MINISTER OF ENERGY AND MINERAL RESOURCES REPUBLIC · PDF fileMINISTER OF ENERGY AND MINERAL...
Transcript of MINISTER OF ENERGY AND MINERAL RESOURCES REPUBLIC · PDF fileMINISTER OF ENERGY AND MINERAL...
Unofficial translation by Repit Suliyono----------------------------- http://repit.wordpress.com/ [email protected]
MINISTER OF ENERGY AND MINERAL RESOURCES
REPUBLIC OF INDONESIA
MINISTER OF ENERGY AND MINERAL RESOURCES REGULATION
NUMBER 04 OF 2009
CONCERNING
ELECTRIC POWER DISTRIBUTION CODES
BY THE GRACE OF GOD ALMIGHTY
MINISTER OF ENERGY AND MINERAL RESOURCES
Considering:
a. that the power distribution system has been developed and supported by the electricity supply
business, so the need for rules of distribution of electricity to create electrical power distribution
systems which are integrated, efficient, safe, reliable and quality;
b. that based on the considerations as referred to in letter a, it is necessary to stipulate Regulation of
the Minister of Energy and Mineral Resources concerning the Regulation on Electric Power
Distribution;
Bearing in mind:
I. Law Number 15 Year 1985 on Electricity (State Gazette of the Republic of lndonesia year 1985 No.
74, Supplement to State Gazette Number 3317 lndonesia);
2. Government Regulation Number 10 Year 1989 on Electricity Supply and Utilization (State lndonesia
1989 No. 24, Supplement to State Gazette Number 3394 lndonesia) as has been amended twice by
Government Regulation Number 26 Year 2006 (State Gazette of the Republic of lndonesia Year 2006
Number 56, Supplement to State Gazette of the Republic of lndonesia Number 4628);
3. Presidential Decree No. 187lM year 2004 dated October 20, 2004 as has been amended several
times and the latest amended by Presidential Decree No. 77lP Year 2007 dated August 28, 2007;
4. Regulation of the Minister of Energy and Mineral Resources No. 0030 of 2005 dated July 20, 2005
regarding Organization and Working Procedure of Ministry of Energy and Mineral Resources;
DECIDED:
To Stipulate: REGULATION OF THE MINISTER OF ENERGY AND MINERAL RESOURCES CONCERING THE
POWER DlSTRlBUTION CODES.
Article 1
Electric Power Distribution Codes are as set out in Annex which is an integral part of this Minister
Regulation.
Unofficial translation by Repit Suliyono----------------------------- http://repit.wordpress.com/ [email protected]
Article 2
Electricity Distribution Codes as referred to in Article 1 shall be adhered to by all electricity supply
businesses operator and consumers of electricity who are connected to the Electric Power Distribution
System.
Article 3
Electricity Distribution Codes may be reviewed as needed.
Article 4
This Ministerial Regulation shall come into force on the date of enactment.
For public cognizance, it is ordered that this Minister regulation be promulgated in the State Gazette of
the Republic of Indonesia.
Stipulated in Jakarta
on February 20, 2009
MINISTER OF ENERGY AND MINERAL RESOURCES
Signed
Purnomo Yusgiantoro
Promulgated in Jakarta
on February 20, 2009
MINISTER OF JUSTICE AND HUMAN RIGHTS
REPUBLIC OF INDONESIA,
Signed
ANDl MATTALATTA
STATE GAZETTE OF THE REPUBLIC OF INDONESIA NUMBER 25 OF 2009
Unofficial translation by Repit Suliyono----------------------------- http://repit.wordpress.com/ [email protected]
ATTACHMENT TO THE REGULATION OF MINISTER OF ENERGY AND MINERAL RESOURCES
NUMBER : 04 OF 2009
DATE : 20 FEBRUARY 2009
ELECTRIC POWER
DISTRIBUTION CODES
DEPARTMENT OF ENERGY AND MINERAL RESOURCES
2009
Unofficial translation by Repit Suliyono----------------------------- http://repit.wordpress.com/ [email protected]
TABLE OF CONTENT
CHAPTER I INTRODUCTION.
CHAPTER II DISTRIBUTION CODE. (DC)
DC 1.0. Definitions.
DC 2.0. Scope
CHAPTER III DISTRIBUTION MANAGEMENT CODE (DMC)
DMC 1.0. The objectives.
DMC 2.0. Distribution Code Management Committee (KMAD)
DMC 3.0. Membership of KMAD
DMC 4.0. Organizational Structure of KMAD
DMC 5.0. Work Period KMAD Membership.
DMC 6.0. Sub-Committee
DMC 7.0. Meeting Time of KMAD
DMC 8.0. KMAD expenses.
DMC 9.0. Changes in Distribution Code.
DMC 10.0. Settlement of Disputes.
DMC 11.0. Enforcement of Distribution Code.
DMC 12.0. The report.
CHAPTER IV CONNECTION CODE-(CC)
CC 1.0. The objectives.
CC 2.0. Limitation of Connection Pont.
CC 3.0. Distribution System Technical Requirements
CC 4.0. PSD and Consumer Equipment Requirements
Equipment Requirements and Standards Used in Connection Distribution Point
CCL 1.0. General.
CCL 2.0. Requirements associated with the PSD and Consumer on Connection Point
CC 5.0. Connection procedures from the PSD with PD and PD with the Customer.
CC 6.0. Responsibilities of PD.
CHAPTER V OPERATING CODE-(OC)
OC 1. 0. Objectives .
OC 2.0. Responsibilities
OC 3.0. Distribution Protection
Unofficial translation by Repit Suliyono----------------------------- http://repit.wordpress.com/ [email protected]
OC 4.0 Load Settings
OC 5.0 Emergency.
OC 6.0 Recovery Procedures.
OC 7.0 Testing and Inspection
OC 8.0 Inspection and Permissions to enter the Installation Location
OC 9.0 Communication and Reporting Procedures.
OC 10.0 Limits of responsibility of Distribution System Maintenance
OC 11.0 Preparation Procedure and Implementation of Maintenance Works
OC 12.0 Procedures on Occupational Health and Safety (K3)
CHAPTER VI PLANNING CODE-PC
PC 1.0. Objectives
PC 2.0. Responsibilities of All Parties
PC 3.0. Development of Distribution System Planning Study.
PC 4.0. Planning Data
PC 5.0. Spatial Planning
PC 6.0. Data needs.
CHAPTER VII SETTLEMENT CODE -(SC)
SC 1.0. Objectives
SC 2.0. Terms of the Transaction.
SC 3.0. Readings and Payments
SC 4.0. Dispute Settlement of the Transactions
SC 5.0. Settlement Process Audit Procedures
CHAPTER Vlll METERING CODE-(MC)
MC 1.0. Objectives
MC 2.0. Measurement Criteria.
MC 3.0. Meter Equipment Requirements
MC 4.0. Commissioning
MC 5.0. Post commissioning Tests
MC 6.0. Sealing and Reprogramming.
MC 7.0. Examination of Data Meter and Equipment.
MC 8.0. Measurement Equipment Security.
MC 9.0. Exceptions and Deadline
MC 10.0. Other provisions
GLOSSARY
Unofficial translation by Repit Suliyono----------------------------- http://repit.wordpress.com/ [email protected]
CHAPTER l
INTRODUCTION
Electricity Distribution Code is an integral part of Regulation of the Minister of Energy and Mineral
Resources No. 04 of 2009 dated February 20, 2009 on Electric Power Distribution Code.
Electric Power Distribution Code is a set of rules and requirements to ensure the safety, reliability and
operations and development of an efficient distribution system to meet increased electricity demand.
Electric Power Distribution Code is based on current conditions, to be applied to all businesses in the
distribution system, i.e. Suppliers of Distribution Systems (Power Grid and Small and Medium Scale Power
Plant), Distribution Operator, Consumers, and Resellers whose installation is directly connected to the
distribution system.
The operator of distribution system shall meet in all provisions of Electricity Distribution Codes as the
basis for the installation operation of power supply owned. In addition, provisions on Electric Power
Distribution Code will provide clarity regarding the obligations of each business operators in the
distribution system.
Electric Power Distribution Code is a dynamic document so it should always be updated by the
Management Committee of Distribution Code along with the development of distribution system
conditions and business structures and changes in the electrical system complexity.
Electric Power Distribution Code is equipped with a glossary which is an integral part of the Electric Power
Distribution Code.
Unofficial translation by Repit Suliyono----------------------------- http://repit.wordpress.com/ [email protected]
CHAPTER II
DISTRIBUTION CODE - DC
DC 1.0. Definition
Electric Power Distribution Code, hereinafter referred to as Distribution Code is a set of rules,
requirements and standards to ensure the safety, reliability and operations and the development of an
efficient distribution system to meet increasing electricity demand.
Distribution Code consist of:
a. Distribution Management Code.
b. Grafting Code.
c. Operating Code.
d. Planning Code.
e. Settlement Code.
f. Measurement Code.
DC 2.0. Scope
Scope of Distribution Code apply to all transactions and Suppliers interactions on Distribution Systems
(Power Grid and Small and Medium Scale Power Plant), Distribution Operator(PD),
Consumers, and Resellers as described in the following Scheme of Distribution System:
SCHEME OF DISTRIBUTION SYSTEM
Unofficial translation by Repit Suliyono----------------------------- http://repit.wordpress.com/ [email protected]
CHAPTER Ill.
DISTRIBUTION MANAGEMENT CODE –(DMC)
DMC 1.0. Objectives
Distribution Management Code is a rule and procedure that aims to:
a. ease monitoring of the suitability of Distribution Code;
b. ensure that all Parties are represented in the review and make recommendations if there are changes
to the Distribution Code;
c. establish a dispute resolution process and the enforcement of Distribution Code.
DMC 2.0. Distribution Management Committee Code
To run the Distribution Code it is necessary to form the Management Committee for Distribution Code,
hereinafter referred as KMAD with the following tasks:
a. monitor the implementation of the Distribution Code;
b. evaluate and review the administration of Distribution Code, if necessary;
c. study the proposed changes to Distribution Code;
d. resolve differences in understanding and/or disputes relating to the Distribution Code;
e. collect and/or publish information deemed necessary without violating any confidentiality, in a special
publication which is used for the purpose of distribution Code;
f. Disseminate the Distribution Code or issue necessary recommendations in writing;
g. form the Sub Committee and the Secretariat as required.
DMC 3.0. KMAD Membership
KMAD is formed by the Director General of Electricity and Energy Utilization with membership
representing the parties, namely:
a. PD represented by a maximum of 5 (five);
b. PLN head office is represented by 2 (two);
c. PSD represented by 3 (three), each 2 (two) of the Grid and 1 (one) out of PSKM;
d. large consumers represented 2 (two) persons
e. professional organizations in the field of electricity represented by 1 (one);
f. Directorate General of Electricity and Energy Utilization, represented by 1 (one);
g. Consumers Institute represented 1 (one).
KMAD members must have adequate background and experience so that they can understand and can
evaluate aspects related to the operation, planning, development and commercial distribution systems.
Unofficial translation by Repit Suliyono----------------------------- http://repit.wordpress.com/ [email protected]
DMC 4.0. Organizational Structure KMAD
a. KMAD led by the Chairman.
b. KMAD consist of 1 (one) as Chairman and member, 1 (one) as deputy chairman and member, 1 (one)
as secretary and the members and at most 12 (twelve) members.
c. KMAD Membership is valid for 3 (three) years, and can be re-elected. Chairman elected by members
through a specific mechanism for the establishment and the first time determined by the Director
General of Electricity and Energy Utilization.
d. In carrying out its duties, KMAD assisted by the Sub Committee and the Secretariat. Sub Committee
consisting of at least Sub-Committee on Planning and Operations Sub-Committee.
DMC 5.0 Work Period KMAD Membership
the working period of KMAD Chairman is for 3 (three) years and may be reelected for the next work
period. The chairmanship KMAD automatically expire if the party concerned permanently absent or no
longer working for the company / agencies represented and immediately elected his successor. While
working period for KMAD Members automatically terminate if there is an official letter from company /
agencies about withdrawal from KMAD membership concerned or concerned permanently absent or no
longer working for the company they represent and be elected his successor immediately.
DMC 6.0. Sub-Committee
KMAD form a Sub Committee on Planning and Operations Sub-Committee, and if required to establish
another subcommittee either a temporary or permanent.
DMC 6.1 Planning Sub Committee
Planning Sub Committee has the task:
a. Reviewing the annual development plan of distribution systems to ensure adequate provision of
reliability and efficiency of operations for the future;
b. review and recommend follow-up project proposals of distribution system development.
Unofficial translation by Repit Suliyono----------------------------- http://repit.wordpress.com/ [email protected]
DMC 6.2.
Operation of the Sub Committee
Operation of the Sub Committee has the task:
a. reviewing the annual report of the operation planning of distribution systems, and
b. recommend changes in operating procedures for reliability and economical operation of the
distribution system.
Sub-Committee shall conduct meetings every 3 (three) months to evaluate the realization of the
operation of 3 (three) months earlier.
DMC 7.0.
Meeting Time KMAD
a. KMAD can hold meetings for discussion of changes and / or disputes that occur any time.
b. Minimum of once of 1 (one) year KMAD hold a meeting to analyze and evaluate the implementation
of the Distribution Codes.
DMC 8.0.
KMAD costs
KMAD must prepare the operating budget for next year every September.
Operational costs are charged to the business operator of KMAD Distribution Codes and shall be further
regulated by KMAD.
DMC 9.0.
Distribution Code Changes
a. Proposed changes shall be submitted in writing to KMAD.
b. KMAD will study the proposal.
c. Proposed changes will be submitted in writing by KMAD to the Parties to obtain input / comments in
writing.
d. the Sub-Committee is ordered by KMAD the to examine, review and propose if the proposal of
changes is accepted / rejected to be determined by KMAD.
e. KMAD to make changes recommendations and propose to the Minister of Energy and Mineral
Resources through Director General of Electricity and Energy Utilization to be determined by the
Minister of Energy and Mineral Resources.
Unofficial translation by Repit Suliyono----------------------------- http://repit.wordpress.com/ [email protected]
DMC 10.0. settlement of Disputes
a. Notice of the dispute shall be submitted in writing to KMAD.
b. KMAD will study the notice.
c. Any dispute resolved by KMAD after hearing the responses from each party and be settled within no
later than 3 (three) months.
d. KMAD will establish dispute settlement decisions are final.
DMC 11.0. Enforcement Codes of Distribution
If KMAD believes there who violates the Codes of Distribution and the action deemed necessary KMAD
got the right to take action as follows:
a. KMAD will send a written warning to the party who commits an offense with an explanation of the
rules which are violated and the actions to be taken by the party break;
b. parties can use that violates the right of reply or take action recommended by KMAD the maximum
period I (one) month after receiving a written warning;
c. if KMAD approved the contents of the right of reply then the offense is considered closed;
d. KMAD if not approved the content of the right of reply then KMAD determined that the decision is
final.
DMC 12.0. Reports
a. Annual Report.
KMAD make a brief report of operational implementation of the Codes of Distribution to the
Directorate General of Electricity and Energy Utilization in March every year.
b. Important Events Reports
1) No later than 1 (one) week after an important event in the distribution system, PD sends a written
report to KMAD through the Operation Sub-Committee. The report contains details of the causes
and sequence of events as well as other relevant information such as number and duration of
power outages.
2) At least 1 (one) month after receipt of the report from the PD about important events, KMAD
decided sanctions or who should be responsible, in case there are those who violate the Codes of
Distribution.
c. Special Report :
If there is a special request from the Directorate General of Electricity and Energy Utilization, KMAD
must make a report on demand.
Unofficial translation by Repit Suliyono----------------------------- http://repit.wordpress.com/ [email protected]
CHAPTER IV
CONNECTION CODE-(CC)
Connection Code is a rule that details about the installation of the electrical connection procedures and
requirements must be met both technical and operational by the PD, PSD and Consumers who connect or
be connected to the distribution system.
CC 1.0. Objective
Connection is the Objective of the Rule:
a. explain procedures, techniques and operational requirements that must be complied with by the PSD
and the Consumer before and when connected to the distribution system;
b. ensure that the PSD and the Consumer will only be connected to the distribution system if the
fulfillment of the requirements engineering and connection procedures and other requirements listed
in Connection Code;
c. ensure that the PSD, Consumer and PD have the same reference in the connection process.
CC 2.0.
Connection Point Limit
Limitation of connection points include:
a. Consumer Connection 400/230 Volt electrical voltage.
1) The connection point is located after the APP.
2) PD can determine the location of a connection point other than the items a.1. for special technical
and economical consideration.
b. 20 kV Consumer electrical voltage connection.
1) The point of connection is located after the APP.
2) PD can determine the location of a connection point other than the items b.1. for special
consideration is technically and economically.
c. Consumers of high voltage electrical connections.
1) The point of connection is located after the APP.
2) PD can determine the location of a connection point other than item c.1. for special technical and
economical consideration.
d. PSD connection.
1) The point of connection is located after the APP energy transactions from PSD to PD.
2) The point of connection can be made in addition to the PSD in item D.1. according to collective
agreement
Unofficial translation by Repit Suliyono----------------------------- http://repit.wordpress.com/ [email protected]
CC 3.0. Distribution Technical System Requirements
a. All connection points following the distribution technical system requirements as follows:
1) the nominal system frequency is 50 Hz and have a normal frequency range between 493 Hz to
50.5 Hz.
2) voltage distribution system must be maintained at the boundaries of normal conditions of
maximum +5% and minimum -10% of nominal voltage.
3) a maximum total harmonic distortion is as the following table:
table 1
Maximum Limit of Harmonics Distortion - Voltage
Harmonics Distortion Individual Voltage (%)
Harmonics Distortion Individual Voltage (%)
3.0 5.0
table 2
Maximum Limit of Harmonics Distortion - Flows
Odd Harmonics, h H<11 11<h<17 17<h<23 23<h<35 35<h< TDD
Harmonics Distortion - Flows (%)
4.0 2.0 1.5 0.6 0.3 5.0
Note:
i. Harmonics Distortion Limit - Even Flow is 25% of the value in Table 2 above.
ii. Figures in the table apply to the number of harmonics (h) multiple of a frequency of 50 Hz.
4) Fluctuations in voltage at a high voltage connection point refers to the Codes of Distribution.
b. Distribution technical system requirements referred to in CC 3.0.a shall not apply during a fault
condition on the distribution system. And all the PD and PSD and Consumers are required to work
together to ensure that all distribution technical system requirements can be met.
CC 4.0. PSD and Consumer Equipment Requirements
CC 4.1. General Requirements
a. The entire equipment installed shall be operated and maintained in accordance with the technical
requirements of usage and distribution systems.
b. The whole equipment PSD, PD and Consumers must meet the requirements and standards provided
in these Terms and Standard Equipment Used at Connection Distribution Point, as follows:
Equipment Requirements and Standards Used to Connection Distribution Point
Unofficial translation by Repit Suliyono----------------------------- http://repit.wordpress.com/ [email protected]
CCL 1.0. General
All equipment connected to the distribution system must meet the standards set in SNI. For standard
equipment that has not been set within the SNI, can refer to international standards such as ANSI, IEEE,
NEC, NEMA, IEC or refer to the standards set by the PD (e.g.: SPLN).
CCL 2.0. Requirements Relating to the PSD and the Consumer Connection Point
Any connection between PSD, PD and Consumers will be controlled by the protective device that is able to
break the short circuit current and overload current the connection points.
CCL 2.1. Setting Protection Equipment
a. Protection on the PSD installation and Consumers connected to the distribution system must meet
the minimum requirements standard release time for interference.
b. Protection settings on the installations of PSD, PD, and the Customer shall be coordinated in order to
reduce the influence of disturbances on the distribution system.
CCL. 2.1.1 20 kV Network Protection
a. Protection system depends on the pattern of the system applied to the distribution system in each PD
(e.g.: Security Pattern System 6 kV and 20 kV SPLN 52-3: 1983).
b. Conductor terminals with power breaker shall be equipped with relay protection at least against short
circuit interruption
CCL. 2.1.2. Network Protection Low Voltage (400/230 Volt)
All low voltage network (400/230 Volt) connected to the distribution system must be equipped with load
divider and protection in accordance with SNI-04-0225-2000: General Requirements for Electrical
lnstallation 2000.
CCL. 2.1.3 protection PSKM
Protection of all PSKM connected on distribution system must be coordinated with the protection of
distribution systems are equipped with at least a short-circuit current protection phases and phase-
ground, power back protection, voltage protection more/less and frequency protection more/less.
2.1.4 CCL. Distribution Transformer Protection
All transformers which are connected to the distribution system shall be equipped with lightning
protection equipment and protective equipment against overload and short circuit current of the switch
or breaker fuser.
Unofficial translation by Repit Suliyono----------------------------- http://repit.wordpress.com/ [email protected]
CCL. 2.1.5 Protection for Low Voltage Connection (400/230 Volt)
All PSD and Consumers directly connected to the low voltage network must be equipped with barrier and
protection against interruption of short circuit / overload automatic switches or safety of melting.
CC 4.2. PSD Equipment Requirements
a. PSD equipment should be able to operate in accordance with available capacity.
b. PSD must complete the means of communication that may be associated with PD for the purpose of
coordination of operation system.
c. Protection equipment owned by the PSD and PD should be coordinated.
CC 4.3. Consumer Equipment Requirements
Consumer's protection equipment should be coordinated with the protection that apply in the
distribution system.
CC 5.0. Connection Procedures of the PSD with PD and PD with Consumers
CC 5.1. Connection procedures PSD with PD
CC 5.1.1. Connection procedures Grid with PD
Valid Procedures refer to the Codes of Networking
CC 5.1.2. Connection procedures of PSKM with PD
Procedures that apply generally to all PSKM are as follows:
a. PSKM must notify to the PD that the commissioning was done on PSKM's installation and have
obtained the SLO from an accredited institution;
b. PSKM must provide data and setting of the protection pattern to be approved by PD;
c. PSKM submit an installation connection request to the distribution system in writing;
d. PSKM together with PD to check and test the connection point of distribution to ensure that all
equipment functioning properly in accordance with the usability and capacity;
e. after the administrative and technical requirements be met as well as cooperation agreements or
agreed to purchase electrical energy, then PD expressed its approval of the connection of the
installations belonging to the PSKM to distribution system in writing.
Unofficial translation by Repit Suliyono----------------------------- http://repit.wordpress.com/ [email protected]
CC 5.2. Connection procedures between PD with Consumers
a. Consumers complete the administrative requirements.
b. Consumers passed the SLO from an accredited institution and / or electrical installation guarantee.
c. Consumers and the PD jointly checking against equipment / installation belonging to the Customer at
a connection point of distribution.
d. Consumers filed a request providing voltage to the PD after checking with equipment / installation
belonging to Consumers in the distribution connection point and has been found to comply with the
technical requirements of Connection Code by the PD.
e. PD can connect if equipment / installation meet the techniques requirements of Connection Code.
CC 6.0. Responsibility of PD
Before giving the voltage at a connection point, the PD must:
a. ensure that the installation of the PSD and the Customer have met all the requirements as referred to
in CC 3.0. and CC 4.0.
b. convey to the PSD and Consumer information as follows:
1) a list of equipment and performance that is owned by PD at connection points;
2) the level of service provided by the PD to the Customer at the connection point;
3) distribution system SOP to the PSD.
CC 6.1. Connection Points Inspection
PD did inspection / checking and evaluation at a connection point to ensure that distribution system is
safe for operation. The results of inspections communicated in writing by the PD to PSKM and Large
Consumers.
CC 6.2. Distribution of Voltage On Connection Point
after PD issued approval of the connection to the PSKM and Consumers, then an agreement is made
between the PD and PSKM/Consumer on the procedure and timing of the voltage distribution.
Unofficial translation by Repit Suliyono----------------------------- http://repit.wordpress.com/ [email protected]
CHAPTER V
OPERATING CODES (OC)
Codes of Operation explains the rules and procedures established to ensure human safety, equipment
safety, the environment and to ensure quality, reliability, operational efficiency and standards at a level
that can be maintained in the distribution system.
OC 1.0. Objective
The objective of this rule is to set things as follows:
a. operational responsibility of the PSD, PD and all distribution systems Consumers for safety and
reliability of distribution operations;
b. protection of distribution;
c. setting the load to overcome the shortage of supply of the PSD;
d. procedures to be followed by the PD, PSD, and the Consumer during emergencies;
e. restoration of distribution systems;
f. testing, monitoring, and inspection of the distribution system;
g. examination and admission to the installation location;
h. communication and reporting;
i. limits of responsibility in connection with maintenance activities;
j. coordinating the preparation and execution of maintenance work;
k. coordination of Occupational Health and Safety (K3).
OC 2.0. responsibility
This rule states the basic responsibility for the PSD, PD and Consumers for the safety and reliability of
distribution operations.
OC 2.1. Responsibilities and Obligations of Distribution Security
PD coordinate the distribution system operations to maintain the quality, reliability and security for the
distribution for PSD and consumer interests. PSD and the Customer shall be obliged to work with PD in
terms of testing of equipment and distribution facilities.
OC 2. I.I. Responsibility PD
To optimize the distribution system operating with a level of quality and good reliability, PD responsible
for:
a. maintain, monitor and maintain the quality and reliability in the distribution system;
b. maintain all equipment of distribution system;
c. guarantee to always follow the distribution system operating procedures which are safe and
economical;
d. make a list of Big Consumers which can reduce the burden voluntarily and / or turn on emergency
units (backup power plant).
Unofficial translation by Repit Suliyono----------------------------- http://repit.wordpress.com/ [email protected]
e. create a priority list of feeders to be extinguished manually (Manual Load Shedding);
f. create a priority list of feeders to be extinguished corresponding schema, UFR load shedding;
g. have standard operating procedures (SOP) that must be adapted to the development of the operating
system distribution;
h. maneuvering distribution network.
OC 2.1.2. Responsibility for PSD
PSD is obliged to ensure the safety, quality, reliability and quantity of electricity supply to the distribution
system.
PSD is responsible for:
a. coordinating maintenance plan, repair and development of PSD equipment that can affect the safety,
quality, reliability and continuity of supply of electricity;
b. immediately inform the PD of PSD operational conditions that will affect the disruption of quality,
reliability and continuity of supply of electricity;
c. provide data for the purpose of calculation of short circuit at a connection point for the coordination
of protection, among others, to ensure the reliability of the system and adjustments distribution
equipment capacity.
OC 2.1.3. Big Consumer Responsibility
Big consumers are responsible to participate in maintaining the integrity of the system, by the way:
a. maintain the flicker limit with numbers of voltage Depression on short Circuit (DTHS) does not
exceed 3% of nominal voltage.
b. individual harmonic distortion does not exceed 3% and the total harmonic distortion not exceed 5%. If
the above limit is exceeded, PD is entitle to check and take the necessary action to correct deviations
occur;
c. participate to reduce the burden of deficit;
d. disconnect the load when ordered by the PD or automatically with the under frequency relays and /
or under voltage relays to protect the security of energy supply of electricity.
OC 3.0. Distribution Protection
adequate Distribution protective devices and coordination of protection needed to protect distribution
equipment and prevent the widespread of disturbances on the distribution system. Distribution
protection procedures are as follows:
a. PSD and the Customer shall submit any changes to the pattern of protection to the PD for the
coordination of protection;
b. protection pattern of distribution should be according to the provisions of the applicable standards in
Indonesia.
Unofficial translation by Repit Suliyono----------------------------- http://repit.wordpress.com/ [email protected]
OC 4.0. Load Settings
OC 4.1. Coordination Load Settings When Power Deficit
If for any reason Grid issued a power supply shortage (deficit), then the PD along with Big Customer will
perform in the following order:
a. PD coordinate Big Consumers to reduce the burden or turn on the emergency unit (power backup) -
owned by Big Consumer voluntarily in accordance with appropriate SOPs agreed upon;
b. if the load reductions referred to in item a has not been able to overcome the power deficit then
voltage reduction will be done;
c, if the voltage reductions as referred to in point b has not been able to overcome the power deficit
then the load release is carried out manually.
When Grid has expressed the normal system conditions the PD immediately restore and normalize the
medium voltage system and notify the Big Consumers.
OC 4.2. Load Shedding through the UFR
In order to anticipate system disorder that causes the power deficit then to maintain the integrity of the
system, it is designed using the UFR load reduction scheme as follows:
a. sequence and a large load which is released by the UFR is considering operational needs and vital
loads;
b. Grid with PD determine the load to be released per area per stage for Load Shedding through UFR;
c. after a normal condition, PD should strive to quickly restore critical facilities which are included in the
Load Shedding.
OC 5.0. Emergency
Distribution system emergencies occur when:
a, shortage of electricity supply or distribution system voltage is not normal;
b. disorder that causes the separation of distribution system outages and or partial or total blackout;
c. severe weather, earthquakes, fires, riots, etc.. that threaten the security of the distribution.
PD, PSD and Consumers shall comply with the procedures referred to in OC 5.2. and OC 5.3. to restore the
distribution system as quickly as possible to the normal or standby network operation condition.
OC 5.1. Emergency Distribution Procedures Guidelines
PD create and inform the distribution of emergency procedures and make list of parties who are notified
in an emergency including name, address and contact phone number.
OC 5.2. Emergency Distribution Statement
PD will declare emergency distributions conditions in case of conditions as referred to in OC.5.0. letter a
up to c at least 1 x 24 hours after an emergency occurs.
Unofficial translation by Repit Suliyono----------------------------- http://repit.wordpress.com/ [email protected]
OC 5.3. Distribution Emergency Condition Notification
Immediately after the emergency condition of distribution has been declared, the PD will:
a. prepare the load that can be extinguished by priority to overcome the shortage of electricity supply.
Large load which is extinguished is based on the load target specified by the Grid;
b. notify the Customer of the emergency condition.
OC 5.4. Preparation of Emergency condition of Distribution
a. PD provides information to consumers in order to reduce the effect of disconnection of power supply
caused by:
1) natural disasters;
2) riots; or
3) events that can not be avoided,
b. conduct emergency condition of distribution simulations which is conducted of at least 1 (one) time a
year so that all responsible personnel trained in dealing with emergency distribution condition.
OC 6.0. Recovery Procedures
Recovery procedures are actions taken to restore the operating state of the fault conditions. For that
recovery SOP is needed to be established so that recovery can be done quickly and safely.
OC 6.1. The disruption in PSD side
a. If the disturbance in the PSD side resulted in interruption of power supply to the distribution system,
then the recovery procedure will be performed in accordance with mutual agreement between the
PSD and PD.
b. If the disturbance on the PSD side resulting passed the normal range of voltage and frequency, then
the PD will request information about the causes disruption of the PSD and asked for a recovery to
normal network operating conditions. Furthermore, the PD will inform the specific disorder to the
Large Consumers.
OC 6.2. The disturbances in Distribution System Side
If the disturbances in the distribution system side resulting in the operation of protection equipment 20
kV feeders, then the recovery procedure is performed following the SOP on the distribution system of
each PD.
OC 7.0. Testing and Inspection
This section sets out the activities procedures associated with testing and inspections. If deemed
necessary, the PD will perform testing of PSD equipment or Consumer.
Unofficial translation by Repit Suliyono----------------------------- http://repit.wordpress.com/ [email protected]
OC 7.1. Testing
PD, PSD and Consumers have the right to test any equipment along with related equipment connection
point between PD, PSD and Consumers. Testing provisions are as follows:
a. if there is one party has a good reason and felt that the equipment which is operated by the other
party does not fulfill the Distribution Codes, then such party may request testing of the equipment by
giving written notice;
b. the two sides will cooperate in conducting testing as referred to in letter a;
c. cost of testing that emerge borne by the party requesting the test, unless the equipment tested is
found not to meet the Distribution Codes, then the cost of testing borne by the party being tested;
d. testing costs are not included losses due to interruption or reduction in power supply, but the PD will
minimize the losses in the testing process;
e. testing was conducted according to standard procedures that apply.
OC 7.2. Testing Equipment Protection
a. PSD and consumers which are connected at a connection point will work with PD in the examination
or testing of protection equipment periodically.
b. PD, PSD and Consumer shall bear their respective costs of testing on the system of protection, unless
there is another deal.
OC 7.3. Consumer Owned Equipment Testing
If Consumers carry out testing of his equipment that impact the reliability and security of the distribution
system operations and the measurement at a connection point, then the Customer must obtain prior
approval of the PD.
OC 7.4. Notice of Testing
PSD or consumers who will conduct the test on his equipment associated with a connection point, is
obliged to submit notification in writing to the PD within 5 (five) working days prior to testing.
Such notification shall contain:
a. details of the testing;
b. approximate start and end time of testing;
c. introduction of the equipment under test;
d. system conditions required to conduct testing;
e. name of the officer in charge during testing.
PD may reject or reschedule, by mutual agreement, if the distribution system condition does not allow.
Unofficial translation by Repit Suliyono----------------------------- http://repit.wordpress.com/ [email protected]
OC 8.0. Inspection and Permissions to enter the Installation Location
OC 8.1. Permissions to enter the installation location
a. PSD and the Consumer shall provide direct access for PD officer who will conduct an audit of assets
belonging to PD.
b. the PSD or Consumers can enter PD's installation after obtaining written permission from the PD.
OC 8.2. Right to Inspect
a. PD, PSD and Consumers have the right to inspect the equipment with each other at a connection
point. The right to inspect only applies to efforts to ensure conformity with the Codes of Distribution.
b. If one party suspected that the other party does not comply with Code of Distribution and that has an
adverse effect on the operation of the distribution system, then such party may file an examination of
the suspected equipment.
c. party who inspected will appoint qualified personnel to accompany the representative Person that
checks to enter the examination site.
d. Parties that checks will ensure that its representatives qualified to carry out the inspection.
OC 8.3. Inspection by PD
a. PD can inspect PSKM and Consumers equipment connected to the distribution system according to
the provisions referred to in OC 8.2. to:
1) assess the suitability of PSKM or Consumer equipment connected to the distribution system as
their operational obligations of the Codes of Distribution;
2) investigate any potential threats that may happen to the security of the distribution system.
b. During the inspection, the PD officer;
1) take no action that could cause damage to PSKM or Consumer equipment connected to the
distribution system;
2) only operate PSKM or Consumer equipment connected to the distribution system to the extent
required and approved by PSKM or Consumer;
3) comply with the internal regulations of the PSKM or Consumer with respect to employment,
health and safety.
c. PSKM and Consumers appoint officers who have the competence to accompany PD officers during
inspection.
Unofficial translation by Repit Suliyono----------------------------- http://repit.wordpress.com/ [email protected]
OC 9.0. Communication and Reporting Procedures
a. For the purposes of safe and reliable distribution system operation then PSKM, PD and Consumers
need to communicate on any network operating conditions. PD is responsible for communicating the
events on the distribution system to PSKM or Consumers who are affected by these events.
b. PSKM or the Customer is obliged to notify the PD, with regard to operation and maintenance plan as
well as disorders that affect the operation of distribution systems. The implementation of
communication procedures will be outlined in communication and reporting SOP as agreed by the
parties concerned.
OC 10.0. Limits of Liability to the Distribution System Maintenance
a. Limits and responsibilities of maintenance of an asset based on the principle of ownership of assets
such as the maintenance scope of distribution system is started from cells of 20 kV outgoing
substations (GI), 20 kV Medium Voltage Network (JTM), Distribution Substation, Low Voltage Network
(JTR), External Connection (SL) up to and Measuring Tool Delimiter (APP) in the Customer’s building,
including SCADA and communications facilities.
b. Exceptions to the provisions referred to in letter a can be done separately in accordance with the
agreement between the asset owner and maintenance operator which is set forth in a separate
agreement.
OC11.0. Preparation and Implementation Procedure for Maintenance Works
Implementation of maintenance work on distribution system involving multiple parties that require
coordination with each other. Parties involved in the implementation of distribution systems maintenance
work are PSD, PD and Consumers.
OC 11.1. PSD
the PSD is responsible for implementing network and installation of electric power maintenance within
the limits of ownership. Maintenance work on the upstream side sometimes require power blackout on
the distribution side and vice versa, there is work on the distribution side that requires electricity blackout
of the PSD, so that coordination between the PSD and PD needs to be done.
Unofficial translation by Repit Suliyono----------------------------- http://repit.wordpress.com/ [email protected]
OC 1 1.1.1. Preparation of Maintenance Work
a. PSD submit plans for maintenance work on the side of the PSD which affects the distribution system.
b. The maintenance work scheduled submitted to the PD no later than 2 (two) weeks before the day of
execution.
c. Maintenance work which resulted in electric power blackout to the distribution system can only be
implemented after approval of the PD.
d. PSD receives notifications of maintenance approval from the PD no later than 1 (one) week prior to
the implementation of maintenance.
OC 11. I.2. Implementation and Responsible for Maintenance Work
a. On the day of the maintenance work on the upstream side related the electricity outages in
distribution system, person in charge of the work of the PSD should be coordinating with PD
b. the implementation Setting of the maintenance work is set in accordance with SOP agreed.
OC 11.2. PD
PD is responsible for the execution of maintenance work on distribution systems. In carrying out
maintenance work, the PD must coordinate with the PSD and the Consumer.
OC 11.2.1 Preparation of Maintenance Work
a. PD deliver maintenance schedule distribution system according to the PSD and Consumer needs.
b. PD informed the work plan that resulted in the electricity outages to the Customer no later than 24
(twenty four) hours prior to the outage.
OC. 11.2.2 Implementation and Maintenance Work Responsible Parties
a. Distribution system maintenance work can be carried out by a network outage or without a network
outage. Maintenance work with network outage as far as possible be avoided.
b. maintenance work can be carried out without power outage by using the facilities in the Work-in
voltage (PDKB) on Medium Voltage Air Line system (SUTM) and the Mobile Unit Substation (UGB) on
the Distribution Substation maintenance.
Unofficial translation by Repit Suliyono----------------------------- http://repit.wordpress.com/ [email protected]
c. the network maneuver in order to perform network maintenance and normalization in accordance
with standard operating procedures that have been specified.
d. Implementation of maintenance work is supervised by a responsible person who meets certain
competency.
e. Work responsible person / Occupational safety coordinator is in charge to:
1) examine the readiness of the implementation of maintenance work either for working tools,
safety equipment or personnel;
2) coordinate with the network regulatory in order to maneuver the network to release tension and
network re-normalization;
3) examine that the work was actually completed and the network is safe from personnel and other
working tools for the voltage reloading.
f. Maintenance work can be done by third parties that meet certain qualifications and competence.
OC 11.3. Big consumers
OC 11.3.1 Preparation of Maintenance Work
a. Big consumers submit a written installation maintenance schedule that requires power outages to the
PD as needed no later than 2 (two) weeks before the day of execution by enclosing the reasons for
maintenance work is to be performed and the approximate duration of the job will be done.
b. PD will provide the approval in writing of the work schedule of at least 1 (one) week prior to the
implementation of maintenance.
OC 11.3.2 Implementation and Maintenance Work Responsible Parties
a. Implementation of maintenance work on the network and the installation of Big Consumers is
supervised by officers in accordance with their competences.
b. Work Responsible Party is to re- confirm of the proposed network outages, request for network
outages in the framework of the implementation of maintenance work on the installation of the Big
Consumers to the PD on the day of execution.
c. Work Responsible Party is to supervise the implementation of the work from preparation until the job
has been completed.
d. Responsible for the work request that normalized power flow back to the PD after work is completed.
OC 12.0. Safety and Occupational Health procedures (K3)
PSD, PD and Big Consumers, each is responsible for safety and health for the officer in carrying out
maintenance work on electric power network according to their responsibilities. Each party shall have
person in charge of the implementation of the K3. K3 responsible task, among others:
a. examine if the equipment complies with the standard K3;
b. examine if the condition of readiness and K3safety equipment used;
c. supervise if the use of K3 equipment is in a proper way during the execution of the work
Unofficial translation by Repit Suliyono----------------------------- http://repit.wordpress.com/ [email protected]
CHAPTER VI
PLANNING CODE- (PC)
Distribution Planning Codes explain the rules to establish the liability of the PSD, PD and Consumers in the
development of distribution systems.
PC 1.0. Objectives
The objective of the Planning Code is:
a. to establish criteria and standards of planning design to manifest distribution system that is safe,
reliable and efficient;
b. to establish the necessary data from the PSD, PD and Consumers for the benefit of the development
of distribution systems;
c. to provide clarity and certainty for all PSD and Consumers, associated with the development plan
distribution system, to realize a secure distribution system, with quality and adequate levels of
reliability and operating efficiencies that can be justified.
PC 2.0. Responsibilities of Parties
a. PD responsibilities are:
1) analyze the impact of electrical facilities connection to the distribution system originating from
the PSD and consumers on the performance of distribution system operations;
2) identify and plan the development of distribution systems to ensure availability of supply to meet
load demand, the realization of the quality and supply reliability as well as the efficiency of
operations;
b. PSD and Consumers should work with PD in meeting the data needs for the purposes of distribution
system development plan for the realization of the expected distribution of operating performance.
PC 2.1. Planning Data Delivery
a. If there are connection plans or modification of the installation, PSD or Consumer who is connected to
the distribution system shall submit the relevant data and detailed.
b. PSD and Consumers at the beginning of each year shall submit the relevant historical data for the last
3 (three) years and outline planning data for the next 5 (five) years to the PD.
c. planning data as determined necessary must contain the information necessary by PD to evaluate the
impact of on the development of PSD and Consumers sides to the distribution system.
d. The planning data should provide the information necessary to conduct the development of a more
accurate distribution system. The data referred to include the parameters of the distribution and
protection system who are connected directly to or affects the distribution system and should be
adequate for the PD to conduct a study on the impacts associated with the connection point.
e. Planning data must be sent by the PSD and Consumer to the PD according to the following categories:
I) projection data load requirements;
2) loading data to electrical facility from the PSD;
3) PSKM capabilities data;
4) equipment data to be installed;
5) attached equipment data.
Unofficial translation by Repit Suliyono----------------------------- http://repit.wordpress.com/ [email protected]
PC 2.2. Planning Data Collection and Rejuvenation
a. For a period of next 2 (two) years, no later than August 1, PD must collect and rejuvenate the
distribution planning data according to the following categories:
I) load requirements projection data;
2) loading data electrical facility from the PSD;
3) PSKM capabilities data;
4) the equipment data to be installed;
5) attached equipment data.
b. If there are changes to the planning data, the PSD and the Customer shall immediately inform the
changes to the PD no later than February 1 of the coming year.
PC 2.3. Evaluation Against Development Proposals with Impact Against Distribution Network
a. PD must conduct a review of development proposals submitted by the PSD and the Customer that
affect the distribution system.
b. PD must submit the results of the review include recommendations to the PSD and the Consumer.
c. PD must also convey to the PSD and Consumers on planned development of distribution systems that
will impact on the PSD and the Consumer.
PC 2.4. Distribution System Development Plan Preparation
a. PD must collect and process planning data sent by the PSD and Consumers into the load forecasting
data to be used as a distribution system development plan.
b. PD should consider economic growth and regional development plans of relevant agencies (including
the Central PLN).
c. The distribution system development plan includes:
1) load growth and energy forecast;
2) the proposed increase in capacity and site development of new substation (GI);
3) improvement of quality, reliability and efficiency of operation of distribution networks;
4) a summary of the technical and economical analysis performed for the development of
distribution systems.
d. Development plan for rural electricity distribution system to be coordinated with the Directorate
General of Electricity and Energy Utilization.
PC 3.0. Planning on Distribution System Development Review
Distribution system planning review to be performed include:
a. distribution system planning review conducted by the PD to ensure the safety, quality and reliability
of distribution systems, namely:
1) evaluation of project development program of distribution system;
2) evaluation of development proposals from the PSD and the Consumer,
b. distribution planning review should be conducted to review the impact on distribution system
regarding loads planning or equipment changes.
Unofficial translation by Repit Suliyono----------------------------- http://repit.wordpress.com/ [email protected]
c. technical study as referred to in PC 3.1. up to. PC 3.4. and planning the necessary data as referred to
in PC 4.0. should be used in conducting distribution system planning studies.
d. distribution system planning analysis conducted by PD includes:
1) determination of an optimal design for the selection of the location and capacity of GI;
2) Determination of the optimum design for distribution system realization that meets the criteria of
quality and level of reliability and operating efficiency.
e. distribution planning study should be done using the cost approach to the Least Cost Planning.
PC 3.1. Voltage Drop Studies
a. The voltage drop studies should be performed to gain of the voltage rate at the connection point on
existing distribution system and the conditions of its development.
b. Voltage drop studies should be performed to evaluate the impact on the distribution system for
connection of the PSD, the Consumer and the addition of the distribution network.
PC 3.2. Short circuit Study
a. Short circuit only to determine the coordination of relay settings gradation between the PD and PSD
consumers installations.
b. Short circuit capacity of the equipment specified maximum of 500 MVA at 20 kV voltage side.
c. Three-phase short circuit should be made to all the nodes of the distribution system for the
coordination of relays.
d. Single phase short circuit to ground should be made to the node distribution system that ensured the
protection system can function properly.
e. PSD sends the results of short circuit of the three phase and a phase to ground periodically or there is
a change in the PSD system to the PD for the sake of safety equipment distribution system.
f. PD informs the consumer if there are changes in short circuit current 3 phase and a phase to ground.
PC 3.3. Distribution Losses Study
a. Technical level of losses in the distribution network is determined by the choice of conductor, cross-
sectional area and the specifications of the selected transformer.
b. distribution losses study should be conducted to identify the magnitude of losses on the distribution
of JTM, distribution substations and JTR in the distribution system.
c. distribution losses study should be conducted to determine the effect of the development of PSD,
Consumer and development of distribution systems on the efficiency of distribution system
operation.
PC 3.4. Distribution Reliability Studies
a. Degree of reliability in the distribution network is determined by the selection of system configuration
and Medium Voltage Cable Channels (SKTM) and SUTM which is adjusted with the load conditions
and the availability of investment.
b. the distribution reliability studies must be done to determine a reasonable level of reliability for the
relevant distribution system.
Unofficial translation by Repit Suliyono----------------------------- http://repit.wordpress.com/ [email protected]
PC 4.0 Planning Data
Planning data includes energy and load forecasted data. PD developed forecasts of energy demand and
loads, including peak loads for 5 (five) years.
a. Data forecasts for the first year in the form of monthly, and the following 4 (four) years sufficient
energy forecasts and the annual load.
b. The following factors must be considered by the PD in preparing the load forecasts:
I) historical load data;
2) the trend of load growth;
3) important events;
4) the use of captive power;
5) interconnection with the nearest PD; and
6) other relevant factors (population growth, economic, urban design master plan).
PC 5.0 Spatial Planning
To facilitate the planning of the development of the distribution system, it is required that outlines the
spatial planning of Right of Way (ROW) and location of land or space for distribution substations and GI
are listed in the General Spatial Plan Areas.
PC 6.0. Data Needs
Data needs include:
a. Generating Unit Design Data
This section describes the technical design of the data requirements of each generator unit, including
general technical data, reactance and resistance data, saturation parameters, transformer data, active
and reactive power, the characteristics of excitation and governor equipment, prime mover data and
data power system stabilizer.
b. PSD Installation Data
This section covers the installation of PSD data which are connected to the distribution system such as
voltage rating, insulation coordination, current rating, transformer capacity, specifications of the
transformer, grounding, source impedance, the characteristics of the nominal load current, power
quality measurement data (flashing voltage, harmonics, the work factor ).
c. Distribution System Consumer Data
This section summarizes the distribution system consumers data, such as voltage rating at a
connection point, installed protected, the internal backup supply schemes.
d. Load Characteristics of Consumer Data
This section describes the type of load, load growth forecasts and plans for the imposition of a daily /
weekly / monthly provided by the Big Consumer.
PC 6.1. Data Update Procedure
a. PSD, PD and Consumers together provide data in accordance with the format and time set forth in
this rule.
b. PD can act actively to collect data necessary for the smooth distribution of electric power.
c. If there is a change of equipment contained in the PSD and consumers are already listed on the PD,
then the PSD and the Customer shall notify the PD no later than 1 (one) month after the change
occurs.
Unofficial translation by Repit Suliyono----------------------------- http://repit.wordpress.com/ [email protected]
CHAPTER VII
SETTLEMENT CODE-(SC)
Settlement Code govern transactions between PSD-PD and PD-Consumers, to the extent not otherwise
specified in the contract approved by the Parties.
SC 1.0. Objective
The objective of this rule is to clarify procedures relating to meter reading transactions, cost calculation,
billing, payment and risk mitigation for the failure of payment of power purchase and sale transactions.
Terms of Transaction
a. Implementation of the distribution system transactions between PSD and PD and between PD and
Consumer electric bills that is embodied in the calculation of costs and power consumption of
electrical energy and other costs determined in accordance with the provisions of legislation or upon
agreement of both parties involved in the transaction.
b. In doing a transaction between PD and consumer, PD can define different forms of risk mitigation for
the failure of payment of power purchase and sale transactions.
c. PD is required to announce the distribution system quality reliability levels that include the average
number of power outages per customer and the perceived average completion time of power
outages.
d. Determination of the selling price of electricity should be guided by the Electricity Basic Tariff in
accordance with the provisions of legislation.
e. In the event that average power factor of each month is less than 0.9 lagging, so in some classes of
consumers will be charged the excess consumption of reactive power according to the applicable
tariff.
f. PD determine the comparative factor (K factor) between the time of peak load pricing and time
outside of peak load pricing in accordance with local electrical load characteristic.
g. If consumers can not meet the obligation to settle payment of electricity bills, then the PD is entitled
to temporary disconnect that is terminating the connection temporarily of electrical power supply to
consumers for a while without dismantling the measurement equipment belongs to the PD.
h. If after temporary disconnection at certain times Consumer can not settle electric bills, then the PD
will do the complete termination that is termination for onward dispatching electricity to customers
installation and PD take all the existing PD's equipment at the Customer location.
i. PD will put on a power imitator to limit the amount of power that is agreed by PD and Consumers in a
power purchase agreement.
j. For the purposes of regulating the use of electricity, PD can and is entitled to perform inspection to
the installation of PD's mounted in a location owned by the Customer to be supplied from the
distribution network owned by PD.
Unofficial translation by Repit Suliyono----------------------------- http://repit.wordpress.com/ [email protected]
SC 3.0. Readings and Payment
SC 3.1. Reading of Transactions
SC 3.1. I. Transactions readings between Grid with PD
Reading of the transaction between the Grid with PD is regulated in Network Code.
SC 3.1.2. Transactions readings between PSKM with PD
a. Transactions Meters between PSKM and PD is read at 10:00 the first day of each month and put into
the Minutes of Meters Reading. If there is no dispute about the data that is read, then PSKM publish
the Minutes of Electricity Transaction no later than 15 (fifteen) working days after receiving the
Minutes of Meters Reading.
b. If the transaction meter data is incomplete or contained errors then meter data comparator must be
used. If the meter data comparison is not complete or there are errors, PD uses a viable method to
make estimates that can be agreed upon.
SC 3.1.3 Reading Transactions PD with PD
a. Transactions meters between PD and PD is read at 10:00 the first day of each month and put into the
Minutes of Meters Reading. If there is no dispute about the data that is read, then the owner of the
PD distribution network assets deliver electricity to other PD publish the Minutes of Electricity
Transaction no later than 15 (fifteen) working days after receiving the Minutes of Meters Reading.
b. If the transaction meter data is incomplete or contained errors, the owner of the PD distribution
network assets that dispatch electricity using a viable method to make estimates that can be agreed
upon.
SC 3.1.4 Reading PD Transactions with Consumers and Resellers with Consumers
Transaction Meter is read every 1 (one) month or as PD/Reseller determination. If the transaction meter
data is incomplete or contained errors, PD/Reseller using appropriate methods to make estimates that
can be agreed upon.
SC 3.2. Costs of Transaction
SC 3.2.1 Costs that is charged by PD to Consumers
In managing the distribution system PD may charge a fee to the Customer in accordance with the
provisions of the legislation.
SC 3.2.2. Consumer payment to the PD
Schedule, location and manner of payment is governed by the PD based on the agreement or provision of
the contract.
SC 3.3. Sanctions of Failure to Pay
Sanctions will be given to consumers in case of late payment, or does not refill the customer deposit, in
accordance with the power purchase agreement.
Unofficial translation by Repit Suliyono----------------------------- http://repit.wordpress.com/ [email protected]
SC 4.0. Transactions Dispute Settlement
SC 4.1. Transaction Dispute Settlement between PSD and PD
SC 4.1.1 Transactions Dispute Settlement between Grid and PD
Settlement of transactions disputes between Grid with PD is regulated in Network Code.
SC 4.1.2 Transactions Dispute Settlement between PSKM and PD
Copies of meter readings, time of transaction and other information used for the determination of billing
and payments can be given to the Parties that require on request. If there is any questions or corrections
suggestions of the Parties to the above data, then the question or corrections suggestions is submitted in
writing.
Transaction Dispute settlement process are as follows:
a. The Parties shall endeavor to resolve this issue through informal efforts either through a telephone
conversation or through meetings at the time and place mutually agreed;
b. if the informal efforts to resolve disputes of this transaction is not successful, the Parties in dispute to
prepare a written document of the dispute to then be submitted to KMAD. Furthermore KMAD trying
to resolve the dispute;
c. if not an agreement on the settlement of disputes, the parties who wish to pursue the issue at a
higher level may submit the matter to the arbitration body or court;
d. unless already regulated separately by the contract, if the contract between PSKM and PD contained
provisions governing transactions dispute settlement that occur, then the dispute is resolved by
reference to the provisions in the contract;
e. during the dispute resolution process, PSKM must not disconnect the electric power unilaterally until
a final decision of the National Arbitration.
SC 4.2. Settlement of Transactions Disputes between PD and Consumer
In the event of a dispute the transaction, then the published accounts must be paid in advance by the
Customer. Further agreements are expected to be achieved by both parties. If no agreement then it can
be achieved through legal channels.
SC 5.0. Settlement Process Audit Procedures
The parties have the right to request an audit for the settlement process associated with the following
conditions:
a. the parties may appoint a third party qualified to conduct the audit;
b. all costs incurred audit is the responsibility of requesting party for the audit;
c. audit results should be sent to the party being audited. Furthermore, the audited party is obligated to
provide answers to these audit results.
Unofficial translation by Repit Suliyono----------------------------- http://repit.wordpress.com/ [email protected]
CHAPTER Vlll
METERING CODE-(MC)
Metering Codes describe the minimum technical and operational requirements for the meter transactions
that must be installed by the PD and PSD at the connection point of distribution.
MC 1.0. Objective
The objective of the Metering Codes is to:
a. make metering requirements of the active energy and reactive energy from and / or to the
distribution system;
b. ensure the suitability of equipment and procedures to provide metering data used in the settlement
and payment.
MC 2.0. Metering criteria
MC 2.1. Metering magnitudes
Metering of energy transactions can be done by direct or indirect methods through instrument
transformer (current transformer and voltage transformer). The quantities measured are as follows:
a. Kwh;
b. kVARh;
c. maximum kVA.
MC 2.2. Metering Accuracy
Each component metering instruments must meet the standards of accuracy at least as or better as
follows:
a. transformers instrument
Voltage transformer and current transformer to the transaction with the big consumer at the point of
connection of high voltage following the networks Codes. Voltage transformer and current
transformer for the transaction at a medium voltage connection point must have a 0.5 class accuracy.
Current transformer to the transaction at a connection point must have a Low Voltage accuracy class
1.0
b. Kilo Watt-hour Meter (kwhmeter)
1) 3 phase Connection
Meters for the transaction with the Big Consumer at the point of connection of high voltage
following the networks Codes. Meters for the transaction at a connection point has a medium
voltage accuracy class 0.5 of this type of electronic meters.
Meters for the transaction at the point of connection of low voltage, indirect metering using the
class 1.0 accuracy of this type of electronic meters, while for the direct metering using a class
accuracy of 1.0 from the electromechanical or electronic meters type. Each meter Kwh 3 phase 4
wire electronic meter of this type must have a registration export and import in accordance with
the requirements including peak load time (WBP) and outside peak load time (LWBP).
Unofficial translation by Repit Suliyono----------------------------- http://repit.wordpress.com/ [email protected]
2) Connection 1 phase
Every Kwh meter must be of the type 1 phase 2 wire, having accuracy class 2.0, the type of
electromechanical or electronic meters.
c. KiloVAr-hour meter (kVArhmeter)
Each kVArh meter must be of type 3 phase 4 wire, having export registration and / or import, accuracy
class 2,0 of the type of electromechanical or electronic meters.
d. Maximum kVA demand meters
Every-maximum kVA demand meters shall be of three types of flow elements, multiple tariff, which
has a solid-state registration, accuracy class 0.5 of electromechanical or electronic type meter.
For those who still use the meter Kwh 3 phase 3 wire type can still be used but not developed anymore.
MC 2.3. Burden instrument Transformer
For indirect metering, burden instrument transformer that are used to be in the range between 25% to
100% of its rating.
MC 3.0. Meter Equipment Requirements
MC 3.1. lnstallation requirements
a. All transactions meter for Consumers should be installed at a connection point. Meters are provided
by the seller of electric power.
b. Transactions between the PD meter with PSD meters can be fitted with comparison meter.
c. adequate cupboard (cubicles / box) should be provided for meters at each connection point.
Construction to meet SNI or PD Standard (e.g.: SPLN), with prior approval of the PD. Must have a
meter cupboard doors which can be locked and sealed by the seller of electric power.
d. The diameter of the circuit voltage transformer cable must ensure the voltage drop should be less
than 1%.
e. current transformer secondary circuit and voltage transformer must be directly connected to the
meters terminal.
MC 3.2. ownership
main meters are mounted / installed and owned by the seller of electric power, while the comparison
meters may be held / mounted and owned by the purchaser of electric power with the same class. Each
party is obliged to operate and maintain the meter.
MC 4.0. Commissioning
Unofficial translation by Repit Suliyono----------------------------- http://repit.wordpress.com/ [email protected]
MC 4.1. Metering Equipment Document
Especially for a PSD connection point or Big Consumers should be equipped with measuring equipment
documents as follows:
a. single-line diagram showing the connection point to the meter equipment;
b. initial testing and calibration certificate of the current transformer, voltage transformer and meter,
prepared by the seller of electric energy;
c. calculation of voltage drop on the circuit voltage provided by the electric power seller; and
d. burden calculations on the circuit meter prepared by the seller of electric power.
For any connection point that has been in operation before the Distribution Codes is enacted the above
documents is gradually completed.
MC 4.2. Installation and Testing
Installation and testing of metering equipment will be made by the seller of electric power witnessed by
the purchaser of power.
MC 4.3. test results
The results of the testing and inspection should be included in the minutes signed by the Parties.
MC 5.0. Tests After commissioning
MC 5.1. Repeat testing
Metering system is inspected and retested as needed or on request.
MC 5.2. cost of Testing
Payment of the testing set as follows:
a. if the initial test results indicate that the meter is in accordance with the standards of its class, the
requesting party pay the costs of testing; or
b. if the initial test results indicate that the meter will require recalibration, then the meter owner who
pays the costs.
MC 6.0. Sealing and Reprogramming
After the implementation of re-commissioning or re-testing of metering equipment, the PD must
immediately attach seal with clear identification. If this activity lead to changes in seal tera then sealing
seals tera be implemented by the Agency for Metrology.
Termination of seal by a party must be witnessed by other parties as outlined in the minutes.
MC 7.0. Examination of Meter Data and Equipment
MC 7.1. Rights of Access to Meter Data
The energy buyer can find out the metering data via the display / registers that exist at the meter.
Unofficial translation by Repit Suliyono----------------------------- http://repit.wordpress.com/ [email protected]
MC 7.2. Rights of Access to Metering Equipment
The Energy Seller reserves the right to access directly to the metering equipment at a connection point of
distribution for purposes of inspection and testing, verification of data, read registers, seal checks, control
of electricity usage, and other things necessary.
Buyers of energy is not justified in conducting certain activities that may affect the operation of a meter
either directly or indirectly to the metering equipment at a connection point.
MC 8.0. Metering Equipment Security
MC 8.1. Changes in Metering Equipment
All changes made to the metering equipment by the seller must be witnessed by the buyer and a minutes
must be made and signed together.
MC 8.2. Changes in Metering Data
Changes to the original data stored in a meter is not allowed, and if there are errors of metering then
recalibration must be performed.
MC 9.0. Exceptions and Deadline
To kWhmeter who do not meet the provisions of MC 2.2. point b to be given a time limit of 5 (five) years
to adjust, as of the enactment of Distribution Code.
MC 10.0. Other provisions - Other
Anything else that is operational techniques in detail is not provided for in Metering Code These Metering
Code will be further elaborated by KMAD in permanent operation and maintenance procedures of
metering equipment.
Unofficial translation by Repit Suliyono----------------------------- http://repit.wordpress.com/ [email protected]
GLOSSARY
This glossary defines terms used in the Distribution Codes. The consistent use of these definitions will reduce the
possibility of misunderstanding the provisions of the Codes of Distribution. In the case that a term or word expressed
specifically in a part of the Codes of Distribution, then the statement of the distribution Codes was preferred
compared with the explanations in this Glossary.
The words and the following statements which are used in Distribution Code are defined as follows:
1. ANSI: American National Standards Institute.
2. APP: Metering Equipment and barrier.
3. Short circuit current: The current that occurs due to an interruption 3 phase, 2 phase, ground
-phase.
4. Network Codes: Collection of regulations and technical and operational standards to
ensure reliable operation, safe and efficient.
5. peaks Load: the highest load in a certain time interval
6. Captive Power: The power plant used for its own sake, or private.
7. Active Power: Generation, distribution or use of electrical power, as a result of
multiplying the voltage by a phase component of alternating current,
which is usually expressed in kilowatts (kW) or Megawatts (MW). This is
part of VA or kVA of apparent power that can be transformed into light,
physical motion or heat.
8. Reactive Power: The portion of the electrical power generating and maintaining
electric/magnetic field of an alternating current equipment. Reactive
power must be supplied to the magnetic equipment such as motors and
transformers, and must be supplied to compensate for reactive losses
on transmission facilities. Expressed in kilo quantities Var (kVAR) or
MegaVAr (MVAr).
9. Voltage Depression of Short Circuit: The ratio between the short circuit electric arc furnace with a network
of short circuit power at the connection point at minimum generating
conditions.
10. Harmonic Distortion: Harmonic distortion caused by non-linear characteristics of the
provision of electric power equipment.
11. Active Energy: Magnitude of active power distribution in a period of time, usually
measured in Watt-hours (Wh) or kilowatt-hours (Kwh).
12. Reactive energy Magnitude of reactive power distribution within a period of time,
usually measured in VARhours (VARh) or kiloVAR-hours (kVARh).
13. Power Factor The ratio between active power and complex power.
14. flicker Small changes cascade voltage and continuous that can be detected by
the human eye.
15. Voltage fluctuations: Changes or voltage deviation caused by load changes.
16. Frequency distribution system Frequency in cycles per second (Hz).
17. interruption Unplanned events that resulted in an abnormal condition in the
distribution system.
18. substations Part of Grid which are connected directly to the distribution system and
is a supplier of electric power distribution systems demands.
Unofficial translation by Repit Suliyono----------------------------- http://repit.wordpress.com/ [email protected]
19. Grid interconnection networks which can consist of a voltage 70 kV (which
became part of the transmission system), 150 kV, 275 kV and 500 kV
together with substations and other equipment.
20. Harmonic sinusoidal wave voltages or currents frequency magnitude is a multiple
of the basic frequency.
21. IEC The International Electrotechnical Commission.
22. IEEE Institute of Electrical and Electronic Engineers.
23. capacity power Output that can be achieved by a generating unit, transformer,
conductors or other equipment, which is expressed in MW or MVA.
24. Emergency A situation where the integrity, security or stability of the whole or part
in a state of danger and the presence of electrical outages.
25. Reliability The ability to supply power without interruption in all conditions.
26. Demand / Load Total active and reactive power has been supplied or expected to be
supplied to all customers via the Network (Grid) or the Distribution
Network, which is expressed in Megawatts and MegaVAR, within a
certain time period.
27. Blink of voltage drop voltage RMS (root mean square) in fractions of milliseconds to
several seconds.
28. Important Incident Serious incident affecting the distribution system reliability and
customer convenience that resulted in widespread power outages and
the restoration of electrical distribution system takes more than 3x24
hours.
29. commissioning A series of activities of inspection and testing of an installation of
provision and utilization of electric power supply to ensure the
installation is working properly and operation worthy.
30. Normal Operations of Network Condition Operating conditions on the configuration that should be and no
outages.
31. Consumers Users of electricity connected to distribution systems that are bound in
a contract with PD.
32. Big Consumers consumers with power connected greater than 1 MVA or regulated by
the PD.
33. Special Report The written report in addition to the Annual Report and the Report of
Important Incidents.
34. Load Shedding the intentional load reduction (automatic or manual) with the
termination of certain load because the incidence of shortages of
electric power supply, to maintain integrity and avoid greater network
outages.
35. Meter Apparatus for measuring electrical magnitude such as: real energy
(kWh), reactive energy (kVARh) and maximum power (kVA max) that is
used as a point of transaction.
36. NEMA National Electrical Manufacturers Association (USA).
37. All parties The Parties consist of the PSD, PD and Consumers.
38. PD Distribution Operator, State-owned enterprises designated as the power
holder or holders of electrification business or IUKU that manages the
distribution system (including network systems and facilities owned by
resellers such as operator of market, malls, apartments, etc.).
Unofficial translation by Repit Suliyono----------------------------- http://repit.wordpress.com/ [email protected]
39. PDKB work in a state-voltage by using a special procedure and a set of special safety
equipment and work is generally done for maintenance and new installation of
medium voltage overhead networks with the aim of reducing the number of
outages that consumers perceived.
40. energy buyers the parties who purchase electric power.
41. Power Circuit Breaker Power breaker to close and open the electrical circuit in a state not loaded or
loaded, with a certain ability to break the short circuit current.
42. disconnection Separation of the electrical of equipment from the distribution system.
43. energy sellers Party who sells electric power.
44. grounding electrical connection between one or more conductors to the ground, which is
necessary for the safety of personnel, general and equipment safety.
45. feeders main Distribution Network at substation or connection substation.
46. Metering Equipment All equipment connected to the metering system that includes: current
transformers, voltage transformers, metering instruments.
47. Protection equipment safety equipment that serves to prevent greater damage to electrical equipment
and widespread disruption.
48. PSD Distribution System Suppliers, consisting of Grid and PSK.
49. PSKM Small and Medium Scale Generating plant directly connected to the distribution
system.
50. resellers Parties who buy electric power from the PD and resell to end consumers.
51. SCADA "Supervisory Control And Data Acquisition System", long distance control and
metering systems used to remotely monitor and control the Electric Power
System.
52. Operation acceptance certificate (SLO) Certificate which is issued by an accredited institution as the basis for the
operation of electrical equipment.
53. Settlement Activities associated with the reading and payments on the sale and purchase
transactions and settlement of disputes.
54. knot The point at which of one or more distribution networks in substation or
connection substation.
55. Distribution System network systems and related facilities owned by the licensee as PD, from a
connection point between the Grid and the PD, or PSK and PD, up to the final
consumer. (Including network systems and facilities owned by the bulk buyers
such as operator of market, malls, apartments, etc. that sell back electricity to
final consumers).
56. SNI Indonesia National Standard.
57. SOP Standard Operation Procedure, standard operating procedures to be mutually
agreed.
58. SPLN Technical Standards of PLN.
59. Electricity Basic Tariff selling price of electricity set by the Government.
60. Meter Terminals Terminal in kwhmeter.
61. Connection point The place where there is a connection between power lines PD, PSD and
Consumers.
62. UFR Under Frequency Relay, the relay that will work if there is a frequency lower
than the setting.
63. UGB Moving Substation Unit, is the distribution substations (20 kVl400V) which
moveable used to reduce the occurrence of Consumers blackouts due to work in
the distribution network.
64. Under Voltage Relay Relay that will work if the voltage is lower than the setting.
65. Generating Unit: A combination of first movers and generators (and other equipment) that
generate electric power of alternating current