NOTICE OF MEETING OF THE PLANNING AND ZONING …...BUDA, TX 7:00 PM - Tuesday, April 11, 2017 121 S....

17
Planning and Zoning Commission Agenda Page 1 April 11, 2017 NOTICE OF MEETING OF THE PLANNING AND ZONING COMMISSION OF BUDA, TX 7:00 PM - Tuesday, April 11, 2017 121 S. Main Street Buda, TX 78610 This noce is posted pursuant to the Texas Open Meengs Act. Noce is hereby given that a Regular P&Z Meeng Meeng of the City of Buda, TX, will be held at which me the following subjects will be discussed and may be acted upon. A. CALL TO ORDER A.1. Signed Agenda Agenda PZ 04112017 signed.pdf B. INVOCATION C. PLEDGE OF ALLEGIANCE TO THE FLAGS OF THE UNITED STATES AND TEXAS PLEDGE OF ALLEGIANCE TO THE TEXAS FLAG: Honor the Texas flag; I pledge allegiance to thee, Texas, one state under God, one and indivisible. D. ROLL CALL E. PUBLIC COMMENTS At this me, comments will be take from the audience on non-agenda related topics, for a length of me not to exceed three minutes per person. To address the Planning and Zoning Commission (P&Z), please submit a Cizen's Comment Form to the City Liaison prior to the start of the meeng. No acon may be taken by the P&Z during Public Comments. F. CONSENT AGENDA F.1. Approval of the regular Planning and Zoning Commission meeng minutes dated March 28, 2017. 032817 minutes.pdf G. REGULAR AGENDA G.1. Workshop regarding the draſt Unified Development Code provisions for Subdivision Regulaons (pages 229-335), Sight Visibility Triangle (pages 336-339), Wireless Transmission Facilies (pages 373-385), Tree Preservaon & Park Land (pages 386-398), Environmental Protecon & Water Quality (pages 399-410), Flood Protecon (pages 411-420), and Well Drilling (pages 421-423). UDC Workshop Part 5.pdf H. STAFF REPORTS 1

Transcript of NOTICE OF MEETING OF THE PLANNING AND ZONING …...BUDA, TX 7:00 PM - Tuesday, April 11, 2017 121 S....

Planning and Zoning Commission Agenda Page 1 April11, 2017

NOTICE OF MEETING OF THEPLANNING AND ZONING COMMISSION

OF BUDA, TX

7:00 PM - Tuesday, April 11, 2017121 S. Main Street

Buda, TX 78610

This notice is posted pursuant to the Texas Open Meetings Act. Notice is hereby given that a Regular P&Z MeetingMeeting of the City of Buda, TX, will be held at which time the following subjects will be discussed and may be actedupon.

A. CALL TO ORDER

A.1. Signed Agenda

Agenda PZ 04112017 signed.pdf

B. INVOCATION

C. PLEDGE OF ALLEGIANCE TO THE FLAGS OF THE UNITED STATES AND TEXAS PLEDGE OF ALLEGIANCE TO THE TEXAS FLAG: Honor the Texas flag; I pledge allegiance to thee, Texas, one stateunder God, one and indivisible.

D. ROLL CALL

E. PUBLIC COMMENTS At this time, comments will be take from the audience on non-agenda related topics, for a length of time not toexceed three minutes per person. To address the Planning and Zoning Commission (P&Z), please submit aCitizen's Comment Form to the City Liaison prior to the start of the meeting. No action may be taken by the P&Zduring Public Comments.

F. CONSENT AGENDA

F.1. Approval of the regular Planning and Zoning Commission meeting minutes dated March 28, 2017.

032817 minutes.pdf

G. REGULAR AGENDA

G.1. Workshop regarding the draft Unified Development Code provisions for Subdivision Regulations (pages229-335), Sight Visibility Triangle (pages 336-339), Wireless Transmission Facilities (pages 373-385), TreePreservation & Park Land (pages 386-398), Environmental Protection & Water Quality (pages 399-410),Flood Protection (pages 411-420), and Well Drilling (pages 421-423).

UDC Workshop Part 5.pdf

H. STAFF REPORTS 1

Planning and Zoning Commission Agenda Page 2 April11, 2017

I. COMMISSION REQUEST FOR FUTURE AGENDA ITEMS

J. ADJOURNMENT City Hall is wheelchair accessible and accessible parking spaces are available. Requests for accommodationsmust be made 48 hours prior to the meeting. Please contact City Hall at (512) 312-0084, or FAX (512) 312-1889for information or assistance.

I, the undersigned authority, do hereby certify that the above Notice of Meeting of the Planning and ZoningCommission of the City of Buda, was posted on the bulletin board in front of Buda City Hall, which is readilyaccessible to the public at all times, by 5:00 pm on DATE, 2016.

Council Chambers are set up to publicly broadcast meetings. You may be audio and video recorded while in this facility.

In accordance with Article III, Section 3.10, of the Official Code of the City of Buda, the minutes of this meeting consist of the preceding MinuteRecord and the Supplemental Minute Record. Details on meetings may be obtained from the Board Liaison, or video of the entire meeting may bedownloaded from the website. (Portions of the Supplemental Minute Record video tape recording may be distorted due to equipment malfunctionor other uncontrollable factors.)

Attendance by Other Elected or Appointed Officials: It is anticipated that members of other governmental bodies, and/or city boards,commissions and/or committees may attend the meeting in numbers that may constitute a quorum of the body, board, commission and/orcommittee. Notice is hereby given that the meeting, to the extent required by law, is also noticed as a possible meeting of the other body, board,commission and/or committee, whose members may be in attendance, if such numbers constitute a quorum. The members of the boards,commissions and/or committees may be permitted to participate in discussions on the same items listed on the agenda, which occur at themeeting, but no action will be taken by such in attendance unless such item and action is specifically provided for on an agenda for that body,board, commission or committee subject to the Texas Open Meetings Act.

2

3

4

CITY OF BUDA PLANNING AND ZONING COMMISSION

MEETING MINUTES MARCH 28, 2017 - 7:00 P.M.

A. CALL TO ORDER

Chair Strother called the meeting to order at 7:00 p.m.

B. INVOCATION

C. PLEDGE OF ALLEGIANCE TO THE FLAGS OF THE UNITED STATES AND TEXAS PLEDGE OF ALLEGIANCE TO THE TEXAS FLAG: Honor the Texas flag; I pledge allegiance to thee, Texas, one state under God, one and indivisible.

D. ROLL CALL Commissioner Henry Altmiller Present Commissioner Angela Britain Absent - Excused Commissioner Michael Britton Absent - Excused Vice-Chair Meghan McCarthy Present Commissioner Clark Beach Present Commissioner John Ellis Present Chair Colin Strother Present

E. PUBLIC COMMENTS At this time, comments will be taken from the audience on non-agenda

related topics, for a length of time not to exceed three minutes per person. To address the Planning and Zoning Commission, please submit a Citizen Comment Form to the City Liaison prior to the start of the meeting. No action may be taken by the Planning and Zoning Commission during Public Comments No comments were made.

F. CONSENT AGENDA

1. Approval of the regular Planning and Zoning Commission meeting minutes dated March 14, 2017.

Commissioner Altmiller made the motion to approve the minutes, seconded by Commissioner Ellis. The motion passed 5-0.

G. REGULAR AGENDA ITEMS

1. Deliberation and possible action regarding a final plat of Stoneridge Section 4, located between Old Goforth Road (County Road 119) and Saddleblanket Trail (FP 16-14) Commissioner Altmiller made the motion to approve the final plat, seconded by Commissioner McCarthy. The motion passed 4-1 (Strother opposed).

5

2. Update regarding legislative issues relevant to planning & development and the City of Buda Staff gave a presentation to the commission.

3. Workshop regarding the draft Unified Development Code provisions for Form Based Code (pages 64-103) and Zoning Development Regulations & Compatibility (pages 104-163). Staff gave a presentation to the commission. The Commission provided comments and feedback regarding the respective sections of the draft Code.

H. STAFF REPORTS

The Planning & Zoning Commission may discuss any of the items under Staff Reports, but no formal action will be taken. Update regarding the Unified Development Code Re-Write Update regarding the activities of other city Boards and Commissions, including the Economic

Development Corporation Board. Update regarding recent and ongoing Capital Improvements Projects

I. COMMISSION REQUESTS FOR FUTURE AGENDA ITEMS

No deliberation or discussion may take place by the Commission during this agenda item. J. ADJOURNMENT

Commissioner Altmiller made a motion to adjourn the meeting, and a second was made by Commissioner Ellis. Upon a unanimous vote and having no further business to consider, Chair Strother adjourned the meeting at 8:50 p.m.

ATTEST:

________________________ Recording Secretary

6

Planning & Zoning Commission Agenda Item Report

April 11, 2017

Contact – Chance Sparks, AICP, CNU-A, Assistant City Manager – 512-312-5745 – [email protected]

SUBJECT: WORKSHOP REGARDING THE DRAFT UNIFIED DEVELOPMENT CODE PROVISIONS FOR SUBDIVISION

REGULATIONS (PAGES 229-335), SIGHT VISIBILITY TRIANGLE (PAGES 336-339), WIRELESS TRANSMISSION FACILITIES (PAGES 373-385), TREE PRESERVATION & PARK LAND (PAGES 386-398), ENVIRONMENTAL PROTECTION & WATER QUALITY (PAGES 399-410), FLOOD PROTECTION (PAGES 411-420), AND WELL DRILLING (PAGES 421-423).

1. EXECUTIVE SUMMARY Note: the schedule has been revised below to allow further discussion of the form based code aspects at the Planning & Zoning Commission and to allow the Planning & Zoning Commission to review input from the Historic Preservation Commission. The adjusted schedule also leaves space should a particular topic area need follow-up. Staff will be systematically bringing workshops to the Commission and City Council over the next two months pertaining to the draft Unified Development Code. The intent is to allow both bodies to review the document in smaller portions as it is prepared for adoption. A secondary purpose is to help staff familiarize themselves with the new Code for implementation. Rather than include code excerpts behind this staff report, staff has provided page references to the draft, which has been provided in hard & electronic copy to the Commission and City Council and posted online (viewable at http://ci.buda.tx.us/404/Unified-Development-Code-Re-Write). The anticipated schedule is as follows. Some of these groups have more pages to review, but staff attempted to break them up by topical areas and based on the level of discussion likely involved. 2/14 Planning & Zoning Commission & 2/21 City Council 7

• Signage (pages 340-372) • Provisions & Procedures, including Authorities (pages 1-17) • Zoning Procedures (pages 164-212) • Zoning Relief Procedures (pages 213-221)

2/28 Planning & Zoning Commission & 3/7 City Council

• Zoning Districts (pages 19-22) • Residential Zoning Districts (pages 23-29) • Nonresidential Zoning Districts (pages 30-34) • Special and Form Based Zoning Districts (pages 35-39) – just the descriptions on

the form-based, not the specific regulations • Zoning Use Regulations (pages 40-58) • Zoning Dimensional Regulations (pages 59-63)

3/14 Planning & Zoning Commission & 3/21 City Council

• Zoning Development Regulations & Compatibility (pages 104-163) 3/16 Historic Preservation Commission

• Form Based Code (pages 64-103) • Historic District (pages 186-198)

3/28 Planning & Zoning Commission & 4/4 City Council

• Form Based Code (pages pages 64-103) 4/11 Planning & Zoning Commission & 4/18 City Council

• City Council asked to pass resolution setting the joint public hearing & adoption process

• Subdivision Regulations (pages 229-335) • Sight Visibility Triangle (pages 336-339) • Wireless Transmission Facilities (pages 373-385) • Tree Preservation & Park Land (pages 386-398) • Environmental Protection & Water Quality (pages 399-410) • Flood Protection (pages 411-420) • Well Drilling (pages 421-423)

4/25 Planning & Zoning Commission & 5/2 City Council

• Any clean-up or spillover from prior meeting

5/9 Potential Joint Public Hearing of Planning & Zoning Commission and City Council • Joint hearing at 6:30 p.m. (technically a special called City Council meeting) • Regular Planning & Zoning Commission meeting at 7:00 p.m.

o Planning & Zoning Commission action possible

5/23 Planning & Zoning Commission regular meeting • Can be used for any further clean-up or spillover • Planning & Zoning Commission action possible if not taken on 5/9 8

6/6 City Council

• City Council action

2. BACKGROUND/HISTORY Staff has prepared a draft matrix of comments from the last Commission meeting as well as the City Council meeting for tracking purposes.

3. STAFF’S REVIEW AND ANALYSIS Staff notes this grouping of topics covers a large number of pages. Many of these sections are not changing substantially due to influence of state & federal laws. Subdivision Regulations (229-335)

• 231: Improvement Agreement process formalized. This is to address items like utility oversizing. For example, a project might require only an 8” water line, but the water master plan states an ultimate plan for a 12” water line. An Improvement Agreement serves to address the pro-rata oversize cost so that the ultimate needed line size is installed in order to avoid coming back to upsize in the future at greater expense.

• 233: Clarifying utility extension policies in the ETJ. This is ambiguous in the current UDC.

• 234-239: Procedural items clarified to better link to state law language and become easier to follow.

o 237: update to 15 day personal mailed notice (not as essential as zoning notice, but consistency will make it easier for staff)

• 240: Process diagram needs a few additional notes (cases of fiscal surety allowing plat recording prior to full construction of improvements)

• 242: Types of plats table requires update to reflect P&Z as primary approval authority

• 243-260: Several edits have taken place to reflect P&Z as the approval authority on plats

• 261: Section added to address licensing for ROW/easement encroachment. • 262: Section added to address petitions for development agreements. This was

inadvertently left out of an earlier draft. o These will be relatively rare and should mostly be driven by annexation

timing, unusual circumstances involving public improvements, etc. • 265-275: Standard language regarding public improvements • 276-294:

o Stronger adequate public facilities language o 279-281: tightened block lengths & widths, connectivity ratio increased to

1.60 o 286: Minimum number of subdivision access points is updated

287: edit needed regarding authority to reduce o Remainder thru 294 is engineering technical standards

9

• 295: TIA section was revised previously. It is designed to better address incremental adjacent projects that individually do not trigger a TIA, but collectively would.

• 304: Need minor edit to clarify residential neighborhood stormwater facilities are maintained by the city. Drainage requirements are more detailed in terms of how neighboring properties affect one another.

• 308: should refer to water capacity in 3.05.13.A.4.; B.1.a. needs to clarify that connection to the city or an existing public utility (Goforth, Monarch, etc.).

• 308-320: Remainder of utilities fairly straightforward. Street lighting language is updated/clarified.

• 320-335: Subdivision waiver process goes through City Council. This gives City Council final say, and serves to discourage seeking waivers since it extends the process. Vesting process is set and structured to maximize city authority under state law. Also addresses proportionality under state law.

Sight Visibility Triangle (336-339)

• Poorly described in current code, this provision provides significantly more clarity. It is cross-referenced throughout the UDC, which is why it has its own section.

Wireless Transmission Facilities (373-385)

• Very few changes, mainly just to address recent rulings (co-location language) • There are likely to be changes in laws over the next 2-4 years that will affect this • Improved graphics and additional tables • 377: need to clarify how the wireless areas apply in form districts (will be highly

restricted, similar to “Developed Residential”)

Tree Preservation & Park Land (386-398) • As discussed, now three different classifications of trees (8” protected, 20”

signature & 30” heritage) • Placed critical root zone language into ordinance • Added language regarding arbor disease centers to grant city additional authority • Parkland standards, language largely unchanged

o Staff anticipates updates to fees in late 2017/early 2018

Environmental Protection & Water Quality (399-410) • 399-410: Water Quality standards largely remain the same; integrated into the

UDC document rather than as a confusing appendix.

Flood Protection (411-420) • Major changes are simply to expressly prohibit certain activities in the floodplain,

rather than regulating it out of existence through multiple provisions. • The more significant effort will involve alterations to the engineering criteria

manuals, as those contain the assumptions used for design, storm events, etc. • Potential opportunities:

o Require Zone X (500-year) to be elevated 1.5’ to 2’ above finished grade or crown of street 10

o Require all structures to be elevated 1.5’ to 2’ above finished grade or crown of street

o Require elevation certificate on all new construction, not just in or proximate to floodplain

Well Protection (421-423)

• This is a new provision to establish standards for protection. This was contemplated a few years ago as a separate ordinance. Staff is referring to legal for updated evaluation, as some laws have changed.

4. FINANCIAL IMPACT

N/A

5. SUMMARY/CONCLUSION This is a discussion item.

6. PROS AND CONS N/A

7. ALTERNATIVES

N/A

8. RECOMMENDATION This is a discussion item presented without recommendation.

11

Comment

No. Page Section

City Council

Date Comment

1 2 1.02.01 2/21/2017 There is inconsistency between the SUP processes. The process

should be for P&Z to recommend and City Council to approve. P&Z

could approve extensions only. I think the phrasing of site plan for

a SUP and SUP regulations & procedures is causing some level of

confusion.

2 2 1.02.01 2/21/2017 Rather than have "decide by application", go ahead a break those

out when they occur. For example, tree removal for protected

tree, tree removal for signature tree and tree removal for heritage

would be listed separately. Also, the tree removal for heritage tree

is not listed on City Council.

3 2 General 2/21/2017 It is difficult to find the cross referenced tables and figures when

using a hard copy. Is it possible to prompt the page number the

table appears on? For example, when "Table 30" is referenced,

could it instead say "Table 30 (page ###)"?

4 15 1.03.01.D. 2/21/2017 The refund language is very confusing. Recommend the following:

"Unless waived by City Council, the prescribed fee shall not be

refundable unless it was submitted in error"

5 16 1.04.C. 2/21/2017 Add "Innovative Residential" to the list. Also, Commission

commented about the phrase "concept plan" in reference to

innovative residential. Is the correct term supposed to be "sketch

plan"?

6 164 2.10.01 2/21/2017 B, D, and E appear to conflict with themselves related to when

something is considered accepted, versus complete versus vested.

Basically, how would D even occur since we would not accept an

incomplete application anyway? How can something expire that

was not accepted? Or is this one of those oddly worded provisions

to prevent vesting under Ch. 245 (like the old stories of coctail

napkin drawings resulting in vesting)?

7 169 2.10.03.E.3. 2/21/2017 City staff should be responsible for posting the sign. This is how we

have done it for years, and it assures sign placement in the best

interest of the public (not tucked away in some bushes, etc.)

8 170 2.10.03.H. 2/21/2017 From discussions, we think it would be good to include an example

of how the 20% protest is calculated. For example, the 200' buffer

might equal 10 acres, with six people notified with their respective

amounts of acreage within the notice buffer. Basically,

demonstrate with a commentary example in the code exactly how

the protest is calculated using actual numbers, like a scenario.

4/7/2017 1 of 6 Rolling UDC Workshop Comments

12

9 173 2.10.04.C.5. 2/21/2017 The Commission and City Council would like to go ahead and

codify an additional "courtesy notice" beyond 200'. Staff feels 400'

would work adequately. Suggestion is to make 2.10.04.C.2.b.

"written notice for protest" and then create an additional written

notice subsection called "written notice for courtesy interest" that

applies to properties 200' to 400'. Include a statement that a

property receiving a protest notice is not required to also receive

the courtesy notice.

10 186 2.10.10.C.3. and

2.10.10.C.4.

2/21/2017 The public hearing process & notification timing for designating

historic district overlays and historic district landmarks should be

identical to other zoning districts (timing of published & written

notices, etc.)

11 196 2.10.10.E.8. 2/21/2017 The due process for demolition/right to remove seems weak.

Sending to Texas Historical Commission/Main Street Program for

evaluation.

12 199 2.10.11.C.3.b. 2/21/2017 Add language to allow discretion to adjust sidewalk placement &

dimensions when necessary to protect critical root zones of trees.

13 200 2.10.11.D. 2/21/2017 Add a provision that fuel pumps must be located to the side or

rear of the primary structure in the Rural Overlay

14 203 2.10.12.D. 2/21/2017 Recommend creating a use chart showing base zoning, as some of

these uses are okay in some parts of the overlay but not in other

parts. STAFF IS WORKING ON DRAFT CHART.

15 209 2.10.13.F.5. 2/21/2017 There may be some unintended consequences of this provision.

Opens opportunity for undesirable structures, such as mobile

homes, to get moved around rather than amortized as desired.

16 350 4.02.08.Table 37 2/21/2017 O-H covers both residential and commercial uses. Need to

differentiate, as generic use of O-H implies that someone could

potentially attach a marquee sign to a home. Rather than use O-H,

maybe just break out the F3H, F4H and F5H in the table and delete

O-H. Also, the rural overlay does not appear in the chart.

17 351 4.02.08.all 2/21/2017 On each of the tables for the particular sign type, can we also list

the zoning districts allowed? I know it appears on the Table 37

chart, but placing on each sign type as well allows each sign type

page to function like a handout with all critical information.

18 352 4.02.08.C. 2/21/2017 Preference is to keep all monument signs a maximum of 12'

19 372 4.02.11.C. 2/21/2017 Evaluate violation & removal provisions for efficiency and

consistency with other penalty & fine provisions. STAFF IS

WORKING ON COMPARISON.

20 19 Table 10. 3/7/2017 The table is missing a reference to 2.03.05. for the R-4 district.

21 26 2.03.04. 3/7/2017 The name of this district should be changed to "One & Two Family

Residential (R-3) District", and all references throughout the UDC

draft updated. The density described in the narrative does not

match 2.07.01. on page 59.

4/7/2017 2 of 6 Rolling UDC Workshop Comments

13

22 27 2.03.05. and

2.03.06

3/7/2017 R-4 vs. R-5 is not clear. R-4 should be renamed to "Transitional

Residential (R-4) District". The type of density shown in R-5 should

not occur in isolation outside of a mixed use node, which should

then be utilizing a form district. Several changes are

recommended, as provided in detail in comment 38.

23 35 2.05.01.B. 3/7/2017 Add "Development standards in this overlay apply to those parcels

abutting the Rural Heritage Right-of-Way, or to those parcels

abutting a shallow parcel that does abut the Right-of-Way (for

abutting parcels that are within four undred [400] feet in depth

from the Right-of-Way)"

24 36 2.05.02.B. 3/7/2017 Update referenced depth from 200' to 400' in order to eliminate

potential loophole properties. In addition, the narrative needs to

delete FM 2770 and add W. Goforth (from Cedar St. to Interstate

35.

25 36 Figure 2. 3/7/2017 Update map to show extension of Gateway Overlay to touch the

historic overlay

26 41 2.06.04. 3/7/2017 Remove "Dwelling, Multi-Family (3-Plex/4-Plex)" from the R-3

zoning district. See also comment 38 and the referenced

substitute table.

27 41 2.06.04. 3/7/2017 Remove "Dwelling, Multi-Family (Apartment)" from the R-4 zoning

district. See also comment 38 and the referenced substitute table.

28 45 2.06.04. 3/7/2017 "Stadium or Play Field, Public" contains insufficiently scaled uses.

While a simple ballfield might be fine in any zoning district, a

stadium with lighting is cause for concern. Recommend splitting

the uses and adding a condition requiring a SUP when lighting is

involved.

29 45 2.06.04. 3/7/2017 Prisons and Detention Facilities are not listed as a use. Need to

add the use, a specify that it requires a SUP in LI or HI.

30 46 2.06.05. 3/7/2017 May want to add a cross-reference regarding appeals to the

application or interpretation of conditional uses. May even want

to include it with 2.06.02. & 2.06.03.

31 48 2.06.05.A.3. 3/7/2017 This language appears twice. Recommend deletion & simply cross-

referencing the license contained in 2.06.05.A.1.h.

32 49 2.06.05.A.3. and

2.09.07. by

reference

3/7/2017 Innovative Residential Development should be defined, and the

types of Innovative Residential Development also defined. The

definition for Innocative Residential Development should also link

to the types. While they are somewhat described, they are terms

of art that would benefit from definitions in order to better

communicate with layperson users of the UDC document.

33 51 2.06.05.A.9.e. 3/7/2017 This condition needs to be clarified that it is intended to apply to

open containers, in contrast to package/bottle sales or growler

sales in closed/sealed containers.

34 51 2.06.05.A.9.f. 3/7/2017 This section can be revised to simply reference the City of Buda

Code of Ordinances, as amended, pertaining to Industrial Waste

(Chapter 24)

4/7/2017 3 of 6 Rolling UDC Workshop Comments

14

35 55 2.06.05.A.18.h. 3/7/2017 Consideration of unintended consequences… Example of an

accountant that has an administrative support person come to the

home being inoccuous. Example also given of a home art studio

that might involve some of the listed nuisances (grinding metal of

a metal artist)

36 56 2.06.05.A.20. 3/7/2017 For clarity, recommend pulling in the locational/zoning restrictions

from the separate ordinance in order to make the UDC more

useful to businesses as well as the building official. ADD

LANGUAGE.

37 57 2.06.05.A.23. 3/7/2017 Delete "and temporary building material storage areas." That

clause seemed ripe for abuse.

38 59 2.07.01. 3/7/2017 R-3 thru R-5 need additional consideration in order to

differentiate, get desired results and address inconsistencies. Note

that the changed lot standards will create a number of existing

nonconforming lots--2.10.13.D. (page 206) establishes that

undersized existing lots will be considered conforming, though

there may be variances requested in the future for reconstructions

due to increased side & front setbacks.

SEE RECOMMENDED TABLE ATTACHED. Note that in R-3, the only

way to actually achieve the listed density is to intermix townhouse

and duplex. Goal is a mix of housing types, and if they go entirely

single-family detached then the problems seen in Buda with small-

lot single-family will be addressed. MAY NEED TO ADD A

NOTE/COMMENTARY EXPRESSLY STATING THIS SO FUTURE

READERS DO NOT INTERPRET THIS AS AN INCONSISTENCY

BETWEEN MINIMUM LOT SIZE AND DUA, AND SO FUTURE

READERS UNDERSTAND WHAT THIS PROVISION IS TRYING TO

ENCOURAGE.

39 59 2.07. 3/7/2017 Recommend adding specific cross-references to regulations.

Particularly the water quality restrictions that limit impervious

cover.

40 60 2.07.02. 3/7/2017 Because mixed use is allowed in B-1 thru B-3, there is a need to

include a DUA for the residential component. Recommend B-1 at 6

DUA, B-2 at 10 DUA and B-3 at 14 DUA.

41 62 2.07.03. 3/7/2017 For patio homes, need to add a design requirement for passive vs.

active sides. Recommend adding a provision: "The wall of the

dwelling located on the lot line shall have no windows, doors, air

conditioning units or any other type of opening."

42 60 2.07.02. 3/7/2017 Consider allowance of 0' interior side setback in all, as it is not

uncommon for a commercial center that looks like a single

building & property to actually be 2-3 buildings on fee-simple

ownership land with "party walls" separating them, not unlike a

residential townhouse. As an alternative the table could be left as-

is, and a section added to Modified Area Regulations to craft

language to address commercial buildings on separate lots with a

shared "party wall."

4/7/2017 4 of 6 Rolling UDC Workshop Comments

15

43 113 2.09.02.D. 3/21/2017 Retitle simple as "Electric Fences" since there are provisions that

apply in districts other than AG

44 114 2.09.02.E.4&6 3/21/2017 Modify to allow use of chain link for residential for side and rear

fences not facing a public street

45 124 2.09.04.Table 17 3/21/2017 Would be comfortable reducing rear setbacks in circumstances

involving detached garages down to 10' provided height does not

exceed 20'

46 126 2.09.05.A.2. 3/21/2017 Add a "c." that grants an exemption to exterior materials for

circumstances in which the percentage of Class 1 or Class 2 is less

than the requirement of "a." Also add a "d." that clearly states the

Historic Preservation Commission may waive Section 2.09.05.A.

for properties within the Historic Overlay District.

47 127 2.09.05.D. 3/21/2017 This section can be deleted. Definitions of various classes of

masonry are sufficient and any product that clearly doesn't fit the

definition should be brought as a special exception to P&Z.

48 127 2.09.05. 3/21/2017 Define board & batten

49 130 2.09.06.D.7. 3/21/2017 Is the separation distance measured structure to structure, or

property line to property line? Example: this is in the form-based

area… the service side of the properties facing Main Street is

located on Austin Street, which means residences face directly at

them. Due to site constraints, it may not be possible to locate

dumpsters in a way that results in sufficient separation from single

family residences.

50 131 2.09.07. 3/21/2017 There is a need to create actual definitions for "terms of art" in

this section. I would suggest creating a definition for "Innovative

Residential Development" and then have sub-definitions under it

for "Cluster," "Pocket Neighborhoods," "Low Impact Design," and

"Traditional Neighborhood Design." The section is capturing

intent, but the terms themselves are not well-defined.

STAFF TO PROVIDE DEFINITIONS

51 136 2.09.07.H. 3/21/2017 References 3.05.05.B.1., which no longer exists. Please delete the

"Pathways" requirement.

52 138 2.09.08.B. 3/21/2017 Add a "e." that establishes that a garage door facing the street

cannot comprise more than 50% of the front façade

53 140 2.09.08.C.4. 3/21/2017 See comment for 2.09.04.Table 17 (comment 45). Cross reference

or ensure it is clear that rear setback can be reduced to as little as

10' for rear garages since we want to encourage this design.

54 115 2.09.03.B.1.b. 3/21/2017 This can be deleted. There seems to be discomfort in establishing

a cap, particularly in situations where a building use may change

substantially. The current design of City streets does not facilitate

on-street parking as an overflow option in many instances.

4/7/2017 5 of 6 Rolling UDC Workshop Comments

16

55 41 2.06.04 3/21/2017 For Multifamily Dwelling (Apartment), add a provision for guest

parking. Recommend 1 space per 10 units unless you have a better

recommendation. This is based on known issues in existing

complexes and the lack of on-street parking as an overflow option.

56 128 2.09.06. 3/21/2017 Residential adjacency would clearly apply in circumstances where

a form district abuts R-1 thru R-3, but how does it apply with

residential uses adjacent to commercial uses within the form

districts? For a specific example, how does it apply along Austin

Street, where site constraints cause more significant issues on

items like dumpster placement? What about the masonry

screening wall? What about when a building transitions, such as a

residential home in F4H becomes a medical office, adjacent to a

single-family home in the adjacent F3H district?

57 99 2.08.07.E. 3/21/2017 How do irregular lots fit the dimensional requirements, such as an

irregular trapezoid? While this is listed on page 99, I think we

should add cross references somewhere obvious in the form

based code that link back to how setbacks are applied, building

coverage vs. impervious cover, height, etc. like is shown on Figure

6 on page 61

58 102 2.08.07.H. 3/21/2017 It appears a source of confusion is that terms are not defined

within the form-based code like they are for the regular code. For

example, transparency is not linked to the definitions to provide

clarity.

59 109 2.09.01.B.2.a. 3/21/2017 Need to add a provision that states existing trees can be credited

toward meeting this requirement on a equivalent caliper inch

basis.

60 143 2.09.09.B.2.g. 3/21/2017 Should refer to "Director of Planning" to be consistent with

remainder of document and authorities established in Section 1.

61 109 2.09.01.D.4. 3/21/2017 This section needs to be rewritten. The grammatical

inconsistencies make it difficult to understand.

62 64 2.08 4/4/2017 Please see the marked-up version of the Form-Based Code

sections

4/7/2017 6 of 6 Rolling UDC Workshop Comments