The right burner for virtually any applicationCleaver-Brooks provides a full line of high-quality, low-emissions burners that are specifically engineered
to increase your boiler’s efficiency and decrease fuel costs and emissions. Our commitment
to research and development assures Cleaver-Brooks customers of having the most technologically
advanced burner systems available.
Innovative features help the Cleaver-Brooks ProFire line improve the performance of any boiler. With the
flexibility of multiple fuel options and the availability of high turndown burners, there is a Cleaver-Brooks
burner appropriate for commercial, industrial, and institutional applications.
Designed for maximum efficiency and low emissions, Cleaver-Brooks offers the right burner solution for
virtually any boiler room retrofit application. With our extensive engineering expertise and
vast aftermarket support network, we can help determine what burner is right for you, regardless of
boiler manufacturer.
Capacity Fuel NOx LevelsRecommended
Boiler TypesRecommended
Uses
XL-Series(page 4)
37.8 to 92.4 MMBTU input range / 900 to 2,200 HP
Gas, #2 oil, and combination
Available to less than
9 ppm NOx
FiretubeIndustrial Watertube
IndustrialHeavy Industrial
E-Series(page 5)
8.4 to 42.0 MMBTU input range / 200 to
1,000 HP
Gas, #2 oil, and combination
Available to less than
30 ppm NOx
Commercial WatertubeFirebox
Thermal Fluid Heater Firetube
Industrial Watertube
CommercialLight Industrial
Industrial
D-Series(page 6)
3.36 to 42.0 MMBTU input range
/ 80 to 1,000 HP
Gas, #2–#6 oil, combination,
alternative fuels
Available to less than
9 ppm NOx
Firebox Thermal Fluid Heater
Firetube Industrial Watertube
Light CommercialCommercial
Light IndustrialIndustrial
MTH-Series(page 7)
2.5 to 16.0 MMBTU input range / 60 to
380 HPGas only
Available to less than 9 ppm NOx
Cast IronHot Air Furnace
FiretubeCommercial WatertubeThermal Fluid Heater
FireboxProcess / Line Heaters
Light Commercial Commercial
Light Industrial
NTH-Series(page 8)
2.5 to 12.5 MMBTU input range / 60 to
300 HP
Gas, #2 oil, combination
Available to less than 9 ppm NOx
Firebox Thermal Fluid Heaters Industrial Watertube
Commercial Watertube
Light Commercial Commercial
Light Industrial
M-Series(page 9)
1.4 to 10.5 MMBTU input range / 33 to
250 HP
Gas, #2–#6 oil, combination,
alternative fuels
Uncontrolled NOx only
Cast IronHot Air Furnace
Commercial WatertubeFirebox
Thermal Fluid HeaterFiretube
Light Commercial Commercial
Light Industrial
V-Series(page 10)
1.3 to 16.8 MMBTU input range / 31 to
400 HP
Gas, #2 oil, and combination
Available to less than
30 ppm NOx
Cast IronHot Air Furnace
Commercial WatertubeFirebox
Thermal Fluid Heater Firetube
Light CommercialCommercial
Light Industrial
Q-Series(page 11)
.375 to 2.5 MMBTU input range / 9 to
60 HPGas Only
Uncontrolled NOx only
Firetube
Light Commercial Commercial
Light Industrial Industrial
3
IntegratedControls
HeatRecovery Burners
ExhaustSolutions
WaterSystems
Boilers
3
Vertical or Horizontal ConfigurationThe ProFire-XL series is offered in two standard configurations, vertical and horizontal. Vertical configurations
support capacities ranging from 37.8 to 63.0 MMBTU, and horizontal configurations support capacities from 67.2
to 92.4 MMBTU. The standard low-NOx and ultra low-NOx vertical and horizontal configurations are capable of
burning natural gas, propane gas, air-atomized #2 oil, propane air mix (NTXL only), as well as combination gas/#2
oil. Full modulation operation is standard, and a parallel positioning system is required for burner management and
combustion control.
Available to less than 9 ppm NOx (LNXL/NTXL)
1,800/3,600 rpm Combustion Fan motor horsepower is based on NOx and capacity requirement
Air-atomizing, low-pressure oil nozzle (steam atomization optional)
V-port oil flow control valve is used for maximum capacity and precise oil flow control
Parallel Positioning required for optimal control throughout the firing range
Hinged Rear Door and Access Panels for easy access to internal components
Gas Manifold on oil burners standard for easy upgrade to combination units
Combustion Air Fan efficient airfoil blade design smoothly lifts airflow over the entire blade, resulting in less motor horsepower requirement and significant noise reduction when compared to standard forced-draft fans
#2 Oil capability for backup fuel (LNXL/NTXL)
Uncontrolled Emissions Less than 30 ppm Less than 15 to 9 ppm
MMBTU (Gas Input) 37.8 – 92.4 37.8 – 92.4 37.8 – 92.4
GPH (Oil Input) 270 – 660 270 – 660 270 – 660
BHP (BHP = 33,475 BTU/hr) 900 – 2,200 900 – 2,200 900 – 2,200
Fuels Gas, #2 Oil, Combination Gas, #2 Oil, Combination Gas, #2 Oil, Combination
4
ProFire-Xl
5
IntegratedControls
HeatRecovery Burners
ExhaustSolutions
WaterSystems
Boilers
High Turndown and Low NOx
The ProFire-E series burner offers: natural gas, propane gas, air-atomized #2 oil, and combination gas and oil fuel
options from 8.4 to 42.0 MMBTU. The LNE burner, capable of less than 30 ppm NOx emissions, offers: natural gas,
propane gas, air-atomized #2 oil, and combination gas and oil fuel options from 8.4 to 42.0 MMBTU. Full modulation
operation and cam trim are standard for greater efficiency and cost savings.
Uncontrolled Emissions Less than 30 ppm
MMBTU (Gas Input) 8.4 – 42.0 8.4 – 42.0
GPH (Oil Input) 60 – 300 60 – 270
BHP (BHP = 33,475 BTU/hr) 200 –1,000 200 – 1,000
Fuels Gas, #2 Oil, Combination Gas, #2 Oil, Combination
low-pressure, air-atomizing system on oil with rotary vane compressor
Piston-type positive displacement oil metering system
Cam trim 14-point adjustment range
Parallel Positioning available for optimal control throughout the firing range
Rotary Air Damper precise fuel-to-air ratios
Hinged Air Housing for easy access to internal components
Gas Manifold on oil burners standard for easy upgrade to combination units
Combustion Air Fan efficient airfoil blade design smoothly lifts airflow over the entire blade, resulting in less motor horsepower requirements and significant noise reduction when compared to standard forced-draft fans
Induced FGR FGR modulating valve and shutoff valve (LNE)
#2 Oil capability for backup fuel (LNE)
ul and cul listed
ProFire-E
6
High Efficiency and Fuel VersatilityThe ProFire-D series burner offers: natural gas, propane gas, air-atomized #2–#6 oil and combination gas and
oil fuel options from 4.2 to 42.0 MMBTU. The LND burner, capable of less than 20 ppm NOx emissions, offers:
natural gas, propane gas, air-atomized #2–#6 oil, and combination gas and oil fuel options from 3.36 to 42.0
MMBTU. The ultra low-NOx D series offers natural gas, propane air mix, air atomized #2 oil, and combination gas/
oil fuel at capacities from 12.6 to 33.6 MMBTU. Full modulation operation and cam trim are standard for greater
efficiency and cost savings. The D burner is an excellent choice when firing alternative fuels such as digester,
waste oil, and biodiesel.
Uncontrolled Emissions Less than 20 ppm Less than 15 to 9 ppm
MMBTU (Gas Input) 4.2 – 42.0 3.36 – 42.0 12.6 – 33.6
GPH (Oil Input) 30 – 300 24 – 300 90 – 240
BHP (BHP = 33,475 BTU/hr) 100 – 1,000 80 – 1,000 300 – 800
Fuels Gas, #2–#6 Oil, Combination Gas, #2–#6 Oil, Combination Gas, #2 Oil, Combination
low-pressure, air-atomizing system on oil with rotary vane compressor
Piston-type positive displacement oil metering system for precise oil control
Cam trim 14-point adjustment range
Parallel Positioning available for optimal control throughout the firing range
nozzle line Electric Heater standard on medium to heavy oil burners
Rotary Air Damper for precise fuel-to-air ratios
Hinged Air Housing for easy access to internal components
Gas Manifold on oil burners standard for easy upgrade to combination units
backward-Curved Impeller provides adequate combustion air for various furnace pressures and high-altitude applications
Induced FGR FGR modulating valve and shutoff valve (LND)
#2 Oil capability for backup fuel (LND/NTD)
ul and cul listed (D/LND)
ProFire-D
7
IntegratedControls
HeatRecovery Burners
ExhaustSolutions
WaterSystems
Boilers
Low-NOx No FGR RequiredThe standard MTH series includes full modulation with parallel positioning and offers natural gas and propane gas
from 2.5 to 16.0 MMBTU per hour. Capable of low NOx/CO emissions without FGR, the MTH series features
a rugged FeCrAl-M alloy fiber material combustion element with metal fiber construction over a stainless steel
frame, providing flexibility, longevity and trouble free operation for the life of the burner. The design is ideal for use
with applications where low emissions are required and FGR is impractical or inaccessible. The MTH burner with
surface stabilized combustion guarantees reliable and quiet operation.
Uncontrolled to 9 ppm
MMBTU (Gas Input) 2.5 – 16.0
GPH (Oil Input) Not Applicable
BHP (BHP = 33,475 BTU/hr) 60 – 380
Fuels Gas Only
Parallel Positioning standard for optimal control throughout the firing range
Premix Fuel allows uniform flame distribution, low CO emission and high turndown
Rugged surface stabilized Premix Combustion Element ensures quiet combustion and low NOx/CO emissions throughout the entire firing range
Hinged Air Housing for easy access to internal components
Removable Mantle can be serviced, inspected and replaced without disconnection of fuel or power lines
low-nOx Emissions achieved without FGR
Combustion Air Fan efficient airfoil blade design smoothly lifts airflow over the entire blade, resulting in less motor horsepower requirements and significant noise reduction when compared to standard force draft fans
Inverted Configuration available in lieu of standard configuration to meet space requirements
ProFire-MtH
8
Furnace and Heater ApplicationsThe NTH series burner offers: natural gas, propane gas, propane air mix, air atomized #2 oil, and combination
gas and oil fuel options from 2.5 to 12.5 MMBTU. Suitable for firetube and watertube boilers, the NTH series
features low CO performance, a unique air damper design for easy combustion set up, as well as independent
low and high fire adjustment.
Less than 15 to 9 ppm
MMBTU (Gas Input) 2.5 – 12.5
GPH (Oil Input) 35.7 – 89.3 (size 50 – 125 only)
BHP (BHP = 33,475 BTU/hr) 60 – 300
Fuels Gas, #2 Oil, Combination
Cam trim 14-point adjustment range available
Parallel Positioning available for optimal control throughout the firing range
Center Core Gas stabilzer multiple staged gas injectors
staged Fuel hammerhead injectors with backflow orifices
Induced FGR modulating valve and shutoff valve
#2 Oil capability for backup fuel (sizes 50–125 only)
Panel Mount Options include top or rear mount flexibility
Inverted Configuration available in lieu of standard configuration to meet space requirements Hinged Rear Door and Access Panels for easy access to internal components
IntegratedControls
HeatRecovery Burners
ExhaustSolutions
WaterSystems
Boilers
ProFire-ntH
Heavy Duty and Fuel VersatilityThe ProFire-M series burner offers: natural gas, propane gas, air-atomized #2–#6 fuel oil, and combination gas
and oil fuel options from 1.4 to 10.5 MMBTU. Full modulation operation is standard for optimum performance to
meet load demand. The M burner is an excellent choice when firing alternative fuels such as digester, waste oil,
and biodiesel.
Uncontrolled Emissions
MMBTU (Gas Input) 1.4 –10.5
GPH (Oil Input) 10 – 751
BHP (BHP = 33,475 BTU/hr) 33 – 250
Fuels Gas, #2–#6 Oil, Combination1 Oil input (US GPH) calculated for #2 Oil @ 140,000 BTU/gal
9
low-pressure, air-atomizing system on oil with rotary vane compressor
Piston-type positive displacement oil metering system for precise oil control
Cam trim 14-point adjustment range standard on models M34–M105
Parallel Positioning available for optimal control throughout the firing range
nozzle line Electric Heater standard on medium to heavy oil burners
Rotary Air Damper for precise fuel-to-air ratios
Hinged Air Housing for easy access to internal components
Gas Manifold on oil burners standard for easy upgrade to combination units
Combustion Air Impeller provides adequate combustion air for various furnace pressures and high-altitude applications
ul and cul listed (except ME and MEG 14–30)
IntegratedControls
HeatRecovery Burners
ExhaustSolutions
WaterSystems
Boilers
ProFire-M
9
10
High Efficiency / Low EmissionsThe ProFire-V series burner offers: natural gas, propane gas, pressure-atomized #2 oil, and combination gas and
oil fuel options from 1.3 to 16.8 MMBTU. The LNV burner, capable of less than 30 ppm NOx emissions, offers:
natural gas, propane gas, pressure-atomized #2 oil, and combination gas and oil fuel options from 1.3 to 14.7
MMBTU.
Uncontrolled Emissions Less than 30 ppm
MMBTU (Gas Input) 1.3 – 16.8 1.3 – 14.7
GPH (Oil Input) 9.3 – 120 9.3 – 105.0
BHP (BHP = 33,475 BTU/hr) 31 – 400 31 – 350
Fuels Gas, #2 Oil, Combination Gas, #2 Oil, Combination
Cam trim 14-point adjustment range available
Parallel Positioning available for optimal control throughout the firing range
Dual-blade Air Damper offers precise control of combustion air flow throughout firing range
Gas Manifold on oil burners standard for easy upgrade to combination units
Combustion Air Impeller provides adequate combustion air for various furnace pressures and high-altitude applications
Induced FGR FGR modulating valve and shutoff valve (LNV)
#2 Oil capability for backup fuel
Panel Mount Options include top or rear mount flexibility
Inverted Configuration available in lieu of standard configuration to meet space requirements ul and cul listed
ProFire-V
11
Q SeriesThe standard Q Series includes on/off or modulation linkageless operation with DC pulse width modulation and
offers natural gas from .375 to 2.5 MMBTU per hour. Its totally enclosed, compact design allows provisions
for sealed combustion or fresh air intake. Outside air can easily be connected to the blower inlet without any
modifications to the burner.
Uncontrolled Emissions
MMBTU (Gas Input) .375 – 2.5
GPH (Oil Input) Not Applicable
BHP (BHP = 33,475 BTU/hr) 9 – 60
Fuels Gas Only
linkageless system standard for optimal control throughout the firing range
DC Pulse Width Modulation allows full blower speed contol without the use of air dampers
Full Enclosed Air Housing features a hinged cover for easy access to internal components and quiet operation
Combustion Air Fan efficient airfoil blade design smoothly lifts airflow over the entire blade, resulting in less motor horsepower requirements and significant noise reduction when compared to standard forced draft fans
sealed Combustion eliminates the need for outside air dampers and make-up air units typically required in every boiler room.
ul/cul & CsA listed
IntegratedControls
HeatRecovery Burners
ExhaustSolutions
WaterSystems
Boilers
ProFire-Q
Packaged Burner Systems 351 21st Street, Monroe, WI 53566 USA608.325.3141 • [email protected]
cleaverbrooks.com
Total integration doesn’t stop with the burner.Only Cleaver-Brooks offers complete boiler systems, from fuel inlet to
stack outlet, that are completely designed, engineered, manufactured,
integrated, and serviced by one company. That integration starts
with the burner, and Cleaver-Brooks has been perfecting this integral
element of the boiler system through innovation and expert engineering
for more than 80 years.
Boiler system icons are copyrights of Cleaver-Brooks, Inc.
Printed in the USA©2013 Cleaver-Brooks, Inc
CB-826810/13