Building Performance Modelling -...

10
M. A. Schnabel (ed.), Back to the Future: The Next 50 Years, (51st International Conference of the Architectural Science Association (ANZAScA)), ©2017, Architectural Science Association (ANZAScA), pp. 207–216. Building Performance Modelling Parametric Study of Energy Optimization for Office Retrofit in the Tropics Runddy Ramilo 1 , Sambit Datta 2 and Mohamed Rashid Embi 3 1 International Design Associates, Singapore & Curtin University, Australia [email protected] 2 Curtin University, Australia [email protected] 3 Universiti Teknologi Malaysia, Malaysia b[email protected] Abstract: Buildings are accounted for approximately 40% of global energy consumption and onethird of global greenhouse gas (GHG) emissions. A significant proportion of energy utilization is due to the spread of heating, ventilating, and air conditioning (HVAC) installations in response to the growing demands for better thermal comfort of the built environment. While the proportion of energy consumption of buildings is an issue, architects have not seriously considered to innovate new solutions to tackle the problem particularly existing office building which is centrally airconditioned and consumed substantial amount of energy. Only few has been research to improve its performance to save energy that can be used as bench mark for post occupancy evaluation for existing buildings. To elucidate this issue, this paper is a result of a case study using building performance simulation tool to optimized energy for an actual office retrofit project in the tropics. Its objectives are to explore an energy optimization strategy using building performance simulation tool (IESVE) and to improve existing office building envelop for utmost energy efficiency. The result revealed that using parametric methodology through building performance simulation tool, an office building has the potential to achieve 26.8 % energy savings. Keywords: Building Performance Modelling; building envelop; energy efficiency; office building retrofit. 1. Introduction and Background Increasing concerns about global warming present the building industry with a challenge to cut its energy consumption (Chenvidyakarn, 2010). It was evident that the building sector consumes 40%50% of the total delivered energy (EPA, 2004), (DTI, 2003). Building environment control systems like ventilation, cooling and heating can be fared as much as 70% of the total energy used (BRESCO, 2000). However, this energy consumption can be reduced significantly by utilizing passive design solutions instead of active mechanically designed buildings. For instance, a building engineered for tropics can only consume one third of the energy consumed by an airconditioned building (BRESCU, 2000), (Chenvidyakarn, 2010) while providing comparable level of thermal performance. This is because building in the tropics must be designed to adapt climate and take better advantages (Chenvidyakarn, 2010) of natural energy resources

Transcript of Building Performance Modelling -...

Page 1: Building Performance Modelling - ANZAScAanzasca.net/wp-content/uploads/2017/11/ASA_2017_Ramilo_Datta_E… · indoor climate and environmental considerations. The existing facade of

M. A. Schnabel (ed.), Back to the Future: The Next 50 Years, (51st International Conference of the Architectural Science Association (ANZAScA)), ©2017, Architectural Science Association (ANZAScA), pp. 207–216.  

 

Building Performance Modelling 

Parametric Study of Energy Optimization for Office Retrofit in the Tropics 

Runddy Ramilo1, Sambit Datta2 and Mohamed Rashid Embi3 1 International Design Associates, Singapore & Curtin University, Australia 

[email protected] 2 Curtin University, Australia [email protected] 

3 Universiti Teknologi Malaysia, Malaysia  b‐[email protected] 

Abstract: Buildings are accounted for approximately 40% of global energy consumption and one‐third of global greenhouse gas (GHG) emissions. A significant proportion of energy utilization is due to the spread of heating, ventilating, and air conditioning (HVAC) installations in response to the growing demands for better  thermal  comfort  of  the  built  environment. While  the  proportion  of  energy  consumption  of buildings  is an  issue, architects have not seriously considered  to  innovate new solutions  to  tackle  the problem particularly existing office building which is centrally airconditioned and consumed substantial amount of energy. Only few has been research to  improve  its performance to save energy that can be used as bench mark for post occupancy evaluation for existing buildings. To elucidate this issue, this paper is a result of a case study using building performance simulation tool to optimized energy for an actual office retrofit project  in the tropics.  Its objectives are to explore an energy optimization strategy using building performance simulation tool (IESVE) and to improve existing office building envelop for utmost energy efficiency. The result revealed that using parametric methodology through building performance simulation tool, an office building has the potential to achieve 26.8 % energy savings.   Keywords: Building Performance Modelling; building envelop; energy efficiency; office building retrofit. 

1. Introduction and Background 

Increasing concerns about global warming present the building industry with a challenge to cut its energy consumption (Chenvidyakarn, 2010).  It was evident that the building sector consumes 40%‐50% of the total delivered energy  (EPA, 2004),  (DTI, 2003). Building environment control systems  like ventilation, cooling and heating can be fared as much as 70% of the total energy used (BRESCO, 2000). However, this energy consumption can be reduced significantly by utilizing passive design solutions  instead of active mechanically designed buildings. For  instance, a building engineered for tropics can only consume one third of the energy consumed by an air‐conditioned building (BRESCU, 2000), (Chenvidyakarn, 2010) while providing  comparable  level  of  thermal  performance.  This  is  because  building  in  the  tropics must  be designed to adapt climate and take better advantages (Chenvidyakarn, 2010) of natural energy resources 

Page 2: Building Performance Modelling - ANZAScAanzasca.net/wp-content/uploads/2017/11/ASA_2017_Ramilo_Datta_E… · indoor climate and environmental considerations. The existing facade of

208  R. Ramilo, S. Datta and M. R.Embi 

 

such as wind and thermal buoyancy to help provide acceptable thermal comfort specifically in the tropics where heat of interior environment of a building is a challenge.  

 The Tropics  is regarded as a region where humans evolved and comfort has often been  taken  for granted, built environments are increasingly becoming issues of public concern (Ossen et al, 2008). The tropical indoor environment and thermal comfort has been regarded as important as outdoor in the life of the populace which is remarkably evident in the vernacular architecture of the region. However, today many cities in the region experienced rapid urban growth often without much reference to the evolving urban environment. This tendency has put increased demand on the comfort requirements in the design of buildings. Comfortable outdoor spaces have a significant bearing on  the comfort perception of  the indoor ambience  (Ossen et al, 2008). The demand  for comfort conditions  in buildings are significantly increased  as  a  result  of  exposure  to  uncomfortable  indoors.  Achieving  thermal  comfort  for  building engineered  for  tropics  in hot humid  climates  is  indeed a  challenge  (Chenvidyakarn, 2010),  (Suebarto, 2006). Point out by experts, tropics  is characterized by relatively high temperature and high humidity. These difficulties  lead to many buildings relying for air‐conditioning. However, range of passive design techniques such as design for minimizing cooling requirement and building massing (Wong, 2010), the use of  shading  device  (Garde  et  al,  2001),  (Laopanitchakul  et  al,  2007),  material,  color  and  texture (Leaurungreon et al, 2005), vegetation (Chen and Wong, 2006) cooling and ventilating techniques (Givoni, 1991), (Tantasavasdi et al, 2007), thermal mass (Hunt and Linden, 2004), radiant cooling (Givoni, 1994), indirect evaporative cooling  (Givoni, 1980),  (Bourne and Hoeschele, 1992) was already developed and framed but existing office building in the tropics has not been taken into account.  

2. Objectives 

Advances in digital technologies particularly building simulation environments have focused on algorithm development, data management and interfacing that are analysis based and support independent domain activities (Malkawi, 2004), (Ramilo & Embi, 2013). Currently, there is a broad range of simulation packages (Energy Plus, TRNSYS, Ecotect, IES and COMIS) that evaluate multiple thermal performance for buildings (Ramilo &  Embi,  2013)  (Luther,  2003).  To  shift  the  emphasis  of  these  tools  from  analysis  only  to  a combined model of analysis and synthesis a renewed research into advances in optimization is underway (Kolarevic et el, 2006). It integrates digital simulation tools to support performance driven design using optimization  and  partial  automation  (Pitts  et  al,  2008). Methods  to  assist  in  the  coupling  of  design geometry  with  building  performance  simulation  and  the  prediction  of  the  performance  of  building envelopes (Luther, 2000), (Luther et al, 2007), (Ramilo & Embi, 2016) are being undertaken.  

 One research that have employed the used of digital technology (Ecotect) was Ossen et al (2010) to evaluate  and measure  thermal  performance  in  indoor  environment  in  their  tropical  building  design project. The  thermal  comfort  study  involved  the use of  field and  combination with Ecotect  software. Validation of Ecotect was done by comparing the computer simulation result with the field measurement. Likewise on the research of prediction of thermal performance of facade residential buildings in Singapore (Liping, 2006), a conflation of digital technologies were used such as computational fluid dynamics (CFD and building simulation program  (ESP‐r)  to simulate  thermal performance. The coupling program was validated  by  a  series  of  validation  studies,  including  single  zone  case,  multi‐zone  cases,  and  field measurement  studies. The  result have  shown  that  the  coupled  simulations  can produce much better results  that building simulation alone especially  in  the aspect of  indoor air velocity prediction  (Liping, 2006). 

Page 3: Building Performance Modelling - ANZAScAanzasca.net/wp-content/uploads/2017/11/ASA_2017_Ramilo_Datta_E… · indoor climate and environmental considerations. The existing facade of

209 

 

Building Performance Modelling Parametric 

 However while different research of building performance modelling is evaluated during schematic and design phase of a building project, only few has been research for existing office building to improve its  performance  and  save  energy  particularly  for  actual  office  retrofit  project  that  require  building simulation tools to evaluate iterations of building envelop for final decision making and provides better understanding of how building performance  simulation  tool  can evaluate  façade design and  in a way improve its performance. To elucidate this issue, this paper is a result of a case study made from an actual office  retrofit  project  in  Singapore  to  improve  energy  efficiency  through  improving  existing  building envelop. This study elucidates design methodologies that can be used either in design stage of the project or  post  construction  performance  evaluation  to  improve  building  design  using  building  performance simulation tool (IESVE). Specifically, its main objective is to improve existing office building envelope and explore energy optimization opportunities to improved energy efficiency of 25% to 30% energy savings.  

3. Building Performance Modelling for Energy Optimization 

Building performance modeling is defined as an expression of measurable variables which affect a process or procedure. Common building performance factors are environmental such as solar gain, aerodynamics and heat loss, structural factors such as load and stress, and social factors such as view and privacy (Gunay et al, 2013). This  includes  finding sustainable and green strategies using new digital  technologies  that simulates  building  performance  or  4D  digital  technologies  that  is  available  in  the market.  4D  digital technologies  are  commercial  software  (Ramilo  &  Embi,  2013)  that  can  evaluated  and  stimulate daylighting, heat, energy efficiency, air flows, and indoor humidity. It helps and allow the design teams to provide quality information that is needed to quantify iterative choices, so that design teams can develop innovative green solutions at schematic phase of building design. 

One  notable  project  which  have  utilized  building  performance  modelling  for  energy  efficient responsive facade was Hanwha Headquarters  in Seoul, Korea designed by UN Studio done to mitigate heat flow, optimized facade assembly and increase thermal comfort of its interior spaces (Figure 2).  

 

Figure 2: Hanwha Headquarters, Seoul, Korea by UN Studio (Littlefield, 2008).  

 The high‐rise Hanwha’s headquarter building was mainly a renovation and re‐modeling of the facade which includes refurbishment of its interior public spaces, meeting floors, theatres and executive areas, along with the redesign of the landscaping. UN Studio’s design concept of the building resulted to be a 

Page 4: Building Performance Modelling - ANZAScAanzasca.net/wp-content/uploads/2017/11/ASA_2017_Ramilo_Datta_E… · indoor climate and environmental considerations. The existing facade of

210  R. Ramilo, S. Datta and M. R.Embi 

 

responsive facade which valued and integrates important key variables: program (exterior and interior), indoor  climate  and  environmental  considerations.  The  existing  facade of  the building  contains  single layers of dark glass and horizontal bands of opaque paneling. UN  Studio decided  to  replace by  clear insulated glass and aluminum  framing  to accentuate views and daylight.  It’s  framing and geometry  is defined by the sun and orientation factors to ensure user comfort inside and to be able to reduce energy consumption. The facade workflow module distribution by UN Studio is presented in Figure 3.  

 

 

Figure 3: Facade workflow module distributionby UN Studio (Littlefield, 2008).  

 While the upper portion of the south facade is angled to receive direct sunlight, direct solar impact on the building was reduced by shading which is provided by angling the glazing away from direct sunlight. At south and southeast where there is direct sunlight, photovoltaic cells are placed on the opaque panels on the façade. The challenging part on this process is that even a small variation of the parent geometry of the panel quickly results in an avalanche of child modules, which makes it necessary to develop a tool to automatically generate all possible facade unit variations panel. The idea of developing a “Unit‐Maker Tool” through scripting  is helpful to takes basic geometric  input  information such as transom position, mullion dimensions, glass properties, and outputs numerous facade units. 

3. Methodology 

The scope of the case study dealt with exploring energy saving opportunities through improving building envelop of an existing 9‐storey centralized office building located on the west of Singapore with a gross floor area of 18,879 square meters, with north‐south orientation and window to wall area ratio of 0.57. The exploration was focused on how to improve the existing facade to minimize heat gain, improve day lighting and to minimize energy consumption. The exploration was done in four modified steps 1) post occupancy  evaluation  and measurements,  2)  4d modelling  through  IESVE,  3)  building  performance evaluation and 4) decision making which is briefly explain in 3.1, 3.2, 3.3 and 3.4 

3.1 Post Occupancy Evaluation and Measurements 

The  first  step of  the  exploration was  to  evaluate  the  existing office building.  This was done  through assessing  the architectural plans and evaluating  the data such as area of spaces and record of energy consumption. These data (Figure 4, 5 & 6) were collected, analyzed, validated and subsequently used in 4d modeling.  

Page 5: Building Performance Modelling - ANZAScAanzasca.net/wp-content/uploads/2017/11/ASA_2017_Ramilo_Datta_E… · indoor climate and environmental considerations. The existing facade of

211 

 

Building Performance Modelling Parametric 

 

 

Figure 4: Photo and existing plan of the project 

 

Figure 5: Space areas of the project 

 

Figure 6: Existing building energy consumption 

  

Page 6: Building Performance Modelling - ANZAScAanzasca.net/wp-content/uploads/2017/11/ASA_2017_Ramilo_Datta_E… · indoor climate and environmental considerations. The existing facade of

212  R. Ramilo, S. Datta and M. R.Embi 

 

3.2 4D‐Modelling Using IESVE 

A 4d model was made using the verified architectural plans, sections, elevations and interior spaces of the existing office building project  through  IESVE  (Figure 7).  It was made  to simulate  the existing building orientation and other site condition.  

 

Figure 7: 4d model of the existing project  

3.3 Building Performance Iterations 

When the baseline 3d model was verified, three (3) options of different new facade including the existing office building was modelled as shown in figure 8, made to evaluate the new facade design in terms of energy efficiency. Building performance simulation experiments of three façade options through  IESVE was made, evaluated and assessed on the basis of efficiency and accuracy of thermal performance results. Quantitative data was statistically compared on existing building and each proposed retrofitted building envelop and energy consumption was recorded and analyzed (Figure 9). This was done to further improve the facade and explore the possibility of reducing energy consumption.  

 

 

Figure 8: 3d Models of existing building envelop and the three proposed retrofitted building envelope 1, 2 & 3 showing its WWR and ETTV 

 

Page 7: Building Performance Modelling - ANZAScAanzasca.net/wp-content/uploads/2017/11/ASA_2017_Ramilo_Datta_E… · indoor climate and environmental considerations. The existing facade of

213 

 

Building Performance Modelling Parametric 

Figure 9: Comparison of energy consumption of proposed building Envelope 1, 2 & 3.  

 

3.4 Decision Making 

After the building performance simulation of the new three (3) proposed façade was made, relevant data related to energy efficiency and daylighting was carefully analyzed, verified and final decision was made as to which among the three (3) options is best to utilized.  

4. Results 

Considering energy efficiency, the proposed retrofitted building envelop 3 with the WWR of 0.40 and ETTV of 30.90W/m2 as shown in figure 10 was chosen as the final design façade design. It is because retrofitted building envelop 3 has the highest amount of energy savings (26.8%) among the three models that was presented in Figure 8. A comparison of cooling load savings of proposed building between envelope 1, 2 & 3 is presented in Figure 11.  

 

 

Figure 10: Comparison of existing building envelope and proposed retrofitted building envelope 3 as final design 

 

It was reiterated that the rate of heat transfer through the building envelop was depended on the difference of value between the outside temperatures and the temperature of the interior of the building 

Page 8: Building Performance Modelling - ANZAScAanzasca.net/wp-content/uploads/2017/11/ASA_2017_Ramilo_Datta_E… · indoor climate and environmental considerations. The existing facade of

214  R. Ramilo, S. Datta and M. R.Embi 

 

and the capacity of the facade to control heat flow and heat transfer. Factors that  influence heat flow within  the  facade  is mainly  the overall  thermal  resistance, window  to wall  ratio  (WWR), and envelop thermal transfer value (ETTV). It is also worth noting is that building envelop with high WWR is likely to have greater effect of  the  thermal comfort  than with  low WWR. The optimal WWR must  importantly consider  the  layout of  the space, smaller WWR must be used  for spaces where users are near  to  the penetration for the building envelop facing south. 

 

 

Figure 11: Comparison of Cooling Load Savings of Proposed Building Envelope 1, 2 & 3.  

 

 

Figure 12: Proposed retrofitted building envelope 3 showing the additions of 4 x 300 mm external shading device and how it affects ETTV. 

 

During  the  simulation,  it was evident  that  facade elements  like windows and  light  shelves  is  very significant in as far as thermal fluctuations is concerned. Heat transfer can be dictated the combination of the interior skin temperature of the glazing including the transmitted ultra violet rays through the glazing. This  can be  significantly  influenced by  the glazing units,  the material properties of  the glass, and  the 

Page 9: Building Performance Modelling - ANZAScAanzasca.net/wp-content/uploads/2017/11/ASA_2017_Ramilo_Datta_E… · indoor climate and environmental considerations. The existing facade of

215 

 

Building Performance Modelling Parametric 

effectiveness of the light shelves used above the window (Figure 12). On the iterations, it is noted that light shelves on the south facing building envelope of building remarkably increases the daylighting quality and quantity.  It  reduces cooling cost, efficient daylighting approach by means of  light,  increases  light penetration and therefore decrease artificial  lighting during day  time.  It  is  the most effective  in south facing  envelope,  improves  daylight  penetration,  creates  shading  near  the window,  and  helps  reduce window glare and ultimately decreases the cooling load. 

5. Conclusions 

Building performance modelling play a crucial role in the decision making for designing an energy efficient building retrofit because it help investigate design options prior to construction. It is good tool to assess energy  efficiency,  environmental  and  energy  impacts  of  design  decisions. Without  a  doubt,  it  is  an essential  part  for  designing  sustainable  performative  building  envelope.  In  an  office  retrofit  building project where energy is a concern, building performance simulation tool can quantify and predict energy consumptions and can be further reduced through building envelope iterations. It helps establish metrics that can be utilized  to measure  improvements by using different design strategies.  In  the case of  this study, it is concluded that building performance simulation has an ability to quantify the impact of a design solution like the performance building envelop that can be investigated with actual quantifiable data, not just through theories, and able to analyse, predict energy consumption and saving, and  lastly  improve architectural design with multiple design alternatives.  

References 

Ali M. Malkawi.  (2004) Developments  in Environment Performance Simulation, Automation  in Construction, 13:4, 437‐445. 

Bourne, R. C., & Hoeschele, M. A. (1992) Cool storage roof (Demonstration project monitoring report), Davis Energy Group, Davies, CA 

Building Research  Establishment,  Sustainable Construction Unit  (BRESCU).  (2000).  Energy  consumption guide 19: Energy use in offices, Energy Efficient Best Practice Programme, BRE, Watford, UK. 

Cheng‐an P., and Jeng, T. (2008) Exploring sensing‐based kinetic design for responsive facade, Beyond computer‐aided design, CAADRIA, Chiang Mai, Thailand.  

Chen, Y., & Wong, N. H. (2006). Thermal benefits of city parks. Energy and Buildings, 38, 105‐120. Chenvidyakarn, T. (2010). Review Article: Passive Design for Thermal Comfort in Hot Humid Climates, Department of 

Architecture, University of Cambridge, UK. Chien, SF.  (2009) Proving elders’ needs smart  technologies  in  the domestic environment, Beyond computer‐aided 

design, CAADRIA, Chiang Mai, Thailand. Department  of  Trade  and  Industry  (DTI).  (2003).  Renewables  innovation  review.  Available  from: 

<http://www.berr.gov.uk/files/file21955.pdf> (accessed 2 June 2017). Environmental Protection Agency. USA (EPA). (2004). Buildings and the environment: A statistical summary. Available 

from: <http://www.epa.gov/greenbuilding/pubs/gbstats.pdf> (accessed 2 June 2017). Garde, F., Mara, T., Lauret, A. P., Boyer, H., & Celaire, R. (2001). Bringing simulation to implementation: Presentation 

of a global approach in the design of passive solar buildings under humid tropical climates. Solar Energy, 71(2) 109‐120. 

Givoni, B. (1991). Performance and applicability of passive and low energy cooling systems, Energy and Buildings, 17, 177‐199. 

Givoni, B. (1994). Passive and low energy cooling of buildings. John Wiley & Sons. Givoni, B. (1980). Experimental studies on passive cooling at the Institute for Desert Research in Israel, Proceedings 

of Solar Energy Symposium. Nice, France, 296‐300. 

Page 10: Building Performance Modelling - ANZAScAanzasca.net/wp-content/uploads/2017/11/ASA_2017_Ramilo_Datta_E… · indoor climate and environmental considerations. The existing facade of

216  R. Ramilo, S. Datta and M. R.Embi 

 

Gunay, B., O’Brien, W., and Beausoleil‐Morrison, I. (2013). A Critical Review of Observation Studies, Modeling, and Simulation of Adaptive Occupant Behaviors in Offices, Building and Environment 70 (Dec. 2013), 31–47. 

Hunt, G. R., &  Linden, P. F.  (2004). Displacement and mixing ventilation driven by opposing wind and buoyancy, Journal of Fluid Mechanics, 527, 27‐55. 

Kolarevic, B and Ali M. Malkawi. (2006). Performative Architecture: Beyond Instrumentality. Spon Press, London. Kolarevic, B. (2005). Architecture in the Digital Age: Design and Manufacturing, Taylor & Francis. Lan, JH.  ( 2009) Smart space  for office daily  life: A situated  life pattern approach, Beyond computer‐aided design, 

CAADRIA, Chiang Mai, Thailand  Lan, JH., and Chung, K. ( 2009) Designing smart workplace to assist design activity from emotional approach, Beyond 

computer‐aided design, CAADRIA, Chiang Mai, Thailand. Laopanitchakul, V., Sunakorn, P., & Srisutapan, A. (2007). Climbing‐plants on solid wall reducing energy in tropical    Climate,  in S. W. Shin, & H. W. Lee (Eds.), Proceedings of the  International Conference on Sustainable Building 

Asia, SB07 Seoul, Korean Green Building Council (KGBC), Seoul, Korea, 271‐278. Leaurungreong,  V.,  Oranratmanee,  R.,  Sihalarth,  P.,  &  Insisiengmay,  S.  (2007).  The  local  intelligence  for  a 

dwellingscomfort living, Chiang Mai & Luang Prabang, Journal of Energy Research, 2, 17‐38. Littlefield, D. (2008). Space Craft: Developments in Architectural Computing, RIBA Publishing, London. Liping, W. (2006) The conflation of building simulation and computational fluid dynamics for the prediction of thermal 

performance of façade for naturally ventilated residential buildings, PhD Thesis, Department of Building, School of Design Environment, National University of Singapore. 

Luther, M. B. and Altomonte, S. (2007), Natural and environmentally responsive building envelopes, 37th International Conference on Environmental Systems,Society of Automotive Engineers (SAE), Chicago. 

Luther, M. B. and  J. Cheung,  (2003). High performance  low‐energy, Australian New Zealand Solar Energy Society (ANZSES) Proceedings, Melbourne, Australia.  

Luther, M. B. (2000). Responsive and dynamic building envelopes. Proceedings 30th International Conference on    Environmental Systems and  the 7th European Symposium on Space Environmental Control Systems, Toulouse, 

France  Macintosh, A.,  Priest, R.,  and  Clegg,  F.  (2008)  The Daylight Optimized  Facade, D.,  Space  Craft: Developments  in 

Architectural Computing, RIBA Publishing, London. Menzel, K., Zixiang, C., Allen, T. (2008) Potential for radio frequency identification, S1, 329‐335.  Ozturk, Z., Arayici, Y., Coates, P  (2010) Post occupancy evaluation  (POE)  in  residential buildings utilizing BIM and 

sensing Devises: Salford energy house example, School of Built environment, University of Salford, U.K. Oxman, R. (2007). Digital Architecture as a Challenge for Design Pedagogy: Theory, Knowledge, Models and    Medium, Elsevier, 29(2). Pitts, G and S Datta (2008) Parametric modelling of architectural surfaces, N. Gu, L. Figen Gul, M. Ostwald, A. Williams 

(eds),  ANZAScA'08  :  Innovation,  Inspiration  and  Instruction:  New  Knowledge  in  the  Architectural  Sciences, University of Newcastle, NSW. 

Ramilo, R. D., and Embi, M. R. (2013) Key determinants affecting digital  innovation adoption  in small architectural Organizations, International Journal of Information Technology and Business Management, 16(1). 

Ramilo, R. D., Embi, Rashid M, Datta, S. (2016) Building Information Modelling (BIM): Challenges and Barriers Among 

Architectural Practices, 4th Annual Intern. Conference on Architecture and Civil Engineering (ACE 2016) Singapore. Soebarto, VL., and Handjarinto, S  (1996) Thermal comfort  study  in a naturally ventilated  residential building  in a 

tropical hot humid climate region, Department of Architecture, University of Indonesia. Schoch, O., and Russell, P.  (2009) Kanban as a supporting  tool  for  the sustainable design and operation of smart 

buildings, Beyond computer‐aided design, CAADRIA, Chiang Mai, Thailand  Tantasavasdi, C., Jareemit, D., Suwanchaiskul, A., & Naklada, T. (2007). Natural ventilation: Evaluation and design of 

houses in Thailand. Proceedings of the 3 Conference on Energy Network of Thailand. Bangkok, Thailand. Wong N.H. and Feriadi, H. (2010). Thermal comfort for naturally ventilated houses in Indonesia, Energy and Buildings, 

36, 614‐626. Zhang, G., Zheng, C., Yang, W., Zhang, Q., & Moschandreas, D. J. (2007). Thermal comfort investigation of naturally 

ventilated classrooms in a subtropical region, Indoor and Built Environment, 16(2), 148‐158