Installer Guide - - Intro | Braeburn Systems

18
Installer Guide Programmable Touchscreen Thermostats 1 Specifications 2 Installation and Wiring 3 Quick Reference 4 Installer Settings 5 System Testing To prevent damage to the thermostat, never use a sharp instrument to press the touchscreen keys. Always press keys with your fingers. Attention • Possible electric shock or damage to equipment can occur. • Disconnect power before beginning installation. Caution This thermostat requires 24 Volt AC Power or 2 properly installed “AA” Alkaline batteries for proper operation. When connecting 24 Volt AC Power the batteries may be installed as a backup. For use only as described in this manual. Any other use will void warranty. 6100 Single Stage Heat / Cool Conventional or Heat Pump 6300 Up to 4 Heat / 2 Cool Heat Pump Up to 3 Heat / 2 Cool Conventional 6400 Up to 4 Heat / 2 Cool Heat Pump Up to 3 Heat / 2 Cool Conventional with Humidity Control Warning For installation by experienced service technicians only. Touchscreen TM ®

Transcript of Installer Guide - - Intro | Braeburn Systems

Page 1: Installer Guide -   - Intro | Braeburn Systems

Installer Guide

Programmable Touchscreen Thermostats

1 Specifications 2 Installation and Wiring 3 Quick Reference 4 Installer Settings 5 System Testing

To prevent damage to the thermostat, never use a sharp instrument to press the touchscreen keys. Always press keys with your fingers.

Attention

• Possible electric shock or damage to equipment can occur.• Disconnect power before beginning installation.

Caution

This thermostat requires 24 Volt AC Power or 2 properly installed “AA” Alkaline batteries for proper operation. When connecting 24 Volt AC Power the batteries may be installed as a backup.

For use only as described in this manual. Any other use will void warranty.

6100 Single Stage Heat / Cool Conventional or Heat Pump

6300 Up to 4 Heat / 2 Cool Heat Pump Up to 3 Heat / 2 Cool Conventional

6400 Up to 4 Heat / 2 Cool Heat Pump Up to 3 Heat / 2 Cool Conventional with Humidity Control

Warning For installation by experienced service technicians only.

Touchscreen TM

®

Page 2: Installer Guide -   - Intro | Braeburn Systems

This thermostat is compatible with: • Singlestageheat/coolconventionalandheatpumpsystems • Conventionalsystemsupto3stagesofheatingand2stagesofcooling(6300/6400only) • Heatpumpsystemsupto4stagesofheatingand2stagesofcooling(6300/6400only) • 250–750millivoltheatingonlysystems

Electrical and control specifications: • ElectricalRating:24VoltAC • 1ampmaximumloadperterminal • ACPower:18–30VoltsAC • DCPower:3.0VoltDC(2“AA”AlkalineBatteriesIncluded) • ControlRange:45°–90°F(7°–32°C) • TemperatureAccuracy:+/-1°F(+/-.5°C) • OutdoorTemperatureDisplayRange:-40°-120°F(-40°-49°C)

Humidification Specifications (6400 Only) • HumidificationControlRange:10%-50%RH • DehumidificationControlRange:40%-80%RH

Terminations • 6100:G,Rc,Rh,W,O/B,Y,C,S1,S2 • 6300:A,G,Rc,Rh,W1/E/AUX1,W2/AUX2,W3/O/B,Y1,Y2,C,L,S1,S2 • 6400:H,A/D,G,Rc,Rh,W1/E/AUX1,W2/AUX2,W3/O/B,Y1,Y2,C,L,S1,S2

Thermostat LocationInstallthethermostatapproximately5feet(1.5m)abovethefloorinanareathathasagoodamountofaircirculationandmaintainsanaverageroomtemperature.

Avoidinstallationinlocationswherethethermostatcanbeaffectedbydrafts,deadairspots,hotorcoldairducts,sunlight,appliances,concealedpipes,chimneysandoutsidewalls.

Installer Guide 2

Warning Disconnect power before beginning installation.

2 Installation and Wiring

1 Specifications

Page 3: Installer Guide -   - Intro | Braeburn Systems

3 Installer Guide

Install your new Braeburn thermostat in 4 basic steps:1 Installthesub-base2 ProvidePower3 Connectyourwires4 Attachthethermostattothesub-base

Install the Sub-Base: •Removethesub-basefromthebodyofthethermostat.•Mountthesub-baseasshownbelow:

UP UP

Provide Power

• For24VoltACpower,youmustconnectthecommonsideofthetransformertotheCterminalonthe thermostatsub-base.Indualtransformerinstallations,thetransformercommonmustcomefromthe coolingtransformer.•Forbatterypower,insertthe2supplied“AA”typealkalinebatteriesintothebattercompartmentlocatedinthe rearhousingofthethermostat.MakesuretopositionthePositive(+)andNegative(-)sidesofthebatteries correctlywiththe+/-symbolsinthebatterycompartment.

Drill 3/16” pilot holes in your desired location. Use supplied anchors for drywall or plaster.

C+

+

24VAC Power Terminal (C) Batteries Installed as Shown

1

2

Page 4: Installer Guide -   - Intro | Braeburn Systems

Installer Guide 4

Wiring Terminations for model 6100

Terminal Function Description

G Output FanControl

Rc Input 24VoltACCoolingTransformer (DualTransformerSystemsOnly)

Rh Input PowerConnection(24VoltACHeating TransformerorMillivoltPowerSource)

W Output 1stStageConventionalHeat

OorB Output ReversingValve(CoolActiveorHeatActive)

Y Output 1stStageCompressor

C Input 24VoltACTransformerCommon

S1 Input OptionalRemoteSensor(IndoororOutdoor)

S2 Input OptionalRemoteSensor(IndoororOutdoor)

Wiring Terminations for models 6300 and 6400

Terminal Function Description

H Output Humidifier(6400Only)

A/D* Output (A)EconomizerControl,(D)Dehumidifier

G Output FanControl

Rc Input 24VoltACCoolingTransformer (DualTransformerSystemsOnly)

Rh Input PowerConnection(24VoltACHeating TransformerorMillivoltPowerSource)

W1/E/ Output (W1)1stStageConventionalHeat, AUX1 (E)EmergencyHeat, (AUX1)1stStageAuxiliaryHeat

W2/AUX2 Output (W2)2ndStageConventionalHeat, (AUX2)2ndStageAuxHeat

W3/OorB Output (W3)3rdStageConventionalHeat, (O)CoolActiveReversingValve (B)HeatActiveReversingValve

Y1 Output 1stStageCompressor

Y2 Output 2ndStageCompressor

C Input 24VoltACTransformerCommon

L Input SystemMalfunctionIndicator

S1 Input OptionalRemoteSensor(IndoororOutdoor)

S2 Input OptionalRemoteSensor(IndoororOutdoor)

*ThisterminalappearsasAonthe6300andA/Donthe6400.

Connecting Your Wires3

Page 5: Installer Guide -   - Intro | Braeburn Systems

5 Installer Guide

Heat Only or Millivolt Set System Type to 11CONV

Rh PowerConnection

W1 HeatRelay(appearsasWonthe6100)

1 HEAT / 1 COOL Single or Dual Transformer Set System Type to 11CONV

Rh 24VoltACPower(heatingtransformer)[note 2]

Rc 24VoltACPower(coolingtransformer)[note 2]

W1 HeatRelay(appearsasWonthe6100)

Y1 CompressorRelay(appearsasY onthe6100)

G FanRelay

C 24VoltACTransformerCommon[note 1, 3]

Conventional SystemsTypical Wiring Configurations

NOTE: The “System Type” option will be configured in the Installer Settings section. The 6100 is a single stage thermostat and not intended for multi stage equipment.

NOTES - Conventional Systems[1]Optional24VoltACcommonconnection.[2]Removefactoryinstalledjumperfordual transformersystems.[3] Indualtransformersystems,transformer commonmustcomefromcoolingtransformer.[4]ConnectY2onlyifasecondcoolingcompressor isbeingused.

3 HEAT / 2 COOL Single or Dual Transformer Set System Type to 32CONV

Rh 24VoltACPower(heatingtransformer)[note 2]

Rc 24VoltACPower(coolingtransformer)[note 2]

W1 HeatRelayStage1

W2 HeatRelayStage2

W3 HeatRelayStage3

Y1 CompressorRelayStage1

Y2 CompressorRelayStage2 [note 4]

G FanRelay

C 24VoltACTransformerCommon[note 1, 3]

2 HEAT / 2 COOL Single or Dual transformer Set System Type to 22CONV

Rh 24VoltACPower(heatingtransformer)[note 2]

Rc 24VoltACPower(coolingtransformer)[note 2]

W1 HeatRelayStage1

W2 HeatRelayStage2

Y1 CompressorRelayStage1

Y2 CompressorRelayStage2 [note 4]

G FanRelay

C 24VoltACTransformerCommon[note 1, 3]

Page 6: Installer Guide -   - Intro | Braeburn Systems

Installer Guide 6

Heat Pump SystemsTypical Wiring Configurations

NOTE: The “System Type” option will be configured in the Installer Settings section. The 6100 is a single stage thermostat and not intended for multi stage equipment.

1 HEAT / 1 COOL - No Auxiliary HeatSet System Type to 11HP

Rh 24VoltACPower

Rc ConnectedtoRhwithsuppliedJumperWire

O/BChangeoverValve [note 2]

Y1 CompressorRelay(appearsasYonthe6100)

G FanRelay

C 24VoltACTransformerCommon [note 1]

3 HEAT / 2 COOL – Including Auxiliary HeatSet System Type to 32HP

Rh 24VoltACPower

Rc ConnectedtoRhwithsuppliedJumperWire

O/B ChangeoverValve [note 2]

Y1 Compressor1Relay(1ststageheating/cooling)

Y2 Compressor2Relay(2ndstageheating/cooling)

AUX1/E AuxiliaryHeatRelay(3rdstageheating) /Emergency Heat[note 5]

E EmergencyHeatRelay [note 5]

G FanRelay

C 24VoltACTransformerCommon[note 1]

L OptionalSystemFaultMonitor[note 4]

2 HEAT / 1 COOL - Including Auxiliary Heat Set System Type to 22HP

Rh 24VoltACPower

Rc ConnectedtoRhwithsuppliedJumperWire

O/BChangeoverValve[note 2]

Y1 CompressorRelay(1ststageheating/cooling)

W2 AuxiliaryHeatRelay(2ndstageheating)[note 3]

E EmergencyHeatRelay[note 3]

G FanRelay

C 24VoltACTransformerCommon[note 1]

L OptionalSystemFaultMonitor[note 4]

2 HEAT / 2 COOL - No Auxiliary HeatSet System Type to 32HP

Rh 24VoltACPower

Rc ConnectedtoRhwithsuppliedJumperWire

O/BChangeoverValve[note 2]

Y1 Compressor1Relay(1ststageheating/cooling)

Y2 Compressor2Relay(2ndstageheating/cooling)

G FanRelay

C 24VoltACTransformerCommon[note 1]

L OptionalSystemFaultMonitor[note 4]

4 HEAT / 2 COOL - Including Auxiliary HeatSet System Type to 42HP

Rh 24VoltACPower

Rc ConnectedtoRhwithsuppliedJumperWire

O/B ChangeoverValve[note 2]

Y1 Compressor1Relay(1ststageheating/cooling)

Y2 Compressor2Relay(2ndstageheating/cooling)

AUX1/E AuxiliaryHeatRelay1(3rdstageheating) /EmergencyHeat[note 5]

AUX2 AuxiliaryHeatRelay2Relay(4thstageheating)

E EmergencyHeatRelay[note 5]

G FanRelay

C 24VoltACTransformerCommon[note 1]

L OptionalSystemFaultMonitor[note 4]

NOTES - Heat Pump Systems[1] Optional24VoltACcommonconnection.[2] O(coolactive)orB(heatactive)isselectedinthe InstallerSettingsmenu.[3] InstallafieldsuppliedjumperbetweentheW2/AUX2 andW1/E/AUX1terminalsifthereisnoseparate emergencyheatrelayinstalled.[4] IftheLterminalisused,the24VoltACcommon mustbeconnected(Cterminal).[5] Ifaseparateemergencyheatrelayisinstalled,the W1/E/AUX1terminalshouldhaveboththeauxiliary heat1relayandemergencyheatrelayconnected.

Page 7: Installer Guide -   - Intro | Braeburn Systems

7 Installer Guide

All System TypesAdditional Wiring Options

NOTE: Additional options are configured in the Installer Settings section.

S1 IndoororOutdoorRemoteSensor[note 1]

S2 IndoororOutdoorRemoteSensor[note 1]

A/D* EconomizerControl(6300,6400only)/ DehumidifierOutput(6400only)[note 2]

H HumidifierOutput(6400only)[note 3]

*ThisterminalappearsasAonthe6300andA/Donthe6400.

NOTES - Additional Wiring Options[1]TheseterminalscanbeusedtoconnectaBraeburn®indoororoutdoorremotesensor.[2]Thisterminalcanbeusedeitherforoutsideaircontrol(6300and6400)ortoconnecttoanexternal dehumidifier(6400only).[3]Thisterminalcanbeusedtoconnectanexternalhumidifier(6400only).

Attaching the thermostat to the sub-base

1) Lineupthethermostatbodywiththesub-base.2) Carefullypushthethermostatbodyagainstthe sub-baseuntilitsnapsinplace.

NOTE: This thermostat ships configured as a 1H/1C conventional thermostat. Confirm installer settings. See page 10.

UP UP

S1

S2

G

Y1

Y2

A

H

L

C

W1/E/AUX1

W2/AUX2

W3/O/B

RH

RC

W1/E/AUX1

G

RESETRESET

3) InsertQuickReferenceCardintoslot ontopofthermostat.

4

Page 8: Installer Guide -   - Intro | Braeburn Systems

Installer Guide 8

RESETRESET

Room Temperature...................... Displaysthecurrentroomtemperature Lock Mode Indicator ................... Indicatesifthethermostatislocked Set Temperature.......................... Displaysthecurrentsetpointtemperature Humidity Indicator (6400 only).... Indicateswhenthereisacallforhumidity Fan Indicator................................ Indicateswhenthesystemfanisrunning Service Indicators ...................... Displaysvariousservice/maintenanceinformation Time of Day ................................. Displaysthecurrenttimeofday Program Event Indicator.............. Displaystheprogramevent Day of the Week........................... Displaysthecurrentdayoftheweek System Status Indicator ............. Displaysinformationaboutthestatusofthesystem Hold Mode Indicator ................... IndicatesifthethermostatisinHOLDmode Low Battery Indicator.................. Indicateswhenthebatteriesneedtobereplaced

Quick Reference Instructions...... Storedinslotlocatedattopofthermostat SpeedBar® .................................. Increasesordecreasessettings(time,temperature,etc.) Reset Button ............................... Resetscurrenttime,programandusersettings Installer Clear Button .................. Locatedonbackofthermostatbody–clearsallsettings Battery Compartment ................. Locatedinthebackofthermostat

3 Quick Reference

Instructions

1

2

3

4

5 6

15

8

7

9

14

10

11

1213

1

23

4

5

6

78

9

10

11

12

Thermostat Display

13

14

15

Thermostat

Page 9: Installer Guide -   - Intro | Braeburn Systems

9 Installer Guide

Thermostat TouchPadsTM

NOTE: Thermostat TouchPads are located on the left, right and bottom portions of the display screen. They are the “touch sensitive” segments used to adjust your thermostat. Depending on the equipment installed, all touch pads may not show.

SYSTEM SelectsAUTO(Heat/Cool),COOL,OFFHEATorEMER(EmergencyHeat)FAN SelectsAUTO,ON,CIRC(Circulation)andPROG(Program)fanmodesPROG Selectsprogrammingmodeorpressfor3secondstoselectSpeedSetTMmodeHOLD Enters/ExitstheHOLDmode(programbypass)DAY/TIME SetsthecurrenttimeanddayoftheweekBACK MovesbackinsettingandprogrammingmodesNEXT MovesforwardinsettingandprogrammingmodesRETURN ReturnstonormalmodefromprogramorsettingsmodesOUTDOOR DisplaystheoutdoortemperatureifaBraeburn®outdoorsensorisinstalledHUMIDITY Displaysoradjustthecurrenthumiditylevel(6400only)CONFIG EnterstheUserandInstallersettingsmodesCLEAN Entersabriefscreencleaningmode

RESETRESET

Page 10: Installer Guide -   - Intro | Braeburn Systems

TheInstallerSettingsmustbeproperlyconfiguredinorderforthisthermostattooperatecorrectly.TheInstallerSettingsaremenudriven.Theportionofthesesettingsthatdonotapplytoyoursetupwillbeskipped.Thesesettingsareindicatedbelowwithcomments.Moredetailoneachsettingfollowsthistable.

Installer Guide 10

1. TouchandholddowntheSYSTEMandCONFIGTouchPads™for3seconds.2. Releasebothbuttonsandthefirstinstallersettingwillbedisplayed.3. ChangesettingsasrequiredusingtheUPorDOWNportionoftheSpeedBar®.4. TouchNEXTorBACKtomovetothenextorprevioussetting,touchRETURNtoexit.

NOTE: Shaded areas below do not apply to the 6100.

No. Installer Setting Factory Setting Comments (Notes follow this table) Default Options (More information follows this table)

1 Residentialor RES RES SelectforResidentialprofile orCommercialProfile COMM SelectforCommercialprofile

2 ProgrammingMode 7 PROG 7 PROG Selectfor7dayprogrammingmode [note 1] 52 PROG Selectfor5-2dayprogrammingmode NO PROG Selectfornon-programmablemode

3 ClockFormat 12 HR 12 HR Selectfor12hourclock 24 HR Selectfor24hourclock

4 TemperatureScale F DEG F DEG SelectforFahrenheitdisplay C DEG SelectforCelsiusdisplay

5 AutoChangeover oF AUTO oF AUTO DisablesAutoChangeovermode ON AUTO EnablesAutoChangeovermode 11CONV Selectfor1H/1CConventionalsystem 22CONV Selectfor2H/2CConventionalsystem 32CONV Selectfor3H/2CConventionalsystem

6 SystemType 11CONV 11HP Selectfor1H/1CHeatPumpsystem 22HP Selectfor2H/2CHeatPumpsystem 32HP Selectfor3H/2CHeatPumpsystem 42HP Selectfor4H/2CHeatPumpsystem

7 1stStageDifferential 0.5 DIF1 0.5, 1.0or Selecta1ststagetemperaturedifferentialof.5°, 2.0 DIF1 1°or2°F(.25°,.5°or2°C)

8 2ndStageDifferential 2.0 DIF2 1.0, 2.0, 3.0, Selecta2ndstagetemperaturedifferentialof1°, [note 2] 4.0, 5.0or 2°,3°,4°,5°or6°F(.5°,1°,1.5°,2°,2.5°or3°C) 6.0 DIF29 3rdStageDifferential 2.0 DIF3 1.0, 2.0, 3.0, Selecta3rdstagetemperaturedifferentialof1°,2°, [note 2] 4.0, 5.0or 3°,4°,5°or6°F(.5°,1°,1.5°,2°,2.5°or3°C) 6.0 DIF3 10 4thStageDifferential 2.0 DIF4 1.0, 2.0, 3.0, Selecta4thstagetemperaturedifferentialof1˚, [note 2] 4.0, 5.0or 2°,3°,4°,5°or6°F(.5°,1°,1.5°,2°,2.5°or3°C) 6.0 DIF4

4 Installer Settings

Page 11: Installer Guide -   - Intro | Braeburn Systems

11 Installer Guide

No. Installer Setting Factory Setting Comments (Notes follow this table) Default Options (More information follows this table)

11 1stStageFanControl HG FAN 1 HG FAN 1 Selectfor1ststageGasheating [note 3] HE FAN 1 Selectfor1ststageElectricheating

12 EmergencyHeat] HE EMER HE EMER SelectforElectricEmergencyHeat FanControl[note 4] HG EMER SelectforGasEmergencyHeat

13 ReversingValve REVO REVO SelectforcoolactiveReversingValve(Oterminal) (O/BTerminal)[note 5] REVB SelectforheatactiveReversingValve(Bterminal)

14 FossilFuel AE AUX AE AUX SelectforElectricAuxiliaryheat(withcompressor) BackupHeat[note 4] AG AUX SelectforGasAuxiliaryheat(withoutcompressor)

15 CompressorPowerOutage oF CPOP oF CPOP DisablesPowerOutageLockoutDelay Protection [notes 3, 6] on CPOP EnablesPowerOutageLockoutDelay

16 ACPowerInterrupt AC oF MONR AC oF MONR DisablesACPowerInterruptWarning Warning[note 6] AC on MONR EnablesACPowerInterruptWarning

17 CompressorShort 5 CSCP 5, 4, 3, 2or Selectacompressorshortcycleprotectiondelayof5, CycleProtection 0 CSCP 4,3,2or0minutes

18 ResidualCooling 60 FAN 90, 60, 30 SelectaResidualCoolingFanDelayof90,60, FanDelay or0 FAN 30or0seconds.

19 CirculatingFanLock oF CIRC oF CIRC DisablesCirculatingFanLockmode on CIRC EnablesCirculatingFanLockmode

20 AdaptiveRecovery oF REC oF REC DisablesAdaptive(early)Recoverymode Mode(ARM™) [note 7] on REC EnablesAdaptive(early)Recoverymode

21 IndoorRemoteSensor I SENS I SENS Temperatureissensedfromthermostatonly. Control*[note 8] E SENS Temperatureissensedfromremotesensoronly. A SENS Temperatureiscombinedwiththethermostatand theremotesensor.

22 LockoutSecurityLevel 2 LOCK 2 LOCK Iflocked–Completelockoutisenabled 1 LOCK Iflocked–Partiallockoutisenabled(SpeedBar®is stillfunctional)

23 Humidification OFF OFF DisablesHumidification (6400Only) DEP EnablesDependantHumidification IND EnablesIndependentHumidification

24 AutoHumiditySet AUTO AUTO Enablesautomatichumiditycontrolbasedon PointLimit[notes 9, 11] outdoortemperature. (6400Only) MAN Enablesmanualhumiditycontrolfromthermostat.

25 Dehumidification OFF OFF DisablesDehumidification (6400Only) ON EnablesDehumidification

26 AutoChangeover 3 BAND 2, 3, 4or5 SelectaDeadBandof2°,3°,4°or5˚F DeadBand[note 10] BAND (1°,2°or3°C)forAutoChangeovermode.

27 CompressorBalance NO BALC NO BALC DisablesBalancePoints Point[notes 4, 11] 15-50 BALC SelectaCompressorBalancePointof15°-50°F (-9°-10°C)

28 AuxiliaryHeatBalance NO BALA NO BALA DisablesBalancePoints Point[notes 4, 11] 70-40 BALA SelectaAuxiliaryHeatBalancePointof70°-40°F (21°-4°C)

29 OutsideAirIntake OR NONE OR NONE DisablesOutsideAirIntakeoption (ATerminal)[note 12] OR ECON EnablesOutsideAirIntake(EconomizerMode) OR TOD EnablesOutsideAirIntake(TimeofDayMode)

30 HeatSetPointUpperLimit 90LIM 90-60 LIM SelectaHeatSetPointUpperLimitof90°-60°F(32°-10°C)

31 CoolSetPointLowerLimit 45LIM 45-80 LIM SelectaCoolSetPointLowerLimitof45°-80°F(7°-27°C)

*WhenaBraeburn®outdoorsensorisconnected,thethermostatautomaticallyrecognizesit.

NOTE: Additional options such as Service Monitors, Setting the lock code, audible tone, etc. are located in the User Settings – See User manual for information on setting these options.

Page 12: Installer Guide -   - Intro | Braeburn Systems

Installer Guide 12

NOTES - Installer Settings

1 OnlyavailableifResidentialprofilewasselectedinoption1.2 Onlyavailableifa2,3or4stagesystemtypewasselectedinoption6.3 OnlyavailableifaConventionalsystemwasselectedinoption6.4 Onlyavailableifa2,3or4stageHeatPumpsystemwasselectedinoption6.5 OnlyavailableifaHeatPumpsystemwasselectedinoption6.6 Onlyavailableifthe24VoltACcommonwireisconnectedtotheCterminal.7 Onlyavailableifaprogrammableprofilewasselectedinoption2.8 OnlyavailableifaBraeburn®indoorremotesensorwasconnected.9 Onlyavailableifhumidificationwasenabledinoption23.10 Onlyavailableifautochangeoverwasenabledinoption5.11 OnlyavailableifaBraeburnoutdoorsensorwasconnected.12 OnlyavailableifCommercialprofilewasselectedinoption1.

Detailed Explanation of Installer Settings (also see NOTES above):

1 Profile–Selectsaresidential(RES)orcommercial(COMM)profile.Ifresidentialisselected,4programming eventsperdayareavailable.Ifcommercialisselected,2event,7dayprogrammingisavailable.

2 Programming Mode [note 1]–Selectstheprogrammingmode,eitherfull7dayor5-2day(weekday/ weekend)programmingornon-programmable.

3 Clock Type–Selectseithera12houror24hourclock.

4 Temperature Scale–Selectsatemperaturescaleofeither°For°C.

5 Auto Changeover–Selectsautochangeoveronoroff.Whenautochangeovermodeisenabledand selected,thesystemautomaticallyswitchesbetweenheatingandcoolingmodes. NOTE: Also see “Auto Changeover Dead Band” in option 26.

6 System Type–Selectsthesystemtypeforyourinstallation.NOTE: Changes made to this option will reset options 7 through 15 back to their default values dependant on the system type.

7 1st Stage Differential–Selectsa1ststagetemperaturedifferential.

8 2nd Stage Differential [note 2]–Selectsa2ndstagetemperaturedifferential.

9 3rd Stage Differential [note 2]–Selectsa3rdstagetemperaturedifferential.

10 4th Stage Differential [note 2]–Selectsa4thstagetemperaturedifferential.

11 1st Stage Fan Control [note 3]–Selectsa1ststagefancontrolofeithergasorelectricheat.

12 Emergency Heat Fan Control [note 4]–Selectsemergencyheatfancontrolofeithergasorelectricheat.

13 Reversing Valve [Note 5]–SelectstheoutputstateoftheO/Bterminal.SelectOforthisterminaltobe activeinthecoolmodeorselectBforthisterminaltobeactiveintheheatmode.

14 Auxiliary Fossil Fuel Heat Pump Control [note 4]–Whensettoelectric(AEAUX),boththecompressor (1ststage)andauxiliarystage(s)willrunwhenacallforauxiliaryheatismade.Whensettogas(AGAUX), thecompressorstage(s)willbelockedoutoneminuteafteracallforauxiliaryheat.NOTE: This option can be overridden if setting an auxiliary heat balance point in Option 28.

15 Compressor Power Outage Protection [notes 3, 6]–Selectspoweroutageprotectiononoroff.When enabled,thisthermostatwillprovidecoldweathercompressorprotectionbylockingoutthecompressor stage(s)ofheatingforaperiodoftimeafterapoweroutagegreaterthan60minutes.

Page 13: Installer Guide -   - Intro | Braeburn Systems

13 Installer Guide

16 AC Power Interrupt Warning [note 6]–Whenenabled,thethermostatwilldisplayanoutagewarning whenACpowertothethermostatislost.

17 Short Cycle Protection–Selectsthenumberofminutesthecoolingcompressorwillbelockedoutafter turningoff.Thisshortcycleprotectionisalsoactiveintheheatmodeifaheatpumpsystemwasselectedin Option6.

18 Residual Cooling Fan Delay–Selectsadelayforthesystemfanafterthecoolingcompressorhasturned off.Thisdelaywillhelpremovetheremainingcoolairoutoftheductworkprovidingadditionalefficiency.

19 Circulating Fan Lock–Whenenabled,theonlyuserfanoptionsavailableareONandCIRC(Circulation). TheAUTOoptionisnotavailablewiththisoptionenabled.

20 Adaptive Recovery Mode (early recovery) [note 7]–EnablesordisablestheARMTM(adaptiverecovery mode)feature.DuringARM,roomtemperatureisrecoveredbyturningontheheatingorcoolingbeforethe endofthesetbackperiod.Thesetpointtemperatureischangedtothatoftheupcomingprogramtemperature.

21 Indoor Remote Sensor Control [note 8]–IfaBraeburn®indoorremotesensorisconnectedduring installation,thethermostatwillautomaticallydetectthesensor.Whenanindoorsensorisdetected,youmay selectbetweenthermostatonly(ISENS),remotesensoronly(ESENS)orcombiningthethermostatandthe remotesensor(ASENS).NOTE: This option does not apply to a Braeburn outdoor sensor. When an outdoor sensor is connected the thermostat automatically recognizes it and no further configuration is necessary.

22 Lockout Security Level–Selectsthelevelofkeypadlockoutwhenthethermostatislocked.Level2locks theentirethermostat(includingthefrontresetbutton).Level1lockseverythingexcepttheSpeedBar® allowingforupanddowntemperatureadjustment.NOTE: The lock code is set in the User Settings mode (see User Manual).

23 Humidification Mode (6400 only)–Selectsbetweendisablinghumidification(OFF),dependantcontrol (DEP)orindependentcontrol(IND).TheDEPsettingcontrolshumidificationonlyduringacallforheating. TheINDsettingallowshumidificationoutputintheheatmode,butdoesnotrequireacallforheating. NOTE: It is recommended that the IND setting only be used with systems designed for low air temperature humidification such as steam humidification. Always ensure the heat exchanger or other system parts are not exposed to excess water from condensation or other sources. When there is any doubt, use the OFF or DEP setting.

24 Auto Humidity Set Point Limit (6400 only) [notes 9, 11]–Selectbetweenturningtheautomatichumidity setpointlimittoauto(AUTO)ormanual(MAN).WhenAUTOisselected,humiditycontrolisprovidedauto- maticallybasedontheoutdoortemperature.SelectingMANallowsyoutomanuallycontrolthelevel ofhumidity.

25 Dehumidification (6400 only)–Selectbetweenenabling(ON)anddisabling(OFF)dehumidificationcontrol (Dterminal).Forusewithadehumidifier.

26 Auto Changeover Dead Band [note 10]–Whenautochangeovermodeisenabledinoption5and selected,thesystemautomaticallyswitchesbetweenheatingandcoolingwhentheroomtemperature meetsthenormalcriteriaforeitheraheatingorcoolingcall.Thereisaforcedseparation(deadband) betweentheheatingandcoolingsetpointssothatthesystemsdonotworkagainsteachother.This optionselectstheamountofthisdeadbandindegreeswiththedefaultbeing3°F.

27 Compressor Balance Point [notes 4, 11]–Locksouttheuseofthecompressorheatstagewhenthe outsideairtemperatureislessthantheselectedsettingof15°Fto50°F(-9°Cto10°C)

28 Auxiliary Heat Balance Point [notes 4, 11]–Locksouttheuseoftheauxiliaryheatstagewhenthe outsideairtemperatureexceedstheselectedsettingof70°Fto40°F(21°Cto4°C).NOTE: This balance point overrides the fossil fuel compressor lockout in option 14. If this option is set to gas and the outdoor temperature is over the auxiliary balance point, the compressor will remain on during a call for auxiliary heat.

Page 14: Installer Guide -   - Intro | Braeburn Systems

Installer Guide 14

29 Outside Air Intake [note 12]–Selectseconomizercontroloptions.Selectbetweendisabled(NONE), economizermode(ECON)andtimeofday(TOD)mode.

Time Step / Override Cooling Call

Occupied YES or NO ON ON OFF

YES ON OFF OFF

NO OFF OFF OFF

Override YES or NO ON ON OFF

External Air Output (A)

Economizer Time of Disabled Mode Day Mode

Time Step / Override Heating Call

Occupied YES or NO ON ON OFF

YES OFF OFF OFF

NO OFF OFF OFF

Override YES or NO ON ON OFF

External Air Output (A)

Economizer Time of Disabled Mode Day Mode

Unoccupied

Unoccupied

30 Heat Set Point Upper Limit–Selectstheheatingsetpointupperadjustmentlimit.

31 Cool Set Point Lower Limit–Selectsthecoolingsetpointloweradjustmentlimit.

Page 15: Installer Guide -   - Intro | Braeburn Systems

15 Installer Guide

Warning Read Before Testing

• Donotshort(orjumper)acrossterminalsonthegasvalveorattheheatingorcoolingsystemcontrolboard totestthethermostatinstallation.Thiscoulddamagethethermostatandvoidthewarranty.

• DonotselecttheCOOLmodeofoperationiftheoutsidetemperatureisbelow50ºF(10ºC).Thiscould possiblydamagethecontrolledcoolingsystemandmaycausepersonalinjury.

• Thisthermostatincludesanautomaticcompressorprotectionfeaturetoavoidpotentialdamagetothe compressorfromshortcycling.Whentestingthesystem,makesuretotakethisdelayintoaccount.

NOTE: The compressor delay can be bypassed by pressing the reset button on the front of the thermostat. All user settings will be returned to factory default, however all Installer settings will remain as originally programmed in section 4. 1 TouchtheSYSTEMTouchPad™untilthethermostatisinHEATmode.2 UsingtheSpeedBar®raisethesettemperatureaminimumof3degreesabovethecurrentroom temperature.Thesystemshouldstartwithinafewseconds.Withagasheatingsystem,thefanmay notstartrightaway.3 TouchSYSTEMuntilthethermostatisintheOFFmode.Allowtheheatingsystemtofullyshutdown.4 TouchSYSTEMuntilthethermostatisintheCOOLmode.5 UsingtheSpeedBarlowerthesettemperatureaminimumof3degreesbelowthecurrentroom temperature.Thesystemshouldstartwithinafewseconds(unlesscompressorshortcycleprotection isactive–Seenoteabove).6 TouchSYSTEMuntilthethermostatisintheOFFmode.Allowthecoolingsystemtofullyshutdown.7 TouchFANuntilthethermostatisinFANONmode.Thesystemfanshouldstartwithinafewseconds.8 TouchFANuntilthethermostatisinFANAUTOmode.Allowthesystemfantoturnoff.9 Ifthethermostatiscontrollingauxiliaryequipmentsuchasahumidifier(6400only),economizer,etc., adjustthethermostatsettingstotestthesedevices.

5 System Testing

Page 16: Installer Guide -   - Intro | Braeburn Systems

5 YEAR WARRANT YLIMITED

Limited Warranty

BraeburnSystemsLLCwarrantseachnewBraeburnthermostatagainstanydefectsthatareduetofaultymaterialorworkmanshipforaperiodoffiveyearsaftertheoriginaldateofpurchasebyaprofessionalservicetechnician.Thiswarrantyandourliabilitydoesnotapplytobatteries,nordoesitincludedamagetomerchandiseorthethermostatresulting fromaccident, alteration, neglect,misuse, improper installation or any other failure to followBraeburninstallationandoperatinginstructions.

BraeburnSystemsLLCagreestorepairorreplaceatitsoptionanyBraeburnthermostatunderwarrantyprovideditisreturnedpostageprepaidtoourwarrantyfacilityinapaddedcartonwithinthewarrantyperiod,withproofoftheoriginaldateofpurchaseandabriefdescriptionofthemalfunction.Thislimitedwarrantydoesnotincludethecostofremovalorre-installation.

Thiswarrantygivesyouspecific legal rightsandyoumayalsohaveotherrights thatvary fromstate tostateorprovince to province.Answers to any questions regarding our limitedwarrantymay be obtained bywriting ourcorporateoffices.

WARRANTYFACILITY: BraeburnSystemsLLC Attn:WarrantyDepartment 2215CornellAvenue Montgomery,IL60538

Store this manual for future reference

®

Page 17: Installer Guide -   - Intro | Braeburn Systems

Notes

Page 18: Installer Guide -   - Intro | Braeburn Systems

BraeburnSystemsLLC2215CornellAvenue•Montgomery,IL60538TechnicalAssistance:www.braeburnonline.comCallustoll-free:866-268-5599(U.S.)630-844-1968(OutsidetheU.S.)

©2011BraeburnSystemsLLC•AllRightsReserved•PatentsPending•MadeinChina•6134-100-003

®