PSW-Series ENG Manual
-
Upload
mudassir-hashmi -
Category
Documents
-
view
217 -
download
0
Transcript of PSW-Series ENG Manual
-
7/22/2019 PSW-Series ENG Manual
1/156
Multi-Range DC Power Supply
PSW Series
USER MANUALGW INSTEK PART NO. 82SW-80400MC1
ISO-9001 CERTIFIED MANUFACTURER
-
7/22/2019 PSW-Series ENG Manual
2/156
This manual contains proprietary information, which is protected bycopyright. All rights are reserved. No part of this manual may bephotocopied, reproduced or translated to another language withoutprior written consent of Good Will company.
The information in this manual was correct at the time of printing.However, Good Will continues to improve products and reserves therights to change specification, equipment, and maintenanceprocedures at any time without notice.Good Will Instrument Co., Ltd.No. 7-1, Jhongsing Rd., Tucheng Dist., New Taipei City 236, Taiwan
-
7/22/2019 PSW-Series ENG Manual
3/156
SAFETY INSTRUCTIONS
3
Table of ContentsSAFETY INSTRUCTIONS 5GETTING STARTED 9
PSW Series Overview ........................... 10Appearance .......................................... 15Theory of Operation ............................. 21
OPERATION 33Set Up .................................................. 35 Basic Operation ................................... 49Parallel / Series Operation ................... 62Test Scripts .......................................... 76
CONFIGURATION 84Configuration ....................................... 85
ANALOG CONTROL 101Analog Remote Control Overview ....... 102Remote Monitoring ............................ 118
COMMUNICATION INTERFACE 123Interface Configuration ...................... 124
MAINTENANCE 135FAQ 137APPENDIX 139
PSW Default Settings ......................... 139Error Messages & Messages .............. 141
LCD Display Format ........................... 141
-
7/22/2019 PSW-Series ENG Manual
4/156
PSW Series User Manual
4
PSW Specifications ............................ 142PSW Dimensions ............................... 151Declaration of Conformity .................. 154
INDEX 155
-
7/22/2019 PSW-Series ENG Manual
5/156
SAFETY INSTRUCTIONS
5
SAFETY INSTRUCTIONSThis chapter contains important safetyinstructions that you must follow duringoperation and storage. Read the following beforeany operation to insure your safety and to keepthe instrument in the best possible condition.
Safety Symbols
These safety symbols may appear in this manual or on theinstrument.
WARNINGWarning: Identifies conditions or practices thatcould result in injury or loss of life.
CAUTIONCaution: Identifies conditions or practices thatcould result in damage to the PSW or to otherproperties.
DANGER High Voltage
Attention Refer to the Manual
Protective Conductor Terminal
Earth (ground) Terminal
-
7/22/2019 PSW-Series ENG Manual
6/156
PSW Series User Manual
6
Do not dispose electronic equipment as unsortedmunicipal waste. Please use a separate collectionfacility or contact the supplier from which this
instrument was purchased.
Safety Guidelines
GeneralGuideline
CAUTION
Do not place any heavy object on the PSW.
Avoid severe impact or rough handling thatleads to damaging the PSW.
Do not discharge static electricity to the PSW. Use only mating connectors, not bare wires, for
the terminals.
Do not block the cooling fan opening.
Do not disassemble the PSW unless you arequalified.
(Measurement categories) EN 61010-1:2001 specifies themeasurement categories and their requirements as follows. the
PSW falls under category II.
Measurement category IV is for measurement performed at thesource of low-voltage installation.
Measurement category III is for measurement performed in thebuilding installation.
Measurement category II is for measurement performed on thecircuits directly connected to the low voltage installation.
Measurement category I is for measurements performed oncircuits not directly connected to Mains.
Power Supply
WARNING
AC Input voltage range: 85VAC~265VAC
Frequency: 47Hz~63Hz
To avoid electrical shock connect the protectivegrounding conductor of the AC power cord toan earth ground.
-
7/22/2019 PSW-Series ENG Manual
7/156
SAFETY INSTRUCTIONS
7
Cleaning the PSW Disconnect the power cord before cleaning.
Use a soft cloth dampened in a solution of milddetergent and water. Do not spray any liquid.
Do not use chemicals containing harsh materialsuch as benzene, toluene, xylene, and acetone.
OperationEnvironment
Location: Indoor, no direct sunlight, dust free,almost non-conductive pollution (Note below)
Relative Humidity: 20%~ 85%
Altitude: < 2000m
Temperature: 0C to 50C
(Pollution Degree) EN 61010-1:2001 specifies the pollution degreesand their requirements as follows. The PSW falls under degree 2.
Pollution refers to addition of foreign matter, solid, liquid, orgaseous (ionized gases), that may produce a reduction of dielectricstrength or surface resistivity.
Pollution degree 1: No pollution or only dry, non-conductivepollution occurs. The pollution has no influence.
Pollution degree 2: Normally only non-conductive pollutionoccurs. Occasionally, however, a temporary conductivity causedby condensation must be expected.
Pollution degree 3: Conductive pollution occurs, or dry, non-conductive pollution occurs which becomes conductive due tocondensation which is expected. In such conditions, equipmentis normally protected against exposure to direct sunlight,precipitation, and full wind pressure, but neither temperaturenor humidity is controlled.
Storage
environment
Location: Indoor
Temperature: -25C to 70C
Relative Humidity:
-
7/22/2019 PSW-Series ENG Manual
8/156
PSW Series User Manual
8
Power cord for the United Kingdom
When using the power supply in the United Kingdom, make surethe power cord meets the following safety instructions.
NOTE: This lead/appliance must only be wired by competent persons
WARNING: THIS APPLIANCE MUST BE EARTHEDIMPORTANT: The wires in this lead are coloured in accordance with thefollowing code:Green/ Yellow: EarthBlue: NeutralBrown: Live (Phase)
As the colours of the wires in main leads may not correspond withthe coloured marking identified in your plug/appliance, proceedas follows:
The wire which is coloured Green & Yellow must be connected tothe Earth terminal marked with either the letter E, the earth symbol
or coloured Green/Green & Yellow.
The wire which is coloured Blue must be connected to the terminalwhich is marked with the letter N or coloured Blue or Black.
The wire which is coloured Brown must be connected to theterminal marked with the letter L or P or coloured Brown or Red.
If in doubt, consult the instructions provided with the equipmentor contact the supplier.
This cable/appliance should be protected by a suitably rated andapproved HBC mains fuse: refer to the rating information on theequipment and/or user instructions for details. As a guide, a cableof 0.75mm2should be protected by a 3A or 5A fuse. Larger
conductors would normally require 13A types, depending on theconnection method used.
Any exposed wiring from a cable, plug or connection that isengaged in a live socket is extremely hazardous. If a cable or plug isdeemed hazardous, turn off the mains power and remove the cable,any fuses and fuse assemblies. All hazardous wiring must beimmediately destroyed and replaced in accordance to the abovestandard.
-
7/22/2019 PSW-Series ENG Manual
9/156
GETTING STARTED
9
GETTING STARTEDThis chapter describes the power supply in anutshell, including its main features and front /rear panel introduction. After going through theoverview, please read the theory of operation tobecome familiar with the operating modes,
protection modes and other safety considerations.
PSW Series Overview 10Series lineup .................................................................................................................10Main Features...............................................................................................................11
Accessories ...................................................................................................................12Package Contents ........................................................................................................14Appearance 15PSW Front Panel .........................................................................................................15Rear Panel .....................................................................................................................18
-
7/22/2019 PSW-Series ENG Manual
10/156
PSW Series User Manual
1
PSW Series Overview
Series lineupThe PSW series consists of 9 models, divided into 3 different modeltypes covering 3 power capacities: Type I (360 Watt), Type II (720Watt) and Type III (1080 Watt).
Model name Type Voltage Rating Current Rating Power
PSW 30-36 Type I 0~30V 0~36A 360W
PSW 80-13.5 Type I 0~80V 0~13.5A 360WPSW 160-7.2 Type I 0~160V 0~7.2A 360W
PSW 30-72 Type II 0~30V 0~72A 720W
PSW 80-27 Type II 0~80V 0~27A 720W
PSW 160-14.4 Type II 0~160V 0~14.4A 720W
PSW 30-108 Type III 0~30V 0~108A 1080W
PSW 80-40.5 Type III 0~80V 0~40.5A 1080WPSW 160-21.6 Type III 0~160V 0~21.6A 1080W
Apart from the differences in output, each unit differs in size. The720 and 1080 watt models are larger than the 360 watt models toaccommodate the increase in power.
360 Watt models
Type I
A
W
V
W
%W10080604020
ISR
C C
DLY
ALM
RMT
C V
VSR
Function OVP/OCP SetOutput
PWR DSPLLock/LocalTest
PSW 30-36 360W
Multi-RangeDC Power Supply Voltage
Current
720 Watt models
Type II
A
W
V
W
%W10080604020
ISR
C C
DLY
ALM
RMT
C V
VSR
Function OVP/OCP SetOutput
PWR DSPLLock/LocalTest
PSW 30-72 720W
Voltage
Current
Multi-RangeDC Power Supply
1080 Watt models
Type III
A
W
V
W
%W10080604020
ISR
C C
DLY
ALM
RMT
C V
VSR
Function OVP/OCP SetOutput
PWR DSPLLock/LocalTest
PSW 30-108 1080W
Voltage
Current
Multi-Range DC Power Supply
-
7/22/2019 PSW-Series ENG Manual
11/156
GETTING STARTED
11
Main Features
Performance High performance/power
Power efficient switching type power supply
Low impact on load devices
Fast transient recovery time of 1ms
Fast output response time
Features OVP, OCP and OTP protection
Adjustable voltage and current slew rates
User adjustable bleeder control to quicklydissipate the power after shutdown to safelevels.
Extensive remote monitoring and controloptions
Support for serial and parallel connections
Power on configuration settings.
Supports test scripts
Web server monitoring and control
Interface Ethernet port
Analog connector for analog voltage and currentmonitoring
USB host and device port
-
7/22/2019 PSW-Series ENG Manual
12/156
PSW Series User Manual
12
Accessories
StandardAccessories Part number Description
Region dependant User manual
4323-30600101 Power cord (Type I/II)
4320-91001101 Power cord (Type III)
63SC-XF100201 Output terminal cover: top
63SC-XF100301 Output terminal cover:bottom
GTL-123 Test leads: 1x red, 1x black
GTL-240 USB Cable
PSW-004 Basic Accessory Kit:
M4 terminal screws andwashers x2, M8 terminal
bolts, nuts and washers x2,Air filter x1, Analog controlprotection dummy x1,Analog control lock level x1
OptionalAccessories
Part number Description
GET-001 Extended terminal
PSW-001 Accessory Kit:Pin contact x10, Socket x1,Protection cover x1
PSW-002 Simple IDCTool
PSW-003 Contact
Removal Tool
-
7/22/2019 PSW-Series ENG Manual
13/156
GETTING STARTED
13
PSW-005 Series operation cable for 2units.
PSW-006 Parallel operation cable for
2 units.PSW-007 Parallel operation cable for
3 units.
GRA-410-J Rack mount adapter (JIS)
GRA-410-E Rack mount adapter (EIA)
GUG-001 GPIB to USB adapter
GTL-240 USB Cable
57RG-30B00201 Large filter (Type II/III)
Download Name Description
psw_cdc.inf USB driver
-
7/22/2019 PSW-Series ENG Manual
14/156
PSW Series User Manual
14
Package Contents
Check the contents before using the PSW.
Opening the box
Contents(single unit)
Main unit
Output terminal cover(top x1, bottom x1)
Test leads (red x1,black x1)
M4 terminal screwsand washers x2
Air filter x1
L-type USB cable x1
Power cord x1 (regiondependent)
Analog controlprotection dummy x1
Analog control lock
lever x1
M8 terminal bolts,nuts and washers X2
-
7/22/2019 PSW-Series ENG Manual
15/156
GETTING STARTED
15
Appearance
PSW Front PanelPSW 160-14.4, PSW 80-27, PSW 30-72 (720W)
A
W
V
W
%W10080604020
ISR
C C
DLY
ALM
RMT
C V
VSR
Funct ion OVP/OCP SetOutput
PWR DSPLLock/LocalTest
PSW 30-72 720W
Voltage
Current
Multi-Range DC Power Supply
Current
knob
Outputkey
Powerswitch
Voltageknob
USB Aport
Display
Coverpanel
Functionkeys
PSW 160-21.6, PSW 80-40.5, PSW 30-108(1080W)
PSW 160-7.2,PSW 80-13.5,PSW 30-36 (360W)
A
W
V
W
%W10080604020
ISR
C C
DLY
ALM
RMT
C V
VSR
Funct ion OVP/OCP SetOutput
PWR DSPLLock/LocalTest
PSW 30-108 1080WVoltage
Current
Multi-Range DC Power Supply
A
W
V
W
%W10080604020
ISR
C C
DLY
ALM
RMT
C V
VSR
Funct ion OVP/OCP SetOutput
PWR DSPLLock/LocalTest
PSW 30-36 360WMulti-Range DC Power Supply Voltage
Current
-
7/22/2019 PSW-Series ENG Manual
16/156
PSW Series User Manual
16
Function Keys The Function keys along with the Output key will
light up when a key is active.
Function
The Function key is used toconfigure the power supply.
OVP/OCP
Set the over current or overvoltage protection levels.
Set
Sets the current and voltage limits.
Test
Used to run customized scripts fortesting.
Lock/Local
Locks or unlocks the panel keys toprevent accidentally changingpanel settings.
PWR DSPL
Toggles the display from viewingV/AV/WA/W.
DisplayIndicatorsVSR
Voltage Slew RateC V Constant Voltage Mode
RMT Remote Control Mode
ALM Alarm on
DLY Delay Output
C C Constant Current Mode
ISR Current Slew Rate
-
7/22/2019 PSW-Series ENG Manual
17/156
GETTING STARTED
17
20 40 60 80 100 % W
Power bar
Indicates the current power outputas a percentage.
Voltage Knob Voltage
Sets the voltage.
Current Knob Current
Sets the current.
Output Output
Press to turn on the output. TheOutput key will light up when theoutput is active.
USB USB A port for data transfer,loading test scripts etc.
Power Switch Used to turn the power on/off.
-
7/22/2019 PSW-Series ENG Manual
18/156
PSW Series User Manual
18
Rear Panel
PSW 160-14.4, PSW 80-27, PSW 30-72 (720W)
Outputterminal(+)
Fan
Outputterminal(-)
USB Bport
LAN
AC Input
Sense-terminal
Analog controlconnector
LAN100 240V
1000VA MAX.
AC
47 63Hz
SER.NO. LABEL
Sense+terminal
PSW 160-21.6, PSW 80-40.5, PSW 30-108(1080W)
PSW 160-7.2,PSW 80-13.5,PSW 30-36 (360W)
1 00 2 40 VAC
1500VAMAX.4 7 6 3H z
LANLN
SER.NO. LABEL
AC Input
LAN
100 240V
4 7 6 3H z 5 00 VA MAX.
AC
-
7/22/2019 PSW-Series ENG Manual
19/156
GETTING STARTED
19
Analog ControlConnector
Standard 26 pin MIL connector(OMRON XG4 IDC plug).
The analog control connector isused to monitor current and voltageoutput, machine status (OVP, OCP,OTP etc.), and for analog control ofthe current and voltage output.
Use an OMRON XG5 IDC socket asthe mating socket.
Output Terminals Positive (+) and negative (-) outputterminals.
Chassis ground
Sense (-) and Sense (+) terminals.
USB B port The USB B port is used for remotecontrol.
Fans Temperature controlled fans
Ethernet Port LAN
The ethernet port is used for remotecontrol and digital monitoring froma PC.
Line VoltageInput
(Type I/TypeII)
Type I: PSW 30-36/80-13.5/160-7.2
Type II: PSW 30-72/80-27/160-14.4
Voltage Input: 100~240 VAC
Line frequency: 50Hz/60 Hz
(Automatically switchable)
-
7/22/2019 PSW-Series ENG Manual
20/156
PSW Series User Manual
2
Line VoltageInput
(Type III)
LN
Type III:PSW 30-108/80-40.5/160-21.6
Voltage Input: 100~240 VAC
Line frequency: 50Hz/60 Hz(Automatically switchable)
-
7/22/2019 PSW-Series ENG Manual
21/156
GETTING STARTED
21
Theory of OperationThe theory of operation chapter describes the basic principles of
operation, protection modes and important considerations thatmust be taken into account before use.
Operating Area Description
Background The PSW power supplies are regulated DCpower supplies with a high voltage and current
output. These operate in CC or CV modewithin a wide operating range limited only bythe output power.
The operating area of each power supply isdetermined by the rated output power as wellas the voltage and current rating. For examplethe operating area and rated power output forthe PSW 30-36 is shown below.
Voltage
Current
30
360W rated power
10
12 36
PSW 30-36 Operating Area
When the power supply is configured so thatthe total output (current x voltage output) isless than the rated power output, the powersupply functions as a typical constant current,constant voltage power supply.
If however, the power supply is configuredsuch that the total output (current x voltageoutput) exceeds the rated power output, the
-
7/22/2019 PSW-Series ENG Manual
22/156
PSW Series User Manual
22
effective output is actually limited to the powerlimit of the unit. In this case the output currentand voltage then depend purely on the loadvalue.
Below is a comparison of the operating areas ofeach power supply.
PSW 160V Series Operating Area
020
160
Current (A)
Voltage(V
)
406080
140
0 5 10 15 20
180
25
Type IIIType IIType I
100120
2.25 4.5 6.75
160
50
14.4 21.67.2
PSW 80V Series Operating Area
Current (A)
Voltage(V)
26.6
4.5 9.0 13.5
80
Type IIIType IIType I
30 4540205 10 15 250 35
0
20
40
60
8090
27 40.5
-
7/22/2019 PSW-Series ENG Manual
23/156
GETTING STARTED
23
PSW 30V Series Operating Area
0
5
30
Current (A)
Voltage(V)
10
15
20
25
0 20 40 60 80 100
10
12 24 36
30
35
120
Type IIIType IIType I
72 108
CC and CV Mode
CC and CV modeDescription
When the power supply is operating inconstant current mode (CC) a constant currentwill be supplied to the load. When in constant
current mode the voltage output can vary,whilst the current remains constant. When theload resistance increases to the point where thecurrent limit (ISET) can no longer be sustainedthe power supply switches to CV mode. Thepoint where the power supply switches modesis the crossover point.
When the power supply is operating in CVmode, a constant voltage will be supplied tothe load, whilst the current will vary as theload varies. At the point that the loadresistance is too low to maintain a constantvoltage, the power supply will switch to CCmode and maintain the set current limit.
The conditions that determine whether the
power supply operates in CC or CV modedepends on the set current (ISET), the set voltage
-
7/22/2019 PSW-Series ENG Manual
24/156
PSW Series User Manual
24
(VSET), the load resistance (RL) and the criticalresistance (RC). The critical resistance isdetermined by VSET/ISET. The power supplywill operate in CV mode when the load
resistance is greater than the critical resistance.This means that the voltage output will beequal to the VSETvoltage but the current will beless than ISET. If the load resistance is reducedto the point that the current output reaches theISETlevel, the power supply switches to CCmode.
Conversely the power supply will operate inCC mode when the load resistance is less thanthe critical resistance. In CC mode the currentoutput is equal to ISETand the voltage output isless than VSET.
RL=RC
RLRCCrossover
point
-
7/22/2019 PSW-Series ENG Manual
25/156
GETTING STARTED
25
Slew Rate
Theory The PSW has selectable slew rates for CC andCV mode. This gives the PSW power supplythe ability to limit the current/voltage draw ofthe power supply. Slew rate settings aredivided into High Speed Priority and SlewRate Priority. High Speed Priority modedisables slew rate settings for CC or CV mode.Slew Rate Priority mode allows for user
adjustable slew rates for CC or CV mode. Therising and falling slew rate can be setindependently.
Slew rate=
Disabled Slew rate =
Enabled
Bleeder Control
Background The PSW DC power supplies employ a bleedresistor in parallel with the output terminals.
PSW LoadBleed
resistor
Bleed resistors are designed to dissipate thepower from the power supply filter capacitors
when power is turned off and the load isdisconnected. Without a bleed resistor, power
-
7/22/2019 PSW-Series ENG Manual
26/156
PSW Series User Manual
26
may remain charged on the filter capacitors forsome time and be potentially hazardous.
In addition, bleed resistors also allow for
smoother voltage regulation of the powersupply as the bleed resistor acts as a minimumvoltage load.
The bleed resistance can be turned on or offusing the configuration settings.
NoteBy default the bleed resistance is on. For batterycharging applications, be sure to turn the bleedresistance off as the bleed resistor can dischargethe connected battery when the unit is off.
Internal Resistance
Background On the PSW, the internal resistance of thepower supply can be user-defined in software.
(Internal Resistance Setting, page89). When theinternal resistance is set it can be seen as aresistance in series with the positive outputterminal. This allows the power supply tosimulate power sources that have internalresistances such as lead acid batteries.
InternalResistance Range
Unit Model Internal Resistance Range
PSW 30-36 0.000 ~ 0.833PSW 30-72 0.000 ~ 0.417PSW 30-108 0.000 ~ 0.278PSW 80-13.5 0.000 ~ 5.926PSW 80-27 0.000 ~ 2.963PSW 80-40.5 0.000 ~ 1.975PSW 160-7.2 0.000 ~ 22.222PSW 160-14.4 0.000 ~ 11.111PSW 160-21.6 0.000 ~ 7.407
-
7/22/2019 PSW-Series ENG Manual
27/156
GETTING STARTED
27
Alarms
The PSW power supplies have a number of protection features.
When one of the protection alarms are set, the ALM icon on thedisplay will be lit. For details on how to set the protection modes,please see page49.
OVP Overvoltage protection (OVP) prevents a highvoltage from damaging the load.
OCP Overcurrent protection prevents high current
from damaging the load.
OTP Over temperature protection protects theinstrument from overheating.
Power Switch Trip When the Power Switch Trip configurationsetting is enabled, the power supply willautomatically shut down when a protection
setting has been tripped (OCP, OVP, OTP).
Alarm output Alarms are output via the analog controlconnector. The alarm output is an isolatedopen-collector photo coupler output.
-
7/22/2019 PSW-Series ENG Manual
28/156
PSW Series User Manual
28
Considerations
The following situations should be taken into consideration when
using the power supply.
Inrush current When the power supply switch is first turnedon, an inrush current is generated. Ensure thereis enough power available for the powersupply when first turned on, especially if anumber of units are turned on at the sametime.
CautionAllow at least 15 seconds between cycling thepower. Cycling the power on and off quickly cancause the inrush current limiting circuit to fail aswell as reduce the working life of the input fuseand power switch.
Pulsed or Peaked
loads
When the load has current peaks or is pulsed, it
is possible for the maximum current to exceedthe mean current value. The PSW powersupply ammeter only indicates mean currentvalues, which means for pulsed current loads,the actual current can exceed the indicatedvalue. For pulsed loads, the current limit mustbe increased, or a power supply with a greatercapacity must be chosen. As shown below, apulsed load may exceed the current limit and
the indicated current on the power supplyammeter.
-
7/22/2019 PSW-Series ENG Manual
29/156
GETTING STARTED
29
Current limit
level
Measured
Ammeter
current
Reverse Current:Regenerative load
When the power supply is connected to aregenerative load such as a transformer or
inverter, reverse current will feed back to thepower supply. The PSW power supply cannotabsorb reverse current. For loads that createreverse current, connect a resistor in parallel tothe power supply to bypass the reversecurrent. This description only applies when thebleed resistance is off.
PSW LoadResistor
Reverse current
NoteThe current output will decrease by the amount ofcurrent absorbed by the resistor.
Ensure the resistor used can withstand the power
capacity of the power supply/load.
-
7/22/2019 PSW-Series ENG Manual
30/156
PSW Series User Manual
3
Reverse Current:Accumulativeenergy.
When the power supply is connected to a loadsuch as a battery, reverse current may flowback to the power supply. To prevent damage
to the power supply, use a reverse-current-protection diode in series between the powersupply and load.
PSW Load
Diode
CAUTIONEnsure the reverse withstand voltage of the diodeis able to withstand 2 times the rated outputvoltage of the power supply and the forwardcurrent capacity can withstand 3 to 10 times therated output current of the power supply.
Ensure the diode is able to withstand the heatgenerated in the following scenarios.
When the diode is used to limit reverse voltage,remote sensing cannot be used.
-
7/22/2019 PSW-Series ENG Manual
31/156
GETTING STARTED
31
Grounding
The output terminals of the PSW power supplies are isolated with
respect to the protective grounding terminal. The insulationcapacity of the load, the load cables and other connected devicesmust be taken into consideration when connected to the protectiveground or when floating.
Floating As the output terminals are floating, the loadand all load cables must have an insulationcapacity that is greater than the isolation
voltage of the power supply.
PSWLoad
Ext-V
Ext-R
Analog
connector
( ) Insulation capacity isolation voltage
of power supply
WARNINGIf the insulation capacity of the load and loadcables is not greater than the isolation voltage ofthe power supply, electric shock may occur.
-
7/22/2019 PSW-Series ENG Manual
32/156
PSW Series User Manual
32
Grounded outputterminal
If the positive or negative terminal is connectedto the protective ground terminal, theinsulation capacity needed for the load and
load cables is greatly reduced. The insulationcapacity only needs to be greater than themaximum output voltage of the power supplywith respect to ground.
PSWLoad
Ext-V
Ext-R
Analog
connector
( ) Insulation capacity voltage of power
supply with respect to ground
CAUTIONIf using external voltage control, do not ground
the external voltage terminal as this will create ashort circuit.
-
7/22/2019 PSW-Series ENG Manual
33/156
OPERATION
33
OPERATIONSet Up 35Line Voltage Connection Type III Models .........................................................35Filter Installation .........................................................................................................37Power Up ......................................................................................................................38
Wire Gauge Considerations ......................................................................................39Output Terminals ........................................................................................................40Using the Output Terminal Cover ...........................................................................42Using the Rack Mount Kit ........................................................................................43How to Use the Instrument ......................................................................................43Reset to Factory Default Settings .............................................................................45
View System Version and Build Date .....................................................................46Basic Operation 49Setting OVP/OCP Levels .........................................................................................49Set to C.V. Mode .........................................................................................................51Set to C.C. Mode .........................................................................................................54Display Modes .............................................................................................................57Panel Lock ....................................................................................................................58Remote Sense ...............................................................................................................59Parallel / Series Operation 62Master-Slave Parallel Overview ................................................................................63Master-Slave Parallel Connection .............................................................................65Master-Slave Parallel Operation ...............................................................................68Master-Slave Series Overview ...................................................................................70Master-Slave Series Connection ...............................................................................72Master-Slave Series Operation ..................................................................................74Test Scripts 76
Test Script File Format ..............................................................................................77Test Script Settings .....................................................................................................77Setting the Test Script Settings .................................................................................78Load Test Script from USB .......................................................................................79
-
7/22/2019 PSW-Series ENG Manual
34/156
PSW Series User Manual
34
Run Test Script ........................................................................................................... 80Export Test Script to USB ....................................................................................... 81Remove Test Script .................................................................................................... 82
-
7/22/2019 PSW-Series ENG Manual
35/156
OPERATION
35
Set Up
Line Voltage Connection Type III Models
Background The Type III (PSW 30-108/PSW 80-40.5/PSW160-21.6) models use a universal power inputthat can be used with 100 and 200 VACsystems. To connect or replace the power cord(GW Instek part number: 4320-91001101, usethe procedure below:
WarningThe following procedure should only be attemptedby competent persons.
Ensure the AC power cord is not connected topower.
Removal 1. Turn off the power switch.
1
2. Unscrew the power cordprotective sheath.
3. Remove the 2 screwsholding the power cordcover and remove.
3
2
-
7/22/2019 PSW-Series ENG Manual
36/156
PSW Series User Manual
36
4. Slide the cover off the ACterminals.
5. Remove the AC powercord wires.
5
4
Installation 1. Connect the AC powercord wires to the AC inputterminals.
White/BlueNeutral(N)
Green/Green-
yellowGND ( )
Black/BrownLine(L)
LN
Line
N
eutral
G
round
2. Set the cover back over theAC terminals.
2
3. Re-install the power cordcover.
4. Screw the power cordsheath back onto the cover. 3
4
-
7/22/2019 PSW-Series ENG Manual
37/156
OPERATION
37
Filter Installation
Background The PSW has a small filter (GW Instek partnumber, 57RG-30B00101) that must first beinserted under the control panel beforeoperation. The small filter must be inserted forall model types (Type I/II/II).
Steps 1. Insert the small filterin the open area
under the controlpanel.
Type II shown as anexample
2. The unit is now ready to power up.
-
7/22/2019 PSW-Series ENG Manual
38/156
PSW Series User Manual
38
Power Up
Steps 1. Type I or II: Connect thepower cord to the rearpanel socket.
Type III: Connect thepower cord to theuniversal power input.
Page35
2. Press the POWER key. If used for the first time,the default settings will appear on the display,otherwise The PSW recovers the state rightbefore the power was last turned OFF.
For default configuration settings, see page139.
V
A
CAUTIONThe power supply takes around 8 seconds to fullyturn on and shutdown.
Do not turn the power on and off quickly. Pleasewait for the display to fully turn off.
-
7/22/2019 PSW-Series ENG Manual
39/156
OPERATION
39
Wire Gauge Considerations
Background Before connecting the output terminals to aload, the wire gauge of the cables should beconsidered.
It is essential that the current capacity of theload cables is adequate. The rating of the cablesmust equal or exceed the maximum currentrated output of the instrument.
Recommendedwire gauge
Wire Gauge Maximum Current
20 2.5A18 4A16 6A14 10A12 16A10 21A8 36A
6 61A4 97A
-
7/22/2019 PSW-Series ENG Manual
40/156
PSW Series User Manual
4
Output Terminals
Background Before connecting the output terminals to theload, first consider whether voltage sense willbe used, the gauge of the cable wiring and thewithstand voltage of the cables and load.
The output terminals can be connected to loadcables using M4 sized screws or M8 sized bolts.
WARNING Dangerous voltages. Ensure that the power to theinstrument is disabled before handling the powersupply output terminals. Failing to do so may leadto electric shock.
Steps 1. Turn the power switch off.
2. Remove the output terminal cover. Page42
3. If necessary, screw the chassisground terminal to either thepositive or negative terminal. Seethe grounding chapter for details.
Page31
Sense joining plates
Ground
4. Choose a suitable wire gauge for
the load cables.
Page39
-
7/22/2019 PSW-Series ENG Manual
41/156
OPERATION
41
5. Choose a suitable crimp for the terminals.
6. If using voltage sense, remove the
sense terminal joining plates andconnect sensing wires to theload(s).
Page59
7. Connect the positive load cable to the positiveoutput terminal and the negative cable to thenegative output terminal.
8.
Reattach the output terminalcover. Page42
Connectionwithout sensewiring
Using M4 screws
Positivepotential
Negativepotential
Using M8 bolts
Positivepotential
Negativepotential
Connection withsense wiring
Using M4 screwsSense -
Sense +
Using M8 boltsSense -
Sense +
-
7/22/2019 PSW-Series ENG Manual
42/156
PSW Series User Manual
42
Using the Output Terminal Cover
Steps 1. Remove the screw holding the top cover to thebottom cover.
2. Line-up the bottom cover with the notches inthe output terminals.
3. Place the top terminal cover over the bottomcover.
Details2
3
1
4. Use your thumb to slide the terminal coversshut, as shown in the diagram below.
5. When the top and bottom covers are flush, re-insert the screw that was removed in step 1.
4
5
-
7/22/2019 PSW-Series ENG Manual
43/156
OPERATION
43
Removal Reverse the procedure to remove the terminalcovers.
Using the Rack Mount Kit
Background The PSW series has an optional Rack MountKit (GW Instek part number: [JIS] GRA-410-J,[EIA] GRA-410-E[EIA]) that can be used tohold 6x PSW Type I models, 3x Type II models,2x Type III models or a combination of all
models (1x Type I, 1x Type II and 1x Type III).
Rack mountdiagram
Type I Type II Type III
How to Use the Instrument
Background The PSW power supplies use a novel methodof configuring parameter values only using thevoltage or current knobs. The knobs are used to
quickly edit parameter values at 0.01, 0.1 or 1unit steps at a time.
When the user manual says to set a value orparameter, use the steps below.
Example Use the voltage knob to set a voltage of 10.05volts.
-
7/22/2019 PSW-Series ENG Manual
44/156
PSW Series User Manual
44
1. Repeatedly press the voltage knobuntil the last digit is highlighted.This will allow the voltage to be
edited in 0.01 volt steps.
2. Turn the voltage knob till 0.05volts is shown.
Voltage
Voltage
V
A
V
A
3. Repeatedly press the voltage knob until thefirst digit is highlighted. This will allow thevoltage to be edited in 1 volt steps.
4. Turn the voltage knob until 10.05 is shown.
V
A
V
A
NoteNotice the Set key becomes illuminated whensetting the current or voltage.
If the voltage or current knobs are unresponsive,press the Set key first.
-
7/22/2019 PSW-Series ENG Manual
45/156
OPERATION
45
Reset to Factory Default Settings
Background The F-88 configuration setting allows the PSWto be reset back to the factory default settings.See page139 for the default factory settings.
Steps 1. Press the Function key. TheFunction key will light up.
Function
2. The display should show F-01 on the top and theconfiguration setting forF-01 on the bottom.
3. Rotate the voltage knob to changethe F setting to F-88 (Factory SetValue).
Voltage
4. Use the current knob to set theF-88 setting to 1 (Return to factorysettings).
Current
5. Press the Voltage knob to confirm.ConF will be displayed when
successful.
Voltage
6. Press the Function key again to
exit. The function key light willturn off.
Function
-
7/22/2019 PSW-Series ENG Manual
46/156
PSW Series User Manual
46
View System Version and Build Date
Background The F-89 configuration setting allows you toview the PSW version number, build date,keyboard version, analog-control version,kernel build, test command version and testcommand build date.
Steps 1. Press the Function key. TheFunction key will light up.
Function
2. The display should show F-01 on the top and theconfiguration setting forF-01 on the bottom.
3. Rotate the voltage knob to change
the F setting to F-89 (ShowVersion).
Voltage
4. Rotate the current knob to viewthe version and build date for thevarious items.
Current
-
7/22/2019 PSW-Series ENG Manual
47/156
OPERATION
47
F-89 0-XX: PSW Main Program Version1-XX: PSW Main Program Version2-XX: PSW Main Program Build On-Year.
3-XX: PSW Main Program Build On-Year.4-XX: PSW Main Program Build On-Month.5-XX: PSW Main Program Build On-Day.6-XX: Keyboard CPLD version.7-XX: Keyboard CPLD version.8-XX: Analog CPLD version.9-XX: Analog CPLD version.A-XX: Reserved.B-XX: Reserved.C-XX: Kernel Build On-Year.D-XX: Kernel Build On-Year.E -XX: Kernel Build On-Month.F-XX: Kernel Build On-Day.G-XX: Test Command Version.H-XX: Test Command Version.I-XX: Test Command Build On-Year.
-XX: Test Command Build On-Year.K-XX: Test Command Build On-Month.L-XX: Test Command Build On-Day.
5. Press the Function key again toexit. The function key light willturn off.
Function
Example Main Program Version: V01.09, 2011/08-01
0-01: PSW Main Program Version1-09: PSW Main Program Version2-20: PSW Main Program Build On-Year.3-11: PSW Main Program Build On-Year.4-08: PSW Main Program Build On-Month.5-01: PSW Main Program Build On-Day.
-
7/22/2019 PSW-Series ENG Manual
48/156
PSW Series User Manual
48
Example Keyboard CPLD Version: 0x030c
6-03: Keyboard CPLD Version.
7-0c: Keyboard CPLD Version.
Example Analog CPLD Version: 0x0421
8-04: Analog CPLD Version.9-21: Analog CPLD Version.
Example Kernel Version: 2011/05/22
C-20: Kernel Build On-Year.D-11: Kernel Build On-Year.E-05: Kernel Build On-Month.F-22: Kernel Build On-Day.
Example Test Command Version: V01:00, 2011/07/25
G-01: Test Command Version.H-00: Test Command Version.I-20: Test Command Build On-Year.-11: Test Command Build On-Year.
K-07: Test Command Build On-Month.L-25: Test Command Build On-Day.
-
7/22/2019 PSW-Series ENG Manual
49/156
OPERATION
49
Basic OperationThis section describes the basic operations required to operate the
power supply. Setting OVP/OCP from page49
C.V. mode from page51
C.C. mode from page54
Display modes page57
Panel lock page58
Remote sensing from page59
Before operating the power supply, please see the Getting Startedchapter, page9.
Setting OVP/OCP Levels
The OVP level has a selectable range of 10% to110% of the rated output voltage. The OCPlevel has a selectable range 10%~ 110% of therated output current, alternatively the OCPlevel can also be turned off. The OVP and OCPlevel is set to 110% by default.
When one of the protection measures are on,ALM is shown on the panel display. By default,
the power switch will turn off when any of theprotection levels are tripped.
ALM
V
A
-
7/22/2019 PSW-Series ENG Manual
50/156
PSW Series User Manual
5
Before setting the OVP or OCP level:
Ensure the load is not connected.
Ensure the output is set to off.
Steps 1. Press the OVP/OCP key. TheOVP/OCP key lights up.
OVP/OCP
2. The OVP setting will be displayed on the topand the OCP setting (or OFF) will be displayedon the bottom.
V
A
OVP Setting
OCP Setting
OVP Level 3. Use the voltage knob to set the
OVP level.
Voltage
Range 10%~110% of rated
output voltage.
OCP Level 4. Use the current knob to set theOCP level.
Current
Range 10%~110% of rated
output current, OFF.
5. Press OVP/OCP again to exit. TheOVP/OCP indicator will turn off.
OVP/OCP
Power switch trip Set F-95 (Power switch trip) to 1 (todisable the power switch trip) or to0 (to enable the power switch trip)
and save.
Page99
F-95 1 (Disable) or 0 (Enable)
-
7/22/2019 PSW-Series ENG Manual
51/156
OPERATION
51
Clear OVP/OCPprotection
The OVP or OCP protection can becleared after it has been tripped byholding the OVP/OCP button for 2
seconds.(Only applicable when the powerswitch trip setting is disabled[F-95 = 1])
OVP/OCP
(hold)
Set to C.V. Mode
When setting the power supply to constant voltage mode, a current
limit must also be set to determine the crossover point. When thecurrent exceeds the crossover point, the mode switches to C.C.mode. For details about C.V. operation, see page21.C.C. and C.V.mode have two selectable slew rates: High Speed Priority and SlewRate Priority. High Speed Priority will use the fastest slew rate forthe instrument while Slew Rate Priority will use a user-configuredslew rate.
Background Before setting the power supply to C.V. mode,ensure:
The output is off.
The load is connected.
Steps 1. Press the Function key. TheFunction key will light up.
Function
2. The display should show F-01 on the top and theconfiguration setting forF-01 on the bottom.
3. Rotate the voltage knob to changethe F setting to F-03 (V-I ModeSlew Rate Select).
Voltage
-
7/22/2019 PSW-Series ENG Manual
52/156
PSW Series User Manual
52
4. Use the current knob to set the F-03setting.
Set F-03 to 0 (CV High SpeedPriority) or 2 (CV Slew RatePriority).
Current
F-03 0 = CV High Speed Priority
2 = CV Slew Rate Priority
5. Press the Voltage knob to save theconfiguration setting. ConF will be
displayed when successful.
Voltage
6. If CV Slew Rate Priority was chosen as the
operating mode, repeat steps 3~5 to set F-04(Rising Voltage Slew Rate) and the F-05 (FallingVoltage Slew Rate) and save.
F-04 / F-05 0.1V/s~60V/s (PSW 30-XX)
0.1V/s~160V/s (PSW 80-XX)0.1V/s~320V/s (PSW160-XX)
7. Press the Function key again to exit
the configuration settings. Thefunction key light will turn off.
Function
8. Use the Current knob to set thecurrent limit (crossover point).
Current
-
7/22/2019 PSW-Series ENG Manual
53/156
OPERATION
53
9. Use the Voltage knob to set thevoltage.
Voltage
NoteNotice the Set key becomes illuminated whensetting the current or voltage. If the voltage orcurrent knobs are unresponsive, press the Set keyfirst.
10.Press the Output key. The Output
key becomes illuminated.
Output
C V
% W
V
A
CV and the Power Bar
will become illuminated
(top left & center)20 40 60 80 100 % W
NoteOnly the voltage level can be altered when theoutput is on. The current level can only be changedby pressing the Set key.
For more information on the Normal FunctionSettings (F-00 ~ F-61, F-88~F-89) see page89.
-
7/22/2019 PSW-Series ENG Manual
54/156
PSW Series User Manual
54
Set to C.C. Mode
When setting the power supply to constant current mode, a voltage
limit must also be set to determine the crossover point. When thevoltage exceeds the crossover point, the mode switches to C.V.mode. For details about C.C. operation, see page21.C.C. and C.V.mode have two selectable slew rates: High Speed Priority and SlewRate Priority. High Speed Priority will use the fastest slew rate forthe instrument while Slew Rate Priority will use a user-configuredslew rate.
Background Before setting the power supply toC.C. mode, ensure:
The output is off.
The load is connected.
Steps 1. Press the Function key. TheFunction key will light up.
Function
2. The display should show F-01 on the top and theconfiguration setting forF-01 on the bottom.
3. Rotate the voltage knob to changethe F setting to F-03 (V-I Mode
Slew Rate Select).
Voltage
4. Use the current knob to set the F-03setting.
Set F-03 to 1 (CC High SpeedPriority) or 3 (CC Slew RatePriority) and save.
Current
-
7/22/2019 PSW-Series ENG Manual
55/156
OPERATION
55
F-03 1 = CC High Speed Priority
3 = CC Slew Rate Priority
5. Press the Voltage knob to save theconfiguration setting. ConF will bedisplayed when successful.
Voltage
6. If CC Slew Rate Priority was chosen as theoperating mode, set F-06 (Rising Current SlewRate) and F-07 (Falling Current Slew Rate) andsave.
F-06 / F-07 0.01A/s~72.00A/s (PSW 30-36)0.01A/s~144.0A/s (PSW 30-72)0.01A/s~216.0A/s (PSW 30-108)0.01A/s~27.00A/s (PSW 80-13.5)
0.01A/s~54.00A/s (PSW 80-27)0.01A/s~81.00A/s (PSW 80-40.5)0.01A/s~14.40A/s (PSW 160-7.2)0.01A/s~28.80A/s (PSW 160-14.4)0.01A/s~43.20A/s (PSW 160-21.6)
7. Press the Function key again to exitthe configuration settings. Thefunction key light will turn off.
Function
8. Use the Voltage knob to set thevoltage limit (crossover point).
Voltage
-
7/22/2019 PSW-Series ENG Manual
56/156
PSW Series User Manual
56
9. Use the Current knob to set thecurrent.
Current
NoteNotice the Set key becomes illuminated whensetting the current or voltage. If the voltage orcurrent knobs are unresponsive, press the Set keyfirst.
10.Press the Output key. The Output
key becomes illuminated.
Output
% W
V
AC C
% W20 40 60 80 100
CC and the Power Bar
will become illuminated
(bottom left & center)
NoteOnly the current level can be altered when theoutput is on. The voltage level can only be changedby pressing the Set key.
For more information on the Normal FunctionSettings (F-00 ~ F-61, F-88~F-89) see page89.
-
7/22/2019 PSW-Series ENG Manual
57/156
OPERATION
57
Display Modes
The PSW power supplies allow you to view the output in three
different modes: voltage and current, voltage and power or currentand power.
Steps 1. Press the PWR/DSPL key. ThePWR DSPL key lights up.
PWR DSPL
2. The display changes to voltage and power
(V/W).
3. To switch between displaying A/W and V/W,simply press the corresponding voltage orcurrent knob.
For example: when in A/W mode, press thevoltage knob to display V/W. Conversely
when in V/W mode, press the current knob todisplay A/W.
V
W
V
Voltage
Current
W
A
When V/W is displayed, the voltage knobcan still be used to change the voltage level.
When A/W is displayed, the current knobcan still be used to change the current level.
Exit Press the PWR/DSPL key again toreturn to normal display mode.The PWR DSPL light will turn off.
PWR DSPL
-
7/22/2019 PSW-Series ENG Manual
58/156
PSW Series User Manual
58
Panel Lock
The panel lock feature prevents settings from being changed
accidentally. When activated, the Lock/Local key will becomeilluminated and all keys and knobs except the Lock/Local key andOutput key (if active) will be disabled.
If the instrument is remotely controlled via the USB/LAN interface,the panel lock is automatically enabled.
Activate the panellock
Press the Lock/Local key to active
the panel lock. The key willbecome illuminated.
Lock/Local
Disable the panellock
Hold the Lock/Local key for ~3seconds to disable the panel lock.The Lock/Local light turns off.
Lock/Local
-
7/22/2019 PSW-Series ENG Manual
59/156
OPERATION
59
Remote Sense
Remote sense is used to compensate for the voltage drop seen
across load cables due to the resistance inherent in the load cables.The remote sense terminals are connected to the load terminals todetermine the voltage drop across the load cables.
Remote sense can compensate up to 0.6 volts (compensationvoltage). Load cables should be chosen with a voltage drop lessthan the compensation voltage.
WARNINGEnsure the output is off before connecting anysense cables.
Use sense cables with a voltage rating exceedingthe isolation voltage of the power supply.
Never connect sensing cables when the output ison. Electric shock or damage to the power supplycould result.
NoteBe sure to remove the Sense joining plates so theunits are not using local sensing.
Single Load 1. Connect the Sense+ terminal to the positivepotential of the load. Connect the Sense-terminal to the negative potential of the load.
Output
Sense
Sense
PSW
Output
Load
Input
Input
Page40
2. Operate the instrument as normal.See the Basic Operation chapter for
details.
Page45
-
7/22/2019 PSW-Series ENG Manual
60/156
PSW Series User Manual
6
Parallel PSWUnits
1. Connect the Sense+ terminals to the positivepotential of the load. Connect the Sense-terminals to the negative potential of the load.
Output
Sense
Sense
PSW #2
Output
Output
Sense
Sense
PSW #1
Output
Load
Input
Input
Page40
2. Operate the instrument as normal.See the Parallel Operation chapterfor details.
Page63
Serial PSW Units 1. a. Connect the 1stSense+ terminal to thepositive potential of the load.
b. Connect the 1stSense- terminal to thepositive output terminal of the second PSW
unit.
c. Connect the 2ndSense+ terminal to thepositive terminal of the second PSW unit.
d. Connect the 2ndSense- terminal to negativeterminal of the load.
-
7/22/2019 PSW-Series ENG Manual
61/156
OPERATION
61
PSW #2
a
b
c
d
Load
Input
Input
Output
Sense
Sense
PSW #1
Output
Output
Sense
Sense
Output
Page40
2. Operate the instrument as normal.See the Serial Operation chapterfor details.
Page70
Wire Shieldingand Load lineimpedance
To help to minimize the oscillation due to theinductance and capacitance of the load cables,use an electrolytic capacitor in parallel with theload terminals.
To minimize the effect of load line impedanceuse twisted wire pairing.
PSW Loadss
Twisted pair
Capacitor
-
7/22/2019 PSW-Series ENG Manual
62/156
PSW Series User Manual
62
Parallel / Series OperationThis section describes the basic operations required to operate the
power supply in series or parallel. Operating the PSW series inparallel increases the total power output of the power supply units.When used in series, the total output voltage of the power suppliescan be increased.
The number of the power supplies that can be connected in seriesor parallel depends on the model and the mode:
Series Mode: 2 units maximum
Parallel Mode: 3 units maximum
To use the power supplies in series or parallel, units must be usedin a Master-Slave configuration. In the master-slave configuration amaster power supply controls any other connected slavepower supplies.
Master-Slave Parallel overview from page63
Parallel connection from page65 Parallel operation from page68
Master-Slave Series overview page70
Series connection page72
Series operation from page74
Before operating the power supply, please see the Getting Started
chapter, page9.
-
7/22/2019 PSW-Series ENG Manual
63/156
OPERATION
63
Master-Slave Parallel Overview
Background When connecting the PSW power supplies inparallel, up to 3 units can be used in paralleland all units must be of the same model.
When the units are used in parallel, a numberof precautions and limitations apply. Pleaseread this overview before operating the powersupplies in parallel.
Master
Load
Ext-V
Ext-R
Slave
VMON
IMON
Slave
Limitations Display
Only the master unit will display the voltage
and current.
-
7/22/2019 PSW-Series ENG Manual
64/156
PSW Series User Manual
64
OVP/ OCP
The master unit can shut down slave unitswhen OVP/OCP is tripped on the master
unit (if the slave connector is wired for shutdown on alarm).
OVP/OCP can be independently tripped oneach slave unit, however the shutdown ofthe power or output of the unit is disabled.Only the alarm will be enabled.
Remote monitoring
Voltage monitoring (VMON) and currentmonitoring (IMON) are only supported onthe master unit.
The IMON current represents the totalcurrent of the all the parallelized units.
Remote Sense
Please see the remote sense chapter fordetails, page59.
External Voltage and Resistance Control
Voltage/Resistance controlled remotecontrol can only be used with the masterunit.
The full scale current (in parallel) isequivalent to the maximum external voltageor resistance.
Internal Resistance
For 2 units in parallel, the internal resistanceis actually half of the setting value.
For 3 units in parallel, the internal resistanceis actually a third of the setting value.
-
7/22/2019 PSW-Series ENG Manual
65/156
OPERATION
65
Bleeder Control
The Master unit is used to control thebleeder settings. The bleeder resistors in all
the slave units are always turned off whenin parallel mode.
Output Voltage/Output Current
Model Single unit 2 units 3 unitsPSW 30-36 30V 30V 30V
36A 72A 108A
PSW 80-13.5 80V 80V 80V13.5A 27A 40.5A
PSW 160-7.2 160V 160V 160V7.2A 14.4A 21.6A
PSW 30-72 30V 30V 30V72A 144A 216A
PSW 80-27 80V 80V 80V27A 54A 81A
PSW 160-14.4 160V 160V 160V14.4A 28.8A 43.2A
PSW 30-108 30V 30V 30V108A 216A 324A
PSW 80-40.5 80V 80V 80V40.5A 81A 121.5A
PSW 160-21.6 160V 160V 160V21.6A 43.2A 64.8A
Master-Slave Parallel Connection
Master-SlaveConnector
The Analog Control Connector is used for bothserial and parallel connections. The way theconnector is configured determines thebehavior of the master and slave units. For thecomplete connector pin assignment, see page102.
-
7/22/2019 PSW-Series ENG Manual
66/156
PSW Series User Manual
66
Analog ConnectorConnection
To operate the power supplies in parallel,connect the analog connectors on the masterand slave units as shown in the diagrams
below.Master with 2 slave units:
12
13
14
1517
20
21
24 20 12
17 15 3 1715
31224 20
11 12 1
OUTPUT ON STATUS21
Master unit
ALM STATUS20
STATUS COM17
FEEDBACK15
CURRENT_SUM_113
SHUTDOWN12
OUT ON/OFF CONT24
Slave Unit 1
12 SHUTDOWN
20 ALM STATUS
15 FEEDBACK
3 CURRENT SUM OUT
Slave Unit 2
OUT ON/OFF CONT24
12 SHUTDOWN
17 STATUS COM 17 STATUS COM
2 D COM
15 FEEDBACK
CURRENT_SUM_2 CURRENT SUM OUT314
20 ALM STATUS
11 1 1I MON CURRENT SHARE CURRENT SHARE
Master with 1 slave unit:
2
12
131517
20
21
24 20 12
17 15 323
OUTPUT ON STATUS21
Master unit
ALM STATUS20
STATUS COM17
FEEDBACK15
CURRENT_SUM_113
SHUTDOWN12
OUT ON/OFF CONT24
Slave Unit 1
12 SHUTDOWN
20 ALM STATUS
15 FEEDBACK
3 CURRENT SUM OUT
17 STATUS COM
2 D COM
11 1I MON CURRENT SHARE
11 1
-
7/22/2019 PSW-Series ENG Manual
67/156
OPERATION
67
Parallel OutputConnection
-
+
Load
Master
unit
Slave
unit 2
Slave
unit 1
Steps 1. Ensure the power is off on all power supplies.
2. Choose a master and a slave unit(s).
3. Connect the analog connectors for the masterand slave unit as shown above.
4. Remove the Output Terminal
covers and the protection dummyplug from the analog controlconnector.
Page42
5. Connect the master and slave unit in parallel asshown above.
6. Reattach the terminal covers. Page42
NoteEnsure the load cables have sufficientcurrent capacity.
Page39
Re-attach the Protection dummy plug when not inuse.
-
7/22/2019 PSW-Series ENG Manual
68/156
PSW Series User Manual
68
Master-Slave Parallel Operation
Master-SlaveConfiguration
Before using the power supplies in parallel, themaster and slave units need to be configured.
Steps 1. Configure the OVP and OCPsettings for the master unit.
Page49
2. For each unit, hold the Functionkey while turning the power on to
enter the power on configurationsettings.
A
W
V
W
%W10080604020
ISR
CC
DLY
ALM
RMT
CV
VSR
F unc t ion OV P/OCP S e tOutput
PWRDSPLLock/LocalTest
PSW 30-36 360W
Voltage
Current
Multi-RangeDC PowerSupply
3. Configure F-93 (Master/Slave)setting for each master/slave unit.
Page99
UnitF-93
Master (with 1 slave in parallel) 1
Master (with 2 slaves in parallel) 2
Slave unit (parallel slave) 3
4. Cycle the power on the units (reset the power).
NoteConfiguration settings can be checked for both themaster and slave units by pressing the Functionkey and checking F-93.
Only the Master OVP and OCP level is used forover voltage and current protection. Slave OVP andOCP level is disregarded.
OTP works independently for each unit.
-
7/22/2019 PSW-Series ENG Manual
69/156
OPERATION
69
Master-SlaveOperation
Only operate the power supplies in parallel ifthe units are configured correctly.
1. Turn on the master and slave units. The slaveunit(s) will show a blank display.
Master unit Slave units
2. Operation of all units is controlledvia the master unit. Operation ofthe master unit is the same as for asingle unit. See the Basic Operationchapter.
Page45.
3. Press the Output key to begin. Output
CautionOnly operate the power supplies in parallel if usingunits of the same model number.
Only a maximum of 3 units can be used in parallel.
NoteThe panel controls are disabled on slave units,including the output key. On slave units only theFunction key can be used to view the currentsettings.
-
7/22/2019 PSW-Series ENG Manual
70/156
PSW Series User Manual
7
Master-Slave Series Overview
Background When connecting PSW power supplies inseries, up to 2 units can be used in series and allunits must be of the same model.
When the units are used in series, a number ofprecautions and limitations apply. Please readthis overview before operating the powersupplies in series.
Master
Load
Ext-V
Ext-R
Slave
VMON
IMON
Limitations Display
Only the master unit will display thecurrent.
Master and slave units display the voltage.The total voltage is the sum of the units.
OVP/OCP The master unit can shut down the slave
unit when OVP/OCP is tripped on themaster unit (if the slave connector is wiredfor shut down on alarm).
OVP and OCP level is determined by themaster OVP and OCP level. The OVP andOCP level on the slave unit is ignored.
-
7/22/2019 PSW-Series ENG Manual
71/156
OPERATION
71
Remote monitoring
Voltage monitoring (VMON) and currentmonitoring (IMON) are only supported on
the master unit. The VMON voltage represents the total
voltage of the all the serialized units.
Remote Sense
Please see the remote sense chapter fordetails, page59.
External Voltage and Resistance Control Voltage/Resistance controlled remote
control can only be used with the masterunit.
The full scale voltage (in series) is equivalentto the maximum external voltage orresistance.
Slew Rate The actual slew rate is double that of the
setting slew rate. I.e., A slew rate setting of60.00V/s is actually 120V/s when in series.
Internal Resistance
The internal resistance is actually twice thatof the setting value.
Bleeder Control
The Master unit is used to control thebleeder settings. The bleeder resistor isalways turned on for the slave unit in seriesmode.
-
7/22/2019 PSW-Series ENG Manual
72/156
PSW Series User Manual
72
Output Voltage/Output Current
Model Single unit 2 unitsPSW 30-36 30V 60V
36A 36A
PSW 80-13.5 80V 160V
13.5 13.5APSW 160-7.2 160V 320V
7.2A 7.2A
PSW 30-72 30V 60V72A 72A
PSW 80-27 80V 160V27A 27A
PSW 160-14.4 160V 320V14.4A 14.4A
PSW 30-108 30V 60V108A 108A
PSW 80-40.5 80V 160V40.5A 40.5A
PSW 160-21.6 160V 320V
21.6A 21.6A
Master-Slave Series Connection
Master-SlaveConnector
The Analog Control Connector is used for bothserial and parallel connections. The way theconnector is configured determines thebehavior of the master and slave units. For theconnector pin assignment, see page102.
Analog ConnectorConnection
To operate the power supplies in series, connectthe analog connectors on the master and slaveunit as shown in the diagram below.
-
7/22/2019 PSW-Series ENG Manual
73/156
OPERATION
73
2
12
17
20
21
Master unitA COM16
OUTPUT ON STATUS21
ALM STATUS20
STATUS COM17
SHUTDOWN12
Slave Unit 125 SER SLV IN
20 ALM STATUS
12 SHUTDOWN
2 D COM
24 OUT OFF/ON CONT
2 D COM
24 20 12
1725 2
16
17 STATUS COM
Series OutputConnection
Master unitLoad
+-
Slave unit
Steps 1. Ensure the power is off on both power supplies.
2. Choose a master and slave unit.
3. Connect the analog connectors for the masterand slave unit as shown above.
4. Remove the output terminal coverand the protection dummy plug
from the analog control connector.
Page42
5. Connect the master and slave unit in series asshown above.
6. Reattach the terminal cover. Page42
NoteEnsure load cables have sufficient
current capacity.
Page39
-
7/22/2019 PSW-Series ENG Manual
74/156
PSW Series User Manual
74
Re-attach the protection dummy plug when not inuse.
Master-Slave Series Operation
Master-SlaveConfiguration
Before using the power supplies in series, themaster and slave units need to be configured.
1. Configure the OVP and OCPsettings for the master unit.
Page49
2. For each unit, hold the Functionkey while turning the power on toenter the power on configurationsettings.
A
W
V
W
%W10080604020
ISR
CC
DLY
ALM
RMT
CV
VSR
F unc t ion OV P/OCP S e tOutput
PWRDSPLLock/LocalTest
PSW 30-36 360W
Voltage
Current
Multi-RangeDC PowerSupply
3. Configure F-93 (Master/Slave)setting for each master/slave unit.
Page99
Unit F-93
Master (local or series operation) 0
Slave unit (series) 4
4. Cycle the power on the units (reset the power).
NoteConfiguration settings can be checked for both themaster and slave units by pressing the Functionkey.
-
7/22/2019 PSW-Series ENG Manual
75/156
-
7/22/2019 PSW-Series ENG Manual
76/156
PSW Series User Manual
76
Test ScriptsThis section describes how to use the Test function to run, load and
save test scripts for automated testing. The Test function is useful ifyou want to perform a number of tests automatically. The PSW testfunction can store ten test scripts in memory.
Each test script is programmed in a scripting language. For moreinformation on how to create test scripts, please contact GW Instek.
Test Script File Format from page77
Test Script Settings from page77 Setting the Test Script Settings from page78
Load Test Script from page79
Run Test Script from page80
Export Test Script from page81
Remove Test Script from page82
-
7/22/2019 PSW-Series ENG Manual
77/156
OPERATION
77
Test Script File Format
Background The test files are saved in *.tst file format.
Each file is saved as tXXX.tst, where XXX is thesave file number 001~010.
Test Script Settings
Test Run Runs the chosen test script from the internalmemory. A script must first be loaded into theinternal memory before it can be run. See thetest function Test Save, below.
The script will run as soon as the test function isstarted.
T-01 1~10
Test Load Loads a test script from the USB drive to thedesignated save slot in memory. A script mustfirst be loaded into internal memory before itcan be run.
T-02 1~10 (USBPSW)
Test Export Exports a script from the designated memorysave slot to the USB drive.
T-03 1~10 (PSWUSB)
Test Remove Deletes the chosen test file from the PSWinternal memory.
T-04 1~10
-
7/22/2019 PSW-Series ENG Manual
78/156
PSW Series User Manual
78
Setting the Test Script Settings
Steps The test script settings (T-01~T-04) are set withthe Test key.
1. Press the Test key. The Test keywill light up.
Test
2. The display will show T-01 on the top and the
memory no. for T-01 on the bottom.
Test Setting
Memory
number
3. Rotate the voltage knob to change
the T setting (Test setting).
Voltage
Test Run
Test Load
Test Export
Test Remove
T-01
T-02
T-03
T-04
4. Rotate the current knob to choose amemory number.
Current
Range 1~10
5. Press the Voltage knob to completethe setting.
Voltage
-
7/22/2019 PSW-Series ENG Manual
79/156
OPERATION
79
Exit Press the Test key again to exit theTest settings. The Test key lightwill turn off.
Test
Load Test Script from USB
Overview Before a test script can be run, it must first beloaded into a one of the 10 memory save slots.Before loading a test script into memory:
Ensure the script file is placed in the rootdirectory.
Ensure the file name number corresponds tothe memory number that you wish to saveto.
For example: A test file named t001.tst canonly be saved to memory number 01, t002.tstcan only be saved to memory number 02,and so on.
Steps 1. Insert a USB flash drive into thefront panel USB-A slot. Ensure theflash drive contains a test script inthe root directory.
2. Turn on the power. MS (Mass Storage) will bedisplayed on the screen after a few seconds ifthe USB drive is recognized.
-
7/22/2019 PSW-Series ENG Manual
80/156
PSW Series User Manual
8
NoteIf the USB drive is not recognized, check to seethat the function settings for F-20 = 1 (page93). Ifnot, reinsert the USB flash drive.
3. Configure T-02 (Test Load) to 1~10(save memory slot)
Page78
T-02 range 1~10 (t001 ~t010)
4. The script will now be available in the memoryslot the script was saved to.
Note Error messages: If you load a file that is notpresent on the USB drive Err 002 will bedisplayed on the display.
Run Test Script
Overview A test script can be run from one of ten memoryslots.
Steps 1. Before a test script can be run, it
must first be loaded into one of the10 memory save slots.
Page79
2. Configure T-01 (Run Test) to 1~10(save memory slot)
Page78
T-01 range 1~10
3. The test script will automatically start to run.
-
7/22/2019 PSW-Series ENG Manual
81/156
OPERATION
81
NoteError messages: If you try to run a test script froman empty memory location Err 003 will bedisplayed on the display.
NoteWhen a script starts to run, there is no way to abortthe script. Pressing the Output key has no effect. If
you wish to stop a test early, turn the power off.
Export Test Script to USB
Overview The Export Test function saves a test file to theroot directory of a USB flash drive.
Files will be saved as tXXX.tst where XXX isthe memory number 001~010 from whichthe test script was exported from.
Files of the same name on the USB flashdrive will be written over.
Steps 1. Insert a USB flash drive into thefront panel USB-A slot.
2. Turn on the power. MS (Mass Storage) will bedisplayed on the screen after a few seconds ifthe USB drive is recognized.
-
7/22/2019 PSW-Series ENG Manual
82/156
PSW Series User Manual
82
NoteIf the USB drive is not recognized, check to seethat the function settings for F-20 = 1 (page93). Ifnot, reinsert the USB flash drive.
3. Configure T-03 (Test Export) to0~10 (save memory slot)
Page78
T-03 range 1~10
4. The script will now be copied to the USB flashdrive.
Note Error messages: If you try to export a test scriptfrom an empty memory location Err 003 will bedisplayed on the display.
Remove Test Script
Overview The Remove Test function will delete a testscript from the internal memory.
Steps 1. Select T-04 (Test Remove) and
choose which test script to removefrom the internal memory.
Page78
T-04 range 1~10
2. The test script will be removed from theinternal memory.
-
7/22/2019 PSW-Series ENG Manual
83/156
OPERATION
83
NoteError messages: If you try to remove a test scriptfrom an empty memory location Err 003 will bedisplayed on the display.
-
7/22/2019 PSW-Series ENG Manual
84/156
PSW Series User Manual
84
CONFIGURATIONConfiguration 85Configuration Table ................................................................................................... 85Normal Function Settings ......................................................................................... 89USB/GPIB Settings ................................................................................................... 93LAN Settings ............................................................................................................... 94System Settings ........................................................................................................... 95Power On Configuration Settings ........................................................................... 96Calibration ................................................................................................................... 97
-
7/22/2019 PSW-Series ENG Manual
85/156
CONFIGURATION
85
ConfigurationConfiguration of the PSW power supplies is divided into five
different configuration settings: Normal Function, USB/GPIB, LAN,Power ON Configuration, Calibration Settings and System Settings.Power ON Configuration differs from the other settings in that thesettings used with Power ON Configuration settings can only be setduring power up. The other configuration settings can be changedwhen the unit is already on. This prevents some importantconfiguration parameters from being changed inadvertently. PowerOn Configuration settings are numbered F-90 to F-95 and the otherconfiguration settings are numbered F-00 to F-61 and F-88 to F-89.
Configuration Table
Please use the configuration settings listed below when applyingthe configuration settings.
Normal FunctionSettings Setting Setting Range
Output ON delay time F-01 0.00s~99.99sOutput OFF delay time F-02 0.00s~99.99s
V-I mode slew rate select F-03
0 = CV high speed priority1 = CC high speed priority2 = CV slew rate priority3 = CC slew rate priority
Rising voltage slew rate F-040.01V/s~60.00V/s (PSW 30-XX)0.1V/s~160.0V/s (PSW 80-XX)0.1V/s~320.0V/s (PSW 160-XX)
Falling voltage slew rate F-050.01V/s~60.00V/s (PSW 30-XX)0.1V/s~160.0V/s (PSW 80-XX)0.1V/s~320.0V/s (PSW 160-XX)
-
7/22/2019 PSW-Series ENG Manual
86/156
PSW Series User Manual
86
Rising current slew rate F-06
0.01A/s~72.00A/s (PSW 30-36)0.1A/s~144.0A/s (PSW 30-72)0.1A/s~216.0A/s (PSW 30-108)0.01A/s~27.00A/s (PSW 80-13.5)
0.01A/s~54.00A/s (PSW 80-27)0.01A/s~81.00A/s (PSW 80-40.5)0.01A/s~14.40A/s (PSW 160-7.2)0.01A/s~28.80A/s (PSW 160-14.4)0.01A/s~43.20A/s (PSW 160-21.6)
Falling current slew rate F-07
0.01A/s~72.00A/s (PSW 30-36)0.1A/s~144.0A/s (PSW 30-72)0.1A/s~216.0A/s (PSW 30-108)0.01A/s~27.00A/s (PSW 80-13.5)
0.01A/s~54.00A/s (PSW 80-27)0.01A/s~81.00A/s (PSW 80-40.5)0.01A/s~14.40A/s (PSW 160-7.2)0.01A/s~28.80A/s (PSW 160-14.4)0.01A/s~43.20A/s (PSW 160-21.6)
Internal resistancesetting
F-08
0.000~0.833(PSW 30-36)0.000~0.417(PSW 30-72)0.000~0.278(PSW 30-108)0.000~5.926(PSW 80-13.5)0.000~2.963(PSW 80-27)0.000~1.975(PSW 80-40.5)0.000~22.222(PSW 160-7.2)0.000~11.111(PSW 160-14.4)0.000~7.407(PSW 160-21.6)
Bleeder circuit control F-09 0 = OFF, 1 = ON
Buzzer ON/OFF control F-10 0 = ON, 1 = OFF
USB/GPIB settings
Front panel USB State F-20 0 = Absent, 1 = Mass Storage
Rear panel USB State F-210 = Absent, 2 = USB-CDC, 3 = GPIB-USB adapter
Rear panel USB mode F-220 = Disable, 1 = GPIB-USB adapter,2 = USB CDC
GPIB address F-23 0~30
LAN settings
MAC Address-1 F-30 0x00~0xFF
MAC Address-2 F-31 0x00~0xFFMAC Address-3 F-32 0x00~0xFF
-
7/22/2019 PSW-Series ENG Manual
87/156
CONFIGURATION
87
MAC Address-4 F-33 0x00~0xFF
MAC Address-5 F-34 0x00~0xFF
MAC Address-6 F-35 0x00~0xFFLAN F-36 0 = Disable, 1 = Enable
DHCP F-37 0 = Disable, 1 = EnableIP Address-1 F-39 0~255
IP Address-2 F-40 0~255
IP Address-3 F-41 0~255IP Address-4 F-42 0~255
Subnet Mask-1 F-43 0~255
Subnet Mask-2 F-44 0~255
Subnet Mask-3 F-45 0~255
Subnet Mask-4 F-46 0~255Gateway-1 F-47 0~255
Gateway-2 F-48 0~255
Gateway-3 F-49 0~255Gateway-4 F-50 0~255
DNS address -1 F-51 0~255
DNS address -2 F-52 0~255
DNS address-3 F-53 0~255
DNS address-4 F-54 0~255
Sockets active F-57 0 = Disable, 1 = EnableWeb Server active F-59 0 = Disable, 1 = Enable
Web password active F-60 0 = Disable, 1 = Enable
Web setting password F-61 0000~9999
System Settings
Factory Set Value F-880 = Disable1 = Return to factory settings
Show Version F-89
0, 1 = PSW version
2, 3 = PSW build year4, 5 = PSW build month/day6, 7 = Keyboard CPLD version8, 9 = Analog-Control CPLD versionA, B = ReservedC, D = Kernel build yearE, F = Kernel build month/dayG, H = Test command versionI, J = Test command build year
K, L = Test command buildmonth/day
-
7/22/2019 PSW-Series ENG Manual
88/156
PSW Series User Manual
88
Power On Configuration Settings*
CV ControlF-90
0 = Panel control (local)1 = External voltage control2 = External resistance control
(Ext-R 10k= Vo, max)3 = External resistance control
(Ext-R 10k = 0)
CC Control F-91
0 = Panel control (local)1 = External voltage control2 = External resistance control
(Ext-R 10k = Io,max)3 = External resistance control
(Ext-R 10k = 0)
Power-ON Output F-92 0 = OFF at startup, 1 = On at startup
Master/Slave F-93
0 = Master/Local1 = Master/Parallel12 = Master/Parallel23 = Slave/Parallel4 = Slave/Series
External Out Logic F-94 0 = High ON, 1 = Low ON
Power Switch trip F-95 0 = Enable , 1 = Disable
Calibration Settings*Calibration F-00 0000 ~ 9999
*NotePower On and Calibration settings can only be setduring power up.
-
7/22/2019 PSW-Series ENG Manual
89/156
CONFIGURATION
89
Normal Function Settings
Output ON DelayTime
Delays turning the output on for a designatedamount of time. The Delay indicator will lightwhen the Delay time is not 0.
Note: The Output ON Delay Time setting has amaximum deviation (error) of 20ms.
The Output ON Delay Time setting is disabled
when the output is set to external control.
DLY
F-01 0.00s~99.99s
Output OFFDelay Time Delays turning the output off for a designatedamount of time. The Delay indicator will lightwhen the Delay time is not 0.
Note: The Output OFF Delay Time setting has amaximum deviation (error) of 20ms.
The Output OFF Delay Time setting is disabledwhen the output is set to external control.
DLY
F-02 0.00s~99.99s
-
7/22/2019 PSW-Series ENG Manual
90/156
PSW Series User Manual
9
V-I Mode Selects High Speed Priority or Slew RatePriority for CV or CC mode. The voltage orcurrent slew rate can only be edited if CC/CV
Slew Rate Priority is selected. The ISR indicatorwill be lit for CC Slew Rate Priority and theVSR indicator will be lit for CV Slew RatePriority.
Note: CC and CV Slew Rate Priority mode aredisabled when voltage/current output is set toexternal control.
ISR
CC Slew Rate priority
VSR
CV Slew Rate priority
F-03 0 = CV high speed priority
1 = CC high speed priority2 = CV slew rate priority3 = CC slew rate priority
Rising VoltageSlew Rate
Sets the rising voltage slew rate. Onlyapplicable if V-I Mode is set to CV Slew RatePriority.
F-04 0.01V/s~60V/s (PSW 30-XX)0.1V/s~160V/s (PSW 80-XX)0.1V/s~320V/s (PSW 160-XX)
Falling VoltageSlew Rate
Sets the falling voltage slew rate. Onlyapplicable if V-I Mode is set to CV Slew RatePriority.
F-05 0.01V/s~60V/s (PSW 30-XX)0.1V/s~160V/s (PSW 80-XX)0.1V/s~320V/s (PSW 160-XX)
-
7/22/2019 PSW-Series ENG Manual
91/156
CONFIGURATION
91
Rising CurrentSlew Rate
Sets the rising current slew rate. Onlyapplicable if V-I Mode is set to CC Slew RatePriority.
F-06 0.01A/s~72.00A/s (PSW 30-36)0.1A/s~144.0A/s (PSW 30-72)0.1A/s~216.0A/s (PSW 30-108)0.01A/s~27.00A/s (PSW 80-13.5)0.01A/s~54.00A/s (PSW 80-27)0.01A/s~81.00A/s (PSW 80-40.5)0.01A/s~14.40A/s (PSW 160-7.2)0.01A/s~28.80A/s (PSW 160-14.4)0.01A/s~43.20A/s (PSW 160-21.6)
Falling CurrentSlew Rate
Sets the falling current slew rate. Onlyapplicable if V-I Mode is set to CC Slew RatePriority.
F-07 0.01A/s~72.00A/s (PSW 30-36)0.1A/s~144.0A/s (PSW 30-72)0.1A/s~216.0A/s (PSW 30-108)0.01A/s~27.00A/s (PSW 80-13.5)
0.01A/s~54.00A/s (PSW 80-27)0.01A/s~81.00A/s (PSW 80-40.5)0.01A/s~14.40A/s (PSW 160-7.2)0.01A/s~28.80A/s (PSW 160-14.4)0.01A/s~43.20A/s (PSW 160-21.6)
InternalResistanceSettings
Sets the internal resistance of the power supply.
F-08 0.000~0.833(PSW 30-36)0.000~0.417(PSW 30-72)
0.000~0.278(PSW 30-108)0.000~5.926(PSW 80-13.5)0.000~2.963(PSW 80-27)0.000~1.975(PSW 80-40.5)0.000~22.222 (PSW 160-7.2)0.000~11.111(PSW 160-14.4)0.000~7.407(PSW 160-21.6)
-
7/22/2019 PSW-Series ENG Manual
92/156
PSW Series User Manual
92
Bleeder Control Bleeder control turns ON/OFF the bleederresistor. Bleeder resistors discharge the filtercapacitors after power is turned off as a safety
measure.F-09 0 = OFF, 1 = ON
Buzzer ON/OFF Turns the buzzer sound on or off. The buzzer isassociated with alarm sounds and keypad entrysounds.
F-10 0 = ON, 1 = OFF
-
7/22/2019 PSW-Series ENG Manual
93/156
CONFIGURATION
93
USB/GPIB Settings
Front Panel USBState
Displays the front panel USB-A port state. Thissetting is not configurable.
F-20 0 = Absent, 1 = Mass Storage
Rear Panel USBState
Displays the rear panel USB-B port state. Thissetting is not configurable.
F-210 = Absent, 2 = USB-CDC,3 = GPIB-USB adapter
Rear Panel USBMode
Sets the rear panel USB mode.
F-220 = Disable, 1 = GPIB-USBadapter (for GUG-001),2 = USB CDC
GPIB Address Sets the GPIB address.
F-23 0~30
-
7/22/2019 PSW-Series ENG Manual
94/156
PSW Series User Manual
94
LAN Settings
MAC Address-1~6
Displays the MAC address 1~6. This setting isnot configurable.
F-30~F-35 0x00~0xFF
LAN Turns Ethernet on or off.
F-36 0 = Disable, 1 = Enable
DHCP Turns DHCP on or off.
F-37 0 = Disable, 1 = Enable
IP Address-1~4 Sets the default IP address. IP address 1~4splits the IP address into four sections.
(F-39 : F-40 : F-41 : F-42)(0~255 : 0~255 : 0~255 : 0~255)
Subnet Mask 1~4 Sets the subnet mask. The subnet mask is splitinto four parts.
(F-43 : F-44 : F-45: F-46)(0~255 : 0~255 : 0~255 : 0~255)
Gateway 1~4 Sets the gateway address. The gateway addressis split into 4 parts.
(F-47 : F-48 : F-49 : F-50)(0~255 : 0~255 : 0~255 : 0~255)
DNS Address 1~4 Sets the DNS address. The DNS address is splitinto 4 parts.
(F-51 : F-52 : F-53 : F-54)(0~255 : 0~255 : 0~255 : 0~255)
Sockets active Enables WebSocket connections.
F-57 0 = Disable, 1 = Enable
Web server active Turns Web server control on/off.F-59 0 = Disable, 1 = Enable
-
7/22/2019 PSW-Series ENG Manual
95/156
CONFIGURATION
95
Web Passwordactive
Turns a web password on/off.
F-60 0 = Disable, 1 = Enable
Web Password Sets the Web password.
F-61 0000 ~ 9999
System Settings
Factory Set Value Returns the PSW to the factory default settings.
See page139 for a list of the default settings.F-88 0 = Disable, 1 = Return to factory
default settings.
Show Version
Displays the PSW version number, build date,keyboard version, analog-control version,kernel build, test command version and testcommand build date.
F-89
0, 1 = PSW version2, 3 = PSW build year4, 5 = PSW build month/day6, 7 = Keyboard CPLD version8, 9 = Analog-Control CPLD
versionA, B = ReservedC, D = Kernel build yearE, F = Kernel build month/day
G, H = Test command versionI, J = Test command build yearK, L = Test command build
month/day
-
7/22/2019 PSW-Series ENG Manual
96/156
PSW Series User Manual
96
Power On Configuration Settings
CV Control Sets the constant voltage (CV) control modebetween local and external voltage/resistancecontrol. For external voltage control, see page104 (External Voltage Control of VoltageOutput)and page109 (External ResistanceControl of Voltage Output).
F-90 0= Panel control (local)1 = External voltage control
2 = External resistance control(Ext-R 10k= Vo,max)3 = External resistance control
(Ext-R 10k = 0)
CC Control Sets the constant current (CC) control modebetween local and external voltage/resistancecontrol. For details on external voltage control,see