Busbar Protection IED

-Distributed model

Page 2: Busbar Protection IED - Toshiba€¦ ·  · 2017-11-21Programmable control, trip and alarm logic with PLC tool software Graphical LCD and 7 configurable function keys USB port for

GR-200 seriesThe GRtransmission/distribution networks and providing a platform for distributed and renewable energy systems and railway applications. Flexible adaptation is enabled using extensive hardware and modular software co

Meeting your needs Extensive hardware and modular software combinations provide the flexibility to meet your application and engineering requirements.Future upgrade paths and minor modifications are readily achievable on demand.

PowerfulIn addition to protection & control, GRadvantage of developments in information & comm

APPLICATION

GRBnext generation GRhigh speeduserrequirementspeace of mind.

200 seriesThe GR-200 Series is Toshiba’s next generation of protection and control IED’s, designed transmission/distribution networks and providing a platform for distributed and renewable energy systems and railway applications. Flexible adaptation is enabled using extensive hardware and modular software co

Meeting your needs Extensive hardware and modular software combinations provide the flexibility to meet your application and engineering requirements.Future upgrade paths and minor modifications are readily achievable on demand.owerful and wide application In addition to protection & control, GRadvantage of developments in information & comm

APPLICATION

B200 low impedance differential relay for busbarnext generation GRhigh speed and selective user-friendly IED will provide you requirements, in addition to offering peace of mind.

- GRB200 can be applied for various busbar systems.・ Single busbars with/without transfer・ Double busbars with/without transfer busbar・ Ring busbars with/without transfer busbar・ One and a half busbar・ Four bus

- GRB200 can detect phase and earth faults on the protectphase segregated current differential schemecan be input from feeders, sections and busbetween internal and external faults even in the event of CT saturation.

- Circuit breakalso available.

- Backup overcurrent - Communications

・ Within 61850

200 series - 200 Series is Toshiba’s next generation of protection and control IED’s, designed

transmission/distribution networks and providing a platform for distributed and renewable energy systems and railway applications. Flexible adaptation is enabled using extensive hardware and modular software co

Meeting your needs - Extensive hardware and modular software combinations provide the flexibility to meet your application and engineering requirements.Future upgrade paths and minor modifications are readily achievable on demand.

and wide application In addition to protection & control, GRadvantage of developments in information & comm

APPLICATION

low impedance differential relay for busbarnext generation GR-200 series IED platform and has b

and selective protection for friendly IED will provide you

in addition to offering

GRB200 can be applied for various busbar systems.Single busbars with/without transferDouble busbars with/without transfer busbarRing busbars with/without transfer busbarOne and a half busbarFour bus-coupler busbar

GRB200 can detect phase and earth faults on the protectphase segregated current differential schemecan be input from feeders, sections and busbetween internal and external faults even in the event of CT saturation.Circuit breaker failure protection, end zone protection and blind zone protection are also available.

ackup overcurrent Communications

Within a substation automation system or to a remote control centre,61850-8-1 [Station bus

200 Series is Toshiba’s next generation of protection and control IED’s, designed transmission/distribution networks and providing a platform for distributed and renewable energy systems and railway applications. Flexible adaptation is enabled using extensive hardware and modular software combinations facilitating an ap

Extensive hardware and modular software combinations provide the flexibility to meet your application and engineering requirements.Future upgrade paths and minor modifications are readily achievable on demand.

and wide application - In addition to protection & control, GR-200 has been designed to meet the challenges and take advantage of developments in information & comm

low impedance differential relay for busbar200 series IED platform and has b

protection for friendly IED will provide you with the flexibility to meet your application and engineering

in addition to offering outstanding

GRB200 can be applied for various busbar systems.Single busbars with/without transferDouble busbars with/without transfer busbarRing busbars with/without transfer busbarOne and a half busbar

coupler busbar GRB200 can detect phase and earth faults on the protectphase segregated current differential schemecan be input from feeders, sections and busbetween internal and external faults even in the event of CT saturation.

er failure protection, end zone protection and blind zone protection are

ackup overcurrent and earth fault

substation automation system or to a remote control centre,1 [Station bus].

2

200 Series is Toshiba’s next generation of protection and control IED’s, designed transmission/distribution networks and providing a platform for distributed and renewable energy systems and railway applications. Flexible adaptation is enabled using extensive

mbinations facilitating an ap

Extensive hardware and modular software combinations provide the flexibility to meet your application and engineering requirements. Future upgrade paths and minor modifications are readily achievable on demand.

200 has been designed to meet the challenges and take

advantage of developments in information & communications technology.

low impedance differential relay for busbar200 series IED platform and has b

protection for various typewith the flexibility to meet your application and engineering

outstanding performance, high quality and operational

GRB200 can be applied for various busbar systems.Single busbars with/without transfer busbarDouble busbars with/without transfer busbarRing busbars with/without transfer busbar

GRB200 can detect phase and earth faults on the protectphase segregated current differential schemecan be input from feeders, sections and busbetween internal and external faults even in the event of CT saturation.

er failure protection, end zone protection and blind zone protection are

and earth fault protection

substation automation system or to a remote control centre,

200 Series is Toshiba’s next generation of protection and control IED’s, designed transmission/distribution networks and providing a platform for distributed and renewable energy systems and railway applications. Flexible adaptation is enabled using extensive

mbinations facilitating an application ori

Extensive hardware and modular software combinations provide the flexibility to meet your

Future upgrade paths and minor modifications are readily achievable on demand.

200 has been designed to meet the challenges and take unications technology.

low impedance differential relay for busbar protection is implemented on Toshiba’s 200 series IED platform and has been designed to provide

various types of busbar systemwith the flexibility to meet your application and engineering

performance, high quality and operational

GRB200 can be applied for various busbar systems. busbar

Double busbars with/without transfer busbar Ring busbars with/without transfer busbar

GRB200 can detect phase and earth faults on the protectphase segregated current differential scheme. A maximum can be input from feeders, sections and bus-couplers, which can between internal and external faults even in the event of CT saturation.

er failure protection, end zone protection and blind zone protection are

protections are provided as option

substation automation system or to a remote control centre,

200 Series is Toshiba’s next generation of protection and control IED’s, designed transmission/distribution networks and providing a platform for distributed and renewable energy systems and railway applications. Flexible adaptation is enabled using extensive

plication oriented

Extensive hardware and modular software combinations provide the flexibility to meet your

Future upgrade paths and minor modifications are readily achievable on demand.

200 has been designed to meet the challenges and take unications technology.

protection is implemented on Toshiba’s een designed to provide

sbar system. This powerful and with the flexibility to meet your application and engineering

performance, high quality and operational

GRB200 can detect phase and earth faults on the protected busbar by employingmaximum of 32 threeplers, which can correctly

between internal and external faults even in the event of CT saturation.er failure protection, end zone protection and blind zone protection are

provided as option

substation automation system or to a remote control centre,

200 Series is Toshiba’s next generation of protection and control IED’s, designed transmission/distribution networks and providing a platform for distributed and renewable energy systems and railway applications. Flexible adaptation is enabled using extensive

ented solution.

Extensive hardware and modular software combinations provide the flexibility to meet your

Future upgrade paths and minor modifications are readily achievable on demand.

200 has been designed to meet the challenges and take

protection is implemented on Toshiba’s een designed to provide very reliable,

This powerful and with the flexibility to meet your application and engineering

performance, high quality and operational

busbar by employingthree-phase currents correctly distinguish

between internal and external faults even in the event of CT saturation. er failure protection, end zone protection and blind zone protection are

provided as options in each bay

substation automation system or to a remote control centre,

200 Series is Toshiba’s next generation of protection and control IED’s, designed for transmission/distribution networks and providing a platform for distributed and renewable energy systems and railway applications. Flexible adaptation is enabled using extensive

Extensive hardware and modular software combinations provide the flexibility to meet your

200 has been designed to meet the challenges and take

protection is implemented on Toshiba’s very reliable,

This powerful and with the flexibility to meet your application and engineering

performance, high quality and operational

busbar by employing a phase currents

distinguish

er failure protection, end zone protection and blind zone protection are

bay.

substation automation system or to a remote control centre, IEC

Page 3: Busbar Protection IED - Toshiba€¦ ·  · 2017-11-21Programmable control, trip and alarm logic with PLC tool software Graphical LCD and 7 configurable function keys USB port for

FEATURES• Application- GRB200 can be applied for various

busbar systems.

- GRB200 incorporates a single central unit (CU) and bay units (BU). performs current differential protection. Thanalogue data from each CT which is converted to digital data for transmission to the CU via optical fiber for the differential protection. The BU also receives the trip command from the CU and performs tripping of the cibreaker. The CU can be provided with an optional voltage check element.

- Centralized or Decentralized installation is

A system installation in Figure 1.

EATURESApplication

GRB200 can be applied for various busbar systems.- Single busbars with/without transfer

busbar - Double busbars with/without

transfer busbar- Ring busbars

busbar - One and a half busbar- Four busGRB200 incorporates a single central unit (CU) and bay units (BU). performs current differential protection. The BU is a terminal used to acquire analogue data from each CT which is converted to digital data for transmission to the CU via optical fiber for the differential protection. The BU also receives the trip command from the CU and performs tripping of the cibreaker. The CU can be provided with an optional voltage check element.

Centralized or Decentralized installation is available.

A system installation in Figure 1.

GRB200 can be applied for various busbar systems.

Single busbars with/without transfer

Double busbars with/without transfer busbar Ring busbars with/without transfer

One and a half busbarFour bus-coupler busbar

GRB200 incorporates a single central unit (CU) and bay units (BU). performs current differential protection.

e BU is a terminal used to acquire analogue data from each CT which is converted to digital data for transmission to the CU via optical fiber for the differential protection. The BU also receives the trip command from the CU and performs tripping of the cibreaker. The CU can be provided with an optional voltage check element.

Centralized or Decentralized installation

A system installation example

Figure

GRB200 can be applied for various

Single busbars with/without transfer

Double busbars with/without

with/without transfer

One and a half busbar coupler busbar

GRB200 incorporates a single central unit (CU) and bay units (BU). The CU performs current differential protection.

e BU is a terminal used to acquire analogue data from each CT which is converted to digital data for transmission to the CU via optical fiber for the differential protection. The BU also receives the trip command from the CU and performs tripping of the circuit breaker. The CU can be provided with an optional voltage check element.

Centralized or Decentralized installation

example is shown

Figure 1 System

3

Single busbars with/without transfer

with/without transfer

GRB200 incorporates a single central The CU

performs current differential protection. e BU is a terminal used to acquire

analogue data from each CT which is converted to digital data for transmission to the CU via optical fiber for the differential protection. The BU also receives the trip command from the CU

rcuit breaker. The CU can be provided with an

Centralized or Decentralized installation

is shown

• Functionality- - - -

• Communication-

- • Security-

• Flexibility-

- -

- -

• Human Machine Interface- - - -

- -

System Installation Example

Functionality Eight settings group Automatic supervision Metering and recording functions Time synchronization by external clock

such as IRIGCommunication System interface

100BASE-TX, Protocol - IECSecurity Password protectionFlexibility Various models and

flexible application depending on system requirement and controlled object

Combined 1A / 5A current inputs Multi range DC power supply: 110 to

250V Configurable binary inputs and outputs Programmable control, trip and alarm

logic with PLC tool softwareHuman Machine Interface Graphical LCD and 7 configurable function keys USB port for local PC co Direct control buttons for open/close (O/I)

and control authority (43R/L) Help key for supporting operation Monitoring terminals for testin

Electrical

GRB

Installation Example

Eight settings groups Automatic supervision Metering and recording functionsTime synchronization by external clock

as IRIG-B and system networkCommunication

System interface - Fiber optic, TX,-FX IEC 61850

Password protection

Various models and hardware options for flexible application depending on system requirement and controlled objectCombined 1A / 5A current inputsMulti range DC power supply: 110 to

Configurable binary inputs and outputsProgrammable control, trip and alarm

with PLC tool softwareHuman Machine Interface

Graphical LCD and 24 LEDsonfigurable function keys

port for local PC coirect control buttons for open/close (O/I)

and control authority (43R/L)Help key for supporting operation

onitoring terminals for testin

CU

BU

Electrical cables

GRB200

Installation Example

Metering and recording functions Time synchronization by external clock

system network

Fiber optic,

hardware options for flexible application depending on system requirement and controlled object Combined 1A / 5A current inputs Multi range DC power supply: 110 to

Configurable binary inputs and outputsProgrammable control, trip and alarm

with PLC tool software Human Machine Interface

24 LEDs onfigurable function keys

port for local PC connection irect control buttons for open/close (O/I)

and control authority (43R/L) Help key for supporting operation

onitoring terminals for testing

BU

Optical

Time synchronization by external clock system network

hardware options for flexible application depending on system

Multi range DC power supply: 110 to

Configurable binary inputs and outputs Programmable control, trip and alarm

irect control buttons for open/close (O/I)

Page 4: Busbar Protection IED - Toshiba€¦ ·  · 2017-11-21Programmable control, trip and alarm logic with PLC tool software Graphical LCD and 7 configurable function keys USB port for

FUNCTIONS• Protection

-

-

-

-

-

-

-

-

-

-

• Monitoring- CT failure detection- Status and

primary apparatus- Switchgear operation monitoring- Plausibility check- Measu- Measurement and

individual and total harmonic

UNCTIONSProtection

Low impedance differential protection for up to 4 check zone

Percentage restrained characteristic ensures stability against external faults

Countermeasure for CT saturation

Available for busbar with different CT ratio

Dynamic busbar replica

BU out of service

Circuit breaker failure protection

End zone protection and blind zone protection Backup Overcurrent protection Independent voltage check element (option)

• Monitoring CT failure detectionStatus and condition monitoring of primary apparatusSwitchgear operation monitoringPlausibility checkMeasurement of I, V(option) and fMeasurement and individual and total harmonic

Low impedance differential protection discriminating zone

check zone

Percentage restrained characteristic ensures stability against external faults

Countermeasure for CT saturation

Available for busbar with different CT

busbar replica

BU out of service

Circuit breaker failure protection

End zone protection and blind zone

Overcurrent and Earth fault

Independent voltage check element

CT failure detection (Option)condition monitoring of

primary apparatus Switchgear operation monitoringPlausibility check

rement of I, V(option) and fMeasurement and supervisionindividual and total harmonic

Low impedance differential protection discriminating zones and

Percentage restrained characteristic ensures stability against external faults

Countermeasure for CT saturation

Available for busbar with different CT

busbar replica

Circuit breaker failure protection

End zone protection and blind zone

and Earth fault

Independent voltage check element

(Option) condition monitoring of

Switchgear operation monitoring

rement of I, V(option) and f supervision of

individual and total harmonic content up

4

Low impedance differential protection and

Percentage restrained characteristic ensures stability against external faults

Available for busbar with different CT

End zone protection and blind zone

and Earth fault

Independent voltage check element

up

- • HMI function- -

-

• Recording- - -

• Communication-

• General function- - - -

-

-

-

to 15th, sag, swell, interruption Current and voltageHMI function Standard LCD 24 configurable tri

red/green/yellow 7 Programmable function keys for user

configurableRecording Fault record Event record Disturbance recordCommunication IEC 61850 General function Eight settings group Automatic supervision Metering and recording functions Time synchronization by external clock

using IRIG- Password protection for setting

selection of Checking internal

signal. Checking internal circuit

jacks.

to 15th, sag, swell, interruptionand voltage circuit supervision

Standard LCD 24 configurable tri-state LEDs selectable red/green/yellow 7 Programmable function keys for user configurable operation

Fault record Event record Disturbance record

Communication

General function s Eight settings groups Automatic supervision Metering and recording functionsTime synchronization by external clock

-B or system networkPassword protection for settingselection of local / remote

internal circuit

internal circuit

to 15th, sag, swell, interruption circuit supervision

state LEDs selectable

7 Programmable function keys for user

Metering and recording functions Time synchronization by external clock

system network Password protection for settings and

/ remote control circuit by forcible

internal circuit using monitoring

circuit supervision

state LEDs selectable

7 Programmable function keys for user

Time synchronization by external clock

and

using monitoring

Page 5: Busbar Protection IED - Toshiba€¦ ·  · 2017-11-21Programmable control, trip and alarm logic with PLC tool software Graphical LCD and 7 configurable function keys USB port for

5

APPLICATIONS

PROTECTION

� Busbar Differential Protection

GRB200 applies current differential protection for each individual busbar zone, which are sectioned by the bus section and buscoupler switches (discriminating zone protection), as well as for the overall busbar system (check zone protection)

The discriminating zone protection, inputs current and disconnector position signals from feeders, transformer banks, busbar sections and buscouplers which are connected to the protected zone, and outputs trip signals to all the circuit breakers of the zone. The zone covered by the discriminating zone protection depends on the busbar configuration and varies with open/close status of the disconnectors. GRB200 introduces a replica setting which identifies which circuit is connected to which zone and follows changes in busbar operation. Up to four zone protections are available by employing relevant input currents and disconnector signals.

The check zone protection inputs currents from all feeder bays and transformer banks and performs overall differential protection for the entire busbar system and outputs trip signals to all the circuit breakers. As the protection does not use the disconnector position signals, the check zone protection is very secure against such false operation in the no-fault and through fault conditions.

By using these two protections, GRB200 ensures a very reliable protection for various types of busbar system.

Figure 2 shows a typical application to a double busbar system. DIFCH is the check zone protection which covers all busbars. DIFZA and DIFZB are the discriminating zone protections for busbars A and B respectively. The voltage elements UVSFA, UVSFB, UVGFA, UVGFB, OVGFA and OVGFB can be provided for each busbar as the voltage check function (optional).

Figure 3 shows the scheme logic with check zone protection, discriminating zone protections and voltage check function for a double busbar system.

Figure 2 Typical Application to Double Busbar System

Page 6: Busbar Protection IED - Toshiba€¦ ·  · 2017-11-21Programmable control, trip and alarm logic with PLC tool software Graphical LCD and 7 configurable function keys USB port for

6

Figure 3 Scheme Logic with Check Zone, Discriminating Zone and Voltage Check

DS-nA : Disconnector condition - busbar A side DS-nB : Disconnector condition - busbar B side DS-BS** : Disconnector condition - bus section

DIFCH

[Current]

UVSFA

UVGFA

[Voltage Check]

CU

DIFZB

DIFZA &

DS-1A

DS-1B

≧1

DS-nA

DS-nB &

DS-1A

DS-1B

Trip(1)

BU (Feeder 1)

DS-BC1

Trip(BS1)

BU (Bus section CT1)

DS-nA

DS-nB

Trip(n)

BU (Feeder n)

DS-BC2

Trip(BS2)

BU (Bus section CT2)

≧1

≧1

≧1

≧1

≧1

OVGFA

UVSFB

UVGFB ≧1

OVGFB

Figure 5 Waveform for CT saturation

Figure 4 Characteristic of Current Differential Element

� Discriminating zone and check zone elements

The check zone element (DIFCH) and discriminating zone elements (DIFZA - DIFZD) are based on the current differential principle and have a differential characteristic for the small current region, and a percentage restraint characteristic for the large current region to cope with erroneous differential current caused by a through-fault current.

The characteristics are shown in Figure 4, and each zone (DIFCH, DIFZA - DIFZD) and each phase (A, B, C phase) have these characteristics respectively.

The minimum operating current (Idk) and the percent slope (k) of the restraint characteristic in the large current region are user-programmable.

CT saturation under external fault conditions can be a serious problem for busbar protection. GRB200 overcomes the CT saturation problem by using a “CT saturation detection” function. When an external fault occurs, a very large erroneous current may be caused by CT saturation. However, once the CT saturates, there is a short period of several milliseconds of non-saturation between the saturation periods in a cycle. By detecting this non-saturation period, the current differential element can be blocked to prevent false operation arising from CT saturation.

Idk

Id=Ir

Operate

Ir

Id

Id=k×Ir

Restraining current

Diff

eren

tial

curr

ent

Incoming terminal current

Outgoing terminal current (Saturation)

Differential current

Non-saturation period

Page 7: Busbar Protection IED - Toshiba€¦ ·  · 2017-11-21Programmable control, trip and alarm logic with PLC tool software Graphical LCD and 7 configurable function keys USB port for

7

� Breaker Failure Protection Phase-segregated breaker failure protection is provided for each bay and can be initiated by either an internal or external signal.

When an overcurrent element remains in operation after a tripping signal has been issued the breaker is judged to have failed and a 2 stage CBF sequence is initiated. The first stage issues a re-trip command to the circuit breaker. If this also fails then the command to backtrip adjacent circuit breakers is executed. The overcurrent element has a high-speed reset time.

GRB200 has two kinds of timer for Breaker Failure Protection. One timer is used for re-trip, the other timer is used for CBF trip.

A remote transfer trip is provided for feeder circuits.

� End zone and Blind Zone Protection This function is provided to cater for circumstances when a dead zone or blind zone is created between the CB and the associated CT.

End zone protection detects a fault located between the CB and the associated CT when the CB is open. Depending on the location of the CT, either the busbar section CB is tripped or an intertrip is sent to the CB at the remote end of the line.

Blind zone protection is used to detect and trip for faults located between the bus-section CB and the associated CT for the arrangement when the CT is installed on one side of the CB only.

� BU out-of-Service Function GRB200 provides a BU out-of-service function for maintenance purposes. When a particular BU is set to out-of-service condition, it is excluded from the operation of the protection scheme.

� Voltage Check Function (Option) GRB200 can enhance security against false tripping due to a failure in a CT or CT secondary circuits by the provision of a voltage check element in the form of a check relay with circuits that are independent from other circuits:

The voltage check function incorporates the following elements.

- Undervoltage element for earth fault detection - Undervoltage element for phase fault detection

- Zero-phase overvoltage element for earth fault detection

� Backup Overcurrent and Earth Fault Protection

Backup overcurrent and earth fault protection are provided in each bay. Each provides two stage overcurrent and earth fault protection respectively, and can be set to either a definite time or an inverse time characteristic.

The inverse time overcurrent elements are available in conformity with the IEC 60255-151 standard which encompasses both the IEC and IEEE/ANSI standard characteristics. Alternatively, a user-configurable curve may be created.

The definite time overcurrent protection is enabled by the instantaneous overcurrent element and pickup-delay timer.

Page 8: Busbar Protection IED - Toshiba€¦ ·  · 2017-11-21Programmable control, trip and alarm logic with PLC tool software Graphical LCD and 7 configurable function keys USB port for

8

HMI FUNCTION

■ Front Panel

GRB200 provides the Standard LCD.

The standard LCD panel incorporates the user

interfaces listed below. Setting the relay and viewing

stored data are possible using the Liquid Crystal

Display (LCD) and operation keys. - 21 character, 8 line LCD with back light

The local human machine interface is simple and easy

to understand with the following facilities and

indications. - Status indication LEDs (IN SERVICE, ERROR

and 24 configurable LEDs) - 7 Function keys for control, monitoring, setting

group change and screen jump functions of which operation is configurable by the user

- Test terminals which can monitor three different signals from the front panel without connection to the rear terminals.

- USB port

■ Local PC connection

The user can communicate with GRB200 from a local

PC via the USB port on the front panel. Using GR-200

series engineering tool software (called GR-TIEMS),

the user can view, change settings and monitor

real-time measurements.

MONITORING

■ Metering

The following power system data is measured

continuously and can be displayed on the LCD on the

relay fascia, and on a local or remotely connected PC. - Measured analog currents, voltages (option) and

frequency.

The accuracy of analog measurement is ±0.5% for I, V

at rated input and ±0.03Hz for frequency

measurement.

■ Status Monitoring

The open or closed status of each switchgear device

and failure information concerning power apparatus

and control equipment are monitored by GRB200.

Both normally open and normally closed contacts are

used to monitor the switchgear status. If an unusual

status is detected, a switchgear abnormality alarm is

generated.

Page 9: Busbar Protection IED - Toshiba€¦ ·  · 2017-11-21Programmable control, trip and alarm logic with PLC tool software Graphical LCD and 7 configurable function keys USB port for

9

RECORDING

■ Event Record

Continuous event-logging is useful for monitoring of

the system from an overview perspective and is a

complement to specific disturbance recorder functions.

Up to 1,024 time-tagged events are stored with 1ms

resolution.

■ Fault records

Information about the pre-fault and fault values for

currents and voltages are recorded and displayed for

trip event confirmation. The most recent 8 time-tagged

faults with 1ms resolution are stored. Fault record

items are as follows. - Date and time - Faulted phase - Phases tripped - Tripping mode - Pre-fault and post-fault current and voltage data

(phase, symmetrical components)

■ Disturbance records

The Disturbance Recorder function supplies fast,

complete and reliable information for disturbances in

the power system. It facilitates understanding of

system behavior and performance of related primary

and secondary equipment during and after a

disturbance.

The Disturbance Recorder acquires sampled data

from all selected analogue inputs and binary signals.

The data is stored in COMTRADE format.

COMMUNICATION

■ Station bus

Ethernet port(s) for the substation communication

standards IEC 61850 is provided for the station bus.

■ Serial communication

GRB200 can function as a protocol converter to

connect to a Substation Automation System.

GENERAL FUNCTION

■ Self supervision

Automatic self-supervision of internal circuits and

software is provided. In the event of a failure being

detected, the ALARM LED on the front panel is

illuminated, the ‘UNIT FAILURE’ binary output

operates, and the date and time of the failure is

recorded in the event record.

■ Time synchronization

Current time can be provided with time

synchronization via the station bus by SNTP (Simple

Network Time Protocol) with the IEC 61850 protocol.

■ Setting groups

8 settings groups are provided, allowing the user to

set one group for normal conditions, while the other

groups may be set to cover alternative operating

conditions.

■ Password protection

Password protection is available for the execution of

setting changes, clearing records and switching

between local/remote controls.

■ Simulation and test

GRB200 provides simulation and test functions to

check control functions without modification to wiring

provided by a dummy circuit breaker (virtual

equipment), and the capability to test communication

signals by forced signal status change.

The simulation and test functions can work in the Test

mode only.

Page 10: Busbar Protection IED - Toshiba€¦ ·  · 2017-11-21Programmable control, trip and alarm logic with PLC tool software Graphical LCD and 7 configurable function keys USB port for

TOOLThe PC interface

GRB

a local

stored data,

screen, to configure sequential logics and

purposes.

The engineering t

settings and to view and analyze fault and d

records stored in GRB

disturbance record

measure

version of the engineering to

and powerful analysis tool

support functions.

TOOLS & ACCESSORYThe PC interface

GRB200 and other Toshiba GR

a local personal

stored data,

screen, to configure sequential logics and

purposes.

■ Remote Setting And Monitoring

The engineering t

settings and to view and analyze fault and d

records stored in GRB

disturbance record

measured and analyzed in detail.

version of the engineering to

and powerful analysis tool

support functions.

Figure

& ACCESSORYThe PC interface GR-TIEMS allows users to access

200 and other Toshiba GR

personal computer (PC) to view on

to change settings, to edit

screen, to configure sequential logics and

Remote Setting And Monitoring

The engineering tool supports functions to change

settings and to view and analyze fault and d

records stored in GRB200. Waveform data in the

disturbance records can be displayed, edited,

and analyzed in detail.

version of the engineering to

and powerful analysis tool

support functions.

Figure 7 PC Display of

& ACCESSORY TIEMS allows users to access

200 and other Toshiba GR-200 series IEDs from

computer (PC) to view on

change settings, to edit

screen, to configure sequential logics and

Remote Setting And Monitoring

ool supports functions to change

settings and to view and analyze fault and d

200. Waveform data in the

can be displayed, edited,

and analyzed in detail.

version of the engineering tool can provide additional

and powerful analysis tools and setting calculation

PC Display of GR-

TIEMS allows users to access

200 series IEDs from

computer (PC) to view on-line or

change settings, to edit the LCD

screen, to configure sequential logics and for other

Remote Setting And Monitoring

ool supports functions to change

settings and to view and analyze fault and disturbance

200. Waveform data in the

can be displayed, edited,

and analyzed in detail. The advanced

ol can provide additional

and setting calculation

-TIEMS

10

TIEMS allows users to access

200 series IEDs from

line or

LCD

other

ool supports functions to change

isturbance

200. Waveform data in the

can be displayed, edited,

dvanced

ol can provide additional

and setting calculation

The

configure

operation.

and LEDs are

logic editor.

Programmable Logic Editor

The programmable

configure flexible

operation. Configurable binary inputs, binary outputs

and LEDs are also

logic editor. This complies

Figure

Programmable Logic Editor

programmable logic capability allows

flexible logic for customized

Configurable binary inputs, binary outputs

also programmed by

This complies with IEC

igure 9 PC display of PLC editor

Programmable Logic Editor

logic capability allows

customized application and

Configurable binary inputs, binary outputs

programmed by the programmable

with IEC 61131

PC display of PLC editor

logic capability allows the user

application and

Configurable binary inputs, binary outputs

programmable

61131-3 standard.

PC display of PLC editor

to

application and

Configurable binary inputs, binary outputs

programmable

3 standard.

Page 11: Busbar Protection IED - Toshiba€¦ ·  · 2017-11-21Programmable control, trip and alarm logic with PLC tool software Graphical LCD and 7 configurable function keys USB port for

11

TECHNICAL DATA

HARDWARE

Analog Inputs

Rated current In 1A / 5A (selectable by user)

Rated voltage Vn 100V to 120V

Rated Frequency 50Hz / 60Hz

Overload Rating

Current inputs 4 times rated current continuous 5 times rated current for 3 mins

6 times rated current for 2 mins

30 times rated current for 10 sec 100 times rated current for 1 second 250 times rated current for one power cycle (20 or 16.6ms)

Voltage inputs 2 times rated voltage continuous 2.5 times rated voltage for 1 second

Burden

Phase current inputs ≤ 0.1VA at In = 1A, ≤ 0.2VA at In = 5°

Earth current inputs ≤ 0.3VA at In = 1A, ≤ 0.4VA at In = 5A

Sensitive earth fault inputs ≤ 0.3VA at In = 1A, ≤ 0.4VA at In = 5A

Voltage inputs ≤ 0.1VA at Vn

Power Supply

Rated auxiliary voltage 110/250Vdc or 100/220Vac (Operative range: 88 – 300Vdc or 80 – 230Vac)

Superimposed AC ripple on DC supply ≤ 15%

Supply interruption ≤ 20ms at 110Vdc

Restart time < 5ms

Power consumption ≤ 15W (quiescent) ≤ 25W (maximum)

Binary Inputs

Input circuit DC voltage 110/125/220/250Vdc (Operating range: 88 – 300Vdc)

Capacitive discharge immunity 10µF charged to maximum supply voltage and discharged into the input terminals, according to ENA TS 48-4 with an external resistor

Maximum permitted voltage 300Vdc for 110/250Vdc rating

Power consumption ≤ 0.5W per input at 220Vdc

Binary Outputs

Fast operating contacts Make and carry

Break Operate time

5A continuously

30A, 290Vdc for 0.2s (L/R=5ms)

0.15A, 290Vdc (L/R=40ms) Typical 3 ms

Semi-fast operating contacts Make and carry Break Operate time

8A continuously 30A, 240Vdc for 1s (L/R=5ms) 0.1A, 250Vdc (L/R=40ms) 0.2A, 110Vdc (L/R=40ms) Typical 6 ms

Auxiliary contacts Make and carry

Break

8A continuously

30A, 240Vdc for 1s (L/R=5ms)

0.1A, 250Vdc (L/R=40ms) 0.2A, 110Vdc (L/R=40ms)

Page 12: Busbar Protection IED - Toshiba€¦ ·  · 2017-11-21Programmable control, trip and alarm logic with PLC tool software Graphical LCD and 7 configurable function keys USB port for

12

Operate time Typical 8 ms

Hybrid contacts (10 A breaking) Make and carry

Break

Operate time

8A continuously

10A, 220Vdc for 0.5s (L/R=5ms) 10A, 220Vdc (L/R=20ms)

10A, 110Vdc (L/R=40ms)

1 ms

Durability ≥ 10,000 operations (loaded contact) ≥ 100,000 operations (unloaded contact)

Measuring input capability

Full scale Standard current input

Voltage input

Sampling rate Frequency response

≥ 60A (1A rating) or 300A (5A rating)

≥ 200V

48 samples / cycle < 5% deviation over range 16.7Hz to 600Hz

Mechanical Design

Installation Flush mounting

Weight Approx. 10kg (1/3 size), 12kg (1/2 size), 25kg (1/1 size)

Case colour 2.5Y7.5/1 (approximation to Munsell value)

LED

Number 26 (Fixed for “In service” and “ERROR”)

Colour Red / Yellow / Green (configurable) except “In service” (green) and “Error” (red)

Function keys

Number 7

Local Interface

USB Type B

Maximum cable length 2m (max.)

System Interface (rear port)

100BASE-TX Fast Ethernet

Physical medium Twisted pair cable, RJ-45 connector

100BASE-FX Fast Ethernet

Physical medium Protocol

50/125 or 62.5/125µm fibre, SC connector IEC61850

CU to BU communication

Type: Connector:

Cable:

GI optical fibre ST connector

Graded-index multi-mode 50/125µs or 62.5/125µs

Terminal Block

CT/VT input M3.5 Ring terminal (ring lug type terminal only)

Binary input, Binary output M3.5 terminal with 15mm stripping length (for compression type terminal)

Page 13: Busbar Protection IED - Toshiba€¦ ·  · 2017-11-21Programmable control, trip and alarm logic with PLC tool software Graphical LCD and 7 configurable function keys USB port for

13

Compression type terminal

Page 14: Busbar Protection IED - Toshiba€¦ ·  · 2017-11-21Programmable control, trip and alarm logic with PLC tool software Graphical LCD and 7 configurable function keys USB port for

14

FUNCTIONAL DATA

Current Differential Protection (87B)

Minimum operating current (DIFCH, DIFZ):

% slope (SLPCH, SLPZ):

Primary rating of CT:

500 to 3000A in 1A steps (CT primary amps)

0.30 to 0.90 in 0.1 steps

100 to 10000A in 1A steps

Circuit Breaker Failure Protection (50BF)

Overcurrent element (OCB):

BF timer for retrip of failed breaker:

BF timer for related breaker trip:

Operating time of overcurrent element

Resetting time of overcurrent element

Accuracy of overcurrent element:

DO/PU ratio:

0.1 to 2.0 times of current rating in 0.1 steps

0 to 500ms in 1ms steps

50 to 500ms in 1ms steps

less than 20ms at 50Hz or less than 17ms at 60Hz

less than 15ms at 50Hz or less than 13ms at 60Hz

±5% (±10% at I < 0.5×In)

0.8

Voltage Check Function

Undervoltage element (UVGF):

Undervoltage element (UVSF):

Zero-phase overvoltage element (OVGF):

Undervoltage change detection element (UVDF)

20 to 60V in 1V steps

60 to 100V in 1V steps

0.1 to 10.0V in 0.1V steps

0.07 times voltage before fault

Phase Overcurrent Protection (50, 51)

Definite time overcurrent element

Pick up level (OC)

Delay time (TOC)

Operating time

0.02 to 50.00pu in 0.01pu steps

0.00 to 10.00s in 0.01s steps

typical 30ms (without delay time)

Inverse time overcurrent element

Pick up level (OCI)

Time multiplier (TOCI)

Characteristic

Reset type

Reset Definite delay

0.02 to 5.00pu in 0.01pu steps

0.010 to 50.00 in 0.01 steps

IEC-NI / IEC-VI / IEC-EI / UK-LTI / IEEE-MI / IEEE-VI / IEEE-EI /

US-CO2 / US-CO8 / Original

Definite Time or Dependent Time

0.0 to 300.0s in 0.1s steps

Reset Time Multiplier Setting RTMS 0.010 to 50.000 in 0.001 steps

Earth Fault Protection (50N, 51N)

Definite time overcurrent element

Pick up level (EF)

Delay time (TEF)

Operating time

Inverse time overcurrent element

Pick up level (EFI)

Time multiplier (TEFI)

Characteristic

Reset type

Reset Definite delay

Reset Time Multiplier Setting RTMS

0.02 to 50.00pu in 0.01pu steps

0.00 to 10.00s in 0.01s steps

typical 30ms (without delay time)

0.02 to 5.00pu in 0.01pu steps

0.010 to 50.00 in 0.01 steps

IEC-NI / IEC-VI / IEC-EI / UK-LTI / IEEE-MI / IEEE-VI / IEEE-EI /

US-CO2 / US-CO8 / Original

Definite Time or Dependent Time

0.0 to 300.0s in 0.1s steps

0.010 to 50.000 in 0.001 steps

Metering Function

Current

Voltage

Accuracy ± 0.5% (at rating)

Accuracy ± 0.5% (at rating)

Page 15: Busbar Protection IED - Toshiba€¦ ·  · 2017-11-21Programmable control, trip and alarm logic with PLC tool software Graphical LCD and 7 configurable function keys USB port for

15

Frequency Accuracy ± 0.03Hz

Time Synchronisation

Protocol SNTP

Page 16: Busbar Protection IED - Toshiba€¦ ·  · 2017-11-21Programmable control, trip and alarm logic with PLC tool software Graphical LCD and 7 configurable function keys USB port for

16

ENVIRONMENTAL PERFORMANCE

Atmospheric Environment

Temperature IEC 60068-2-1/2

IEC 60068-2-14

Operating range: -10°C to +55°C.

Storage / Transit: -25°C to +70°C.

Cyclic temperature test as per IEC 60068-2-14

Humidity IEC 60068-2-30

IEC 60068-2-78

56 days at 40°C and 93% relative humidity.

Cyclic temperature with humidity test as per IEC 60068-2-30

Enclosure Protection IEC 60529 IP52 - Dust and Dripping Water Proof IP20 for rear panel

Mechanical Environment

Vibration IEC 60255-21-1 Response - Class 1

Endurance - Class 1

Shock and Bump IEC 60255-21-2 Shock Response Class 1 Shock Withstand Class 1

Bump Class 1

Seismic IEC 60255-21-3 Class 1

Electrical Environment

Dielectric Withstand IEC 60255-5 2kVrms for 1 minute between all terminals and earth. 2kVrms for 1 minute between independent circuits. 1kVrms for 1 minute across normally open contacts.

High Voltage Impulse IEC 60255-5 IEEE C37.90

Three positive and three negative impulses

of 5kV(peak), 1.2/50µs, 0.5J between all

terminals and between all terminals and

earth.

Voltage Dips, Interruptions, Variations and Ripple on DC supply

IEC 60255-11,

IEC 61000-4-29, IEC 61000-4-17

IEC 60255-26 Ed 3

1. Voltage dips:

0 % residual voltage for 20 ms 40 % residual voltage for 200 ms

70 % residual voltage for 500 ms

2. Voltage interruptions: 0 % residual voltage for 5 s

3. Ripple:

15 % of rated d.c. value, 100 / 120 Hz 4. Gradual shut-down / start-up:

60 s shut-down ramp, 5 min power off, 60s start-up ramp

5. Reversal of d.c. power supply polarity: 1 min

Capacitive Discharge ENA TS 48-4 10µF charged to maximum supply voltage and discharged into the input terminals with an external resistance

Page 17: Busbar Protection IED - Toshiba€¦ ·  · 2017-11-21Programmable control, trip and alarm logic with PLC tool software Graphical LCD and 7 configurable function keys USB port for

17

Electromagnetic Environment

High Frequency Disturbance /

Damped Oscillatory Wave

IEC 60255-22-1 Class 3,

IEC 61000-4-18 IEC 60255-26 Ed 3

1 MHz burst in common / differential modes

Auxiliary supply and I/O ports: 2.5 kV / 1 kV Communications ports: 1 kV / 0 kV

Electrostatic Discharge IEC 60255-22-2 Class 4, IEC 61000-4-2

IEEE C37.90.3-2001 IEC 60255-26 Ed 3

Contact: 2, 4, 6, 8kV Air: 2, 4, 8, 15kV

Radiated RF Electromagnetic Disturbance

IEC 60255-22-3, IEC 61000-4-3 Level 3 IEC 60255-26 Ed 3

Sweep test ranges: 80 MHz to 1 GHz and 1.4 GHz to 2.7 GHz.

Spot tests at 80, 160, 380, 450, 900, 1850 and 2150 MHz.

Field strength: 10 V/m

Radiated RF

Electromagnetic

Disturbance

IEEE C37.90.2-1995 Field strength 35V/m for frequency sweep of

25MHz to 1GHz.

Fast Transient

Disturbance

IEC 60255-22-4

IEC 61000-4-4

IEC 60255-26 Ed 3

5 kHz, 5/50ns disturbance

Auxiliary supply and input / output ports: 4 kV

Communications ports: 2 kV

Surge Immunity IEC 60255-22-5

IEC 61000-4-5

IEC 60255-26 Ed 3

1.2/50µms surge in common/differential

modes:

Auxiliary supply and input / output ports: 4, 2,

1, 0.5 kV / 1, 0.5 kV

Communications ports: up to 1, 0.5 kV / 0 kV

Surge Withstand IEEE C37.90.1-2002 3kV, 1MHz damped oscillatory wave

4kV, 5/50ns fast transient

Conducted RF

Electromagnetic

Disturbance

IEC 60255-22-6

IEC 61000-4-6

IEC 60255-26 Ed 3

Sweep test range: 150 kHz to 80MHz

Spot tests at 27 and 68 MHz.

Voltage level: 10 V r.m.s

Power Frequency

Disturbance

IEC 60255-22-7

IEC 61000-4-16

IEC 60255-26 Ed 3

50/60 Hz disturbance for 10 s in common /

differential modes

Binary input ports: 300 V / 150 V

Power Frequency

Magnetic Field

IEC 61000-4-8 Class 4

IEC 60255-26 Ed 3

Field applied at 50/60Hz with strengths of:

30A/m continuously,

300A/m for 1 second.

Conducted and

Radiated Emissions

IEC 60255-25

EN 55022 Class A,

EN 61000-6-4

IEC 60255-26 Ed 3

Conducted emissions:

0.15 to 0.50MHz: <79dB (peak) or <66dB

(mean)

0.50 to 30MHz: <73dB (peak) or <60dB

(mean)

Radiated emissions

30 to 230 MHz: < 40 dB(uV/m)

230 to 1000 MHz: < 47 dB(uV/m)

Measured at a distance of 10 m

Page 18: Busbar Protection IED - Toshiba€¦ ·  · 2017-11-21Programmable control, trip and alarm logic with PLC tool software Graphical LCD and 7 configurable function keys USB port for

18

Performance and Functional Standards

Category Standards

General

Common requirements IEC 60255-1

Data Exchange IEC 60255-24 / IEEE C37.111 (COMTRADE)

Product Safety IEC 60255-27

Functional

Under/Over Voltage Protection IEC 60255-127

Thermal Protection IEC 60255-149

Over/Under Current Protection IEC 60255-151

European Commission Directives

2004/108/EC

Compliance with the European Commission

Electromagnetic Compatibility Directive is

demonstrated according to generic EMC standards

EN 61000-6-2 and EN 61000-6-4, and product

standard IEC 60255-26.

2006/95/EC

Compliance with the European Commission Low

Voltage Directive for electrical safety is

demonstrated according EN 60255-27.

Page 19: Busbar Protection IED - Toshiba€¦ ·  · 2017-11-21Programmable control, trip and alarm logic with PLC tool software Graphical LCD and 7 configurable function keys USB port for

19

ORDERING INFORMATION

[Hardware selection] CU (Central Unit)

7 8 9 A B C D E F G H J K L

Configurations G R B 2 0 0 - - - C - - 1 - 0 0

Central Unit

Application of power system

Without Voltage input 0

With Voltage input 4ZONEs 1

AC Rating

50Hz 1

60Hz 2

DC Rating

110-250 Vdc or 100-220 Vac 1

Outline

Standard LCD, 1/1 x 19’’ rack for flush/rack mounting 4

BI/BO Module

Refer to Number of BI/BO Table BI/BO Terminal Type

Compression plug type terminal 0

Maximum Number of BU to Connect

8 CH 1

16 CH 2

24 CH 3

32 CH (Only for 50Hz) 4

Number of Serial and/or Ethernet Communication and/ or Time Synch Port(s)

1 port 1

1 port + IRIG-B 3

2 ports 4

2 ports + IRIG-B 6

3 ports 7

3 ports + IRIG-B (Note : Selectable when Communication for Protection is 0 or 1 CH.) 9

Selection of Serial and/or Ethernet Communication P ort(s)

100Base-TX x 1 port (When position E = 1 - 3 and B – D) 3

100Base-FX x 1 port (When position E = 1 - 3 and B – D) 4

100Base-TX x 2 ports (When position E = 4 - 6 and E – G) 5

100Base-FX x 2 ports (When position E = 4 - 6 and E – G) 6

Page 20: Busbar Protection IED - Toshiba€¦ ·  · 2017-11-21Programmable control, trip and alarm logic with PLC tool software Graphical LCD and 7 configurable function keys USB port for

20

7 8 9 A B C D E F G H J K L

Configurations G R B 2 0 0 - - - C - - 1 - 0 0

Function Block (linked with software selection)

See function table of software selection

Please contact with our sales staffs when you require user configurable models that are not indicated in the ordering sheet above.

Page 21: Busbar Protection IED - Toshiba€¦ ·  · 2017-11-21Programmable control, trip and alarm logic with PLC tool software Graphical LCD and 7 configurable function keys USB port for

21

[Hardware selection] BU (Bay Unit)

7 8 9 A B C D E F G H J K L

Configurations G R B 2 0 0 - - - B 0 - 4 E - 1 - 0

Bay Unit

Application of power system

(CTx4) for 1/3x 19’’ rack 1

(CTx4) for 1/2 x 19’’ rack 2

AC Rating

50Hz 1

60Hz 2

1A 1

5A 2

DC Rating

110-250 Vdc or 100-220 Vac 1

Outline

Standard LCD, 1/3 x 19’’ rack for flush mounting 1

Standard LCD, 1/2 x 19’’ rack for flush mounting 2

Standard LCD, 1/3 x 19’’ rack for rack mounting E

Standard LCD, 1/2 x 19’’ rack for rack mounting F

BI/BO Module

Refer to Number of BI/BO Table BI/BO Terminal Type

Compression plug type terminal 0

Function Block (linked with software selection)

See function table of software selection Please contact with our sales staffs when you require user configurable models that are not indicated in the ordering sheet above.

Page 22: Busbar Protection IED - Toshiba€¦ ·  · 2017-11-21Programmable control, trip and alarm logic with PLC tool software Graphical LCD and 7 configurable function keys USB port for

22

Number of BI/BO BI/BO 1 x I/O module - For BU(1/3x19” rack, 1/2x19” rack), CU(1/1x19”rack)

Number of BI/BO Ordering No.

(Position “A” to “B”)

Configuration

Inde

pend

ent

BI

Inde

pend

ent

BI (

varia

ble)

Com

mon

B

I

DC

-AI

Fas

t-B

O

Sem

i-fas

t BO

BO

Hyb

rid B

O

DC

-AO

7 - - - - 6 4 - - 11 1xBIO1 12 - - - - 3 2 - - 12 1xBIO2 8 - - - 6 - 2 - - 13 1xBIO3

18 - - - - - - - - 15 1xBI1 - - 32 - - - - - - 17 1xBI3

BI/BO 2 x I/O module - For BU(1/2x19” rack), CU(1/1 x19”rack)

Number of BI/BO Ordering No.

(Position “A” to “B”)

Configuration

Inde

pend

ent

BI

Inde

pend

ent

BI (

varia

ble)

Com

mon

B

I

DC

-AI

Fas

t-B

O

Sem

i-fas

t BO

BO

Hyb

rid B

O

DC

-AO

- - 32 - - 6 12 - - 21 1xBI3+1xBO1 7 - 32 - - 6 4 - - 22 1xBI3+1xBIO1

12 - 32 - - 3 2 - - 23 1xBI3+1xBIO2 18 - - - - 6 12 - - 24 1xBI1+1xBO1 25 - - - - 6 4 - - 25 1xBI1+1xBIO1 30 - - - - 3 2 - - 26 1xBI1+1xBIO2 8 - - - 6 6 14 - - 27 1xBO1+1xBIO3

15 - - - 6 6 6 - - 28 1xBIO1+1xBIO3 7 - - - - 12 16 - - 29 1xBO1+1xBIO1

16 12 4 2A 2xBIO3 - - 32 - - - - 16 - 2B 1xBI3+1xBO2 - 12 - - - 6 12 - - 2C 1xBI2 +1xBO1 - - 32 10 - - - - - 2D 1xBI3+1xDCAI2

Page 23: Busbar Protection IED - Toshiba€¦ ·  · 2017-11-21Programmable control, trip and alarm logic with PLC tool software Graphical LCD and 7 configurable function keys USB port for

23

BI/BO 3 x I/O module - For BU(1/2x19” rack)

Number of BI/BO Ordering No.

(Position “A” to “B”)

Configuration

Inde

pend

ent

BI

Inde

pend

ent

BI (

varia

ble)

Com

mon

B

I

DC

-AI

Fas

t-B

O

Sem

i-fas

t BO

BO

Hyb

rid B

O

DC

-AO

15 - - - 6 12 18 - - 31 1xBO1+1xBIO1+1xBIO3 20 - - - 6 9 16 - - 32 1xBO1+1xBIO2+1xBIO3 23 - - - 12 6 8 - - 33 1xBIO1+2xBIO3 26 - - - 6 6 14 - - 34 1xBI1+1xBO1+1xBIO3 8 - 32 - 6 6 14 - - 35 1xBI3+1xBO1+1xBIO3

24 - - - 18 - 6 - - 36 3xBIO3 25 - - - - 12 16 - - 37 1xBI1+1xBO1+1xBIO1 - - 32 10 - 6 12 - - 38 1xBI3+1xDCAI2+1xBO1

36 - - - - 6 12 - - 39 2xBI1+1xBO1 7 - 32 - - 6 4 16 - 3C 1xBI3+1xBIO1+1xBO2 7 - 32 - - 12 16 - - 3D 1xBI3+1xBO1+1xBIO1 - - 32 - - 6 12 16 - 3E 1xBI3+1xBO1+1xBO2

16 - - - 12 6 16 - - 3G 1xBO1+2xBIO3 26 - - - 6 6 14 - - 3J 1xBO1+1xBIO3+1xBI1 - - 62 - - 6 12 - - 3K 2xBI3+1xBO1

14 - 32 - - 12 8 - - 3L 1xBI3+2xBIO1 - - 96 - - - - - - 3M 3xBI3 8 12 - - 6 6 14 - - 3N 1xBI2+1xBO1+1xBIO3 - - 32 - - 12 24 - - 3P 1xBI3 + 2xBO1

36 - - - - - - 16 - 3Q 2xBI1 + 1xBO2 - - - 30 - - - - - 3R 3xDCAI2

Page 24: Busbar Protection IED - Toshiba€¦ ·  · 2017-11-21Programmable control, trip and alarm logic with PLC tool software Graphical LCD and 7 configurable function keys USB port for

24

[Software selection] CU (Central Unit)

1 2 3 4 5 6 7 S G T E F U 9 V

Configurations G R B 2 0 0 - 0 - - E

Application of power system

Assignment on position “7”

Function Block

Refer to Function Table

Communication for Remote / Time Synch. (1)

Assignment on position “E”

Communication for Remote / Time Synch. (2)

Assignment on position “F”

Protocol

IEC 61850 2

Outline

Assignment on position “9”

Language

English E

[Software selection] BU (Bay Unit)

1 2 3 4 5 6 7 S G T E F U 9 V

Configurations G R B 2 0 0 - 0 - 4 E 9 - E

Application of power system

Assignment on position “7”

Function Block

Refer to Function Table

Outline

Assignment on position “9”

Language

English E

Page 25: Busbar Protection IED - Toshiba€¦ ·  · 2017-11-21Programmable control, trip and alarm logic with PLC tool software Graphical LCD and 7 configurable function keys USB port for

25

[FUNCTION TABLE] CU (Central Unit)

[FUNCTION TABLE] BU (Bay Unit)

Function Block Protection function Ordering No. (Position “ G & T”)

11 12

DIF 87 Phase-segregated current differential protection ● ● CTF CT failure detection by Id ● -- Differential current monitoring ● ●

CBF 50BF Circuit breaker failure protection ● ● EFP -- End fault protection ● ● COMTP -- Command trip function ● ● FS FS Fail-safe function (Voltage check function) ●

Function Block Protection function Ordering No. (Position “ G & T”)

12 14

DIF 87 Phase-segregated current differential protection ● ● CTF CT failure detection by Id ● -- Differential current monitoring ● ●

CBF 50BF Circuit breaker failure protection ● ● EFP -- End fault protection ● ● COMTP -- Command trip function ● ●

OC 50 Non-directional definite time over-current protection

● ● 51 Non-directional inverse time over-current protection

EF 50N

Non-directional definite time earth fault over-current protection

● ● 51N Non-directional inverse time earth fault over-current

protection FS FS Fail-safe function (Voltage check function) ●

Page 26: Busbar Protection IED - Toshiba€¦ ·  · 2017-11-21Programmable control, trip and alarm logic with PLC tool software Graphical LCD and 7 configurable function keys USB port for

26

DIMENSION AND PANEL CUT-OUT (1/1 size)

(Panel cut-out)

Note: For a rack mount unit, there are holes for joint kits assembling on top and bottom of the unit.

Figure 10 – Dimension and Panel Cut-out – 1/1 x 19” case size (Central Unit)

(when compression plug type terminals are applied)

Page 27: Busbar Protection IED - Toshiba€¦ ·  · 2017-11-21Programmable control, trip and alarm logic with PLC tool software Graphical LCD and 7 configurable function keys USB port for

27

DIMENSION AND PANEL CUT-OUT (1/3 size)

(Panel cut-out)

Note: For a rack mount unit, there are holes for joint kits assembling on top and bottom of the unit.

Figure 11 – Dimension and Panel Cut-out – 1/3 x 19’’ case size (Bay unit)

(when compression plug type terminals are applied)

Page 28: Busbar Protection IED - Toshiba€¦ ·  · 2017-11-21Programmable control, trip and alarm logic with PLC tool software Graphical LCD and 7 configurable function keys USB port for

28

DIMENSION AND PANEL CUT-OUT (1/2 size)

(Panel cut-out)

Note: For a rack mount unit, there are holes for joint kits assembling on top and bottom of the unit.

Figure 12 – Dimension and Panel Cut-out – 1/2 x 19’’ case size (Bay unit)

(when compression plug type terminals are applied)

Page 29: Busbar Protection IED - Toshiba€¦ ·  · 2017-11-21Programmable control, trip and alarm logic with PLC tool software Graphical LCD and 7 configurable function keys USB port for

29

19” RACK MOUNTING JOINT KITS ATTACHMENT

<Panel mounting kits – only for compressed terminal type racks> Name Code Joint kits for single 1/3 x 19” size rack EP-201 Joint kits for two 1/3 x 19” size racks EP-202 Joint kits for three 1/3 x 19” size racks EP-203 Joint kits for single 1/2 x 19” size rack EP-204 Joint kits for two 1/2 x 19” size racks EP-205

EP-204 (single 1/2 x 19” size rack) EP-205 (two 1/2 x 19” size racks)

Figure 13 – Joint kits example for 19” rack panel mounting

Page 30: Busbar Protection IED - Toshiba€¦ ·  · 2017-11-21Programmable control, trip and alarm logic with PLC tool software Graphical LCD and 7 configurable function keys USB port for

30

CONNECTIONS DIAGRAM (COMPRESSION PLUG TYPE)

BI1 A

1

2 BI1

(+)

(-)

3

4 BI2

(+)

(-)

5

6 BI3

(+)

(-)

7

8 BI4

(+)

(-)

9

10 BI5

(+)

(-)

13

14 BI7

(+)

(-)

11

12 BI6

(+)

(-)

15

16 BI8

(+)

(-)

17

18 BI9

(+)

(-)

21

22 BI10

(+)

(-)

23

24 BI11

(+)

(-)

25

26 BI12

(+)

(-)

27

28 BI13

(+)

(-)

29

30 BI14

(+)

(-)

31

32 BI15

(+)

(-)

35

36 BI17

(+)

(-)

33

34 BI16

(+)

(-)

37

38 BI18

(+)

(-)

BI3 A

35

36

(-)

(-)

37

38

(-)

(-)

1 (+) BI1

2 (+) BI2

3 (+) BI3

4 (+) BI4

5 (+) BI5

6 (+) BI6

7 (+) BI7

8 (+) BI8

9 (+) BI9

10 (+) BI10

11 (+) BI11

12 (+) BI12

13 (+) BI13

14 (+) BI14

15 (+) BI15

16 (+) BI16

17 (+) BI17

18 (+) BI18

21 (+) BI19

22 (+) BI20

23 (+) BI21

24 (+) BI22

25 (+) BI23

26 (+) BI24

27 (+) BI25

28 (+) BI26

29 (+) BI27

30 (+) BI28

31 (+) BI29

32 (+) BI30

33 (+) BI31

34 (+) BI32

Figure 14 – Binary input board module (for Compression plug type terminal)

Page 31: Busbar Protection IED - Toshiba€¦ ·  · 2017-11-21Programmable control, trip and alarm logic with PLC tool software Graphical LCD and 7 configurable function keys USB port for

31

CONNECTIONS DIAGRAM (COMPRESSION PLUG TYPE)

BO1 A

BO10

21

22

BO1(*2)

1

2

BO2(*2)

3

4

BO3(*2)

5

6

BO4(*2)

7

8

BO5(*2)

9

10

BO6(*2)

11

12

BO7

13

14

BO8

15

16

BO9

17

18

BO11

23

24

BO12

25

26

BO13

27

28

BO14

29

30

BO15

31

32

BO16

33

34

BO17

35

36

BO18

37

38

BO2 A

BO1(*3)

1

2

(+)

(-)

BO2(*3)

3

4

(+)

(-)

BO3(*3)

5

6

(+)

(-)

BO4(*3)

7

8

(+)

(-)

BO5(*3)

9

10

(+)

(-)

BO6(*3)

11

12

(+)

(-)

BO7(*3)

13

14

(+)

(-)

BO8(*3)

15

16

(+)

(-)

BO9(*3)

17

18

(+)

(-)

BO10(*3)

21

22

(+)

(-)

BO11(*3)

23

24

(+)

(-)

BO12(*3)

25

26

(+)

(-)

BO13(*3)

27

28

(+)

(-)

BO14(*3)

29

30

(+)

(-)

BO15(*3)

31

32

(+)

(-)

BO16(*3)

33

34

(+)

(-)

PWS1 A

29

30

31

32

38

DC/DC

(+)

(-)

35

37

36

3

1

2

4

FAIL1

9

7

8

10

FAIL2

Protective Earth

(*2) Semi-fast BO (*3) Hybrid BO

Figure 15 – Binary output board module and DC/DC module

(for Compression plug type terminal)

Page 32: Busbar Protection IED - Toshiba€¦ ·  · 2017-11-21Programmable control, trip and alarm logic with PLC tool software Graphical LCD and 7 configurable function keys USB port for

32

CONNECTIONS DIAGRAM (COMPRESSION PLUG TYPE)

BIO1 A

BO1(*2)

15

16

BO2(*2)

17

18

BO3(*2)

21

22

BO4(*2)

23

24

BO5(*2)

25

26

BO6(*2)

27

28

BO7

29

30

BO8

31

32

BO9

33

34

1

2 BI1

(+)

(-)

3

4 BI2

(+)

(-)

5

6 BI3

(+)

(-)

7

8 BI4

(+)

(-)

9

10 BI5

(+)

(-)

13

14 BI7

(+)

(-)

11

12 BI6

(+)

(-)

36

38

35

37

BO10

BIO2 A

BO1(*2)

27

28

BO2(*2)

29

30

BO3(*2)

31

32

BO4

33

34

36

38

35

37

BO5

1

2 BI1

(+)

(-)

3

4 BI2

(+)

(-)

5

6 BI3

(+)

(-)

7

8 BI4

(+)

(-)

9

10 BI5

(+)

(-)

13

14 BI7

(+)

(-)

11

12 BI6

(+)

(-)

15

16 BI8

(+)

(-)

17

18 BI9

(+)

(-)

21

22 BI10

(+)

(-)

23

24 BI11

(+)

(-)

25

26 BI12

(+)

(-)

BIO3 A

BO1(*1)

21

22

BO2(*1)

23

24

BO3(*1)

25

26

BO4(*1)

27

28

BO5(*1)

29

30

BO6(*1)

31

32

BO7

33

34

36

38

35

37

BO8

1

2 BI1

(+)

(-)

3

4 BI2

(+)

(-)

5

6 BI3

(+)

(-)

7

8 BI4

(+)

(-)

9

10 BI5

(+)

(-)

13

14 BI7

(+)

(-)

11

12 BI6

(+)

(-)

15

16 BI8

(+)

(-)

(*1) Fast BO (*2) Semi-fast BO (*3) Hybrid BO

Figure 16 – Combined binary input and output module

(for Compression plug type terminal)

Page 33: Busbar Protection IED - Toshiba€¦ ·  · 2017-11-21Programmable control, trip and alarm logic with PLC tool software Graphical LCD and 7 configurable function keys USB port for

33

CONNECTIONS DIAGRAM

CT/VT Module

For CU For CU For BU – 1/3 rack For BU – 1/2 r ack

VcD

23

24

VaD

19

20

VcC

17

18

VbC

15

16

VaC

13

14

VcB

11

12

VCT21B

VaA

1

2

30

VbA

3

4

VcA

5

6

VaB

7

8

VbB

9

10

VbD

21

22

GRB (1.0)

VcH

23

24

VaH

19

20

VcG

17

18

VbG

15

16

VaG

13

14

VcF

11

12

VCT21B

VaE

1

2

30

VbE

3

4

VcE

5

6

VaF

7

8

VbF

9

10

VbH

21

22

GRB(1.0)

VCT32B

20

Ia

7

8

Ib

9

10

Ic

11

12

(Not used) 13

14

Ie

15

16

(Not Used)

17

18

GRB(1.0)

VCT22B

30

Ia

19

20

Ib

21

22

Ic

23

24

Ie

25

26

GRB(1.0)

Module no.21 Module no.21 Module no.32 Module no.22 (VT x 12) (VT x 12) (CT x 4) (CT x 4)

Figure 20 – CT/VT module

Page 34: Busbar Protection IED - Toshiba€¦ ·  · 2017-11-21Programmable control, trip and alarm logic with PLC tool software Graphical LCD and 7 configurable function keys USB port for

34

EXTERNAL CONNECTIONS DIAGRAM

CU (Central Unit) – 1/1 size

PWS1 A

29

30

31

32

38

DC/DC

(+)

(-)

35

37

36

FG

3

1

2

4

FAIL1

9

7

8

10

FAIL2

BO1 A

BO10(*4)

21

22

BO1(*2)

1

2

BO2(*2)

3

4

BO3(*2)

5

6

BO4(*2)

7

8

BO5(*2)

9

10

BO6(*2)

11

12

BO7(*4)

13

14

BO8(*4)

15

16

BO9(*4)

17

18

BO11(*4)

23

24

BO12(*4)

25

26

BO13(*4)

27

28

BO14(*4)

29

30

BO15(*4)

31

32

BO16(*4)

33

34

BO17(*4)

35

36

BO18(*4)

37

38

BI1 A

1

2 BI1

(+)

(-)

3

4 BI2

(+)

(-)

5

6 BI3

(+)

(-)

7

8 BI4

(+)

(-)

9

10 BI5

(+)

(-)

13

14 BI7

(+)

(-)

11

12 BI6

(+)

(-)

15

16 BI8

(+)

(-)

17

18 BI9

(+)

(-)

21

22 BI10

(+)

(-)

23

24 BI11

(+)

(-)

25

26 BI12

(+)

(-)

27

28 BI13

(+)

(-)

29

30 BI14

(+)

(-)

31

32 BI15

(+)

(-)

35

36 BI17

(+)

(-)

33

34 BI16

(+)

(-)

37

38 BI18

(+)

(-)

TX1

RX1

TX2

RX2

TX3

RX3

TX4

RX4

TX5

RX5

TX6

RX6

TX7

RX7

TX8

RX8

TX1

RX1

TX2

RX2

TX3

RX3

TX4

RX4

TX5

RX5

TX6

RX6

TX7

RX7

TX8

RX8

TX1

RX1

TX2

RX2

TX3

RX3

TX4

RX4

TX5

RX5

TX6

RX6

TX7

RX7

TX8

RX8

TX1

RX1

TX2

RX2

TX3

RX3

TX4

RX4

TX5

RX5

TX6

RX6

TX7

RX7

TX8

RX8

TX1

RX1

TX2

RX2

TX3

RX3

TX4

RX4

TX5

RX5

TX6

RX6

TX7

RX7

TX8

RX8

TX1

RX1

TX2

RX2

TX3

RX3

TX4

RX4

TX5

RX5

TX6

RX6

TX7

RX7

TX8

RX8

TX1

RX1

TX2

RX2

TX3

RX3

TX4

RX4

TX5

RX5

TX6

RX6

TX7

RX7

TX8

RX8

TX1

RX1

TX2

RX2

TX3

RX3

TX4

RX4

TX5

RX5

TX6

RX6

TX7

RX7

TX8

RX8

100BASE-FX

RX

TX

100BASE-FX

RX

TX

VcD

23

24

VaD

19

20

VcC

17

18

VbC

15

16

VaC

13

14

VcB

11

12

VCT21B

VaA

1

2

30

VbA

3

4

VcA

5

6

VaB

7

8

VbB

9

10

VbD

21

22

VcH

23

24

VaH

19

20

VcG

17

18

VbG

15

16

VaG

13

14

VcF

11

12

VCT21B

VaE

1

2

30

VbE

3

4

VcE

5

6

VaF

7

8

VbF

9

10

VbH

21

22

Figure 21 – Typical external connection diagram (VC T: No.21B x 2, IO: BI1A, BO1A )

T3 T2 T1 OP8 VC1 VC2 C11

C12

C13

C14

C15

[IO#2] [IO#1] [OPT#2] [OPT#1] [VCT#1] [VCT#2]

OP7 OP6 OP5 OP4 OP2 OP1 OP3

[OPT#3] [OPT#4] [OPT#5] [OPT#6] [OPT#7] [OPT#8]

(*)

●FG E●

(CASE EARTH)

●FG1 ●FG2

(*)This connection is connected by green earth wire before shipment.

(*) (*) (*)

Page 35: Busbar Protection IED - Toshiba€¦ ·  · 2017-11-21Programmable control, trip and alarm logic with PLC tool software Graphical LCD and 7 configurable function keys USB port for

35

EXTERNAL CONNECTIONS DIAGRAM

BU (Bay Unit) – 1/3 size

PWS1 A

29

30

31

32

38

DC/DC

(+)

(-)

35

37

36

FG

3

1

2

4

FAIL1

9

7

8

10

FAIL2

BIO3 A

BO1(*1)

21

22

BO2(*1)

23

24

BO3(*1)

25

26

BO4(*1)

27

28

BO5(*1)

29

30

BO6(*1)

31

32

BO7(*4)

33

34

36

38

35

37

BO8(*5)

1

2 BI1

(+)

(-)

3

4 BI2

(+)

(-)

5

6 BI3

(+)

(-)

7

8 BI4

(+)

(-)

9

10 BI5

(+)

(-)

13

14 BI7

(+)

(-)

11

12 BI6

(+)

(-)

15

16 BI8

(+)

(-)

100BASE-TX

CU Communication

RX

TX

VCT32B

20

Ia

7

8

Ib

9

10

Ic

11

12

Ie

15

16

Figure 22 – Typical external connection diagram (VC T: No.32B, IO: BIO3A )

(*)This connection is connected by green earth wire before shipment.

[IO#1] [VCT#1]

●FG

●FG1

T2 T1 VC1

E●(CASE EARTH)

(*)

(*)

(*)

C11

C12

C13

C14

C15

Page 36: Busbar Protection IED - Toshiba€¦ ·  · 2017-11-21Programmable control, trip and alarm logic with PLC tool software Graphical LCD and 7 configurable function keys USB port for

36

EXTERNAL CONNECTIONS DIAGRAM

BU (Bay Unit) – 1/2 size

PWS1 A

29

30

31

32

38

DC/DC

(+)

(-)

35

37

36

FG

3

1

2

4

FAIL1

9

7

8

10

FAIL2

BIO3 A

BO1(*1)

21

22

BO2(*1)

23

24

BO3(*1)

25

26

BO4(*1)

27

28

BO5(*1)

29

30

BO6(*1)

31

32

BO7(*4)

33

34

36

38

35

37

BO8(*5)

1

2 BI1

(+)

(-)

3

4 BI2

(+)

(-)

5

6 BI3

(+)

(-)

7

8 BI4

(+)

(-)

9

10 BI5

(+)

(-)

13

14 BI7

(+)

(-)

11

12 BI6

(+)

(-)

15

16 BI8

(+)

(-)

BO1 A

BO10(*4)

21

22

BO1(*2)

1

2

BO2(*2)

3

4

BO3(*2)

5

6

BO4(*2)

7

8

BO5(*2)

9

10

BO6(*2)

11

12

BO7(*4)

13

14

BO8(*4)

15

16

BO9(*4)

17

18

BO11(*4)

23

24

BO12(*4)

25

26

BO13(*4)

27

28

BO14(*4)

29

30

BO15(*4)

31

32

BO16(*4)

33

34

BO17(*4)

35

36

BO18(*4)

37

38

BI1 A

1

2 BI1

(+)

(-)

3

4 BI2

(+)

(-)

5

6 BI3

(+)

(-)

7

8 BI4

(+)

(-)

9

10 BI5

(+)

(-)

13

14 BI7

(+)

(-)

11

12 BI6

(+)

(-)

15

16 BI8

(+)

(-)

17

18 BI9

(+)

(-)

21

22 BI10

(+)

(-)

23

24 BI11

(+)

(-)

25

26 BI12

(+)

(-)

27

28 BI13

(+)

(-)

29

30 BI14

(+)

(-)

31

32 BI15

(+)

(-)

35

36 BI17

(+)

(-)

33

34 BI16

(+)

(-)

37

38 BI18

(+)

(-)

100BASE-TX

CU Communication

RX

TX

VCT22B

30

Ia

19

20

Ib

21

22

Ic

23

24

Ie

25

26

Figure 23 – Typical external connection diagram (VC T: No.22B, IO: BI1A, BO1A, BIO3A )

[IO#1] [VCT#1] [IO#2] [IO#3]

●FG

●FG1

T4 T3 T2 T1 VC1

E●(CASE EARTH)

(*)

(*)

(*)

C11

C12

C13

C14

C15

(*)This connection is connected by green earth wire before shipment.

Page 37: Busbar Protection IED - Toshiba€¦ ·  · 2017-11-21Programmable control, trip and alarm logic with PLC tool software Graphical LCD and 7 configurable function keys USB port for

72-34Tel +81http://www.toshiba

34, Horikawa+81-44-331-1462

http://www.toshiba

Horikawa-cho, Saiwai1462 Fax +81

http://www.toshiba-relays.com

Saiwai-Ku, KawasakiFax +81-44-548-9540

relays.com

Kawasaki 212-85859540

・The information given in this catalog is subject to change without notice.・The information given in this catalog is a・The information given in this catalog is presented only as a guide for the

applications of our products. No responsibility is assumed by TOSHIBA for any infringementsresult from its use. No licensany patent or patent rights of TOSHIBA or others.

・TOSHIBA products should not be embedded to the downstream products which are prohibited to be produced and sold, under any law and regulations.

- Toshiba does not take any loss of business profit, business iand other pecuniary damage) arising out of the use or disability to use the products.

8585, Japan

The information given in this catalog is subject to change without notice.The information given in this catalog is aThe information given in this catalog is presented only as a guide for the applications of our products. No responsibility is assumed by TOSHIBA for any infringements of patents or other rights of the third parties which may result from its use. No licensany patent or patent rights of TOSHIBA or others.TOSHIBA products should not be embedded to the downstream products which are prohibited to be produced and sold, under any law and regulations. oshiba does not take any

loss of business profit, business iand other pecuniary damage) arising out of the use or disability to use the products.

The information given in this catalog is subject to change without notice.The information given in this catalog is aThe information given in this catalog is presented only as a guide for the applications of our products. No responsibility is assumed by TOSHIBA for

of patents or other rights of the third parties which may result from its use. No license is granted by implication or otherwise under any patent or patent rights of TOSHIBA or others.TOSHIBA products should not be embedded to the downstream products which are prohibited to be produced and sold, under any law and

oshiba does not take any responsibilityloss of business profit, business interruption, loss of business information and other pecuniary damage) arising out of the use or disability to use the

The information given in this catalog is subject to change without notice.The information given in this catalog is as of 25 OctoberThe information given in this catalog is presented only as a guide for the applications of our products. No responsibility is assumed by TOSHIBA for

of patents or other rights of the third parties which may e is granted by implication or otherwise under

any patent or patent rights of TOSHIBA or others. TOSHIBA products should not be embedded to the downstream products which are prohibited to be produced and sold, under any law and

responsibility for incidental damage (including nterruption, loss of business information

and other pecuniary damage) arising out of the use or disability to use the

GKP

The information given in this catalog is subject to change without notice.October 2017.

The information given in this catalog is presented only as a guide for the applications of our products. No responsibility is assumed by TOSHIBA for

of patents or other rights of the third parties which may e is granted by implication or otherwise under

TOSHIBA products should not be embedded to the downstream products which are prohibited to be produced and sold, under any law and

for incidental damage (including nterruption, loss of business information

and other pecuniary damage) arising out of the use or disability to use the

GKP-99-13011 Rev 1.0

©C

opyri

gh

t 2017 T

osh

iba E

ner

gy S

yst

ems

& S

olu

tion

s C

orp

orati

on. A

ll r

igh

ts r

eser

ved

.

The information given in this catalog is subject to change without notice.

The information given in this catalog is presented only as a guide for the applications of our products. No responsibility is assumed by TOSHIBA for

of patents or other rights of the third parties which may e is granted by implication or otherwise under

TOSHIBA products should not be embedded to the downstream products which are prohibited to be produced and sold, under any law and

for incidental damage (including nterruption, loss of business information

and other pecuniary damage) arising out of the use or disability to use the

13011 Rev 1.01