CD03: 3/6/1995: CLOSURE REPORT: UST CLOSURE CONSULTING … · 2019. 7. 29. · GeosciencesInc...

18
,, i UST CLOSURE CONSULTING SERVICES BUILDING PT-3 CAMP LEJEUNE, NORTH CAROLINA CONTRACT #N62470-93-B-0286 GEOSCIENCES JOB NO. MC-94-177A PREPARED FOR OMEGA ENVIRONMENTAL SERVICES, INC. 4661 HAMMERMILL ROAD SUITE B TUCKER, GEORGIA 30084 PREPARED BY GEOSCIENCES, INC. 5021 MERCER UNIVERSITY DRIVE SUITE D-2 MACON, GEORGIA 31210

Transcript of CD03: 3/6/1995: CLOSURE REPORT: UST CLOSURE CONSULTING … · 2019. 7. 29. · GeosciencesInc...

Page 1: CD03: 3/6/1995: CLOSURE REPORT: UST CLOSURE CONSULTING … · 2019. 7. 29. · GeosciencesInc CEOTECHNICAL, ENVIRONMENTAL & CONSTRUCI’ION MATERIALS CONSULTANTS March 6, 1995 Mr.

,, i

UST CLOSURE CONSULTING SERVICES BUILDING PT-3

CAMP LEJEUNE, NORTH CAROLINA CONTRACT #N62470-93-B-0286

GEOSCIENCES JOB NO. MC-94-177A

PREPARED FOR OMEGA ENVIRONMENTAL SERVICES, INC.

4661 HAMMERMILL ROAD SUITE B

TUCKER, GEORGIA 30084

PREPARED BY GEOSCIENCES, INC.

5021 MERCER UNIVERSITY DRIVE SUITE D-2

MACON, GEORGIA 31210

Page 2: CD03: 3/6/1995: CLOSURE REPORT: UST CLOSURE CONSULTING … · 2019. 7. 29. · GeosciencesInc CEOTECHNICAL, ENVIRONMENTAL & CONSTRUCI’ION MATERIALS CONSULTANTS March 6, 1995 Mr.

GeosciencesInc CEOTECHNICAL, ENVIRONMENTAL & CONSTRUCI’ION MATERIALS CONSULTANTS

March 6, 1995

Mr. Doug Driver Omega Environmental Services, Inc. 4661 Hammermill Road Suite B Tucker, Georgia 30084

SUBJECT: UST Closure Consulting Services, PT-3 Camp Lejeune, North Carolina Contract #N62470-93-B-0286 Geosciences Job No. MC-94-177A

Dear Mr. Driver:

Geosciences, Inc. is pleased to present this report of the Underground Storage Tank (UST) Closure consulting services at the above referenced site. At the discretion of the Camp Lejeune Environmental Management Division (EMD), a copy of this report may be submitted to the North Carolina Department of Environment, Health and Natural Resources, Wilmington Regional Office, 127 Cardinal Drive Extension, Wilmington, NC 28405-3845. North Carolina Form GW/UST2 (Appendix II) should also be signed by the UST owner or the owner's authorized representative.

Geosciences, Inc. greatly appreciates the opportunity to provide these services to you. If you have any questions, or need further assistance, please do not hesitate to call.

Very Truly Yours, GEOSCIENC&3, INC.

H ,’ 'Thomas 2, Driver, P.E. Senior Engineer NC. Fteg. #19125

Page 3: CD03: 3/6/1995: CLOSURE REPORT: UST CLOSURE CONSULTING … · 2019. 7. 29. · GeosciencesInc CEOTECHNICAL, ENVIRONMENTAL & CONSTRUCI’ION MATERIALS CONSULTANTS March 6, 1995 Mr.

TABLE OF CONTENTS

PAGE #

1.0 PROJECT INFORMATION

2.0 UST SITE LOCATION

3.0 UST REMOVAL

4.0 SOIL SAMPLING SCREENING PROCEDURES 4.1 QUALITY CONTROL MEASURES

5.0 SAMPLE RESULTS

6.0 FINAL DESTINATION OF UST AND CONTENTS

1

1

1

2 2

2

3

APPENDIX I

FIGURE 1: U.S.G.S. QUADRANGLE MAP, SITE LOCATION FIGURE 2: SCALE MAP OF THE UST SITE

APPENDIX II

NORTH CAROLINA FORM GW/UST-2

APPENDIX III

UST CERTIFICATE OF DESTRUCTION UST CONTENTS MANIFEST

APPENDIX IV

PHOTOGRAPHS

Page 4: CD03: 3/6/1995: CLOSURE REPORT: UST CLOSURE CONSULTING … · 2019. 7. 29. · GeosciencesInc CEOTECHNICAL, ENVIRONMENTAL & CONSTRUCI’ION MATERIALS CONSULTANTS March 6, 1995 Mr.

1.0 PROJECT INFORMATION

Omega Environmental Services, Inc., (OES) of Tucker, Georgia performed the removal of Underground Storage Tanks (USTs) at the Marine Corps Base, Camp Lejeune, North Carolina, and the Marine Corps Air Station, New River, Jacksonville, North Carolina. A base map and scale map of the subject UST site is included in Appendix I. The work described in this report was undertaken adjacent to building PT-3. The work was conducted in general accordance with Contract N62470-93-B-0286 and subsequent amendments to the specifications or special instructions from the contracting office.

Omega Environmental's senior project manager for the work is Doug Driver, (404) 621-9414. The Installation Contracting Officer assigned to the project is LTJG Kevin Bartoe, (910) 451-5821. Additional contact information is provided on Form GW-UST-2 in Appendix II.

OES retained Geosciences, Inc. to monitor the site assessment portion of the UST Closures, perform soil/groundwater sampling as instructed by the Contracting Office, and upon completion of the project, submit UST Site Closure Reports to the Camp Lejeune Contracting Officer.

UST status determinations as "Regulated" or "Nonregulated" were made solely by the Contract Specifications or the Camp Lejeune Contracting Office. This report details the close-out of a site which the specifications defined as Nonregulated.

Where possible, this report meets the general UST Closure information requirements of North Carolina Administrative Code 15A NCAC 2N .0800, and The Groundwater Section Guidelines For The Investigation and Remediation of Soils and Groundwater, Section 11.3, Site Closure. However, analytical testing of soil and/or groundwater was conducted only by the direction of the Contracting Office, and Geosciences was not instructed to submit samples for analytical testing at this UST site.

Close-out of Nonregulated sites may be approved by the North Carolina Department of Environment, Health, and Natural Resources when documentation is provided that indicates no contaminated soils remain in excess of the appropriate cleanup level (Site Sensitivity Evaluation - SSE). Establishing the appropriate SSE action levels for the subject UST site was beyond the scope of Geosciences services.

2.0 UST SITE LOCATION

The general vicinity of PT-3 can be found on the Camp Lejeune, NC U.S.G.S. Quadrangle Map, Appendix I, Figure 1. A detailed scale map of the excavation area is also provided in Appendix I, Figure 2.

PAGE -I-

Page 5: CD03: 3/6/1995: CLOSURE REPORT: UST CLOSURE CONSULTING … · 2019. 7. 29. · GeosciencesInc CEOTECHNICAL, ENVIRONMENTAL & CONSTRUCI’ION MATERIALS CONSULTANTS March 6, 1995 Mr.

3.0 UST REMOVAL

OES removed the UST at building PT-3 on November 22, 1994. The removal began by draining the UST piping into the tank. Product was then removed from the UST. A backhoe was used to excavate down to the tank top. All lines were then capped except the fill and vent. The UST was purged of practically all product and sludge by a vacuum truck and a compressor driven barrel vacuum. Vapors were purged with an eductor-type air mover driven by compressed air. After essentially all product, sludge and vapors were removed, all accessible tank openings were capped except for a l/8 inch vent hole, and the tank was lifted from the excavation with a backhoe and chains.

4.0 SOIL SAMPLING/SCREENING PROCEDURES

Geosciences used a Mini RAE Systems, Inc. Professional Photoionization Detector (PID) to screen excavated soils and soils at the excavation limits for petroleum hydrocarbon vapors. The PID was calibrated before each use in the field as per the manufacturer's instructions.

The soil contamination headspace analysis technique consists of filling a 16 ounce jar half full with soil and tightly sealing it with foil. After the temperature of the jar and its contents has equilibrated, the probe of the PID is inserted through the foil seal to measure the concentration of organic vapors in the space between the soil and the foil seal (headspace).

Every effort was made to collect soils which were representative samples, with as little debris as possible. Samples were collected from the excavated soils and from the base of the excavation, or from the lower one third of the excavation area.

4.1 QUALITY CONTROL MEASURES

Soil samples were transferred directly to the 16 ounce jar from a stainless steel hand auger or from the backhoe bucket with a stainless steel spoon. Sampling equipment was cleaned between sample locations with a laboratory grade detergent, isopropanol, and tap water rinse. The soil jars were also washed between samples and allowed to air dry. Disposable sampling gloves were worn when obtaining the soil samples.

5.0 SAMPLE RESULTS

Several soil contamination headspace analyses were performed during the UST removal. The range of the highest headspace readings encountered in the excavated soils and from the base of the excavation is provided below:

PAGE -2-

Page 6: CD03: 3/6/1995: CLOSURE REPORT: UST CLOSURE CONSULTING … · 2019. 7. 29. · GeosciencesInc CEOTECHNICAL, ENVIRONMENTAL & CONSTRUCI’ION MATERIALS CONSULTANTS March 6, 1995 Mr.

Headspace samples were not taken from the capillary fringe (transition zone from the soil column to the water table) or below the water table.

Based on the PID screening results, returned to the excavation.

6.0 FINAL DESTINATION OF UST AND CONTENTS

The removed UST was cleaned and scrapped by OES in accordance with American Petroleum Institute (API) Recommended Practices 1604, 2015, and 2015A.

A Certificate of Destruction signed by John Fleming (OES) is provided in Appendix III. Further information regarding the destruction and destination of the UST can be obtained from Doug Driver (OES) at (404) 621-9414.

All UST contents, including sludges, were removed by Noble Oil Services, 5617 Clyde Rhyne Dr., Sanford, NC 27330. Approximately 1800 gallons were removed from the PT-3 UST. A copy of the Noble Removal Manifest is included in Appendix III. Please note that the manifest may include the UST contents from other UST closure sites.

PAGE -3-

Page 7: CD03: 3/6/1995: CLOSURE REPORT: UST CLOSURE CONSULTING … · 2019. 7. 29. · GeosciencesInc CEOTECHNICAL, ENVIRONMENTAL & CONSTRUCI’ION MATERIALS CONSULTANTS March 6, 1995 Mr.

APPENDIX I

Page 8: CD03: 3/6/1995: CLOSURE REPORT: UST CLOSURE CONSULTING … · 2019. 7. 29. · GeosciencesInc CEOTECHNICAL, ENVIRONMENTAL & CONSTRUCI’ION MATERIALS CONSULTANTS March 6, 1995 Mr.

Foul

?ARNELL

BA Y

Figure 1 Site Location Map, Camp Lejeune, NC

U.S.G.S.

Geosciences Job No. KC-94-177A Geoscienceslnc.

Page 9: CD03: 3/6/1995: CLOSURE REPORT: UST CLOSURE CONSULTING … · 2019. 7. 29. · GeosciencesInc CEOTECHNICAL, ENVIRONMENTAL & CONSTRUCI’ION MATERIALS CONSULTANTS March 6, 1995 Mr.

_--- J -1 -7 ‘-1 -1 -l-l1l11l----ll‘=--l---li”l===Ir

r

i

NORTH

KENNEL

OFFICE

PT-3 NONREGULATED UST - HEATING FUEL (DIESEL) LENGTH = 17 FEET DIAMETER = 5.3 FEET VOLUME = 2725 GALLONS UST BOTTOM DEPTH = 8.5 FEET

SCALE: tin = 20ft

RABIES OBSERVATION KENNEL

EXCAVATION AREA AND UST /

FIGURE 2 UST CLOSURE, SITE PLAN, PT-3 CONTRACT a N62470-93-B-0286 CAMP LEJEUNE, NCRTH CAROLINA GEOSi:IENCES JOB NO. MC-94-177A GeosciencesI,,

Page 10: CD03: 3/6/1995: CLOSURE REPORT: UST CLOSURE CONSULTING … · 2019. 7. 29. · GeosciencesInc CEOTECHNICAL, ENVIRONMENTAL & CONSTRUCI’ION MATERIALS CONSULTANTS March 6, 1995 Mr.

APPENDIX II

Page 11: CD03: 3/6/1995: CLOSURE REPORT: UST CLOSURE CONSULTING … · 2019. 7. 29. · GeosciencesInc CEOTECHNICAL, ENVIRONMENTAL & CONSTRUCI’ION MATERIALS CONSULTANTS March 6, 1995 Mr.

‘TANKS Return Completed Form To: The appropriate OEM Regional Office according to the county of the facility’s location.

State Use Only

[SEE MAP ON REVERSE SIDE OF OWNER’S COPY (PINK) FOR REGIONAL I.D. Number OFFICE ADDRESS]. Date Received -1

Gxndere and return within (30) days following completion of site investigation.

BLDG. 1, PSC BOX 20084 I

Facility Name. MARINE CORPS BASE (or Company)

Facility ID # (if available). NC 61 70022580 :

County ONSLOW Street Address

ClrU:Cva Sbte. NC Z I I) &de~8542-0004 (or state Roa

(;puntv:# 8

_ Telephone Number: [ 910 ) 451-5063 Temr:( 910 \ 451-5063

See reverse side of pink copy :

(owner’s copy) for additional

information required by N.C. DEM

in the written report and sketch.

NOTE: The -assessmentportIon ~

of the tank closure must be con-

NFNT CLOSUmvfna or Abv _. _

a Contact local Iire marshal

cx Notify DEM R eglonal Office before abandonment [z1 Dram 8 flush Piping Into tank a Remove all product and residuals tram tank KJ Excavate down lo tank K? Cl can and inspect tank

&?~I Remove drop lube. fill p~pc. gauge pipe, vapor recovery tank connecttons svbmcrslble pumps and other tank fixtures

Cap or plug all lines excepl the vent and fill lines Purge tank of all producf 8 flammable vapors

Ei ht Om’ or more large hoks In the tanks IA : P.ir-kfill ltw ri,c<i

Date Tank(s) Permanently closed: I Date of Change-In-Scrvicc:

8 ;;I1 tank unbl maternal overflow tank opening

ug or cap all openings

H Llld Inert malenal used specify, Isconnect and cap or remove vent lme

.~__ ._ __

Page 12: CD03: 3/6/1995: CLOSURE REPORT: UST CLOSURE CONSULTING … · 2019. 7. 29. · GeosciencesInc CEOTECHNICAL, ENVIRONMENTAL & CONSTRUCI’ION MATERIALS CONSULTANTS March 6, 1995 Mr.

APPENDIX III

Page 13: CD03: 3/6/1995: CLOSURE REPORT: UST CLOSURE CONSULTING … · 2019. 7. 29. · GeosciencesInc CEOTECHNICAL, ENVIRONMENTAL & CONSTRUCI’ION MATERIALS CONSULTANTS March 6, 1995 Mr.

m . OMEGA ENVIRONMENTAL SERVICES, hc. ___-

4661 Hammermill Rd. Suite B Tucker, GA 3CO84 Tel: (404) 621-9414 Fax: (404) 934-X.51

OFFICER IN CHARGE OF CONSTRUCTION Jacksonville North Carolina Area 1005 Michael Road Camp LeJeune, North Carolina 28547-2521

Subject: Underground Storage Tank (UST) Certification of Destruction Contract N62470-93-B-0286

The undersigned certifies that the UST(s) listed below were removed, transported, cleaned and scrapped in general accordance with the following:

American Petroleum Institute (API) API RF’ 1604 API PUBL 2015

Code of Federal Regulation 29 CFR 1910 40 CFR 280

Corps of Engineers (COE) COE EM-385-l-l

The UST was received from: Camp LeJeune Building PT - 3

For destruction, the UST was delivered to:

Jacksonville Scrap Iron and Metal Company, Inc.

UST ID#: PT - 3

Place of Origin: Parachute Tower

Date: 11-22-94

Buyer: Jacksonville Scrap Iron and Metal Company, Inc.

Seller: Omega Environmental Services, Inc.

If there are any questions regarding this Certificate of Destruction, please contact Doug Driver or John Fleming at Omega Environmental Services, Inc.

Page 14: CD03: 3/6/1995: CLOSURE REPORT: UST CLOSURE CONSULTING … · 2019. 7. 29. · GeosciencesInc CEOTECHNICAL, ENVIRONMENTAL & CONSTRUCI’ION MATERIALS CONSULTANTS March 6, 1995 Mr.

INDUSTRIAL SERVICES DIVISION l-800-662-5364 5617 CLYDE RHYNE DR. SANFORD, N.C. 27330

25786

FOR EMERGENCY RESPONSE: Spill. Leak, Fire, Accident

24 HRS. PER DAY, 7 DAYS PER WEEK

EPA ID# NCD 9861-72476 DATE //-/7-y

TRUCK# 3-2 .

GENERATOR BILL TO:

DRUMS/ UNIT SRV MATERIAL

I PRICE CHARGE TOTAL

PETROLEUM OIL MIXTURE. N 0 S (USED OIL/WATER MIXTURE). COMBUSTIBLE LIOUID, UN 12jO. PG 11)

SLUDGE/NON-HAZARDOUS SOLIDS

GASOLINE. CLASS 3. UN 1203. PG II (GASOLINE) FOR RECOVERY/RECYCLING

GASOLINE/MIXTURE. CCASS 3. UN 1203. PG II (GASOLINE/WATER MIXTURE) FROM U S T ‘S OR EXEMPT

, -- FUEL OIL MIXTURE. COMBUSTIBLE LIOUID. NA 1993, PG Ill [FUEL OIL/WATER MIX) .3L’_

/

$ ,$,- L2 // < if. CA‘ G:

TERMS: PAYA& UPON RECEIPT TOTAL DUE

Generators Certification: PROFILE NUMBER

certify that the materials above are accurately described, classified, packaged, marked and labeled, and are in proper andition for transport according to applicable state, EPA, and D.O.T, regulations. Furthermore, l have no knowledge of any

hazardous waste contained or mixed with the material that is to be transported. I, the generator, expressly agree and promise +? hold Noble Oil Services, Inc. and all its officers and employees free from and otherwise indemnify the same against any and

II penalties and other liability resulting from uch materials under this manifest.

riuthorized Customer Agent (Sign) x

.Dble 011 Services Agent (Sign) x

Job

escrlptlon -__- --

Page 15: CD03: 3/6/1995: CLOSURE REPORT: UST CLOSURE CONSULTING … · 2019. 7. 29. · GeosciencesInc CEOTECHNICAL, ENVIRONMENTAL & CONSTRUCI’ION MATERIALS CONSULTANTS March 6, 1995 Mr.

APPENDIX IV

Page 16: CD03: 3/6/1995: CLOSURE REPORT: UST CLOSURE CONSULTING … · 2019. 7. 29. · GeosciencesInc CEOTECHNICAL, ENVIRONMENTAL & CONSTRUCI’ION MATERIALS CONSULTANTS March 6, 1995 Mr.

PHOTOGRAPH 1 SOUTH TO NORTH VIEW OF EXCAVATION SITE

PHOTOGRAPH 2 EXCAVATION AREA

Page 17: CD03: 3/6/1995: CLOSURE REPORT: UST CLOSURE CONSULTING … · 2019. 7. 29. · GeosciencesInc CEOTECHNICAL, ENVIRONMENTAL & CONSTRUCI’ION MATERIALS CONSULTANTS March 6, 1995 Mr.

PHOTOGRAPH 3 EXCAVATION AREA

(VENT PIPE APPARENT)

PHOTOGRAPH 4 EXCAVATION OF UST

Page 18: CD03: 3/6/1995: CLOSURE REPORT: UST CLOSURE CONSULTING … · 2019. 7. 29. · GeosciencesInc CEOTECHNICAL, ENVIRONMENTAL & CONSTRUCI’ION MATERIALS CONSULTANTS March 6, 1995 Mr.

rnvTvrjKArH 5 EXCAVATION OF UST