FEE + ROC cooling

36
FEE + ROC cooling S. Popescu CERN, U. Frankenfeld, H.R. Schmidt GSI

description

FEE + ROC cooling. S. Popescu CERN, U. Frankenfeld, H.R. Schmidt GSI. Lauda System. PUMP. Lauda System. IROC in Thermal Box + 4 FEC (3.1). Inside: Sensors on pad plane. T8. T8. T9. T10. T13. T7. T5. T6. T11. T12. IROC. ~10cm. ~10cm. T14. T15. FEC. - PowerPoint PPT Presentation

Transcript of FEE + ROC cooling

Page 1: FEE + ROC cooling

FEE + ROC cooling

S. Popescu CERN, U. Frankenfeld, H.R. Schmidt GSI

Page 2: FEE + ROC cooling

12.2.2004 TPC meeting 2

IROC in Thermal Box + 4 FEC (3.1)

Lauda System

PUMP

IROC

Lauda System

T8T9

T10

T12

T13

T11

T7 T6T5

Inside: Sensors on pad plane

T8

FEC

T14T15

Separate cool. circuits for chamber + FEC

Sensors on FEC cool. plates

~10cm ~10cm

Page 3: FEE + ROC cooling

12.2.2004 TPC meeting 3

FEC

IN

Thermal Box T=21 ˚C

Chamber cool. T=21˚C

Cooling In

Temp sensors

PS

Cooling Out

Page 4: FEE + ROC cooling

12.2.2004 TPC meeting 4

Input Cooling circuit

Output Cooling circuit

Cham

ber

Coolin

g c

ircu

it

4 FEC (3.1)~10.5 W/card(3.2: ~6.9 W/card)

T11

T9 T10

T12

IROC

Page 5: FEE + ROC cooling

12.2.2004 TPC meeting 5

ELMB

PT1000 two wire sensors connected

Can Bus port

Page 6: FEE + ROC cooling

12.2.2004 TPC meeting 6

Cooling plate

Inner screws

T14

Page 7: FEE + ROC cooling

12.2.2004 TPC meeting 7

Single card w/o inner screws

LV OFF LV ON

ΔT ~5.5 ˚C

ΔT c

oolin

g p

late

s

Page 8: FEE + ROC cooling

12.2.2004 TPC meeting 8

Card w/o inner screws in set-up

LV ON LV OFF

ΔT ~4 ˚C

ΔT c

oolin

g p

late

s

Page 9: FEE + ROC cooling

12.2.2004 TPC meeting 9

Single card with all screws

All screws in

ΔT ~1 ˚C

ΔT c

oolin

g p

late

s

Page 10: FEE + ROC cooling

12.2.2004 TPC meeting 10

Chamber cooling

~ 50 minutes

Cc off Cooling circuit on

chamber

Pad

Page 11: FEE + ROC cooling

12.2.2004 TPC meeting 11

Chamber cooling

• All circuits 21˚C• Chamber

21 -> 19.5 ˚C

ΔT ~1.5 ˚C

chamber cooling

chamber

pads

Page 12: FEE + ROC cooling

12.2.2004 TPC meeting 12

Chamber cooling

• All circuits 21˚C• Gradients on

the pad plane

ΔT ~0.08 ˚C

pad under FEC

pad

Page 13: FEE + ROC cooling

12.2.2004 TPC meeting 13

ΔT ~0.18˚C

Δt ~ 30 min

LV OFF LV ON

Heat transfer to pad plane

Pad under FEC

Page 14: FEE + ROC cooling

12.2.2004 TPC meeting 14

Heat transfer with cable

• Chamber 21˚C• FEE cooling 19˚C• Thermal box 21˚C

Heat transfer: ~0.19˚C

pad under FEC

pad

LV ON | LV OFF

Page 15: FEE + ROC cooling

12.2.2004 TPC meeting 15

Heat transfer without cable

• Chamber 21˚C• FEE cooling 19˚C• Thermal box 21˚C

Heat transfer: ~0.15˚C

pad under FEC

pad

LV ON | LV OFF

Page 16: FEE + ROC cooling

12.2.2004 TPC meeting 16

Compensation 19-24 ˚C

LV OFF LV ON LV OFF

FEC cool:T=19 ˚C T=24 ˚C T=19 ˚C T=24 ˚C

Page 17: FEE + ROC cooling

12.2.2004 TPC meeting 17

Temperature cooling FEE 19->24 ˚C

ΔT ~ 0.14˚C

pad under FEC

pad

Page 18: FEE + ROC cooling

12.2.2004 TPC meeting 18

Compensate: Switching ON

ΔT ~ 0.05˚C

pad under FEC

pad

Page 19: FEE + ROC cooling

12.2.2004 TPC meeting 19

Compensate: Switching OFF

pad under FEC

pad

FEC cool. temperature (scaled)

Page 20: FEE + ROC cooling

12.2.2004 TPC meeting 20

Compensate: Switching OFF

ΔT ~ 0.06˚C

pad under FEC

pad

Page 21: FEE + ROC cooling

12.2.2004 TPC meeting 21

Compensation (16-21˚C)

LV OFF LV ON LV OFF

FEC cool: T=21˚C T=16˚C T=21 ˚C

Page 22: FEE + ROC cooling

12.2.2004 TPC meeting 22

Compensation (16-21˚C)

ΔT ~ 0.05˚Cpad under FEC

pad

LV ON LV OFF

Page 23: FEE + ROC cooling

12.2.2004 TPC meeting 23

Summary + Conclusion

• Setup with 4 FEC (Ver. 3.1) 10.5 W per Card• Heat transfer between both sides of cooling plates

thru screws: Single sided cooling? • Chamber circuit for stabilization not compensation

– Time constant Δt ~ 50 min

• Heat transfer FEC -> pads– Time constant Δt ~ 30 min– ~0.19 ˚C with cable– ~0.14 ˚C without cable

• Compensation with Cooling temperature per sector– Test setup: Compensation on pads with ΔT ~ 0.05 ˚C

Page 24: FEE + ROC cooling

FEE + ROC cooling update

S. Popescu CERN, U. Frankenfeld, H.R. Schmidt GSI

Page 25: FEE + ROC cooling

12.2.2004 TPC meeting 25

IROC in Thermal Box + 15 FEC (3.1)

Lauda System

PUMP

IROC

Lauda System

T8T9

T10

T12

T13

T11T7 T6T5

Inside: Sensors on pad plane

T8

Separate cool. circuits for chamber + FEC

~10cm ~10cm

Page 26: FEE + ROC cooling

12.2.2004 TPC meeting 26

Setup

• 15 FEC ver. 3.1• 10.5 W/card

– ver. 3.2: ~6 W

• Test of single side cooling

• Simulation of OROC• 15 cards:

– 3.3V: 40A– 4.3V: 8A

• Voltage drop:– 0.5 V@40A (2m)

Page 27: FEE + ROC cooling

12.2.2004 TPC meeting 27

Page 28: FEE + ROC cooling

12.2.2004 TPC meeting 28

15 cards no chamber stabilization

LV: ON OFF Half ON OFF

Page 29: FEE + ROC cooling

12.2.2004 TPC meeting 29

15 cards chamber stabilization

LV: ON OFF HALF ON OFF

Page 30: FEE + ROC cooling

12.2.2004 TPC meeting 30

IROC

ΔT ~ 0.43˚C

LV:OFF ON OFF

Page 31: FEE + ROC cooling

12.2.2004 TPC meeting 31

IROC single sided

ΔT ~ 0.62˚C

LV:OFF ON OFF

Page 32: FEE + ROC cooling

12.2.2004 TPC meeting 32

IROC half power

ΔT ~ 0.24˚C

LV:OFF half ON OFF

Page 33: FEE + ROC cooling

12.2.2004 TPC meeting 33

OROC simulation

Page 34: FEE + ROC cooling

12.2.2004 TPC meeting 34

OROC

ΔT ~ 0.31˚C

LV:OFF ON OFF

Page 35: FEE + ROC cooling

12.2.2004 TPC meeting 35

OROC single sided

ΔT ~ 0.60˚C

LV:OFF ON OFF

Page 36: FEE + ROC cooling

12.2.2004 TPC meeting 36

Summary