FIRESTOP SUBMITTAL PACKAGE - Acousti...

21
FIRESTOP SUBMITTAL PACKAGE Project: Date: Submitted by: 210 Evans Way Somerville, NJ 08876 (800) 992-1180 (908) 526-8000 Fax (908) 526-9623 www.stifirestop.com Perimeter Fire Containment Systems

Transcript of FIRESTOP SUBMITTAL PACKAGE - Acousti...

Page 1: FIRESTOP SUBMITTAL PACKAGE - Acousti Firestopacoustifirestop.com/wp-content/uploads/2013/12/Perimeter-Fire... · SpecSeal® Series SSS Intumescent Sealant SpecSeal® Series LCI ...

FIRESTOP SUBMITTAL PACKAGE

Project:

Date:

Submitted by:

210 Evans Way • Somerville, NJ 08876 • (800) 992-1180 • (908) 526-8000 • Fax (908) 526-9623

www.stifirestop.com

Perimeter Fire Containment Systems

Page 2: FIRESTOP SUBMITTAL PACKAGE - Acousti Firestopacoustifirestop.com/wp-content/uploads/2013/12/Perimeter-Fire... · SpecSeal® Series SSS Intumescent Sealant SpecSeal® Series LCI ...

Certificate of Conformance • Technical Service 1-800-992-1180 • www.stifirestop.com

SpecSeal® Series SSS Intumescent Sealant SpecSeal® Series LCI Intumescent Sealant SpecSeal® Series LC Firestop Sealant

SpecSeal® Series ES Elastomeric Sealant SpecSeal® Series SIL300 Silicone Sealant SpecSeal® Series SIL300SL Silicone Sealant

Pensil® PEN300 Silicone Sealant Pensil® PEN300SL Silicone Sealant Pensil® PEN200 Silicone Foam

BlazeStop™ WF300 Firestop Caulk SpecSeal® Series AS200 Elastomeric Spray SpecSeal® Series FT Fast Tack™ Firestop Spray

SpecSeal® Series SSP Putty & Putty Pads SpecSeal® Series EP PowerShield™ Box Insert SpecSeal® Series SSM Firestop Mortar

SpecSeal® Series SSB Firestop Pillows SpecSeal® Series CS Composite Sheet SpecSeal® Series SSW Wrap Strips

SpecSeal® Series LCC Firestop Collars SpecSeal® Series SSC Firestop Collars SpecSeal® Series RTC Firestop Collars

SpecSeal® Series FP Firestop Plugs SpecSeal® Series CD Cast-In Firestop Devices FyreFlange® Firestop Angle

EZ-Path® Series 22 EZ-Path® Series 33 EZ-Path® Series 44 or 44+

Ready® Sleeve Ready® Sleeve Split EZ-Path® Firestop Grommet

SpecSeal® Series SSAMW Mineral Wool SpecSeal® SpeedFlex® Fire Rated Joint Profile SpecSeal® Closet Flange Firestop Gasket

SpecSeal® Series CS105 Cable Spray SpecSeal® SpeedFlex® Track Top Gasket

Description:

SpecSeal® Firestop Products; Pensil® Silicone Sealants; EZ-Path® Fire Rated Pathways; Ready® Sleeve Firestop Sleeves; STI Firestop Products

Included Products:

These products are tested to one or more of the following standards:

• ASTM E814 (ANSI/UL1479) Standard Test Method for Fire Tests of Penetration Firestop Systems

• ASTM E1966 (ANSI/UL2079) Standard Test Method for Fire-Resistive Joint Systems

• ASTM E119 (ANSI/UL263) Standard Test Methods for Fire Tests of Building Construction and Materials

• ASTM E2307 Standard Test Method for Determining Fire Resistance of Perimeter Fire Barrier Systems Using Intermediate Scale, Multi-Story Test Apparatus

• ASTM E1399 Standard Test Method for Cyclic Movement and Measuring the Minimum and Maximum Joint Widths of Architectural Joint Systems

• ASTM E84 (ANSI/UL723) Standard Test Method for Surface Burning Characteristics of Building Materials

• CAN/ULC S115 Standard Method of Fire Tests of Firestop Systems

• CAN/ULC S101 Standard Methods of Fire Endurance Tests of Building Construction and Materials

Chemical Content Statement:

No asbestos, PCB’s, lead, or water-soluble intumescent ingredients are used or contained in these products.

Paul M. JankowskiQuality Control Manager

James P. Stahl Jr., CFPSVice President of Engineering

GENERAL CERTIFICATE OF CONFORMANCEJUNE 2013

Page 3: FIRESTOP SUBMITTAL PACKAGE - Acousti Firestopacoustifirestop.com/wp-content/uploads/2013/12/Perimeter-Fire... · SpecSeal® Series SSS Intumescent Sealant SpecSeal® Series LCI ...

F Rating - 2 HrT Rating - 1/2 Hr

Linear Opening Width - 1 In. MaxL Rating At 400°F - Less Than 1 CFM/Lin Ft

1. Floor Assembly - Min 4-1/2 in. (114 mm) thick reinforced lightweight or normal weight (100-150 pcf or 1600-2400 kg/m3)structural concrete slab.

2. Curtain Wall Assembly - The curtain wall assembly shall incorporate the following construction features:A. Steel Floor and Ceiling Runners - Floor and ceiling runners of wall assembly shall consist of channels sized to

accommodate steel studs and formed from min 25 gauge (min 0.025 in. or 0.64 mm thick) galv steel. Steel runnerchannels installed to extend max 1 in. (25 mm) beyond edge of slab and secured to slab with steel masonry anchorsspaced max 16 in. (406 mm) OC.

B. Steel Studs - C-shaped studs formed from min 25 gauge (min 0.025 in. or 0.64 mm thick) galv steel. The steel studsshall be min 6 in. (152 mm) wide by 1-1/4 in. (31 mm) deep with 5/16 in. (8 mm) wide stiffening flanges. Studsspaced max 16 in. (406 mm) OC and fastened to steel runner channels with steel screws or welds.

B1. King Studs - (Optional, Not Shown) - Where required, a king stud may be substituted for Item 2b. King studs toconsist of two min 6 in. (152 mm) wide by 1-1/4 in. (31 mm) deep C-shaped studs formed from min 25 gauge (min0.025 in. or 0.64 mm thick) galv steel secured together by welds.

C. Gypsum Board* - One layer of nom 5/8 in. (16 mm) thick, 48 in. (1.2 m) wide gypsum sheathing installed to coverentire exterior surface of wall. Sheathing applied with joints centered over studs and secured to steel studs with min 1in. (25 mm) long bugle head steel screws spaced max 8 in. (203 mm) OC along the edges and max 12 in. (305 mm)OC in the field of each sheet.See Gypsum Board (CKNX) category for names of Classified Companies and product types.

C1. Cementitious Backer Units* - As an alternate to the gypsum sheathing (Item 2C), nom 1/2 in. or 5/8 in. (13 or 16mm) thick square-edge boards attached to studs with 1-1/4 in. (31 mm) long corrosion resistant self-tappingwafer-head steel screws spaced 6 in. (152 mm) OC. Joints covered with glass fiber mesh tape.UNITED STATES GYPSUM CO - Type DCB

R Created or Revised:Reproduced courtesy of Underwriters Laboratories, Inc.

PAGE OF(800)992-1180 (908)526-8000 FAX (908)231-8415 E-Mail:[email protected] Website:www.stifirestop.comFebruary 28, 2014

1 2

Ì86CWSÇ*#ÈAOÇ"<.[Î

CW-S-0003

3B

2D

2A

2E

2G

2B1

2D

2E

2F

3A

2C

Page 4: FIRESTOP SUBMITTAL PACKAGE - Acousti Firestopacoustifirestop.com/wp-content/uploads/2013/12/Perimeter-Fire... · SpecSeal® Series SSS Intumescent Sealant SpecSeal® Series LCI ...

D. Batts and Blankets* - Any glass fiber insulation bearing the UL Classification Marking as to fire resistance orsurface burning characteristics, of a width and thickness to completely fill stud cavity. Insulation batts friction fit tocompletely fill all stud cavities of curtain wall above the top of the fill material (Item 3B) and below the formingmaterial (Item 3A).

See Batts and Blankets (BZJZ) category for names of manufacturers.

E. Gypsum Board* - One layer of nom 5/8 in. (16 mm) thick, 48 in. (1.2 m) wide gypsum board applied with jointscentered over studs. Gypsum board secured to steel studs on interior surface of curtain wall with min 1 in. (25 mm)long bugle head steel screws spaced max 8 in. (203 mm) OC along the edges and max 12 in. (305 mm) OC in thefield of each sheet. Gypsum board installed to cover interior surface of wall above the top of the fill material (Item 3C)for a min distance of 4-1/2 in. (114 mm).

See Gypsum Board (CKNX) category for names of Classified Companies and product types.

F. Framed Window - Metal-framed window with nom 1 in. (25 mm) thick (double pane) transparent heat-strengthenedor tempered glass panels. Sill of window to be min 4-1/2 in. (114 mm) above top of floor slab. Vertical separationbetween window punch-outs to be min 36 in. (914 mm). Top of window to be min 24 in. (610 mm) below bottom offloor slab.

G. Exterior Insulation and Finish System (EIFS) - Nom 2 in. (51 mm) thick extruded polystyrene Foamed Plastic*insulation bearing the UL Classification Marking, attached over sheathing and finished with coating system, orPortland cement or synthetic stucco systems, in accordance with manufacturer's instructions.

See Foamed Plastic (BRYX or CCVW) category for names of Classified companies.

H. Siding, Brick or Stucco - (Not Shown) - Aluminum siding, steel siding, brick veneer or stucco installed over gypsumsheathing or cementitious backer units and meeting the requirements of local code agencies. Brick veneer wallattached to studs with corrugated metal wall ties attached to each stud with steel screws.

I. Glass Fiber Reinforced Concrete (GFRC) Panels - (Not Shown) - Min 1/2 in. (13 mm) thick glass fiber reinforcedconcrete (GFRC) panels installed over gypsum sheathing or cementitious backer units and meeting the requirementsof local code agencies.

3. Safing System - The safing system shall incorporate the following construction features:A. Forming Material* - Nom 4 pcf (64 kg/m3) mineral wool batt insulation cut to a width nominally 1/2 in. (13 mm)

wider than width of stud cavity and the on-center spacing between the vertical studs. Forming material friction-fittedinto steel runner channel on top surface of floor to min 4 in. (102 mm) depth.

ROCKWOOL MALAYSIA SDN BHD - Safe

ROXUL INC - Safe

THERMAFIBER INC - SAF

B. Fill, Void or Cavity Material* - Spray - Min 1/8 in. (3.2 mm) wet thickness (min 1/16 in. or 1.6 mm dry thickness) offill material spray-applied atop mineral wool safing (Item 3A) with min 1/2 in. (13 mm) overlap onto sheathing, steelstuds, and concrete floor.

SPECIFIED TECHNOLOGIES INC - SpecSeal AS200 Elastomeric Spray or SpecSeal Fast Tack Spray

*Bearing the UL Classification Mark

R Created or Revised:Reproduced courtesy of Underwriters Laboratories, Inc.

PAGE OF(800)992-1180 (908)526-8000 FAX (908)231-8415 E-Mail:[email protected] Website:www.stifirestop.comFebruary 28, 2014

2 2CW-S-0003

Page 5: FIRESTOP SUBMITTAL PACKAGE - Acousti Firestopacoustifirestop.com/wp-content/uploads/2013/12/Perimeter-Fire... · SpecSeal® Series SSS Intumescent Sealant SpecSeal® Series LCI ...

R Created or Revised:Reproduced courtesy of Underwriters Laboratories, Inc.

PAGE OF(800)992-1180 (908)526-8000 FAX (908)231-8415 E-Mail:[email protected] Website:www.stifirestop.comFebruary 28, 2014

1 2

Ì79CWSÇ*3ÈAOÇ"<.yÎ

CW-S-1019

2G3B

2E

3A

2F

2E

2D2C

2B

1

2B

2H

2G

F Rating - 2 HrT Ratings - 0 and 1/2 Hr (See Item 2K)Linear Opening Width - 2-1/2 In. Max

L Rating At Ambient - Less Than 1 CFM/Lin FtL Rating At 400°F - Less Than 1 CFM/Lin Ft

1. Floor Assembly - Min 4-1/2 in. (114 mm) thick reinforced lightweight or normal weight (100-150 pcf or 1600-2400 kg/m3) structuralconcrete. Perimeter of floor assembly to be provided with min 3 by 3 by 1/4 in. (76 by 76 by 6 mm) thick cast-in-place structural steelangle for weld-attachment of mounting angles (Item 2A).

2. Curtain Wall Assembly - The curtain wall assembly shall incorporate the following construction features:A. Mounting Angles - (Not Shown) - Nom 3 in. (76 mm) long angles with one nom 3 in. (76 mm) leg for attachment to edge of

floor assembly and with one leg approx 2-1/2 to 3 in. (64 to 76 mm) longer than distance to interior face of steel studs. Anglesto be formed of min 1/8 in. (3.2 mm) thick steel. Angles welded to cast-in-place structural steel angle at edge of floor assembly(Item 1) on one side of each steel stud (Item 2B) at each floor level. Top edge of each mounting angle to be recessed 1/2 to 1in. (13 to 25 mm) below top surface of floor.

B. Steel Studs - C-shaped studs formed from min 0.059 in. (1.5 mm) thick galv steel. The steel studs shall be min 6 in. (152 mm)wide by 1-1/4 in. (31 mm) deep with 5/16 in. (8 mm) wide stiffening flanges and shall be assembled using runner channelsformed from min 0.059 in. (1.5 mm) thick galv steel. Studs spaced max 16 in. (406 mm) OC and welded, bolted or screwed tomounting angles (Item 2A) at each floor level. Interior face of studs to be max 2-1/2 in. (64 mm) from edge of floor assembly.Studs reinforced by means of nom 1-1/2 in. (38 mm) wide by 9/16 in. (14 mm) deep min 0.059 in. (1.5 mm) thick cold rolledsteel channels inserted through steel stud keyways on max 48 in. (1.2 m) centers and welded to steel studs.

B1. King Studs - (Optional, Not Shown) - Where required, a king stud may be substituted for Item 2B. King studs to consist of twomin 6 in. (152 mm) wide by 1-1/4 in. (31 mm) deep C-shaped studs formed from min 0.059 in. (1.5 mm) thick galv steel securedtogether by welds. See Item 3C.

C. Gypsum Board* - One layer of nom 5/8 in. (16 mm) thick, 48 in. (1.2 m) wide gypsum sheathing installed to cover entireexterior surface of wall. Sheathing applied with joints centered over studs and secured to steel studs with min 1 in. (25 mm)long bugle head steel screws spaced max 8 in. (204 mm) OC along the edges and max 12 in. (305 mm) OC in the field of eachsheet.See Gypsum Board (CKNX) category for names of Classified Companies and product types.

D. Cementitious Backer Units* - As an alternate to the gypsum sheathing (Item 2C), nom 1/2 in. or 5/8 in. (13 or 16 mm) thicksquare-edge boards attached to studs with 1-1/4 in. (31 mm) long corrosion resistant self-tapping wafer-head steel screwsspaced 6 in. (152 mm) OC. Joints covered with glass fiber mesh tape.UNITED STATES GYPSUM CO - Type DCB

Page 6: FIRESTOP SUBMITTAL PACKAGE - Acousti Firestopacoustifirestop.com/wp-content/uploads/2013/12/Perimeter-Fire... · SpecSeal® Series SSS Intumescent Sealant SpecSeal® Series LCI ...

R Created or Revised:Reproduced courtesy of Underwriters Laboratories, Inc.

PAGE OF(800)992-1180 (908)526-8000 FAX (908)231-8415 E-Mail:[email protected] Website:www.stifirestop.comFebruary 28, 2014

2 2CW-S-1019

E. Batts and Blankets* - Any glass fiber insulation bearing the UL Classification Marking as to fire resistance or surface burningcharacteristics, of a width and thickness to completely fill stud cavity. Insulation batts friction fit to completely fill all stud cavitiesof curtain wall above the top of the fill material (Item B) and below the forming material (Item 3A).

See Batts and Blankets (BZJZ) category for names of manufacturers.F. Gypsum Board* - One layer of nom 5/8 in. (16 mm) thick, 48 in. (1.2 m) wide gypsum board applied with joints centered over

studs. Gypsum board secured to steel studs on interior surface of curtain wall with min 1 in. (25 mm) long bugle head steelscrews spaced max 8 in. (204 mm) OC along the edges and max 12 in. (305 mm) OC in the field of each sheet. Gypsum boardinstalled to cover interior surface of wall above the top of the fill material (Item 3C) for a min distance of 6 in. (152 mm).Gypsum board is optional below floor assembly.

See Gypsum Board (CKNX) category for names of Classified Companies and product types.G. Framed Window - Metal-framed window with nom 1 in. (25 mm) thick (double pane) transparent heat-strengthened or

tempered glass panels. Sill of window to be min 6 in. (152 mm) above top of floor slab. Vertical separation between windowpunch-outs to be min 36 in. (914 mm). Top of window to be min 22-1/2 in. (572 mm) below bottom of floor slab.

H. Exterior Insulation and Finish System (EIFS) - Nom 2 in. (51 mm) thick extruded polystyrene Foamed Plastic* insulationbearing the UL Classification Marking, attached over sheathing and finished with coating system, or Portland cement orsynthetic stucco systems, in accordance with manufacturer's instructions.

See Foamed Plastic (BRYX or CCVW) category for names of Classified companies.I. Siding, Brick or Stucco - (Not Shown) - Aluminum siding, steel siding, brick veneer or stucco installed over gypsum sheathing

or cementitious backer units and meeting the requirements of local code agencies. Brick veneer wall attached to studs withcorrugated metal wall ties attached to each stud with steel screws.

J. Glass Fiber Reinforced Concrete (GFRC) Panels - (Not Shown) - Min 1/2 in. (13 mm) thick glass fiber reinforced concrete(GFRC) panels installed over gypsum sheathing or cementitious backer units and meeting the requirements of local codeagencies.

K. Through Penetrant - (Optional, Not Shown) - Nom 1 in. (25 mm) diam rigid Sch 5 (or heavier) steel pipe, Regular (or heaviercopper pipe, or Type M (or heavier) copper tube, steel conduit, steel electrical metallic tubing (EMT), flexible steel conduit, Sch40 PVC conduit, or max 3/C-10 AWG (or smaller) metal-clad cable may be installed within the stud cavity. The throughpenetrant shall be located approximately midway between studs and nominally centered within the depth of stud. A max of onethrough penetrant is permitted in an individual stud cavity. When through penetrant is installed in stud cavity, the hourly TRating of the perimeter fire containment system is 0 hr.

3. Safing System - The safing system shall incorporate the following construction features:A. Forming Material* - Nom 4 pcf (64 kg/m3) density mineral wool batt insulation. Batt sections to be cut to a min width of 4 in.

(102 mm) and stacked to a thickness which is 25 percent greater than the width of linear gap between the gypsum sheathingand the edge of the concrete floor to attain a min 20 percent compression in the thickness direction when installed. The formingmaterial is compressed and inserted cut-edge-first into linear gap between edge of floor slab and sheathing material such thatits top surface is flush with the top surface of the floor assembly. Length of batt to be equal to on-center spacing of steel studssuch that it is friction-fitted between studs and mounting angles without seams. Additional pieces of mineral wool batt to bestuffed inside the channel of each steel stud throughout the thickness of the forming material.

THERMAFIBER INC - SAF

B. Fill, Void or Cavity Material* - Spray - Min 1/8 in. (3.2 mm) wet thickness (min 1/16 in. or 1.6 mm dry thickness) of fill materialspray-applied over top of forming material and lapping min 1/2 in. (13 mm) onto the top surface of the floor and onto thegypsum sheathing and steel studs and optional through penetrant (Item 2K).

SPECIFIED TECHNOLOGIES INC - SpecSeal AS200 Elastomeric Spray or SpecSeal Fast Tack Spray

C. Fill, Void or Cavity Material* - Pillows - (Not Shown) - Where king studs (Item 2B1) are located, channel within stud to besealed with pillows. Max 9 in. long by 6 in. wide by 3 in. thick plastic covered intumescent pillows compressed and tightlypacked into channel at each floor line.

SPECIFIED TECHNOLOGIES INC - SpecSeal Firestop Pillows

*Bearing the UL Classification Mark

Page 7: FIRESTOP SUBMITTAL PACKAGE - Acousti Firestopacoustifirestop.com/wp-content/uploads/2013/12/Perimeter-Fire... · SpecSeal® Series SSS Intumescent Sealant SpecSeal® Series LCI ...

R Created or Revised:Reproduced courtesy of Underwriters Laboratories, Inc.

PAGE OF(800)992-1180 (908)526-8000 FAX (908)231-8415 E-Mail:[email protected] Website:www.stifirestop.comFebruary 28, 2014

1 2

Ì87CWDÇ*+ÈAOÇ"<.RÎ

CW-D-1011

2G3B

2E

3A

2F

2E

2D2C

2B

1

2B

2H

2G

F Rating - 2 HrT Rating -1/2 Hr

Linear Opening Width - 2-1/2 In. MaxClass II Movement Capabilities - 5% Vertical Shear

L Rating At Ambient - Less Than 1 CFM/Lin FtL Rating At 400°F - Less Than 1 CFM/Lin Ft

1. Floor Assembly - Min 4-1/2 in. (114 mm) thick reinforced lightweight or normal weight (100-150 pcf or 1600-2400 kg/m3)structural concrete. Perimeter of floor assembly to be provided with min 3 by 3 by 1/4 in. (76 by 76 by 6 mm) thick cast-in-placestructural steel angle for weld-attachment of mounting angles (Item 2A).

2. Curtain Wall Assembly - The curtain wall assembly shall incorporate the following construction features:A. Mounting Angles - (Not Shown) - Nom 3 in. (76 mm) long angles with one nom 3 in. (76 mm) leg for attachment to edge

of floor assembly and with one leg approx 2-1/2 to 3 in. (64 to 76 mm) longer than distance to interior face of steel studs.Angles to be formed of min 1/8 in. (3.2 mm) thick steel. Angles welded to cast-in-place structural steel angle at edge offloor assembly (Item 1) on one side of each steel stud (Item 2B) at each floor level. Top edge of each mounting angle to berecessed 1/2 to 1 in. (13 to 25 mm) below top surface of floor.

B. Steel Studs - C-shaped studs formed from min 0.059 in. (1.5 mm) thick galv steel. The steel studs shall be min 6 in. (152mm) wide by 1-1/4 in. (31 mm) deep with 5/16 in. (8 mm) wide stiffening flanges and shall be assembled using runnerchannels formed from min 0.059 in. (1.5 mm) thick galv steel. Studs spaced max 16 in. (406 mm) OC and welded, boltedor screwed to mounting angles (Item 2A) at each floor level. To allow for designed amount of movement, elongated holesmay be integrated into either the mounting angle (Item 2A) or the stud (Item 2B). Interior face of studs to be max 2-1/2 in.(64 mm) from edge of floor assembly. Studs reinforced by means of nom 1-1/2 in. (38 mm) wide by 9/16 in. (14 mm) deepmin 0.059 in. (1.5 mm) thick cold rolled steel channels inserted through steel stud keyways on max 48 in. (1.2 m) centersand welded to steel studs.

B1. King Studs - (Optional, Not Shown) - Where required, a king stud may be substituted for Item 2B. King studs to consist oftwo min 6 in. (152 mm) wide by 1-1/4 in. (31 mm) deep C-shaped studs formed from min 0.059 in. (1.5 mm) thick galvsteel secured together by welds. See Item 3C.

C. Gypsum Board* - One layer of nom 5/8 in. (16 mm) thick, 48 in. (1.2 m) wide gypsum sheathing installed to cover entireexterior surface of wall. Sheathing applied with joints centered over studs and secured to steel studs with min 1 in. (25mm) long bugle head steel screws spaced max 8 in. (204 mm) OC along the edges and max 12 in. (305 mm) OC in thefield of each sheet.See Gypsum Board (CKNX) category for names of Classified Companies and product types.

Page 8: FIRESTOP SUBMITTAL PACKAGE - Acousti Firestopacoustifirestop.com/wp-content/uploads/2013/12/Perimeter-Fire... · SpecSeal® Series SSS Intumescent Sealant SpecSeal® Series LCI ...

R Created or Revised:Reproduced courtesy of Underwriters Laboratories, Inc.

PAGE OF(800)992-1180 (908)526-8000 FAX (908)231-8415 E-Mail:[email protected] Website:www.stifirestop.comFebruary 28, 2014

2 2CW-D-1011

D. Cementitious Backer Units* - As an alternate to the gypsum sheathing (Item 2C), nom 1/2 in. or 5/8 in. (13 or 16 mm)thick square-edge boards attached to studs with 1-1/4 in. (31 mm) long corrosion resistant self-tapping wafer-head steelscrews spaced 6 in. (152 mm) OC. Joints covered with glass fiber mesh tape.

UNITED STATES GYPSUM CO - Type DCB

E. Batts and Blankets* - Any glass fiber insulation bearing the UL Classification Marking as to fire resistance or surfaceburning characteristics, of a width and thickness to completely fill stud cavity. Insulation batts friction fit to completely fill allstud cavities of curtain wall above the top of the fill material (Item B) and below the forming material (Item 3A).See Batts and Blankets (BZJZ) category for names of manufacturers.

F. Gypsum Board* - One layer of nom 5/8 in. (16 mm) thick, 48 in. (1.2 m) wide gypsum board applied with joints centeredover studs. Gypsum board secured to steel studs on interior surface of curtain wall with min 1 in. (25 mm) long bugle headsteel screws spaced max 8 in. (204 mm) OC along the edges and max 12 in. (305 mm) OC in the field of each sheet.Gypsum board installed to cover interior surface of wall above the top of the fill material (Item 3C) for a min distance of 6in. (152 mm). Gypsum board is optional below floor assembly.See Gypsum Board (CKNX) category for names of Classified Companies and product types.

G. Framed Window - Metal-framed window with nom 1 in. (25 mm) thick (double pane) transparent heat-strengthened ortempered glass panels. Sill of window to be min 6 in. (152 mm) above top of floor slab. Vertical separation betweenwindow punch-outs to be min 36 in. (914 mm). Top of window to be min 22-1/2 in. (572 mm) below bottom of floor slab.

H. Exterior Insulation and Finish System (EIFS) - Nom 2 in. (51 mm) thick extruded polystyrene Foamed Plastic* insulationbearing the UL Classification Marking, attached over sheathing and finished with coating system, or Portland cement orsynthetic stucco systems, in accordance with manufacturer's instructions.See Foamed Plastic (BRYX or CCVW) category for names of Classified companies.

I. Siding, Brick or Stucco - (Not Shown) - Aluminum siding, steel siding, brick veneer or stucco installed over gypsumsheathing or cementitious backer units and meeting the requirements of local code agencies. Brick veneer wall attached tostuds with corrugated metal wall ties attached to each stud with steel screws.

J. Glass Fiber Reinforced Concrete (GFRC) Panels - (Not Shown) - Min 1/2 in. (13 mm) thick glass fiber reinforcedconcrete (GFRC) panels installed over gypsum sheathing or cementitious backer units and meeting the requirements oflocal code agencies.

3. Safing System - Max separation between edge of floor assembly and face of framing members is 2-1/2 in. (64 mm). Thesafing system is designed to accommodate vertical shear movement up to a max of 5 percent of its installed width. The safingsystem shall incorporate the following construction features:A. Forming Material* - Nom 4 pcf (64 kg/m3) density mineral wool batt insulation. Batt sections to be cut to a min width of 4

in. (102 mm) and stacked to a thickness which is 25 percent greater than the width of linear gap between the gypsumsheathing and the edge of the concrete floor to attain a min 20 percent compression in the thickness direction wheninstalled. The forming material is compressed and inserted cut-edge-first into linear gap between edge of floor slab andsheathing material such that its top surface is flush with the top surface of the floor assembly. Length of batt to be equal toon-center spacing of steel studs such that it is friction-fitted between studs and mounting angles without seams. Additionalpieces of mineral wool batt to be stuffed inside the channel of each steel stud throughout the thickness of the formingmaterial.

THERMAFIBER INC - SAF

B. Fill, Void or Cavity Material* - Spray - Min 1/8 in. (3.2 mm) wet thickness (min 1/16 in. or 1.6 mm dry thickness) of fillmaterial spray-applied over top of forming material and lapping min 1/2 in. (13 mm) onto the top surface of the floor andonto the gypsum sheathing and steel studs.

SPECIFIED TECHNOLOGIES INC - SpecSeal AS200 Elastomeric Spray or SpecSeal Fast Tack Spray

C. Fill, Void or Cavity Material* - Pillows - (Not Shown) - Where king studs (Item 2B1) are located, channel within stud tobe sealed with pillows. Max 9 in. long by 6 in. wide by 3 in. thick plastic covered intumescent pillows compressed andtightly packed into channel at each floor line.

SPECIFIED TECHNOLOGIES INC - SpecSeal Firestop Pillows

*Bearing the UL Classification Mark

Page 9: FIRESTOP SUBMITTAL PACKAGE - Acousti Firestopacoustifirestop.com/wp-content/uploads/2013/12/Perimeter-Fire... · SpecSeal® Series SSS Intumescent Sealant SpecSeal® Series LCI ...

1Technical Service 1-800-992-1180www.stifirestop.com

SERIES AS200 ELASTOMERIC SPRAY

PRODUCT DATA SHEET

APPLICATIONSSpecSeal® Elastomeric Spray is designed primarily for

the protection of construction joints, curtain wall safing

gaps, and certain through-penetrations.

PRODUCT DESCRIPTIONSpecSeal® Series AS200 Elastomeric Spray is a non-halogenated latex-based, highly elastomeric coating designed to provide passive smoke and fire protection in construction joints.

SpecSeal® Series AS200 Elastomeric Spray is engineered to adhere to virtually all construction surfaces and may be applied using airless spray equipment or with a brush (ideally for, but not limited to, small applications or touch ups).

SpecSeal® Series AS200 Elastomeric Spray dries to form a flexible shield against the propagation of fire. Its premium latex binder system is totally resistant to water and will not re-emulsify after drying. SpecSeal® Series AS200 Elastomeric Spray contains no inorganic fibers, asbestos, solvents.

• Water-Based for easy installation and cleanup

• Non-halogenated.

• Thixotropic for high-build application.

• Auto Bonding. • Safe... no solvents! No asbestos!

• Flexible! • Water Resistant!• Low Abrasion for longer pump life and less maintenance.

• UL Classified.

• Tested with spray applied fire resistive materials (SFRM).

• Paintable

FEATURES

When applied to a wet film thickness of 1/8" (3.2 mm) over appropriate backing materials, SpecSeal® Series AS200 Elastomeric Spray has been successfully tested in one, two, three and four hour joints tested in accordance with ASTM E1966 (ANSI/UL2079) and CAN/ULCS115. This product has also been tested for use in Perimeter Fire Barrier Systems in accordance with ASTM E2307. Consult factory for individual system designs and application requirements.

LIMITATIONS: Use product as per manufacturer’s instructions. Use only in applications per the manufacturer’s tested and published designs or specific recommendations. End user must ultimately determine the suitability of the product and designs to his specific requirement and assumes responsibility for its use. PRODUCT CONTAINS WATER AND IS CONDUCTIVE UNTIL DRY. DO NOT APPLY IN THE PRESENCE OF EXPOSED OR ENERGIZED ELECTRICAL CONDUCTORS.

PERFORMANCE

PHYSICAL PROPERTIES

STI Product Data Sheet • Series AS200 Elastomeric Spray • FOD-5042-1292

PROPERTIES: SERIES AS SPRAYColor Pale Blue and Red

Odor Mild Latex

Specific Gravity 1.3

Solids Content by Weight

Solids Content by Volume

74%

66.4%

Flame Spread 0*

Smoke Developed 25*

Movement ±50%**

Coverage 12.8 sq ft/gal @ 1/8˝ (0.31 sq m/L @ 3.2 mm)

Viscosity 110,000 cps

pH 7.5

PROPERTIES: SERIES AS SPRAYSolvent Content None

Plasticizer None

In-Service Temp. ≤185° F (85° C)

Storage Temp. 40°F (4°C) - 95°F (35°C)

Drying Time Tack Free 2 Hours

Dry Through 24-48 HoursA

STC Rating 61

VOC ContentB 10 g/L

Shelf Life 18 Months

* Tested to ASTM E84 (UL723) @ 14% coverage.**500 Cycles per UL2079, AC30 (ICBO) and ASTM E1399A Dependent on temperature and humidity.BPer ASTM D3960 EPA Fed. Reference Method 24

FILL, VOID OR CAVITY MATERIALS FOR USE IN JOINT SYSTEMS & THROUGHPENETRATION FIRESTOP

SYSTEMS. SEE UL FIRE RESISTANCE DIRECTORY.

3L73

FBC™ System Compatible indicates that this product has been tested, and is monitored on an ongoing basis, to assure its chemical compatibility with FlowGuard Gold®, BlazeMaster® and Corzan® pipe and fittings. FBC, FlowGuard Gold, BlazeMaster and Corzan are licensed trademarks of The Lubrizol Corporation.

Page 10: FIRESTOP SUBMITTAL PACKAGE - Acousti Firestopacoustifirestop.com/wp-content/uploads/2013/12/Perimeter-Fire... · SpecSeal® Series SSS Intumescent Sealant SpecSeal® Series LCI ...

2 Technical Service 1-800-992-1180www.stifirestop.com

STI Product Data Sheet • Series AS200 Elastomeric Spray • FOD-5042-1292

FIG. 2: SLAB-EDGE SAFING GAP APPLICATIONS

UL System No. CW-S-2061F Rating – 2 Hr • T Rating – 1/4 HrLinear Opening Width - 8 In Max

L Rating At Ambient - Less than 1 CFM/Lin FtL Rating At 400o F - Less Than 1 CFM/Lin Ft

FIG. 1: METALLIC PIPE PENETRATIONS - CONCRETE/MASONRY FLOORS & WALLS

UL System No. C-AJ-1318F Rating – 2 Hr • T Rating – 0 Hr

Steel or Iron Pipe: <12", Copper Pipe: <6"Annulus: Point Contact to 2"

Forming Material: Nom 4 pcf mineral wool to 4" depthSpray Depth: 1/8" wet depth (+1/2" overlap)

UL System No. HW-D-0043Assembly Ratings - 1,2,3 and 4 Hr.Nominal Joint Widths - 1 and 2 In.

L Rating At Ambient - Less than 1 CFM/Lin Ft.L Rating At 400o F - Less Than 1 CFM/Lin Ft.Class II Movement Capabilities - 40 or 50%

Compression and extension.

FIG. 3: HEAD-OF-WALL APPLICATIONS

Page 11: FIRESTOP SUBMITTAL PACKAGE - Acousti Firestopacoustifirestop.com/wp-content/uploads/2013/12/Perimeter-Fire... · SpecSeal® Series SSS Intumescent Sealant SpecSeal® Series LCI ...

3Technical Service 1-800-992-1180www.stifirestop.com

STI Product Data Sheet • Series AS200 Elastomeric Spray • FOD-5042-1292

AVAILABILITY

MAINTENANCEInspection: Installations should be inspected periodically for subsequent damage. Following safety precautions listed below (See Precautionary Information) and pertinent installation guidelines, remove coating in damaged areas down to undamaged material. Reapply fresh coating material to original coating thickness.

TECHNICAL SERVICE

Specified Technologies Inc. provides toll free technical support to assist in product selection and appropriate installation design. UL Systems, Material Safety Data Sheets and other technical information is available at the Technical Library at www.stifirestop.com.

PRECAUTIONARY INFORMATION

Consult Material Safety Data Sheet for additional information on the safe handling and disposal of this material. Wash areas of skin contact with soap and water. Avoid contact with eyes. The use of an OSHA or NIOSH approved mask for dust and mist environment is recommended. Apply in areas with adequate ventilation.

SpecSeal® Series AS200 Elastomeric Spray is available worldwide from authorized distributors. Consult factory for the names and locations of the nearest sales representatives or distributors..

GENERAL: Areas to be protected must be clean and free of oil, loose dirt, rust or scale. Recommended storage temperatures range between40°F (4°C) and 95°F (35°C). Installation temperature shall be between 40˚F (4˚C) and 95˚F (35˚C). Although not a requirement, the optimal application temperature range is 60°F (16°C) to 90°F (32°C). When applying product at the lower end of the temperature range, warming the material to 70°F (21°C) will enhance drying characteristics. Drying time will vary according to prevailing temperature and humidity. Allow to thoroughly dry before exposure to moisture.

Consult appropriate manufacturer’s drawing for system design requirements. Forming or packing materials are required as an integral part of various system designs.

Coating may be applied by airless spray in a single pass up to 3/16" (4.8mm) wet coating depth. If applying by brush or spraying on vertical surfaces where coating appears to be prone to slumping, multiple coats or the application of a thin tack coat may be required. DO NOT ATTEMPT TO THIN PRODUCT BY ADDING WATER. When dry, may be painted using most non-solvent based paints.

INSTALLATION INSTRUCTIONS

SPECIFICATIONS

The fire protective joint coating shall be a water-based, non-halogenated elastomeric coating and shall contain no solvents, inorganic fibers, nor asbestos. The coating shall dry to form a flexible, moisture resistant film and shall adhere to all common construction surfaces. The coating shall provide up to 50 percent movement. The coating shall be thixotropic and shall be capable of being applied by brush or by airless spray. The approved coating shall be SpecSeal® Series AS200 Elastomeric Spray.

SPECIFIED DIVISIONS

DIV. 7 07 84 00 Through-Penetration Firestopping

DIV. 4 04 22 00 Concrete Unit Masonry

DIV. 7 07 21 00 Thermal Insulation

DIV. 8 08 44 00 Curtain Wall and Glazed Assemblies

Page 12: FIRESTOP SUBMITTAL PACKAGE - Acousti Firestopacoustifirestop.com/wp-content/uploads/2013/12/Perimeter-Fire... · SpecSeal® Series SSS Intumescent Sealant SpecSeal® Series LCI ...

4 Technical Service 1-800-992-1180www.stifirestop.com

STI Product Data Sheet • Series AS200 Elast Spray • FOD-5042 01/2012

Important Notice: All statements, technical information, and recommendations contained herein are based upon testing believed to be reliable, but the accuracy and completeness thereof is not guaranteed.

WARRANTY: Specified Technologies Inc. manufactures its goods in a manner to be free of defects. Should any defect occur in its goods (within one year), Specified Technologies Inc., upon prompt notification, will at its option, exchange or repair the goods or refund the purchase price.

Limitations and Exclusions: THIS WARRANTY IS IN LIEU OF ALL OTHER REPRESENTATIONS EXPRESSED OR IMPLIED (INCLUDING THE IMPLIED WARRANTIES OF MERCHANTABILITY OR FITNESS FOR USE) AND UNDER NO CIRCUMSTANCES SHALL SPECIFIED TECHNOLOGIES INC. BE RESPONSIBLE FOR ANY INCIDENTAL OR CONSEQUENTIAL PROPERTY DAMAGE OR LOSSES. PRIOR TO USE, THE USER SHALL DETERMINE THE SUITABILITY OF THE PRODUCT FOR ITS INTENDED USE, AND THE USER ASSUMES ALL RISKS AND LIABILITY FOR SUBSEQUENT USE.No statement or recommendation not contained herein shall have any force or effect unless in an agreement signed by officers of seller and manufacturer.

MADE IN THE USA – COPYRIGHT © 2012 SPECIFIED TECHNOLOGIES INC.

ORDERING INFORMATION

SpecSeal® Elastomeric Spray is available in 5 gal. pails, 55 gal. drums are available on a special order basis.

AS205 Pale Blue Color 5 gal. Pail 1,155 cu. in. (19 liters)AS205R Red Color 5 gal. Pail 1,155 cu. in. (19 liters)

CITY OF NEW YORK MEA 310-99-M

210 Evans Way, Somerville NJ 08876 USA • Phone: 800.992.1180 • Fax: 908.526.9623

TABLE A: APPLICATION EQUIPMENT

NOTICE: Spray application of SpecSeal Elastomeric Spray requires airless spray equipment meeting the following specifications:

Working Pressure: Min. 2500 PSI (172 Bar)

Delivery: Min. .72 U.S. gpm (2.7 l/min.) recommended

Spray Tip Orifice: 0.023˝ to 0.026˝ (0.58 to 0.66 mm) recommended

Wetted Parts All seals and contact surfaces suitable for contact with latex emulsions.

A minimum 3/8˝ (9.5 mm) fluid line is required, a 1/2˝ (13 mm) line is preferred. Consult pump manufacturer for long hose runs or lifts to higher elevations. A reversible spray tip is recommended. A 6˝ (152 mm) fan pattern is suggested to minimize overspray.

The following airless spray equipment has demonstrated suitability for application of this product. STI makes no warranties concerning the suitability or use of this equipment and has no affiliation of any kind with its manufacturer.

Manufacturer Model Number & Description

Titan Tool Inc. 740ix Electric Airless Sprayer

Graco Inc. Ultra Max II 695 Electric Airless Sprayer

Page 13: FIRESTOP SUBMITTAL PACKAGE - Acousti Firestopacoustifirestop.com/wp-content/uploads/2013/12/Perimeter-Fire... · SpecSeal® Series SSS Intumescent Sealant SpecSeal® Series LCI ...

1Technical Service 1-800-992-1180www.stifirestop.com

• Slab/edge/curtain wall conditions

• Floor to floor joints

• Floor to wall joints

FILL, VOID OR CAVITY MATERIALS FOR USE IN JOINT SYSTEMS & THROUGH-PENETRATION FIRESTOP SYSTEMS. SEE UL FIRE RESISTANCE DIRECTORY

3L73

PROPERTIES FAST TACK® FIRESTOP SPRAY

Color Neutral / Off White

Odor Negligible

Density 9.25 +0.25 lbs/gal (1108 +30 g/L)

Solids Content by Weight 83%

Coverage 12.8 sq. ft/gal. @ 1/8”, (0.31 m2/L @ 3.2 mm)

Tack Free Time, hours 2-4

Skin Over Time, minutes 45Viscosity, Centipoises 15,000 ± 5000

FAST TACK® FIRESTOP SPRAY

PRODUCT DATA SHEET

APPLICATIONSSpecSeal® Fast Tack® Firestop Spray is designed primarily for the protection of con-struction joints and excels in curtain wall safing gap conditions.

PRODUCT DESCRIPTIONSpecSeal® Fast Tack® Firestop Spray is an elastomeric single component silicone/urethane hybrid spray coating designed to provide passive smoke and fire protection in construction joints.

SpecSeal® Fast Tack® Firestop Spray is engineered to adhere to common construction substrates and may be applied using airless spray equipment or with a brush (for small applications or touch ups). As an option, SpecSeal® Fast Tack® Firestop Spray may also be used as a self-leveling sealant and poured into the linear opening to the required thickness as specified in the individual UL System design.

SpecSeal® Fast Tack® Firestop Spray dries rapidly and cures in the presence of atmospheric moisture to form a durable, flexible, water-resistant shield against the propagation of fire, smoke and combustion byproducts. SpecSeal® Fast Tack® Firestop Spray does not contain asbestos or PCB’s.

• Skins over quickly to resist water!

• Tack free in 2-4 hours!

• Cures below freezing.

• Tough, water-resistant flexible shield against fire and smoke.

• Will Not Wash Out!

FEATURES

PERFORMANCEWhen applied to a wet film thickness of 1/8” (3.2 mm) over appropriate backing materials, SpecSeal® Fast Tack® Firestop Spray has been success-fully tested to the exacting criteria of ASTM E 2307, ASTM E 1966, ANSI/UL2079, ASTM E 1399 and to the time-temperature requirements of ASTM E 119 (ANSI/UL 263) in one, two and three hour rated joint and perimeter fire containment systems. Visit the Technical Library at www.stifirestop.com for individual UL System designs and application requirements.

LIMITATIONS: Use product as per manufacturer’s instructions. Use only in applications per the manufacturer’s tested and published designs or specific recommendations. End user must ultimately determine suitability of the product and designs to his or her specific requirements and assumes responsibil-ity for its use.

PROPERTIES FAST TACK®FIRESTOP SPRAYTensile Strength, psi 80-100

Elongation % 200

Peel Strength, lbs/inch 5

Hardness, Shore A 25 +5

Permeability 0.04

Volatile Organic Content (VOC), g/L 132 g/L

Flame Spread* 0

Smoke Development* 20

In Service Temp -35˚F (-37˚C) - 350˚F (177˚C)

Storage Temp 0˚F (18˚C) - 80˚F (27˚C)

Shelf Life** 1 Yr*ASTM E 84 (UL723) @ 14% Surface Coverage (modified test for sealants and caulks)**From date of manufacture.

SPECIFICATIONSThe fire protective joint coating shall be a single component, moisture curing elastomeric silicone/urethane hybrid coating. The coating as applied shall be insoluble and immiscible in water, and cure to form a flexible, moisture resistant film. The coating shall adhere to all common construction surfaces and be of a high static viscosity, capable of being applied by brush, roller, or airless sprayer. The approved coating shall be SpecSeal® Fast Tack® Firestop Spray.

SPECIFIED DIVISIONSDIV. 7 07840 Through-Penetration FirestoppingDIV. 13 13900 Special Construction Fire Suppression & Supervisory SystemsDIV. 15 15250 Mechanical Insulation – Fire ProtectionDIV. 16 16050 Basic Electrical Materials & Methods

PHYSICAL PROPERTIES

STI Product Data Sheet • Series FT Fast Tack® Firestop Spray • FOD-5080 02/2013

Page 14: FIRESTOP SUBMITTAL PACKAGE - Acousti Firestopacoustifirestop.com/wp-content/uploads/2013/12/Perimeter-Fire... · SpecSeal® Series SSS Intumescent Sealant SpecSeal® Series LCI ...

2 Technical Service 1-800-992-1180www.stifirestop.com

ORDERING INFORMATIONCAT. NO. DESCRIPTION FT305 5 gallon pail 1,155 cu. in. (19 liters)

APPLICATION EQUIPMENT

NOTICE: Spray application of SpecSeal® FastTack® Spray requires airless spray equipment meeting the following specifications. Working Pressure: Minimum 2500 psi Delivery: Minimum 1.0 US gpm (2.1 l/min) recommended. Spray Tip Orifice: 0.023 to 0.026-in. recommended Wetted Parts: All seals, hoses and contact surfaces should be Teflon®.A minimum 3/8-in. diameter fluid line is required. Consult pump manufacturer for long hose runs or lifts to higher elevations. A reversible spray tip is recommended. A 6-in. fan pattern is suggested to minimize overspray.The following airless spray equipment has demonstrated suitability for application of this product. STI makes no warranties concerning the suitability or use of this equipment and has no affiliation of any kind with its manufacturer.

The following equipment is manufactured by Titan Tool, Inc. Franklin Lakes, NJ:

Item Item Name & DescriptionPowrTwin Model 5500 Sprayer Electric or gas powered airless sprayer

Additional SpecSeal Products...

Elastomeric Joint SealantsEconomical products for sealing construction joints. Choose caulk or spray applied products tested to UL2079.

City of NY MEA 102-05-M

Important Notice: All statements, technical information, and recommendations contained herein are based upon testing believed to be reliable, but the accuracy and completeness thereof is not guaranteed.WARRANTY: Specified Technologies Inc. manufactures its goods in a manner to be free of defects. Should any defect occur in its goods (within one year), Specified Technologies Inc., upon prompt notification, will at its option, exchange or repair the goods or refund the purchase price.Limitations and Exclusions: THIS WARRANTY IS IN LIEU OF ALL OTHER REPRESENTATIONS EXPRESSED OR IMPLIED (INCLUDING THE IMPLIED WARRANTIES OF MERCHANTABILITY OR FITNESS FOR USE) AND UNDER NO CIRCUMSTANCES SHALL SPECIFIED TECHNOLOGIES INC. BE RESPONSIBLE FOR ANY INCIDENTAL OR CONSEQUENTIAL PROPERTY DAMAGE OR LOSSES. PRIOR TO USE, THE USER SHALL DETERMINE THE SUITABILITY OF THE PRODUCT FOR ITS INTENDED USE, AND THE USER ASSUMES ALL RISKS AND LIABILITY FOR SUBSEQUENT USE. No statement or recommendation not contained herein shall have any force or effect unless in an agreement signed by officers of seller and manufacturer.

MADE IN THE USA – COPYRIGHT © 2013 SPECIFIED TECHNOLOGIES INC.

INSTALLATION INSTRUCTIONSGENERAL: Areas to be protected must be clean and free of oil, loose dirt, rust or scale. Unsound surfaces may need to be power washed with clean water dilut-ed bleach solution, and then power rinsed to remove dirt. Recommended storage temperatures range between 0° F (-18° C) and 80° F (27° C). Recommended application temperatures range between 40° F (4° C) and 95° F (35° C). Applying coating in lower temperatures than specified will lengthen skin over, tack-free and ultimate cure time. For best results, relative humidity should be above 20%. Lower humidity will slow the cure rate significantly.

Consult appropriate manufacturer’s system drawing for design requirements. Forming or packing materials may be required as an integral part of various system designs.

For best performance, coating may be applied by airless spray to a 1/8” (3.2 mm) wet thickness. Do not attempt to add water or solvent to SpecSeal® Fast Tack® Firestop Spray.

Clean up of equipment containing uncured material may be accomplished by flushing with mineral spirits. SpecSeal® Fast Tack® Firestop Spray should not be left in pumping equipment and/or hoses for prolonged periods of time. Hoses shall be TEFLON® lined, connections shall be sealed with TEFLON® and pump seals shall be TEFLON®. SpecSeal® Fast Tack® Firestop Spray cures by reacting with moisture vapor to form cured material. Equipment without TEFLON® lining and seals will transmit sufficient moisture vapor to gradually cure material on hose walls and unsealed connections which may directly result in increased operating pressures and material flow restriction. As an option, SpecSeal® Fast Tack® Firestop Spray may also be used as a self-leveling sealant and poured into the linear opening to the required thickness as specified in the individual UL System design. TEFLON® is a registered trademark of Dupont.

MAINTENANCEINSPECTION: Installations should be periodically inspected for subsequent damage. Following safety precautions listed below and pertinent installation guidelines remove coating in damaged areas and reapply fresh coating material to original coating thickness.

TECHNICAL SERVICESpecified Technologies, Inc. provides toll free technical support to assist in product selection and installation information. UL Classified Systems are available at the Technical Library at www.stifirestop.com.

PRECAUTIONARY INFORMATIONConsult Material Safety Data Sheet for additional information on the safe handling and disposal of this material. Avoid contact with eyes. The use of an OSHA or NIOSH approved mask for dust and mist environment is recommended. Use only in well ventilated areas. To clean areas of skin contact, wipe off uncured material with a dry cloth or paper towel prior to washing. Waterless hand cleaners are particularly effective when sealant is uncured.

AVAILABILITYSpecSeal® Fast Tack® Firestop Spray is available from authorized distributors. Consult factory for the names and locations of the nearest sales rep-resentatives or distributors.

STI Product Data Sheet • Series FT Fast Tack® Firestop Spray • FOD-5080 02/2013

Page 15: FIRESTOP SUBMITTAL PACKAGE - Acousti Firestopacoustifirestop.com/wp-content/uploads/2013/12/Perimeter-Fire... · SpecSeal® Series SSS Intumescent Sealant SpecSeal® Series LCI ...

Material Safety Data Sheet ___________________________________________________

28-AUGUST-2013

SpecSeal® AS200 ELASTOMERIC SPRAY

CHEMICAL PRODUCT/COMPANY IDENTIFICATION Material Identification PRODUCT NAME …… ........................................SpecSeal® AS200 SPRAYCHEMICAL FAMILY .............................................Mixture

Company Identification

MANUFACTURER/DISTRIBUTOR Specified Technologies Inc.210 Evans WaySomerville, NJ 08876

PHONE NUMBERS Product Information : 1-908-526-8000 Emergency : 1-800-255-3924

HAZARDS IDENTIFICATION

***********EMERGENCY OVERVIEW************ * Possible skin and eye irritant. Paste. *

*******************************************************Potential Health Effects:EYE: Contact may cause irritation.SKIN: Contact may cause irritation.INGESTION: Relatively non-toxic.INHALATION: Irritation of the nose, throat, and lungs may result from over-exposure to vapors or mist. CHRONIC (CANCER) INFORMATION: Not classified as carcinogenic.LONG TERM TOXIC EFFECTS: None known.

COMPOSITION/INFORMATION ON INGREDIENTS

Proprietary mixture containing in part: INGREDIENT NAME CAS NUMBER ACRYLIC COPOLYMER Non Hazardous CALCIUM CARBONATE 1317-65-3 TITANIUM DIOXIDE 13463-67-7 ALUMINA TRIHYDRATE 21645-51-2

Page 1 of 3 MSDS - SpecSeal® SERIES AS200 Elastomeric Spray FOD-5043

Page 16: FIRESTOP SUBMITTAL PACKAGE - Acousti Firestopacoustifirestop.com/wp-content/uploads/2013/12/Perimeter-Fire... · SpecSeal® Series SSS Intumescent Sealant SpecSeal® Series LCI ...

FIRST AID MEASURES

First Aid

INHALATION: Remove to fresh air. SKIN CONTACT: Wash thoroughly. EYE CONTACT: Irrigate eyes with running water for at least 15 minutes. Get medical attention if irritation develops.INGESTION: None applicable.

FIRE FIGHTING MEASURES

Not a fire hazard.

EXTINGUISHING MEDIA………………….……...…Dry Chemical; Carbon Dioxide; Foam; Water spray for large fires.SPECIAL FIRE FIGHTING PROCEDURES:……As for surrounding fire.

ACCIDENTAL RELEASE MEASURES

Safeguards (Personnel) NOTE: Review FIRE FIGHTING MEASURES and HANDLING (PERSONNEL) sections before proceeding with clean-up. Use appropriate PERSONAL PROTECTIVE EQUIPMENT during clean-up.

HANDLING AND STORAGE

Store under ambient conditions. No special handling required.

EXPOSURE CONTROLS/PERSONAL PROTECTION

EYE PROTECTION REQUIREMENTS: ................Safety glasses/goggles.SKIN PROTECTION REQUIREMENTS: ..............Gloves.RESPIRATOR REQUIREMENTS: ........................None.VENTILATION REQUIREMENTS: ........................If needed, use local exhaust ventilation to keep airborne concentrations below the

TLV.Exposure Guidelines Exposure Limits PEL(OSHA) : Particulates (Not Otherwise Classified) 15 mg/m3, 8 Hr. TWA, total dust 5 mg/m3, 8 Hr. TWA, respirable dust TLV(ACGIH): None Established

PHYSICAL AND CHEMICAL PROPERTIES

PHYSICAL FORM…………………………… ..............PasteSPECIFIC GRAVITY………………………………… ..1.25PERCENT VOLATILES .............................................23+/-2EVAPORATION RATE ..............................................>1BOILING POINT………………………………… ........ 100 deg. CSOLUBILITY IN WATER ........................................... Infinitely dilutableCARB VOC (Calculated) ..........................................0.48 Wt.%SCAQMD VOC (US EPA Method 24) .......................10 Grams/Liter

STABILITY AND REACTIVITY STABILITY: ...............................................................This is a stable material.CONDITIONS TO AVOID .........................................Storage >55 deg. CHAZARDOUS POLYMERIZATION: ..........................Will not occur.INCOMPATIBILITIES:........ .. ....................................None special

TOXICOLOGICAL INFORMATION

Mixture not tested but based on components:May be irritating to skin and eyes and may produce symptoms of nausea in poorly ventilated areas.None of the components are listed as carcinogens.

Page 2 of 3 MSDS - SpecSeal® SERIES AS200 Elastomeric Spray FOD-5043

Page 17: FIRESTOP SUBMITTAL PACKAGE - Acousti Firestopacoustifirestop.com/wp-content/uploads/2013/12/Perimeter-Fire... · SpecSeal® Series SSS Intumescent Sealant SpecSeal® Series LCI ...

ECOLOGICAL INFORMATION No data.

DISPOSAL CONSIDERATIONS Waste Disposal: Treatment, storage, transportation, and disposal must be in accordance with applicable Federal, State/Provincial, and Local regulations.

TRANSPORTATION INFORMATIONDOT – not regulated.

REGULATORY INFORMATION U.S. Federal Regulations TSCA Inventory Status : Reported/Included. Section 313 Supplier Notifications. This product contains no toxic chemicals subject to the reporting requirements of Section 313 of the Emergency Planning and Community Right-To-Know Act of 1986 and of 40 CFR 372

OTHER INFORMATION NPCA-HMIS Rating Health : 1 Flammability : 0 Reactivity : 0Personal Protection rating to be supplied by user depending on use conditions.

STATE RIGHT-TO-KNOW LAWS No substances on the state hazardous substances list, for the states indicated below, are used in the manufacture of products on this Material Safety Data Sheet, with the exceptions indicated. While we do not specifically analyze these products, or the raw materials used in their manufacture, for substances on various state hazardous substances lists, to the best of our knowledge the products on this Material Safety Data Sheet contain no such substances except for those specifically listed below:

SUBSTANCES ON THE NEW JERSEY WORKPLACE HAZARDOUS SUBSTANCE LIST PRESENT AT A CONCENTRATION OF 1% OR MORE (0.1% FOR SUBSTANCES IDENTIFIED AS CARCINOGENS, MUTAGENS OR TERATOGENS): Alumina, Titanium Dioxide. WARNING: SUBSTANCES KNOWN TO THE STATE OF CALIFORNIA TO CAUSE CANCER: None Known.. WARNING: SUBSTANCES KNOWN TO THE STATE OF CALIFORNIA TO CAUSE BIRTH DEFECTS OR OTHER REPRODUCTIVE HARM: None known.

This information relates to the specific material designated and may not be valid for such material used in combination with any other materials or in any process. Such information is to the best of our knowledge and belief accurate and reliable as of the data compiled. However, no representation, warranty, or guarantee is made as to its accuracy, reliability or completeness. It is the user’s responsibility to satisfy himself as to the suitability and completeness of such information for his own particular use. We do not accept liability for any loss or damage that may occur form the use of this information.

Responsibility for MSDS : Specified Technologies Inc.210 Evans WaySomerville, NJ 08876

Page 3 of 3 MSDS - SpecSeal® SERIES AS200 Elastomeric Spray FOD-5043

Page 18: FIRESTOP SUBMITTAL PACKAGE - Acousti Firestopacoustifirestop.com/wp-content/uploads/2013/12/Perimeter-Fire... · SpecSeal® Series SSS Intumescent Sealant SpecSeal® Series LCI ...

Material Safety Data Sheet ____________________________________________________

22-JAN-2009

SpecSeal® Fast Tack AWG

CHEMICAL PRODUCT/COMPANY IDENTIFICATION

Material Identification

PRODUCT NAME......................SpecSeal® Fast Tack AWGCHEMICAL FAMILY..................Mixture

Company Identification

MANUFACTURER/DISTRIBUTOR

Specified Technologies, Inc. 200 Evans Way Somerville, NJ 08876

PHONE NUMBERS

Product Information : 1-908-526-8000 Emergency : 1-800-255-3924

COMPOSITION/INFORMATION ON INGREDIENTS

INGREDIENT NAME CAS NUMBER PERCENT D4 & HMDZ TREATED SILICON DIOXIDE 68937-51-9 1-5 METHYLTRIMETHOXYSILANE 1185-55-3 1-5 LIMESTONE 1317-65-3 >37.1 STEARIC ACID 57-11-4 <1.95 QUARTZ 14808-60-7 <0.39 DISTILLATES, PETROLEUM 64742-47-8 10-30 HYDROTREATED LIGHT POLYDIMETHYLSILOXANE SILANOL/STPD 70131-67-8 30-60

HAZARDS IDENTIFICATION

**************************EMERGENCY OVERVIEW****************************** * Combustible. Irritating to skin, eyes and respiratory tract irritant. May be * * harmful if swallowed, inhaled or absorbed through skin. Off-white liquid. *

***************************************************************************************

Potential Health Effects:

EYE: Contact with vapor or liquid causes irritation. SKIN: Contact may cause irritation and defatting. May be absorbed through skin to cause toxic effects. INGESTION: May be harmful if swallowed. May cause headache, dizziness, nausea, vomiting and gastrointestinal irritation and central nervous depression. INHALATION: Irritation of the nose, throat, and lungs may result from over-exposure to vapors or mist from uncured material. CHRONIC (CANCER) INFORMATION: Crystalline silica is a carcinogenic. LONG TERM TOXIC EFFECTS: None known.

Page 1 of 4 MSDS - SpecSeal® Fast Track AWG FOD-5081

Page 19: FIRESTOP SUBMITTAL PACKAGE - Acousti Firestopacoustifirestop.com/wp-content/uploads/2013/12/Perimeter-Fire... · SpecSeal® Series SSS Intumescent Sealant SpecSeal® Series LCI ...

FIRST AID MEASURES

First Aid INHALATION: Remove to fresh air. SKIN CONTACT: Wash thoroughly. EYE CONTACT: Irrigate eyes with running water for at least 15 minutes. Get medical attention if irritation develops. INGESTION: Do not induce vomiting. Give 1-3 glasses of water. Get medical attention. Never give anything by mouth to an unconscious person.

FIRE FIGHTING MEASURES

FLASH POINT: 40 deg. C. AUTOIGNITION TEMPERATURE: 232 DEG. C.

Flammable limits in Air, % by Volume: lower limit: 1.0 upper limit: 6.0

EXTINGUISHING MEDIA ............................................Dry Chemical; Carbon Dioxide; Foam; Water spray for large fires.

SPECIAL FIRE FIGHTING PROCEDURES……............Fire Fighting Protective Equipment: A self-contained breathing apparatus and full protective clothing should be worn in fire conditions.

ACCIDENTAL RELEASE MEASURES Safeguards (Personnel) NOTE: Review FIRE FIGHTING MEASURES and HANDLING (PERSONNEL) sections before proceeding with clean-up. Use appropriate PERSONAL PROTECTIVE EQUIPMENT during clean up.

Dispose of materials in container intended for flammable waste.

HANDLING AND STORAGE

Store away from heat, sources of ignition, and incompatibles. Emptied containers may retain hazardous properties. Do not cut, puncture or weld on or near the container.

Avoid breathing vapors. Avoid contact with skin and eyes.

EXPOSURE CONTROLS/PERSONAL PROTECTION

EYE PROTECTION REQUIREMENTS:.............Safety glasses with side shields/goggles. SKIN PROTECTION REQUIREMENTS:...........Rubber gloves. RESPIRATOR REQUIREMENTS:.....................Supplied air respirators may be required for non-routine or emergency situations. VENTILATION REQUIREMENTS:…………......Use ventilation that is adequate to keep employee exposure to airborne concentrations below limits. Exposure Guidelines Exposure Limits PEL(OSHA) : Particulates (Not Otherwise Classified) 15 mg/m3, 8 Hr. TWA, total dust 5 mg/m3, 8 Hr. TWA, respirable dust TLV( ACGIH): None Established

QUARTZ (CRYSTALLINE SILICA) TLV(ACGIH): 0.05mg/m3

PHYSICAL AND CHEMICAL PROPERTIES

PHYSICAL FORM ................................................... Off-white liquid. SPECIFIC GRAVITY ............................................... 1.21 PERCENT VOLATILES ........................................... none SOLUBILITY IN WATER .......................................... Insoluble SOLUBILITY IN ORGANIC SOLVENT……...…........Soluble in petroleum distillate BOILING POINT…………………………………........156 deg. C. VAPOR PRESSURE (20 C)(MM HG)…………..........<5 VAPOR DENSITY (AIR=1)………………………........4-5 FREEZING POINT………………………………..........NE ODOR……………………………………………..........MILD SOLVENT % VOLATILE BY VOLUME……………………….......21 EVAP. RATE (BUTYL ACETATE=1)……………........>1 VOC EXCL.H2O & EXEMPTS (G/L)……………........37

Page 2 of 4 MSDS - SpecSeal® Fast Track AWG FOD-5081

Page 20: FIRESTOP SUBMITTAL PACKAGE - Acousti Firestopacoustifirestop.com/wp-content/uploads/2013/12/Perimeter-Fire... · SpecSeal® Series SSS Intumescent Sealant SpecSeal® Series LCI ...

STABILITY AND REACTIVITY

STABILITY:................................................................This is a stable material.CONDITIONS TO AVOID: ........................................ Keep away from heat, sparks and flame.HAZARDOUS POLYMERIZATION:...........................Will not occur.INCOMPATIBILITIES:……………………………........None known.

TOXICOLOGICAL INFORMATION

POTENTIAL HEALTH EFFECTS:

INGESTION: May be harmful if swallowed. May cause headache, dizziness, nausea, vomiting, gastrointestinal irritation and central nervous system depression. May cause pneumonitis as a result of aspiration.

SKIN CONTACT: Uncured product contact may irritate the skin. May cause skin defatting with prolonged exposure. May be absorbed through skin and produce effects as listed under “Ingestion”.

INHALATION: Applies only in uncured state. May be harmful if inhaled. A dust hazard would exist if solid particles were separated from the liquid phase. May also cause other effects as listed under “Ingestion”. May cause respiratory tract irritation. Inhalation of dusts may result in acute pneumoconiosis.

EYE CONTACT: Vapor and/or liquid cause irritation.

MEDICAL CONDITIONS AGGRAVATED: Central nervous system disorders. Pre-existing skin or respiratory diseases.

SUBCHRONIC (TARGET ORGAN) EFFECTS: Central nervous system Kidneys Skin

Quartz (crystalline silica) is listed as a carcinogen by IARC, NTP and ACGIH.

ECOLOGICAL INFORMATION

No data. Not anticipated to be environmental hazard.

DISPOSAL CONSIDERATIONS

Waste Disposal: Treatment, storage, transportation, and disposal must be in accordance with applicable Federal, State/Provincial, and Local regulations.

TRANSPORTATION INFORMATION

DOT DOT SHIPPING NAME: FOR BULK CONTAINERS (>119 GAL) ONLY: COMBUSTIBLE LIQUID N.O.S. (PETROLEUM DISTILLATE) DOT HAZARD CLASS: COMBUSTIBLE LIQUID - FOR BULK CONTAINERS ONLY DOT LABEL (S): COMBUSTIBLE LIQUID - FOR BULK CONTAINERS ONLY UN/NA NUMBER: NA1993 - FOR BULK CONTAINERS ONLY PLACARDS: COMBUSTIBLE - FOR BULK CONTAINERS ONLY

REGULATORY INFORMATION

U.S. Federal Regulations TSCA Inventory Status: Reported/Included.Section 313 Supplier Notifications. This product contains no toxic chemicals subject to the reporting requirements of Section 313 of the Emergency Planning and Community Right-To-Know Act of 1986 and of 40 CFR 372:

Page 3 of 4 MSDS - SpecSeal® Fast Track AWG FOD-5081

Page 21: FIRESTOP SUBMITTAL PACKAGE - Acousti Firestopacoustifirestop.com/wp-content/uploads/2013/12/Perimeter-Fire... · SpecSeal® Series SSS Intumescent Sealant SpecSeal® Series LCI ...

OTHER INFORMATION

STATE RIGHT-TO-KNOW LAWS

No substances on the state hazardous substances list, for the states indicated below, are used in the manufacture of products on this Material Safety Data Sheet, with the exceptions indicated. While we do not specifically analyze these products, or the raw materials used in their manufacture, for substances on various state hazardous substances lists, to the best of our knowledge the products on this Material Safety Data Sheet contain no such substances except for those specifically listed below:

SUBSTANCES ON THE NEW JERSEY WORKPLACE HAZARDOUS SUBSTANCE LIST PRESENT AT A CONCENTRATION OF 1% OR MORE (0.1% FOR SUBSTANCES IDENTIFIED AS CARCINOGENS, MUTAGENS OR TERATOGENS): Crystalline silica. WARNING: SUBSTANCES KNOWN TO THE STATE OF CALIFORNIA TO CAUSE CANCER: Crystalline Silica.

WARNING: SUBSTANCES KNOWN TO THE STATE OF CALIFORNIA TO CAUSE BIRTH DEFECTS OR OTHER REPRODUCTIVE HARM: None known.

------------------------------------------------------------------

This information relates to the specific material designated and may not be valid for such material used in combination with any other materials or in any process. Such information is to the best of our knowledge and belief accurate and reliable as of the data compiled. However, no representation, warranty, or guarantee is made as to its accuracy, reliability or completeness. It is the user’s responsibility to satisfy himself as to the suitability and completeness of such information for his own particular use. We do not accept liability for any loss or damage that may occur form the use of this information.

Responsibility for MSDS :

Specified Technologies, Inc.200 Evans WaySomerville, NJ 08876

Page 4 of 4 MSDS - SpecSeal® Fast Track AWG FOD-5081