CSC-150 Busbar Protection IED Engineering and Operation Manual

129
CSC-150 Busbar Protection IED Engineering and Operation Manual

Transcript of CSC-150 Busbar Protection IED Engineering and Operation Manual

Page 1: CSC-150 Busbar Protection IED Engineering and Operation Manual

CSC-150

Busbar Protection IED

Engineering and Operation

Manual

Page 2: CSC-150 Busbar Protection IED Engineering and Operation Manual

CSC-150 Busbar Protection IED

Engineering and Operation Manual

Compiled: Jin Rui

Checked: Hou Changsong

Standardized: Li Lianchang

Inspected: Cui Chenfan

Version: V1.00

Doc.Code:0SF.460.078(E)

Issued Date:2012.8.31

Page 3: CSC-150 Busbar Protection IED Engineering and Operation Manual

Version:V1.00

Doc. Code: 0SF.460.078(E)

Issued Date:2012.8

Copyright owner: Beijing Sifang Automation Co., Ltd

Note: The company keeps the right to perfect the instruction. If equipments do

not agree with the instruction at anywhere, please contact our company in time.

We will provide you with corresponding service.

® is registered trademark of Beijing Sifang Automation Co., Ltd.

We reserve all rights to this document, even in the event that a patent is issued and a different commercial proprietary right is registered. Improper use, in particular reproduction and dissemination to third parties, is not permitted.

This document has been carefully checked. If the user nevertheless detects any errors, he is asked to notify us as soon as possible.

The data contained in this manual is intended solely for the IED description and is not to be deemed to be a statement of guaranteed properties. In the interests of our customers, we constantly seek to ensure that our products are developed to the latest technological standards as a result it is possible that there may be some differences between the hardware/software product and this information product.

Manufacturer: Beijing Sifang Automation Co., Ltd.

Tel: +86 10 62962554, +86 10 62961515 ext. 8998 Fax: +86 10 82783625 Email: [email protected] Website: http://www.sf-auto.com

Add: No.9, Shangdi 4th Street, Haidian District, Beijing, P.R.C.100085

Page 4: CSC-150 Busbar Protection IED Engineering and Operation Manual

Preface

Purpose of this manual

This manual describes operation, installation, commissioning, protection test

and putting the IED into service. The manual includes the following chapters:

Introduction, this chapter presents the basic content and have a brief

introduction of this manual

Local human machine interface, this chapter presents the configuration

of HMI interface and how to use the HMI

Installing the IED, this chapter introduces the procedure to install IED and

how to check that the IED is properly connected to the protection system

Read and change setting, this chapter introduces how to read and

change the setting value via LHMI or software tool, and switch the setting

value group

Testing the communication connection and time synchronization, this

chapter presents how to test the communication port connection and

introduces how to test time synchronization

IED testing, this chapter contains that what should be tested and how to

test the IED

Operating maintenance, this chaper describes the items for maintenance

and how to maintain the IED when operating

Transportion and storage, this chapter presents how to transport and

store the IED

Appendix, this chapter presents the significant data and diagram of the

IED

Target audience

This manual mainly face to installation engineer, commissioning engineer and

operation engineer with perfessional electric and electrical knowledge, rich

experience in protection function, using protection IED, test IED, responsible

Page 5: CSC-150 Busbar Protection IED Engineering and Operation Manual

for the installation, commissioning, maintenance and taking the protection

IED in and out of normal service.

Applicability of this manual

This manual is valid for CSC-150 Busbar Protection IED.

Technical support

In case of further questions concerning the CSC family, please contact Sifang

compay or your local Sifang representative.

Safety information

Strictly follow the company and international safety regulations.

Working in a high voltage environment requires serious approch to

aviod human injuries and damage to equipment

Do not touch any circuitry during operation. Potentially lethal

voltages and currents are present

Avoid to touching the circuitry when covers are removed. The IED

contains electirc circuits which can be damaged if exposed to static

electricity. Lethal high voltage circuits are also exposed when covers

are removed

Using the isolated test pins when measuring signals in open circuitry.

Potentially lethal voltages and currents are present

Never connect or disconnect wire and/or connector to or from IED

during normal operation. Dangerous voltages and currents are

present. Operation may be interrupted and IED and measuring

circuitry may be damaged

Always connect the IED to protective earth regardless of the

Page 6: CSC-150 Busbar Protection IED Engineering and Operation Manual

operating conditions. Operating the IED without proper earthing may

damage both IED and measuring circuitry and may cause injuries in

case of an accident.

Do not disconnect the secondary connection of current transformer

without short-circuiting the transformer’s secondary winding.

Operating a current transformer with the secondary winding open will

cause a high voltage that may damage the transformer and may

cause injuries to humans.

Do not remove the screw from a powered IED or from an IED

connected to power circuitry. Potentially lethal voltages and currents

are present

Using the certified conductive bags to transport PCBs (modules).

Handling modules with a conductive wrist strap connected to

protective earth and on an antistatic surface. Electrostatic discharge

may cause damage to the module due to electronic circuits are

sensitive to this phenomenon

Do not connect live wires to the IED, internal circuitry may be

damaged

When replacing modules using a conductive wrist strap connected to

protective earth. Electrostatic discharge may damage the modules

and IED circuitry

When installing and commissioning, take care to avoid electrical

shock if accessing wiring and connection IEDs

Changing the setting value group will inevitably change the IEDs

operation. Be careful and check regulations before making the

change

Page 7: CSC-150 Busbar Protection IED Engineering and Operation Manual

Contents

Chapter 1 IED Introduction ............................................................................................................... 1

Chapter 2 Local human machine interface .................................................................................... 3

1 Introduction ....................................................................................................................................... 4

2 Liquid crystal display(LCD) ....................................................................................................... 6

3 Keyboard .......................................................................................................................................... 7

4 IED menu .......................................................................................................................................... 8

4.1 Menu construction ........................................................................................................... 8

4.2 Operation status .............................................................................................................. 9

4.3 Query reports ................................................................................................................. 10

4.4 Set time ........................................................................................................................... 10

4.5 Contrast .......................................................................................................................... 10

4.6 Settings ........................................................................................................................... 11

4.7 IED setting ...................................................................................................................... 11

4.8 Test binary output .......................................................................................................... 12

4.9 Testing operation ........................................................................................................... 12

Chapter 3 Installing IED .................................................................................................................. 13

1 Unpacking and checking the IED ................................................................................................ 14

2 Installing the IED ........................................................................................................................... 15

3 IED connection .............................................................................................................................. 16

3.1 IED connector ................................................................................................................ 16

3.1.1 Introduction ............................................................................................................. 16

3.1.2 Terminals of Analogue Input Module (AIM) ....................................................... 17

3.1.3 Terminals of Binary Input Module (BIM) ............................................................. 19

3.1.4 Terminals of Binary Output Module (BOM) ........................................................ 20

3.1.5 Terminals of Communication module (COM) .................................................... 24

3.1.6 Communication ports of CPU module (CPU) .................................................... 25

3.1.7 Terminals of Power Supply Module (PSM) ........................................................ 26

3.1.8 RS232 port ............................................................................................................. 27

3.2 Connecting to protective earth .................................................................................... 27

3.3 Connecting the power supply module ........................................................................ 27

3.4 Connecting to CT and VT circuits ............................................................................... 27

3.5 Connecting the binary inputs and outputs ................................................................. 27

3.6 Making the screen connection ..................................................................................... 29

3.7 Optical connections ....................................................................................................... 29

3.8 RS485 and RS232 ports connection .......................................................................... 30

3.8.1 RS485 port connection ......................................................................................... 30

3.8.2 RS232 port connection ......................................................................................... 30

3.9 Connecting the GPS ..................................................................................................... 31

4 Checking before energizing ......................................................................................................... 32

4.1 Introduction ..................................................................................................................... 32

Page 8: CSC-150 Busbar Protection IED Engineering and Operation Manual

4.2 Checking the protective earth connection .................................................................. 32

4.3 Checking the power supply connection ...................................................................... 32

4.4 Checking the CT and VT circuits connection ............................................................ 32

4.4.1 Checking the CT circuits connection .................................................................. 32

4.4.2 Checking the VT connection ................................................................................ 33

4.5 Checking the binary input and output connection ..................................................... 33

4.5.1 Checking the binary input connection ................................................................. 33

4.5.2 Checking the binary output connection .............................................................. 34

4.6 Checking the screened cables connection ................................................................ 34

4.7 Checking the optical connections ................................................................................ 34

4.8 Checking the S485 and RS232 port connectios ....................................................... 34

4.8.1 Checking the RS485 port connection ................................................................. 34

4.8.2 Checking RS232 port connection ........................................................................ 34

4.9 Checking GPS connection ........................................................................................... 34

4.10 Checking the insulation voltage and insulation resistance ...................................... 34

4.10.1 Checking the insulation voltage ........................................................................... 35

4.10.2 Checking the insulation resistance ..................................................................... 35

5 Checking after energizing ............................................................................................................. 36

5.1 Introduction ..................................................................................................................... 36

5.2 Test LCD ......................................................................................................................... 36

5.3 Test the keyboard .......................................................................................................... 36

5.4 Setting the IED time ...................................................................................................... 36

5.5 Self-supervision HMI data ............................................................................................ 37

5.6 Checking the software and hardware version ........................................................... 37

Chapter 4 Read and change setting .............................................................................................. 39

1 Read and change the setting vaule ............................................................................................ 40

1.1 Read and change the setting value via LHMI............................................................ 40

1.1.1 Introduction ............................................................................................................. 40

1.1.2 Communication parameter ................................................................................... 40

1.1.3 Equipment parameter ............................................................................................ 41

1.1.4 Setting values and binary settings for protection function ............................... 44

2 Switching the setting group .......................................................................................................... 45

2.1 Introduction ..................................................................................................................... 45

2.2 Method for switching setting group via LHMI ............................................................ 45

2.3 Method for switching setting group via binary input ................................................. 45

Chapter 5 Testing the communication connection and time synchronization ......................... 47

1 Testing the communication connection ...................................................................................... 48

1.1 Testing the Ethernet communication .......................................................................... 48

1.1.1 Testing the electrical Ethernet communication .................................................. 48

1.1.2 Testing the optical Ethernet communication ...................................................... 48

1.2 Testing the RS485 port ................................................................................................. 48

1.3 Testing the RS232 port ................................................................................................. 48

2 Testing the time synchronization ................................................................................................. 50

2.1 Network mode ................................................................................................................ 50

Page 9: CSC-150 Busbar Protection IED Engineering and Operation Manual

2.2 Pulse mode .................................................................................................................... 50

2.3 IRIG-B mode .................................................................................................................. 50

Chapter 6 IED testing ...................................................................................................................... 51

1 Introduction ..................................................................................................................................... 52

2 Points for attention during testing ............................................................................................... 54

3 Preparing for test ........................................................................................................................... 56

3.1 Introduction ..................................................................................................................... 56

3.2 Connecting test equipment to IED .............................................................................. 56

4 Testing the power supply .............................................................................................................. 58

4.1 Checking the self-startup performance ...................................................................... 58

4.2 DC power on and power off testing ............................................................................ 58

4.3 Checking the expiry date of power supply ................................................................. 58

5 Checking the analog channel ...................................................................................................... 59

5.1 Checking the zero drift .................................................................................................. 59

5.2 Calibrating ...................................................................................................................... 59

5.3 Checking the accuracy and the linearity of analog quantitis ................................... 60

5.4 Checking the polarity of analog quantities ................................................................. 60

6 Testing binary input ....................................................................................................................... 62

7 Testing binary output ..................................................................................................................... 63

8 Verifying the IED functions ........................................................................................................... 64

8.1 Differential protection .................................................................................................... 64

8.1.1 Verifying the settings ............................................................................................. 64

8.1.2 Completing the test ............................................................................................ 70

8.1.3 Reference setting list for test ............................................................................... 70

8.2 Circuit breaker failure protection ................................................................................. 71

8.2.1 Verifying the settings ............................................................................................. 71

8.2.2 Completing the test ............................................................................................... 75

8.2.3 Reference setting list for test ............................................................................... 75

8.3 Dead zone protection .................................................................................................... 83

8.3.1 Verifying the settings ............................................................................................. 83

8.3.2 Completing the test ............................................................................................... 84

8.3.3 Reference setting list for test ............................................................................... 84

8.4 Voltage transformer secondary circuit supervision .................................................. 86

8.4.1 Verifying the settings ............................................................................................. 86

8.4.2 Completing the test ............................................................................................... 88

8.4.3 Reference setting list for test ............................................................................... 89

9 Checking before operation ........................................................................................................... 90

9.1 Checking the LED ......................................................................................................... 90

9.2 Checking the display on LCD ...................................................................................... 90

9.3 Checking the clock ........................................................................................................ 90

9.4 Checking the voltage and current ............................................................................... 90

9.5 Checking the setting group .......................................................................................... 90

9.6 Checking the setting ..................................................................................................... 90

9.7 Checking the binary input ............................................................................................. 91

Page 10: CSC-150 Busbar Protection IED Engineering and Operation Manual

9.8 Checking the normal operation mode ......................................................................... 91

9.8.1 Trip and close test with the circuit breaker ......................................................... 91

9.9 Put into operation ........................................................................................................... 91

Chapter 7 Operating maintenance ................................................................................................ 93

1 Attentions during operating .......................................................................................................... 94

2 Routine checking ........................................................................................................................... 96

3 Periodical checking ....................................................................................................................... 97

4 Operation after updating software or replacing modules ......................................................... 98

4.1 Operation after updating software or replacing CPU module ................................. 98

4.2 Operation after updating software or replacing communication module ............... 98

4.3 Operation after replacing the binary input or output module ................................... 99

4.4 Operation after replacing the analog input module .................................................. 99

4.5 Operation after replacing power supply module ....................................................... 99

5 The alarm information and measure ......................................................................................... 100

5.1 Alarm information ......................................................................................................... 100

Chapter 8 Transportation and storage ........................................................................................ 103

1 Transportion.................................................................................................................................. 104

2 Storage .......................................................................................................................................... 105

Chapter 9 Appendix ....................................................................................................................... 107

1 Arrangement diagram of modules ............................................................................................. 108

2 Typical diagram ............................................................................................................................ 109

Page 11: CSC-150 Busbar Protection IED Engineering and Operation Manual

Chapter 1 IED Introduction

1

Chapter 1 IED Introduction

About this chapter

This chapter presents the overview of the engineering and operation about

the IED.

Page 12: CSC-150 Busbar Protection IED Engineering and Operation Manual

Chapter 1 IED Introduction

2

The Human Machine Interface (HMI) on the IED provides an ideal

mechanism for the day to day operation and even advanced use of the IED.

The keyboard, LCD and LEDs on the front of the IED are what constitute the

HMI. Troubleshooting, monitoring, setting and configuring are all possible via

this interface. Through the screens and menu elements available, as well as

the keypad, the user is able to navigate throughout the menu structure and

move from screen to screen.

The IED is unpacked and visually checked. The connection to the protection

system has to be checked in order to verify that the installation is successful.

The settings for each function must be calculated before the commissioning

task. The functions setting menu have been listed in detail so that the user

can find and change the required settings directly and correctly. For the

different application, the IED can be performed conveniently through

switching the setting group.

For the functions included in the IED can be tested by users, the testing

procedure have been listed as reference to verify that protection function

operate correctly.

After the IED is in service, some checking items also need to be done for

maintenance in order to ensure that the IED is in good condition during

operation, some suggestions have been preset as reference and the user can

perform some other checking items according to the relevant regulations.

Page 13: CSC-150 Busbar Protection IED Engineering and Operation Manual

Chapter 2 Local human machine interface

3

Chapter 2 Local human machine

interface

About this chapter

This chapter describes the structure of human-machine interface (HMI), LCD,

LED, keyboard, RS232 and IED menu. Instruction on how to operate with

keys, how to configure the LED and menu information introduction.

Page 14: CSC-150 Busbar Protection IED Engineering and Operation Manual

Chapter 2 Local human machine interface

4

1 Introduction

The HMI is simple and easy to be used for routine operation, the front panel

of the HMI consists of LCD, LED and keyboard. As shown in the following

picture, the setting, configuration, monitoring, maintenance and fault analysis

can be performed in HMI.

1

2

3

45

68 7

CSC-150

Figure 1 IFront plate with 8 LEDs

Page 15: CSC-150 Busbar Protection IED Engineering and Operation Manual

Chapter 2 Local human machine interface

5

1

2

3

45

68 7

CSC-150

Figure 2 Front plate with 20 LEDs

1. Liquid crystal display (LCD)

2. LEDs

3. Shortcut function keys

4. Arrow keys

5. Reset key

6. Quit key

7. Set key

8. RS232 communication port

Page 16: CSC-150 Busbar Protection IED Engineering and Operation Manual

Chapter 2 Local human machine interface

6

2 Liquid crystal display(LCD)

The LCD back light of HMI is blue, 8 lines with up to 28 characteristics per line

can be displayed.

When operating keys are pressed or in the case of IED alarming or operating

report appearance, the back light will turn on automatically until the preset

time delay elapse after the latest operation or alarm.

Page 17: CSC-150 Busbar Protection IED Engineering and Operation Manual

Chapter 2 Local human machine interface

7

3 Keyboard

The keyboard is used to monitor and operate IED. The keyboard has the

same look and feel in CSC family. As shown in Figure 1, keyboard is divided

into Arrow keys, Reset key, Quit key, Set key and shorcut function keys. The

specific instructions on the keys as the following table described:

Table 1 HMI keys on the front of the IED

Key Function

Up arrow key Move up in menu

Page up between screens

Increase value in setting

Down arrow key Move down in menu

Page down between screens

Decrease value in setting

Left arrow key Move left in menu

Right arrow key Move Right in menu

Reset key Reset the LEDs

Return to normal scrolling display state directly

Set key Enter main menu or submenu

Confirm the setting change

Quit key Back to previous menu

Cancel the current operation and back to previous menu

Return to scrolling display state

Lock or unlock current display in the scrolling display state (the

lock state is indicated by a key type icon on the upright corner of

the LCD)

Page 18: CSC-150 Busbar Protection IED Engineering and Operation Manual

Chapter 2 Local human machine interface

8

4 IED menu

4.1 Menu construction

OpStatus

QueryRpt

Set Time

Contrast

Settings

Setup

Test BO

Testing

AI Version

BI

Impen.Z

EquipCode

Measure

EventRpt AlarmRpt

Log

Cur Time Set Time

TestEffect

Protocol

ModifyPW

SOEReset

SetPrint

103Type

ProtSet

EquipPara

SimuReSig SwSetGr

ViewDrift AdjDrift

ViewScale AdjScale

PrtSample

CommuPara

ProtContWdMainMenu

Test Menu

AI DisplaySet

StartRpt

Page 19: CSC-150 Busbar Protection IED Engineering and Operation Manual

Chapter 2 Local human machine interface

9

Table 2 Full name for the menu

Sub-menu Full name Sub-sub menu Full name

OpStatus Operation status

AI Analog input

EquipCode Equipment code

Measure Measurement quantity

Version IED version

BI Binary input

Impen.Z Impedance value

QueryRpt Query reports

EventRpt Event reports

AlarmRpt Alarm reports

StartRpt Startup report

Log Operation logging

Set time Setting time Cur Time Current time

Set Time Set time

Contrast LCD contrast TestEffect Test effect

Settings Setting value

CommuPara Communication parameter

ProtSet Protection setting

Test menu Test menu

EquipPara Equipment parameter

PortContwd Protection binary setting

Setup IED setting

SOEReset SOE reset selection

ModifyPW Modify password

SetPrint Setting the print

Protocol Protocol selection

103Type 103 function type

Test BO Test binary output

Testing Testing operation

SimuReSig Simulation remote signalization

ViewDrift View zero drift

ViewScale View scale

PrtSample Print sample value

SwSetGr Switch setting group

AdjDrift Adjust zero drift

AdjScale Calibrating

4.2 Operation status

Sub menu Sub-sub menu Explanation

OpStatus

AI Read the secondary analogue of the selected CPU

module

EquipCode Read the versions, released time and CSC code of all

modules

Page 20: CSC-150 Busbar Protection IED Engineering and Operation Manual

Chapter 2 Local human machine interface

10

Sub menu Sub-sub menu Explanation

Measure Read the analogue value and calculation value

Version Read the IED type, date and CPU version

BI Read the current status of binary inputs, “Off” or “On”

Impen.Z Read the impedace value of real and imaginary parts,

including: Za , Zb , Zc , Zab , Zbc , Zca

4.3 Query reports

Sub

menu

Sub-sub menu Sub-sub-sub

menu

Explanation

QueryRpt

EventRpt Latest Rpt Query the latest event report, press the Set

key to see the report

Last 6 Rpts Query the latest six event reports, press the

Set key to see the report

QueryRpt by

Date Query the reports by date

AlarmRpt Last 6 Rpts Query the latest six alarm reports, press the

Set key to see the report

QueryRpt by

Date Query the reports by date

StartRpt

Latest Rpt Query the latest event report, press the Set

key to see the report

Last 6 Rpts Query the latest six event reports, press the

Set key to see the report

QueryRpt by

Date Query the reports by date

Log Last 6 Rpts Query the latest six operation reports, press

the Set key to see the report

QueryRpt by

Date Query the reports by date

4.4 Set time

Sub menu Sub-sub menu Explanation

Set time Cur Time

Modify the time with arrow keys Set Time

4.5 Contrast

Page 21: CSC-150 Busbar Protection IED Engineering and Operation Manual

Chapter 2 Local human machine interface

11

Sub menu Sub-sub menu Explanation

Contrast TestEffect Modify the contrast with arrow keys

4.6 Settings

Sub

menu

Sub-sub menu Sub-sub-sub

menu

Explanation

Settings

CommuPara

BayName Enter into the line name

TimeMode NetworkTimeMode

PulseTimeMode

IRIG-B TimeMode

CommAddr Enter into the LON and RS485 address, and

the Ethernet 1 and Ethernet 2 address

BaudR485 Selection with up or down buttons

ProtSet

Common Common protection setting in this menu

Current Protection setting relation with current in this

menu

CBF Protection setting relation with CBF in this

menu

Distance Distance protection setting in this menu

Voltage Protection setting relation with voltage in this

menu

Reclose Protection setting relation with reclosure in

this menu

Test Menu

EquipPara

PortContwd

Common Common protection binary setting in this

menu

Current Protection binary setting relation with current

in this menu

CBF Protection binary setting relation with CBF in

this menu

Distance Distance protection binary setting in this

menu

Voltage Protection binary setting relation with

voltage in this menu

Reclose Protection binary setting relation with

reclosure in this menu

4.7 IED setting

Page 22: CSC-150 Busbar Protection IED Engineering and Operation Manual

Chapter 2 Local human machine interface

12

Sub

menu

Sub-sub menu Sub-sub-sub

menu

Explanation

Setup

SOEReset

Manual Reset

Automatic

Reset

Really Reset

ModifyPW The fatory password: 8888

103Type IEC60870-5-103 code

Protocol If communication with automation system

via RS485 port, this item can be ignored

SetPrint RecPrt Setup

Print Mode

AI DisplaySet Display Sec Ai Display secondary analog input quantity

Display Pri Ai Display primary analog input quantity

4.8 Test binary output

Sub

menu

Sub-sub menu Sub-sub-sub

menu

Explanation

Test BO

4.9 Testing operation

Sub

menu

Sub-sub menu Sub-sub-sub

menu

Explanation

Testing

SimuReSig

Simu Alarm

Using“√” or “X” to select the simulation point

Simu Connt

TransRecData

Simu Trip

Simu BI

Simu MST

Alarm

ViewDrift

Enter into the CPU number

ViewScale

PrtSample

SwSetGr

AdjDrift

AdjScale

Page 23: CSC-150 Busbar Protection IED Engineering and Operation Manual

Chapter 3 Installing IED

13

Chapter 3 Installing IED

About this chapter

This chapter describes how to install the protection IED, introduces

connection of the contactor, analogue quantities, binary inputs and outputs

and power supply, and what should to do before and after energizing.

Page 24: CSC-150 Busbar Protection IED Engineering and Operation Manual

Chapter 3 Installing IED

14

1 Unpacking and checking the IED

Procedure:

1. Remove the transporting case

2. Visually inspect the IED

3. Check all items included in accordace with the delivery documents. Once

the IED has been started make sure that the software functions ordered

have been included in the delivery

4. Check for transport damages

If transport damage is discovered appropriate action must be taken

against the latest carrier and the latest SiFang office or representative

should be informed. If there are any discrepancies in relation to the

delivery documents, the SiFang company should be notified immediately

5. If the protection IED is repacked for transport again, the storage packing

of the IED must provide proper degree of protection against possible

damage, in accordance with the standard of IEC 60255-21-1 class 1 and

IEC 60255-21-2 class 1

Page 25: CSC-150 Busbar Protection IED Engineering and Operation Manual

Chapter 3 Installing IED

15

2 Installing the IED

Procedure:

1. Insert the IED into cabinet and the bottom of the IED should be supported

on the frame of cabinet

2. Fix the IED by tightening all screws against the cabinet. The IED should

be fixed in the cabinet and each screw should be firmed

3. Connect the earthing screw on the rear panel to the nearest protective

earthing point in the cubicle. The protective earth cables should be green

or yellow conductors with cross-sectional area 2.5mm2 according to

electrical regulations and electrical standards requirement

The cubicle must be properly connected to station earthing system, using

the conductor with cross-sectional area of at least 4mm2.

4. Power supply module connection

The wiring from the cubicle terminal block to the IED terminals must be

connected in accordance with the established guidelines for this type of

IED. The wires from binary inputs and outputs and the auxiliary power

supply must be routed separated from the current transformer cables

between the terminal blocks of the cubicle and the IEDs connections.

5. Connection to CT and VT circuits

CT and VT are connected to the analogue input module on the rear side

of the IED.

Using solid conductor with cross-sectional 2.5-6mm2 (AWG14-10) or

stranded conductor with cross-sectional 2.5-4mm2 (AWG14-12). The

screws used for fixation conductor should be tightened.

6. Connecting the binary input and output signals

Auxiliary power supply and binary input and output signals are connected

using female connectors. Signal wires are connected to a female

connector, which is then plugged into the corresponding male connector,

located at the rear of the IED.

Page 26: CSC-150 Busbar Protection IED Engineering and Operation Manual

Chapter 3 Installing IED

16

3 IED connection

3.1 IED connector

3.1.1 Introduction

The quantity and designation of connectors depend upon the ordering

information and application. The rear cover plates are prepared with enough

space for each configuration in ordering information and the cut-outs that are

not in use are covered with a plate from factory.

Page 27: CSC-150 Busbar Protection IED Engineering and Operation Manual

Chapter 3 Installing IED

17

3.1.2 Terminals of Analogue Input Module (AIM)

b01 a01

b02 a02

b03 a03

a04b04

a05b05

a06b06

a07b07

a08b08

a09b09

a10b10

a11b11

ab

Figure 3 Terminals arrangement of AIM A

Table 3 Description of terminals of AIM

Terminal Analogue

Input Remark

a01 I1 Star point

b01 I’1

a02 I2 Star point

b02 I’2

a03 Null

b03 Null

a04 Null

b04 Null

a05 U3B Star point

b05 U3C Star point

a06 U3A Star point

b06 U3N

a07 U2B Star point

b07 U2C Star point

a08 U2A Star point

b08 U2N

a09 U1B Star point

b09 U1C Star point

a10 U1A Star point

b10 U1N

a11 Null

b11 Null

Page 28: CSC-150 Busbar Protection IED Engineering and Operation Manual

Chapter 3 Installing IED

18

b01 a01

b02 a02

b03 a03

a04b04

a05b05

a06b06

a07b07

a08b08

b09

b10

b11

ab

a10

a11

a09

Figure 4 Terminals arrangement of AIM H

Table 4 Description of terminals of AIM H

Terminal Analogue

Input Remark

a01 I1 Star point

b01 I’1

a02 I2 Star point

b02 I’2

a03 I3 Star point

b03 I’3

a04 I4 Star point

b04 I’4

a05 I5 Star point

b05 I’5

a06 I6 Star point

b06 I’6

a07 I7 Star point

b07 I’7

a08 I8 Star point

b08 I’8

a09 I9 Star point

b09 I’9

a10 I10 Star point

b10 I’10

a11 Null

b11 Null

Page 29: CSC-150 Busbar Protection IED Engineering and Operation Manual

Chapter 3 Installing IED

19

3.1.3 Terminals of Binary Input Module (BIM)

c02 a02

c04 a04

c06 a06

a08c08

a10c10

a12c12

a14c14

a16c16

a18c18

a20c20

a22c22

a24c24

a26c26

a28c28

a30c30

a32c32

ac

DC -DC -

Figure 5 Terminals arrangement of BIM

Table 5 Description of terminals of BIM

Terminal Definition Remark

a02 BI1 BI group 1

c02 BI2 BI group 2

a04 BI3 BI group 1

c04 BI4 BI group 2

a06 BI5 BI group 1

c06 BI6 BI group 2

a08 BI7 BI group 1

c08 BI8 BI group 2

a10 BI9 BI group 1

c10 BI10 BI group 2

a12 BI11 BI group 1

c12 BI12 BI group 2

a14 BI13 BI group 1

c14 BI14 BI group 2

a16 BI15 BI group 1

c16 BI16 BI group 2

a18 BI17 BI group 1

c18 BI18 BI group 2

a20 BI19 BI group 1

c20 BI20 BI group 2

a22 BI21 BI group 1

c22 BI22 BI group 2

a24 BI23 BI group 1

c24 BI24 BI group 2

a26 BI25 BI group 1

c26 BI26 BI group 2

a28 BI27 BI group 1

c28 BI28 BI group 2

a30 BI29 BI group 1

c30 BI30 BI group 2

a32 DC - Input

Common

terminal of BI

group 1

c32 DC - Input

Common

terminal of BI

group 2

Page 30: CSC-150 Busbar Protection IED Engineering and Operation Manual

Chapter 3 Installing IED

20

3.1.4 Terminals of Binary Output Module (BOM)

Binary Output Module A

The module provides 16 output relays for tripping or initiating, with total 16 contacts.

a02

R

1

a04

a06

a08

a10

a12

a14

a16

a18

a20

a22

a24

a26

a28

a30

a32

ac

c02

c04

c06

c08

c10

c12

c14

c16

c18

c20

c22

c24

c26

c28

c30

c32

R

3

R

5

R

7

R

9

R

11

R

13

R

15

R

16

R

2

R

4

R

6

R

8

R

10

R

12

R

14

Figure 6 Terminals arrangement of BOM A

Page 31: CSC-150 Busbar Protection IED Engineering and Operation Manual

Chapter 3 Installing IED

21

Table 6 Description of terminals of BOM A

Terminal Definition Related relay

a02 Trip contact 1-0 Output relay 1

c02 Trip contact 1-1 Output relay 1

a04 Trip contact 2-0 Output relay 2

c04 Trip contact 2-1 Output relay 2

a06 Trip contact 3-0 Output relay 3

c06 Trip contact 3-1 Output relay 3

a08 Trip contact 4-0 Output relay 4

c08 Trip contact 4-1 Output relay 4

a10 Trip contact 5-0 Output relay 5

c10 Trip contact 5-1 Output relay 5

a12 Trip contact 6-0 Output relay 6

c12 Trip contact 6-1 Output relay 6

a14 Trip contact 7-0 Output relay 7

c14 Trip contact 7-1 Output relay 7

a16 Trip contact 8-0 Output relay 8

c16 Trip contact 8-1 Output relay 8

a18 Trip contact 9-0 Output relay 9

c18 Trip contact 9-1 Output relay 9

a20 Trip contact 10-0 Output relay 10

c20 Trip contact 10-1 Output relay 10

a22 Trip contact 11-0 Output relay 11

c22 Trip contact 11-1 Output relay 11

a24 Trip contact 12-0 Output relay 12

c24 Trip contact 12-1 Output relay 12

a26 Trip contact 13-0 Output relay 13

c26 Trip contact 13-1 Output relay 13

a28 Trip contact 14-0 Output relay 14

c28 Trip contact 14-1 Output relay 14

a30 Trip contact 15-0 Output relay 15

c30 Trip contact 15-1 Output relay 15

a32 Trip contact 16-0 Output relay 16

c32 Trip contact 16-1 Output relay 16

Page 32: CSC-150 Busbar Protection IED Engineering and Operation Manual

Chapter 3 Installing IED

22

Binary Output Module C

The module provides 16 output relays for signal, with total 19 contacts.

a02

a04

a06

a08

a10

a12

a14

a16

a18

a20

a22

a24

a26

a28

a30

a32

ac

c02

c04

c06

c08

c10

c12

c14

c16

c18

c20

c22

c24

c26

c28

c30

c32

R

4

R

5

R

1

R

2

R

3

R

6

R

7

R

16

R

9

R

10

R

11

R

12

R

13

R

14

R

15

R

8

Figure 7 Terminals arrangement of BOM C

Page 33: CSC-150 Busbar Protection IED Engineering and Operation Manual

Chapter 3 Installing IED

23

Table 7 Description of terminals of BOM C

Terminal Definition Related relay

a02 Signal 1-0, Common terminal of signal contact group 1

c02 Signal 2-0, Common terminal of signal contact group 2

a04 Signal contact 1-1 Output relay 1

c04 Signal contact 2-1 Output relay 1

a06 Signal contact 1-2 Output relay 2

c06 Signal contact 2-2 Output relay 2

a08 Signal contact 1-3 Output relay 3

c08 Signal contact 2-3 Output relay 3

a10 Signal 3-0, Common terminal of signal contact group 3

c10 Signal 4-0, Common terminal of signal contact group 4

a12 Signal contact 3-1 Output relay 4

c12 Signal contact 4-1 Output relay 7

a14 Signal contact 3-2 Output relay 5

c14 Signal contact 4-2 Output relay 6

a16 Signal contact 5-0 Output relay 8

c16 Signal contact 5-1 Output relay 8

a18 Signal contact 6-0 Output relay 9

c18 Signal contact 6-1 Output relay 9

a20 Signal contact 7-0 Output relay 10

c20 Signal contact 7-1 Output relay 10

a22 Signal contact 8-0 Output relay 11

c22 Signal contact 8-1 Output relay 11

a24 Signal contact 9-0 Output relay 12

c24 Signal contact 9-1 Output relay 12

a26 Signal contact 10-0 Output relay 13

c26 Signal contact 10-1 Output relay 13

a28 Signal contact 11-0 Output relay 14

c28 Signal contact 11-1 Output relay 14

a30 Signal contact 12-0 Output relay 15

c30 Signal contact 12-1 Output relay 15

a32 Signal contact 13-0 Output relay 16

c32 Signal contact 13-1 Output relay 16

Page 34: CSC-150 Busbar Protection IED Engineering and Operation Manual

Chapter 3 Installing IED

24

3.1.5 Terminals of Communication module (COM)

01

02

03

04

05

06

07

08

09

10

11

12

13

14

15

16

Ethernet port B

Ethernet port A

Ethernet port C

Figure 8 Terminals arrangement of COM

5

6

7

8

9

10Ethernet

port

Figure 9 Examples of COM module

Table 8 Description of terminals of COM

Terminal Definition

01 Null

02 Null

03 Null

04 Null

05 Optional RS485 port - 2B

06 Optional RS485 port - 2A

07 Optional RS485 port - 1B

08 Optional RS485 port - 1A

09 Time synchronization

10 Time synchronization GND

11 Null

12 Null

13 Null

14 Null

15 Null

16 Null

Ethernet

Port A

Optional optical fiber or RJ45

port for station automation

system

Ethernet

Port B

Optional optical fiber or RJ45

port for station automation

system

Ethernet

Port C

Optional optical fiber or RJ45

port for station automation

system

Page 35: CSC-150 Busbar Protection IED Engineering and Operation Manual

Chapter 3 Installing IED

25

3.1.6 Communication ports of CPU module (CPU)

RX

TX

RX

TX

Ch A

Ch B

Figure 10 Communication ports

arrangement of CPU module

Figure 11 Examples of CPU module

Table 9 Definition of communication ports

of CPU module

Ports Definition

Ch A RX Remote communication

channel A optical fiber data

receiving port

Ch A TX Remote communication

channel A optical fiber data

transmitting port

Ch B RX Remote communication

channel B optical fiber data

receiving port

Ch B TX Remote communication

channel B optical fiber data

transmitting port

Note: These ports are optional.

Page 36: CSC-150 Busbar Protection IED Engineering and Operation Manual

Chapter 3 Installing IED

26

3.1.7 Terminals of Power Supply Module (PSM)

c02 a02

c04 a04

c06 a06

a08c08

a10c10

a12c12

a14c14

a16c16

a18c18

a20c20

a22c22

a24c24

a26c26

a28c28

a30c30

a32c32

ac

DC 24V +

OUTPUTS

DC 24V -

OUTPUTS

AUX.DC +

INPUT

AUX. DC -

INPUT

Figure 12 Terminals arrangement of PSM

Table 10 Description of terminals of PSM

Terminal Definition

a02 AUX.DC 24V+ output 1

c02 AUX.DC 24V+ output 2

a04 AUX.DC 24V+ output 3

c04 AUX.DC 24V+ output 4

a06 Isolated terminal, not wired

c06 Isolated terminal, not wired

a08 AUX.DC 24V- output 1

c08 AUX.DC 24V- output 2

a10 AUX.DC 24V- output 3

c10 AUX.DC 24V- output 4

a12 AUX.DC 24V- output 5

c12 AUX.DC 24V- output 6

a14 Alarm contact A1, for

AUX.DC power input failure

c14 Alarm contact A0, for

AUX.DC power input failure

a16 Alarm contact B1, for

AUX.DC power input failure

c16 Alarm contact B0, for

AUX.DC power input failure

a18 Isolated terminal, not wired

c18 Isolated terminal, not wired

a20 AUX. power input 1, DC +

c20 AUX. power input 2, DC +

a22 AUX. power input 3, DC +

c22 AUX. power input 4, DC +

a24 Isolated terminal, not wired

c24 Isolated terminal, not wired

a26 AUX. power input 1, DC -

c26 AUX. power input 2, DC -

a28 AUX. power input 3, DC -

c28 AUX. power input 4, DC -

a30 Isolated terminal, not wired

c30 Isolated terminal, not wired

a32 Terminal for earthing

c32 Terminal for earthing

Page 37: CSC-150 Busbar Protection IED Engineering and Operation Manual

Chapter 3 Installing IED

27

3.1.8 RS232 port

RS232 serial port is located on front panel, the software tool in PC can be

connected with the IED via this port to make setting, testing and cofiguration,

etc.

3.2 Connecting to protective earth

Connect the earthing screw on the rear panel to the nearest protective

earthing point in the cubicle. The protective earth cables should be green or

yellow conductors with cross-sectional area 2.5mm2 according to electrical

regulations and electrical standards requirement.

The cubicle must be properly connected to station earthing system, using the

conductor with cross-sectional area of at least 4mm2.

3.3 Connecting the power supply module

The wiring from the cubicle terminal block to the IED terminals must be

connected in accordance with the established guidelines for this type of IED.

The wires from binary inputs and outputs and the auxiliary power supply must

be routed separated from the current transformer cables between the terminal

blocks of the cubicle and the IEDs connections.

3.4 Connecting to CT and VT circuits

CT and VT are connected to the analogue input module on the rear side of

the IED.

Using solid conductor with cross-sectional 2.5-6mm2 (AWG14-10) or stranded

conductor with cross-sectional 2.5-4mm2 (AWG14-12). The screws used for

fixation conductor should be tightened.

3.5 Connecting the binary inputs and outputs

Auxiliary power supply and binary input and output signals are connected

using female connectors. Signal wires are connected to a female connector,

which is then plugged into the corresponding male connector, located at the

Page 38: CSC-150 Busbar Protection IED Engineering and Operation Manual

Chapter 3 Installing IED

28

rear of the IED.

Procedure:

1. Connect signals to the female connector

All wiring to the female connector should be done before it is plugged into

the male part and screwed to the case. The conductors can be of rigid

type (solid, stranded) or of flexible type.

The female connectors accept conductors with a cross section area of

0.2-1.5 mm2 (AWG 24-15). If two conductors are used in the same

terminal, the maximum permissible cross section area is 0.2-0.8 mm2

(AWG 24-18, each conductor corresponding to one cross section area).

If two conductors, each with area 1.5 mm2 (AWG 15) need to be

connected to the same terminal, a ferrule must be used to combine the

two conductors, no soldering is needed.

Press the locking button by screwdriver to insert the wiring with ferrule

into the connector, move away the screwdriver after the ferrule has been

inserted into the connector completely to lock the wiring tightly. The follow

picture illustrate this process.

Figure 13 Connection illustration without inserting the connector

Page 39: CSC-150 Busbar Protection IED Engineering and Operation Manual

Chapter 3 Installing IED

29

Figure 14 Connection illustration with inserting the connector

2. Plug the connector to the corresponding back-side mounted male

connector

3. Lock the connector by fastening the lock screws

3.6 Making the screen connection

When using screened cables always make sure screens are earthed and

connected according to applicable engineering methods. This may include

checking for appropriate earth points near the IED, for instance, in the cubicle

and/or near the source of measuring. Ensure that earth connections are

made with short conductors of an adequate cross section, at least 6 mm2

(AWG10) for single screen connections.

3.7 Optical connections

This port is used to transmit the binary data between IEDs, there are two

optical ports at the rear side of CPU moduel, Figure 10 and Figure 11, the

two ports works in redundancy communication mode.

Page 40: CSC-150 Busbar Protection IED Engineering and Operation Manual

Chapter 3 Installing IED

30

The fiber optical cables are very sensitive to handling. Do not bend

too sharply. If cable straps are used to fix the cables, apply with

loose fit. Always hold the connector, never the cable, when

connecting or disconnecting optical fibers. Do not twist, pull or bend

the fiber. Invisible damage may increase fiber attenuation thus

making communication impossible.

Strictly follow the instructions from manufacture for each type of

optical cables or connectors.

3.8 RS485 and RS232 ports connection

3.8.1 RS485 port connection

The RS485 interface is capable of half-duplex service with the signals A/A'

and B/B' to transmit signals.

The network topology of RS485 adopts bus type of terminal matched, do not

support ring or star network. Use the single and continuous channel as bus.

The terminating resistance is located on beginning and terminal of the bus

cable. The other ports do not need the terminating resistance.

As shown in Figure 8 and Figure 9, RS485 port located on the rear side of

communication module. The IED provides two electrical isolation RS485

ports, the two ports can work at the same time with IEC60870-5-103 protocol

supported.

3.8.2 RS232 port connection

One RS232 serial port is provided and located on front panel, which is used to

connect personal computer. The RS232 port adopts half-dupex

communication mode, usually which is connected with 9-pin D-subminiature

female connectors

Connection method: direction connection cable for serial port, the IED

terminal is pins and the PC termianl is female connector. The terminal of 2, 3,

4 and 5 is connected directly. As shown in the following picture:

Page 41: CSC-150 Busbar Protection IED Engineering and Operation Manual

Chapter 3 Installing IED

31

Figure 15 Example for serial port connection

The line 4 must be connected directly

3.9 Connecting the GPS

Mount the GPS antenna on the building roof or the place of visibility to all

direction is obtained, top of the antenna should be horizontal. Mount the

antenna to console and fix the console on the building roof with expansion

bolts. The turning radius should not be too small when laying the cables. The

length of antenna cables is designed strictly based on antenna gain, so, it is

not allowed to lengthen, shorten or add connectors that will affect signal

reception or can't receive any signals.

The principle for mounting GPS antenna is that the position is visible

completely to all directions in 360°, however, for some special conditions,

mount the antenna at the place with best visibility as far as possible.

The GPS port is located on the rear side of communication module, as shown

in Figure 8 and Figure 9, which can be connected with screened twist-pair

cable.

Page 42: CSC-150 Busbar Protection IED Engineering and Operation Manual

Chapter 3 Installing IED

32

4 Checking before energizing

4.1 Introduction

After completing the IED connections, the related connections need to be

checked, this section descirbes what should be checked before energizing.

This is done with IED and all connected circuits de-energized.

4.2 Checking the protective earth connection

Check the protective earthing connection of IED is connected reliably in

accordance with the related electrical regulations and standards.

4.3 Checking the power supply connection

Check that the auxiliary power supply voltage remains within the permissible

input voltage range under all operating conditions. Check that the polarity is

correct.

4.4 Checking the CT and VT circuits connection

4.4.1 Checking the CT circuits connection

Check that the wiring is in strict accordance with the supplied connection

diagram. If any errors appearance, do not continue before any errors are

corrected. The following tests shall be performed on every primary CT

connected to IED:

Primary injection test to verify the current change ratio of the CT, the

correct wiring up to the protection IED and correct phase sequence

connection (i.e. A, B, C)

Polarity checking to prove that the predicted direction of secondary

current flow is correct for a given direction of primary current flow

CT secondary loop resistance measurement in order to confirm that the

current transformer secondary loop DC resistance is within specification

and that there are no high resistance joints in the CT winding or wiring

Page 43: CSC-150 Busbar Protection IED Engineering and Operation Manual

Chapter 3 Installing IED

33

CT excitation test in order to confirm that the current transformer is of the

correct accuracy rating and that there are no shorted turns in the current

transformer windings. Manufacturer's design curves should be available

for the current transformer in order to compare the actual results

Check the earthing of the individual CT secondary circuits to verify that

each three-phase set of main CTs is properly connected to the station

earth and only at one electrical point

Checking the insulation resistance

Phase identification of CT shall be made

Both primary and secondary sides must be disconnected from the

line and IED when plotting the excitation characteristics

If the CT secondary circuit earth connection is removed without the

current transformer primary being de-energized, dangerous voltages

may result in the secondary CT circuits

4.4.2 Checking the VT connection

Check that the wiring is in strict accordance with the supplied connection

diagram. If any errors appearance, do not continue before any errors are

corrected.

The following tests are recommended:

Polarity check

VT circuit voltage measurement (primary injection test)

Grounding check

Phase relationship

Insulation resistance check

4.5 Checking the binary input and output connection

4.5.1 Checking the binary input connection

Page 44: CSC-150 Busbar Protection IED Engineering and Operation Manual

Chapter 3 Installing IED

34

When checking the binary inputs, it's better to disconnect the binary input

connector from binary input module. Check all connected signals in order to

make sure that both the input level and polarity of voltage are in accordance

with the IEDs specifications.

4.5.2 Checking the binary output connection

When checking the binary outputs, it's better to disconnect the binary output

connector from binary output module. Check all connected signals in order to

make sure that both the input level and polarity of voltage are in accordance

with the IEDs specifications.

4.6 Checking the screened cables connection

Check that the screened cables are connected correctly.

4.7 Checking the optical connections

Check that the Tx and Rx optical connections are correct.

4.8 Checking the S485 and RS232 port connectios

4.8.1 Checking the RS485 port connection

Check that the RS485 port connections are correct.

4.8.2 Checking RS232 port connection

Check that the RS232 serial port connections are correct.

4.9 Checking GPS connection

Check that the GPS connections are correct.

4.10 Checking the insulation voltage and insulation resistance

Page 45: CSC-150 Busbar Protection IED Engineering and Operation Manual

Chapter 3 Installing IED

35

4.10.1 Checking the insulation voltage

Using the withstand voltage tester to apply correspondung level voltage

between tested circuit and earth, and between circuits (e.g. 2000VAC

/2800VDC), lasting 1 min. No flashover and breakdown apperance, the

leakage current is less than 10mA.

4.10.2 Checking the insulation resistance

Using a rotating meter with 500V to test insulation resistance in turn between

analog circuits and earth, and the circuits to each other. Every resistance

must not be less than 100 MΩ. And the lasting time for resistance test is not

less than 5s to ensure that the value of insulation resistance is read in a

steady state.

Page 46: CSC-150 Busbar Protection IED Engineering and Operation Manual

Chapter 3 Installing IED

36

5 Checking after energizing

5.1 Introduction

After completing of the external circuits connection, checking all connections

and energizing the IED, LCD and keyboard should be tested. Check that the

software version, serial number and the installed modules are in accordance

with ordering information. The IED time need to be set to ensure that the IED

time is synchronized with local time. The self-supervision function should also

be checked to verify that the IED operates properly.

5.2 Test LCD

After energizing the IED, the blue back light of LCD light up, operate the keys

to turn pages to check that the LCD display is correct.

5.3 Test the keyboard

All the keys on front panel including Arrow keys, Reset key, Set key, Quit key

and shortcut key can be operated to check that these keys satisfy with the

correpsonding function, the detail functions of each key are described in

Table 1.

5.4 Setting the IED time

This procedure describes how to set the IED time from the local HMI.

1. Enter into the time setting menu: Set Time, press the Set button to enter

into the setting menu

2. Set the date and time

Use the Left and Right arrow buttons to move between the time and date

values (year, month, day, hours, minutes and seconds). Use the Up and

Down arrow buttons to change the value.

3. Confirm the setting

Press the Set button to set the data and clock to the new values.

Page 47: CSC-150 Busbar Protection IED Engineering and Operation Manual

Chapter 3 Installing IED

37

5.5 Self-supervision HMI data

Table 11 Self-supervision HMI data

Information Detail information Possible reason and solutions

Communication

Fail

Communication

Failure

Communication fails between CPU and COM module.

In this condition either the CPU is working abnormal or

the CAN (Controller Area Network) network

communication has been interruptted. Check each

CPU working state or CAN network on backboard.

Write Set Fail Write setting failure Write setting again

Write DevPara Fail Write Device

parameter failure Write device parameter again

No response for calling CPU configuration

Maybe the address of two CPU modules are same,

one of the two modules is not inserted or connected

badly

Alarming code XX One of the CPU modules is disabled

5.6 Checking the software and hardware version

Enter into menu: OpStatus/EquipCode

Checking the software version: In this menu, to check the protection

programm version.

Check the hardware version: In this menu, to check the equipment code, the

version of binary input and output module, communication module and HMI.

Page 48: CSC-150 Busbar Protection IED Engineering and Operation Manual

Chapter 3 Installing IED

38

Page 49: CSC-150 Busbar Protection IED Engineering and Operation Manual

Chapter 4 Read and change setting

39

Chapter 4 Read and change setting

About this chapter

This chapter describes how to set and read the setting values and parameters

either through LHMI or software tool, and how to switch the setting value

group.

This chapter does not contain instructions on how to calculate the setting

value, for the detail setting calculation information please refer to the

Technical application manual.

Page 50: CSC-150 Busbar Protection IED Engineering and Operation Manual

Chapter 4 Read and change setting

40

1 Read and change the setting vaule

1.1 Read and change the setting value via LHMI

1.1.1 Introduction

All the function settings and binary settings can be read and set through LHMI.

The user can browse to the desired settings and enter into the appropriate

vaules, The parameters for each function can be found in the LHMI. See the

Technical applciation manual for a complete list of setting parameters for

each function.

1.1.2 Communication parameter

1.1.2.1 Bay name

Enter into menu: Settings/CommPara/BayName

Check and change bay name.

1.1.2.2 Time synchronization mode

SNTP mode

Enter into menu: Settings/CommuPara/TimeMode/NetworkTimeMode

The time synchronization mode can be changed into network time mode via

this setting.

PulseTimeMode

Enter into menu: Settings/CommuPara/TimeMode/PulesTimeMode

The time synchronization mode can be changed into pulse time mode via this

setting.

IRIG-BTimeMode

Enter into menu: Settings/CommuPara/TimeMode/IRIG-BTimeMode

The time synchronization mode can be changed into IRIG-B time mode via

Page 51: CSC-150 Busbar Protection IED Engineering and Operation Manual

Chapter 4 Read and change setting

41

this setting.

1.1.2.3 Communication address

Enter into menu: Settings/CommuPara/CommAddr

The address of Lon network, RS485 port, Ethernet port 1and Ethernet 2 can

be modified in this setting .

1.1.2.4 485 baud rate

Enter into menu: Settings/CommuPara/BaudR485

485 baud rate is displayed and modified here.

1.1.3 Equipment parameter

Enter into menu: Settings/EquipPara

In this menu, the following items are displayed and can be modified: sampling

frequency for recording, rising or falling edge selection for each function.

All the functions are enabled or disabled via 1 or 0, 1 means enable, 0 means

disable.

Left or right keys are used to select value for pre-recording time and the up

and down keys are used to change value.

Note: when the cursor move to this item, at the bottom of screen,

displays the time limit for pre-recording time.

Left or right keys are used to select value for post-recording time and the up

and down keys are used to change value.

Note: when the cursor move to this item, at the bottom of screen,

displays the time limit for post-recording time.

1.1.3.1 Equipment parameter setting

1.1.3.1.1 Bus Voltage Connected

Enter into menu: Settings/EquipPara

Page 52: CSC-150 Busbar Protection IED Engineering and Operation Manual

Chapter 4 Read and change setting

42

Check and set whether to monitor the voltage transformer circuit

1.1.3.1.2 CT1 As the B/C Main CT

Enter into menu: Settings/EquipPara

Check and set whether CT1 is set as the main CT of bus coupler

1.1.3.1.3 Isol Fail Block Protec

Enter into menu: Settings/EquipPara

Check and set whether Isolator 1 fail to block the protection

1.1.3.1.4 DR_Sample Rate 600

Enter into menu: Settings/EquipPara

Check and set the the disturbance recording sampling rate

1.1.3.1.5 BI SetGrp Switch

Enter into menu: Settings/EquipPara

Check and set whether binary input could set group switch

1.1.3.1.6 Max Bays

Enter into menu: Settings/EquipPara

Check and set the max bays

1.1.3.1.7 VT_Primary:Ph-Ph

Enter into menu: Settings/EquipPara

Check and set the primary VT (VT connection: phase-phase)

1.1.3.1.8 VT_Secondary:Ph-Ea

Enter into menu: Settings/EquipPara

Check and set the secondary VT (VT connection: phase-earth)

Page 53: CSC-150 Busbar Protection IED Engineering and Operation Manual

Chapter 4 Read and change setting

43

1.1.3.1.9 CT_Secondary

Enter into menu: Settings/EquipPara

Check and set the secondary CT

1.1.3.1.10 CT1_Ratio:Bay 1

Enter into menu: Settings/EquipPara

Check and set the bay 1 CT1 ratio

1.1.3.1.11 CT2_Ratio:Bay 1

Enter into menu: Settings/EquipPara

Check and set the bay 1 CT2 ratio

1.1.3.1.12 Other Bay CT ratio

Enter into menu: Settings/EquipPara

Check and set other bay CT ratio as bay 1

1.1.3.1.13 Time Pre Fault

Enter into menu: Settings/EquipPara

Check and set the time for pre-fault

1.1.3.1.14 Time Post Fault

Enter into menu: Settings/EquipPara

Check and set the time for post-fault

1.1.3.1.15 Time Iso confirm

Enter into menu: Settings/EquipPara

Check and set the time for isolator status confirmation

Page 54: CSC-150 Busbar Protection IED Engineering and Operation Manual

Chapter 4 Read and change setting

44

1.1.3.1.16 Time CB confirm

Enter into menu: Settings/EquipPara

Check and set the time for CB status confirmation

1.1.4 Setting values and binary settings for protection function

1.1.4.1 Introduction

Protection setting

The menu of protection setting is used to check and modify every function

setting, using left and right button to choose the vaule and the up and down

buttons are used to modify the value, the upper and lower limits of setting

value will be displayed when the cursor move to corresponding setting items.

Protection binary setting

The protection binary settings are used to enable or disable each function,

1means enable and 0 means disable.

1.1.4.2 Differential protection

Enter into menu: Settings/ProtContwd/Pls Input SetGrNo/Func_Diff

Enable or disable the functions related with differential protection.

Enter into menu: Settings/ProtSet/Pls Input SetGrNo/Func_Diff

Check and set the corresponding setting values for differential protetion.

1.1.4.3 Circuit breaker failre protection

Enter into menu: Settings/ProtContwd/Pls Input SetGrNo/Func_CBF

Enable or disable the circuit breaker failure protection and functions related

with circuit breaker failure protection.

Enter into menu: Settings/ProtSet/Pls Input SetGrNo/Func_CBF

Check and set the relevant settings of circuit breaker failure protection.

Page 55: CSC-150 Busbar Protection IED Engineering and Operation Manual

Chapter 4 Read and change setting

45

1.1.4.4 Dead zone protection

Enter into menu: Settings/ProtContwd/Pls Input SetGrNo/Func_Dead

Zone

Enable or disable the dead zone portection.

Enter into menu: Settings/ ProtSet /Pls Input SetGrNo/ Func_Dead Zone

Check and set the relevant settings of dead zone protection.

2 Switching the setting group

2.1 Introduction

There are 4 setting groups with same setting items in the IED, for each group

settings can be set and saved separately, the different setting groups can be

switched according to different application.

2.2 Method for switching setting group via LHMI

Testing/SwSetGr/InputChgSetGrNo

The current setting group number and the chosen setting group number are

displayed in the LCD, move the cursor by left and right button and change the

value by up and down button, comfirm the result by Set button after the

setting group number is chosen.

After setting group switching success, the information about switching

success will be reported to show the setting group is switched from which

setting group to which setting group, for example, 1—>2, which means that

the group is switched from setting group 1 to group 2.

2.3 Method for switching setting group via binary input

Settings/ProtSet/Pls Input SetGrNo/Common

The binary setting "BI SetGrp Switch" in the menu described above is used

for switching setting group via binary input, when this binary setting is set to 1,

and the corresponding binary input is active, the setting group is switched

Page 56: CSC-150 Busbar Protection IED Engineering and Operation Manual

Chapter 4 Read and change setting

46

from group 1 to group 2. If the binary setting is set to 1 and the binary input is

inactive, the setting group is switched from group 2 to group 1.

Note: The method for swithing setting group via binary input is only available

for switching between group 1 and group2.

Page 57: CSC-150 Busbar Protection IED Engineering and Operation Manual

Chapter 5 Testing the communication connection and time synchronization

47

Chapter 5 Testing the communication

connection and time

synchronization

About this chapter

This chapter describes how to test each communication port and the function

of time synchronization.

Page 58: CSC-150 Busbar Protection IED Engineering and Operation Manual

Chapter 5 Testing the communication connection and time synchronization

48

1 Testing the communication connection

1.1 Testing the Ethernet communication

1.1.1 Testing the electrical Ethernet communication

Connect the IED with automation system to check the connection is

successful, if connection fail, check the communication network.

If connection successes, in the menu: Testing/SimuReSig, send the

simulation point information to automation system, check the information and

compare with IED information, if the automation system does not receive any

information or the information received is not true, check the automation

system configuration.

1.1.2 Testing the optical Ethernet communication

Connect the IED with automation system to check the connection is

successful, if connection fail, check the communication network.

If connection successes, in the menu: Testing/SimuReSig, send the

simulation point information to automation system, check the information and

compare with IED information, if the automation system does not receive any

information or the information received is not true, check the automation

system configuration.

1.2 Testing the RS485 port

Connect the IED with automation system to check the connection is

successful, if connection fail, check the communication network.

If connection successes, in the menu: Testing/SimuReSig, send the

simulation point information to automation system, check the information and

compare with IED information, if the automation system does not receive any

information or the information received is not true, check the automation

system configuration.

1.3 Testing the RS232 port

Page 59: CSC-150 Busbar Protection IED Engineering and Operation Manual

Chapter 5 Testing the communication connection and time synchronization

49

Using the dedicated cable for serial port to connect the PC with IED, if

connection fail, check the corresponding configuration of IED is true or not. If

all configurations are true, and the connection is still unsuccessful, please

check the connection cable and communication port.

Page 60: CSC-150 Busbar Protection IED Engineering and Operation Manual

Chapter 5 Testing the communication connection and time synchronization

50

2 Testing the time synchronization

2.1 Network mode

Select time synchronization mode:

Settings/CommuPara/TimeMode/NetworkTimeMode

Change the IED time to any other time

Wait for a period of time

Check that the IED time is changed automatically in accordance with time

synchronization source

2.2 Pulse mode

Select time synchronization mode:

Settings/CommuPara/TimeMode/PulseTimeMode

Change the IED time to any other time

Wait for a period of time

Check that the IED time is changed automatically in accordance with time

synchronization source

2.3 IRIG-B mode

Select time synchronization mode:

Settings/CommuPara/TimeMode/IRIG-BTimeMode

Change the IED time to any other time

Wait for a period of time

Check that the IED time is changed automatically in accordance with time

synchronization source

Page 61: CSC-150 Busbar Protection IED Engineering and Operation Manual

Chapter 6 IED testing

51

Chapter 6 IED testing

About this chapter

This chapter describes the method of hardware testing, such as

power supply, binary input and output, analog quantities and all

functions testing method and testing procedure.

Page 62: CSC-150 Busbar Protection IED Engineering and Operation Manual

Chapter 6 IED testing

52

1 Introduction

IED test requirements:

Setting value list

The correct IED setting value must have been set before the

testing can start.

Application configuration diagram

Terminal diagram

The terminal diagram and module arrangement diagram,

available in the Technical application manual, is a general

diagram of the IED. but note that the same diagram is not

always applicable to each specific delivery (especially for the

configuration of all the binary inputs and outputs). Therefore,

before testing, check that the available terminal diagram

corresponds to the IED.

Technical application maunal

The Technical application manual contains application and

functionality summaries, function block, logic diagram, input

and output signals, setting parameters and technical data

sorted per function.

The three-phase test equipment

The test equipment should be able to provide a three-phase

supply of voltages and currents. The magnitude of voltage and

current as well as the phase angle between voltage and

current must be variable. The voltages and currents from the

test equipment must be obtained from the same source and

they must have minimal harmonic content. If the test

equipment cannot indicate the phase angle, a separate

phase-angle measuring instrument is necessary.

Prepare the IED for test before testing a function. Consider the

logic diagram of the tested protection function when perform the

test. All included functions in the IED are tested according to the

corresponding test instrunctions in this chapter.

Page 63: CSC-150 Busbar Protection IED Engineering and Operation Manual

Chapter 6 IED testing

53

The response from a test can be viewed in different ways:

Binary output signals

Display value in HMI

All setting groups that are used should be tested.

The IED is designed for a maximum continuous current of

three times the rated current

Please observe the measuring accuracy of the IED, the

test equipment and angular accuracy for both of them

Page 64: CSC-150 Busbar Protection IED Engineering and Operation Manual

Chapter 6 IED testing

54

2 Points for attention during testing

Be familiar with the engineering drawings, engineering and

operation manual and technical application manual

Before testing, check that the short-circuited wire used to avoid

CT secondary circuit opening is connected correctly and firmly.

The short-circuited phenomenon of VT secondary circuit does

not exist

It is allowed to plug-in and pull out each module after the power

supply disconnection. Aviod AC current circuit opened when

plug in and pull out the modules

Keep cleaning and pay attention to dust prevention for each

module

Adoption the measure of the human body electrostatic

grounding prevention to make sure that the IED is not

damaged by hunam electrostatic

In principle, the electric iron can't be used in field, if the electric

iron need to be used for welding during testing, the welding

can be performed after the power disconnection or using the

electric iron with earthed wire

During testing, do not insert the module into the wrong position.

When plug in and pull out the module apply appropriate force

instead of overexerting to avoid pins bending or damage the

fastening components of module

Short-circuited or disconnected terminals temporarily for

checking, it should be recorded one by one and return to

original state after the testing is completed

Using the electronic devices (e.g. oscillograph, etc.) with AC

power supply to measure the circuit parameters, the case of

the device should be earthed in the same grounding with

protection IED cabinet

During testing, consider the safety measure between the IED

and other running equipment and the safety measure of

related circuit between external running equipment and the

IED

Page 65: CSC-150 Busbar Protection IED Engineering and Operation Manual

Chapter 6 IED testing

55

During testing, if the current magnitude that is input into IED is

large than three times of rated current, it should be noticed that

the time should not be too long

When energizing the IED in the first time, using multimeter to

check the power supply, the circuit of voltages and currents are

connected correcly to avoid short circuit or open circuit

Tighten all the screws of all terminals again for the new project

in order to prevent improper connection, and plug in and pull

out all the modules again to aovid the modules loosing result

from operation or installation

Page 66: CSC-150 Busbar Protection IED Engineering and Operation Manual

Chapter 6 IED testing

56

3 Preparing for test

3.1 Introduction

Please read the corresponding manuals that is provided by

manufacturer in detail before testing, try best to understand the

basic operation, protection principle and the relevant

capabilities. If have any questions in this procedure, please

inquire the field service engineer or the technical support

engineer of SiFang.

All checking should be done before energizing, inspection well

and no damage on the surface, all modules are inserted firmly,

the insulation of the power circuit are satisfied the specified

requirement.

Disconnect the external circuit before testing to avoid safety

accident or injuries to the human

If the modules are needed to be plugged in or pulled out, make

sure that the power is disconnected, and the measure of

prevention electrostatic should be done in order to avoid the

damage to module or performance degradation

The opened or short-circuited terminal temporarily should be

recorded in detail in order to return to original state reliably

3.2 Connecting test equipment to IED

Before testing, connect the test equipment according to the IED

specific connection diagram. Pay special attention to the correct

connection of the input and output current terminals. Check that the

input and output logical signals in the logic diagram for the function

under test are connected to the corresponding binary inputs and

outputs of the IED. The testing connection diagram is shown in

Figure 16.

The user must verify that the connections are correct and the

analog signals are measured correctly after connection completed.

Procedure:

Page 67: CSC-150 Busbar Protection IED Engineering and Operation Manual

Chapter 6 IED testing

57

1. Inject a symmetrical three-phase current and voltage at rated

value

2. Inject a phase-to-phase voltage and phase-to-phase current

at rated value

3. Check that the magnitude and phasor of analog quantities

displayed in LHMI are in accordance with the input values

4. Inject an asymmetrical three-phase current and voltage at

rated value in two phases

5. Check that the magnitude and phasor of analog quantities

displayed in LHMI are in accordance with the input values

6. If the compared value is consistent, perform the testing, if the

compared value is different, check the analog circuit

connections

IA

IB

IC

UA

UB

UC

UN

IA

IB

IB

UA

UB

UC

UN

I’A

I’B

I’C

Trip A

Trip B

Trip C

Tester IED

Figure 16 Testing connection diagram

Page 68: CSC-150 Busbar Protection IED Engineering and Operation Manual

Chapter 6 IED testing

58

4 Testing the power supply

4.1 Checking the self-startup performance

Power on the IED, in order to check the self-startup performance of

the IED, energizing the IED with the voltage rised slowly from zero

to 80% rated voltage, at this time, observe the green “Run” LED on

the front panel that should be lighted continuously. After the DC

power disappears, the normal closed contact should be

disconnected, which can be tested using the multimeter, the

contact is show in Figure 12.

4.2 DC power on and power off testing

Changing the DC power to 80% rated voltage, power off and power

on the power supply some times, the “Run” LED on the front panel

should turn off and turn on correspondingly. The normal closed

contact should be in the “on” or “off” state. The contact is show in

Figure 12.

4.3 Checking the expiry date of power supply

When period checking, check the expiry date for the power supply

module, if the power supply module has been used more than 5

years, please replace it.

Page 69: CSC-150 Busbar Protection IED Engineering and Operation Manual

Chapter 6 IED testing

59

5 Checking the analog channel

5.1 Checking the zero drift

MainMenu/Testing/ViewDrift

In this menu to check the zero drift of CPU1 and CPU2. The zero

drift values of all analog channels have been listed in detail, check

that the zero drift is met the requirement. Generally, the

requirement of the current channels is <0.02A (if the CT of analog

input module is 1A) or <0.1A (if the CT of analog input module is

5A), the voltage channels is <0.1V. If the zero drift value is not

satisfied the requirement, adjust the corresponding zero drift.

MainMenu/Testing/AdjDrift

It is allowed to check zero drift after energizing the IED for 5

minutes, when adjusting the zero drift, disconnect electrical

connection of the IED, test equipment, standard source and

external circuit, make sure that there are no any inputs to analog

terminals, select the menu and adjust zero drift.

5.2 Calibrating

MainMenu/Testing/AdjScale

Using the test equipment with the accuracy of analogue output

should be no less than 0.5%, connect the voltages and currents of

test equipment to the corresponding input terminals, select the

channel need to be adjusted with arrow keys and Set key, set the

adjustment value In and UN, output the analog quantities from test

equipment to IED and comfirm it. If the operation fails, the

abnormity of analog channel and the channel number will be

displayed in the HMI, check the connection, standard value and

version is correct or not.

Note: during testing, if the measuring tolerance of the analog

quantities are large than the required range, check that the testing

connection, testing method and external measurement meter is

correct, the testing source has not wave distortion, before all of the

exteral equipments are checked, it should not adjust or change the

components of the IED immediately.

Page 70: CSC-150 Busbar Protection IED Engineering and Operation Manual

Chapter 6 IED testing

60

5.3 Checking the accuracy and the linearity of analog quantitis

MainMenu/Testing/ViewScale

After scale and zero drift adjustment completed, check the

measurement linearity tolerance of the IED with test equipment(the

accuracy of analogue output should be no less than 0.5%), and

record the testing result, the requirement:

If the secondary rated current of CT is 5A, inject current 25A

and 10A (the time for these two injected current can't be more

than 10s), 2A, 1A, 0.4A respectively; if the secondary rated

current of CT is 1A, inject current 5A, 2A, 0.5A, 0.2A, 0.08A

respectively

Inject voltage 60V, 30V, 5V, 1V, 0.4V respectively

Observe the HMI display or check the menu described above, the

voltage channel tolerance is less than 0.1V between HMI display

value and measured value of external meter when the voltage is

0.4V and 1V, for the other voltage value, the tolerance is less than

2.5%; the current channel tolerance is less than 0.2In when the

current is 0.08In and 0.2In, for the other current value, the tolerance

is less than 2.5%.

5.4 Checking the polarity of analog quantities

MainMenu/OpStatus/Measure

Connect all current circuits in series and connect all voltage circuits

in parallel. Inject rated current and three-phase symmetrical AC

voltage with 50V, each phase voltage lead 60° to the corresponding

current. Check the scroll diaplay in HMI or enter into the menu

described above, the angle difference of volage of phase A, B, C

should be 120°, the angle difference of current of phase A, B, C

should be 120°, the current should lag 60° to the corresponding

phase voltage (tolerance ≤3°), if the diaplayed quantities are not

satisfied the requirement, check the IED or the connectin of analog

input module.

Inject three-phase symmetrical AC voltage with 50V, inject phase A

current (rated current) that lag 60° to the phase A voltage, observe

Page 71: CSC-150 Busbar Protection IED Engineering and Operation Manual

Chapter 6 IED testing

61

the magnitude and angle of 3I0 which are same with IA, if the

difference between 3I0 and IA is larger than the tolerance range,

check the IED and the connection of analog input module.

Page 72: CSC-150 Busbar Protection IED Engineering and Operation Manual

Chapter 6 IED testing

62

6 Testing binary input

MainMenu/OpStatus/BI

Check the binary input status in this menu, all the binary input

status should be “Off”. Make sure that the circuit of binary input is in

good condition, the power of binary input have been connected

(110V or 220V). Test the binary input one by one according to the

engineering drawing, the tested binary input status displayed in

HMI should be “On”.

Page 73: CSC-150 Busbar Protection IED Engineering and Operation Manual

Chapter 6 IED testing

63

7 Testing binary output

MainMenu/Test BO

Testing binary output in this menu to verify the correctness of signal

circuit and output circuit.

During testing the binary output, the corresponding relay contact

operate and the configured LED should be lighted, the irrelevant

contacts should not operate. Use the multimeter to measure the

corresponding output contacts of the tripping and signal.

Page 74: CSC-150 Busbar Protection IED Engineering and Operation Manual

Chapter 6 IED testing

64

8 Verifying the IED functions

Procedure:

1. Enable the protection function binary setting via software tool

or LHMI

2. Input the corresponding settings value via software tool or

LHMI

3. Input the rated currents and voltages to make the IED

operating normally for 20s

4. Active the binary input for the corresponding protection

function

5. Simulate the fault occurance

6. Observe the testing result, the output contact

7. Stop the output from test equipment and restore to original

state

8. Continue to test another function or complete the test

8.1 Differential protection

Before starting the test, please make sure that the protection

function setting values and parameters are correct, refer to section

Introduction, Points for attention during testing and Preparing

for test in this chapter.

8.1.1 Verifying the settings

8.1.1.1 Verifying the differential curve of differentail protection

1 Verifying the phase A setting

1.1 Verifying the current setting

Table 12 Current setting verifying

Page 75: CSC-150 Busbar Protection IED Engineering and Operation Manual

Chapter 6 IED testing

65

Test item Description

5% scope error verifying

Binary setting Settings/ProtContwd/Pls Input SetGrNo/Diff Set/Func_Percent

Diff, set the binary setting as 1

Setting value Settings/ProtSet/Pls Input SetGrNo/Diff Set, the detail setting list

refer to the “Reference setting list for test” in this section

Binary input Connect the binary output of “Diff Trip” to one binary input of the test

machine

Fault simulation

Input current into 2 feeders of busbar zone 1, set the testing curve

according to the reference setting list ('' I_Diff '', '' K_Diff ''),with every

restraint point interval 0.1In;

Test result The searched curve should within 5% scope below curve and 5%

scope above curve.

2 Verifying the settings of other phase

The test method and test items of verifying the other phase are

same as phase A, only need to change the corresponding test

conditions and settings into the conrresponding other phase

required.

8.1.1.2 Verifying the feeder CT failure alarm current

1 Verifying the phase A setting

1.2 Verifying the current setting

Table 13 Current setting verifying

Test item Description

105% of current setting verifying

Binary setting

Settings/ProtContwd/Pls Input SetGrNo/Func_ Diff/Func_Diff

ON, set the binary setting as 1

Settings/ProtContwd/Pls Input SetGrNo/Func_ Diff/CT Fail

Alarm ON, set the binary setting as 1

Setting value Settings/ProtSet/Pls Input SetGrNo/Func_Diff, the detail setting

list refer to the “Reference setting list for test” in this section

Fault simulation

Pre-fault stage:

Input current into 2 feeders of busbar zone 1

Current: 105% of the setting value, three phase

Direction: feeder 1 flow in; feeder 2 flow out

Duration: 5s

Fault stage:

Decrease phase A current of feeder 1 to zero instantaneously

Page 76: CSC-150 Busbar Protection IED Engineering and Operation Manual

Chapter 6 IED testing

66

Test item Description

Duration: 15s

Test result

IED operation:

The corresponding output contacts should be closed

IED report:

“BZ1 CT Fail:PhA'', with 10s time delay

95% of current setting verifying

Binary setting

Settings/ProtContwd/Pls Input SetGrNo/Func_ Diff/Func_Diff

ON, set the binary setting as 1

Settings/ProtContwd/Pls Input SetGrNo/Func_ Diff/CT Fail

Alarm ON, set the binary setting as 1

Setting value Settings/ProtSet/Pls Input SetGrNo/Func_Diff, the detail setting

list refer to the “Reference setting list for test” in this section

Fault simulation

Pre-fault stage:

Input current into 2 feeders of busbar zone 1

Current: 95% of the setting value, three phase

Direction: feeder 1 flow in; feeder 2 flow out

Duration: 5s

Fault stage:

Decrease phase A current of feeder 1 to zero instantaneously

Duration: 15s

Test result IED operation:

The corresponding output contacts should not close

2 Verifying the settings of other phase

The test method and test items of verifying the other phase are

same as phase A, only need to change the corresponding test

conditions and settings into the conrresponding other phase

required.

8.1.1.3 Verifying the feeder CT failure block current

1 Verifying the phase A setting

1.1 Verifying the current setting

Table 14 Current setting verifying

Test item Description

105% of current setting verifying

Binary setting

Settings/ProtContwd/Pls Input SetGrNo/Func_ Diff/Func_Diff

ON, set the binary setting as 1

Settings/ProtContwd/Pls Input SetGrNo/Func_ Diff/CT Fail

Page 77: CSC-150 Busbar Protection IED Engineering and Operation Manual

Chapter 6 IED testing

67

Test item Description

Block ON, set the binary setting as 1

Setting value Settings/ProtSet/Pls Input SetGrNo/Func_Diff, the detail setting

list refer to the “Reference setting list for test” in this section

Fault simulation

Pre-fault stage:

Input current into 2 feeders of busbar zone 1

Current: 105% of the setting value, three phase

Direction: feeder 1 flow in; feeder 2 flow out

Duration: 5s

Fault stage:

Decrease phase A current of feeder 1 to zero instantaneously

Duration: 15s

Test result

IED operation:

The corresponding output contacts should be closed

IED report:

“BZ1 CT Fail:PhA'', with 10s time delay

95% of current setting verifying

Binary setting

Settings/ProtContwd/Pls Input SetGrNo/Func_ Diff/Func_Diff

ON, set the binary setting as 1

Settings/ProtContwd/Pls Input SetGrNo/Func_ Diff/CT Fail

Block ON, set the binary setting as 1

Setting value Settings/ProtSet/Pls Input SetGrNo/Func_Diff, the detail setting

list refer to the “Reference setting list for test” in this section

Fault simulation

Pre-fault stage:

Input current into 2 feeders of busbar zone 1

Current: 95% of the setting value, three phase

Direction: feeder 1 flow in; feeder 2 flow out

Duration: 5s

Fault stage:

Decrease phase A current of feeder 1 to zero instantaneously

Duration: 15s

Test result IED operation:

The corresponding output contacts should not close

2 Verifying the settings of other phase

The test method and test items of verifying the other phase are

same as phase A, only need to change the corresponding test

conditions and settings into the conrresponding other phase

required.

8.1.1.4 Verifying the B/C CT failure alarm current

1 Verifying the phase A setting

Page 78: CSC-150 Busbar Protection IED Engineering and Operation Manual

Chapter 6 IED testing

68

1.1 Verifying the current setting

Table 15 Current setting verifying

Test item Description

105% of current setting verifying

Binary setting

Settings/ProtContwd/Pls Input SetGrNo/Func_ Diff/Func_Diff

ON, set the binary setting as 1

Settings/ProtContwd/Pls Input SetGrNo/Func_ Diff/CT Fail

Alarm ON, set the binary setting as 1

Setting value Settings/ProtSet/Pls Input SetGrNo/Func_Diff, the detail setting

list refer to the “Reference setting list for test” in this section

Fault simulation

Pre-fault stage:

Input current into 2 feeders of busbar zone 1

Current: 105% of the setting value, three phase

Direction: feeder 1 flow in; feeder 2 flow out

Duration: 5s

Fault stage:

Decrease phase A current of feeder 1 to zero instantaneously

Duration: 15s

Test result

IED operation:

The corresponding output contacts should be closed

IED report:

“B/C CT Fail:PhA'', with 10s time delay

95% of current setting verifying

Binary setting

Settings/ProtContwd/Pls Input SetGrNo/Func_ Diff/Func_Diff

ON, set the binary setting as 1

Settings/ProtContwd/Pls Input SetGrNo/Func_ Diff/CT Fail

Alarm ON, set the binary setting as 1

Setting value Settings/ProtSet/Pls Input SetGrNo/Func_Diff, the detail setting

list refer to the “Reference setting list for test” in this section

Fault simulation

Pre-fault stage:

Input current into 2 feeders of busbar zone 1

Current: 95% of the setting value, three phase

Direction: feeder 1 flow in; feeder 2 flow out

Duration: 5s

Fault stage:

Decrease phase A current of feeder 1 to zero instantaneously

Duration: 15s

Test result IED operation:

The corresponding output contacts should not close

2 Verifying the settings of other phase

Page 79: CSC-150 Busbar Protection IED Engineering and Operation Manual

Chapter 6 IED testing

69

The test method and test items of verifying the other phase are

same as phase A, only need to change the corresponding test

conditions and settings into the conrresponding other phase

required.

8.1.1.5 Verifying the B/C CT failure block current

1 Verifying the phase A setting

1.1 Verifying the current setting

Table 16 Current setting verifying

Test item Description

105% of current setting verifying

Binary setting

Settings/ProtContwd/Pls Input SetGrNo/Func_ Diff/Func_Diff

ON, set the binary setting as 1

Settings/ProtContwd/Pls Input SetGrNo/Func_ Diff/CT Fail

Block ON, set the binary setting as 1

Setting value Settings/ProtSet/Pls Input SetGrNo/Func_Diff, the detail setting

list refer to the “Reference setting list for test” in this section

Fault simulation

Pre-fault stage:

Input current into 2 feeders of busbar zone 1

Current: 105% of the setting value, three phase

Direction: feeder 1 flow in; feeder 2 flow out

Duration: 5s

Fault stage:

Decrease phase A current of feeder 1 to zero instantaneously

Duration: 15s

Test result

IED operation:

The corresponding output contacts should be closed

IED report:

“B/C CT Fail:PhA'', with 10s time delay

95% of current setting verifying

Binary setting

Settings/ProtContwd/Pls Input SetGrNo/Func_ Diff/Func_Diff

ON, set the binary setting as 1

Settings/ProtContwd/Pls Input SetGrNo/Func_ Diff/CT Fail

Block ON, set the binary setting as 1

Setting value Settings/ProtSet/Pls Input SetGrNo/Func_Diff, the detail setting

list refer to the “Reference setting list for test” in this section

Fault simulation

Pre-fault stage:

Input current into 2 feeders of busbar zone 1

Current: 95% of the setting value, three phase

Direction: feeder 1 flow in; feeder 2 flow out

Page 80: CSC-150 Busbar Protection IED Engineering and Operation Manual

Chapter 6 IED testing

70

Test item Description

Duration: 5s

Fault stage:

Decrease phase A current of feeder 1 to zero instantaneously

Duration: 15s

Test result IED operation:

The corresponding output contacts should not close

2 Verifying the settings of other phase

The test method and test items of verifying the other phase are

same as phase A, only need to change the corresponding test

conditions and settings into the conrresponding other phase

required.

8.1.2 Completing the test

Continue to test another function or end the test. Restore

connections and settings to their original values, if they were

changed for testing purposes.

8.1.3 Reference setting list for test

Table 17 Function setting list for busbar differential protection

NO. Default Abbr. Explanation Unit Min. Max.

1. 1 I_Diff Current setting for busbar

differential protection A 0.1 99.99

2. 0.6 K_Diff Restraint factor for busbar

differential protection 0.3 0.99

3. 0.5 I_CTFailAlm:Feeder Current setting for CT

failure alarm: feeder A 0.01 99.99

4. 0.5 I_CTFailBlk:Feeder Current setting for CT

failure blocking: feeder A 0.01 99.99

5. 0.1 I_CTFailAlm:B/C Current setting for CT

failure alarm: B/C A 0.01 99.99

6. 0.1 I_CTFailBlk:B/C Current setting for CT

failure blocking: B/C A 0.01 99.99

Table 18 Binary setting list for busbar differential protection

Name Description Default Unit Min. Max.

Page 81: CSC-150 Busbar Protection IED Engineering and Operation Manual

Chapter 6 IED testing

71

Name Description Default Unit Min. Max.

Func_Diff ON Busbar differential protection

enabled or disabled 1 0 1

CT Fail Alarm ON CT fail alarm enabled or disabled 1 0 1

CT Fail Block ON CT fail blocking enabled or disabled 0 0 1

8.2 Circuit breaker failure protection

Before starting the test, please make sure that the protection

function setting values and parameters are correct, refer to section

Introduction, Points for attention during testing and Preparing

for test in this chapter.

8.2.1 Verifying the settings

8.2.1.1 Verifying the settings of stage 1 of CBF protection

1 Verifying the bay1 settings

1.1 Verifying the current setting

Table 19 Current setting verifying

Test item Description

103% of the current setting verifying

Binary setting Settings/ProtContwd/Pls Input SetGrNo/Func_CBF/Bay1

Func_CBF On, set the binary setting as 1

Setting value Settings/ProtSet/Pls Input SetGrNo/Func_CBF, the detail setting

list refer to the “Reference setting list for test” in this section

Binary input Active the binary input of “PHA INI BF BAY1”

Fault simulation

Input current into 1 feeder (bay 1) of busbar zone 1

Current: 103% of the setting value, phase A

Duration: 40s

In the fifth second, active the binary input of “PHA INI BF BAY1”,

with duration shorter than the setting ''T_CBF Bay1''

Test result

IED operation:

The corresponding output contacts should be closed

Report:

“CBF Startup”

“CBF1 Trip”

''BZ1 CBF2 Trip''

Page 82: CSC-150 Busbar Protection IED Engineering and Operation Manual

Chapter 6 IED testing

72

Test item Description

''CBF Transf. Trip''

97% of the current setting verifying

Binary setting Settings/ProtContwd/Pls Input SetGrNo/Func_CBF/Bay1

Func_CBF On, set the binary setting as 1

Setting value Settings/ProtSet/Pls Input SetGrNo/Func_CBF, the detail setting

list refer to the “Reference setting list for test” in this section

Binary input Active the binary input of “PHA INI BF BAY1”

Fault simulation

Input current into 1 feeder (bay 1) of busbar zone 1

Current: 97% of the setting value, phase A

Duration: 40s.

In the fifth second, active the binary input of “PHA INI BF BAY1”,

with duration shorter than the setting ''T_CBF Bay1''

Test result IED operation:

The corresponding output contacts should not close

1.2 Verifying the zero-sequence current setting

Table 20 Zero-sequence current setting verifying

Test item Description

103% of the zero-sequence current setting verifying

Binary setting

Settings/ProtContwd/Pls Input SetGrNo/Func_CBF/Bay1

Func_CBF On, set the binary setting as 1

Settings/ProtContwd/Pls Input SetGrNo/Func_CBF/Bay1 CBF

Chk 3I0/3I2, set the binary setting as 0

Setting value Settings/ProtSet/Pls Input SetGrNo/Func_CBF, the detail setting

list refer to the “Reference setting list for test” in this section

Binary input Active the binary input of “PHA INI BF BAY1”

Fault simulation

Input current into 1 feeder (bay 1) of busbar zone 1

Current: 103% of the setting value, zero-sequence

Duration: 40s

In the fifth second, active the binary input of “PHA INI BF BAY1”,

with duration shorter than the setting ''T_CBF Bay1''

Test result

IED operation:

The corresponding output contacts should be closed

Report:

“CBF Startup”

“CBF1 Trip”

''BZ1 CBF2 Trip''

''CBF Transf. Trip''

97% of the zero-sequence current setting verifying

Binary setting Settings/ProtContwd/Pls Input SetGrNo/Func_CBF/Bay1

Func_CBF On, set the binary setting as 1

Page 83: CSC-150 Busbar Protection IED Engineering and Operation Manual

Chapter 6 IED testing

73

Test item Description

Settings/ProtContwd/Pls Input SetGrNo/Func_CBF/Bay1 CBF

Chk 3I0/3I2, set the binary setting as 0

Setting value Settings/ProtSet/Pls Input SetGrNo/Func_CBF, the detail setting

list refer to the “Reference setting list for test” in this section

Binary input Active the binary input of “PHA INI BF BAY1”

Fault simulation

Input current into 1 feeder (bay 1) of busbar zone 1

Current: 97% of the setting value, zero-sequence

Duration: 40s

In the fifth second, active the binary input of “PHA INI BF BAY1”,

with duration shorter than the setting ''T_CBF Bay1''

Test result IED operation:

The corresponding output contacts should not close

1.3 Verifying the negative-sequence current setting

Table 21 Negative-sequence current setting verifying

Test item Description

103% of the negative-sequence current setting verifying

Binary setting

Settings/ProtContwd/Pls Input SetGrNo/Func_CBF/Bay1

Func_CBF On, set the binary setting as 1

Settings/ProtContwd/Pls Input SetGrNo/Func_CBF/Bay1 CBF

Chk 3I0/3I2, set the binary setting as 1

Setting value Settings/ProtSet/Pls Input SetGrNo/Func_CBF, the detail setting

list refer to the “Reference setting list for test” in this section

Binary input Active the binary input of “PHA INI BF BAY1”

Fault simulation

Input current into 1 feeder (bay 1) of busbar zone 1

Current: 103% of the setting value, negative-sequence

Duration: 40s

In the fifth second, active the binary input of “PHA INI BF BAY1”,

with duration shorter than the setting ''T_CBF Bay1''

Test result

IED operation:

The corresponding output contacts should be closed

Report:

“CBF Startup”

“CBF1 Trip”

''BZ1 CBF2 Trip''

''CBF Transf. Trip''

97% of the negative-sequence current setting verifying

Binary setting

Settings/ProtContwd/Pls Input SetGrNo/Func_CBF/Bay1

Func_CBF On, set the binary setting as 1

Settings/ProtContwd/Pls Input SetGrNo/Func_CBF/Bay1 CBF

Chk 3I0/3I2, set the binary setting as 1

Page 84: CSC-150 Busbar Protection IED Engineering and Operation Manual

Chapter 6 IED testing

74

Test item Description

Setting value Settings/ProtSet/Pls Input SetGrNo/Func_CBF, the detail setting

list refer to the “Reference setting list for test” in this section

Binary input Active the binary input of “PHA INI BF BAY1”

Fault simulation

Input current into 1 feeder (bay 1) of busbar zone 1

Current: 97% of the setting value, negative-sequence

Duration: 40s

In the fifth second, active the binary input of “PHA INI BF BAY1”,

with duration shorter than the setting ''T_CBF Bay1''

Test result IED operation:

The corresponding output contacts should not close

1.4 Verifying the time setting of CBF

Table 22 Time setting verifying

Test item Description

Binary setting Settings/ProtContwd/Pls Input SetGrNo/Func_CBF/Bay1

Func_CBF On, set the binary setting as 1

Setting value Settings/ProtSet/Pls Input SetGrNo/Func_CBF, the detail setting

list refer to the “Reference setting list for test” in this section

Binary input Active the binary input of “PHA INI BF BAY1”

Fault simulation

Input current into 1 feeder (bay 1) of busbar zone 1

Current: 103% of the setting value ''I_CBF: Bay1'', phase A

Duration: 40s

In the fifth second, active the binary input of “PHA INI BF BAY1”,

with duration shorter than the setting ''T_CBF Bay1''

Test result

IED operation:

The corresponding output contacts should be closed, and the

operate time meets the requirement in technical data

Report:

“CBF Startup”

“CBF1 Trip”

''BZ1 CBF2 Trip''

''CBF Transf. Trip''

2 Verifying the settings of other phase

The test method and test items of verifying the settings of other

phase protection are same as phase A, only need to change the

corresponding test conditions and settings into the conrresponding

phase A required.

3 Verifying the settings of other bay

Page 85: CSC-150 Busbar Protection IED Engineering and Operation Manual

Chapter 6 IED testing

75

The test method and test items of verifying the settings of other

bays are same as bay 1, only need to change the corresponding

test conditions and settings into the conrresponding bay 1 required.

8.2.2 Completing the test

Continue to test another function or end the test. Restore

connections and settings to their original values, if they were

changed for testing purposes.

8.2.3 Reference setting list for test

Table 23 CBF protection function setting list

NO. Default Abbr. Explanation Unit Min. Max.

1. 1.00 I_CBF:Bay1 Phase current setting for

CBF protection of bay 1 A 0.05 100.0

2. 1.00 3I0_CBF:Bay1

Zero sequence current

setting for CBF

protection of bay 1

A 0.05 100.0

3. 1.00 3I2_CBF:Bay1

Negative sequence

current setting for CBF

protection of bay 1

A 0.05 100.0

4. 2.00 T_CBF1:Bay1 Time delay for CBF

stage 1 of bay 1 s 0 32.00

5. 2.00 T_CBF2:Bay1 Time delay for CBF

stage 2 of bay 1 s 0 32.00

6. 1.00 I_CBF:Bay2 Phase current setting for

CBF protection of bay 2 A 0.05 100.0

7. 1.00 3I0_CBF:Bay2

Zero sequence current

setting for CBF

protection of bay 2

A 0.05 100.0

8. 1.00 3I2_CBF:Bay2

Negative sequence

current setting for CBF

protection of bay 2

A 0.05 100.0

9. 2.00 T_CBF1:Bay2 Time delay for CBF

stage 1 of bay 2 s 0 32.00

10. 2.00 T_CBF2:Bay2 Time delay for CBF

stage 2 of bay 2 s 0 32.00

11. 1.00 I_CBF:Bay3 Phase current setting for

CBF protection of bay 3 A 0.05 100.0

12. 1.00 3I0_CBF:Bay3 Zero sequence current A 0.05 100.0

Page 86: CSC-150 Busbar Protection IED Engineering and Operation Manual

Chapter 6 IED testing

76

NO. Default Abbr. Explanation Unit Min. Max.

setting for CBF

protection of bay 3

13. 1.00 3I2_CBF:Bay3

Negative sequence

current setting for CBF

protection of bay 3

A 0.05 100.0

14. 2.00 T_CBF1:Bay3 Time delay for CBF

stage 1 of bay 3 s 0 32.00

15. 2.00 T_CBF2:Bay3 Time delay for CBF

stage 2 of bay 3 s 0 32.00

16. 1.00 I_CBF:Bay4 Phase current setting for

CBF protection of bay 4 A 0.05 100.0

17. 1.00 3I0_CBF:Bay4

Zero sequence current

setting for CBF

protection of bay 4

A 0.05 100.0

18. 1.00 3I2_CBF:Bay4

Negative sequence

current setting for CBF

protection of bay 4

A 0.05 100.0

19. 2.00 T_CBF1:Bay4 Time delay for CBF

stage 1 of bay 4 s 0 32.00

20. 2.00 T_CBF2:Bay4 Time delay for CBF

stage 2 of bay 4 s 0 32.00

21. 1.00 I_CBF:Bay5 Phase current setting for

CBF protection of bay 5 A 0.05 100.0

22. 1.00 3I0_CBF:Bay5

Zero sequence current

setting for CBF

protection of bay 5

A 0.05 100.0

23. 1.00 3I2_CBF:Bay5

Negative sequence

current setting for CBF

protection of bay 5

A 0.05 100.0

24. 2.00 T_CBF1:Bay5 Time delay for CBF

stage 1 of bay 5 s 0 32.00

25. 2.00 T_CBF2:Bay5 Time delay for CBF

stage 2 of bay 5 s 0 32.00

26. 1.00 I_CBF:Bay6 Phase current setting for

CBF protection of bay 6 A 0.05 100.0

27. 1.00 3I0_CBF:Bay6

Zero sequence current

setting for CBF

protection of bay 6

A 0.05 100.0

28. 1.00 3I2_CBF:Bay6

Negative sequence

current setting for CBF

protection of bay 6

A 0.05 100.0

29. 2.00 T_CBF1:Bay6 Time delay for CBF

stage 1 of bay 6 s 0 32.00

Page 87: CSC-150 Busbar Protection IED Engineering and Operation Manual

Chapter 6 IED testing

77

NO. Default Abbr. Explanation Unit Min. Max.

30. 2.00 T_CBF2:Bay6 Time delay for CBF

stage 2 of bay 6 s 0 32.00

31. 1.00 I_CBF:Bay7 Phase current setting for

CBF protection of bay 7 A 0.05 100.0

32. 1.00 3I0_CBF:Bay7

Zero sequence current

setting for CBF

protection of bay 7

A 0.05 100.0

33. 1.00 3I2_CBF:Bay7

Negative sequence

current setting for CBF

protection of bay 7

A 0.05 100.0

34. 2.00 T_CBF1:Bay7 Time delay for CBF

stage 1 of bay 7 s 0 32.00

35. 2.00 T_CBF2:Bay7 Time delay for CBF

stage 2 of bay 7 s 0 32.00

36. 1.00 I_CBF:Bay8 Phase current setting for

CBF protection of bay 8 A 0.05 100.0

37. 1.00 3I0_CBF:Bay8

Zero sequence current

setting for CBF

protection of bay 8

A 0.05 100.0

38. 1.00 3I2_CBF:Bay8

Negative sequence

current setting for CBF

protection of bay 8

A 0.05 100.0

39. 2.00 T_CBF1:Bay8 Time delay for CBF

stage 1 of bay 8 s 0 32.00

40. 2.00 T_CBF2:Bay8 Time delay for CBF

stage 2 of bay 8 s 0 32.00

41. 1.00 I_CBF:Bay9 Phase current setting for

CBF protection of bay 9 A 0.05 100.0

42. 1.00 3I0_CBF:Bay9

Zero sequence current

setting for CBF

protection of bay 9

A 0.05 100.0

43. 1.00 3I2_CBF:Bay9

Negative sequence

current setting for CBF

protection of bay 9

A 0.05 100.0

44. 2.00 T_CBF1:Bay9 Time delay for CBF

stage 1 of bay 9 s 0 32.00

45. 2.00 T_CBF2:Bay9 Time delay for CBF

stage 2 of bay 9 s 0 32.00

46. 1.00 I_CBF:Bay10

Phase current setting for

CBF protection of bay

10

A 0.05 100.0

47. 1.00 3I0_CBF:Bay10 Zero sequence current

setting for CBF A 0.05 100.0

Page 88: CSC-150 Busbar Protection IED Engineering and Operation Manual

Chapter 6 IED testing

78

NO. Default Abbr. Explanation Unit Min. Max.

protection of bay 10

48. 1.00 3I2_CBF:Bay10

Negative sequence

current setting for CBF

protection of bay 10

A 0.05 100.0

49. 2.00 T_CBF1:Bay10 Time delay for CBF

stage 1 of bay 10 s 0 32.00

50. 2.00 T_CBF2:Bay10 Time delay for CBF

stage 2 of bay 10 s 0 32.00

51. 1.00 I_CBF:Bay11

Phase current setting for

CBF protection of bay

11

A 0.05 100.0

52. 1.00 3I0_CBF:Bay11

Zero sequence current

setting for CBF

protection of bay 11

A 0.05 100.0

53. 1.00 3I2_CBF:Bay11

Negative sequence

current setting for CBF

protection of bay 11

A 0.05 100.0

54. 2.00 T_CBF1:Bay11 Time delay for CBF

stage 1 of bay 11 s 0 32.00

55. 2.00 T_CBF2:Bay11 Time delay for CBF

stage 2 of bay 11 s 0 32.00

56. 1.00 I_CBF:Bay12

Phase current setting for

CBF protection of bay

12

A 0.05 100.0

57. 1.00 3I0_CBF:Bay12

Zero sequence current

setting for CBF

protection of bay 12

A 0.05 100.0

58. 1.00 3I2_CBF:Bay12

Negative sequence

current setting for CBF

protection of bay 12

A 0.05 100.0

59. 2.00 T_CBF1:Bay12 Time delay for CBF

stage 1 of bay 12 s 0 32.00

60. 2.00 T_CBF2:Bay12 Time delay for CBF

stage 2 of bay 12 s 0 32.00

61. 1.00 I_CBF:Bay13

Phase current setting for

CBF protection of bay

13

A 0.05 100.0

62. 1.00 3I0_CBF:Bay13

Zero sequence current

setting for CBF

protection of bay 13

A 0.05 100.0

63. 1.00 3I2_CBF:Bay13

Negative sequence

current setting for CBF

protection of bay 13

A 0.05 100.0

Page 89: CSC-150 Busbar Protection IED Engineering and Operation Manual

Chapter 6 IED testing

79

NO. Default Abbr. Explanation Unit Min. Max.

64. 2.00 T_CBF1:Bay13 Time delay for CBF

stage 1 of bay 13 s 0 32.00

65. 2.00 T_CBF2:Bay13 Time delay for CBF

stage 2 of bay 13 s 0 32.00

66. 1.00 I_CBF:Bay14

Phase current setting for

CBF protection of bay

14

A 0.05 100.0

67. 1.00 3I0_CBF:Bay14

Zero sequence current

setting for CBF

protection of bay 14

A 0.05 100.0

68. 1.00 3I2_CBF:Bay14

Negative sequence

current setting for CBF

protection of bay 14

A 0.05 100.0

69. 2.00 T_CBF1:Bay14 Time delay for CBF

stage 1 of bay 14 s 0 32.00

70. 2.00 T_CBF2:Bay14 Time delay for CBF

stage 2 of bay 14 s 0 32.00

71. 1.00 I_CBF:Bay15

Phase current setting for

CBF protection of bay

15

A 0.05 100.0

72. 1.00 3I0_CBF:Bay15

Zero sequence current

setting for CBF

protection of bay 15

A 0.05 100.0

73. 1.00 3I2_CBF:Bay15

Negative sequence

current setting for CBF

protection of bay 15

A 0.05 100.0

74. 2.00 T_CBF1:Bay15 Time delay for CBF

stage 1 of bay 15 s 0 32.00

75. 2.00 T_CBF2:Bay15 Time delay for CBF

stage 2 of bay 15 s 0 32.00

76. 1.00 I_CBF:Bay16

Phase current setting for

CBF protection of bay

16

A 0.05 100.0

77. 1.00 3I0_CBF:Bay16

Zero sequence current

setting for CBF

protection of bay 16

A 0.05 100.0

78. 1.00 3I2_CBF:Bay16

Negative sequence

current setting for CBF

protection of bay 16

A 0.05 100.0

79. 2.00 T_CBF1:Bay16 Time delay for CBF

stage 1 of bay 16 s 0 32.00

80. 2.00 T_CBF2:Bay16 Time delay for CBF

stage 2 of bay 16 s 0 32.00

Page 90: CSC-150 Busbar Protection IED Engineering and Operation Manual

Chapter 6 IED testing

80

NO. Default Abbr. Explanation Unit Min. Max.

81. 1.00 I_CBF:Bay17

Phase current setting for

CBF protection of bay

17

A 0.05 100.0

82. 1.00 3I0_CBF:Bay17

Zero sequence current

setting for CBF

protection of bay 17

A 0.05 100.0

83. 1.00 3I2_CBF:Bay17

Negative sequence

current setting for CBF

protection of bay 17

A 0.05 100.0

84. 2.00 T_CBF1:Bay17 Time delay for CBF

stage 1 of bay 17 s 0 32.00

85. 2.00 T_CBF2:Bay17 Time delay for CBF

stage 2 of bay 17 s 0 32.00

Table 24 CBF protection binary setting list

Name Description Default Unit Min. Max.

Bay1 Func_CBF On CBF protection enabled or

disable for bay 1 0 0 1

Bay1 CBF Chk 3I0/3I2

Enable or disable the function

for checking zero or negative

sequence current for bay 1

0 0 1

Bay1 Init from Ext CBF Initiated from external CBF

function for bay 1 0 0 1

Bay2 Func_CBF On CBF protection enabled or

disable for bay 2 0 0 1

Bay2 CBF Chk 3I0/3I2

Enable or disable the function

for checking zero or negative

sequence current for bay 2

0 0 1

Bay2 Init from Ext CBF Initiated from external CBF

function for bay 2 0 0 1

Bay3 Func_CBF On CBF protection enabled or

disable for bay 3 0 0 1

Bay3 CBF Chk 3I0/3I2

Enable or disable the function

for checking zero or negative

sequence current for bay 3

0 0 1

Bay3 Init from Ext CBF Initiated from external CBF

function for bay 3 0 0 1

Bay4 Func_CBF On CBF protection enabled or

disable for bay 4 0 0 1

Bay4 CBF Chk 3I0/3I2

Enable or disable the function

for checking zero or negative

sequence current for bay 4

0 0 1

Page 91: CSC-150 Busbar Protection IED Engineering and Operation Manual

Chapter 6 IED testing

81

Name Description Default Unit Min. Max.

Bay4 Init from Ext CBF Initiated from external CBF

function for bay 4 0 0 1

Bay5 Func_CBF On CBF protection enabled or

disable for bay 5 0 0 1

Bay5 CBF Chk 3I0/3I2

Enable or disable the function

for checking zero or negative

sequence current for bay 5

0 0 1

Bay5 Init from Ext CBF Initiated from external CBF

function for bay 5 0 0 1

Bay6 Func_CBF On CBF protection enabled or

disable for bay 6 0 0 1

Bay6 CBF Chk 3I0/3I2

Enable or disable the function

for checking zero or negative

sequence current for bay 6

0 0 1

Bay6 Init from Ext CBF Initiated from external CBF

function for bay 6 0 0 1

Bay7 Func_CBF On CBF protection enabled or

disable for bay 7 0 0 1

Bay7 CBF Chk 3I0/3I2

Enable or disable the function

for checking zero or negative

sequence current for bay 7

0 0 1

Bay7 Init from Ext CBF Initiated from external CBF

function for bay 7 0 0 1

Bay8 Func_CBF On CBF protection enabled or

disable for bay 8 0 0 1

Bay8 CBF Chk 3I0/3I2

Enable or disable the function

for checking zero or negative

sequence current for bay 8

0 0 1

Bay8 Init from Ext CBF Initiated from external CBF

function for bay 8 0 0 1

Bay9 Func_CBF On CBF protection enabled or

disable for bay 9 0 0 1

Bay9 CBF Chk 3I0/3I2

Enable or disable the function

for checking zero or negative

sequence current for bay 9

0 0 1

Bay9 Init from Ext CBF Initiated from external CBF

function for bay 9 0 0 1

Bay10 Func_CBF On CBF protection enabled or

disable for bay 10 0 0 1

Bay10 CBF Chk 3I0/3I2

Enable or disable the function

for checking zero or negative

sequence current for bay 10

0 0 1

Page 92: CSC-150 Busbar Protection IED Engineering and Operation Manual

Chapter 6 IED testing

82

Name Description Default Unit Min. Max.

Bay10 Init from Ext CBF Initiated from external CBF

function for bay 10 0 0 1

Bay11 Func_CBF On CBF protection enabled or

disable for bay 11 0 0 1

Bay11 CBF Chk 3I0/3I2

Enable or disable the function

for checking zero or negative

sequence current for bay 11

0 0 1

Bay11 Init from Ext CBF Initiated from external CBF

function for bay 11 0 0 1

Bay12 Func_CBF On CBF protection enabled or

disable for bay 12 0 0 1

Bay12 CBF Chk 3I0/3I2

Enable or disable the function

for checking zero or negative

sequence current for bay 12

0 0 1

Bay12 Init from Ext CBF Initiated from external CBF

function for bay 12 0 0 1

Bay13 Func_CBF On CBF protection enabled or

disable for bay 13 0 0 1

Bay13 CBF Chk 3I0/3I2

Enable or disable the function

for checking zero or negative

sequence current for bay 13

0 0 1

Bay13 Init from Ext CBF Initiated from external CBF

function for bay 13 0 0 1

Bay14 Func_CBF On CBF protection enabled or

disable for bay 14 0 0 1

Bay14 CBF Chk 3I0/3I2

Enable or disable the function

for checking zero or negative

sequence current for bay 14

0 0 1

Bay14 Init from Ext CBF Initiated from external CBF

function for bay 14 0 0 1

Bay15 Func_CBF On CBF protection enabled or

disable for bay 15 0 0 1

Bay15 CBF Chk 3I0/3I2

Enable or disable the function

for checking zero or negative

sequence current for bay 15

0 0 1

Bay15 Init from Ext CBF Initiated from external CBF

function for bay 15 0 0 1

Bay16 Func_CBF On CBF protection enabled or

disable for bay 16 0 0 1

Bay16 CBF Chk 3I0/3I2

Enable or disable the function

for checking zero or negative

sequence current for bay 16

0 0 1

Page 93: CSC-150 Busbar Protection IED Engineering and Operation Manual

Chapter 6 IED testing

83

Name Description Default Unit Min. Max.

Bay16 Init from Ext CBF Initiated from external CBF

function for bay 16 0 0 1

Bay17 Func_CBF On CBF protection enabled or

disable for bay 17 0 0 1

Bay17 CBF Chk 3I0/3I2

Enable or disable the function

for checking zero or negative

sequence current for bay 17

0 0 1

Bay17 Init from Ext CBF Initiated from external CBF

function for bay 17 0 0 1

8.3 Dead zone protection

Before starting the test, please make sure that the protection

function setting values and parameters are correct, refer to section

Introduction, Points for attention during testing and Preparing

for test in this chapter.

8.3.1 Verifying the settings

1 Verifying the bay1 setting

1.1 Verifying the time setting

Table 25 Time setting verifying

Test item Description

Binary setting Settings/ProtContwd/Pls Input SetGrNo/Func_Dead Zone, set

the binary setting as 1

Setting value

Settings/ProtSet/Pls Input SetGrNo/ Func_Dead Zone, the detail

setting list refer to the “Reference setting list for test” in this

section

Binary input The corresponding side CB status “BAY1 CB OPEN”is 1

Active the binary input of “PHA INI BF BAY1”

Fault simulation

Input current into 1 feeder (bay 1) of busbar zone 1.

Current: 103% of the setting value, phase A

Duration: longer than 40s

Active the binary input of “BAY1 CB OPEN”

In the fifth second, active the binary input of “PHA INI BF BAY1”,

with duration shorter than the setting ''T_DeadZone''

Test result IED operation:

The corresponding output contacts should be closed, and the

Page 94: CSC-150 Busbar Protection IED Engineering and Operation Manual

Chapter 6 IED testing

84

Test item Description

operate time meets the requirement in technical data

Report:

“DeadZone startup”

“DeadZone Trip”

2 Verifying the settings of other phase

The test method and test items of verifying the other phase are

same as phase A, only need to change the corresponding test

conditions and settings into the conrresponding other phase

required.

3 Verifying the settings of other bay

The test method and test items of verifying the settings of other

bays are same as bay 1, only need to change the corresponding

test conditions and settings into the conrresponding bay 1 required.

8.3.2 Completing the test

Continue to test another function or end the test. Restore

connections and settings to their original values, if they were

changed for testing purposes.

8.3.3 Reference setting list for test

Table 26 Dead zone protection function setting list

NO. Default Abbr. Explanation Unit Min. Max.

1. 0.1 T_DeadZone:Bay1 Time delay of dead zone

protection for bay 1 s 0 32.00

2. 0.1 T_DeadZone:Bay2 Time delay of dead zone

protection for bay 2 s 0 32.00

3. 0.1 T_DeadZone:Bay3 Time delay of dead zone

protection for bay 3 s 0 32.00

4. 0.1 T_DeadZone:Bay4 Time delay of dead zone

protection for bay 4 s 0 32.00

5. 0.1 T_DeadZone:Bay5 Time delay of dead zone

protection for bay 5 s 0 32.00

6. 0.1 T_DeadZone:Bay6 Time delay of dead zone

protection for bay 6 s 0 32.00

Page 95: CSC-150 Busbar Protection IED Engineering and Operation Manual

Chapter 6 IED testing

85

7. 0.1 T_DeadZone:Bay7 Time delay of dead zone

protection for bay 7 s 0 32.00

8. 0.1 T_DeadZone:Bay8 Time delay of dead zone

protection for bay 8 s 0 32.00

9. 0.1 T_DeadZone:Bay9 Time delay of dead zone

protection for bay 9 s 0 32.00

10. 0.1 T_DeadZone:Bay10 Time delay of dead zone

protection for bay 10 s 0 32.00

11. 0.1 T_DeadZone:Bay11 Time delay of dead zone

protection for bay 11 s 0 32.00

12. 0.1 T_DeadZone:Bay12 Time delay of dead zone

protection for bay 12 s 0 32.00

13. 0.1 T_DeadZone:Bay13 Time delay of dead zone

protection for bay 13 s 0 32.00

14. 0.1 T_DeadZone:Bay14 Time delay of dead zone

protection for bay 14 s 0 32.00

15. 0.1 T_DeadZone:Bay15 Time delay of dead zone

protection for bay 15 s 0 32.00

16. 0.1 T_DeadZone:Bay16 Time delay of dead zone

protection for bay 16 s 0 32.00

17. 0.1 T_DeadZone:Bay17 Time delay of dead zone

protection for bay 17 s 0 32.00

Table 27 Dead zone protection binary setting list

Name Description Default Unit Min. Max.

Bay1 Func_Dead Zone On Enable or disable the dead

zone protection for bay 1 0 0 1

Bay2 Func_Dead Zone On Enable or disable the dead

zone protection for bay 2 0 0 1

Bay3 Func_Dead Zone On Enable or disable the dead

zone protection for bay 3 0 0 1

Bay4 Func_Dead Zone On Enable or disable the dead

zone protection for bay 4 0 0 1

Bay5 Func_Dead Zone On Enable or disable the dead

zone protection for bay 5 0 0 1

Bay6 Func_Dead Zone On Enable or disable the dead

zone protection for bay 6 0 0 1

Bay7 Func_Dead Zone On Enable or disable the dead

zone protection for bay 7 0 0 1

Bay8 Func_Dead Zone On Enable or disable the dead

zone protection for bay 8 0 0 1

Page 96: CSC-150 Busbar Protection IED Engineering and Operation Manual

Chapter 6 IED testing

86

Name Description Default Unit Min. Max.

Bay9 Func_Dead Zone On Enable or disable the dead

zone protection for bay 9 0 0 1

Bay10 Func_Dead Zone On Enable or disable the dead

zone protection for bay 10 0 0 1

Bay11 Func_Dead Zone On Enable or disable the dead

zone protection for bay 11 0 0 1

Bay12 Func_Dead Zone On Enable or disable the dead

zone protection for bay 12 0 0 1

Bay13 Func_Dead Zone On Enable or disable the dead

zone protection for bay 13 0 0 1

Bay14 Func_Dead Zone On Enable or disable the dead

zone protection for bay 14 0 0 1

Bay15 Func_Dead Zone On Enable or disable the dead

zone protection for bay 15 0 0 1

Bay16 Func_Dead Zone On Enable or disable the dead

zone protection for bay 16 0 0 1

Bay17 Func_Dead Zone On Enable or disable the dead

zone protection for bay 17 0 0 1

8.4 Voltage transformer secondary circuit supervision

Before starting the test, please make sure that the protection

function setting values and parameters are correct, refer to section

Introduction, Points for attention during testing and Preparing

for test in this chapter.

8.4.1 Verifying the settings

8.4.1.1 Three-phase VT failure surpervision

1 Verifying the phase-to-earth voltage setting

Table 28 Phase-to-earth voltage setting verifying

Test item Description

103% of the phase-to-earth voltage setting verifying

Binary setting Settings/EquipPara/Bus Voltage Connected, set the binary

setting as 1

Setting value Detail setting list refer to the “Reference setting list for test” in this

section

Page 97: CSC-150 Busbar Protection IED Engineering and Operation Manual

Chapter 6 IED testing

87

Test item Description

Binary input None

Fault simulation

Pre-fault stage:

Input voltage into busbar 1

Voltage: rated, three phase

Input current into one feeder of busbar 1

Current: rated current

Duration:5s

Fault stage:

Decrease voltage suddenly to 103% of the threshold value (8V),

three phase

Continue inputting rated current into one feeder of busbar 1

Duration: 20s

Test result IED operation:

The corresponding output contacts should not close

97% of the phase-to-earth voltage setting verifying

Binary setting Settings/EquipPara/Bus Voltage Connected, set the binary

setting as 1

Setting value Detail setting list refer to the “Reference setting list for test” in this

section

Binary input None

Fault simulation

Pre-fault stage:

Input voltage into busbar 1

Voltage: rated, three phase

Input current into one feeder of busbar 1

Current: rated current

Duration:5s

Fault stage:

Decrease voltage suddenly to 97% of the threshold value (8V),

three phase

Continue inputting rated current into one feeder of busbar 1

Duration: 20s

Test result

IED operation:

The corresponding output contacts should be closed

Report:

“BZ1 VT Fail” with 10s delay

8.4.1.2 Single/ two phases VT failure surpervision

1 Verifying the zero-sequence voltage setting

Table 29 Zero-sequence voltage setting verifying

Test item Description

Page 98: CSC-150 Busbar Protection IED Engineering and Operation Manual

Chapter 6 IED testing

88

Test item Description

103% of the phase-to-earth voltage setting verifying

Binary setting Settings/EquipPara/Bus Voltage Connected, set the binary

setting as 1

Setting value Detail setting list refer to the “Reference setting list for test” in this

section

Binary input None

Fault simulation

Pre-fault stage:

Input voltage into busbar 1

Voltage: rated, three phase

Duration:5s

Fault stage:

Decrease voltage suddenly to 103% of the threshold value

(7/3V), phase A, B and C with same phase angle

Duration: 20s

Test result

IED operation:

The corresponding output contacts should be closed

Report:

“BZ1 VT Fail” with 10s delay

97% of the phase-to-earth voltage setting verifying

Binary setting Settings/EquipPara/Bus Voltage Connected, set the binary

setting as 1

Setting value Settings/ProtSet/Pls Input SetGrNo/Other Set, the detail setting

list refer to the “Reference setting list for test” in this section

Binary input None

Fault simulation

Pre-fault stage:

Input voltage into busbar 1

Voltage: rated, three phase

Duration:5s

Fault stage:

Decrease voltage suddenly to 97% of the threshold value (7/3V),

phase A, B and C with same phase angle

Duration: 20s

Test result IED operation:

The corresponding output contacts should not close

2 Verifying the settings of other bay

The test method and test items of verifying the settings of other

bays are same as bay 1, only need to change the corresponding

test conditions and settings into the conrresponding bay 1 required.

8.4.2 Completing the test

Page 99: CSC-150 Busbar Protection IED Engineering and Operation Manual

Chapter 6 IED testing

89

Continue to test another function or end the test. Restore

connections and settings to their original values, if they were

changed for testing purposes.

8.4.3 Reference setting list for test

Table 30 VT failure supervision function setting list

Setting Title Unit Defa

ult Min. Max. Comment

Bus Voltage Connected 0 0 1

VT failure supervision function

enabled or disabled

1-On, 0-Off.

Page 100: CSC-150 Busbar Protection IED Engineering and Operation Manual

Chapter 6 IED testing

90

9 Checking before operation

Note: The following items are only for reference. Users should

make the proper operation guideline based on the actual site

conditions

9.1 Checking the LED

Power on the IED, the LED “Run” is lit steadily in green, other LEDs

should be extinguished.

9.2 Checking the display on LCD

In normal operation condition, the information of “year-month-day,

hour : minute : second, magnitude and angle of analog quantities,

channel state, current setting group: 01” should be scrolling

displayed on the LCD.

9.3 Checking the clock

After setting the date and time of the IED, power on and off the IED

with five times in short time, checking the tolerance of date and

time is within the permissible range.

9.4 Checking the voltage and current

Inject system currents (load current must be larger than 0.08In) and

voltages into the IED, and then check whether the magnitude,

phase angle, polarity and phase sequence of each measuring

analog value are correct or not.

9.5 Checking the setting group

Make sure the active setting group is correct.

9.6 Checking the setting

Checking the settings one by one of each group which are possibly

Page 101: CSC-150 Busbar Protection IED Engineering and Operation Manual

Chapter 6 IED testing

91

used in the actual operation modes.

9.7 Checking the binary input

Check the state of all binary inputs. Particularly ensure that the IED

is not in test mode, meaning there is not a hand type icon displayed

at the upright corner of the LCD.

9.8 Checking the normal operation mode

9.8.1 Trip and close test with the circuit breaker

9.8.1.1 Switching the circuit breaker state by local command

Trip and close the circuit breaker, the corresponding feedback state

of circuit breaker injected via binary inputs should be read out and

compared with the actual state of circuit breaker, the displayed

state should be in accordance with the actual state.

9.8.1.2 Switching the circuit breaker state from remote control

center

If the IED is connected to a remote substation via SCADA, the

corresponding switching tests may also be checked from the

substation.

9.9 Put into operation

If all the checking items described above and the other checking

items need to be performed according to the site condition have

been checked and correct, the IED can be put into operation.

Page 102: CSC-150 Busbar Protection IED Engineering and Operation Manual

Chapter 6 IED testing

92

Page 103: CSC-150 Busbar Protection IED Engineering and Operation Manual

Chapter 7 Operating maintenance

93

Chapter 7 Operating maintenance

About this chapter

This chapter introduces attentions and the required checking, operation after

updating software or replacing modules and the measure for alarm

information.

Page 104: CSC-150 Busbar Protection IED Engineering and Operation Manual

Chapter 7 Operating maintenance

94

1 Attentions during operating

Warning

Do not disconnect the secondary circuit connection of current

transformer without short-circuiting the transformer's secondary

winding. Operating a current transformer with the secondary

winding open will cause a masssive potential that may damage the

current transformer and may cause injuries to humans.

Caution

Never connect or disconnect a wire and/or a connector to or from a

IED during normal operation. Dangerous voltages and currents are

present that may be lethal. Operation may be disrupted and IED and

measuring circuitry may be damaged.

Note

Strictly follow the power system operation maintenance instruction

or regulations, the following items for reference:

During operating, prohibition the following operation manually:

Touch the parts of IED with electricity

Plug in and pull out each module

Manually operation to the HMI menu:

Testing binary output

Changing setting value

Setting systme parameter

Changing the IP address

Fault occurrence during operation, if the protection IED tripping, the

corresponding LED in front panel will be lighted, and the event reports

will be displayed in HMI; if the auto-reclosing function operate, the

Page 105: CSC-150 Busbar Protection IED Engineering and Operation Manual

Chapter 7 Operating maintenance

95

corresponding LED will be lighted and the reports will be displayed in

HMI

If the alarming class I appearance during operation, stop running the IED,

record the alarm information and inform the responsible engineer, at this

time, it is not allowed to press the Reset button. If the alarming class II

appearance, record the alarm information and inform the responsible

engineer to analyse and deal with.

Page 106: CSC-150 Busbar Protection IED Engineering and Operation Manual

Chapter 7 Operating maintenance

96

2 Routine checking

Checking the LEDs status

Checking scroll display information in HMI

Checking the setting group number

Page 107: CSC-150 Busbar Protection IED Engineering and Operation Manual

Chapter 7 Operating maintenance

97

3 Periodical checking

Check that the inside and outside of the IED are cleanly and no ash

deposition

All components (including the chips, transformer and relay, etc.) of the

IED are fixed well, no loosing phenomenon, the IED apperance is regular

and no damage and distortion phenomenon

The buttons are operated flexibly with good feeling and fixed reliably

All the IED terminals for connection are firmd without loosing

phenomenon, and the marked number are clear and correct

Energizing the IED with DC power supply for several seconds, the green

“Run” LED will be lighted without any alarm or operation lED lighted (if

lighted, press Reset button to reset), the analog quantities is displayed in

HMI

Check the zero drift and scale

Check the operation setting values

Measure the output voltage of power supply

Check the alarm circuit

Check the binary input

Check the tripping and closing circuit

Test the insulation resistance

Page 108: CSC-150 Busbar Protection IED Engineering and Operation Manual

Chapter 7 Operating maintenance

98

4 Operation after updating software or replacing modules

4.1 Operation after updating software or replacing CPU module

If the IED software needs to be updated or the CPU module needs to be

replaced for some problem that can’t be handled during operation, the

corresponding operation as follows:

Check the address jumper of CPU module is correct, and input and write

the setting values and parameters

Check the CPU software version number and CRC code

Check the zero drift and scale of all analog quantities channel again

Test all the binary inputs and outputs

Check the setting value and setting group

Perform other relevant testing according to the user’s site operating

regulation before the IED is in service

4.2 Operation after updating software or replacing communication module

Downloading the latest version configuration files to the communication

module by software tool

Checking the detail information for the following items:

Checking the communication module version and the software

version

Checking the communication parameter and protocol, etc.

Configuring the communication module configuration according to the

former configuration or enter into the former configuration again

Set the following parameters:

Page 109: CSC-150 Busbar Protection IED Engineering and Operation Manual

Chapter 7 Operating maintenance

99

The setting value property and communication mode

Set the network address

Set the IED time again

Check the scroll display is correct after energizing

Perform relevant testing operation

4.3 Operation after replacing the binary input or output module

Check the address jumper of the module is correct

Test all the binary inputs or outputs and the related external secondary

circuit before the IED is in service

4.4 Operation after replacing the analog input module

Check the value and polarity of all analog quantities channel is correct

4.5 Operation after replacing power supply module

Check the accuracy of the output voltage

Test the output relay

Test the binary inputs

Page 110: CSC-150 Busbar Protection IED Engineering and Operation Manual

Chapter 7 Operating maintenance

100

5 The alarm information and measure

5.1 Alarm information

Table 31 Alarm information

No. Abbr. (LCD Display) Description

1 AI Err Analogue input error

2 B/C CBF StartErr CBF of bus coupler startup error

3 B/C CT Fail: PhA Phase A of bus coupler CT fail

4 B/C CT Fail: PhB Phase B of bus coupler CT fail

5 B/C CT Fail: PhC Phase C of bus coupler CT fail

6 Battery Off Battery off

7 Bus Tied Bus Tied

8 BZ1 CT Fail: PhA Phase A of busbar zone 1 CT fail

9 BZ1 CT Fail: PhB Phase B of busbar zone 1 CT fail

10 BZ1 CT Fail: PhC Phase C of busbar zone 1 CT fail

11 BZ1 VT Fail Busbar zone 1 VT fail

12 BZ2 CT Fail: PhA Phase A of busbar zone 2 CT fail

13 BZ2 CT Fail: PhB Phase B of busbar zone 2 CT fail

14 BZ2 CT Fail: PhC Phase C of busbar zone 2 CT fail

15 BZ2 VT Fail Busbar zone 2 VT fail

16 BZT CT Fail: PhA Phase A of transfer busbar zone CT fail

17 BZT CT Fail: PhB Phase B of transfer busbar zone CT fail

18 BZT CT Fail: PhC Phase C of transfer busbar zone CT fail

19 BZT VT Fail Transfer bus VT fail

20 CAN Comm Fail CAN network communication fail

21 CAN Comm Recover CAN network communication recorver

22 CB Discord CB discordance

23 CT Ratio Err CT ratio error

24 CT Secondary Err Secondary side CT error

25 DI Breakdown Binary input break down

26 DI Check Err Binary input check error

27 DI Comm Fail Binary input communication fail

28 DI Config Err Binary input configuration error

29 DI EEPROM Err Binary input EEPROM error

30 DI Err Binary input error

31 DI Input Err Binary input input error

32 DI Module Err Binary input module error

33 DO Breakdown Binary output breakdown

34 DO Comm Fail Binary output communication fail

Page 111: CSC-150 Busbar Protection IED Engineering and Operation Manual

Chapter 7 Operating maintenance

101

No. Abbr. (LCD Display) Description

35 DO Config Err Binary output configuration error

36 DO EEPROM Err Binary output EEPROM error

37 DO Module Err Binary output module error

38 DO No Response Binary output no response

39 EquipPara Err Equipment parameter error

40 FLASH Check Err Falsh check error

41 Isol DC Failure Isolator DC failure

42 Isol Failure Isolator failure

43 NO/NC Discord NO/NC discordance

44 ROM Verify Err ROM verify error

45 Sample Data Err Sample data error

46 Sampling Err Sampling error

47 SamROM VerifyErr Sample ROM verify error

48 Set Group Err Setting group Error

49 Setting Err Setting error

50 Soft Version Err Software version error

51 SRAM Check Err SRAM check error

52 Start 3-Ph Err Startup three phase error

53 Start A-Ph Err Startup phase A error

54 Start B-Ph Err Startup phase B error

55 Start C-Ph Err Startup phase C error

56 SysConfig Err System configuration error

57 TBC CB Discord Transfer bus coupler CB discordance

58 Test DO Un-reset Test binary output unreset

Page 112: CSC-150 Busbar Protection IED Engineering and Operation Manual

Chapter 7 Operating maintenance

102

Page 113: CSC-150 Busbar Protection IED Engineering and Operation Manual

Chapter 8 Transportation and storage

103

Chapter 8 Transportation and storage

About this chapter

This chapter describes how to transport and store the IED.

Page 114: CSC-150 Busbar Protection IED Engineering and Operation Manual

Chapter 8 Transportation and storage

104

1 Transportion

The IED can be transported by means of conveyance, such as car, train, ship, etc. In order to ensure the perfect performance of the IED, prevent the IED from rain, snow, vibration, shock and bump.

Page 115: CSC-150 Busbar Protection IED Engineering and Operation Manual

Chapter 8 Transportation and storage

105

2 Storage

If the IED is to be stored before installation, this is must be done in the original

transport casing in a dry and dust free place. The packed IED should be

stored in a waterproof and snow proof place without acid or alkaline or other

corrosive gas and explosive gas. The storage temperature is from -25°C to

+40°C, and the relative humidity does not exceed 80%. Observe the

environmental requirements stated in the technical data.

Page 116: CSC-150 Busbar Protection IED Engineering and Operation Manual

Chapter 8 Transportation and storage

106

Page 117: CSC-150 Busbar Protection IED Engineering and Operation Manual

Chapter 9 Appendix

107

Chapter 9 Appendix

About this chapter

This chapter contains the diagram of modules arrangement, typical

connection, glossary and the protocol data table.

Page 118: CSC-150 Busbar Protection IED Engineering and Operation Manual

Chapter 9 Appendix

108

1 Arrangement diagram of modules

CAN

Test

port

AIM

AIM

AIM

AIM

AIM

AIM

AIM

AIM

BO

M

CP

U2

CP

U1

BO

M

BO

M

PS

M

BO

M

BO

M

BIM

BO

M

PS

M

CO

M

X1X2X3X4X5X6X7X9

X10X11X12X13X14X15X16X17X18X19

X8

Figure 17 Rear view of the protection 8U IED

BIM

BIM

BIM

BIM

BIM

BIM

BIM

X20X21X22X23X24X25X27

CAN

X26

Figure 18 Rear view of the protection 4U IED

Page 119: CSC-150 Busbar Protection IED Engineering and Operation Manual

Chapter 9 Appendix

109

2 Typical diagram

A. Single busbar with line side CTs arrangement

Busbar-A

CSC-

150

Figure 19 Typical connection diagram A

B. Single busbar with bus side CTs arrangement

Busbar-A

CSC-

150

Figure 20 Typical connection diagram B

Page 120: CSC-150 Busbar Protection IED Engineering and Operation Manual

Chapter 9 Appendix

110

C. Single busbar with tie disconnector (line side CTs) arrangement

Busbar-A

CSC-

150

Busbar-B

Figure 21 Typical connection diagram C

D. Single busbar with tie disconnector (bus side CTs) arrangement

Busbar-A

CSC-

150

Busbar-B

Figure 22 Typical connection diagram D

Page 121: CSC-150 Busbar Protection IED Engineering and Operation Manual

Chapter 9 Appendix

111

E. Single busbar with tie disconnector and one CT (line side CTs) arrangement

Busbar-A

CSC-

150

Busbar-B

Figure 23 Typical connection diagram E

F. Two single busbars connected with bus coupler and one CT (line side CTs) arrangement

Busbar-A

CSC-

150

Busbar-B

Figure 24 Typical connection diagram F

Page 122: CSC-150 Busbar Protection IED Engineering and Operation Manual

Chapter 9 Appendix

112

G. Two single busbars connected with bus coupler and one CT (bus side CTs) arrangement

Busbar-A

CSC-

150

Busbar-B

Figure 25 Typical connection diagram G

H. Two single busbars connected with bus coupler and two CTs (line side CTs) arrangement

Busbar-A

CSC-

150

Busbar-B

Figure 26 Typical connection diagram H

Page 123: CSC-150 Busbar Protection IED Engineering and Operation Manual

Chapter 9 Appendix

113

I. Two single busbars connected with bus coupler and two CTs (bus side CTs) arrangement

Busbar-A

CSC-

150

Busbar-B

Figure 27 Typical connection diagram I

J. One and half breaker arrangement

Busbar-B

Busbar-A

CSC-

150

Figure 28 Typical connection diagram J

Page 124: CSC-150 Busbar Protection IED Engineering and Operation Manual

Chapter 9 Appendix

114

K. Double busbar with one coupler CT arrangement

Busbar-A

Busbar-B

CSC-

150

Figure 29 Typical connection diagram K

L. Double busbar with two coupler CTs arrangement

Busbar-A

Busbar-B

CSC-

150

Figure 30 Typical connection diagram L

Page 125: CSC-150 Busbar Protection IED Engineering and Operation Manual

Chapter 9 Appendix

115

M. Main and transfer busbar with two coupler CTs (inside CTs) arrangement

Busbar-A

Busbar-B

CSC-

150

Figure 31 Typical connection diagram M

N. Main and transfer busbar with two coupler CTs (outside CTs) arrangement

Busbar-A

Busbar-B

CSC-

150

Figure 32 Typical connection diagram N

Page 126: CSC-150 Busbar Protection IED Engineering and Operation Manual

Chapter 9 Appendix

116

O. Main and transfer busbar with one coupler CTs (inside CTs) arrangement

Busbar-A

Busbar-B

CSC-

150

Figure 33 Typical connection diagram O

P. Main and transfer busbar with one coupler CTs (outside CTs) arrangement

Busbar-A

Busbar-B

CSC-

150

Figure 34 Typical connection diagram P

Page 127: CSC-150 Busbar Protection IED Engineering and Operation Manual

Chapter 9 Appendix

117

Q. Main and transfer busbar without coupler CTs (outside CTs) arrangement

Busbar-A

Busbar-B

CSC-

150

Figure 35 Typical connection diagram Q

R. Main and main and/or transfer busbar with inside CTs arrangement

Busbar-A

Busbar-B

CSC-

150

Figure 36 Typical connection diagram R

Page 128: CSC-150 Busbar Protection IED Engineering and Operation Manual

Chapter 9 Appendix

118

S. Main and main and/or transfer busbar with outside CTs arrangement

Busbar-A

Busbar-B

CSC-

150

Figure 37 Typical connection diagram S

T. Double main and transfer busbar with inside CTs arrangement

Busbar-A

Busbar-B

Busbar-C

CSC-

150

Figure 38 Typical connection diagram T

Page 129: CSC-150 Busbar Protection IED Engineering and Operation Manual

Chapter 9 Appendix

119

U. Double main and transfer busbar with outside CTs arrangement

Busbar-A

Busbar-B

Busbar-C

CSC-

150

Figure 39 Typical connection diagram U