LVCB General Leaflet E 0803

24
Leader in Electrics & Automation Electric Equipment MCCB / MCB / MMS / ACB / MS / Mini-MC / EMPR / DMPR Low Voltage Circuit Breakers & Contactors

description

LEAFLET

Transcript of LVCB General Leaflet E 0803

Page 1: LVCB General Leaflet E 0803

Leader in Electrics & Automation

Electric Equipment

MCCB / MCB / MMS / ACB / MS / Mini-MC / EMPR / DMPR

Low Voltage Circuit Breakers & Contactors

Page 2: LVCB General Leaflet E 0803

● 2, 3 and 4 pole series up to 1600AF ●Rated ambient temperature at 40℃ calibrated for 50℃ available●CE marked according to IEC standard and UL approved MCCBs

are also available.

● 1, 2, 3 and 4 pole series up to 125AF●B, C and D Characteristics

● 2 and 4 pole series up to 63AF● Sensitivity up to 300mA●Overcurrent protection type available

Page 4

Page 8

Page 10

Page 12

Page 3: LVCB General Leaflet E 0803

● 3 and 4 pole series up to 800AF Mini-contactors available● AC/DC common use coil from 100AF● Thermal (Bimetallic) and electronic type overload relays are available● CE marked and UL approved

Page 14● 65, 85 and 100kA breaking capacity● High functional digital trip relays● CE marked

Page 18

Page 4: LVCB General Leaflet E 0803

ABS ABH ABE ABS ABH GBL(E) ABE5 10 5 10 25 85 5

2, 3 2, 3 2, 3 2, 3, 4 2, 3, 4 3 2, 3ABS32b ABH32b ABE52b ABS52b ABH52b ABE62bABS33b ABH33b ABE53b ABS53b ABH53b GBL53E ABE63b

ABS54b ABH54b

600 600 600 600 600 600 600250 250 250 250 250 - 250690 690 690 690 690 690 690

6 6 6 6 6 6 6

10 25 10 25 50 125 107.5 14 7.5 14 25 85 7.55 10 5 10 25 85 55 10 5 10 25 85 5

2.5 7.5 2.5 7.5 14 65/50 2.52.5 5 2.5 5 10 35 2.55 10 5 10 20 - 5

2.5 5 2.5 5 14 - 2.550 50 50 50 50 75 50A A A A A A A

8500 8500 8500 8500 8500 10000 85001500 1500 1500 1500 1500 5000 1500

fixedLSIA configuration

fixed fixed fixed fixed fixed

▲ ▲ ▲ ▲ ▲ ▲

● ● ● ● ● ● ●

● ● ● ● ● ● ●

● ● ● ● ● ● ●

● ● ● ● ● ● ●

● ● ● ● ● ● ●

● ● ● ● ● ● ●

● ● ● ● ● ● ●

● ● ● ● ● ● ●

● ● ● ● ● ● ●

- - - - - - -- - - - - - -- - - - - - -

0.45 0.45 0.45 0.45 0.7 - 0.450.65 0.65 0.65 0.65 1 1.7 0.65

- - - 0.85 1.2 - -

Molded case circuit breakers30AF to 225AF

4

Note): 1. ● applicable or available2. ▲ available as a separate breaker3. (3) Breaking capacity(at 415VAC) of

ABS32b 3A ABS33b 3A is 2.5kA

Table 1.

Frame Size(AF) 30 50 60

90×155×60 105×165×80 75×130×60

5, 10, 15,20, 30

(3), 5, 10,15, 20, 30

5, 10, 15, 20,30, 40, 50

15, 20, 3040, 50

6050Electronically adjustable :

(0.5-0.6-0.7-0.8-0.9-1.0) ×In

75×130×60 75×130×60

Frame TypeBreaking capacity(kA), Icu at 415VACNumber of polesType 2 pole

3 pole4 pole

Rated current (A)

Technical data conforming to IEC/EN60947-2Rated operational voltage(V), Ue(50/60Hz)Rated operational voltage(V), Ue(DC)Rated insulation voltage(V), Ui(50/60Hz)Rated impulse withstand voltage(kV), UimpUltimate breaking capacity(kA), Icu

AC 50/60Hz 220/240V380V415V440/460V480/500V600V

DC 125V250V

Service breaking capacity(%Icu), IcsCategory of useEndurance Mechanical(Number of operations) ElectricalType of trip unitThermal-magnetic releaseElectronic releasePre-alarm via LED Hydraulic-magnetic releaseMagnetic release only without thermal tripEarth leakage protection for 3 pole AccessoriesElectrical auxiliaries Auxiliary switch

Alarm switchShunt tripUndervoltage trip

External accessories Direct rotary handleExtended rotary handleTerminal shieldInsulation barrierRear connection Mechanical interlockPlug-in deviceMotor operator

Dimensions (W×H×Dmm) 3 pole breakerWeight(kg) 2 pole

3 pole4 pole

Derating chart : See tables See table 1 See table 1

Amb. Temp. -5℃℃ 0℃℃ 10℃℃ 20℃℃ 25℃℃ 30℃℃ 35℃℃ 40℃℃ 45℃℃ 50℃℃

Calibrated for 40℃℃ In=15 to 30A 111.9% 111.3% 110.0% 108.0% 106.6% 104.9% 102.7% 100.0% 96.8% 93.3%

In=40 to 100A 110.2% 109.8% 108.7% 107.0% 105.8% 104.3% 102.4% 100.0% 97.2% 94.0%

Calibrated for 50℃℃ In=15 to 30A 113.1% 112.5% 111.3% 110.0% 109.1% 108.0% 106.6% 104.9% 102.7% 100.0%

In=40 to 100A 111.2% 110.7% 109.8% 108.7% 108.0% 107.0% 105.8% 104.3% 102.4% 100.0%

Page 5: LVCB General Leaflet E 0803

ABS ABE ABS ABH GBN GBH GBL GBL(E) ABE ABS ABH10 10 25 35 35 50 85 85 18 25 35

2, 3, 4 2, 3, 4 2, 3, 4 2, 3, 4 2, 3, 4 2, 3, 4 2, 3, 4 3 2, 3, 4 2, 3, 4 2, 3, 4ABS62b ABE102b ABS102b ABH102b GBN102 GBH102 GBL102 ABE202b ABS202b ABH202bABS63b ABE103b ABS103b ABH103b GBN103 GBH103 GBL103 GBL103E ABE203b ABS203b ABH203bABS64b ABE104b ABS104b ABH104b GBN104 GBH104 GBL104 ABE204b ABS204b ABH204b

600 600 600 600 600 600 600 600 600 600 600250 250 250 250 250 250 250 - 250 250 250690 690 690 690 690 690 690 690 690 690 6906 6 6 6 6 6 6 6 6 6 6

25 25 50 65 50 85 125 125 35 50 6514 14 25 35 35 50 85 85 18 25 3510 10 25 35 35 50 85 85 18 25 3510 10 25 35 35 50 85 85 18 25 357.5 7.5 14 25 30/22 42/35 65/50 65/50 10 14 255 5 10 18 18 25 35 35 7.5 10 1810 10 20 25 - - - - 15 20 255 5 14 18 35 50 85 - 10 14 1850 50 50 50 75 75 75 75 50 50 50A A A A A A A A A A A

8500 8500 8500 8500 20000 20000 10000 10000 7000 7000 70001500 1500 1500 1500 10000 10000 5000 5000 1000 1000 1000

fixed fixed fixed fixed fixedLSIA configuration

fixed fixed▲

▲ ▲ ▲ ▲ ▲ ▲ ▲

● ● ● ● ● ● ● ● ● ● ●

● ● ● ● ● ● ● ● ● ● ●

● ● ● ● ● ● ● ● ● ● ●

● ● ● ● ● ● ● ● ● ● ●

● ● ● ● ● ● ● ● ● ● ●

● ● ● ● ● ● ● ● ● ● ●

● ● ● ● ● ● ● ● ● ● ●

● ● ● ● ● ● ● ● ● ● ●

● ● ● ● ● ● ● ● ● ● ●

- - - - - - - - - - -- - - - - - - - - - -- - - - - - - - - - -

0.45 0.45 0.7 0.7 1.1 1.1 1.5 - 1.1 1.1 1.10.65 0.65 1.1 1.1 1.2 1.2 1.7 1.7 1.2 1.2 1.20.85 0.85 1.2 1.2 1.5 1.5 2.1 - 1.5 1.5 1.5

5

60 100 225

75×130×60 90×140×86 105×165×86 105×165×60

Adjustable-thermal, Fixed-magnetic

100, 125, 150, 175, 200, 22560 100Electronically adjustable :

(0.5-0.6-0.7-0.8- 0.9-1.0) ×In

5, 10, 15, 2030, 40, 50

60, 75, 100

15, 20, 30, 40, 5060, 75, 100

63, 80, 100Thermally adjustable ;

(0.8- 0.9-1.0) ×In

90×155×60

See table 1 See table 1 See table 3 See table 2 (table 4 for GBL type)

Table 2.Amb. Temp. -5℃℃ 0℃℃ 10℃℃ 20℃℃ 25℃℃ 30℃℃ 35℃℃ 40℃℃ 45℃℃ 50℃℃

Calibrated for 50℃℃In=16 to 25A 122.0% 120.0% 116.0% 112.0% 110.0% 108.0% 106.0% 104.0% 102.0% 100.0%In=32 to 100A 127.5% 125.0% 120.0% 115.0% 112.5% 110.0% 107.5% 105.0% 102.5% 100.0%

Table 3.Amb. Temp. -5℃℃ 0℃℃ 10℃℃ 20℃℃ 25℃℃ 30℃℃ 35℃℃ 40℃℃ 45℃℃ 50℃℃

Calibrated for 40℃℃ In=100 to 225A 114.3% 113.2% 110.6% 107.5% 105.8% 140.0% 102.0% 100.0% 97.9% 95.6%Calibrated for 50℃℃ In=100 to 225A 116.3% 115.4% 113.2% 110.6% 109.1% 107.5% 105.8% 104.0% 102.0% 100.0%

Page 6: LVCB General Leaflet E 0803

Mold case circuit breakers250AF to 1600AF

6

Note ;● applicable or available▲ available as a separate breaker

Table 4.

Amb. Temp. -5℃℃ 0℃℃ 10℃℃ 20℃℃ 25℃℃ 30℃℃ 35℃℃ 40℃℃ 45℃℃ 50℃℃Calibrated for 50℃℃ In=40 to 200A 127.5% 125.0% 120.0% 115.0% 112.5% 110.0% 107.5% 105.0% 102.5% 100.0%

In=250A 122.0% 120.0% 116.0% 112.0% 110.0% 108.0% 106.0% 104.0% 102.0% 100.0%

GBN GBH GBL GBL(E) ABE ABS ABH ABL35 50 85 85 25 35 50 85

2, 3, 4 2, 3, 4 2, 3, 4 3 2,3,4 2,3,4 2,3,4 2, 3, 4GBN202 GBH202 GBL202 ABE402b ABS402b ABH402b ABL402bGBN203 GBH203 GBL203 GBL203E ABE403b ABS403b ABH403b ABL403bGBN204 GBH204 GBL204 ABE404b ABS404b ABH404b ABL404b

250

600 600 600 600 600 600 600 600250 250 250 - 250 250 250 250690 690 690 690 690 690 690 690

6 6 6 6 6 6 6 6

50 85 125 125 35 50 85 12535 50 85 85 30 42 65 10035 50 85 85 25 35 50 85/50(Ics)35 50 85 85 25 35 50 85

30/22 42/35 65/50 65/50 18 25 35 6518 25 35 35 18 22 25 30- - - - - - - -- - - - 20 30 50 60

35 50 85 - 10 20 40 4075 75 75 75 100 100 50 50A A A A A A A A

10000 10000 10000 10000 4000 4000 4000 40005000 5000 5000 5000 1000 1000 1000 1000

fixed fixed fixed fixedLSIA configuration●

▲ ▲ ▲

▲ ▲ ▲ ▲

● ● ● ● ● ● ● ●

● ● ● ● ● ● ● ●

● ● ● ● ● ● ● ●

● ● ● ● ● ● ● ●

● ● ● ● ● ● ● ●

● ● ● ● - - - -

● ● ● ● ● ● ● ●

● ● ● ● ● ● ● ●

● ● ● ● ● ● ● ●

- - - - ● ● ● ●

- - - - - - - -- - - - - - - -

105×165×86 140×257×1131.5 1.5 1.5 - 5.2 5.2 5.2 5.21.7 1.7 1.7 1.7 6.2 6.2 6.2 6.22.1 2.1 2.1 - 7.8 7.8 7.8 7.8

Frame Size(AF) 250 400Frame TypeBreaking capacity(kA), Icu at 415VACNumber of polesType 2 pole

3 pole4 pole

Rated current (A)

Technical data conforming to IEC/EN60947-2Rated operational voltage(V), Ue(50/60Hz)Rated operational voltage(V), Ue(DC)Rated insulation voltage(V), Ui(50/60Hz)Rated impulse withstand voltage(kV), UimpUltimate breaking capacity(kA), Icu

AC 50/60Hz 220/240V380V415V440/460V480/500V600V690V

DC 125V250V

Service breaking capacity(%Icu), IcsCategory of useEndurance Mechanical(Number of operations) ElectricalType of trip unitThermal-magnetic releaseElectronic releasePre-alarm via LED Hydraulic-magnetic releaseMagnetic release only without thermal tripEarth leakage protection for 3 pole AccessoriesElectrical auxiliaries Auxiliary switch

Alarm switchShunt tripUndervoltage trip

External accessories Direct rotary handleExtended rotary handleTerminal shieldInsulation barrierRear connection Mechanical interlockPlug-in deviceMotor operator

Dimensions (W×H×Dmm) 3 pole breakerWeight(kg) 2 pole

3 pole4 pole

Derating chart : See tables

Electronicallyadjustable :

(0.5-0.6-0.7-0.8-0.9-1.0)×In

250, 300, 350, 400Interchangeable via rating plug between

250 and 300350 and 400

125, 160, 200, 250Thermally adjustable :

(0.8- 0.9-1.0) ×InSee table 4 See table 5

Page 7: LVCB General Leaflet E 0803

GBN(E) GBH(E) ABE ABS ABL GBN(E) GBH(E) ABS ABS(electronic trip) GBN(E)35 50 35 50 85 35 50 65 65 653 3 2, 3, 4 2, 3, 4 2, 3, 4 3 3 3, 4 3 3

ABE802b ABS802b ABL802bGBN403E GBH403E ABE803b ABS803b ABL803b GBN803E GBH803E ABS1003 ABS1203 ABS1203E GBN1603E

ABE804b ABS804b ABL804b ABS1004 ABS12041000 1200 1200 1600

600 600 600 600 600 600 600 600 600 600- - 250 250 250 - - 250 250 -

690 690 690 690 690 690 690 690 690 6906 6 6 6 6 6 6 6 6 8

50 85 50 100 125 50 85 100 100 -35 50 42 65 100 35 50 65 65 -35 50 35 50 85/50(Ics) 35 50 65 65 6530 42 35 50 85 30 42 65 65 4522 35 25 45 65 22 35 50 50 2218 25 22 25 30 18 25 45 45 -- - - - - - - - - 20- - 30 50 60 - - - - -- - 20 40 40 - - 40 - -

50 50 100 50 50 50 50 50 50 50A A A A A A A A A A

4000 4000 2500 2500 2500 2500 2500 2500 2500 100001000 1000 500 500 500 500 500 500 500 4000

fixed fixed fixedLSIA configuration LSIA configuration LSIA configuration ●

● ● ● ● ● ●

▲ ▲ ▲ ●

● ● ● ● ● ● ● ● ● ●

● ● ● ● ● ● ● ● ● ●

● ● ● ● ● ● ● ● ● ●

● ● ● ● ● ● ● ● ● ●

● ● ● ● ● ● ● - - ●

- - - - - - - - - ●

● ● ● ● ● ● ● - - ●

● ● ● ● ● ● ● ● ● ●

● ● ● ● ● ● ● ● ● ●

● ● ● ● ● ● ● - - -- - - - - - - - - ●

- - - - - - - - - ●

- 11 11 11 - - - -7.4 11.5 11.5 11.5 11.5 19.4 19.4 23- 18.2 18.2 18.2 - 27 - -

7

Table 5.

Amb. Temp. -5℃℃ 0℃℃ 10℃℃ 20℃℃ 25℃℃ 30℃℃ 35℃℃ 40℃℃ 45℃℃ 50℃℃

Calibrated for 40℃℃ 110.0% 109.0% 107.0% 105.0% 104.0% 103.0% 101.5% 100.0% 98.5% 97.0%

Calibrated for 50℃℃ 113.0% 112.0% 110.0% 108.0% 107.0% 106.0% 104.5% 103.0% 101.5% 100.0%

400 800 1200 1600

140×257×113 210×400×105 210×350×142.5

Adjustable-thermal, Fixed-magnetic

210×280×113

400Electronically adjustable :

(0.5-0.6-0.7-0.8-0.9-1.0)×In

800Electronically adjustable :(0.5-0.6-0.7-0.8-0.9-1.0)×In

500, 600, 630, 700, 800Interchangeable via rating plug between

500 and 600, 500 and 630, 700 and 800Electronically adjustable :(0.5-0.6-0.7-0.8- 0.9-1.0)×In

See table 5

Page 8: LVCB General Leaflet E 0803

3kA at 230VAC 6kA at

400VAC6kA at

230/400VAC

1 changeover contact

6A at 240VAC, 3A at 415VAC

2A at 48VDC, 1A at 125VDC

Lug terminal

cable capacity 2.5㎟

9mm wide

Type BKP BKN

1A2A3A4A6A10A16A20A25A32A40A50A63A80A

100A125A

Auxiliary switch, AXOptional

Dimension See drawing 1 See drawing 2Characteristic curve See curve 1 See curve 1

Protection Overload and short circuit Overload and short circuitRated current 3,6,10,16,20,25,32A 1,2,3,4,6,10,16,20,25,32,40,50,63ACharacteristic B, C, D curve B, C, D curveNumber of poles 1p+N 1p, 1p+N, 2p, 3p, 3p+N, 4pBreaking capacity 1 pole 2~4 pole

Standard IEC 60898 IEC 60898Type of trip Thermal magnetic release Thermal magnetic releaseElectrical endurance 20000 operations 6000 operationsMount On 35mm DIN rail On 35mm DIN railWidth 9mm per pole 17.8mm per poleTerminal Lug type(cable up to 10㎟) Lug type(cable up to 25㎟)

Miniature circuit breakers1, 2, 3 and 4 pole series up to 125AF

8

Drawing 1 : Type BKP

17.8

8.9

60 82

60

37

455

45

68

(22)

(22)

(17)

Drawing 2 : Type BKN

5

37

4560

(14)

45

17.8

63

68

82

Page 9: LVCB General Leaflet E 0803

10kA at 400VAC

10kA at400VAC

10kA at 230/400VAC

10kA at 400VAC

BKN-b BKH

See drawing 3 See drawing 4See curve 1 See curve 1

Overload and short circuit Overload and short circuit1,2,3,4,6,10,20,25,32,40,50,63A 63, 80, 100, 125AB, C, D curve C, D curve1p, 1p+N, 2p, 3p, 3p+N, 4p 1p, 1p+N, 2p, 3p, 3p+N, 4p1 pole 2~4 pole 1 pole 2~4 pole

IEC 60898 IEC 60947-2Thermal magnetic release Thermal magnetic release8000 operations 6000 operationsOn 35mm DIN rail On 35mm DIN rail17.8mm per pole 27mm per poleLug type(cable up to 25㎟) Lug type(cable up to 50㎟)

9

Drawing 3 : Type BKN-b

17.8

(33)

(19)

4537

5 43.8

6860

65 82

Drawing 4 : Type BKH

Curve 1 : Type BKP, BKN, BKN-b, BKH, RKP

Page 10: LVCB General Leaflet E 0803

Residual current circuit breakers 2 and 4 pole series up to 63AF

10

Drawing 1 : Type RKP

35.6

8.9

8260

45

60

5

(22)

68

37

(22)

(17)

45

70

Drawing 2 : Type RKN

561

74

(13)45

36 45

22

72

68 82

36

68 82

1 3 5 N

2

1

24 6 N

N

N

Drawing 3 : Type KGR Drawing 4 : Type BKD

37

5

60

70

45

(10)

45

60

17.8

82

Drawing 5 : Type RKS

5523

18

18

Type RKP RKS RKNProtection Ground fault and overcurrent Ground fault and overcurrent Ground fault Ground faultRated current, In 3(C,D),6,10,16,20,25,32A(B,C,D curve) 6, 10, 16, 20, 25, 32A (B, C curve) 25, 32, 40, 63ARated residual current

Operating, I△n 30, 100, 300mA(non-adjustable) 30, 100mA (non-adjustable) 30, 100, 300mA(non-adjustable)Non-operating, I△no 0.5I△n 0.5I△n 0.5I△n

Number of poles 1P+N 1P+N 2, 4 poleRated voltage 230VAC 230VAC 230VAC(2p), 230/400VAC(4p)Residual current off-time ≤ 0.1 sec. ≤ 0.3s ≤ 0.1 sec.Standard IEC 61009 IEC 61009 IEC 61008Type of trip

Ground fault Electro-magnetic Electro-magnetic Electro-magneticOvercurrent Thermal-magnetic Thermal-magnetic N.A

Breaking capacity 3kA 10kAConditional short circuit capacity 6kA for In=25, 32, 40, 63AElectrical endurance 20000 operations ≤ 4000 operations 6000 operationsMount On 35mm DIN rail On 35mm DIN rail On 35mm DIN railWidth 9mm per pole 9mm per pole 18mm per poleTerminal Lug type(cable up to 10㎟) Lug type(cable up to 10㎟) Lug type(cable up to 35㎟)Dimension See drawing 1 See drawing 5 See drawing 2Characteristic curve See page 9 (curve 1)

Page 11: LVCB General Leaflet E 0803

11

Type BKDRated current, In 40, 50, 63, 80, 100, 125ANumber of poles 1p, 2p, 3p, 4pRated voltage 230/400VACStandard IEC 60947-3

Electrical 40, 50, 63A 20000 operationsendurance 80, 100, 125A 10000 operationsMount On 35mm DIN railWidth 17.8mm per poleTerminal Lug type(cable up to 50㎟)Dimension See drawing 4

32KGRb32KGRa

Curve 1 : Type 32KGRa, 32KGRb

Ground fault and overcurrent15, 20, 30A

15, 30mA(non-adjustable)0.5I△n2 pole110/220VAC≤ 0.03 sec.KS, JIS *(IEC61009)

ElectronicBimetallic1.5kA 2.5kA

6000 operationsOn 35mm DIN rail35mm Screw clamp type(cable up to 25㎟)See drawing 3See curve 1

Note) * IEC61009 standard is applicable for 32KGRa only.

Page 12: LVCB General Leaflet E 0803

12

Manual motor startersQuick selection table ... IEC rating

220V 220V240V 415V 460V 525V 690V 240V 415V 460V 525V 690V

230V 400V 440V 500V 600V 230V 400V 440V 500V 600V

Icu Ics Icu Ics Icu Ics Icu Ics Icu Ics

100 100 100 100 100 100 100 100 100 100100 100 100 100 100 100 100 100 100 100100 100 100 100 100 100 100 100 100 100100 100 100 100 100 100 100 100 100 100100 100 100 100 100 100 100 100 100 100100 100 100 100 100 100 100 100 3 3100 100 100 100 100 100 50 38 3 3100 100 100 100 50 38 15 11 3 3100 100 100 100 15 11 10 8 3 3100 100 100 100 15 11 10 8 3 3100 100 50 38 15 11 6 5 3 3100 100 50 38 10 8 6 5 3 350 38 20 15 10 8 6 5 3 340 30 15 11 8 6 6 5 3 340 30 15 11 8 6 6 5 3 330 22 15 11 6 4 5 4 3 3- - - - - - - - - -- - - - - - - - - -- - - - - - - - - -- - - - - - - - - -- - - - - - - - - -- - - - - - - - - -

Icu Ics Icu Ics Icu Ics Icu Ics Icu Ics

100 100 100 100 100 100 100 100 100 100100 100 100 100 100 100 100 100 100 100100 100 100 100 100 100 100 100 100 100100 100 100 100 100 100 100 100 100 100100 100 100 100 100 100 100 100 100 100100 100 100 100 100 100 100 100 100 100100 100 100 100 100 100 100 100 8 8100 100 100 100 100 100 100 100 8 8100 100 100 100 100 100 100 100 6 6100 100 100 100 50 38 50 38 6 6100 100 100 100 50 38 50 38 6 6100 100 100 100 50 38 42 32 6 6100 100 50 38 20 15 10 8 4 4100 100 50 38 20 15 10 8 4 4100 100 50 38 20 15 10 8 4 4100 100 50 38 20 15 10 8 4 4

- - - - - - - - - -- - - - - - - - - -- - - - - - - - - -- - - - - - - - - -- - - - - - - - - -- - - - - - - - - -

0.160.250.40.63

11.62.54681013172226324050637590100

TypeCurrent adjustable type MMS-32S MMS-32HInstantaneous type - MMS-32HIBreaking capacity Standard High breakingHandle Type Toggle Rotary

Number of poles 3 3Rated operational voltage (Ue) Up to 690V Up to 690VRated frequency 50/60 Hz 50/60 HzRated insulation voltage (Ui) 690V 690VRated impulse voltage (Uimp) 6kV 6kVUtilization category IEC 60 947-2 (Breaker) Cat. A Cat. A

IEC 60 947-4 (Motor starter) AC 3 AC 3Mechanical endurance (Operating) 100,000 100,000Electrical endurance (Cycles) 100,000 100,000Max operating frequency per hour (Ope./h) 25 25Temperature compensation (Operation) -20 ~ +60℃ -20 ~ +60℃Instantaneous short circuit release 13 × Ie max. 13 × Ie max.Overload protection � �

Phase failure function � �

Trip indicating function × ×

Test function � �

Weight (g) 320 360Rated Rated Thermal releasebreaking operational Adjustmentcapacity

current (Ie)range

(kA) (A)0.1~0.160.16~0.250.25~0.40.4~0.630.63~11~1.6

1.6~2.52.5~44~65~86~109~1311~1714~2218~2622~3228~4034~5045~6355~7570~9080~100

Frame 32AF

Page 13: LVCB General Leaflet E 0803

13

220V 220V240V 415V 460V 525V 690V 240V 415V 460V 525V 690V

230V 400V 440V 500V 600V 230V 400V 440V 500V 600V

220V 220V240V 415V 460V 525V 690V 240V 415V 460V 525V 690V

230V 400V 440V 500V 600V 230V 400V 440V 500V 600V

- - - - - - - - - -- - - - - - - - - -- - - - - - - - - -- - - - - - - - - -- - - - - - - - - -- - - - - - - - - -- - - - - - - - - -- - - - - - - - - -- - - - - - - - - -- - - - - - - - - -

100 100 100 100 15 12 10 8 4 3100 100 50 38 10 8 6 5 4 3100 100 25 19 10 8 6 5 4 350 38 25 19 10 8 6 5 4 350 38 25 19 10 8 6 5 4 350 38 25 19 10 8 6 5 4 350 38 25 19 10 8 6 5 4 350 38 25 19 10 8 6 5 4 350 38 25 19 10 8 6 5 4 3

- - - - - - - - - -- - - - - - - - - -- - - - - - - - - -

- - - - - - - - - -- - - - - - - - - -- - - - - - - - - -- - - - - - - - - -- - - - - - - - - -- - - - - - - - - -- - - - - - - - - -- - - - - - - - - -- - - - - - - - - -- - - - - - - - - -

100 100 100 100 50 38 50 38 6 5100 100 100 100 50 38 42 32 6 5100 100 50 50 50 38 12 9 5 5100 100 50 50 50 38 12 9 5 5100 100 50 50 35 27 12 9 5 5100 100 50 50 35 27 10 8 5 5100 100 50 50 35 27 10 8 5 5100 100 50 50 35 27 10 8 5 5100 100 50 50 35 27 10 8 5 5

- - - - - - - - - -- - - - - - - - - -- - - - - - - - - -

- - - - - - - - - -- - - - - - - - - -- - - - - - - - - -- - - - - - - - - -- - - - - - - - - -- - - - - - - - - -- - - - - - - - - -- - - - - - - - - -- - - - - - - - - -- - - - - - - - - -- - - - - - - - - -- - - - - - - - - -

100 100 50 38 40 30 25 19 10 8100 100 50 38 40 30 25 19 10 8100 100 50 38 40 30 25 19 10 8100 100 50 38 40 30 15 11 10 8100 100 50 38 40 30 15 11 6 5100 100 50 38 40 30 12 9 6 5100 100 50 38 40 30 12 9 6 5100 100 50 38 40 30 8 6 5 4100 100 50 38 40 30 8 6 5 4100 100 50 38 40 30 8 6 5 4

Icu Ics Icu Ics Icu Ics Icu Ics Icu IcsIcu Ics Icu Ics Icu Ics Icu Ics Icu IcsIcu Ics Icu Ics Icu Ics Icu Ics Icu IcsIcu Ics Icu Ics Icu Ics Icu Ics Icu Ics

- - - - - - - - - -- - - - - - - - - -- - - - - - - - - -- - - - - - - - - -- - - - - - - - - -- - - - - - - - - -- - - - - - - - - -- - - - - - - - - -- - - - - - - - - -- - - - - - - - - -- - - - - - - - - -- - - - - - - - - -

100 100 100 100 50 38 35 27 12 9100 100 100 50 50 38 35 27 12 9100 100 100 50 50 38 35 27 12 9100 100 100 50 50 38 25 19 12 9100 100 100 50 50 38 20 15 12 9100 100 100 50 50 38 15 11 10 8100 100 100 50 50 38 15 11 8 6100 100 75 50 50 38 12 9 6 6100 100 75 50 50 38 12 9 6 6100 100 75 50 50 38 12 9 6 6

MMS-63S MMS-63H MMS-100S MMS-100H- MMS-63HI - MMS-100HI

Standard High breaking Standard High breakingRotary Rotary Rotary Rotary

3 3 3 3Up to 690V Up to 690V Up to 690V Up to 690V

50/60 Hz 50/60 Hz 50/60 Hz 50/60 Hz1,000V 1,000V 1,000V 1,000V

8kV 8kV 8kV 8kVCat. A Cat. A Cat. A Cat. AAC 3 AC 3 AC 3 AC 3

50,000 50,000 50,000 50,00025,000 25,000 25,000 25,000

25 25 25 25-20 ~ +60℃ -20 ~ +60℃ -20 ~ +60℃ -20 ~ +60℃

13 × Ie max. 13 × Ie max. 13 × Ie max. 13 × Ie max.� � � �

� � � �

× × � �

� � � �

1,000 1,000 2,200 2,200

63AF 100AF

Page 14: LVCB General Leaflet E 0803

Air circuit breakersRatings

14

Note) 1. Rated current of IEC standard2. Trip relay is divided into 50Hz and 60Hz. Please be careful when you order it.3. The generator protection relay is only available in OCR -III. 4. Ace-MEC ACB with interlock device can be a substitute for ATS5. For mainbody, only horizontal type is available. For cradle, vertical type is optional. In case of vertical type use of the horizontal type,

the user needs to apply the vertical adapter, The vertical type is standard for 4000/500AF.6. For 4000/5000AF, height is 455mm7. Slim type 4000AF, height is H:460, D:509

Type LBA-06������C LBA-08������C LBA-10������C LBA-13������C LBA-16������C

Rated current (In max) (A) 630, 400, 250 800 1000 1250 1600

Rated operating voltage (Ue) (V) 690 690 690 690 690

Rated insulation voltage (Ui) (V) 1000 1000 1000 1000 1000

Frequency (Hz) 50/60 50/60 50/60 50/60 50/60

Number of poles (P) 3,4 3,4 3,4 3,4 3,4

OCR-II For industry In max. × 1.0-0.9-0.8-0.7-0.6-0.5-0.4(7 Steps)

Setting current (In) (A) OCR-III

For industry In max. × 1.0-0.9-0.8-0.7-0.6-0.5-0.4(7 Steps)

For generator protection In max. × 1.0-0.9-0.8-0.7-0.6-0.5-0.4-0.3-0.2(9 Steps)

Rated current of (A) 630 800 1000 1250 1600

neutral pole

690V 50 50 50 50 50

600V 50 50 50 50 50

500V Under 65 65 65 65 65

Rated service(ICS) (kA) …% × ICU 100% 100% 100% 100% 100%

breaking capacity

690V 105 105 105 105 105

600V 105 105 105 105 105

500V Under 143 143 143 143 143

1 sec 65 65 65 65 65

Rated short-time capacity (ICW) (kA) 2 sec 40 40 40 40 60

3 sec 30 30 30 30 50

Maximum total breaking time 40 40 40 40 40

Closing time 80 80 80 80 80

Without maintenance 12000 12000 12000 12000 12000

With maintenance 20000 20000 20000 20000 20000

Without maintenance 3000 3000 3000 3000 3000

With maintenance 5000 5000 5000 5000 5000

Without maintenance 10000 10000 10000 10000 10000

Without maintenance 3000 3000 3000 3000 3000

Motor charging type 66/80 67/81 67/81 67/81 67/81

Manual charging type 63/77 64/78 64/78 64/78 64/78

26/30 26/30 26/30 26/30 26/30

Motor charging type 43/53 44/54 44/54 44/54 44/54

Manual charging type 40/50 41/51 41/51 41/51 41/51

Horizontal type Standard Standard Standard Standard Standard

Vertical type Option Option Option Option Option

Motor charging type Standard Standard Standard Standard Standard

Manual charging type Option Option Option Option Option

Draw-out type (mm) H: 435, D: 479 W(3P/4P) 350/435 350/435 350/435 350/435 350/435

Fixed type (mm) H: 410, D: 375 W(3P/4P) 345/430 345/430 345/430 345/430 345/430

Certificate & Approval KERI, CESI, KEMA

Rated breaking capacity (ICU)

(Sym) IEC 60947-2 AC

IEC 60947-2 AC

(kA)

(kA)

(ms)

(time)

(time)

Mechanical

Electrical

Mechanical

Electrical

Draw-out

type

Fixed type

Cradle only

Main body

(with cradle)

(kg)

Rated making capacity (ICm)

(peak)

Operating time ( t )

Life cycle

Weight

(3P/4P)

Bus-bar

Closing type

External

dimension

Connection type

ACB

ATS withACBs Note 4)

Note5)

Note2)

Note3)

Page 15: LVCB General Leaflet E 0803

15

Type LBA-20������C LBA-25������C LBA-32������C LBA-4S����EC LBA-40������C LBA-50������C

Rated current (In max) (A) 2000 2500 3200(3150) 4000 4000 5000

Rated operating voltage (Ue) (V) 690 690 690 690 690 690

Rated insulation voltage (Ui) (V) 1000 1000 1000 1000 1000 1000

Frequency (Hz) 50/60 50/60 50/60 50/60 50/60 50/60

Number of poles (P) 3,4 3,4 3,4 3,4 3,4 3,4

OCR-II For industry In max. ×1.0-0.9-0.8-0.7-0.6-0.5-0.4(7 Steps)

Setting current (In) (A) OCR-III

For industry In max. × 1.0-0.9-0.8-0.7-0.6-0.5-0.4(7 Steps)

For generator protection In max. ×1.0-0.9-0.8-0.7-0.6-0.5-0.4-0.3-0.2(9 Steps)

Rated current of (A) 2000 2500 3150 4000 2500 2500

neutral pole

690V 50 50 50 50 50 50

600V 65 65 65 65 85 85

500V Under 85 85 85 85 100 100

Rated service(ICS) (kA) …% ×ICU 100% 100% 100% 100% 100% 100%

breaking capacity

690V 105 105 105 105 105 105

600V 143 143 143 143 187 187

500V Under 187 187 187 187 220 220

1 sec 65 65 65 65 85 85Rated short-time

(ICW) (kA) 2 sec 60 60 60 60 65 65capacity

3 sec 60 60 60 60 65 65

Maximum total breaking time 40 40 40 40 40 40

Closing Time 80 80 80 80 80 80

Without maintenance 10000 10000 10000 10000 10000 10000

With maintenance 20000 20000 20000 20000 20000 20000

Without maintenance 3000 3000 3000 3000 3000 3000

With maintenance 5000 5000 5000 5000 5000 5000

Without maintenance 10000 10000 10000 - - -

Without maintenance 3000 3000 3000 - - -

Motor charging type 95/116 96/117 98/119 244/267 244/267

Manual charging type 92/113 93/114 95/116 240/263 240/263

35/43 35/43 36/44 125/140 125/140

Motor charging type 63/75 64/76 66/78 - 119/127 119/127

Manual charging type 60/72 61/73 63/75 - 115/123 115/123

Horizontal type Standard Standard Standard -

Vertical type Option Option Option Standard

Motor charging type Standard Standard Standard Standard Standard Standard

Manual charging type Option Option Option Option Option Option

Draw-out type (mm) H: 435, D: 479 W(3P/4P) 485/615 485/615 485/615 485/615 960/1090 960/1090

Fixed type (mm) H: 410, D: 375 W(3P/4P) 480/610 480/610 480/610 - 870/1000 870/1000

Certificate & Approval KERI, CESI, KEMA KEMA KEMA, CCC

Rated breaking (ICU)

capacity (Sym) IEC 60947-2 AC

IEC 60947-2 AC

(kA)

(kA)

(ms)

(time)

(time)

Mechanical

Electrical

Mechanical

Electrical

Draw

-out

type

Fixed type

Cradle only

Main body

(with cradle)

(kg)

Rated making (ICm)

capacity (peak)

Operating time ( t )

Life cycle

Weight

(3P/4P)

Bus-bar

Closing type

External

dimension

Connection type

ACB

ATS with

ACBs Note 4)

Note5)

Note2)

Note3)

Note6) Note7)

Note1)

Standard offer in the fixed type

Standard offer in the draw-out type

New

Note 8) Slim type 4000A① The cubicle of High capacity low voltage cubicle can get the most suitable space(Dimension is 40% smaller than existing Ace-Mec ACB 4000A)② Current capacity of neutral line(N phase) is 100%③When the OCR-II is applied, only external input power is available.④ Only vertical type of plug in type is available.

Note 9) It is guaranteed by KEMA CB certificate.

Note 9) Note 9)

Note 8)

Page 16: LVCB General Leaflet E 0803

Air circuit breakersElectronic trip relays : OCR-II

16

Characteristics of protection

Deratings by ambient temperature● Ambient temperature: -5℃~±40℃ (Only applicable when the 24 hours average temperature is below ±35℃)● Altitude : Below 2000m● Environmental condition

-Below 85% in humidity with ±40℃maximum temperature-Within the flammable, ammonia and corrosive gas environment can not be used and stored(H2S≤0.01ppm, SO2≤0.01ppm, NH3≤a few ppm)

● Safekeeping temperature : -20℃~±60℃ below ±35℃ degree of 24 hours average temperature

Applicable current of braker in temperatureIn case of use of over 40℃ in ambient temperature, please refer to below table as adjusting the rated currents

40℃ 630 800 1,000 1,250 1,600 2,000 2,500 3,200 4,000 5,000

45℃ 630 800 1,000 1,250 1,600 2,000 2,500 3,200 4,000 5,000

50℃ 630 800 1,000 1,250 1,600 2,000 2,500 3,200 4,000 5,000

55℃ 630 800 1,000 1,250 1,550 2,000 2,450 3,000 3,900 4,850

60℃ 630 800 1,000 1,200 1,500 2,000 2,350 2,900 3,750 4,700

LBA-50LBA-40LBA-32LBA-25LBA-20LBA-16LBA-13LBA-10LBA-08LBA-06AmbienttemperatureType

IEC 60947-2(Standard temp:40℃

① Long-time delay pick-up current② Long-time delay tripping time③ Short-time delay pick-up current④ Short-time delay tripping time:I2t 0N (Operating characteristics inverse)I2t 0FF (Operating characteristics definite)

⑤ Instantaneous pick-up current⑥ Pre-alarm pick-up current⑦ Pre-alarm tripping time⑧Ground fault pick-up current⑨Ground fault trip time

Note 1) For type LN5 and LN6, please use Neutral CT (output: 5A) in case of using 3P ACB in 3phase 4wire circuit.Note 2) In case of short circuit accident, instantaneous operation time of OCR is under 15ms.Note 3) Inp is a function for neutral protection. It protects neutral phase in 4 pole ACB from over current.Note 4) LS6, LS5 : ①②③④⑤⑥⑦

LF6, LF5, LN6, LN6 : ①②③④⑤⑥⑦⑧⑨

Type 60Hz50Hz

ApplicationPossible number of ACB polesOperating voltageCommunication

Long-time delay (L)Short-time delay (S)

Operating characteristics Instantaneous time delay ( I )Ground fault (G)Pre-alarm (P)

Setting current (A) In = …× In Max

Continuous current (A) Ic = …× InLong-time delay(L) Trip current (A) IL = …× Ic(Error tolerance : ±10%) Trip time (sec) LTDShort-time delay(S) Trip current (A) Is = …× In(Error tolerance : ±15%) Trip time (sec) STDInstantaneous time delay(I) Trip current (A) li = …× In(Error tolerance : ± 20%) Trip time (sec) INST

Ground fault(G) Trip current (A)Ig = …× In Max

(Error tolerance : ±20%)Inp= …× In Max

Trip time (sec) GTDPre-alarm(P) Trip current (A) Ip = …× Ic(Error tolerance : ±10%) Trip time (sec) PAL = …× LTD

Classification Types and ratings of trip relaysLS6 LF6 LN6 Note1)

LS5 LF5 LN5 Note1)

For industry For industry For industry3, 4P 3,4P 3P

AC/DC 110V~220V AC/DC 110V~220V AC/DC 110V~220V- - -� � �

� � �

� � �

- � �

� � �

0.4-0.5-0.6-0.7-0.8-0.9-1.00.6-0.7-0.8-0.85-0.9-0.95-1.0

1.515-30-60-120-240-480

2-3-4-6-8-10-OFF0.05-0.1-0.2-0.3-0.4-0.5

4-6-8-10-12-16-OFF0.025 under Note2)

0.1-0.2-0.3-0.4-0.5-OFF0.5-1.0-OFF Note3)

0.1-0.3-0.5-0.7-1.0-1.5-3.00.7-0.8-0.9-0.95-1.0-OFF

0.5(setting Ip 1.0), Operating time : Half of the long time inverse time

Page 17: LVCB General Leaflet E 0803

17

OCR-III

Characteristics of protection① Long-time delay pick-up current

② Long-time delay tripping time

③ Short-time delay pick-up current

④ Short-time delay tripping time

⑤ Instantaneous pick-up current

⑥ Pre-alarm pick-up current

⑦ Pre-alarm tripping time

⑧Ground fault pick-up current

⑨Ground fault trip time

Note 1) In case of short circuit accident, instantaneous operation time of OCR is under 15ms.Note 2) N�6/5, P�6/5 : ①②③④⑤⑥⑦⑧⑨

C�6/5, M�6/5 : ①②③④⑤⑥⑦⑧⑨

Type 60Hz

50Hz

Application

Possible number Of ACB poles

1

Operating voltage 2

4

Communication

Communication protocol

Protocol

Transmission speed

Long-time delay(L)

Short-time delay(S)

Operating characteristics Instantaneous time delay (I)

Ground fault (G)

Pre-alarm (P)

Rated current (A) In = …× In Max.

Continuous current (A) Ic = …× In

Long-time delay(L)Trip current (A) IL = …× Ic

(Error tolerance : ±10%) Trip time (sec) LTD

Short-time delay(S) Trip current (A) Is = …× In

(Error tolerance: ±15%) Trip time (sec) STD

Instantaneous time delay(I) Trip current (A) li = …× In

(Error tolerance : ±15%)Trip time (sec) INST

Trip current (A) Ig = …× In Max.Ground fault(G)

(Error tolerance : ±20%)Trip time (sec) GTD

Pre-alarm(P) Trip current (A) Ip = …× Ic

(Error tolerance : ±10%) Trip time (sec) PAL = … x LTD

N�6 C�6 P�6 M�6

N�5 C�5 P�5 M�5

For industry For industry For generator protection For generator protection

3, 4P 3, 4P 3, 4P 3, 4P

AC/DC 110V/220V AC/DC 110V/220V AC/DC 110V/220V AC/DC 110V/220V

DC24V DC24V DC24V DC24V

DC48V DC48V DC48V DC48V

- � - �

- RS 485 - RS 485

- DNP 3.0 - DNP 3.0

- 9600 bps - 9600 bps

� � � �

� � � �

� � � �

� � � �

� � � �

�For industry: 0.4-0.5-0.6-0.7-0.8-0.9-1.0

�For generator protection: 0.2-0.3-0.4-0.5-0.6-0.7-0.8-0.9-1.0

0.6-0.65-0.7-0.75-0.8-0.85-0.9-0.95-1.0

1.5

�For industry : 15-20-25-30~465-470-475-480(Steps: 5sec)

�For generator protection: 1.5-2.0-2.5-3.0~46.5-47.0-47.5-48.0(Steps: 0.5sec)

1.5-2-3-4-5-6-7-8-9-10-no(Steps: 0.5)

0.05-0.06~0.49-0.5(Steps: 0.01sec)

�4000A under: 2-3-4-5-6-7-8-9-10-11-12-13-14-15-16-no(Steps: 1)

�5000A over: 2-3-4-5-6-7-8-9-10-11-12-no(Steps: 1)

0.025 under Note)

�3 pole: 0.2-0.3-0.4-0.5-0.6-0.7-0.8-0.9-10-no(Steps: 0.1)

�4 pole: 0.1-0.2-0.3-0.4-0.5-0.6-0.7-0.8-0.9-10-no(Steps: 0.1)

0.1-0.2-0.3~2.8-2.9-3.0 (Step: 0.1sec)

0.7-0.8-0.9-1.0

0.5(setting Ip 1.0)

Classification Types and ratings of trip relays

Page 18: LVCB General Leaflet E 0803

Contactors & Overload relays9 to 85A

18

2-poleSide mount

4-poleFront mount

2-poleFront mount

Types AC coil GMC-9 GMC-12 GMC-18 GMC-22 DC coil GMD-9 GMD-12 GMD-18 GMD-22

Ratings / IEC60947-4 kW A kW A kW A kW AAC1 25 25 40 40AC3 200/240V 2.5 11 3.5 13 4.5 18 5.5 22

380/440V 4 9 5.5 12 7.5 18 11 22500/550V 4 7 7.5 12 7.5 13 15 22690V 4 5 7.5 9 7.5 9 15 18

Ratings / UL508 hp A hp A hp A hp Acontinuous current 20 25 30 32single phase 115V 0.5 0.5 1 2

230V 1 2 3 3three phase 200V 2 3 5 7

230V 2 3 5 7.5460V 5 7.5 10 10575V 7.5 10 15 15

NEMA size 00 00 0 0

Types AC coil GMC-9/4 GMC-12/4 GMC-18/4 GMC-22/4DC coil GMD-9/4 GMD-12/4 GMD-18/4 GMD-22/4

AC1(A) 20 20 25 32

Additional auxiliary contacts

3-pole Contactors

9AFrame size 12A 18A 22A

4-pole Contactors

Overload Relays

Bimetallic styleType GT

Base for separate mount

Setting ranges (A)

DifferentialClass10A Non-differential (3-heater)

Non-differential (2-heater)Class 20 Differential

GTK-22GTH-22/3GTH-22

GTK-22/L

0.1 - 0.160.16 - 0.250.25 - 0.4

0.4 - 0.630.63 - 1

1 - 1.61.6 - 2.52.5 - 4

4 - 65 - 86 - 97 - 109 - 13

12 - 1616 - 22

Electronic styleType GMP

Class 1�30 adjustableSeparate mount type

GMP22

Setting ranges (A)

0.1 - 1.51 - 5

4.4 - 22

GT-22

Page 19: LVCB General Leaflet E 0803

19

Base for separate mount

Setting ranges(A) : 16 ~ 80A

Separate mountWiring by screw

GMP80

Setting ranges(A) : 5 ~ 60A

Separate mountWiring by CT tunnelGMP60

Setting ranges (A)4 - 20

8 - 40

GMC-32 GMC-40 GMC-50 GMC-65 GMC-75 GMC-85 GMD-32 GMD-40 GMD-50 GMD-65 GMD-75 GMD-85

kW A kW A kW A kW A kW A kW A50 60 80 100 110 135

7.5 32 11 40 15 55 18.5 65 22 75 25 8515 32 18.5 40 22 50 30 65 37 75 45 85

18.5 28 22 32 30 43 33 60 37 64 45 7518.5 20 22 23 30 28 33 35 37 42 45 45hp A hp A hp A hp A hp A hp A

45 50 70 80 90 1002 3 3 5 5 7.55 5 7.5 10 15 15

7.5 10 10 15 20 2510 10 15 20 25 3020 25 30 40 50 5020 25 30 40 50 501 1 2 2 2 3

GMC-32/4 GMC-40/4 GMC-50/4 GMC-65/4 GMC-75/4 GMC-85/4 GMD-32/4 GMD-40/4 GMD-50/4 GMD-65/4 GMD-75/4 GMD-85/4

50 60 80 100 110 135

32A

Base for separate mountGT-85

Setting ranges (A)

GTK-40GTH-40/3GTH-40

GTK-40/L

GTK-85GTH-85/3GTH-85

GTK-85/L

7 - 109 - 13

12 -1816 - 2218 - 2624 - 36

28 - 4034 -5045 - 6554 - 7563 - 85

GT-40

Setting ranges (A)

4 - 65 - 86 - 97 - 109 - 13

12 -1816 - 2218 - 2624 - 3628 - 40

separate mount

40A 50A 65A 75A 85A

GMP40

2-poleSide mount

4-poleFront mount

2-poleFront mount

Page 20: LVCB General Leaflet E 0803

20

Contactors & Overload relays100 to 800A

Types AC/DC GMC-100 GMC-125 GMC-150 common coil

Ratings / IEC60947-4 kW A kW A kW A

AC1 160 160 210

AC3 200/240V 30 105 37 125 45 150

380/440V 55 105 60 120 75 150

500/550V 55 85 60 90 90 140

690V 55 65 60 70 90 100

Ratings / UL508 hp A hp A hp A

continuous current 160 160 210

single phase 115V 7.5 10 15

230V 15 20 25

three phase 200V 30 40 40

230V 30 40 50

460V 60 75 100

575V 60 75 100

NEMA size 3 3 4

Types AC/DC GMC-100/4 GMC-125/4 GMC-150/4common coil

AC1(A) 160 160 210

Additional auxiliary contacts

3-pole Contactors

100AFrame size 125A 150A

4-pole Contactors

Overload Relays

Bimetallic styleType GT

GT- 100

Setting ranges (A)

Differential

Class10A Non-differential (3-heater)

Non-differential (2-heater)

Class 20 Differential

GTK-100

GTH-100/3

GTH-100

GTK-100/L

GTK-150

GTH-150/3

GTH-150

GTK-150/L

34 - 50

39 - 57

43 - 65

54 - 80

65 - 100

85 - 125GT- 150

Setting ranges (A)

34 - 50

39 - 57

43 - 65

54 - 80

65 - 100

85 - 125

100 - 150

AU-1001NO+1NC, Side mount

Page 21: LVCB General Leaflet E 0803

21

GTK-220

GTH-220/3

GTH-220

GTK-220/L

GTK-400

GTH-400/3

GTH-400

GTK-400/L

GTK-600

GTH-600/3

GTH-600

GTK-600/L

GMC-180 GMC-220 GMC-300 GMC-400 GMC-600 GMC-800

kW A kW A kW A kW A kW A kW A

230 275 350 450 660 900

55 180 75 250 90 300 125 400 190 630 220 800

90 180 132 250 160 300 220 400 330 630 440 800

110 180 132 200 160 250 225 350 330 500 550 720

110 120 132 150 200 220 250 300 330 420 500 630

hp A hp A hp A hp A hp A hp A

230 275 350 450 660 900

15 15

30 40

60 60 100 125 150 250

60 75 100 150 200 300

125 150 200 300 400 600

125 150 200 300 400 600

4 4 5 5 6 7

GMC-180/4 GMC-220/4 GMC-300/4 GMC-400/4 GMC-600/4 GMC-800/4

230 275 350 450 660 900

180A 220A 300A 400A 600A 800A

GT- 220

Setting ranges (A)

65 - 100

85 - 125

100 - 150

120 - 180

160 - 240GT- 400

Setting ranges (A)

85 - 125

100 - 150

120 - 180

160 - 240

220 - 300

260 - 400

Setting ranges (A)

220 - 300

260 - 400

400 - 600

520 - 800

AU-1001NO+1NC, Side mount

GT- 800

Page 22: LVCB General Leaflet E 0803

Mini contactors6 to 16A

22

3NO main contacts

1 auxiliary contactsScrew clamp type Fast-on type Cage clamp type Solder pin type

Mini contactors

Overload Relays

Bimetallic styleType GT

Screw clamp type AC coil GMC-6M GMC-9M GMC-12M GMC-16M

DC coil GMD-6M GMD-9M GMD-12M GMD-16M

Fast-on type AC coil GMC-6MF GMC-9MF GMC-12MF GMC-16MF

DC coil GMD-6MF GMD-9MF GMD-12MF GMD-16MF

Cage clamp type AC coil GMC-6MC GMC-9MC GMC-12MC GMC-16MC

DC coil GMD-6MC GMD-9MC GMD-12MC GMD-16MC

Solder pin type AC coil GMC-6MP GMC-9MP GMC-12MP GMC-16MP

DC coil GMD-6MP GMD-9MP GMD-12MP GMD-16MP

Ratings / IEC60947-4 kW A kW A kW A kW A

AC1 20 20 20 20

AC3 200/240V 1.5 7 2.2 9 3 12 4 15

380/440V 2.2 6 4 9 5.5 12 7.5 16

500/550V 3 5 3.7 6 4 7 5.5 9

690V 3 4 4 5 4 5 4 5

Ratings / UL508 hp A hp A hp A hp A

continuous current Ith = 20A (maximum for cage clamp type is 10A)

single phase 120V 1/2 1/2 1 * -

230V/240V 1 1.5 2 * * -

three phase 240V 1.5 3 3 -

480V 3 5 7.5 * * * -

600V 3 5 7.5 -

Wire Range : Copper, 75°C, Stranded, 18-12AWG

NEMA size 00 00 00 0

Base for separate mountGT-12M

Setting ranges (A)

Differential

Non-differential (3-heater)

Non-differential (2-heater)

GTK-12M

GTH-12M/3

GTH-12M

0.1 - 0.160.16 - 0.250.25 - 0.40.4 - 0.63

0.63 - 11 - 1.6

1.6 - 2.52.5 - 4

4 - 65 - 86 - 97 - 109 - 13

12 - 16

Frame size 6A 9A 12A 16A

AU-2M

AU-1M

AU-4M

AU-2MF

AU-1MF

AU-4MF

AU-2MC

AU-1MC

AU-4MC AU-1MP

Additional auxiliary contacts

Note) * = 1/2 for cage clamp type, ** = 1.5hp for cage clamp type, *** = 5hp for cage clamp type16AF : not approved from UL

2-pole, Front mount

4-pole, Front mount

2-pole, Side mount

Fast-on type Cage clamp type Solder pin typeScrew clamp type

Page 23: LVCB General Leaflet E 0803

23

Digital motor protection relay

Model No. DMP06-S/Sa DMP60-S/Sa DMP06-T/Ta DMP06-T/Ta Wiring Screw type Tunnel type

Panel mount Unit or Extension Note1)

Operation time Select either reverse time characteristics or definite time characteristics

Protection Over current According to the setting time

Phase failure 3 sec.

Reverse phase Within 0.1 sec.

Asymmetry 5 sec.

Stall 5 sec.

Lock Within 0.5 sec.

Under current 3 sec.

Ground fault Within 0.05~1 sec. Selectable (0.05~1.0sec)

Short circuit Note2) Within 50ms

Alarm Variable (60~110% of the setting current)

Current setting range (A) 0.5~6 5~60 0.5~6 5~60

Motor capacity 220~240V 0.09~0.75 1.1~11 0.09~0.75 1.1~11

(kW) 380~440V 0.12~1.5 2.2~22 0.09~1.5 2.2~22

Time setting Definite Delay in starting 0~60sec

range (sec) time Delay in operating 0~30sec

Inverse time 0~60sec

Reset Manual reset

Tolerance Current ±5%

Time ±5% (or±0.5sec)

Operating power Voltage AC 190~250V

Note3) Frequency 60Hz (50Hz)

Aux. contact OL 2-SPST 3A/250Vac Resistive load

AL SPST 3A/250Vac Resistive load

Insulation resistance Over DC500V 100㏁

Surge impulse voltage(IEC1000-4-5) 1.2×50㎲ 6kV (Apply standard wave form)

Fast transient burst(IEC1000-4-4) 2.5kV/5min

Environment Temperature Operation -25~70℃

Storage -30~80℃

Humidity 30~90% RH (No freezing)

Display 7-Segment 3 phase current, cause of a fault

Bar-Graph 60~110% of real load current

Mounting type 35mm Din-rail/Panel

Note1) In extension type, the digital EMPR is calibrated with combining the display past and main body so, please cautious not to combine the display part and main body with different part No.

Note2) Instantaneous short circuit protection is optional Note3) Operational voltage of AC 110V and 50Hz is optional

DMP��-S/Sa DMP��-T/Ta

Page 24: LVCB General Leaflet E 0803

��For your safety, please read user's manual thoroughly before operating.

��Contact the nearest authorized service facility for examination, repair, or adjustment.

��Please contact qualified service technician when you need maintenance.Do not disassemble or repair by yourself!

��Any maintenance and inspection shall be performed by the personnel having expertise concerned.Safety Instructions

��LS Industrial Systems (Middle East) FZE ����Dubai, U.A.E. Address: P.O.Box-114216, API World Tower, 303B, Sheikhe Zayed Road, Dubai, U.A.E. Tel: 971-4-332-8289 Fax: 971-4-332-9444 e-mail: [email protected]

��Dalian LS Industrial Systems Co., Ltd. ����Dalian, ChinaAddress: No.15, Liaohexi 3-Road, Economic and Technical Development zone, Dalian 116600, ChinaTel: 86-411-8273-7777 Fax: 86-411-8730-7560 e-mail: [email protected]

��LS Industrial Systems (Wuxi) Co., Ltd. ����Wuxi, chinaAddress: 102-A , National High & New Tech Industrial Development Area, Wuxi, Jiangsu,214028, P.R.ChinaTel: 86-510-8534-6666 Fax: 86-510-522-4078 e-mail: [email protected]

��LS-VINA Industrial Systems Co., Ltd. ����Hanoi, VietnamAddress: Nguyen Khe - Dong Anh - Ha Noi - Viet NamTel: 84-4-882-0222 Fax: 84-4-882-0220 e-mail: [email protected]

��LS Industrial Systems Tokyo Office ����Tokyo, JapanAddress: 16FL, Higashi-Kan, Akasaka Twin Tower 17-22, 2-chome, Akasaka, Minato-ku Tokyo 107-8470, JapanTel: 81-3-3582-9128 Fax: 81-3-3582-2667 e-mail: [email protected]

��LS Industrial Systems Shanghai Office ����Shanghai, ChinaAddress: Room E-G, 12th Floor Huamin Empire Plaza, No.726, West Yan'an Road Shanghai 200050, P.R. ChinaTel: 86-21-5237-9977 (609) Fax: 89-21-5237-7191 e-mail: [email protected]

��LS Industrial Systems Beijing Office ����Beijing, ChinaAddress: B-Tower 17FL.Beijing Global Trade Center B/D. No.36, BeiSanHuanDong-Lu, DongCheng-District,Beijing 100013, P.R. ChinaTel: 86-10-5825-6025,7 Fax: 86-10-5825-6026 e-mail: [email protected]

��LS Industrial Systems Guangzhou Office ����Guangzhou, ChinaAddress: Room 1403,14F,New Poly Tower,2 Zhongshan Liu Road,Guangzhou, P.R. ChinaTel: 86-20-8326-6764 Fax: 86-20-8326-6287 e-mail: [email protected]

��LS Industrial Systems Chengdu Office ����Chengdu, ChinaAddress: 12Floor, Guodong Buiding, No52 Jindun Road Chengdu, 610041, P.R. ChinaTel: 86-28-8612-9151 Fax: 86-28-8612-9236 e-mail: [email protected]

��LS Industrial Systems Qingdao Office ����Qingdao, ChinaAddress: 7B40,Haixin Guangchang Shenye Building B, No.9, Shandong Road Qingdao 26600, P.R. ChinaTel: 86-532-8501-6568 Fax: 86-532-583-3793 e-mail: [email protected] in this catalog are subject to change without notice due to

continuous product development and improvement.

�� HEAD OFFICEYonsei Jaedan Severance Bldg., 84-11, Namdaemunno 5ga,Jung-gu, Seoul, 100-753, KoreaTel. (82-2)2034-4870Fax. (82-2)2034-4713

�� CHEONG-JU PLANTCheong-Ju Plant #1, Song Jung Dong, Hung Duk Ku,Cheong Ju, 361-720, Korea

Leader in Electrics & Automation

��Global Network

www.lsis.biz

2008. 03 LOW VOLTAGE CIRCUIT BREAKERS & CONTACTORS(E) 2004. 02/(20) 2008. 03 Printed in Korea STAFF

ⓒ 2004.2 LS Industrial Systems Co.,Ltd. All rights reserved.