A-eberle Relay Reg Da
-
Upload
anonymous-m65ttcfot -
Category
Documents
-
view
223 -
download
0
Transcript of A-eberle Relay Reg Da
-
8/21/2019 A-eberle Relay Reg Da
1/3161
REG-DA
REG-DA operating manual
Operating ManualREG-DARelay for Voltage Control & Transformer
Monitoring
Issue 18.10.07/03
Issue GB
Version 10.2007
Software Version
-
8/21/2019 A-eberle Relay Reg Da
2/3162
REG-DA
REG-DA operating manual
REG-DARelay for Voltage Control & Transformer
Monitoring
Operating Manual
Issue 18.10.07
Copyright 2007 byA. Eberle GmbH & Co. KG..
All rights reserved.
Published by:
A. Eberle GmbH & Co. KG
Aalener Strae 30/32
90441 Nuremberg, Germany
Tel.: +49 (0) 911 / 62 81 08 - 0
Fax No.: +49 (0)-911 / 66 66 64
e-mail: [email protected]
Internet: www.a-eberle.de, www.regsys.de
The companyA. Eberle GmbH & Co. KGcannot be held liable for
any damages or losses resulting from printing errors or changes
in this operating manual.
Furthermore,A. Eberle GmbH & Co. KGdoes not assume
responsibility for any damages and losses resulting from
defective devices or from devices altered by the user.
-
8/21/2019 A-eberle Relay Reg Da
3/3163
REG-DA
REG-DA operating manual
Table of Contents
1 Warnings and Information. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
2 Scope of Delivery. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
3 Technical Data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
3.1 Basic equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
3.2 Connection diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
3.3 Overview of features. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
3.4 Block diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 213.4.1 Block diagram for features D0/D1/D4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 213.4.2 Block diagram for features D2/D3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
3.5 Pin Assignment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 233.5.1 Pin assignment level I . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
3.5.2 Pin assignment level II . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
3.5.3 Pin assignment level III. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
3.6 Types of REG-DA Relay for Voltage Control & Transformer Monitoring . . . . . . . . . . . . . . . . . . . 443.6.1 Wall-mounting version . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
3.6.2 Panel-mounting version . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
3.6.3 Mounting on Standard Mounting Rails. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
4 Operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
4.1 Display and control elements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 474.1.1 Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
4.2 Operating principle. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
4.3 Selecting the display mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
4.4 Lamp check. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
4.5 Resetting fault signals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
4.6 Operating the recorder . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
-
8/21/2019 A-eberle Relay Reg Da
4/3164
REG-DA
REG-DA operating manual
5 Commissioning. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .63
5.1 Regulator mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
5.2 Measurement transducer mode. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
5.3 Recorder mode. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
5.4 Statistics mode. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
5.5 ParaGramer mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
5.6 Choosing the language . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
5.7 Setpoint value . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
5.8 Permissible regulative deviation Xwz . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
5.9 Time behaviour. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
5.10 Backward high-speed switching . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
5.11 Tap-changer running time. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
5.12 Knx transformer mounting ratios and transformer connection . . . . . . . . . . . . . . . . . . . . . . . . . 79
5.13 Setting the nominal current . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80
5.14 Inhibit low limit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82
5.15 Trigger. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84
5.16 Short description of individual limit values, setpoint values and permissible regulative deviation. 85
5.16.1 Description of the individual settings. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .85
6 Basic Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91
6.1 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 916.1.1 Station ID . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .91
6.1.2 Station name. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .92
6.1.3 Setting the time/date . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .93
6.1.4 LCD contrast (display) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .94
6.1.5 Password . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .94
6.1.6 Deleting recorder data (resetting the measured value memory). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .95
6.1.7 Deleting tap-change sums (resetting the tap-counter to zero). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .96
6.1.8 Actual value correction of the measuring voltage UE. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .96
6.1.9 Actual value correction of the measuring current IE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .96
6.2 RS-232 interfaces . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 976.2.1 COM 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .97
6.2.2 COM 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .99
6.3 E-LAN (Energy-Local Area Network). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101
6.4 PAN-D voltage monitoring unit. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104
6.5 Status (current ID data of the REG-DA Relay for Voltage Control & Transformer Monitoring). . . 104
-
8/21/2019 A-eberle Relay Reg Da
5/3165
REG-DA
REG-DA operating manual
7 Parameterisation of the REG-DA Relay for Voltage Control & Transformer
Monitoring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 108
7.1 Permissible regulative deviation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1097.2 Time behaviour (regulation behaviour) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1097.2.1 Time factor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 109
7.2.2 Time program . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 110
7.2.3 Trend memory. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 110
7.3 Setpoints . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1117.3.1 1st setpoint value . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 111
7.3.2 Further setpoint values. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 112
7.4 Programs (parameters for parallel regulation of transformers and for the compensation of the
voltage drop on the line) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1137.4.1 Selection of the parallel programs (regulation programs) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 113
7.4.2 Parameters for the parallel program . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 114
7.4.3 Current influence (line-drop compensation) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 116
7.4.4 LDC parameter (line drop compensation). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 116
7.5 Gradient (U/I characteristic). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 117
7.6 Limitation (U/I characteristic). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 117
7.7 < U Undervoltage. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 117
7.8 > U Overvoltage. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 118
7.9 > I, < Limit (upper and lower current limits). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1187.10 Trigger inhibit high (highest limit value of the voltage). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 119
7.11 High-speed switching during undervoltage/overvoltage. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1207.11.1 High-speed switching when undervoltage occurs (RAISE) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 120
7.11.2 High-speed switching when overvoltage occurs (LOWER) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 120
7.12 REG-DA inhibit low when undervoltage occurs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 121
7.13 Time delays (limit signals). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1217.13.1 Time delay > U . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 121
7.13.2 Time delay < U . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 122
7.13.3 Time delay > I, < I limit value. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1227.13.4 Time delay trigger . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 122
7.13.5 Time delay forward high-speed switching . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 123
7.13.6 Time delay backward high-speed switching . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 123
7.13.7 Time delay inhibit low . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 124
-
8/21/2019 A-eberle Relay Reg Da
6/3166
REG-DA
REG-DA operating manual
7.14 Add-Ons (Relay for Voltage Control & Transformer Monitoring behaviour). . . . . . . . . . . . . . . . 1247.14.1 Overview of the Add-Ons menus numbers 1 to 6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .124
7.14.2 Maximum time TC in operation (motor-drive-in operation-time) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .126
7.14.3 Manual/Automatic. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1277.14.4 Tap-changing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .128
7.14.5 Self-conduction of the operating mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .129
7.14.6 Current display (of the transformer) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .129
7.14.7 LCD saver (display) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .130
7.14.8 Regulator mode: large display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .130
7.14.9 Language selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .131
7.14.10 Parallel Program Activation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .132
7.14.11 Up/down relay on time. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .132
7.14.12 AUTO(MATIC) LOCK in the event of an E-LAN error . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .133
7.14.13 Setpoint adjustment. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .133
7.14.14 Creeping net breakdown . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .134
7.14.15 Limit base (reference value) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .135
7.14.16 Setting the Relay for Voltage Control & Transformer Monitoring to inhibit low if I . . . . . . . . . . . . . . .136
7.14.17 Maximum tap difference (monitoring) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .136
7.14.18 ParaGramer activation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .137
7.15 Transformer configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1387.15.1 Transformer mounting voltage (measurement voltage) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .138
7.15.2 Transformer mounting ratio for the voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .140
7.15.3 Transformer mounting current (conductor connection) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .140
7.15.4 Transformer mounting current (conversion 1 A / 5 A). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .140
7.15.5 Transformer mounting ratio for the current . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .141
7.16 Input assignments (binary inputs). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 142
7.17 Relay assignments . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 143
7.18 LED assignments . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 145
8 Measurement Value Simulation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 146
8.1 Setting the simulated voltage. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 148
8.2 Setting the simulated current. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 148
8.3 Setting the simulated phase angle . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1488.4 Setting the simulated tap-change . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 149
9 Parallel Operation of Transformers with REG-DA . . . . . . . . . . . . . . . . . . . . . . . 150
9.1 Circuit diagram (schematic). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 152
9.2 Programs for parallel operation and their prerequisites . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1549.2.1 Preparation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .154
9.2.2 Preparing manual activation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .156
9.2.3 Preparing automatic activation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .163
9.3 Parallel operation using the Master-Slave-Independent (MSI) procedure . . . . . . . . . . . . . . . 1739.3.1 Trouble-shooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .184
-
8/21/2019 A-eberle Relay Reg Da
7/3167
REG-DA
REG-DA operating manual
10 Resistance Measuring Equipment for Tap-Changers with Resistance-Coded Tap-
Change Signalling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 187
10.1 Error detection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18810.2 Level detection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 188
10.3 Pin assignment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 189
10.4 Connection options. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 190
10.5 Setting of the DIP switch S1 and S2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19110.5.1 Location of the switch on the circuit board: level 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 191
11 mA-Inputs, mA-Outputs. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 192
11.1 Analogue inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 193
11.2 Analogue outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 203
12 Updating the Operating Software . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 214
12.1 Preparing the PC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21512.1.1 Windows NT/2000/XP operating system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 215
12.2 Starting the bootstrap loader. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 215
13 Maintenance and Current Consumption . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 220
13.1 Cleaning information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 220
13.2 Changng fuses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22113.3 Changing the battery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 221
13.4 REG-DA Current Consumption. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 223
13.5 Replacing the device . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 224
14 Storage Information. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 225
15 Background Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 226
15.1 Regulator mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 226
15.2 Command variable W . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22715.2.1 Fixed command variable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 227
15.2.2 Variable command variable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 228
15.2.3 Current-dependent setpoint value increment. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 231
15.3 Summary and Examples for Current Influencing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 235
15.4 Regulative deviations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23815.4.1 Regulative deviation Xw . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 238
15.4.2 Permissible regulative deviation Xwz. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 238
15.4.3 Displaying the regulative deviation Xw. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 239
15.4.4 Setting the permissible regulative deviation Xwz . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 239
15.5 Monitoring extreme operating values (faults) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24115.5.1 Limit signal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 241
-
8/21/2019 A-eberle Relay Reg Da
8/3168
REG-DA
REG-DA operating manual
15.6 Add-Ons . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24615.6.1 High-speed switching add-on. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .246
15.6.2 Relay for Voltage Control & Transformer Monitoring inhibit low function . . . . . . . . . . . . . . . . . . . . . . . . . .247
15.6.3 Measuring the Creeping Net Breakdown . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24815.6.4 Maximum tap-change difference monitoring Add-On . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .250
15.6.5 Add-On: monitoring the tap-changer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .250
15.7 Time behaviour of the Relay for Voltage Control & Transformer Monitoring when a control command
is output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25215.7.1 Determining the reaction delay tv . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .255
15.7.2 Integrated time program . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .259
15.7.3 Trend memory. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .260
15.7.4 Const time program . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .262
15.7.5 Setting the time factor Ft . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .266
15.8 E-LAN (Energy Local Area Network) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 267
15.9 Voltage regulation with transformers operating in parallel . . . . . . . . . . . . . . . . . . . . . . . . . . . 27115.9.1 Regulation programs for transformers operating in parallel. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .272
15.9.2 Functional principle . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .273
15.9.3 Influence of the circulating current regulation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .273
15.9.4 Activation of the regulation program . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .274
15.9.5 Description of the regulation programs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .275
15.10 Nominal transformation of the measurement transformers . . . . . . . . . . . . . . . . . . . . . . . . . . 292
15.11 Self-Conduct . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 293
15.12 LCD display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29315.12.1 LCD contrast. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .293
15.12.2 LCD Saver. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .293
15.12.3 Background illumination. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .293
16 Definition of the Abbreviations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 294
17 Symbols and their Definition. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 300
18 Factory Settings of the Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 303
19 Notes on the Interpreter Language . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 305
20 Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 306
Appendix
Labels
Drill hole-pattern
-
8/21/2019 A-eberle Relay Reg Da
9/3169
REG-DA
REG-DA operating manual
1 Warnings and Information
The REG-DA Relay for Voltage Control & Transformer
Monitoring is exclusively designed for implementation in
systems and equipment for electrical energy technology. Only
trained experts are permitted to carry out all required work.
Experts are persons who are familiar with the installation,
mounting, commissioning and operation of these types of
products. Furthermore, experts have qualifications which
correspond with the requirements of their field of work.
The REG-DA Relay for Voltage Control & TransformerMonitoring left the factory in a condition that fulfils all relevant
safety regulations. To maintain this condition and to ensure safe
operation, the following instructions and warnings in this
operating manual must be observed.
The REG-DA Relay for Voltage Control & Transformer
Monitoring has been designed to comply with IEC 10110/
EN61010 (DIN VDE 0411), degree of protection I and was
tested according to this standard before delivery.
The REG-DA Relay for Voltage Control & TransformerMonitoring must be earthed via a protective earth
conductor. This condition is fulfilled when the Relay for
Voltage Control & Transformer Monitoring is connected to
an auxiliary voltage with a protective earth conductor
(European power supply system). If the auxiliary voltage
power supply system does not have a protective earth
conductor, an additional connection must be established
from the protective earth conductor terminal to earth.
The upper limit of the permissible auxiliary voltage UAUXmaynot be exceeded, neither permanently nor for a short period
of time.
Before changing the fuse, separate the REG-DA Relay for
Voltage Control & Transformer Monitoring completely from
the auxiliary voltage UAUX.
The use of fuses other than those of the indicated type and
rated current is prohibited.
A REG-DA Relay for Voltage Control & Transformer
Monitoring which displays visible damage or clearmalfunctioning must not be used and has to be secured
against unintentionally being switched on.
-
8/21/2019 A-eberle Relay Reg Da
10/31610
REG-DA
REG-DA operating manual
Maintenance and repair work on a REG-DA Relay for
Voltage Control & Transformer Monitoring with an open
door may only be carried out by authorised experts.
Warning signs
Please familiarise yourself with the nominal insulation voltage of
the Relay for Voltage Control & Transformer Monitoring before
connecting the device.
Ensure that the voltages are connected via a disconnecting
mechanism, and that the current path can be short circuited if
there is a device fault to enable problem-free device
replacement.
When wiring, please ensure that the conductors are either
bound short or kept sufficiently short so that they cannot reach
level 2 or 3.
If a fault occurs (connection becomes loose), no line that carries
a voltage that is dangerous when touched (> 50 V) or line to
which a nominal isolation voltage larger than 50 V is assigned,
may come into contact with the circuits in levels 2 and 3.
!
-
8/21/2019 A-eberle Relay Reg Da
11/31611
REG-DA
REG-DA operating manual
2 Scope of Delivery
1 REG-DA Relay for Voltage Control & Transformer Monitoring,
with built-in components
1 terminal diagram in English
1 operating manual in English
1 WinREG programming and parameterisation software
1 cable
1 replacement fuse
2 tools
(7 mm Allen key and special screwdriver for the terminals on
levels 2 and 3)
-
8/21/2019 A-eberle Relay Reg Da
12/31612
REG-DA
REG-DA operating manual
3 Technical Data
3.1 Basic equipment
Dimensions
Lead sealing Each Relay for Voltage Control & Transformer Monitoring canbe locked with a password so that the parameters cannot be
changed.
The REG-DA can also be lead-sealed to show whether it has
been opened by unauthorized persons.
For this purpose, a lead-sealing wire is pulled diagonally
through the bores in the lower right corner of the housing corner
and is secured with a lead-sealing tool.
This measure ensures that the device can only be opened by
breaking the lead seal.
Dimensions in mm
-
8/21/2019 A-eberle Relay Reg Da
13/31613
REG-DA
REG-DA operating manual
Connection levels
Side view (section) of opened housing
NoteReference is made to the connection levels (levels I...III)
in both the block diagram (Page 21) and the pin
assignment (Page 23).
Membrane keypad
area III
area II
area I
-
8/21/2019 A-eberle Relay Reg Da
14/31614
REG-DA
REG-DA operating manual
3.2 Connection diagram
Contact load R1, R2: AC 250 V, 5 A, cos= 1,250 V DC, 150 W
* Please observe the contact load at R1 and R2!
(see below)!
** The connections for I and U can be freely assigned
via the menu.
110 V DC 230 V AC
20 A Switch on 5 A @ cos= 1
5 A Hold 3 A @ cos
= 0.4
0.4 A Switch off
-
8/21/2019 A-eberle Relay Reg Da
15/31615
REG-DA
REG-DA operating manual
3.3 Overview of features
REG-DA is a highly variable product.
The operating manual must take this factor into account andprovide different descriptions for the for the various
specifications.
Because the features ... M2, S1... D4 ... are noted on the name
plate of the device, but the relation to the function which it
stands for is not always given, the complete structure of the
device's features is listed here.
Feature: ID
REG-DA Relay for Voltage Control & Transformer
Monitoring
Basic version with E-LAN double interfaces,
COM 2, COM 3 and a mA input channel for e.g.
measuring the oil temperature
or for the measuring of the tap-changer position using
a measurement transducer
with 16 binary inputs and 12 relay outputs plus status
outputinclusive of WinREG parameterisation software for
parameterisation, programming
and displaying of all Relay for Voltage Control &
Transformer Monitoring data incl. connecting cable
Note: COM 2 is only freely accessible
if a log connection is not required.
REG-DA
Design
Panel-mounting or wall-mounting version
(H x W x D) 307 x 250 x 102 mm
with standard mounting rail adapter
B0
B1
Current supply
external
85 V ... 110 V ... 264 V AC / 88 V ... 220 V ... 280 V DC
external 18 V ... 60 V ... 72 V DC
H0
H2
Input currents (can be changed later)
IEN1A
IEN5A
F1
F2
-
8/21/2019 A-eberle Relay Reg Da
16/31616
REG-DA
REG-DA operating manual
Measurement transducer display functions for network
quantitiesThree-phase current with balanced load
Three-phase current with unbalanced load
Voltage (HV-side), current and voltage (MV-side)
measurement
Other uses of the three current and two voltage
transformers
M1
M2
M3
M9
Recorder functions
for network quantities with evaluation software
WithoutWith S0S1
Transformer monitoring
Without
With
T0
T1
Parallel operation
Without firmware for parallel operation
With firmware for parallel operation
K0
K1
Feature: ID
-
8/21/2019 A-eberle Relay Reg Da
17/31617
REG-DA
REG-DA operating manual
Additional analogue inputs and outputs
WithoutWith one a PT 100 input
With two mA inputs
With two mA outputs
With one PT 100 input and one mA output
With two mA inputs and one mA output
With three mA outputs
Tap-change potentiometer input
Total resistance 200 Ohm ... 2 kOhm
Tap-change potentiometer input
Total resistance >2 kOhm ... 20 kOhmOther combinations of inputs and outputs
Note about E91 ... E99:
Please specify the scale if known!
Example: 1 -100 ... 0 ... +100 MW
-20 ... 0 ... +20 mA
Example: 2 0 ... 80 ... 120 V
4 ... 16 ... 20 mA
Example: 3 1 ... 19 levels
0 ... 20 mA
Example: 4 50 ... 140C
4 ... 20 mA
E00E91
E92
E93
E94
E95
E96
E97
E98E99
Feature: ID
-
8/21/2019 A-eberle Relay Reg Da
18/31618
REG-DA
REG-DA operating manual
Binary inputs and tap-changer potentiometer input
16 binary inputs 48 ... 250 V AC/DC8 binary inputs 10 ... 48 V AC/DC
and 8 binary inputs 48 ... 250 V AC/DC
1 tap-change potentiometer input
(total resistance 200 ... 2 kOhm)
and 8 binary inputs 48 ... 250 V AC/DC
1 tap-change potentiometer input
(total resistance >2 ... 20 kOhm)
and 8 binary inputs 10 ... 48 V AC/DC
16 binary inputs 10 ... 48 V AC/DC
1 tap-change potentiometer input(total resistance 200 ... 2 kOhm)
and 8 binary inputs 10 ... 48 V AC/DC
1 tap-change potentiometer input
(total resistance >2 ... 20 kOhm)
and 8 binary inputs 48 ... 250 V AC/DC
D0D1
D2
D3
D4
D5
D6
Level II: additional inputs and outputs
Without
With 6 binary inputs 48 ... 250 V AC/DC
With 12 binary inputs 48 ... 250 V AC/DCWith 6 relay outputs
With 12 relay outputs
With 6 binary inputs and 6 relay outputs
With 2 analogue inputs
With 4 analogue inputs
With 2 analogue outputs
With 4 analogue outputs
Other combinations 6 inputs, 6 outputs, 2 analogue
inputs, 2 analogue outputs
Note about C90: Two terminals are normally available
on level II.
Each terminal can be equipped with either 6 binary
inputs, 6 binary outputs or an analogue module.
Either 2 inputs or 2 outputs are available per analogue
module.
Up to 4 additional modules can be equipped assuming
that a control system connection (XW90, 91 or L1, L9)
is not used.
C00
C01
C02C03
C04
C05
C06
C07
C08
C09
C90
Feature: ID
-
8/21/2019 A-eberle Relay Reg Da
19/31619
REG-DA
REG-DA operating manual
Integrated control system connection according to:
IEC61850 or IEC 60870- 5-104Without
IEC 60850 - 5 - 104 (more in feature group G)
Note: Please specify the target system for connections
according to IEC 60850-5-104
IEC 61850 (more in feature group G)
XW00
XW90
XW91
Integrated control system connection according to: IEC
60870- 5-101/ ..-103,DNP
Without (more in feature group G)
for the control system connection of a REG-DAFor the control system connection of multiple systems
(REG-D/DA/DP, etc.)
Note: L9 can only be combined with feature XW90,
Z15 to Z19 and Z91.
L0
L1L9
Type of connection:
Copper RS 232
RS 485 only for 2-wire operation
Fibre-optic cable with FSMA connection system
Glass fibre(Wavelength 800...900 nm, range 2000 m)
Plastic fibre
(Wavelength 620...680 nm, range 50 m)
Fibre-optic cable with ST connection system
Glass fibre
(Wavelength 800...900 nm, range 2000 m)
Plastic fibre
(Wavelength 620...680 nm, range 50 m)
V10
V11
V13
V15
V17
V19
Feature: ID
-
8/21/2019 A-eberle Relay Reg Da
20/31620
REG-DA
REG-DA operating manual
Log:
IEC60870-5-103 for ABBIEC60870-5-103 for Areva
IEC60870-5-103 for SAT
IEC60870-5-103 for Siemens (LSA/SAS)
IEC60870-5-103 for Sprecher Automation
IEC60870-5-103 for others
IEC60870-5-101 for ABB
IEC60870-5-101 for IDS
IEC60870-5-101 for SAT
IEC60870-5-101 for Siemens (LSA/SAS)IEC60870-5-101 for others
DNP 3.00
LONMark
SPABUS
MODBUS RTU
Z10Z11
Z12
Z13
Z14
Z90
Z15
Z17
Z18
Z19Z91
Z20
Z21
Z22
Z23
Operating Manual
German
EnglishFrench
Spanish
Italian
Russian
Other
G1
G2G3
G4
G5
G6
G9
Display text
German
English
French
SpanishItalian
Russian
Other
A1
A2
A3
A4A5
A6
A9
Feature: ID
-
8/21/2019 A-eberle Relay Reg Da
21/31621
REG-DA
REG-DA operating manual
3.4 Block diagrams
3.4.1 Block diagram for features D0/D1/D4
-
8/21/2019 A-eberle Relay Reg Da
22/31622
REG-DA
REG-DA operating manual
3.4.2 Block diagram for features D2/D3
-
8/21/2019 A-eberle Relay Reg Da
23/31623
REG-DA
REG-DA operating manual
3.5 Pin Assignment
Signals with non-exposed voltages are connected first of all on
level I.All of the circuits on level I have a nominal insulation voltage of
> 50 V and are therefore considered to be non-exposed in
accordance with VDE 0110 (exception: resistance input,
feature D2/D3).
Please observe this condition even if small voltages are present
at the relay contacts or the binary inputs.
Terminal area on connection level III
Terminal area on connection level I
Terminal area on connection level II
-
8/21/2019 A-eberle Relay Reg Da
24/31624
REG-DA
REG-DA operating manual
*) The Relay for Voltage Control & Transformer Monitoring with
feature M1 provides only one voltage input. One voltage
transformer is sufficient for standard regulating functions.
When carrying out measurements in arbitrarily-loaded three-
phase current systems, the three external-conductor voltages
must be connected to terminals 2, 5 and 8 (Feature M2).
Triple-wound applications function with two separate input
voltages U1and U2.
LevelI
No. M1 * M2 * Triple*-
woundregulator
2 Voltage inputU1
UL1U1
5 Voltage input UL2
8 Voltage input
UL3U2
10 Voltage input
1 kCurrent input I1
3 I4 k
Current input I26 I
7 kCurrent input I3
9 I
21 L / (+)Auxiliary voltage
22 L / (-)
-
8/21/2019 A-eberle Relay Reg Da
25/31625
REG-DA
REG-DA operating manual
NoteAll of the inputs and relay outputs are freely
programmable, with the exception of inputs 5 and 6 and
the outputs R1, R2, R12and R13.
The assignment specified in the terminal diagramcorresponds to the delivery state and can be changed if
necessary.
LevelI
No. D0, D1, D4 D2, D3
11 Input 1 Tap-changer in progress
12 Input 2 Freely programmable
13 Input 3 Freely programmable
14 Input 4 Freely programmable
15 Input 1...4 GND
16 Input 5 AUTO / MANUAL -
AUTO
(see Page 127)17 Input 6 MANUAL
18 Input 7 Freely programmable
19 Input 8 Freely programmable
20 Input 5...8 GND
23 Input 9 BCD 1
please also
refer to Page
34
24 Input 10 BCD 2
25 Input 11 BCD 4
26 Input 12 BCD 8
27 Input 9...12 GND
28 Input 13 BCD 10
29 Input 14 BCD 20
30 Input 15 BCD signal
31 Input 16 Freely programmable
32 Input 13 ... 16 GND
-
8/21/2019 A-eberle Relay Reg Da
26/31626
REG-DA
REG-DA operating manual
LevelI
No.
33Freely programmable R5
34
35Freely programmable R4
36
37Freely programmable R3
38
39
Lower R240
41
42
43
Raise R144
45
4647 > I R11
48 >U R10
49
-
8/21/2019 A-eberle Relay Reg Da
27/31627
REG-DA
REG-DA operating manual
LevelII
No.
IEC
LON
DNP 3.0
SPA bus
Modbus
For additional equipping possibilities for level II see "Pin
assignment level II" on page 35.
The connections of the control system can be found in the
information attached to the operating manual.
LevelIII
No.
63 mA input +A1 (standard equipment)
64 mA input -
61 Input or
output
+
A2
62 Input oroutput
-
65 Input or
output
+
A366 Input or
output
-
67 Input or
output
+
A4
68 Input oroutput
-
65
66
68
Pt100
-
8/21/2019 A-eberle Relay Reg Da
28/31628
REG-DA
REG-DA operating manual
LevelIII
No.
69 E-
E-LAN (L)70 E+
71 EA-
72 EA+
73 E-
E-LAN (R)74 E+
75 EA-
76 EA+
77 Tx +
COM 3 (RS 485)78 Tx -
79 Rx +
80 Rx -
81 du dont use
82 TxD
COM 2 (RS 232)
83 RxD
84 RTS
85 CTS
86 GND
-
8/21/2019 A-eberle Relay Reg Da
29/31629
REG-DA
REG-DA operating manual
3.5.1 Pin assignment level I
3.5.1.1 Auxiliary voltage, current input and voltage input
Terminals 21, 22 and 1 to 10
The REG-DA Relay for Voltage Control & Transformer
Monitoring is equipped for carrying out measurements in
arbitrarily loaded three-phase current networks. Therefore, up
to three current transformers are available.
Voltage regulation generally only requires a single-phase
connection (one delta or phase voltage and one line current),because it may be assumed that the network conditions at the
transformer are approximately symmetrical (feature M1).
If a more precise measurement of the outputs (P, Q, S) is
required, it is possible to switch over to the Aron circuit. In this
case, two voltages and two currents must be connected
(feature M2).
The third current input is reserved for special cases, which must
be coordinated before the device is delivered.
-
8/21/2019 A-eberle Relay Reg Da
30/31630
REG-DA
REG-DA operating manual
Auxiliary voltage (terminals 21 and 22)
The protective earth must be connected first, because the
REG-DA is a device with degree of protection I.
A plug-in shoe (6.3 x 0.8 mm) is provided in the lower part of
the housing for connecting the protective earth.
The auxiliary voltage is supplied via the twin connector block
(terminals 21 and 22).
Two types of power supply units are available:
Therefore, please ensure that the intended supply voltage
corresponds to the auxiliary voltage of the device as stated on
the printed nameplate, before connecting.
Feature H0:
Both direct and alternating voltages may be connected.
Ranges: 88 V ... 220 V ... 280 V DC
85 V ... 110 V ... 264 V AC
Power consumption: < 15 VA
Feature H1:
18 V ... 60 V ... 72 V DC
Power consumption: < 10 W
The auxiliary voltage, and thus the power supply of the device,
is protected by a T2L 250 V microfuse.The fuse holder can be opened with a screwdriver. The device
is supplied with a spare fuse.
Flat-plug
connection
for protective
earth
-
8/21/2019 A-eberle Relay Reg Da
31/31631
REG-DA
REG-DA operating manual
NotePlease note that the fuse catch should never be
screwed on without having a fuse inserted, because
otherwise it is difficult to open the fuse holder.
3.5.1.2 Control voltage
(Terminals 2, 5 and 8, 10)
The control voltage must be connected to the terminals 2 and
5.
Any voltage from the three-phase current network can be used
as the control voltage. The type of voltage (delta or phasevoltage, UL1L2, UL2L3, UL3L1, U1N, U2N, U3N) must be
communicated to the Relay for Voltage Control & Transformer
Monitoring via the menu (SETUP 5, F2).
The permissible nominal application range of the control voltage
ranges from 60 to 140 V and is expressed in terms of delta
voltage.
If there is a connection between the phase and N, the nominal
application range of 34.6 to 140 V becomes available.
Please note that a single-pole high-resistance earth connection
affects L1 like a voltage dip if only a phase voltage (e.g. L1N) is
available for measuring the actual value of the voltage.
If a phase voltage is used as the control voltage rather than the
recommended delta voltage, you must pay attention to the
behaviour if a single-pole earth fault occurs.
In high-resistance faults, situations may occur where the
voltage appears to be too high or too low.
The Relay for Voltage Control & Transformer Monitoring
generally switches itself into standby mode for low resistancefaults.
Strongly distorted signals may also be connected by means of
a complex filtering of the measurement voltages and the
measurement currents.
If feature M2 is used, voltage UL1must be connected to terminal
2, voltage UL2to terminal 5 and voltage UL3to terminal 8.
i.e.:UL12UL25UL38
-
8/21/2019 A-eberle Relay Reg Da
32/31632
REG-DA
REG-DA operating manual
Voltage inputs U1 and U2 are both available for triple-wound
applications.
In each case, this is a special version for the triple-wound
application, each of which is described separately.
3.5.1.3 Current inputs
(Terminals 1, 3 and 4, 6 and 7, 9)
A connection to a power supply is not required for normal
regulator operation.
In many cases, however, the voltage must be raised and/or
lowered according to the respective load.It is necessary to connect the current transformer I1 (1 and 3)
to carry out this additional task.
However, even without current-dependent regulation, we
recommend connecting the current, because this means that
network can be measured and displayed in the measurement
transducer mode.
Ensure that the correct connection (k, l!) is used when
connecting the current transformer.
Two current transformers must be connected for carrying out
measurements in arbitrarily loaded three-phase networks.
The third current can be calculated on the basis of both of the
measured currents. The third current connection (4, 6) is
reserved for special cases, which will be described separately.
The changeover from 1 A to 5 A or vice-versa is accomplished
via the menu. The use of hardware such as a bridge or jumper
is not necessary.
Caution!Please observe that the line(s) must be short-circuited
before releasing the lines on terminals 1/3, 4/6 and 7/9.
-
8/21/2019 A-eberle Relay Reg Da
33/31633
REG-DA
REG-DA operating manual
3.5.1.4 Relay outputs
(Terminals 33 ... 59)
The REG-DA Relay for Voltage Control & TransformerMonitoring has 13 relays.
Relay 13 is used as a life contact and monitors the running of
the processor as well as the supply voltages of the system.
Relays 1 ... 12 are available for regulating and controlling the
transformer.
Relays R1, R2 and R12 are permanently assigned to specific
functions, whereas all of the other relays are freely
programmable. The relays are programmed with frequentlyused functions when delivered.
R1 ... R13: Potential-free relay contacts
Load: 250 V AC, 5 A, cos= 1,250 V DC, 150 W (also refer to
Page 14)
Relays R1 and R2 may be switched as follows in order to lock
a control command:
R1
Raise
R2
Lower
-
8/21/2019 A-eberle Relay Reg Da
34/31634
REG-DA
REG-DA operating manual
3.5.1.5 Binary inputs, feature D0/D1
(Terminals 11 ... 32)
The REG-DA Relay for Voltage Control & TransformerMonitoring has 16 binary inputs.
Only inputs 5 and 6 (Manual/Automatic) are permanently
assigned. All of the other inputs can be programmed freely.
Frequently used input functions are already assigned to some
of the inputs when it is delivered (see table on page 24 to page
26).
3.5.1.6 Binary inputs and resistance inputsfor tap-change potentiometer (D2/D3)
(Terminals 11 ... 26)
Only binary inputs 5 and 6 (Manual/Automatic) are permanently
assigned. All of the other binary inputs can be programmed
freely. Frequently used input functions are already assigned to
some of the inputs when it is delivered (see table on Page 24 to
Page 26).
Feedback of the tap-change position is often sent back to theRelay for Voltage Control & Transformer Monitoring as a BCD
code.
The binary inputs are parameterised to correspond with the
number of steps in this case (see "Binary inputs, feature D0/D1"
on page 34, terminals 23 to 32).
-
8/21/2019 A-eberle Relay Reg Da
35/31635
REG-DA
REG-DA operating manual
If the tap-change position is supplied as a resistance value (e.g.
10 Ohm / tap-change position), the resistance module can be
connected directly to terminals 23 to 26.
For further information see "Resistance Measuring Equipment
for Tap-Changers with Resistance-Coded Tap-Change
Signalling" on page 187:
3.5.2 Pin assignment level II
Level II is not equipped in the standard version of the Relay for
Voltage Control & Transformer Monitoring.
However, a larger number of additional inputs and outputs can
be provided via this connection level if additional binary or
analogue inputs/outputs are required.
The equipment changes according to features C01 to C99.
A total of four different modules are available, that can be used
in any combination if required.
Module 1: 6 binary inputs
Module 2: 6 relay outputs
Module 3: 2 mA inputs
Module 4: 2 mA outputs
The connection assignment of the individual features can be
found in the terminal diagram.
-
8/21/2019 A-eberle Relay Reg Da
36/31636
REG-DA
REG-DA operating manual
Feature C01
6 additional binary inputs 48 ... 250 V AC/DC
Feature C02
12 additional binary inputs 48 ... 250 V AC/DC
No.
Module1
100 Binary input E17
101 Binary input E18
102 Binary input E19
103 Binary input E20
104 Binary input E21
105 Binary input E22
106 GND E17 ... E22
No.
Module1
100 Binary input E17
101 Binary input E18
102 Binary input E19
103 Binary input E20
104 Binary input E21
105 Binary input E22
106 GND E17 ... E22
Module1
107 Binary input E23
108 Binary input E24
109 Binary input E25
110 Binary input E26
111 Binary input E27
112 Binary input E28
113 GND E23 ... E28
-
8/21/2019 A-eberle Relay Reg Da
37/31637
REG-DA
REG-DA operating manual
Feature C03
6 additional relay outputs (NO contacts)
Feature C04
12 additional relay outputs (NO contacts)
No.
Module2
100 R14
101 R15
102 R16
103 R17
104 R18
105 R19
106 GND R14 ... R19
No.
Module2
100 R14
101 R15
102 R16
103 R17
104 R18
105 R19
106 GND R14 ... R19
Module2
107 R20
108 R21
109 R22
110 R23
111 R24
112 R25
113 GND R20 ... R25
-
8/21/2019 A-eberle Relay Reg Da
38/31638
REG-DA
REG-DA operating manual
Feature C05
6 additional binary inputs 48 ... 250 V AC/DC and
6 relay outputs (NO contacts)
Feature C06
2 additional analogue inputs
No.
Module1
100 Binary input E17
101 Binary input E18
102 Binary input E19
103 Binary input E20
104 Binary input E21
105 Binary input E22
106 GND E17 ... E22
Module2
107 R14
108 R15
109 R16
110 R17
111 R18
112 R19
113 GND R14 ... R19
No.
Module
3100
Analogue input+
E10
101 -
102Analogue input
+E11
103 -
-
8/21/2019 A-eberle Relay Reg Da
39/31639
REG-DA
REG-DA operating manual
Feature C07
4 additional analogue inputs
Feature C08
2 additional analogue outputs
Feature C09
4 additional analogue outputs
No.
Module3
100Analogue input
+E10
101 -
102Analogue input
+E11
103 -
Mod
ule3
104Analogue input
+E12
105 -
106Analogue input
+E13
107 -
No.
Module
4100
Analogue output+
A10
101 -
102Analogue output
+A11
103 -
No.
Module4 100 Analogue output + A10
101 -
102Analogue output
+A11
103 -
Module4
104Analogue output
+A12
105 -
106Analogue output
+A13
107 -
-
8/21/2019 A-eberle Relay Reg Da
40/31640
REG-DA
REG-DA operating manual
The hardware for all the control system connections is also
contained on level II.
The corresponding connection elements on level II must be
used for RS232 or RS485 connections.If the Ethernet connection is used (required for IEC 61850 or
IEC 60870-5-104 connections!), the corresponding connection
is also accessible on level II.
Please refer to the configuration documentation supplied with
this operating manual, since the terminal assignment can be
very different for the individual interfaces.
The connection elements for fibre-optic cables (send and
receive diodes as ST or FSMA connection) are mounted directly
on the flange plate and can be connected there withoutopening the device.
Fibre-optic cable connection
(FSMA-connection system)
Fibre-optic cable connection
(ST-connection system)
-
8/21/2019 A-eberle Relay Reg Da
41/31641
REG-DA
REG-DA operating manual
3.5.3 Pin assignment level III
It is possible to access interfaces COM 1, COM 2 and COM 3
via level III.
The connection elements for the E-LAN transport bus and
certain combinations of analogue inputs and outputs (Features
E91 to E99) are also available via level III.
Interface COM 1
Function Pin
DCD 1
RXD 2
TXD 3
DTR 4
Signal-Ground 5
DSR 6
RTS 7
CTS 8
RI 9
-
8/21/2019 A-eberle Relay Reg Da
42/31642
REG-DA
REG-DA operating manual
Equipping analogue inputs is dependent on the selected
structure of the features.
Both mA inputs and mA outputs may be implemented.
A module can be supplied for measuring the oil temperature
(transformer monitoring), which can be directly attached to a PT
100.
The connection is designed as a three-conductor circuit andcan be used over a distance of approximately 100 m.
The inputs can operate continuously in a short-circuited or
open state. All inputs are electrically isolated from all of the other
COM 2, suitable for
connecting:
- Modem
- PC
- DCF 77
- E-LAN-L
- E-LAN-R
COM 3, only suitable
for connecting BIN-D
and ANA-D interface
components!
optional
-
8/21/2019 A-eberle Relay Reg Da
43/31643
REG-DA
REG-DA operating manual
circuits. The Relay for Voltage Control & Transformer
Monitoring is equipped with one analogue input as standard.
The type of use can be specified at the time of ordering, or a
specific measurement quantity can be assigned using WinREGor the device's keyboard.
The outputs can operate continuously in a short-circuited or
open state. All outputs are electrically isolated from all of the
other circuits.
-
8/21/2019 A-eberle Relay Reg Da
44/31644
REG-DA
REG-DA operating manual
3.6 Types of REG-DA Relay for Voltage Control &Transformer Monitoring
3.6.1 Wall-mounting version
The mounting bars provided must be screwed onto the rear of
the device.
The entire unit must be attached with suitable screws to/onto a
stable mounting surface.
If the mounting holes are drilled laterally, both mounting barscan also be folded inwards (see shaded area).
NotePlease note and use the enclosed hole pattern (last
page).
Mounting bars
Dimensions in mm
-
8/21/2019 A-eberle Relay Reg Da
45/31645
REG-DA
REG-DA operating manual
3.6.2 Panel-mounting version
After the cutout has been cut in the mounting panel, the four
grub screws (1) must be screwed into the bottom of the
housing. The device is then pushed through the cutout and is
fixed with the two clamping angles (2).
In general, it is advisable to remove the flange plate first, then
push the housing through the cutout.
(1)
(2)(2)
(1)
-
8/21/2019 A-eberle Relay Reg Da
46/31646
REG-DA
REG-DA operating manual
3.6.3 Mounting on Standard Mounting Rails
The Relay for Voltage Control & Transformer Monitoring can
also be mounted on 35 mm standard mounting rails.
-
8/21/2019 A-eberle Relay Reg Da
47/31647
REG-DA
REG-DA operating manual
4 Operation
4.1 Display and control elements
The MPC operation level (people-process communication) of
the REG-D Relay for Voltage Control & Transformer Monitoring
is implemented as a membrane keypad with integrated light-
emitting diodes (LEDs).
Indicators and labels
Seven labels are available. Each label is designed for two
signals (2 LEDs).
The labelling of each individual field may be changed at any time
by pulling the label strip downwards out of the clear vinyl
pocket.
Function keys
Indicators
Field
Label
Parameterisation
FieldTransformer control
LCD displayLEDField 1
LEDField 7
.
.
.
.
.
.
.
.
Label strips
-
8/21/2019 A-eberle Relay Reg Da
48/31648
REG-DA
REG-DA operating manual
NoteFurther label strips can be found in Annex 2.
A program for generating label strips called
Beschriftungsprogramm.xlscan be found on the programCD.
If you have a colour printer at your disposal, the
individual fields can even be printed in colour (yellow and
red).
Any standard pen can be used to write on the labels.
Indicator 1 is programmed as default and cannot be changed.
LED 1 in field 1 (green) lights up when the device is
operating fault-free (service).
LED 2 in field 1 (red) lights up when the device has a fault
(blocked).
The LEDs in field 2 to field 5 (yellow) are freely
programmable for general signalling, and are not
programmed when delivered.
The LEDs in field 6 to field 7 (red) are freely programmable.
They are primarily intended for fault signals and are not
programmed when delivered.
Transformer control panel
7 keys are assigned to the transformer control panel.
The AUTOMATIC key with an integrated green LED
lights up when the Relay for Voltage Control & Transformer
Monitoring is functioning in the Automatic operating mode.The Manual key with integrated red LED lights up
when the Relay for Voltage Control & Transformer Monitoring is
functioning in the manual mode.
The arrow keys Raise and Lower
can be used to manually select the taps of the transformer.
Prerequisite: The LOCAL key (red)
is activated.
All remote control commands via binary inputs or a serial
connection are suppressed when in the LOCAL setting.
Remote control is only possible in the REMOTE mode (green).
-
8/21/2019 A-eberle Relay Reg Da
49/31649
REG-DA
REG-DA operating manual
The REG-DA Relay for Voltage Control & Transformer
Monitoring was designed in such a way that all of the display
elements of the transformer control panel (Manual/Auto and
Local/Remote) have to be green when the operatingpersonnel leave the control room.
The ACK key is currently still out of operation.
In the future, this key will be able to be used to acknowledge
process signals and/or fault signals which the Relay for Voltage
Control & Transformer Monitoring generates itself and indicates
in the display.
Parameterisation panel
The keys in the parameterisation panel can be used to manually
parameterise the REG-DA Relay for Voltage Control &
Transformer Monitoring.
The Menu key is used to switch between the various
operating modes and to select a specific parameterization
menu (SETUP 1 ... SETUP 6)
The Return key is used to confirm a specific
parameter in the SETUP menus.
NoteChanges to the parameterisation which are important
for operation can only be carried out in the manual
operating mode.
The Esc key is used to exit any menu. The user can
move the cursor within the parameterisation menus using the
and keys.
Function keys
The function keys, F1 to F5 , are
implemented as so-called softkeys.
The function of the keys is context-controlled and depends on
the corresponding menu.
-
8/21/2019 A-eberle Relay Reg Da
50/31650
REG-DA
REG-DA operating manual
4.1.1 Display
LCD display
LCD Display Recorder Mode
Address at bus (station identification) Relay name Time
Setpoint value inSetpoint value in
regulative deviation
Backwards high-speed switching is indicated by
-
8/21/2019 A-eberle Relay Reg Da
51/31651
REG-DA
REG-DA operating manual
4.2 Operating principle
The operation of the REG-DA Relay for Voltage Control &
Transformer Monitoring is completely menu-guided and theprinciple is the same for each item in the SETUP menu.
The following operating principle applies for setting or changing
the regulation parameters:
MANUAL OPERATING MODEchanges the operating mode to
manual operation
MENU displays the list of operating modes
MENU selects the SETUP menu item
MENU can be used to scroll through the pages of
the SETUP menu selection until the required parameter
appears on the display.
Select a parameter via the corresponding function key
(F1 ... F5).
Set the value of the parameter via the function keys.
F1 increases the value in large steps
F2 increases the value in small steps
F4 increases the value in small steps
F5 decreases the value in large steps
F3 has a special function in some of the SETUP
menus.
After entering a value, the changed value is confirmed by
pressing RETURN .
If the entry is protected with a password, enter the
password (see "Password request" on page 95).
Return or leave the SETUP menus
ESC (CANCEL)
The SETUP menus will be automatically exited if no key ispressed for approx. 15 seconds.
-
8/21/2019 A-eberle Relay Reg Da
52/31652
REG-DA
REG-DA operating manual
The REG-DA Relay for Voltage Control & Transformer
Monitoring can be switched back to the automatic
operating mode using AUTO once the required
parameters are entered, checked and individually
confirmed by pressing the RETURN key.
4.3 Selecting the display mode
The display modes of the REG-DA Relay for Voltage Control &
Transformer Monitoring can be selected after pressing the
MENU key.
The following modes are available:
Regulator Mode
Measurement transducer mode
Recorder mode
Statistics mode (Monitor mode)
ParaGramer mode
Regulator Mode The F1 key is used to select the RegulatorMode.
The display indicates the set setpoint
value in V (kV) and as a percentage of
the nominal voltage, the momentary
actual value, the value of the
permissible regulative deviation and the
present tap-changer position of the
tap-changing transformer.
The present deviation of the setpoint is
also indicated on a scale (by an
analogue pointer) with a bandwidth of 10%.
The colour of the scales pointer changes from transparent
to black if the specified permissible regulative deviation is
overshot or undershot.
-
8/21/2019 A-eberle Relay Reg Da
53/31653
REG-DA
REG-DA operating manual
If required, the present value of the current may also be
displayed.
Note If Actual Value is displayed in capital letters, i.e.
ACTUAL VALUE, then the MEASUREMENT VALUE
SIMULATION is active!
(see Page 146).
Measurement
transducer
mode
The F2 key is used to select the Measurement
Transducer Mode.
When the Relay for Voltage Control & Transformer Monitoring
carries out measurements in the Aron circuit (feature M2), a
second measurement transducer screen can be selected todisplay the measured values of the three-phase current
networks loaded according to the requirements of the user.
NoteIn the measurement transducer mode, only the reactive
current I sinof each transformer will be displayed.However, it is not possible to determine on the basis of
this display which share of the current pertains to the
load and which pertains to the reactive current.
The second measurement transducer screen can be selected
by pressing either the or key.
-
8/21/2019 A-eberle Relay Reg Da
54/31654
REG-DA
REG-DA operating manual
The third transducer screen may be selected by pressing either
the or key.
If the device is switched in parallel, it is advantageous to display
the circulating reactive current as well.
The circulating current Icirc provides information about the
share of the current that is circulating in the parallel-switched
transformers and not taken up by the load.
The quasi-analogue scale illustrates the relationship between
the circulating reactive current Icirc and the permissible
circulating reactive current perm. Icirc.
If the permissible Icirc is 50 A, the circulating reactive current
Icirc is actually -100 A and the value -2 is shown on the scale.
If the circulating current becomes zero, the quotient will also
become zero and the pointer will be positioned in the middle of
the scale.
However, generally speaking, this ideal situation can in practice
only then be reached when the parallel-switched transformers
exhibit the same electrical features.
Recorder mode The F3 key is used to select the RecorderMode.
As standard, every Relay for Voltage
Control & Transformer Monitoring is
equipped with a DEMO recorder
(feature: DEMO in the lower left corner
of the grid).
Above the grid, the set permissibleregulative deviation is displayed by
means of two black arrows. In this
manner, the recorder display is capable
-
8/21/2019 A-eberle Relay Reg Da
55/31655
REG-DA
REG-DA operating manual
of supplying all of the information needed for operating the
Relay for Voltage Control & Transformer Monitoring (see "LCD
Display Recorder Mode" on page 50).
In addition to the value of the present voltage and the tap-
changer position (in the lower left-hand corner), the display also
indicates the permissible regulative deviation (black arrows
above the grid) and the change of the voltage over a period of
time (past values).
Within the grid, the present voltage is the value which intersects
the lower line of the two parallel border lines at the top of the
grid.
Independent of the selected feedrate speed (F4), the memorystores values at a constant rate of 1 second.
Each 1 second value is composed of 10 100ms values.
Seven scale divisions are available in total on the display. Thus,
a maximum time range of 7 x 10 minutes (70 minutes) may be
shown on the screen.
The shortest time range with the biggest optical resolution is 7
x 14 seconds (98 seconds).
Apart from the voltage, the recorder can also record the currentand the angle . The tap-changer position and the setpointvalue with tolerance band are always recorded as well.
In the second recorder menu (F3-F3), the desired mode can be
selected via the menu item Number of channels (F4). It is
possible to change modes at any time without loss of data.
Displaying the recorder data
In the first recorder menu (F3), the menu item Dual Display (F4)
can be used to switch the recorder display between the one-
channel display of U and the two-channel display. The leftchannel is always reserved for the control voltage U. The Relay
for Voltage Control & Transformer Monitoring offers a selection
of measurement quantities for the second channel (see 2nd
recorder menu).
The time axis is the same for both curves. Only the resolution of
the left channel can be changed using the dx (F5 key); the
scale of the second channel remains the same.
-
8/21/2019 A-eberle Relay Reg Da
56/31656
REG-DA
REG-DA operating manual
Derived variables from the recorder data
In the first recorder menu (F3,F3), the
menu item MMU display (F5) can be
used to switch the display of variables
derived from the present cursor value
(at the very top) on and off.
I and S are displayed as numeric values
if only two recorder channels (U + I)
have been selected (second recorder
menu (F3, F3, F4)).
If all three recorder channels (U + I + ) are activated, then I, ,P and Q will be displayed as numeric values.
It is also possible to search for an event in the second recordermenu. If both the date and the time of a certain event are
known, a specific day and time can be selected in the Time
Search submenu.
After returning to the recorder main menu (by pressing F3 or
Enter), the recorder lists the selected time and displays all of the
electrical measurement values as well as the corresponding
tap-changes.
Statistics mode The F4 key is used to select the StatisticsMode.
The total number of tap-changes made
since the counter was last set to zero is
shown on the display. Thus tap-
changes made under load and tap-
changes made with a load of less than
5% of the nominal current In(1 A or 5 A)
are distinguishable.
Changes made under load areadditionally displayed for each tap-
change.
NoteIf the tap-changer is working under load (I > 0.05 In), adouble arrow >> indicates the present tap-changer
position.
If the load condition is not fulfilled, the present tap-
changer position will be indicated by a single arrow >.
In conjunction with the recorder, the statistics mode provides
valuable information regarding the controlled system.
-
8/21/2019 A-eberle Relay Reg Da
57/31657
REG-DA
REG-DA operating manual
The parameters Time factor and Permissible regulative
deviation can be used to reach an optimum between the
voltage stability and the number of tap-changes. However, this
relation cannot be calculated mathematically as it is subject tothe individual conditions at the respective feeding point.
ParaGramer F5 selects ParaGramer mode.
The ParaGramer is a tool used for
automatically preparing parallel
connections and for the one-line
display of the switching status.
The artificial word ParaGramer is
derived from the terms
parallel and one-line diagram.
The ParaGramer displays the switching
status of the individual transformers in one-line graphics and
can be loaded by pressing the F5 key in the main menu.
The function is activated by feeding a complete busbar replica
(positions of the circuit breakers, disconnectors, bus ties and
bus couplings) into each Relay for Voltage Control &
Transformer Monitoring by means of binary inputs.
On the basis of the switching statuses, the system can
independently recognise which transformer should work in
parallel operation with which other transformer(s) on a busbar.
The system treats busbars connected via bus couplings as one
single busbar.
As shown in the graphic, both transformers T1 and T3 are
working on busbar a, whereas transformer T2 is feeding on
busbar b.
If special crosslinks are needed
between the busbars, we recommend
that you contact the headquarters of
our company A. Eberle GmbH & Co.
KG for assistance, since it is not
possible to describe all the options in
this operating manual.
The crosslinks feature is depicted in
the graphic. With its assistance, two
busbars may be coupled crosswise.
Crosslink
-
8/21/2019 A-eberle Relay Reg Da
58/31658
REG-DA
REG-DA operating manual
Setup menus MENU selects the SETUP men 1
4.4 Lamp check
Press the F5 key to check the functions of the light-
emitting diodes on the front panel. Select F5 .
NoteThis check can only be carried out in the Regulator
Mode or Statistics Mode.
4.5 Resetting fault signals
To reset fault signals that occur, the operating mode must be
changed from AUTOMATIC to MANUAL and then back to
AUTOMATIC again.
4.6 Operating the recorder
F1 and F2 allow access to historical values.
The time and date corresponding to a particular event can be
found by setting the voltage-time diagram back to the time-
reference line (beginning of the grid at the top) using the F1
and F2 keys. The time, date, voltage value and
tap-changer position can then be read below the grid.
If historical data is displayed, the term HIST appears in the
lower left-hand corner of the grid. Display of past measurement
values may be aborted at any time by pressing the ESC
(CANCEL) key.
Press F3 to go to the recorder 1 menu. The scroll
displacement for searching using the F1 and
Time reference line
-
8/21/2019 A-eberle Relay Reg Da
59/31659
REG-DA
REG-DA operating manual
F2 keys (in recorder mode) can be set using the scroll
menu item. This helps to speed up the search procedure. It is
also possible to switch back and forth between Dual Display
and MMU display in the Recorder -1 menu.
Pressing the F3 key in the Recorder -1 menu will take
you to the Recorder -2 menu. In this menu a specific search
date and time can be set under the menu item Time Search.
The type of display (U, U+I, U+I+Phi, U+U2, U+OilT, U+WndT)
can be selected under the menu item Channel Display.
The time-line diagram for the selected point in time appears
after returning to the recorder mode again by pressing F3
.The Recorder 1 and Recorder 2 menus display the present
memory capacity status in % as well as in days.
-
8/21/2019 A-eberle Relay Reg Da
60/31660
REG-DA
REG-DA operating manual
The feedrate speed can be selected by pressing the F4
key. Four different times can be selected: 14 s, 1 min, 5 min, 10
min.
-
8/21/2019 A-eberle Relay Reg Da
61/31661
REG-DA
REG-DA operating manual
The dt values refer to the time which must pass before a scale
section (division) is recorded.
The scale of the 1st channel can be changed using the
F5 dx key.
An extension of WinREG permits the data to be read out.
The data may be archived on the PC from firmware version 1.78
onwards.
The evaluation program can also generate data records that
can be read by MS EXCEL.
Note
If the note DEMO appears in the lower left-handcorner of the grid of the regular recorder display, the
recorder is operating in demo mode. In this operating
mode, the recorder only records the measured values
for a period of 4 - 6 hours. After this period, the older
values are replaced by the new ones.
dT = 14sdT = 1m
dT = 5mdT = 10m
1 division
-
8/21/2019 A-eberle Relay Reg Da
62/31662
REG-DA
REG-DA operating manual
-
8/21/2019 A-eberle Relay Reg Da
63/31663
REG-DA
REG-DA operating manual
5 Commissioning
The REG-DA Relay for Voltage Control & Transformer
Monitoring is a complex device with many functions.
This variety of functions necessitates a comprehensive
operating manual.
It was considered whether it was better to fill the individual
screenshots with all the theoretical information, or whether it is
better to separate the two parts by summarising the
background information and guiding the reader through the
individual screens.
We finally decided to offer two separate parts with the
corresponding cross-references.
However, in order to make it as easy as possible to start the
parameterisation without constantly having to jump between
two sections, we have inserted a commissioning section which
enables a standard voltage regulation to be carried out step-by-step.
Thus we based the description on the most important functions
of voltage regulation.
A summary of the limit values with a short explanation and links
to the appropriate chapters can be found on Page 85
Whilst the parameterisation can be implemented using the
WinREG parameterisation program, this chapter only deals withparameterisation using the device keypad.
The parameters that are particularly important for voltage
regulation will be briefly mentioned in seven steps and the
parameterisation explained.
Further settings that are required in special cases can be found
in chapter 7.
After applying the operating voltage, the
REG-DA will indicate that it is in regulator mode.
Other modes, such as measurement transducer mode,
recorder mode, statistics mode and ParaGramer mode, can be
selected at any time.
-
8/21/2019 A-eberle Relay Reg Da
64/31664
REG-DA
REG-DA operating manual
Therefore it is important to realise that all modes run parallel to
each other in the background. If one selects the recorder mode
(for example), the regulating tasks and all the other
parameterised task settings will also naturally be processed.
Press MENU and then use the keys
F2 ... F5 to select the desired mode.
The individual operating modes are briefly described below.
In total, six SETUPs are designed for the parameterisation.
You can scroll through the individual SETUPs in the following
manner:
Starting at the main menu (regulator, measurement transducer,
recorder, statistics or ParaGramer), press MENU to enterSETUP 1.
Repeatedly pressing the MENU key selects SETUP 2 to SETUP
6.
If you are already in one of the SETUPs, you can reach all the
other menus by pressing the and keys.
Caution!
Please observe the Warnings and Notes on Page 9without fail!
-
8/21/2019 A-eberle Relay Reg Da
65/31665
REG-DA
REG-DA operating manual
5.1 Regulator mode
After the auxiliary voltage is applied, the Relay for Voltage
Control & Transformer Monitoring indicates that it is in regulator
mode.
The important parameters for assessing a regulation situation
are shown in this display mode.The tap-changer position and the present regulative deviation
are shown in addition to the actual voltage value. The present
regulative deviation is shown in quasi-analogue form.
If the pointer is at 0 the actual value is the same as the
setpoint value. If the regulative deviation is within the tolerance
range the pointer is transparent. If the regulative deviation is
outside the permissible regulative deviation the pointer changes
to black.
In this way one can judge the present condition of the controlled
system at a glance.
An alternative display with additional information the compactdisplay can be selected using the F1 key.
In addition to the actual value and the tap-changer position, the
setpoint value in V (kV) and % as well as the permissible
regulative deviation in % are shown in this display.
If you