Lighting Controls

1.0 BASIC INSTALLATION 3.0 EMERGENCY INSTALLATION

4.0 EMERGENCY + RECEPTACLE INSTALLATION

2.0 RECEPTACLE

Loads Line Voltage (lights)

Line Voltage (lights) with emergency backup power

BASIC + EMERGENCY LIGHTING

Daylight Sensor

2-Wire Network

Occupancy Sensor Wall Switches

Dimming Zone 1

Dimming Zone 2

Dimming Zone 3

Dimming Zone 4

4

1

2

3

EM1

EM2

Neutral not shown - these illustrations are for reference purposes only. For site installations, please review Kit wiring diagrams and follow local and national electrical codes.

40

Line Voltage Passive Infrared (PIR) Occupancy / Vacancy Sensor Product Details Line Voltage Passive Infrared (PIR) Occupancy / Vacancy Sensor

www.DouglasLightingControls.comDiversa by Douglas Lighting Controls Passive Infrared (PIR) Occupancy / Vacancy Sensor Product Details

14040500-ALine Voltage Passive Infrared (PIR) Occupancy / Vacancy Sensor Product Details Line Voltage Passive Infrared (PIR) Occupancy / Vacancy Sensor

www.DouglasLightingControls.comDiversa by Douglas Lighting Controls Passive Infrared (PIR) Occupancy / Vacancy Sensor Product Details

14040500-A

Page 42: ROOM CONTROLLER 24 - Douglas Lighting Controls

BASIC + RECEPTACLE

1.0 BASIC INSTALLATION 3.0 EMERGENCY INSTALLATION

4.0 EMERGENCY + RECEPTACLE INSTALLATION

2.0 RECEPTACLELoads Line Voltage (receptacle)

Line Voltage (lights)

Daylight Sensor

2-Wire Network

Occupancy Sensor Wall Switches

Dimming Zone 1

Dimming Zone 2

Dimming Zone 3

Dimming Zone 4

1

2

3

Neutral not shown - these illustrations are for reference purposes only. For site installations, please review Kit wiring diagrams and follow local and national electrical codes.

41

Line Voltage Passive Infrared (PIR) Occupancy / Vacancy Sensor Product Details Line Voltage Passive Infrared (PIR) Occupancy / Vacancy Sensor

www.DouglasLightingControls.comDiversa by Douglas Lighting Controls Passive Infrared (PIR) Occupancy / Vacancy Sensor Product Details

14040500-ALine Voltage Passive Infrared (PIR) Occupancy / Vacancy Sensor Product Details Line Voltage Passive Infrared (PIR) Occupancy / Vacancy Sensor

www.DouglasLightingControls.comDiversa by Douglas Lighting Controls Passive Infrared (PIR) Occupancy / Vacancy Sensor Product Details

14040500-A

Page 43: ROOM CONTROLLER 24 - Douglas Lighting Controls

BASIC + RECEPTACLE + EMERGENCY

4.0 EMERGENCY + RECEPTACLE INSTALLATIONDaylight Sensor

2-Wire Network

Occupancy Sensor Wall SwitchesLoads

Dimming Zone 1

Dimming Zone 2

Dimming Zone 3

Dimming Zone 4EM1

EM2

3

2

1

Line Voltage (receptacle)Line Voltage (lights)

Line Voltage (lights) with emergency backup power

Neutral not shown - these illustrations are for reference purposes only. For site installations, please review Kit wiring diagrams and follow local and national electrical codes.

42

Line Voltage Passive Infrared (PIR) Occupancy / Vacancy Sensor Product Details Line Voltage Passive Infrared (PIR) Occupancy / Vacancy Sensor

www.DouglasLightingControls.comDiversa by Douglas Lighting Controls Passive Infrared (PIR) Occupancy / Vacancy Sensor Product Details

14040500-ALine Voltage Passive Infrared (PIR) Occupancy / Vacancy Sensor Product Details Line Voltage Passive Infrared (PIR) Occupancy / Vacancy Sensor

www.DouglasLightingControls.comDiversa by Douglas Lighting Controls Passive Infrared (PIR) Occupancy / Vacancy Sensor Product Details

14040500-A

Page 44: ROOM CONTROLLER 24 - Douglas Lighting Controls

EMERGENCY (REMOTE MOUNT)

Loads

EM1

EM2

Line Voltage (lights) with emergency backup power

2-wire network to Dialog Room Controller

Neutral not shown - these illustrations are for reference purposes only. For site installations, please review Kit wiring diagrams and follow local and national electrical codes.

43

Page 45: ROOM CONTROLLER 24 - Douglas Lighting Controls

WRC-TS-1Teachers Stations

WRC-ES-1Entry Station

WRC-OF-PSPresent Station

WRC-OF-A1Entry Station

OF-TGLOffice Station

WRC-TS-8

WRC-DS-0 WRC-DS-R WRC-DS-Z2WRC-DS-F WRC-DS-Z1 WRC-DS-Z3

Switch Option Summary Dimmer Switch: Optinal Dimming Control

Standard naming ShownCan be Customized at Site or At Customer Request

Device Type Description PNDialog Room Controller Digital 4 Channel ON/OFF Room Controller w/ Receptacle Control, BACNet WRC-3160

Dialog Room Controller UL924 / Relay Expansion Pack Digital 2 Channel UL924 Emergency Lighting Controller / Relay Expansion Pack WUL-3924

Digital Occupancy Sensor Recessed Ceiling Standard Range Lens w/ Time Delay Dial & Aux Relay WORSDG1-R-T

Digital Occupancy Sensor Recessed Ceiling Extended Range Lens w/ Time Delay Dial & Aux Relay WORXDG1-R-T

Digital Vacancy Sensor Recessed Ceiling Standard Range Lens w/ Time Delay Dial & Aux Relay WVRSDG1-R-T

Digital Vacancy Sensor Recessed Ceiling Extended Range Lens w/ Time Delay Dial & Aux Relay WVRXDG1-R-T

Closed Loop Daylight Sensor Interior Daylight Sensor for Closed Loop Controlled dimming (on-board dial) WPP-INT

Digital Dimmer & Switch, 1 Channel, O Type Digital Dimmer & Switch, ALL Up/Down & On/Off WRC-DS-O

Digital Dimmer & Switch, 1 Channel, F Type Digital Dimmer & Switch, FRONT Up/Down & On/Off WRC-DS-F

Digital Dimmer & Switch, 1 Channel, R Type Digital Dimmer & Switch, REAR Up/Down & On/Off WRC-DS-R

Digital Dimmer & Switch, 1 Channel, Zone 1 Type Digital Dimmer & Switch, Zone 1 UP/Down & On/Off WRC-DS-Z1

Digital Dimmer & Switch, 1 Channel, Zone 2 Type Digital Dimmer & Switch, Zone 2 Up/Down & On/Off WRC-DS-Z2

Digital Dimmer & Switch, 1 Channel, Zone 3 Type Digital Dimmer & Switch, Zone 3 Up/Down & On/Off WRC-DS-Z3

4 Button Teacher Switch Station Digital 1 Gang 4 Button Switch WRC-TS-1

2 Button Classroom Entry Switch Station Digital 1 Gang 2 Button Switch WRC-ES-1

4 Button Office Switch Station Toggle Control Digital 1 Gang 4 Button Switch WRC-OF-TGL

4 Button Office Switch Station Preset Control Digital 1 Gang 4 Button Switch WRC-OF-PS

4 Button Office Entry Switch Station Digital 1 Gang 4 Button Switch WRC-OF-ES1

2 Button Office Entry Switch Station Digital 1 Gang 2 Button Switch WRC-OF-ES2

8 Button Dimmer Control Digital 1 Gang 8 Button Switch (dimming & ON/OFF) WRC-TS-8

KIT COMPONENTS

Teaching General 50% R1 Toggle

General On Meeting 100% R2 ToggleGeneral On

A/V Presentation R3 Lights R3 ToggleAll Off

Quiet Mode All Off All Off All Off General Front Rear Zone 1 Zone 2 Zone 3

44

Page 46: ROOM CONTROLLER 24 - Douglas Lighting Controls

FAQ - DIALOG ROOM CONTROLLER

QUESTION: How does the Expansion Pack connect to Dialog Room Controller?

ANSWER: The Expansion Pack can be connected directly to the Room controller via an integrated clip attachment.

• If the Expansion Pack is connected with the Room Controller, then the units communicate through a Dialog protocol connection.

ANSWER: If the Expansion Pack is remotely mounted from the Room Controller, then a 2-wire connection is needed to communicate through a Dialog protocol. The remote mount kit includes a Conduit Adapter and Connector.

QUESTION: What power can the relays support?

ANSWER: There are two 20A circuits coming into the Room Controller, Hot on #1, #2, #3 and Hot on 4.

• #1, #2, #3 are rated for 20A (combined).• #4 is rated for 20A by itself.• There are 2 circuits so different voltages can be used.• Expansion pack can add 2 more 20A Circuits (#5 and #6)

QUESTION: Do the relays support 120VAC, 277VAC and 347VAC?

ANSWER: Yes.

QUESTION: When using Dialog WLC-3150 and Dialog Room Controller and the Dialog WLC-3150 goes down, will the Dialog Room Controller function as a stand-alone?

ANSWER: Yes.

QUESTION: Does Dialog Room Controller work with a GUI?

ANSWER: Graphical UI would be for a centralized system. To drive graphics, a Dialog WLC-3150 and GWS are required.

QUESTION: Do Dialog devices work with Dialog Room Controller?

ANSWER: No. Dialog Room Controller is sold as a kit and includes sensors and switches configured for the specific room applications.

QUESTION: Is the 0-10V dimming isolated?

ANSWER: Yes, each of the four 0-10V dimming outputs are independent channels. 100mA sinking per channel.

QUESTION: What is the maximum number of devices on a room controller?

ANSWER: Dimming: Calculation required based on 100mA per channel of dimming. This will depend on LED driver sinking current requirements. Each DRC is designed to handle up to four Occupancy Sensors and 2 Daylight Sensors plus switches and is limited by the 250mA output of the Dialog Room Controller.

QUESTION: Can Dialog Room Controller provide partition control?

ANSWER: No, it is designed for room control. Partition Control requires WLC-3150 and appropriate firmware version.

QUESTION: How many Dialog Room Controllers on WLC-3150?

ANSWER: WLC-3150 can support up to 64 Dialog Room Controllers. Please contact us for your specific project.

QUESTION: Why or when should I use the expansion pack?

ANSWER: If the room requires a UL924 emergency lighting circuit.ANSWER: If you need to support additional loads.

QUESTION: How does the emergency lighting work when a 0-10v dimmer channel is controlling the fixture/zone?

ANSWER: When power is lost to the room controller, the dimming circuit acts as an open circuit so dimming control is no longer present, while the expansion pack automatically latches both internal relays to ON position. When emergency power is provided, power goes through the UL924 expansion pack and the fixture will turn on at full brightness. – see wiring diagram.

45

Page 47: ROOM CONTROLLER 24 - Douglas Lighting Controls

Since 1962, Douglas Lighting Controls has been solving lighting control challenges by providing convenient and efficient solutions to buildings throughout North America. Their products effectively operate facility lighting while minimizing energy consumption. With over 50 years of providing lighting control solutions, customers trust Douglas Lighting Controls’ experience and product quality.

• Best-in-Class Pre-Sales, Quote, & Design Services• Exceptional Post-Sales Site & Technical Support• 1,500 Projects Annually

• 100% Project Quality Control• Industry Best Practices for Design & Testing• Make use of Highest Performing Components

• Over 50 Years of Proven Experience• Unwavering Commitment to Successful Outcomes• Backed by a Global Leader - Panasonic

What Makes Us Better

Service

Reliability

Integrity

46

Page 48: ROOM CONTROLLER 24 - Douglas Lighting Controls

toll free: 877-873-2797 direct: 604-873-2797lighting@douglaslightingcontrols.comwww.douglaslightingcontrols.com

Your Douglas Lighting Controls representative:

Douglas Lighting Controls is a member of the Panasonic Group