Bill of Quantities (BoQ) ITB-2013-208 85 400 8 1 1 1 of 31
Transcript of Bill of Quantities (BoQ) ITB-2013-208 85 400 8 1 1 1 of 31
Bill of Quantities (BoQ) Refurbishment of a forensic laboratory in Ramallah ITB-2013-208
No. Description Unit Qty Unit Rate
US$ Total US$
1 Demolishing Works
Preamble:
The contractor should be aware that the proposed work will be
carried out in the existing functioning building and that the his
daily activities shall not interrupt others ongoing daily activities in
the other floors of the existing building.
Unit rates shall include, but not limited to, the following:
a. Removing of demolished material out of site to an approved
dump location.
b. The dismantled material are the sole properties of the client.
c. The contractor shall coordinate implementation of his daily
work activities, working hours, throughout the construction period
with the client and the supervising engineer
d. The contractor shall protect and safe guard the existing
facilities and building finishes, including the painting, the floor
tiles, *etc. the contractor shall not use the existing elevator for
loading the construction material
e. The contractor shall make the necessary temporary water,
electrical power connections ..etc to prevent interruption of the
power and water supply for the existing functioning building.
f. The contractor shall take all necessary measures to protect and
minimize environmental hazards including pollution, noise, dust
*etc
1.1
Demolishing of the existing internal partitions including block
works, concrete,* etc, price to include dismantling of the
electrical, mechanical installation; all as approved by the
Engineer.
m2 85
1.2
Dismantle of existing wall or floor tiles as shown on drawing A02
and as per the Engineer instructions. Price should include
removal of mortar, fill material below the floor tiles.
m2 400
1.3
Dismantle and preserving the existing wooden or metal doors as
shown on drawing A02 and A03. Price to include removal of the
door leafs and frames, preserving and storing the doors; all as
instructed by the Engineer.
No. 8
1.4
Dismantle and preserve the existing kitchen cabinets, including
careful removal of the counter tops and any associated
electromechanical fixtures or installations.
Job 1
1.5Dismantle and preserve the existing mechanical fixtures including
one toilet, one sink, water closet.Job 1
Total Demolishing Works carried to summary
1 of 31
Bill of Quantities (BoQ) Refurbishment of a forensic laboratory in Ramallah ITB-2013-208
No. Description Unit Qty Unit Rate
US$ Total US$
2 Block & Plaster Works
The contractor shall, when pricing the rates of this bill, take into
consideration including and allowing for the costs or expenses of
all requirements stipulated in the preambles, drawings and
technical specification of the tender.
2.1
Supply and install 10 cm thick hollow blocks with reinforced
concrete tie beams over all block walls with steel reinforcement
4Ф12mm and stirrups diameter 6mm@20cm, 20cm high and
width equal to the wall thickness. The price should include
4Ф12@20cm length steel dowels to be planted in the adjacent
concrete or stone wall and fastened with the beam reinforcement
Price shall also include properly fixing and anchorage of the block
works with the adjacent concrete elements as approved by the
engineer
m2 160
2.2
Prepare surfaces, apply 13mm thick plaster on new or existing
walls composed of 2 coats of cement sand plaster (rough and
fine finish) over cement splashing coat. The price includes angles
beads, wire mesh on all kinds of joints especially electro-
mechanical. The price should include patching works on
previously plastered walls for electro-mechanical installations.
m2 340
Total for Block and Plaster Works carried to summary
2 of 31
Bill of Quantities (BoQ) Refurbishment of a forensic laboratory in Ramallah ITB-2013-208
No. Description Unit Qty Unit Rate
US$ Total US$
3 Tiling Works
The contractor shall, when pricing the rates of this bill, take into
consideration including and allowing for the costs or expenses of
all requirements stipulated in the preambles, drawings and
technical specification of the tender.
Unit rate shall include all design pattern and cutting, cement
mortars, cement sand filling bellow floor tiles and grouting.
3.1.1
Supply and install non-slip 30X30cm 7mm thick granite porcelain
floor tiles, simlar to model "Coco from TAU CERAMICA" or
equally approved Spanish or Italian tiles; all as per the Engineer's
choice and approval. The price should include the installation of
the tiles at 5mm spacing and to any pattern selected by the
engineer, grouting with anti bacterial epoxy grout. Price shall
include the cement mortar (1:3), sand with cement filling.
m2 330
3.1.2
Supply and install glazed porcelain tiles first grade for wall tiling
Spanish or Italian made and as approved by the Engineer. Tiling
shall be to any pattern and color selected by the Engineer, with
5mm spacing, pointing with water resistant grout like Mapei. Price
shall include surface preparation, installation of the tiles, on new
or existing walls, with approved adhesive material.
m2 30
Total for Tiling Works carried to summary
4 Sealing Works
The contractor shall, when pricing the rates of this bill, take into
consideration including and allowing for the costs or expenses of
all requirements stipulated in the preambles, drawings and
technical specification of the tender.
4.1
Supply and apply three coat of Sika Top Seal 107 or equivalent
on clean surfaces at the wet areas. The price include 5*5cm
angle fillet with smooth sand cement mortar (1:3), applaying of
smooth surface layer of cement- sand screed to recieve the
sealing material.
m2 25
Total for Sealing Works carried to summary
3 of 31
Bill of Quantities (BoQ) Refurbishment of a forensic laboratory in Ramallah ITB-2013-208
No. Description Unit Qty Unit Rate
US$ Total US$
5 Wooden and Carpentry Works
The Contractor shall when pricing the rates of this bill, take into
consideration including and allowing for the cost or expenses of
all requirements stipulated in the preambles, drawings, and
technical specifications.
5.1 Wooden doors
Supply and install the following 45mm thick PLY wooden doors.
Price to include pine woode frames, three door hinges at each
door leaf, 20 cm high stainless steel kick plates from both sides of
the door leafs, door stoppers, door locks, cylinders (Wally or
equally approved), and the accessories as approved by the
Engineer.
Price to include painting of the door leafs and frames by 2 coats
of putty 2 coats of under coat ORANGE as made by APC or
equaly approved,and 3 coats of APC ARAMAT; all as instructed
and approved by the Engineer.
5.1.1D01,clear leaf dimensions 80x210cm. Please refer to drawings
details 34 + 35.No. 9
5.1.2
D02
Dismantled , preserve and re-install the existing wooden doors
as shown on drawing A03 and instructed by the Engineer. Price
shall include, but not limited to, the followings:
1- supply and install pine wooden doors frame 50mm thick and
width equal to the wall thickness. 2- Fixing of the
frames by galvanized steel anchors L75x100mmx40mm width
and 1.5 mm thick ( 4 anchors for each side)
3- Installing new handles, locks and cylinders as made by Wally
or an approved equal.
4- Painting of the new door frames and the dismanteled door
leafs with oil paint including primer, 2 coats of putty, 1 coat of
undercoat and three coats of oil based wooden paint.
No. 8
4 of 31
Bill of Quantities (BoQ) Refurbishment of a forensic laboratory in Ramallah ITB-2013-208
No. Description Unit Qty Unit Rate
US$ Total US$
5.2 Wooden Counters, benches and cabenits
Supply and install laboratory cabinets with the following
specifications:
1- All handles are as made by TIRADOR 2012/14 Length of
handle 96/160 mm, Color is NIROSTA MATT.
2- All hinges are as made by BLOOM
3- All Ply wood used is 17mm BARCELONA made or equivalent
that should be approved by the site engineer.
5.2.1
Supply and install lower laboratory cabinets, as per the detailed
drawings and instructed by the site engineer, price includes
counter with granite tops as made by CAESAR color No. 7100,
Preformed casements, upper and lower steel ends. Refer to
Detail 6 + 7 + 8 + 9 +10 + 11 + 12 +13 + 14 +15 +16+18 +19 +21
+ 22 + 26
mr 25
5.2.2
Supply and install lower laboratory cabinets, as per the detailed
drawings and instructed by the engineer, price includes ready
made Formica top counter c. Refer to Detail 2 + 3 + 4 + 5 + 6 + 9
+ 12 + 13 + 14 + 15 + 16 + 18 + 19 + 20 + 22 + 24 + 25
mr 40
5.2.3Ditto but upper cabinets, 40cm deep, without counter top part.
Refer to Details 3 + 4 + 11 + 21 + 26 + 28mr 20
5.2.4
Ditto but to be installed back to back as a middle counter. Refer
to Details 5 + 6 + 7 + 8 + 9 + 12 + 13 + 17 + 18 + 19+ 20 + 22 +
23 + 24 +25
mr 22
5.2.5 Ditto but covers for electro-mechanical cabinets. m2 4
5.2.6Ditto, but reception counter complete, as shown on drawings and
approved by the Engineer.No. 1
5.2.7
Ditto but for shelving units. The price should include 4*4mm steel
tubes for hanging the shelves from the ceiling. Refer to details 20
+ 22 + 25
mr 10
Total for Wooden and Carpentry Works carried to summary
5 of 31
Bill of Quantities (BoQ) Refurbishment of a forensic laboratory in Ramallah ITB-2013-208
No. Description Unit Qty Unit Rate
US$ Total US$
6 False Ceiling Works
The contractor shall, when pricing the rates of this bill, take into
consideration including and allowing for the costs or expenses of
all requirements stipulated in the preambles, drawings and
technical specification of the tender.
6.1
Supply and install ECOPHONE ADVANTAGE E 15mm thick over
fine line structure 60x60cm false ceiling, price to include structure
and installation using special gloves as instructed and approved
by the site engineer. The Price should include install paper
corner and joints beads on all joints, corners, connections
between walls and boards using putty (GOLD BOND BRAND),
laying one layer of putty over the joints and corners and another
one layer over all gypsum boards, sanding with sand paper and
finishing all as approved by the site engineer. Refer to Details 30
+ 31 + 32
m2 180
6.1.1
For Gypsum False ceiling Supply and install ORBOND water
proofing (GREEN) gypsum board for false ceilings of 12.5 mm
thick gypsum panels with studs at every 40cm in both directions
including decorations, forms, trims with all connections supports ,
fixing, putty sealer , wire mesh and special angles for edge of
boards and all necessary accessories needed for the best
completion of works . The contractor shall provide a shop
drawing for architect approval.
m2 160
6.1.1.2For ORBOND water proofing (GREEN) gypsum Panels12.5 mm
thick less than 50cm widem2 40
Total for False Ceiling Works carried to summary
6 of 31
Bill of Quantities (BoQ) Refurbishment of a forensic laboratory in Ramallah ITB-2013-208
No. Description Unit Qty Unit Rate
US$ Total US$
7 Painting Works
The contractor should allow in his pricing that the engineer may
use as many different colors or combination of colors to meet an
approved color scheme.No hand made color mix is allowed.
The contractor has to prepare a color sample 1.5x1.5m on site for
each color asked by the Engineer
The owner has the right to choose any color of or combination, no
price difference will be measured for any color variation done
All paint works should conform to manufacturer's instructions
regarding number of coats, rate of application or drying time
Painting to be carried out on new or old surfaces. Price shall
include surface preparation , pealing off old defective paint,
batching, ..etc
On walls & ceiling
7.1
Supply all kinds of raw material and apply paint for internal walls,
stairs walls, landings, and wherever needed or instructed by the
site engineer, the price should include preparing surface, clean,
remove dust and foreign matter, sanding with sand paper,
checking the walls with Calcimo X and putty, applying one coat of
APC FILL , laying two coats of putty (GOLD BOND brand or an
approved equivalent), applying one coat of SUPER BOND ROLL
and applying three coats of ARACRYL 2000 all as instructed and
approved by the site engineer
m2 350
7.2
Supply all kinds of raw material and apply paint for gypsum
boards up to 3.6m high, and wherever needed or instructed by
the site engineer, the price should include preparing surface,
clean, remove dust and foreign matter, sanding it well with sand
paper, checking the walls with putty, laying two coats of putty
(GOLD BOND brand or an approved equivalent), applying one
coat of SUPER BOND ROLL and applying three coats of
ARACRYL 2000 all as instructed and approved by the site
engineer
m2 190
Total for Painting Works carried to summary
7 of 31
Bill of Quantities (BoQ) Refurbishment of a forensic laboratory in Ramallah ITB-2013-208
Bill No. Description Total US$
1 Total for Demolishing works
2 Total for Block and Plaster works
3 Total for Tiling works
4 Total for Sealing Works
5 Total for Wooden and Carpentry works
6 Total for False Ceiling works
7 Total for Painting works
Total for Civil Works carried to grand summary
Civil Works BoQ Summary
8 of 31
Bill of Quantities (BoQ) Refurbishment of a forensic laboratory in Ramallah ITB-2013-208
Item
NoDescription Unit QTY
Unit Rate
US$ Total US$
1 DRAINAGE WORKS Connecting the new drainage pipes to the existing
pipes includes all the workmanship and fittings (pipes
will be paid for as per the corresponding bill item), as
well as, any alteration of the drainage pipe passage
through the demolished walls. Contractor should allow
in his unit prices for pipes all such works and fittings.
The smooth flow and continuity of the drainage system
in the building from the upper floors through the lower
floors and down to the basement is the contractor's
responsibility. Hence, contractor should inspect the site
before pricing the drainage system.
1.1
Supply and install (S&I) 4" PVC "Redi " floor drain
(siphon), or approved equal, complete with floor
collector and 110 mm diameter vertical extension from
Huliot or equally apparoved to receive the 2" and 11/2"
diameter PVC under floor drain pipes, and includes
heavy duty stainless steel rim and cover 15x15 cm ,
1.1.1 4" diameter NO 8
1.2 Ditto but clean out NO 4
1.3 Floor trap 2"/2" and 4"/2" NO 12
1.4
S&I UPVC pipe Royal SN6, or approved equal, for
sewage, rain water and air condition drainage. The price
includes also all fittings, elbows, nipples, digging, coring,
plastering and connecting the pipes of the new fixtures
to the existing drainage system.
1.4.1 4" diameter LM 45
1.4.2 2" diameter LM 145
Total Drainage Works
9 of 31
Bill of Quantities (BoQ) Refurbishment of a forensic laboratory in Ramallah ITB-2013-208
Item
NoDescription Unit QTY
Unit Rate
US$ Total US$
2 COLD AND HOT WATER The price for connecting the new cold water pipes to
(taping-in) the existing pipes in the various floors and
basement shall cover for all the needed fittings deemed
necessary to do the job. Also, the continuity and smooth
flow of the water in the building is the contractor's
responsibility.
2.1
Supply and install water collector type Giacomini, NTM,
or equally approved with branch valve for each exit,
suspended in void above false ceiling. Price includes
shut of valve of the same make, air vent Calcify, end-
cap piece,collecter brackets, as a complete job
2.1.1 12 eyes 1" NO 1
2.1.2 10 eyes 1" NO 1
2.1.3 8 eyes -3/4" NO 1
2.1.4 4 eyes -3/4" NO 1
2.2
Supply and install galvanized steel oven painted cabinet
for the collectors with hinged cover and brackets,
designated for radiators meant at low level.
NO 2
2.3
Supply and install electrical water heater as made by
Original/Palestine, or equally approved, of high pressure
quality plus enameled internal paint with all required
fixation, operation and safety to be installed in void or
hung on wall. Price includes shut off valve Sounders,
safety valve 1" type (Califi) and connected to a drain
pipe down to the floor trap to prevent splashing when
activated, air vents (Califi), connection to power socket
as a complete job
2.3.1 80 L capacity NO 2
2.3.2 40L capacity NO 1
2.4
Supply and install thermo pipes type pexgol,pexline with
sleeve, price includes wall elbow, and connection to
collectors and water supply under tiles or suspended to
ceiling, under tiles pipes shall be covered with 5 cm
mortar concrete and wall/ceiling-hung pipes shall be
restrained with hilti holders at 1 meter intervals.
2.4.1 32/50 LM 25
2.4.2 25/32 LM 70
2.4.3 20/25 LM 50
2.4.4 16/25 LM 100
Total Cold & Hot water system Items
10 of 31
Bill of Quantities (BoQ) Refurbishment of a forensic laboratory in Ramallah ITB-2013-208
Item
NoDescription Unit QTY
Unit Rate
US$ Total US$
3 SANITARY FIXTURES
3.1
Supply and install the following sanitary fixtures with the
required original fixing accessories and materials. The
price of the sanitary fixture shall neither include the
supply and installation of the corresponding 2" PVC
pipes from the sanitary fixture to the floor drain
connection box or sewage pipes, nor shall it include the
price of the corresponding 16/25 mm pex pipes from
collectors to each sanitary fixture. The waste water and
supply water pipes from/to the sanitary fixture shall be
measured and paid for as per the corresponding unit
rate and conditions of the item under question.
3.1.1
S&I and install wall hung W.C bowl class A, Pargamon
color .Jika made ref.21370 or equally approved with the
necessary original connections, including Schwab made
concealed flushing system ref. 8118502 9/6 L for wall or
equally approved, with steel reinforcing legs. Price
includes cover, seat, hardware from same make,
connection to cold water and drainage, as well as,
casting reinforced concrete B 250 20cm thick, Ø
8mmx20x20 cm around the tank.
NO 3
3.1.2
Supply and install wash basin porcelain Pargamon
color type Jika Ref 14312 or equally approved, with half
leg of the same make, complete with chrome plated
siphon of CE quality make.
NO 3
3.1.3
Supply and install electronic water mixer hot and cold
for the wash basin 220 volt type Ideal Standard or
approved equal with all the necessary transformers
and valves flexible hose 1/2-3/8 Neil angle valves, or
equally approved.
NO 3
3.1.4
Supply and install porcelain Pargamon color class A
shower tray Creavit make or equally approved, size
90x90 cm with Huliot siphon.
NO 1
3.1.5
Supply and install inside wall chrome plated mixer for
the shower Ideal Standard, or equally approved,
including shower stand, hose and handset.
NO 1
3.1.6
Supply and install stain less steel kitchen sink type
ROCA size 60x40 complete with original siphon and
1/2"-3/8" valve Neil and connection to cold & hot water
as a complete job
NO 1
3.1.7
Supply and install electronic water mixer hot and cold
for the sink 220 volt type ideal standard or approved
equal with all the necessary transformers and valves
flexible hose 1/2-3/8 Neil angle valves
NO 1
3.2
Supply and install robust heat & chemical resistance
sink, Poly-propylene sinks for side working benches, A
600x400x200H mm. polypropylene sink installed in the
center of the washing stand working surface including
drain valve and siphon valve and all required
connections as made by POLYSINK, UK, Cat. No. PS-
0543 S or an approved eq.
NO 7
11 of 31
Bill of Quantities (BoQ) Refurbishment of a forensic laboratory in Ramallah ITB-2013-208
Item
NoDescription Unit QTY
Unit Rate
US$ Total US$
3.3
Supply and install bench mounted one hole mixer with
swivel spout, ceramic head works and
Detachable Nozzle as made by BROEN, Denmark, Cat.
No. 15 274.009 or an approved eq.
NO 7
3.4
Supply and install combined Body and eye shower, wall
mounted in brass with chemical resistant BROEN Poly-
coat with self-draining shower head. Water inlet at the
top or bottom. Eye shower has built-in FLOWFIX (6.7
g/pm). Eye shower, combined wall mounted with two
heads in brass with chemical resistant BROEN Poly-
coat. Water is regulated with a built-in FLOWFIX (6.7
g/pm).Body shower 3/4” NPT male inlet in brass with
chemical resistant BROEN Poly-coat Complete unit. as
made by BROEN, Denmark, Cat No. 17 455.909 or an
approved equal.
NO 3
3.5 Supply and install electronic hand dryer 2500 watt
stainless steel body type Vortice or equally approved NO 3
Total Sanitary Fixtures
12 of 31
Bill of Quantities (BoQ) Refurbishment of a forensic laboratory in Ramallah ITB-2013-208
Item
NoDescription Unit QTY
Unit Rate
US$ Total US$
4 VENTILATION SYSTEM AND FIRE FIGHTING
4.1
Supply and install exhaust fans type S&P, Vortice or
equally approved with all fixing cassowaries in the
toilets and rooms, including coring with coring
machine, and connecting to duct or PVC pipes for small
fans. All galvanized duct, distribution boxes, PVC pipes
and conduits, flexible ducts, grills, and what ever
deemed necessary for the completion of the exhaust
mechanism job should be included in the fan price.
4.2
Silent mixed flow fans with sound absorbent insulation
price include coring in the wall by coring machine,
installing exhaust grill with back draft shutter connection
the fan with the exhaust grill with duct and flexible joint
at both sides of the fan galvanized distributing box with
all the opening and adapters ,flexible ducts to be
connected to the circular exhaust diffusers, fresh air
grill with filter 80-85 % efficiency and volume damper
installed on the galvanized duct ,fresh air rain water
grill , as per the drawings , as one complete job
4.2.1 800m3/h @10 mm NO 2
4.2.2 600 M3/H @10 mm NO 4
4.2.3 450 M3/H @10 mm NO 4
4.2.4 120 M3/H @4 mm with timer NO 5
4.2.5
Ditto as above specification 4.1-4.2 but for the
basement floor water tank room 800 m3/h @15 mm
including all the rain water grill fresh air grill with filter 80-
85 %
NO 1
4.3
Supply and install galvanized sheet metal duct 0.7 mm
as per SMACNA standard, including all the bends,
elbows, hangers, flexible canvas connectors, corig in
the walls, wooden sleeves,etc. for the exhaust fans in
the basement floor
SQM 65
4.4 Fume Hoods:
4.4.1
Supply and Install the following Fume Hood:
Dimensions: Width: 1800mm x Depth: 750 mm Height:
2620 mm.Structure:
18 mm laminated UPVC or Poly-propylene with 63 mm-
thick edges.Working surface:
Ceramic Tiles. with a front 30 mm elevated threshold
and tapering edge which provides a 10 mm elevation
above the worktop, including preparing bores for valves
and sink and water faucet* etc. the unit is equipped by
4 power sockets type GEWISS and cut-off switch to
operate the blower and the lights.
13 of 31
Bill of Quantities (BoQ) Refurbishment of a forensic laboratory in Ramallah ITB-2013-208
Item
NoDescription Unit QTY
Unit Rate
US$ Total US$
Back of the hood:
There will be a double back, allowing routing and
regulating the air flow from the upper and the lower
parts of the hood by means of upper and lower flues,
the hood back is made of 6 mm-thick TRESPA, a
polypropylene lattice will be mounted at the outlet of the
air suction inlet to prevent foreign bodies from entering
the blower.
Status indication:
An electrical mechanism for indicating the operation
status of the air suction blower by means of red lamp
and green lamp mounted on the front panel of the hood
Vertical window:
Made of 6 mm-thick safety glass and stainless-steel
frame slides on polypropylene rails and balanced by
means of ball bearing wheels, balancing bar and
counter weight.
Electrical accessories and wiring:
A Thermo magnet drive for driving the blower motor, 2
single phase power sockets, a lighting switch, a safety
fuse and control lamp. All mounted on the hood’s front
panel.
A 2 x 20 watts fluorescent lamps will be mounted on the
upper cover outside hood, with a sealed transparent
window to ensure that no gases enters the lamp area.
A CL terminal box and marked terminal connections to
the mains and to the blower will be mounted on the
hidden upper part of the hood.
Suction blower:
Rigid PVC, UV resistance centrifugal polypropylene
booster made by COLASIT, Swiss made.
Motor:
3-phase, Completely tight, TEFC, F isolation grade,
1400 r/pm. ½ hp. Manufactured by SIEMENS, Germany.
Direct drive, model RN-250 protected by a safety switch.
In-Line Carbon Filter:
An Integrated sliding drawer containing micro-
coalescing carbon filter with capacity to fit the fume
hoods capacity.Manufacturer: P.V. Plast, Laboratory Equipment &
Furniture, Plastic Engineering or an approved
equivalent
No. 1
4.4.2 Ditto but 1200mm wide No. 2
14 of 31
Bill of Quantities (BoQ) Refurbishment of a forensic laboratory in Ramallah ITB-2013-208
Item
NoDescription Unit QTY
Unit Rate
US$ Total US$
4.5
Supply and install Fully Automatic Duplex Medical Oil-
less Compressed Air System, Consists of two Base
Mount Oil-less Stationary 2 stage Reciprocating Piston
Compressors, each of single phase, with free air
delivery of 205 L/min minimum, with a pressure output
up to 6 bar, both connected to 100 liter medical grade
horizontal receiver tank, made by hot galvanized steel.
System includes all mechanical, electrical fittings
pressure switches, orifices, valves, gauges, shock-
absorbers, and all required components to start up and
to shut down automatically and alternatively by means
of electric control panel with all protection modes and
functions. System also includes an in-line refrigerating
Air Dryer with minimum capacity of 1000 LPM and a
medical grade set of purification filters with by-pass. as
made by ASOULINE COMPRESSORS, Cat. No.: SV-
205X2PlusD or an approved eq.
NO 1
4.5 Supply and install 6 kg fire Extinguisher FM 200 NO 11
Total Ventilation and Fire Fighting System
5 AIR CONDITIONING WORKS
5.1
Supply and install Inverter high wall split unit air
condition type Tadiran, or equal approved gas 410,
price includes electrical wiring, copper piping with
insulation and PVC band between the outdoor unit and
the indoor unit drain pipe to the nearest drain point, and
water proof on-off switch on the external unit,
galvanized steel holder/stand ,opening in walls and
slabs by coring machine for any wall type and thickness
,closing holes with sika sealant, gas and oil
charging.NOMINAL CAPACITY
5.1.1 24000BTU/H NO 2
5.1.2 18000 BTU/H NO 7
5.1.3 12000BTU/H NO 3
5.1.4 9000 BTU/H NO 2
5.2
Dismantling the existing air conditions in the offices and
reinstall and operate them in the required locations as
per the owner's request, including all electrical works,
pipes and hangers. The contractor is responsible for
any damage that might be inflicted on the units during
the relocation process.
NO 4
Total Air Conditioning Works
15 of 31
Bill of Quantities (BoQ) Refurbishment of a forensic laboratory in Ramallah ITB-2013-208
Bill No. Description Total US$
1 Total Drainage Works
2 Total Cold & Hot water system Items
3 Total Sanitary Fixtures
4 Total Ventilation and Fire Fighting System
5 Total Air Conditioning Works
Total Mechanical Works carried to Grand
Summary
Mechanical Works BoQ Summary
16 of 31
Bill of Quantities (BoQ) Refurbishment of a forensic laboratory in Ramallah ITB-2013-208
Item Description Unit Qty Unit Rate
US$ Total US$
1 Electrical and Communication Works
Preamble: The contractor shall, when pricing the rates of the
following electrical bills take into consideration including and
allow for the cost expenses of all requirements stipulated in the
preambles, drawings and technical specifications of the tender.All supplied materials should be class A , new , not used and
Free From any Defects, Having the Supervisor approval
Certificate .
The contractor's total price for works shall include for the supply,
execution, completion and testing of the whole of electrical
installation works and related systems in accordance with the
drawings, bill of quantities and specifications.
the rates includes connection to existing system were applicable
and or adjustment of non removed or cancelled network to allow
for new networks or system .
The contractor shall coordinate his works with the decoration
works, furniture, changes in the positioning of ceiling light
fixtures due to partitioning changes and any other changes
which require design changes on the tender drawings.The contractor must consider all these changes in the shop
drawings which must be submitted and approved before
commencement of works.Plates, labels and tags for the identification of plant, equipment,
cables, switches ,sockets and a like.the unit rate including for forming or cutting holes, chases,
channels etc. in reinforced concrete structures and block works the unit rate including for Jointing, saddles, clamps, brackets,
hangers and providing steel pipes sleeves with plates.
All electrical and low voltage conduits for all different items in the
main B.O.Q. installed above false ceiling level must be colored,
fire proof and first class taken quality and following the PCP
standard for all main and sub main feeders circuits*etc.
The contractor must consider keeping the system running where
needed during the whole construction period.
The contractor's rate must include the supply and install internal
sea sand plastering for the electrical conduits on wall .
composed of two coats base coat ,finish coat . The rate includes
all necessary patching works ,expanded metal latch mesh ,
plastering layers must be applied to meet plastering thickness
The contractor shall submit all samples needed for all electrical
and low voltage points, fittings , accessories and fixtures and
following the PCP standard and to take the approval from the
supervision engineer before starting works.
The contractor shall submit a time schedule for all the works
showing start and end dates for each item in B.O.Q..
the contractor should have his electrical engineer available in a
daily bases and on call to arrange with the Consultant
representative engineer on site and for all written
communications and works
All electrical conduits under tiles, floor, wall should be protected
by cement mortar or concrete layer and all electrical excavation
works should be removed from site as specified in the technical
specification and drawings.
17 of 31
Bill of Quantities (BoQ) Refurbishment of a forensic laboratory in Ramallah ITB-2013-208
Item Description Unit Qty Unit Rate
US$ Total US$
Making holes by hilti for all holes size where required including
all necessary water proofing material ( Sikaflex).for any kind of
electrical and low voltages works.The contractor's rate must include all measures to serve the
smooth running of existing system and network through out the
renovation works without any interruptions.The above mentioned shop drawings, electrical switchboards
shop drawings, as built drawings and all other required detailed
drawings are to be included in the rates for no additional cost.
Access doors opening in false ceilings or gypsum board are
included in the unit rate of installing of any kind of lighting
fixtures and all different electrical, low voltage fixtures*etc.
1 Electrical Distribution Boards:
Supply install , connect and test the electrical switchboard to
site including all associated materials and labor, as described in
the technical specifications. Cabinets with no access from the
rear , made up of transparent polycarbonate cells, Galvanized
2mm sheet metal cabinets with 25% surplus space. Main supply
lines enter from bottom , top or side, while out going lines exit the
switchboard , from both its bottom and top only. Price to
include all structural elements required in order to install the
switchboard including all bus bars , terminals , wiring , bolts ,
clamps, master keys for all different panels doors, etc. and for
the equipments as per dwg specification.
1.1 GMDB-Control Panel
1.1.1
Adding ,connect and test inside existing GMDB The main
modeled case circuit breaker (MCCB) (3X100) A . with standing
36KA cutout and short circuit current.
No. 1
1.2 GMDBUPS -Control Panel
1.2.1
Adding ,connect and test inside existing GMDBUPS MCB 3
x40A rating 400V. Capable of switch-standing 15KA cutout and
short circuit current.
No. 1
1.3 SMDB5 /DBUPS L.S. 1
1.4 DB1 L.S. 1
1.5 DB2 L.S. 1
1.6 DB3 L.S. 1
1.7 DB4 L.S. 1
1.8 DB5 L.S. 1
1.9 DB6 L.S. 1
1.10 DBREC L.S. 1
Total of Electrical Distribution Boards Carried to Summary
Sheet
18 of 31
Bill of Quantities (BoQ) Refurbishment of a forensic laboratory in Ramallah ITB-2013-208
Item Description Unit Qty Unit Rate
US$ Total US$
2 Installation in the Building Points
The following items are supply, installation of same, connection,
wiring, commissioning and all other details, as specified in the
technical specification and drawings.
2.1
Wall, ceiling or false ceiling mounted lighting point normal,
waterproof, emergency or exit (Price includes 16mm diameter
conduit hadash plats type or Approved equivalent, 3x1.5 mm2
cross section cables cabels itac type or Approved equivalent ,
price includes all switches, push button legrand type or approved
equivalent, ceiling box and phase line for emergency lighting
point , and leading from the switch panel to the point including
any needed boxes or accessories).
No. 120
2.2
Standard 1 ph socket outlet point normal (Price includes 16mm
dia. conduits Nacy , hadash plats type or Approved equivalent,
3x2.5mm2 cables intact , synenergy type or Approved
equivalent , with 16A socket Legrand Type Arteor Model with
Brilliant White Finish Color or Approved equivalent, Boxes,
Supports & Plates and leading from the switch panel to the point
, including all accessories).
No. 35
2.3 Ditto but waterproof No. 20
2.4
Standard 1 ph Double socket outlet point normal (Price
includes 16mm dia. conduits Nacy , hadash plast type or
Approved equivalent, 3x2.5mm2cables itac , synenergy type or
Approved equivalent , with 16A socket Legrand Type Arteor
Model with Brilliant White Finish Color or Approved equivalent,
Boxes, Supports & Plates and leading from the switch panel to
the point , including all accessories).
No. 40
2.5 Ditto but waterproof No. 2
2.6
16A Industrial three phase wall-mounted socket outlet point
(Price includes sockets NISKO type N516.110 with lockable
cover, IP 65 , three and single phase Legrand type or Approved
equivalent, 5x2.5mm2 N2XY cable or Approved equivalent,
23mm diameter conduits, and all accessories leading from
distribution board to the point).
No. 6
2.7
Emergency shut off push button kit outlet connection point, price
includes 16 mm2 conduit, 3x2.5mm2 N2XY or Approved
equivalent cable , push button Legrand Type Arteor Model with
Brilliant White Finish Color or Approved equivalent and all
accessories).
No. 9
2.8
Single phase electrical connection of Split Unit (Price includes
3x2.5mm2 N2XY or Approved equivalent cross section cables,
A/C socket Legrand Type Arteor Model with Brilliant White
Finish Color or Approved equivalent, flexible heat conduits,
cable glands, connection boxes, adaptors and all connections
and accessories from relevant panel to machine .
No. 17
2.9
Standard 1 ph socket UPS outlet point normal (Price includes
16mm dia. conduits Nacy , hadash plast type or Approved
equivalent, 3x2.5mm2cables itac , synenergy type or Approved
equivalent , with 16A socket Legrand Type Arteor Model with
Brilliant White Finish Color or Approved equivalent, Boxes,
Supports & Plates and leading from the switch panel to the point
, including all accessories).
No. 15
2.10 Ditto but Double UPS No. 40
19 of 31
Bill of Quantities (BoQ) Refurbishment of a forensic laboratory in Ramallah ITB-2013-208
Item Description Unit Qty Unit Rate
US$ Total US$
2.11
Double pole On-off switch with indication lamp ,including Price
includes 16mm dia. conduit, 3x2.5mm2 N2XY cross section
cable or Approved equivalent, with ON-OFF switch Legrand
Type Arteor Model with Brilliant White Finish Color or Approved
equivalent. Rates also includes Boxes, Supports & Plates and
leading from the switch panel to the point , including all
accessories).
No. 2
2.12
1 ph power connection outlet point for infra red for sink (Price
includes 16mm dia. conduits Nacy , hadash plast type or
Approved equivalent, 3x1.5mm2 cables itac , synenergy type
or Approved equivalent and leading from the switch panel to
the point , including all accessories).
No. 10
2.13
Telephone outlet connection point wall or table mounted (The
price includes 16mm2 conduits with 4 pairs computer cable
shielded type CAT6A and leading from computer HUB to the
points as well an outlet with Easily terminated 10G 6A shielded
RJ-45 style modular outlets/jacks. Meets or exceed all Cat6A
channels requirements via an enhanced design , including alien
crosstalk parameters. and / or 3M Modular CAT6A type or
Approved equivalent including Boxes, Supports & Plates and all
accessories).
No. 35
2.14
T.V. antenna connection point (The price includes 16mm
diameter conduits Nacy , hadash plast type or Approved
equivalent, with American common scope coaxial cable RG6
75 ohms,, as well an outlet with a plastic socket Legrand Type
Arteor Model with Brilliant White Finish Color or Approved
equivalent, Including Boxes, Supports & Plates and leading from
point to the connection box on roof.
No. 2
2.15
Satellite antenna connection point (The price includes 16mm
diameter conduits Nacy , hadash plast type or Approved
equivalent, with American common scope coaxial cable RG6 75
ohms, leading from connection box to the points as well an outlet
with a plastic socket Legrand Type Arteor Model with Brilliant
White Finish Color or Approved equivalent , Including Boxes,
Supports & Plates and leading from point to the connection box
on roof.
No. 2
2.16
CCTV connection point (Each outlet for indoor, out door camera
, monitor, shall be measured as one point. Price includes
16mm2 conduits Nacy , hadash plast type or Approved
equivalent, and CAT6A computer cable teldor type or Approved
equivalent and leading from point to the CCTV section in the
communication cabinet with all accessories).
No. 5
2.17
Fire detection system connection point, (Each outlet for smoke ,
heat detectors, break glass , indoor or outdoor alarm horn, shall
be measured as one point. Price includes 16mm2 conduits and
cables 4x0.8 mm2 ITAC type or Approved equivalent, and
leading from point to the fire detection section in the
communication cabinet or to the nearest point and all
accessories).
No. 50
20 of 31
Bill of Quantities (BoQ) Refurbishment of a forensic laboratory in Ramallah ITB-2013-208
Item Description Unit Qty Unit Rate
US$ Total US$
2.18
Computer outlet connection point wall or table mounted (The
price includes 16mm2 conduits with 4 pairs computer cable
shielded type CAT6A and leading from computer HUB to the
points as well an outlet with Easily terminated 10G 6A shielded
RJ-45 style modular outlets/jacks. Meets or exceed all Cat6A
channels requirements via an enhanced design , including alien
crosstalk parameters. and / or 3M Modular CAT6A type or
Approved equivalent including Boxes, Supports & Plates and all
accessories).
No. 62
2.19
access outlet connection point wall or table mounted (The price
includes 16mm2 conduits with 4 pairs computer cable shielded
type CAT6A and leading from the Access control panel to the
points t including Boxes, Supports & Plates and all accessories).
No. 45
Total of Installation Works Carried to Summary
3 Lighting Fixtures and Accessories Note: work for lighting fixtures is to include supply of the fixtures
specified, installation of same connection, wiring,
commissioning, lamps OSRAM type, tubes, starters louvers,
connections, suspension, clamps and all other accessories
necessary to provide a complete fitting with all terminals and
rates also includes all L,Z and omega profiles if needed , great
opening for lighting fixtures in gypsum board and all other details
, as specified in the technical specifications and drawings and as
approved by the engineer.
3.1
Type (A)4×18W recessed fluorescent lighting fixture with
electronic ballast and double prismatic polycarbonate diffuser
triphosphore lamps, IP44 Gaa'sh type or Approved equivalent.
Unit 53
3.2Type (AE) Ditto but with emergency battery charger 3 hours
duration Gaa'sh type or Approved equivalent.Unit 24
3.3
Type (B) 2×26w compact fluorescent recessed down light
polycarbonate body and high purity metalized aluminum
decorative reflector. IP44 Gaa'sh or Approved equivalent.
Unit 16
3.4Type (BE) Ditto but with emergency battery charger 3 hours
duration or Approved equivalent.Unit 8
3.5
Type (C) 2*18 w compact fluorescent lamp round bulkhead with
opal glass diffuser die cast aluminum body IP65. GAASH or
Approved equivalent .
Unit 4
3.6Type (CE) Ditto but with emergency battery charger 3 hours
duration Gaa'sh type or Approved equivalent.Unit 1
3.7Type (D) 1x8w emergency exit sign with 3 hours maintained
duration GAASH 580121 type or Approved equivalent.Unit 2
3.8Type (F) 1x8w emergency exit sign with 3 hours duration
DOUBLE SIDED GAASH 580501 or Approved equivalent.Unit 2
3.9Type (G) 60W wall mounted light fixture in use sign GAASH
type or Approved equivalentUnit 2
3.10
Type (G) 2×36w surfaced fluorescent lighting with electronic
ballast and opal diffuser IP 65, GAASH type or Approved
equivalent
Unit 2
Total of Lighting Fixtures and Accessories Carried to
Summary
21 of 31
Bill of Quantities (BoQ) Refurbishment of a forensic laboratory in Ramallah ITB-2013-208
Item Description Unit Qty Unit Rate
US$ Total US$
4 Cables & Conductors / Leads Supply, install, test and connect the following electrical cables ,
including insertion into conduit or attachment to structural
elements or laying in ductwork, including all associated
materials, insulation materials, unions, labeling and connection
of cable at both ends and all accessories.
4.1 3x35+16 sq.mm cross section XLPE/PVC/PVC cable. M.L. 30
4.2 5x16 sq.mm cross section N2XY cable. M.L. 30
4.3 5x6 sq.mm cross section N2XY cable. M.L. 170
4.4 3x10 sq.mm cross section N2XY cable. M.L. 170
4.5 3x2.5 sq.mm cross section N2XY cable. M.L 100
4.6 3x1.5 sq.mm cross section N2XY cable. M.L 100
4.7 5x2.5 sq.mm cross section N2XY cable. M.L 100
4.8 5x1.5 sq.mm cross section N2XY cable. M.L 100
4.9 7x1.5 sq.mm cross section N2XY cable. M.L 50
4.10 Copper conductor with PVC insulation cross section 35sq.mm. M.L 150
4.11 Copper conductor with PVC insulation cross section 16sq.mm. M.L 300
Total of Cables & Conductors Works Carried to Summary
Sheet
5 Cable Conduit & Ducts
Supply, install, test and connect the following standard conduits
or color fire proof conduits, processed over or under plaster or
over false ceiling, including junction boxes, unios, connectors,
etc* including galvanized draw strings, ready for use "Pony last"
type or Approved equivalent and all accessories).
5.175 mm diameter heavy, bendable type NACY, Had ash Plast or
Approved equivalent.M.L 50
5.242mm diameter heavy, bendable type NACY, Had ash Plast or
Approved equivalent.M.L 50
5.329mm diameter heavy, bendable type NACY, Had ash Plast or
Approved equivalent.M.L 200
5.423mm diameter heavy, bendable type Had ash Plast or
Approved equivalent.M.L 150
5.516mm diameter heavy, bendable type Had ash Plast or
Approved equivalent.M.L 200
Total of Cable Conduit & Ducts Carried to Summary
22 of 31
Bill of Quantities (BoQ) Refurbishment of a forensic laboratory in Ramallah ITB-2013-208
Item Description Unit Qty Unit Rate
US$ Total US$
6 Telephone Cable and low voltage box
Supply, install, test and connect metallic low voltage box for
Telephone, TV , CCTV systems .The size of the low voltage
shall be the same height and depth of the nearest electrical
board with 45cm width .6.1 SMLV5 L.S. 1
6.2 LVREC L.S. 1
6.3 Lvbox on roof L.S. 1
6.4
Supply, install, test and connect Telephone cable 1NO. 10pairs
Superior from main low voltage box to the floor low voltage
boxes price includes terminal blocks, corona and all
accessories.
M.L 100
6.5
Supply, install, test and connect Fiber type: Single mode ,
outdoor , optimized for 1310nm , ITU-TG.652. to server room
through electrical shaft with PVC insulation cross section 23mm.
labeling and Termination: SC connectors from each end on
patch panel. and all accessories)
M.L 100
Total of Telephone Cable and low voltage box Carried to
Summary Sheet
23 of 31
Bill of Quantities (BoQ) Refurbishment of a forensic laboratory in Ramallah ITB-2013-208
Item Description Unit Qty Unit Rate
US$ Total US$
7 Electrical Appliance & Motor connections & Special Works
The following items are supply, installation of same, connection,
wiring, and all other details and all electrical conduits should be
protected by cement mortar or concrete layer as specified in the
technical specification and drawings..
7.1
Electrical connection of Single phase Extract Fan (the Price
includes 16mm diameter conduit, 3x1.5mm2 cables ITAC type
or Approved equivalent, Isolator switch 10A cable glands,
connection boxes w.p, labeling, adaptors and all accessories
and leading from Relevant panel to machine to the satisfactory
of the engineer.
No. 4
7.2
Electrical connection of Single phase Extract Fan (the Price
includes 16mm diameter flexible heat conduits, 3x1.5mm2
cables ITAC type or equivalent, Isolator switch 10A cable
glands, connection boxes w.p, labeling, adaptors and all
accessories and leading from lighting point to extract fan.
No. 10
Total of Electrical Appliance Works Carried to Summary
Sheet
8 Grounding Works
8.1
Grounding Earthling loop including cold and hot water piping,
fuel piping, air conditioning piping, ducts, all false ceiling systems
in all floors and whole project elevator rails, main and sub main
distribution boards, metallic sewage , supply trunks metallic
cable ducts, Generator, EPABX and any other metallic service in
the building. Rate to include copper conductors as shown on
drawings, main and secondary potential equalizing bus-bar,
protective conduit, junction box, complete with all necessary
accessories that all for all project floors and all mechanical and
metalic bodies at roof floors.
L.S. 1
Total of Grounding Works Carried to Summary Sheet
9 Access & Integrated Security System Type
Supply , install and connect the following Access Security
System infinias IP-based Access Control or approved
equivalent including outlet boxes , cover plates and all
necessary connections, complete with operation, testing and
commissioning works as shown on the drawings and as per
specifications.
9.1 Intelligent Controller or Approved equivalent. No. 1
9.2Ethernet daughter board for TCP/IP communication or Approved
equivalent.No. 1
9.3power / communication daisy chain harness or Approved
equivalent.No. 1
9.4Closer (Wall-mount) Capacity: to handle 14 door . Power supply
and battery included 7*PRO22 R2 or Approved equivalent.No. 1
9.5PRO-2200 Dual Reader Module ( OP30 )
Mini-Mullion Mullion or Approved equivalent.No. 13
9.6 HID Proximity compatible reader wall or Approved equivalent. No. 13
9.7 Strike electric lock S4 No. 13
9.8 Bush button door release No. 13
9.9WIN-PAK SE Access Control Software Server , 1 User win pak
without H.W server or Approved equivalent.No. 1
Total of Access & Integrated Security System Works Carried
to Summary
24 of 31
Bill of Quantities (BoQ) Refurbishment of a forensic laboratory in Ramallah ITB-2013-208
Item Description Unit Qty Unit Rate
US$ Total US$
10 Fire Alarm System
Supply install and connect fire alarm addressable system
BOSCH or Approved equivalent including of the equipment
specified, installation of same connection, wiring commissioning
and all of the details as specified in the technical specifications
and drawing with complete operation capacity 125 detectors.
10.1Fire alarm control panel, 1 loop, expandable, 125 points, and
230V, gray.No. 1
10.2 Analogue addressable photoelectric smoke detector.V-PS No. 30
10.3 Analogue addressable heat detector.V-HRD No. 9
10.4 Analogue manual call break glass station.GSA-M270 No. 5
10.5 Indoor fire siren.G1RF-P No. 5
10.6 Fire alarm outdoor siren with strobe.757-7A-T No. 1
10.7 Automatic telephone dialerDL-125C No. 1
Total of Fire Alarm System Works Carried to Summary Sheet
11 CCTV System
Supply , install and connect the following IP Digital CCTV
System including outlet boxes , cover plates, and all
necessary connections , complete with operation, testing and
commissioning works as shown on the drawings and as per
specifications. The CCTV System shall include the following.
Lens: View: 66° horizontal, F2.0VideoResolution: SVGA (800x600) to 120x90Compression: H.264 (MPEG-4 Part 10/AVC), Motion JPEGFrame rate: 30 fps in all resolutionsMulti-stream supportedVideo motion detectionSecurity: Password protection, IP address filtering, digest
authentication, HTTPS encryption, IEEE 802.1X network access
control, user access logProtocols: IPv4/v6, HTTP, HTTPS, QoS Layer 3 Diffuser, FTP,
SMTP, SNMPv1/v2c/v3(MIB-II), DNS, NTP, RTSP, RTP, TCP,
UDP, IGMP, RTCP, ICMP, DHCP, ARPCasing: Suitable indoor casing includedPower: Power over Ethernet (PoE) IEEE 802.3afOperating conditions: 0°C to 50°CDVR compatibilityTested and demonstrated full compatibility with ZoneMinder
DVR under Linux OS (http://www.zoneminder.com/)Please see the Hardware compatibility list:
http://www.zoneminder.com/wiki/index.php/Hardware_Compatibil
ity_ListExample model: AXIS M3011 or approved equivalent
http://www.axis.com/products/cam_m3011/
Total of CCTV System Works Carried to Summary Sheet
11.1 No. 4
25 of 31
Bill of Quantities (BoQ) Refurbishment of a forensic laboratory in Ramallah ITB-2013-208
Item Description Unit Qty Unit Rate
US$ Total US$
12 Computer Network
12.1
Supply, install and connect , testing and commissioning switch
and patch panel and all necessary accessories with complete
operation. As listed below
12.1 Patch Panel:
Unloaded Patch panel for Cat6A systems
Provides Cat6A performance in a reliable and flexible modular
solution.
Compact design for 1U 48 Port high density application.
Switch:
48 x 10/100/1000 Ethernet LAN ports with automatic speed
detection
PoE+ 802.1at on all ports, minimum 380W available POE budget
MDI/MDIX sensing: Automatic
Form factor: 1U
Switching bandwidth: 170 Gbit/s
Features:
Layer 2 switching
IEEE 802.1Q
Layer 3 routing
IEEE 802.1X with a RADIUS server, multiple IEEE 802.1X users
per port;1
MAC-based port security with RADIUS server
Source-port filtering;
IGMPv3, LLDP, QoS
IPv4, IPv6
DHCP relay
ACL
Manageable: HTTP, SSH, SNMP
Firmware: upgradeable
Rack mount kit: Included
Example model: HP E2910-48G-POE+ J97 29A + POE Power
http://h18000.www1.hp.com/products/quickspecs/13280_na/132
80_na.PDF
12.3
Supply, install, connect and programming Linksys cables less-
N Gigabit Security Router with VPN Secure, high-
speedcablesless networking or Approved equivalent.
No. 2
12.4Computer main feeders cable shielded type Teldor FTP CAT6A
inside pvc conduits.ML 60
Total of Computer Network Carried to Summary Sheet
12.2 No.
26 of 31
Bill of Quantities (BoQ) Refurbishment of a forensic laboratory in Ramallah ITB-2013-208
Item Description Unit Qty Unit Rate
US$ Total US$
13 Fire Fighting SystemSupply install and connect complete in place and in an operable
manner the Fire Fighting system Telefire / Mircom / Kidde or
Approved equivalent For main distribution board at electrical
room . The work is to include the supply of the equipment
specified, installation of same connection, wiring commissioning
and all of the details.
13.1
Automatic Valve Cylinder 3 KG Kidde FM 200 P/ N
90100011001 ( 180 Degree Pendant Nozzle , 3/8" Check
Valves , Bracket , Pressure Gauge , Copper pipe , Safe Cap
*...with all accessories needed )
No 1
13.2Main Control Panel 4- Zone Telefire 2-B or Approved
equivalentNo 1
13.3Photoelectric Smoke Detector MIR-338H / TFO-440 or
Approved equivalentNo 2
13.4 Heat detector - S.S 5601 P / TFH-220F or Approved equivalent No 2
13.5 Indication lamp TFL-1N or Approved equivalent No 2
13.6 Break glass unit TPB-10 R or Approved equivalent No 1
13.7 Fire Indoor Horn TIP-224A or Approved equivalent No 1Total of Fire Fighting System Works Carried to Summary
Sheet
14 Cable TraysSupply and install galvanize cable trays, cable trucking and
sleeves as per drawings and specifications complete with
supports, fixing devices, covers, separators, clamps, end caps,
drawcabless, elbows, joints, branches, reducers, offsets *as
show on drawings and specifications.
14.1LV Cable Tray 100x85 mm Mesh galvanized iron, 6 mm
thickness. M.L. 40
14.2Power Cable Tray 200x85mm Mesh galvanized iron, 6 mm
thickness. M.L. 40
Total of Cable Trays Carried to Summary Sheet
27 of 31
Bill of Quantities (BoQ) Refurbishment of a forensic laboratory in Ramallah ITB-2013-208
Item Description Unit Qty Unit Rate
US$ Total US$
15 Trucking systemSupply and install and connect main SNAP -ON Trucking
system -LEGRAND MODEL or approved equivalent, complete
with Parttions,covers, spacers, internal and external angles ,
end caps joints, body joints, base joints , flat angle 90 degree ,
flat junctions branches, reducers, offsets , The work is to include
the supply of the equipment specified, installation of same
connection, commissioning and all of the details as listed below
for the required complete job. SNAP-ON TRUNK 50X105 1COMP+45MM COVER 2M NO
075602SNAP-ON TRUNK EXTRA PARTITION 2M NO 075609SNAP-ON TRUNK END CAP 50X105 NO 075612SNAP-ON TRUNK INTERNAL ANGLE 50X105 NO 075622SNAP-ON TRUNK EXTERNAL ANGLE 50X105 NO SNAP-ON TRUNK FLAT ANGLE 50X105 NO 075642SNAP-ON TRUNK COUPLING SET 50X105 NO 075688SNAP-ON TRUNK 45MM COVER JOINT NO 07 5669SNAP-ON TRUNK FLAT JUNCTION SIDE 17->50X105 NO
075676SNAP-ON TRUNK FLAT JUNCTION SIDE 29->50X105 NO NO
075676SNAP-ON TRUNK ANGLED JUNCTION->50X80/105/130SNAP-ON TRUNK SOLUCLIP NO 75690
Total of Trunking system Carried to Summary Sheet
16 Electrical Switchboards
16.1 GMDB- Existing Control Panel
16.1.1
Replacing and connecting The Main Molded Case Circuit
Breaker (MCCB) ( 3 x315 )A. Type ABB or approved equivalent
with short circuit current protective coil and adjustable thermal
over current protection capable of with standing 50KA cutout and
short circuit current. Inside the existing GMDB control panel
price includes Bridges , bus bar , cables and all accessories
with complete operation.
No. 2
16.1.2
Adding and connecting ,testing with complete operation A
Motorized ATS 4 pole (4x400) A. Type Klockner Moller Complete
set or equivalent.
No. 1
TOTAL of GMDB- Exist-Control Panel Carried to Summary
17 Cables & Conductors / Leads Supply, install, test and connect the following electrical cables ,
including insertion into conduit or attachment to structural
elements or laying in ductwork, including all associated
materials, insulation materials, unions, labeling and connection
of cable at both ends and all accessories).17.1 3x185+95 sq.mm cross section XLPE/PVC/PVC cable. M.L. 70
17.2 Copper conductor with PVC insulation cross section 95sq.mm. M.L 70Total of Cables & Conductors Works Carried to Summary
Sheet
15.1 M.L. 50
28 of 31
Bill of Quantities (BoQ) Refurbishment of a forensic laboratory in Ramallah ITB-2013-208
Item Description Unit Qty Unit Rate
US$ Total US$
18 Stand-By Power GeneratorSupply, install and connect in place and in an operable manner
an automatic main failure emergency stand by diesel generating
set, 225KVA 3-phase 380volt, 50C/S, 0.8 p.f complete with
control panel, including complete set of digital analyzer controller
unit, frequency meter ( package mounted control panel).The
contractor should install the generator in the specified room,
including radiator fan, fuel filter, engine-driven radiator with
blower fan and all accessories, starting batteries -lead-acid
storage battery- complete with battery charger and control panel
when generator set is not operating and disconnect when
generator set is in operation, original water proof canopy jacket, exhaust system, foundation,
vibration isolators, silencer, earthling, foundation concrete base,
a full tank of diesel fuel,... etc. with all fitting and accessories.
The system should include the main Automatic Voltage
Regulator (AVR) witch maintain the generator output voltage
within +/-0.5% for any constant load between no load and full
load. The contractor and supplier should provide one set of operation
and maintenance manuals covering the generator, and auxiliary
components, include all parts manuals, final as-built wiring
interconnect diagrams and recommended preventative
maintenance schedules. and accessories to complete the
works.
18.1
Stand By Power Generator Set all as described above. All
Manufacturer of original types as MBH Power Generator type ,
Perkins or approved equivalent.
No 1
Total of Emergency Generator Carried to Summary Sheet
19 Fire Fighting System
Supply install and connect complete in place and in an operable
manner the Fire Fighting system Telefire / Mircom / Kidde or
Approved equivalent For main distribution board at electrical
room . The work is to include the supply of the equipment
specified, installation of same connection, wiring commissioning
and all of the details.
19.1
Automatic Valve Cylinder 3 KG Kidde FM 200 P/ N
90100011001 ( 180 Degree Pendant Nozzle , 3/8" Check
Valves , Bracket , Pressure Gauge , Copper pipe , Safe Cap with
all accessories needed )
No 1
19.2Main Control Panel 4- Zone Telefire 2-B or Approved
equivalentNo 1
19.3Photoelectric Smoke Detector MIR-338H / TFO-440 or
Approved equivalentNo 2
19.4 Heat detector - S.S 5601 P / TFH-220F or Approved equivalent No 2
19.5 Indication lamp TFL-1N or Approved equivalent No 2
19.6 Break glass unit TPB-10 R or Approved equivalent No 1
19.7 Fire Indoor Horn TIP-224A or Approved equivalent No 1
Total of Fire Fighting System Works Carried to Summary
29 of 31
Bill of Quantities (BoQ) Refurbishment of a forensic laboratory in Ramallah ITB-2013-208
Item Description Total amount $
1 Total of Electrical Switchboards Works
2 Total of Installation in the Building Points Works
3 Total of Lighting Fixtures Works
4 Total of Cables & Conductors / Leads Works
5 Total of Cable Conduit & Ducts Works
6 Total of Telephone Cable and low voltage box Works
7 Total of Electrical Appliance Works
8 Total of Grounding Works
9 Total of Access & Integrated Security System Works
10 Total of Fire Alarm System Works
11 Total of CCTV System Works
12 Total of Computer Network Works
13 Total of Total of Fire Fighting System Works
14 Total of Cable Trays Works
15 Total of Trunking system Works
16 Total of GMDB- Exist-Control Panel Works
17 Total of Cables & Conductors Works
18 Total of Emergency Generator Works
19 Total of Fire Fighting System Works
Total of Electrical Works..carried to Grand Summary
Electrical Works BoQ Summary
30 of 31
Bill of Quantities (BoQ) Refurbishment of a forensic laboratory in Ramallah ITB-2013-208
Bill No. Description Total US$
1 Summary of Civil Works Bills
2 Summary of Mechanical Works Bills
3 Summary of Electrical Works Bills
Grand Total
Name & Address of the Contractor:
Authorized person Name :
Signature & Stamp :
BoQ Summary
Net Grand Total in Words:
Date:
Net Grand Total Excluding Value Added Tax (VAT):
Discount percentage (if any) :
Discount Amount :
31 of 31