Report on EnergyReport on Energy--Saving SurveySaving Survey · Chiller Plant Each Chiller COP has...
Transcript of Report on EnergyReport on Energy--Saving SurveySaving Survey · Chiller Plant Each Chiller COP has...
Report on EnergyReport on Energy--Saving SurveySaving Survey
Commercial Building WG24Commercial Building WG24
February February 21, 201121, 2011yy ,,
Yamatake CorporationYamatake CorporationYamatake CorporationYamatake Corporation
Table of Contents
1 Background and Objective
Table of Contents
1.Background and Objective2.Introduction of the Survey/Surveyed
CCompanies3.Survey Process4.Results
・Current Status and issuesCurrent Status and issues on Energy Efficiency
・Energy saving plan and its effect・Energy-saving plan and its effect5.Suggestions
All Rights Reserved, Copyright © GIPC 2011 2
BackgroundBackground
Targeted big potential of CO2 reduction
People’s livelihood partPeople’s livelihood
Growth rate from 1973 to 2005 2.1 timesCarrier
2.0times p p
Energy Efficiency Improvement
People s livelihood
1.0timesIndustry
1973 2005
HVAC ・Efficiency up of HVAC Power・Exclusion of wasteful energy use
All Rights Reserved, Copyright © GIPC 2011 3
Objective
Focused on
Objective
・Chillers replacement to high efficiency
・Introduction of BEMS instead of existing BMS- Visualization of energy performance- Infrastructure for Energy Efficiency operation
BEMS ; Building Energy Management System
・Introduction of energy saving application to theChill Pl t S tChiller Plant System- Chiller sequence control system
OthAll Rights Reserved, Copyright © GIPC 2011 4
- Others
Introduction of Surveyed CompanyIntroduction of Surveyed Company
Target building for survey UOB Alexandra BuildingTarget building for survey UOB Alexandra Building
Building Owner United Overseas Bank Ltd.
Type
Commercial Building *** At the beginning, it was a commercial building
with tenants, but now it was 100% occupied by UOB
Total space area 22,694 m2 25stories above and 1 under ground
Construction 1993
Chiller Plant Centrifugal chiller 4sets (550RT*2, 275RT*2)
Air Conditioners AHU 25 setsEquipped with VAV, FCU
All Rights Reserved, Copyright © GIPC 2011 5
Introduction of Survey CompanyIntroduction of Survey Company
CRUDE OIL (T) / M$-2000Y
450
400
350
$
300
250
200200
150
100
50
19731980
1985 50
0
19851990
19952000
2004
All Rights Reserved, Copyright © GIPC 2011 6
Summary of the surveySummary of the survey
Survey Process Result of the Survey
D d Chill ’ COP
Current Status Energy-Saving Plan and Its Effect
First Step(July 2010) for 4 days・Walk through in site for 4 days Chiller replacement・Decreased Chiller’s COP
・Aged sensor, no longer
reliable
・Walk through in site for 4 days
Second Step(Aug 2010) for 6 days
・Chiller replacement
・Installation of Energy Saving Application
reliable
・Balance situation of the
chiller’s ability and the air-
・Installs the measuring instrument・Installs the new type control valve to AHU
・Modification of AHU Control System
・BEMS installation instead of y
conditional load
・Aged VAV units
Third Step(July 2010) for 3 days・Removes the measuring
BMS
Energy Reductionand vane-motor for AHU
・BMS feature
ginstrument
Fourth Step(July 2010~Oct 2010)
gy760,000kW/Year
Electric fee Reduction167,000SGD/Year
All Rights Reserved, Copyright © GIPC 2011 7
(July 2010~Oct .2010)・Data analysis & writing report
167,000SGD/YearCO2 Emission Reduction
380 ton/Year
Survey Process (Summary)Survey Process (Summary)
ProposalAnalysisField Survey
From July 2010 to Sept. 2010Date
First Step (Jul/7 ~Jul/10 2010)
From Sept. 2010 to Oct. 2010
Data AnalysisCalculationComparison
First Step (Jul/7 ~Jul/10 2010)・Walk through in site for 4 days
Second Step (Aug/19 ~Sep/27 2010) Comparison
・Energy Consumption per each dayCOP (O ti ffi i f hill )
・Data Collection・Exchange the AHU control valve from existing one to new type that can
th i f AHU ・COP (Operating efficiency of chiller)・Change of Load frequency per each day・Change of chilled water temperature diff. between Inlet and Outlet of chiller
Action measure the using energy of AHU
Main Data Items1.Chilled Water Flow Rate in Plant (*3sets)2 El t i P i h Chill (*4 t ) between Inlet and Outlet of chiller
・Change of condenser water temperature diff. between Inlet and Outlet of chiller・Pump operation condition
2.Electric Power in each Chiller (*4sets) 3.Temperature・Chilled Water in Plant (*5sets)・Cooling water in each Chiller (*8sets)
All Rights Reserved, Copyright © GIPC 2011 8
・Pump operation condition・Cooling water for PAC (*2sets)
Survey Process (Detail)①Survey Process (Detail)①
Chilled Water Flow Rate in Chiller Plant
99All Rights Reserved, Copyright © GIPC 2011
Survey Process (Detail)②Survey Process (Detail)②
Electric Power in each Chiller
All Rights Reserved, Copyright © GIPC 20111010
Survey Process (Detail)③Survey Process (Detail)③Exchange the AHU control valve from existing one to new type that can measure the usingone to new type that can measure the using energy of AHU
As a control andAs a control and energy monitoring device
1111All Rights Reserved, Copyright © GIPC 2011
Current Status and issues of Energy Efficiency (Summary)(Summary)
ITEM Current Status and issues of Energy EfficiencyChiller Plant Each Chiller COP has decreased, so energy consumption has increased
Chiller Plant Load changes roughly in a day, so it is difficult to decide the operating chiller bChiller Plant numbers
Chiller Plant There is no balance of Chilled water between chiller plant side and load side, so there is waste in pump powerso there is waste in pump power
BMS Original BMS does not have data storage function, so it is impossible to compare the data
BMS Many local sensors are very old and not reliable
BMS Room temperature is local control, therefore no temperature feedback to BMSBMS
AHU Many VAV units are very old, so it is difficult to control room temperature
AHU Most of AHU vane motor to control the static pressure are very old and are
All Rights Reserved, Copyright © GIPC 2011 12
AHU p yfully opened and fixed, so there is waste in AHU power
Current Status and issues of Energy Efficiency (Details)①(Details)① Chiller efficiency
Power Efficien Chill (CH 1 2) COP d i 8/20 9/13Designa
tion
Refrigerator CapacityPower Input
Efficiency
COP
kW USRT MJ (kW) (kW/TR)
CH 1 1 936 550 6 970 328 3 6 5 9
Chiller (CH-1,2) COP during 8/20~9/13
4.0
6.0
Val
ue
CH-1 1,936 550 6,970 328 3.6 5.9
CH-2 1,936 550 6,970 328 3.6 5.9
CH-3 968 275 3,485 179 3.6 5.4
0.0
2.0
0 1,000 2,000 3,000 4,000 5,000 6,000 7,000
Load Calorie (MJ)
CO
P V
CH-4 968 275 3,485 179 3.6 5.4
Chill COP 20108/24
Load Calorie (MJ)
CH-1 Electric Power Consumption rate on20108/24
300
400
Chiller COP on 20108/24
5.0
6.0
7.0
e
0
100
200
300
7:0
0
8:0
0
9:0
0
10
:00
11
:00
12
:00
13
:00
14
:00
15
:00
16
:00
17
:00
18
:00
19
:00
kW
0.0
1.0
2.0
3.0
4.0
CO
P V
alu
1 1 1 1 1 1 1 1 1 1
Time7:0
0
8:0
0
9:0
0
10:0
0
11:0
0
12:0
0
13:0
0
14:0
0
15:0
0
16:0
0
17:0
0
18:0
0
19:0
0
20:0
0
1313All Rights Reserved, Copyright © GIPC 2011
Current Status and issues of Energy Efficiency (Details)②(Details)②
Chiller Load Frequency (8/20~9/16)
40
Chiller load frequency
175RT 550RT
10
15
20
25
30
35
Count
0
5
1~5
6~10
11~15
16~20
21~25
26~30
31~35
36~40
41~45
46~50
51~55
56~60
61~65
66~70
71~75
76~80
81~85
86~90
91~95
96~100
Load (%)
141414
All Rights Reserved, Copyright © GIPC 2011
Current Status and issues of Energy Efficiency (Details)③(Details)③ Chilled water flow rate
2010/9/13 Chilled Water Flow Rate Data
700 0
300A Flow rate 150A Flow rate Bypass Flow rate
Secondary Pump Flow rate Primary Pump Flow rate
400.0
500.0
600.0
700.0
3/h)
0.0
100.0
200.0
300.0
Flow rat
e (m3
-200.0
-100.0
0.0
7:0
0
7:3
0
8:0
0
8:3
0
9:0
0
9:3
0
10:0
0
10:3
0
11:0
0
11:3
0
12:0
0
12:3
0
13:0
0
13:3
0
14:0
0
14:3
0
15:0
0
15:3
0
16:0
0
16:3
0
17:0
0
17:3
0
18:0
0
18:3
0
19:0
0
19:3
0
20:0
0
20:3
0
21:0
0
CH-1 ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○
CH-2 ○ ○ ○
CH 3 ○ ○ ○ ○ ○ ○CH-3 ○ ○ ○ ○ ○ ○
CH-4
Bypass flow, low Delta T
1515
Bypass flow, low Delta THigh Supply TemperatureHigh Flow
High consumption of pumps energy
All Rights Reserved, Copyright © GIPC 2011
Current Status and issues of Energy Efficiency (Details)④ AHU Control(Details)④ AHU Control
1616All Rights Reserved, Copyright © GIPC 2011
Energy-saving Plan and Its Effect (Summary)Energy saving Plan and Its Effect (Summary)
Expected Total Effect Proposals
E i Pl Eff
Chiller replacement
Energy-saving Plan Effect
30% reduction
(300 000kWH/year)
Estimated 13% reduction of total building energy Chiller replacement
Installation of Energy30% reduction
(300,000kWH/year)
E R d ti
g gyconsumption
Installation of Energy Saving Application (392,200kWH/year)Energy Reduction:
760,000kW/YearElectric fee Reduction:
4% reduction
(67,000kWH/year)Modification of AHU
control system167,000SGD/YearCO2 Emission Reduction:380 ton/Year
BEMS installation instead of BMS
Motivation of every person to energy
ti
380 ton/Year
More over, limitless energy reduction can be done by
All Rights Reserved, Copyright © GIPC 2011 17
instead of BMS conservationPDCA cycle through BEMS
Energy-saving Plan and Its Effect (Details) ①Chiller replacement and Chiller Numbers Control
Chiller operation numbers Chiller operation numbers is decided by
Chiller replacement and Chiller Numbers Control
550RT
is decided manually Chiller Plant Control automatically
Chiller Plant
550RT High efficiency High efficiency
Control
550RT High efficiency type 550RT
High efficiency
High efficiency type 175RT
High efficiency type 175RT
275RT
275RT
High efficiency type 550RT
type 175RT
275RT
The reduction of Man Power
All Rights Reserved, Copyright © GIPC 2011 18
The reduction of much electric power
Energy-saving Plan and Its Effect (Details) ②Installation of Energy Saving Application to Chiller Plant System
Cooling Tower
SecondaryPump
Condenser Water Pump
‐VSD control of primary pumps‐VSD control of secondary pumps‐ VSD control of condenser water
Primary Pump
Chillerpumps‐ Optimized condenser water temp. control for PAC
All Rights Reserved, Copyright © GIPC 2011 19
‐ Usage of remaining heat in the chiller plant
Energy-saving Plan and Its Effect (Details) ③M difi ti f AHU t l tModification of AHU control system
・Exchange the existing vane t l t t VSD t t lcontrol motor to VSD to control
static pressure・Exchange the VAV controller gwhich has communication function with AHU Controller・Exchange to the new type・Exchange to the new type control valve with measuring function
・AHU power consumption to be reduced・Measuring and monitoring of the room temperatures by the communication of each VAV controller
All Rights Reserved, Copyright © GIPC 201120
communication of each VAV controller・Restrain the exceed flow rate in AHU
Energy-saving Plan and Its Effect (Details) ④BEMS installation instead of BMS
Energy saving gy ginvestment
Energy saving infrastructure
All Rights Reserved, Copyright © GIPC 201121
BEMS is infrastructure for EE operation!
SuggestionsSuggestions
• Confirmed thing Cl ifi d th t ti l f th i i i ti ffi– Clarified the potential of the energy saving in existing office building
– Further energy saving can be done with lighting itemgy g g g
• Proposal To realize the energy saving, is it necessary to adopt BEMS thatcan visualize the energy performance as the building operationinfrastructureinfrastructure .Investment for BEMS is not the object of ROI.By the operation of BEMS, the trend of energy can be more grasped, y p , gy g p ,and investment for energy saving can be efficiently implemented.The popularization of the BEMS investment is the key that to expand
All Rights Reserved, Copyright © GIPC 2011 22
the energy saving in existing building
SuggestionsSuggestions
For Energy Savings…
ENERGY SAVINGS
View
OperationOperation
Maintenance
All Rights Reserved, Copyright © GIPC 2011 23
Contact ListContact ListIf you have interests in our survey, please feel free to contact to the following addresses.g
Name E-mail adrress Company
Kiritani Satoshi [email protected] Japan Yamatake
M T hihi t @ bil J Y t kMurayama Toshihisa [email protected] Japan Yamatake
Kurosaawa Shuuichi [email protected] Japan Yamatake
Takesako Masashi [email protected] Azbil Singapore
All Rights Reserved, Copyright © GIPC 2011