Thank You For Today’s Opportunity. Agenda Introductions Chiller Plant Design Criteria Chiller...
-
Upload
rowan-hoar -
Category
Documents
-
view
230 -
download
2
Transcript of Thank You For Today’s Opportunity. Agenda Introductions Chiller Plant Design Criteria Chiller...
Thank You ForToday’s Opportunity
Agenda
• Introductions•Chiller Plant Design Criteria•Chiller Plant Configurations•Different Chiller Technologies•Refrigerants•Chiller Plant Optimization Techniques
Introductions• John Calcagno-Formosa Account Manager
– Sales Engineer/Account Manager-Carrier Corporation– BSME Rutgers University – Over 27 Years HVAC Industry Experience
• This presentation applies to typical chiller plants. The type of building or process the plant serves will affect the design.
• Different criteria for different applications.• This presentation will focus on chillers.
Chiller Plant Design
Chiller Plant Design
• Type of application• Process Reliability, durability, life cycle cost • Data Center Reliability, life cycle cost, cold
condenser water.• Health Care Reliability, first cost, efficiency• Higher Education First cost, life cycle cost• Office First cost• District Cooling Reliability, life cycle cost
6
Design Criteria
• Review capacity
7
Design Criteria
Optimizing Chiller Plant Design
Components of Chiller Plant
• Chillers
• Chiller Heat Rejection
• Distribution System
• Load
Piping Configurations
• Variable Primary (Variprime)
Chiller Plant Configurations
• “Keep things as simple as possible but no simpler”
Single Chiller Constant Flow
Single Chiller Constant Flow• Advantages
• Simple• Low first cost
• Disadvantages:• No redundancy• Chiller cannot efficiently match the load• Does not take advantage of varying load• Part load-pumping water not needed
Multiple Chillers Parallel-Constant Flow
Multiple Chillers Parallel-Constant Flow
• Advantages• Redundancy• Can better match capacity at part load
• Disadvantages• Part load- one chiller off – mixing of chilled water supply• Part load- pumping water around that is not needed
Multiple Chillers Parallel-Constant Flow
TempMixing
Multiple Chillers Parallel Part Load Flow Reduction
Shut down one chiller/pump at part LOAD. But what about the flow?
Multiple Chillers Parallel Part Load Flow Reduction
• Advantages• Redundancy• Ability to match load by staging chillers• Saves pump energy at part load
• Disadvantages• Significant reduction of flow at part load• Chiller production loop is hydraulically tied to chiller
consumption loop
Multiple Chillers in Series-Constant Flow
Multiple Chillers In Series-Constant Flow
• Advantages• Eliminates temperature mixing and flow problems• Full flow at all loads• Series/counterflow arrangement-efficiency
• Disadvantages• Flow rate through each chiller is entire system flow-double
the flow for parallel chillers• Pressure drop is additive-bigger pumps and more energy• Part load-pumping water around building not needed• Limited to two chillers
Multiple Chillers In Parallel Primary/Secondary System
Decoupler pipe
Multiple Chillers in Parallel-Primary/Secondary System
• Advantages• Decouples or separates the chilled water production piping
from the chiller water consumption piping• Eliminates temperature mixing and flow reduction • Part load-match chiller capacity to load• Part load-reduced flow
• Disadvantages• More pumps required• Moderately complicated controls required• Water balancing important
Multiple Chillers In Parallel-Variable Primary System
Multiple Chillers In Parellel-Variable Primary System
• Advantages• Eliminates set of pumps• Efficient
• Disadvantages• Must coordinate minimum flow and rate of change with
chiller manufacturer• Moderately complicated controls
Variable Primary FlowPrinciples to follow:• Confirm chiller vendors minimum acceptable flow
rate (may require higher initial design cooler pressure drop)
• Specify flow meters or DP transmitters to measure/ maintain chiller minimum flows
• Design bypass for flow rates below minimum• Find out what rate of change in flow is acceptable
from chiller vendor(s) and put this in sequence of operation
• Provide ton-hr metering to measure machine capacity for sequencing logic (note, 23XRV speed is directly proportional to capacity, so speed can be used to sequence machines)
Variable Primary Flow – Rate of Change
Carrier Other
Model 23XRV Single Centrifugal
Multiple Compressors
Rate of Change (%/min) 70% 30% 10%
Minimum Loop Volume (gal)* 450 900 1,800
Why is this Important?Industry Best!
* = 300 Tons Comfort Cooling Application
In VPF applications, select a machine with high acceptable rate of flow change and specify rate (in %
change/Minute).
Compressor response time in VPF system
If the evaporator flow to the chiller is halved, the load is halved.
If the chiller does not unload quickly enough (VFD, IGV staging), the chilled water temperature will drop and either result in:
1. Recycle (LCWT too far below set point) or 2. Worst Cases, Freeze Trip (LCWT below freeze
protection value) or Surge Trip (at least for a centrifugal compressor).
More Flexibility = Less Nuisance Trips
Summary
• No right configuration for all plants• Must evaluate the design criteria• Take advantage of chiller’s modern
controls
Questions
31
Water Cooled Chiller Technologies
• Centrifugal• Helical Rotary (Screw)• Scroll• Absorption• Direct Fired Absorption
32
Water Cooled Chiller Technologies
• Centrifugal• Helical Rotary (Screw)• Scroll• Absorption• Direct Fired Absorption
Water Cooled Chiller Technologies
Product Portfolio
0 3,000
1,000
250 1,875
100 500 1,500
2,250
SCREW
CENTRIFUGAL
SCROLL
30MP 15-45 Tons
30HX 75-265 Tons
30XW 150-300 Tons Single Circuit 325-400 Tons Dual Circuit
23XRV 275-550 Tons
19XR(V) Single Stage 200-1,600 Tons
WATER-COOLED CHILLERS
23XRV 200-550 Tons
19XR(V)E Two Stage 800-1,600 Tons
19XR6 Two Stage 1,600-2,250 Tons
Q2 - 2014Q2 - 2013
Scroll Compressor
Helical Rotary/Screw Compressor
2 or 3
• Use variable frequency drive to slow down the compressor
Carrier 23XRV – Simple
Simple: 3 moving partsNo surge No purgeNo shaft sealsNo guide vanesNo slide valves No EXV’sNo chlorineNo phase-outNo refrigerant pumpsNo pressurization systemsNo bearing capacitors to changeNo pumps, hoses or clamps for VFDNo glycol cooling required for VFDNo motor heat rejection to the room
Given the choice, aren’t fewer worries better?
Centrifugal Compressor
• Use inlet guide vanes and variable frequency drive for unloading
39
IMPELLER WHEEL
Impeller
40
Shroud
Funnel-type device that ensures that the
refrigerant flows through the compressor.
41
PIPE DIFFUSER
Diffuser
Medium Pressure vs Low Pressure
• Evaporator – water, contaminants are sucked into the chiller
43
• Keeps Air and Contaminants Out• Keeps Refrigerant In• Store Refrigerant Inside Chiller• Equipment Life Extended• Efficiency Losses Avoided• Purge Maintenance Eliminated
Positive Pressure Design
Refrigerants
• HCFC-123 Low pressure refrigerant• Subject to phase out-MAJOR reduction in production NOW
(2015)!
• HFC-134a Medium Pressure Refrigerant• No phase out!
Semi Hermetic Versus Open Drive Design
Semi Hermetic Versus Open Drive Design
• Semi-hermetic: Motor and Compressor are one sealed assembly. Motor is cooled by refrigerant.
• Open Drive: Motor and Compressor are separate assemblies. Compressor has shaft seal to contain refrigerant in compressor.
Replacement of open drive shaft seals costs $3000 to $5000 every 3 to 5 Years.
“Open drive seals lose 2% of total refrigerant charge annually.” ARI Report 11/98
Shaft Seals-Leakage Source
Motor Cooling From Ambient Air
Ventilation vents let contaminants in!(dirt, salt, production debris etc)
Open Drive DesignAirborne dirt and contaminants in
Open Drive design
• Only ONE Major Manufacturer makes an open drive chiller.• If a design is used so that it is easy to repair, shouldn’t this
cause some concern?
Motor HealthOpen Motor Hermetic Motor
Heat – most common cause of premature failure. “Each 10C rise above the rating may reduce the motor lifetime by one half” - NEMA
“Class B Rise” results in 120C (248 F) operating temperature.
Motors can operate cool enough that insulation is applied to prevent sweating.
Dirt – abrasion can cause insulation failure, buildup increases operating temperature
Motor completely exposed to dirt, dust and debris in mechanical room as it actively pulls air through the motor internal vents to cool itself.
Motor completely isolated inside clean, cool refrigerant boundary, unexposed to mechanical room dirt, dust or debris.
Motor HealthOpen Motor Hermetic Motor
Moisture – reduces motor insulation resistance, can cause catastrophic failure.
Open motors must be equipped with internal heaters to prevent condensation.
Condensation on motor windings is not possible – it is sealed in refrigerant circuit.
Vibration – can cause bearing fatigue and failure, or cracks in insulation system and failure.
Compressor and motor balanced separately. Coupling can increase balance issues.
Compressor and motor dynamically balanced together – no coupling.
Mechanical Room Renovation When you need to install equipment, move a pipe , paint
or do some sort of renovation in mechanical room … should you turn your chillers off?
No …Run risk that dirt, dust or debris in air will cause motor failure or shorten
motor life.
Yes …Turn chillers off and
cover motor intakes. Provide temporary
cooling or no cooling at all.
Semi-Hermetic vs. Open Motors
Condensation on motor windings is normal.
Moisture degrades insulation resistance.
Starting a motor with moisture on its winding can cause insulation failure and require a rewind.
To prevent condensation, motor winding heaters are energized any time motors are off.
If power to motor and motor winding heaters is lost, a megger test should be performed to confirm insulation strength before starting.
All of this costs money. Is your customer willing to pay?
User Chiller Load Tons 500
Defined Power Consumption kW/Ton 0.60
Motor Efficiency pts 0.95
Calculated kW 300
hp 402
Motor Loss pts 0.05
hp 20.12
Motor Cooling Load Btu/Hr 51,173
Motor Cooling Load (Tons) 4.3
Competitor Open Motor Drive
• Open motors reject heat to the facility space, which must be tempered (air conditioned) or ventilated to a maximum of 104F indoor ambient to assure design motor and starter life
Carrier Confidential
Motor Heat Rejection
Competitor Open Motor Drive
Open motors require no moisture intrusion at start up. Moisture in windings at start up/after power loss can cause motor failure.
Motor Anti-Condensation Heaters
Megger motor test required $ for insulation checks by technician after idle periods
Strip Winding Heater required to prevent moisture intrusion
$ in motor heater equipment costs$$ yearly heater wattage costs
User Full Load Tons Tons 500IPLV kW/ton 0.34Hours of Operation Hrs 3000
Calculated Annual Mech Room Cooling kW 5,046Annual kW Strip Heaters kW 3,456Total Open Motor Parasitic kW 8,502
Actual IPLV kW/ton 0.350
Water Cooled Oil Cooler
• Requires regular maintenance (scaling/cleaning with acid solution)
• Additional failure modes created– Oil in water (EH&S safety issue)– Water in oil (catastrophic failure)
Additional Costs for Purchasing Open Drive Design
• Maintenance and Operating Costs– Weekly – check the shaft seal
oil bottle– 3-5 Year - Shaft Seal
maintenance cost – Yearly – Motor Air Filter
maintenance cost – As Necessary – Top off
refrigerant charge – As Necessary – Winding
cleaning maintenance cost – As Necessary – Possible
Megger Motor maintenance check
– Yearly - Mechanical Room Cooling operating cost
– Yearly – Strip Heater operating cost
• Efficiency Comparison– 3% for open motor– 4% for harmonic filter– 1-3% refrigerant loss
DID YOU FACTOR AN ADDITIONAL $ IN COSTS FOR YOUR CHILLER
• Additional Unanticipated Costs– Air Conditioner for
Mechanical Room – TEWAC Motor – Harmonic Filter – Storage Tank – Sound Blanket – Motor Heaters
Open Drive vs. Hermetic
• Home refrigerator is a hermetic design
Automobile is an open design
Which design requires more refrigerant to be added?
Advantages of Semi Hermetic Design
Semi-Hermetic Motor• Refrigerant cooled motor keeps
motor heat out of the mechanical room• Saves $ to cool mechanical
room• Minimizes alignment, vibration
and shaft seal maintenance of open motors• Saves $ in maintenance and
shaft seal replacement costs• Refrigerant cooled motors
operate in a clean, cool environment.• Saves $ in motor repair costs
Hermetic Motor vs. Open Drive Motor
Carrier Corporation announces refrigerant warranty for all new centrifugal chillers sold in USA at Engineering Green Building Conference July 20, 2004.
Warranty applicable for all Evergreen centrifugal chillers shipped after October 1, 2004.
Carrier will cover refrigerant leaks above 0.1% for the first five years of operation and for the life of the chiller if the owner has a service contract with Carrier Commercial Service.
R134a Refrigerant Warranty
The Right Technology
Questions
Chiller Part Load Performance
Part load performance can be…• Part load capacity
• 90%, 80%, 70%…
OR• Lower condensing temperature
• Condenser water off the tower (80, 75, 70 degrees…)
• Lower outdoor air temp (90, 85, 80 degrees…)
Full load is defined as 100% load on design day! All other conditions are part load.
What is Part Load?
IPLVOR
NPLV = 0.01 + 0.42 + 0.45 + 0.12 A B C D
1
1% 42% 45% 12%
ECWT 85 75 65 65
WEIGHT %
LOAD 100% 75% 50% 25%
ARI Part Load Weighting Factors
99%
ARI 550-590
Compressor Input kW ~
Mass Flow X Lift
Load
Chiller
CoolingTower
Compressor/Cycle Efficiency
Like pumps, chiller energy consumption is a function of mass flow and differential pressure. KW = Tons x Lift
Chiller Energy
Imagine carrying a backpack of bricks up 55 flights of stairs.
Lift Requires Energy
97 F Saturated Condensing Temperature
55
42 F Saturated Suction Temperature
Refrigerant TemperatureFor refrigerant to condense, it must be warmer than leaving condenser water.
95 F + 2F approach = 97F
To boil, refrigerant must be colder than leaving chilled water. 44F – 2F approach = 42F
95F
44F
85F
54F
Refrigerant temperatures are based on leaving water temperatures! Lift = 97F-42F = 55F
42 F / 40 PSI95F /97 F / 120 PSI
80F /82F
SAT. LIQUID
SAT. VAPOR
Refrigerant Effect(Capacity)
Com
pres
sion
Heat Rejection
Enthalpy
SCT
Reduced Lift
Pre
ssu
re
42
82
97
SST
Lower Lift = Less Work = Lower kW
Pressure Enthalpy Chart-LIFT
Lift = Sat Condensing Temp – Sat Suction TempLift 1 = 97 – 42 = 55 deg FLift 2 = 82 – 42 = 40 deg F BETTER!!
42 F / 40 PSI95F /97 F / 120 PSI
80F /82F / 90 PSI
59F /61F /60 PSI
SAT. LIQUID
SAT. VAPOR
Refrigerant Effect(Capacity)
Com
pres
sion
Heat Rejection
Enthalpy
SCT
Reduced Lift
Pre
ssu
re
42
82
97
SST
Lower Lift = Less Work = Lower kW
Pressure Enthalpy Chart-PRESSURE
60 PSI-40 PSI = 20 PSI. Sufficient differential to provide proper refrigerant flow, oil return, and efficient consistent operation.
How centrifugals change speed
Flow ~ V, ATo increase flow, increase rotor
speed (with fixed flow area)
Lift ~ V2
To increase lift, increase speed
Power ~ Flow x Lift ~ V3
Without LIFT reduction, speed can not reduce
A reduction in LIFT allows a speed reduction.Lift is a function of the speed squared.Power is related to the speed cubed!
V
Diameter
FlowArea
Ideal Fan Laws Dictate the relationship between speed, flow and lift
All centrifugal chillers are subject to Ideal Fan Law – Minimum speed approximately 65%, IGV
for remainder
SAVINGS FROM COLD CONDENSER WATER
• Three 1400 ton Carrier 19XRV variable speed chillers• Data Center• Analyze savings operating chillers with 55 deg F versus 65
deg F and 75 deg F• 0.13 $/kwh simple rate
Net Present Worth Savings from 55 F vs…
ECWT 65F 75F
20 year life cycle $217,550 $468,880
Entering Condenser Water Temperature
570
600
630
643
630
Tons
85oF 75oF 70oF <65oF80oF
550
CarrierCarrier capacity increases as
condenser water temperature decreases
Additional Capacity
Questions
Chiller Heat Recovery
• Instead of rejecting heat to the condenser water loop, why not use this heat?
79
Heat Recovery Benefits
Chillers can transfer heat for as little as 25% of the cost required to create heat with a boiler.
Natural Gas Boiler
($12/1,000 ft3)
Electric Boiler ($0.10/kWh)
Fuel Oil Boiler ($ 3/gal)
10%
20%
30%
40%
50%
60%
70%
80%
50%
71% 75%
30XW Heat Recovery Chiller Savings vs. Boilers
Hot Water SystemsHow can we capture sufficient heat for useful purposes?
Building Heat
Service Hot Water
Process Heat
Why Heat Recovery?ASHRAE 90.1-2004 Heat Recovery for Service Water Heating, Section § 6.5.6.2
• Operates 24 hours a day• Total heat rejection exceeds about 400 tons of chiller
capacity • Service water-heating load exceeds 1,000,000 Btu/h
– 1,000 bed nursing home or 75 room full service hotel
Provide the smaller of:• 60% of the peak heat rejection load at design conditionsor• preheat of the peak service hot water draw to 85°F.
Exceptions:• Minimum 30% recovery from condenser water heat for
space heating or• 60% or more of service water heating from site solar or
cogeneration, condensate subcooling, or solar panels.
Condenser Water Heat RecoveryHEX Captures Condenser Water Heat“Wasted” Heat for Service Hot Water Make-up85°F Make-up Water Caution: Higher LCWT Increases Chiller Lift, Reduces Efficiency
Heat Out
Heat In
Heat Out
83
Confirming Savings
Real World Examplei-Vu® Controls on 30XW Heat Machine at Charlotte
Factory
30XW
Over $100,000 per year in energy savings!!
Questions
Thank You ForToday’s Opportunity