A-eberle Relay Reg Da

download A-eberle Relay Reg Da

of 316

Transcript of A-eberle Relay Reg Da

  • 8/21/2019 A-eberle Relay Reg Da

    1/3161

    REG-DA

    REG-DA operating manual

    Operating ManualREG-DARelay for Voltage Control & Transformer

    Monitoring

    Issue 18.10.07/03

    Issue GB

    Version 10.2007

    Software Version

  • 8/21/2019 A-eberle Relay Reg Da

    2/3162

    REG-DA

    REG-DA operating manual

    REG-DARelay for Voltage Control & Transformer

    Monitoring

    Operating Manual

    Issue 18.10.07

    Copyright 2007 byA. Eberle GmbH & Co. KG..

    All rights reserved.

    Published by:

    A. Eberle GmbH & Co. KG

    Aalener Strae 30/32

    90441 Nuremberg, Germany

    Tel.: +49 (0) 911 / 62 81 08 - 0

    Fax No.: +49 (0)-911 / 66 66 64

    e-mail: [email protected]

    Internet: www.a-eberle.de, www.regsys.de

    The companyA. Eberle GmbH & Co. KGcannot be held liable for

    any damages or losses resulting from printing errors or changes

    in this operating manual.

    Furthermore,A. Eberle GmbH & Co. KGdoes not assume

    responsibility for any damages and losses resulting from

    defective devices or from devices altered by the user.

  • 8/21/2019 A-eberle Relay Reg Da

    3/3163

    REG-DA

    REG-DA operating manual

    Table of Contents

    1 Warnings and Information. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9

    2 Scope of Delivery. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11

    3 Technical Data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12

    3.1 Basic equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12

    3.2 Connection diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14

    3.3 Overview of features. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15

    3.4 Block diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 213.4.1 Block diagram for features D0/D1/D4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 213.4.2 Block diagram for features D2/D3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22

    3.5 Pin Assignment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 233.5.1 Pin assignment level I . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29

    3.5.2 Pin assignment level II . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35

    3.5.3 Pin assignment level III. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41

    3.6 Types of REG-DA Relay for Voltage Control & Transformer Monitoring . . . . . . . . . . . . . . . . . . . 443.6.1 Wall-mounting version . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44

    3.6.2 Panel-mounting version . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45

    3.6.3 Mounting on Standard Mounting Rails. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46

    4 Operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47

    4.1 Display and control elements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 474.1.1 Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50

    4.2 Operating principle. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51

    4.3 Selecting the display mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52

    4.4 Lamp check. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58

    4.5 Resetting fault signals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58

    4.6 Operating the recorder . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58

  • 8/21/2019 A-eberle Relay Reg Da

    4/3164

    REG-DA

    REG-DA operating manual

    5 Commissioning. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .63

    5.1 Regulator mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65

    5.2 Measurement transducer mode. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66

    5.3 Recorder mode. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67

    5.4 Statistics mode. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68

    5.5 ParaGramer mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69

    5.6 Choosing the language . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70

    5.7 Setpoint value . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70

    5.8 Permissible regulative deviation Xwz . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71

    5.9 Time behaviour. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72

    5.10 Backward high-speed switching . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75

    5.11 Tap-changer running time. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77

    5.12 Knx transformer mounting ratios and transformer connection . . . . . . . . . . . . . . . . . . . . . . . . . 79

    5.13 Setting the nominal current . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80

    5.14 Inhibit low limit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82

    5.15 Trigger. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84

    5.16 Short description of individual limit values, setpoint values and permissible regulative deviation. 85

    5.16.1 Description of the individual settings. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .85

    6 Basic Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91

    6.1 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 916.1.1 Station ID . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .91

    6.1.2 Station name. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .92

    6.1.3 Setting the time/date . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .93

    6.1.4 LCD contrast (display) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .94

    6.1.5 Password . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .94

    6.1.6 Deleting recorder data (resetting the measured value memory). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .95

    6.1.7 Deleting tap-change sums (resetting the tap-counter to zero). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .96

    6.1.8 Actual value correction of the measuring voltage UE. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .96

    6.1.9 Actual value correction of the measuring current IE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .96

    6.2 RS-232 interfaces . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 976.2.1 COM 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .97

    6.2.2 COM 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .99

    6.3 E-LAN (Energy-Local Area Network). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101

    6.4 PAN-D voltage monitoring unit. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104

    6.5 Status (current ID data of the REG-DA Relay for Voltage Control & Transformer Monitoring). . . 104

  • 8/21/2019 A-eberle Relay Reg Da

    5/3165

    REG-DA

    REG-DA operating manual

    7 Parameterisation of the REG-DA Relay for Voltage Control & Transformer

    Monitoring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 108

    7.1 Permissible regulative deviation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1097.2 Time behaviour (regulation behaviour) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1097.2.1 Time factor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 109

    7.2.2 Time program . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 110

    7.2.3 Trend memory. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 110

    7.3 Setpoints . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1117.3.1 1st setpoint value . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 111

    7.3.2 Further setpoint values. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 112

    7.4 Programs (parameters for parallel regulation of transformers and for the compensation of the

    voltage drop on the line) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1137.4.1 Selection of the parallel programs (regulation programs) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 113

    7.4.2 Parameters for the parallel program . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 114

    7.4.3 Current influence (line-drop compensation) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 116

    7.4.4 LDC parameter (line drop compensation). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 116

    7.5 Gradient (U/I characteristic). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 117

    7.6 Limitation (U/I characteristic). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 117

    7.7 < U Undervoltage. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 117

    7.8 > U Overvoltage. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 118

    7.9 > I, < Limit (upper and lower current limits). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1187.10 Trigger inhibit high (highest limit value of the voltage). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 119

    7.11 High-speed switching during undervoltage/overvoltage. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1207.11.1 High-speed switching when undervoltage occurs (RAISE) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 120

    7.11.2 High-speed switching when overvoltage occurs (LOWER) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 120

    7.12 REG-DA inhibit low when undervoltage occurs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 121

    7.13 Time delays (limit signals). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1217.13.1 Time delay > U . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 121

    7.13.2 Time delay < U . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 122

    7.13.3 Time delay > I, < I limit value. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1227.13.4 Time delay trigger . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 122

    7.13.5 Time delay forward high-speed switching . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 123

    7.13.6 Time delay backward high-speed switching . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 123

    7.13.7 Time delay inhibit low . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 124

  • 8/21/2019 A-eberle Relay Reg Da

    6/3166

    REG-DA

    REG-DA operating manual

    7.14 Add-Ons (Relay for Voltage Control & Transformer Monitoring behaviour). . . . . . . . . . . . . . . . 1247.14.1 Overview of the Add-Ons menus numbers 1 to 6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .124

    7.14.2 Maximum time TC in operation (motor-drive-in operation-time) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .126

    7.14.3 Manual/Automatic. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1277.14.4 Tap-changing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .128

    7.14.5 Self-conduction of the operating mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .129

    7.14.6 Current display (of the transformer) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .129

    7.14.7 LCD saver (display) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .130

    7.14.8 Regulator mode: large display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .130

    7.14.9 Language selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .131

    7.14.10 Parallel Program Activation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .132

    7.14.11 Up/down relay on time. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .132

    7.14.12 AUTO(MATIC) LOCK in the event of an E-LAN error . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .133

    7.14.13 Setpoint adjustment. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .133

    7.14.14 Creeping net breakdown . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .134

    7.14.15 Limit base (reference value) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .135

    7.14.16 Setting the Relay for Voltage Control & Transformer Monitoring to inhibit low if I . . . . . . . . . . . . . . .136

    7.14.17 Maximum tap difference (monitoring) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .136

    7.14.18 ParaGramer activation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .137

    7.15 Transformer configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1387.15.1 Transformer mounting voltage (measurement voltage) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .138

    7.15.2 Transformer mounting ratio for the voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .140

    7.15.3 Transformer mounting current (conductor connection) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .140

    7.15.4 Transformer mounting current (conversion 1 A / 5 A). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .140

    7.15.5 Transformer mounting ratio for the current . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .141

    7.16 Input assignments (binary inputs). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 142

    7.17 Relay assignments . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 143

    7.18 LED assignments . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 145

    8 Measurement Value Simulation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 146

    8.1 Setting the simulated voltage. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 148

    8.2 Setting the simulated current. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 148

    8.3 Setting the simulated phase angle . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1488.4 Setting the simulated tap-change . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 149

    9 Parallel Operation of Transformers with REG-DA . . . . . . . . . . . . . . . . . . . . . . . 150

    9.1 Circuit diagram (schematic). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 152

    9.2 Programs for parallel operation and their prerequisites . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1549.2.1 Preparation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .154

    9.2.2 Preparing manual activation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .156

    9.2.3 Preparing automatic activation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .163

    9.3 Parallel operation using the Master-Slave-Independent (MSI) procedure . . . . . . . . . . . . . . . 1739.3.1 Trouble-shooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .184

  • 8/21/2019 A-eberle Relay Reg Da

    7/3167

    REG-DA

    REG-DA operating manual

    10 Resistance Measuring Equipment for Tap-Changers with Resistance-Coded Tap-

    Change Signalling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 187

    10.1 Error detection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18810.2 Level detection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 188

    10.3 Pin assignment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 189

    10.4 Connection options. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 190

    10.5 Setting of the DIP switch S1 and S2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19110.5.1 Location of the switch on the circuit board: level 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 191

    11 mA-Inputs, mA-Outputs. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 192

    11.1 Analogue inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 193

    11.2 Analogue outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 203

    12 Updating the Operating Software . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 214

    12.1 Preparing the PC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21512.1.1 Windows NT/2000/XP operating system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 215

    12.2 Starting the bootstrap loader. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 215

    13 Maintenance and Current Consumption . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 220

    13.1 Cleaning information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 220

    13.2 Changng fuses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22113.3 Changing the battery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 221

    13.4 REG-DA Current Consumption. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 223

    13.5 Replacing the device . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 224

    14 Storage Information. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 225

    15 Background Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 226

    15.1 Regulator mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 226

    15.2 Command variable W . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22715.2.1 Fixed command variable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 227

    15.2.2 Variable command variable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 228

    15.2.3 Current-dependent setpoint value increment. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 231

    15.3 Summary and Examples for Current Influencing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 235

    15.4 Regulative deviations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23815.4.1 Regulative deviation Xw . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 238

    15.4.2 Permissible regulative deviation Xwz. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 238

    15.4.3 Displaying the regulative deviation Xw. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 239

    15.4.4 Setting the permissible regulative deviation Xwz . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 239

    15.5 Monitoring extreme operating values (faults) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24115.5.1 Limit signal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 241

  • 8/21/2019 A-eberle Relay Reg Da

    8/3168

    REG-DA

    REG-DA operating manual

    15.6 Add-Ons . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24615.6.1 High-speed switching add-on. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .246

    15.6.2 Relay for Voltage Control & Transformer Monitoring inhibit low function . . . . . . . . . . . . . . . . . . . . . . . . . .247

    15.6.3 Measuring the Creeping Net Breakdown . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24815.6.4 Maximum tap-change difference monitoring Add-On . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .250

    15.6.5 Add-On: monitoring the tap-changer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .250

    15.7 Time behaviour of the Relay for Voltage Control & Transformer Monitoring when a control command

    is output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25215.7.1 Determining the reaction delay tv . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .255

    15.7.2 Integrated time program . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .259

    15.7.3 Trend memory. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .260

    15.7.4 Const time program . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .262

    15.7.5 Setting the time factor Ft . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .266

    15.8 E-LAN (Energy Local Area Network) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 267

    15.9 Voltage regulation with transformers operating in parallel . . . . . . . . . . . . . . . . . . . . . . . . . . . 27115.9.1 Regulation programs for transformers operating in parallel. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .272

    15.9.2 Functional principle . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .273

    15.9.3 Influence of the circulating current regulation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .273

    15.9.4 Activation of the regulation program . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .274

    15.9.5 Description of the regulation programs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .275

    15.10 Nominal transformation of the measurement transformers . . . . . . . . . . . . . . . . . . . . . . . . . . 292

    15.11 Self-Conduct . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 293

    15.12 LCD display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29315.12.1 LCD contrast. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .293

    15.12.2 LCD Saver. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .293

    15.12.3 Background illumination. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .293

    16 Definition of the Abbreviations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 294

    17 Symbols and their Definition. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 300

    18 Factory Settings of the Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 303

    19 Notes on the Interpreter Language . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 305

    20 Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 306

    Appendix

    Labels

    Drill hole-pattern

  • 8/21/2019 A-eberle Relay Reg Da

    9/3169

    REG-DA

    REG-DA operating manual

    1 Warnings and Information

    The REG-DA Relay for Voltage Control & Transformer

    Monitoring is exclusively designed for implementation in

    systems and equipment for electrical energy technology. Only

    trained experts are permitted to carry out all required work.

    Experts are persons who are familiar with the installation,

    mounting, commissioning and operation of these types of

    products. Furthermore, experts have qualifications which

    correspond with the requirements of their field of work.

    The REG-DA Relay for Voltage Control & TransformerMonitoring left the factory in a condition that fulfils all relevant

    safety regulations. To maintain this condition and to ensure safe

    operation, the following instructions and warnings in this

    operating manual must be observed.

    The REG-DA Relay for Voltage Control & Transformer

    Monitoring has been designed to comply with IEC 10110/

    EN61010 (DIN VDE 0411), degree of protection I and was

    tested according to this standard before delivery.

    The REG-DA Relay for Voltage Control & TransformerMonitoring must be earthed via a protective earth

    conductor. This condition is fulfilled when the Relay for

    Voltage Control & Transformer Monitoring is connected to

    an auxiliary voltage with a protective earth conductor

    (European power supply system). If the auxiliary voltage

    power supply system does not have a protective earth

    conductor, an additional connection must be established

    from the protective earth conductor terminal to earth.

    The upper limit of the permissible auxiliary voltage UAUXmaynot be exceeded, neither permanently nor for a short period

    of time.

    Before changing the fuse, separate the REG-DA Relay for

    Voltage Control & Transformer Monitoring completely from

    the auxiliary voltage UAUX.

    The use of fuses other than those of the indicated type and

    rated current is prohibited.

    A REG-DA Relay for Voltage Control & Transformer

    Monitoring which displays visible damage or clearmalfunctioning must not be used and has to be secured

    against unintentionally being switched on.

  • 8/21/2019 A-eberle Relay Reg Da

    10/31610

    REG-DA

    REG-DA operating manual

    Maintenance and repair work on a REG-DA Relay for

    Voltage Control & Transformer Monitoring with an open

    door may only be carried out by authorised experts.

    Warning signs

    Please familiarise yourself with the nominal insulation voltage of

    the Relay for Voltage Control & Transformer Monitoring before

    connecting the device.

    Ensure that the voltages are connected via a disconnecting

    mechanism, and that the current path can be short circuited if

    there is a device fault to enable problem-free device

    replacement.

    When wiring, please ensure that the conductors are either

    bound short or kept sufficiently short so that they cannot reach

    level 2 or 3.

    If a fault occurs (connection becomes loose), no line that carries

    a voltage that is dangerous when touched (> 50 V) or line to

    which a nominal isolation voltage larger than 50 V is assigned,

    may come into contact with the circuits in levels 2 and 3.

    !

  • 8/21/2019 A-eberle Relay Reg Da

    11/31611

    REG-DA

    REG-DA operating manual

    2 Scope of Delivery

    1 REG-DA Relay for Voltage Control & Transformer Monitoring,

    with built-in components

    1 terminal diagram in English

    1 operating manual in English

    1 WinREG programming and parameterisation software

    1 cable

    1 replacement fuse

    2 tools

    (7 mm Allen key and special screwdriver for the terminals on

    levels 2 and 3)

  • 8/21/2019 A-eberle Relay Reg Da

    12/31612

    REG-DA

    REG-DA operating manual

    3 Technical Data

    3.1 Basic equipment

    Dimensions

    Lead sealing Each Relay for Voltage Control & Transformer Monitoring canbe locked with a password so that the parameters cannot be

    changed.

    The REG-DA can also be lead-sealed to show whether it has

    been opened by unauthorized persons.

    For this purpose, a lead-sealing wire is pulled diagonally

    through the bores in the lower right corner of the housing corner

    and is secured with a lead-sealing tool.

    This measure ensures that the device can only be opened by

    breaking the lead seal.

    Dimensions in mm

  • 8/21/2019 A-eberle Relay Reg Da

    13/31613

    REG-DA

    REG-DA operating manual

    Connection levels

    Side view (section) of opened housing

    NoteReference is made to the connection levels (levels I...III)

    in both the block diagram (Page 21) and the pin

    assignment (Page 23).

    Membrane keypad

    area III

    area II

    area I

  • 8/21/2019 A-eberle Relay Reg Da

    14/31614

    REG-DA

    REG-DA operating manual

    3.2 Connection diagram

    Contact load R1, R2: AC 250 V, 5 A, cos= 1,250 V DC, 150 W

    * Please observe the contact load at R1 and R2!

    (see below)!

    ** The connections for I and U can be freely assigned

    via the menu.

    110 V DC 230 V AC

    20 A Switch on 5 A @ cos= 1

    5 A Hold 3 A @ cos

    = 0.4

    0.4 A Switch off

  • 8/21/2019 A-eberle Relay Reg Da

    15/31615

    REG-DA

    REG-DA operating manual

    3.3 Overview of features

    REG-DA is a highly variable product.

    The operating manual must take this factor into account andprovide different descriptions for the for the various

    specifications.

    Because the features ... M2, S1... D4 ... are noted on the name

    plate of the device, but the relation to the function which it

    stands for is not always given, the complete structure of the

    device's features is listed here.

    Feature: ID

    REG-DA Relay for Voltage Control & Transformer

    Monitoring

    Basic version with E-LAN double interfaces,

    COM 2, COM 3 and a mA input channel for e.g.

    measuring the oil temperature

    or for the measuring of the tap-changer position using

    a measurement transducer

    with 16 binary inputs and 12 relay outputs plus status

    outputinclusive of WinREG parameterisation software for

    parameterisation, programming

    and displaying of all Relay for Voltage Control &

    Transformer Monitoring data incl. connecting cable

    Note: COM 2 is only freely accessible

    if a log connection is not required.

    REG-DA

    Design

    Panel-mounting or wall-mounting version

    (H x W x D) 307 x 250 x 102 mm

    with standard mounting rail adapter

    B0

    B1

    Current supply

    external

    85 V ... 110 V ... 264 V AC / 88 V ... 220 V ... 280 V DC

    external 18 V ... 60 V ... 72 V DC

    H0

    H2

    Input currents (can be changed later)

    IEN1A

    IEN5A

    F1

    F2

  • 8/21/2019 A-eberle Relay Reg Da

    16/31616

    REG-DA

    REG-DA operating manual

    Measurement transducer display functions for network

    quantitiesThree-phase current with balanced load

    Three-phase current with unbalanced load

    Voltage (HV-side), current and voltage (MV-side)

    measurement

    Other uses of the three current and two voltage

    transformers

    M1

    M2

    M3

    M9

    Recorder functions

    for network quantities with evaluation software

    WithoutWith S0S1

    Transformer monitoring

    Without

    With

    T0

    T1

    Parallel operation

    Without firmware for parallel operation

    With firmware for parallel operation

    K0

    K1

    Feature: ID

  • 8/21/2019 A-eberle Relay Reg Da

    17/31617

    REG-DA

    REG-DA operating manual

    Additional analogue inputs and outputs

    WithoutWith one a PT 100 input

    With two mA inputs

    With two mA outputs

    With one PT 100 input and one mA output

    With two mA inputs and one mA output

    With three mA outputs

    Tap-change potentiometer input

    Total resistance 200 Ohm ... 2 kOhm

    Tap-change potentiometer input

    Total resistance >2 kOhm ... 20 kOhmOther combinations of inputs and outputs

    Note about E91 ... E99:

    Please specify the scale if known!

    Example: 1 -100 ... 0 ... +100 MW

    -20 ... 0 ... +20 mA

    Example: 2 0 ... 80 ... 120 V

    4 ... 16 ... 20 mA

    Example: 3 1 ... 19 levels

    0 ... 20 mA

    Example: 4 50 ... 140C

    4 ... 20 mA

    E00E91

    E92

    E93

    E94

    E95

    E96

    E97

    E98E99

    Feature: ID

  • 8/21/2019 A-eberle Relay Reg Da

    18/31618

    REG-DA

    REG-DA operating manual

    Binary inputs and tap-changer potentiometer input

    16 binary inputs 48 ... 250 V AC/DC8 binary inputs 10 ... 48 V AC/DC

    and 8 binary inputs 48 ... 250 V AC/DC

    1 tap-change potentiometer input

    (total resistance 200 ... 2 kOhm)

    and 8 binary inputs 48 ... 250 V AC/DC

    1 tap-change potentiometer input

    (total resistance >2 ... 20 kOhm)

    and 8 binary inputs 10 ... 48 V AC/DC

    16 binary inputs 10 ... 48 V AC/DC

    1 tap-change potentiometer input(total resistance 200 ... 2 kOhm)

    and 8 binary inputs 10 ... 48 V AC/DC

    1 tap-change potentiometer input

    (total resistance >2 ... 20 kOhm)

    and 8 binary inputs 48 ... 250 V AC/DC

    D0D1

    D2

    D3

    D4

    D5

    D6

    Level II: additional inputs and outputs

    Without

    With 6 binary inputs 48 ... 250 V AC/DC

    With 12 binary inputs 48 ... 250 V AC/DCWith 6 relay outputs

    With 12 relay outputs

    With 6 binary inputs and 6 relay outputs

    With 2 analogue inputs

    With 4 analogue inputs

    With 2 analogue outputs

    With 4 analogue outputs

    Other combinations 6 inputs, 6 outputs, 2 analogue

    inputs, 2 analogue outputs

    Note about C90: Two terminals are normally available

    on level II.

    Each terminal can be equipped with either 6 binary

    inputs, 6 binary outputs or an analogue module.

    Either 2 inputs or 2 outputs are available per analogue

    module.

    Up to 4 additional modules can be equipped assuming

    that a control system connection (XW90, 91 or L1, L9)

    is not used.

    C00

    C01

    C02C03

    C04

    C05

    C06

    C07

    C08

    C09

    C90

    Feature: ID

  • 8/21/2019 A-eberle Relay Reg Da

    19/31619

    REG-DA

    REG-DA operating manual

    Integrated control system connection according to:

    IEC61850 or IEC 60870- 5-104Without

    IEC 60850 - 5 - 104 (more in feature group G)

    Note: Please specify the target system for connections

    according to IEC 60850-5-104

    IEC 61850 (more in feature group G)

    XW00

    XW90

    XW91

    Integrated control system connection according to: IEC

    60870- 5-101/ ..-103,DNP

    Without (more in feature group G)

    for the control system connection of a REG-DAFor the control system connection of multiple systems

    (REG-D/DA/DP, etc.)

    Note: L9 can only be combined with feature XW90,

    Z15 to Z19 and Z91.

    L0

    L1L9

    Type of connection:

    Copper RS 232

    RS 485 only for 2-wire operation

    Fibre-optic cable with FSMA connection system

    Glass fibre(Wavelength 800...900 nm, range 2000 m)

    Plastic fibre

    (Wavelength 620...680 nm, range 50 m)

    Fibre-optic cable with ST connection system

    Glass fibre

    (Wavelength 800...900 nm, range 2000 m)

    Plastic fibre

    (Wavelength 620...680 nm, range 50 m)

    V10

    V11

    V13

    V15

    V17

    V19

    Feature: ID

  • 8/21/2019 A-eberle Relay Reg Da

    20/31620

    REG-DA

    REG-DA operating manual

    Log:

    IEC60870-5-103 for ABBIEC60870-5-103 for Areva

    IEC60870-5-103 for SAT

    IEC60870-5-103 for Siemens (LSA/SAS)

    IEC60870-5-103 for Sprecher Automation

    IEC60870-5-103 for others

    IEC60870-5-101 for ABB

    IEC60870-5-101 for IDS

    IEC60870-5-101 for SAT

    IEC60870-5-101 for Siemens (LSA/SAS)IEC60870-5-101 for others

    DNP 3.00

    LONMark

    SPABUS

    MODBUS RTU

    Z10Z11

    Z12

    Z13

    Z14

    Z90

    Z15

    Z17

    Z18

    Z19Z91

    Z20

    Z21

    Z22

    Z23

    Operating Manual

    German

    EnglishFrench

    Spanish

    Italian

    Russian

    Other

    G1

    G2G3

    G4

    G5

    G6

    G9

    Display text

    German

    English

    French

    SpanishItalian

    Russian

    Other

    A1

    A2

    A3

    A4A5

    A6

    A9

    Feature: ID

  • 8/21/2019 A-eberle Relay Reg Da

    21/31621

    REG-DA

    REG-DA operating manual

    3.4 Block diagrams

    3.4.1 Block diagram for features D0/D1/D4

  • 8/21/2019 A-eberle Relay Reg Da

    22/31622

    REG-DA

    REG-DA operating manual

    3.4.2 Block diagram for features D2/D3

  • 8/21/2019 A-eberle Relay Reg Da

    23/31623

    REG-DA

    REG-DA operating manual

    3.5 Pin Assignment

    Signals with non-exposed voltages are connected first of all on

    level I.All of the circuits on level I have a nominal insulation voltage of

    > 50 V and are therefore considered to be non-exposed in

    accordance with VDE 0110 (exception: resistance input,

    feature D2/D3).

    Please observe this condition even if small voltages are present

    at the relay contacts or the binary inputs.

    Terminal area on connection level III

    Terminal area on connection level I

    Terminal area on connection level II

  • 8/21/2019 A-eberle Relay Reg Da

    24/31624

    REG-DA

    REG-DA operating manual

    *) The Relay for Voltage Control & Transformer Monitoring with

    feature M1 provides only one voltage input. One voltage

    transformer is sufficient for standard regulating functions.

    When carrying out measurements in arbitrarily-loaded three-

    phase current systems, the three external-conductor voltages

    must be connected to terminals 2, 5 and 8 (Feature M2).

    Triple-wound applications function with two separate input

    voltages U1and U2.

    LevelI

    No. M1 * M2 * Triple*-

    woundregulator

    2 Voltage inputU1

    UL1U1

    5 Voltage input UL2

    8 Voltage input

    UL3U2

    10 Voltage input

    1 kCurrent input I1

    3 I4 k

    Current input I26 I

    7 kCurrent input I3

    9 I

    21 L / (+)Auxiliary voltage

    22 L / (-)

  • 8/21/2019 A-eberle Relay Reg Da

    25/31625

    REG-DA

    REG-DA operating manual

    NoteAll of the inputs and relay outputs are freely

    programmable, with the exception of inputs 5 and 6 and

    the outputs R1, R2, R12and R13.

    The assignment specified in the terminal diagramcorresponds to the delivery state and can be changed if

    necessary.

    LevelI

    No. D0, D1, D4 D2, D3

    11 Input 1 Tap-changer in progress

    12 Input 2 Freely programmable

    13 Input 3 Freely programmable

    14 Input 4 Freely programmable

    15 Input 1...4 GND

    16 Input 5 AUTO / MANUAL -

    AUTO

    (see Page 127)17 Input 6 MANUAL

    18 Input 7 Freely programmable

    19 Input 8 Freely programmable

    20 Input 5...8 GND

    23 Input 9 BCD 1

    please also

    refer to Page

    34

    24 Input 10 BCD 2

    25 Input 11 BCD 4

    26 Input 12 BCD 8

    27 Input 9...12 GND

    28 Input 13 BCD 10

    29 Input 14 BCD 20

    30 Input 15 BCD signal

    31 Input 16 Freely programmable

    32 Input 13 ... 16 GND

  • 8/21/2019 A-eberle Relay Reg Da

    26/31626

    REG-DA

    REG-DA operating manual

    LevelI

    No.

    33Freely programmable R5

    34

    35Freely programmable R4

    36

    37Freely programmable R3

    38

    39

    Lower R240

    41

    42

    43

    Raise R144

    45

    4647 > I R11

    48 >U R10

    49

  • 8/21/2019 A-eberle Relay Reg Da

    27/31627

    REG-DA

    REG-DA operating manual

    LevelII

    No.

    IEC

    LON

    DNP 3.0

    SPA bus

    Modbus

    For additional equipping possibilities for level II see "Pin

    assignment level II" on page 35.

    The connections of the control system can be found in the

    information attached to the operating manual.

    LevelIII

    No.

    63 mA input +A1 (standard equipment)

    64 mA input -

    61 Input or

    output

    +

    A2

    62 Input oroutput

    -

    65 Input or

    output

    +

    A366 Input or

    output

    -

    67 Input or

    output

    +

    A4

    68 Input oroutput

    -

    65

    66

    68

    Pt100

  • 8/21/2019 A-eberle Relay Reg Da

    28/31628

    REG-DA

    REG-DA operating manual

    LevelIII

    No.

    69 E-

    E-LAN (L)70 E+

    71 EA-

    72 EA+

    73 E-

    E-LAN (R)74 E+

    75 EA-

    76 EA+

    77 Tx +

    COM 3 (RS 485)78 Tx -

    79 Rx +

    80 Rx -

    81 du dont use

    82 TxD

    COM 2 (RS 232)

    83 RxD

    84 RTS

    85 CTS

    86 GND

  • 8/21/2019 A-eberle Relay Reg Da

    29/31629

    REG-DA

    REG-DA operating manual

    3.5.1 Pin assignment level I

    3.5.1.1 Auxiliary voltage, current input and voltage input

    Terminals 21, 22 and 1 to 10

    The REG-DA Relay for Voltage Control & Transformer

    Monitoring is equipped for carrying out measurements in

    arbitrarily loaded three-phase current networks. Therefore, up

    to three current transformers are available.

    Voltage regulation generally only requires a single-phase

    connection (one delta or phase voltage and one line current),because it may be assumed that the network conditions at the

    transformer are approximately symmetrical (feature M1).

    If a more precise measurement of the outputs (P, Q, S) is

    required, it is possible to switch over to the Aron circuit. In this

    case, two voltages and two currents must be connected

    (feature M2).

    The third current input is reserved for special cases, which must

    be coordinated before the device is delivered.

  • 8/21/2019 A-eberle Relay Reg Da

    30/31630

    REG-DA

    REG-DA operating manual

    Auxiliary voltage (terminals 21 and 22)

    The protective earth must be connected first, because the

    REG-DA is a device with degree of protection I.

    A plug-in shoe (6.3 x 0.8 mm) is provided in the lower part of

    the housing for connecting the protective earth.

    The auxiliary voltage is supplied via the twin connector block

    (terminals 21 and 22).

    Two types of power supply units are available:

    Therefore, please ensure that the intended supply voltage

    corresponds to the auxiliary voltage of the device as stated on

    the printed nameplate, before connecting.

    Feature H0:

    Both direct and alternating voltages may be connected.

    Ranges: 88 V ... 220 V ... 280 V DC

    85 V ... 110 V ... 264 V AC

    Power consumption: < 15 VA

    Feature H1:

    18 V ... 60 V ... 72 V DC

    Power consumption: < 10 W

    The auxiliary voltage, and thus the power supply of the device,

    is protected by a T2L 250 V microfuse.The fuse holder can be opened with a screwdriver. The device

    is supplied with a spare fuse.

    Flat-plug

    connection

    for protective

    earth

  • 8/21/2019 A-eberle Relay Reg Da

    31/31631

    REG-DA

    REG-DA operating manual

    NotePlease note that the fuse catch should never be

    screwed on without having a fuse inserted, because

    otherwise it is difficult to open the fuse holder.

    3.5.1.2 Control voltage

    (Terminals 2, 5 and 8, 10)

    The control voltage must be connected to the terminals 2 and

    5.

    Any voltage from the three-phase current network can be used

    as the control voltage. The type of voltage (delta or phasevoltage, UL1L2, UL2L3, UL3L1, U1N, U2N, U3N) must be

    communicated to the Relay for Voltage Control & Transformer

    Monitoring via the menu (SETUP 5, F2).

    The permissible nominal application range of the control voltage

    ranges from 60 to 140 V and is expressed in terms of delta

    voltage.

    If there is a connection between the phase and N, the nominal

    application range of 34.6 to 140 V becomes available.

    Please note that a single-pole high-resistance earth connection

    affects L1 like a voltage dip if only a phase voltage (e.g. L1N) is

    available for measuring the actual value of the voltage.

    If a phase voltage is used as the control voltage rather than the

    recommended delta voltage, you must pay attention to the

    behaviour if a single-pole earth fault occurs.

    In high-resistance faults, situations may occur where the

    voltage appears to be too high or too low.

    The Relay for Voltage Control & Transformer Monitoring

    generally switches itself into standby mode for low resistancefaults.

    Strongly distorted signals may also be connected by means of

    a complex filtering of the measurement voltages and the

    measurement currents.

    If feature M2 is used, voltage UL1must be connected to terminal

    2, voltage UL2to terminal 5 and voltage UL3to terminal 8.

    i.e.:UL12UL25UL38

  • 8/21/2019 A-eberle Relay Reg Da

    32/31632

    REG-DA

    REG-DA operating manual

    Voltage inputs U1 and U2 are both available for triple-wound

    applications.

    In each case, this is a special version for the triple-wound

    application, each of which is described separately.

    3.5.1.3 Current inputs

    (Terminals 1, 3 and 4, 6 and 7, 9)

    A connection to a power supply is not required for normal

    regulator operation.

    In many cases, however, the voltage must be raised and/or

    lowered according to the respective load.It is necessary to connect the current transformer I1 (1 and 3)

    to carry out this additional task.

    However, even without current-dependent regulation, we

    recommend connecting the current, because this means that

    network can be measured and displayed in the measurement

    transducer mode.

    Ensure that the correct connection (k, l!) is used when

    connecting the current transformer.

    Two current transformers must be connected for carrying out

    measurements in arbitrarily loaded three-phase networks.

    The third current can be calculated on the basis of both of the

    measured currents. The third current connection (4, 6) is

    reserved for special cases, which will be described separately.

    The changeover from 1 A to 5 A or vice-versa is accomplished

    via the menu. The use of hardware such as a bridge or jumper

    is not necessary.

    Caution!Please observe that the line(s) must be short-circuited

    before releasing the lines on terminals 1/3, 4/6 and 7/9.

  • 8/21/2019 A-eberle Relay Reg Da

    33/31633

    REG-DA

    REG-DA operating manual

    3.5.1.4 Relay outputs

    (Terminals 33 ... 59)

    The REG-DA Relay for Voltage Control & TransformerMonitoring has 13 relays.

    Relay 13 is used as a life contact and monitors the running of

    the processor as well as the supply voltages of the system.

    Relays 1 ... 12 are available for regulating and controlling the

    transformer.

    Relays R1, R2 and R12 are permanently assigned to specific

    functions, whereas all of the other relays are freely

    programmable. The relays are programmed with frequentlyused functions when delivered.

    R1 ... R13: Potential-free relay contacts

    Load: 250 V AC, 5 A, cos= 1,250 V DC, 150 W (also refer to

    Page 14)

    Relays R1 and R2 may be switched as follows in order to lock

    a control command:

    R1

    Raise

    R2

    Lower

  • 8/21/2019 A-eberle Relay Reg Da

    34/31634

    REG-DA

    REG-DA operating manual

    3.5.1.5 Binary inputs, feature D0/D1

    (Terminals 11 ... 32)

    The REG-DA Relay for Voltage Control & TransformerMonitoring has 16 binary inputs.

    Only inputs 5 and 6 (Manual/Automatic) are permanently

    assigned. All of the other inputs can be programmed freely.

    Frequently used input functions are already assigned to some

    of the inputs when it is delivered (see table on page 24 to page

    26).

    3.5.1.6 Binary inputs and resistance inputsfor tap-change potentiometer (D2/D3)

    (Terminals 11 ... 26)

    Only binary inputs 5 and 6 (Manual/Automatic) are permanently

    assigned. All of the other binary inputs can be programmed

    freely. Frequently used input functions are already assigned to

    some of the inputs when it is delivered (see table on Page 24 to

    Page 26).

    Feedback of the tap-change position is often sent back to theRelay for Voltage Control & Transformer Monitoring as a BCD

    code.

    The binary inputs are parameterised to correspond with the

    number of steps in this case (see "Binary inputs, feature D0/D1"

    on page 34, terminals 23 to 32).

  • 8/21/2019 A-eberle Relay Reg Da

    35/31635

    REG-DA

    REG-DA operating manual

    If the tap-change position is supplied as a resistance value (e.g.

    10 Ohm / tap-change position), the resistance module can be

    connected directly to terminals 23 to 26.

    For further information see "Resistance Measuring Equipment

    for Tap-Changers with Resistance-Coded Tap-Change

    Signalling" on page 187:

    3.5.2 Pin assignment level II

    Level II is not equipped in the standard version of the Relay for

    Voltage Control & Transformer Monitoring.

    However, a larger number of additional inputs and outputs can

    be provided via this connection level if additional binary or

    analogue inputs/outputs are required.

    The equipment changes according to features C01 to C99.

    A total of four different modules are available, that can be used

    in any combination if required.

    Module 1: 6 binary inputs

    Module 2: 6 relay outputs

    Module 3: 2 mA inputs

    Module 4: 2 mA outputs

    The connection assignment of the individual features can be

    found in the terminal diagram.

  • 8/21/2019 A-eberle Relay Reg Da

    36/31636

    REG-DA

    REG-DA operating manual

    Feature C01

    6 additional binary inputs 48 ... 250 V AC/DC

    Feature C02

    12 additional binary inputs 48 ... 250 V AC/DC

    No.

    Module1

    100 Binary input E17

    101 Binary input E18

    102 Binary input E19

    103 Binary input E20

    104 Binary input E21

    105 Binary input E22

    106 GND E17 ... E22

    No.

    Module1

    100 Binary input E17

    101 Binary input E18

    102 Binary input E19

    103 Binary input E20

    104 Binary input E21

    105 Binary input E22

    106 GND E17 ... E22

    Module1

    107 Binary input E23

    108 Binary input E24

    109 Binary input E25

    110 Binary input E26

    111 Binary input E27

    112 Binary input E28

    113 GND E23 ... E28

  • 8/21/2019 A-eberle Relay Reg Da

    37/31637

    REG-DA

    REG-DA operating manual

    Feature C03

    6 additional relay outputs (NO contacts)

    Feature C04

    12 additional relay outputs (NO contacts)

    No.

    Module2

    100 R14

    101 R15

    102 R16

    103 R17

    104 R18

    105 R19

    106 GND R14 ... R19

    No.

    Module2

    100 R14

    101 R15

    102 R16

    103 R17

    104 R18

    105 R19

    106 GND R14 ... R19

    Module2

    107 R20

    108 R21

    109 R22

    110 R23

    111 R24

    112 R25

    113 GND R20 ... R25

  • 8/21/2019 A-eberle Relay Reg Da

    38/31638

    REG-DA

    REG-DA operating manual

    Feature C05

    6 additional binary inputs 48 ... 250 V AC/DC and

    6 relay outputs (NO contacts)

    Feature C06

    2 additional analogue inputs

    No.

    Module1

    100 Binary input E17

    101 Binary input E18

    102 Binary input E19

    103 Binary input E20

    104 Binary input E21

    105 Binary input E22

    106 GND E17 ... E22

    Module2

    107 R14

    108 R15

    109 R16

    110 R17

    111 R18

    112 R19

    113 GND R14 ... R19

    No.

    Module

    3100

    Analogue input+

    E10

    101 -

    102Analogue input

    +E11

    103 -

  • 8/21/2019 A-eberle Relay Reg Da

    39/31639

    REG-DA

    REG-DA operating manual

    Feature C07

    4 additional analogue inputs

    Feature C08

    2 additional analogue outputs

    Feature C09

    4 additional analogue outputs

    No.

    Module3

    100Analogue input

    +E10

    101 -

    102Analogue input

    +E11

    103 -

    Mod

    ule3

    104Analogue input

    +E12

    105 -

    106Analogue input

    +E13

    107 -

    No.

    Module

    4100

    Analogue output+

    A10

    101 -

    102Analogue output

    +A11

    103 -

    No.

    Module4 100 Analogue output + A10

    101 -

    102Analogue output

    +A11

    103 -

    Module4

    104Analogue output

    +A12

    105 -

    106Analogue output

    +A13

    107 -

  • 8/21/2019 A-eberle Relay Reg Da

    40/31640

    REG-DA

    REG-DA operating manual

    The hardware for all the control system connections is also

    contained on level II.

    The corresponding connection elements on level II must be

    used for RS232 or RS485 connections.If the Ethernet connection is used (required for IEC 61850 or

    IEC 60870-5-104 connections!), the corresponding connection

    is also accessible on level II.

    Please refer to the configuration documentation supplied with

    this operating manual, since the terminal assignment can be

    very different for the individual interfaces.

    The connection elements for fibre-optic cables (send and

    receive diodes as ST or FSMA connection) are mounted directly

    on the flange plate and can be connected there withoutopening the device.

    Fibre-optic cable connection

    (FSMA-connection system)

    Fibre-optic cable connection

    (ST-connection system)

  • 8/21/2019 A-eberle Relay Reg Da

    41/31641

    REG-DA

    REG-DA operating manual

    3.5.3 Pin assignment level III

    It is possible to access interfaces COM 1, COM 2 and COM 3

    via level III.

    The connection elements for the E-LAN transport bus and

    certain combinations of analogue inputs and outputs (Features

    E91 to E99) are also available via level III.

    Interface COM 1

    Function Pin

    DCD 1

    RXD 2

    TXD 3

    DTR 4

    Signal-Ground 5

    DSR 6

    RTS 7

    CTS 8

    RI 9

  • 8/21/2019 A-eberle Relay Reg Da

    42/31642

    REG-DA

    REG-DA operating manual

    Equipping analogue inputs is dependent on the selected

    structure of the features.

    Both mA inputs and mA outputs may be implemented.

    A module can be supplied for measuring the oil temperature

    (transformer monitoring), which can be directly attached to a PT

    100.

    The connection is designed as a three-conductor circuit andcan be used over a distance of approximately 100 m.

    The inputs can operate continuously in a short-circuited or

    open state. All inputs are electrically isolated from all of the other

    COM 2, suitable for

    connecting:

    - Modem

    - PC

    - DCF 77

    - E-LAN-L

    - E-LAN-R

    COM 3, only suitable

    for connecting BIN-D

    and ANA-D interface

    components!

    optional

  • 8/21/2019 A-eberle Relay Reg Da

    43/31643

    REG-DA

    REG-DA operating manual

    circuits. The Relay for Voltage Control & Transformer

    Monitoring is equipped with one analogue input as standard.

    The type of use can be specified at the time of ordering, or a

    specific measurement quantity can be assigned using WinREGor the device's keyboard.

    The outputs can operate continuously in a short-circuited or

    open state. All outputs are electrically isolated from all of the

    other circuits.

  • 8/21/2019 A-eberle Relay Reg Da

    44/31644

    REG-DA

    REG-DA operating manual

    3.6 Types of REG-DA Relay for Voltage Control &Transformer Monitoring

    3.6.1 Wall-mounting version

    The mounting bars provided must be screwed onto the rear of

    the device.

    The entire unit must be attached with suitable screws to/onto a

    stable mounting surface.

    If the mounting holes are drilled laterally, both mounting barscan also be folded inwards (see shaded area).

    NotePlease note and use the enclosed hole pattern (last

    page).

    Mounting bars

    Dimensions in mm

  • 8/21/2019 A-eberle Relay Reg Da

    45/31645

    REG-DA

    REG-DA operating manual

    3.6.2 Panel-mounting version

    After the cutout has been cut in the mounting panel, the four

    grub screws (1) must be screwed into the bottom of the

    housing. The device is then pushed through the cutout and is

    fixed with the two clamping angles (2).

    In general, it is advisable to remove the flange plate first, then

    push the housing through the cutout.

    (1)

    (2)(2)

    (1)

  • 8/21/2019 A-eberle Relay Reg Da

    46/31646

    REG-DA

    REG-DA operating manual

    3.6.3 Mounting on Standard Mounting Rails

    The Relay for Voltage Control & Transformer Monitoring can

    also be mounted on 35 mm standard mounting rails.

  • 8/21/2019 A-eberle Relay Reg Da

    47/31647

    REG-DA

    REG-DA operating manual

    4 Operation

    4.1 Display and control elements

    The MPC operation level (people-process communication) of

    the REG-D Relay for Voltage Control & Transformer Monitoring

    is implemented as a membrane keypad with integrated light-

    emitting diodes (LEDs).

    Indicators and labels

    Seven labels are available. Each label is designed for two

    signals (2 LEDs).

    The labelling of each individual field may be changed at any time

    by pulling the label strip downwards out of the clear vinyl

    pocket.

    Function keys

    Indicators

    Field

    Label

    Parameterisation

    FieldTransformer control

    LCD displayLEDField 1

    LEDField 7

    .

    .

    .

    .

    .

    .

    .

    .

    Label strips

  • 8/21/2019 A-eberle Relay Reg Da

    48/31648

    REG-DA

    REG-DA operating manual

    NoteFurther label strips can be found in Annex 2.

    A program for generating label strips called

    Beschriftungsprogramm.xlscan be found on the programCD.

    If you have a colour printer at your disposal, the

    individual fields can even be printed in colour (yellow and

    red).

    Any standard pen can be used to write on the labels.

    Indicator 1 is programmed as default and cannot be changed.

    LED 1 in field 1 (green) lights up when the device is

    operating fault-free (service).

    LED 2 in field 1 (red) lights up when the device has a fault

    (blocked).

    The LEDs in field 2 to field 5 (yellow) are freely

    programmable for general signalling, and are not

    programmed when delivered.

    The LEDs in field 6 to field 7 (red) are freely programmable.

    They are primarily intended for fault signals and are not

    programmed when delivered.

    Transformer control panel

    7 keys are assigned to the transformer control panel.

    The AUTOMATIC key with an integrated green LED

    lights up when the Relay for Voltage Control & Transformer

    Monitoring is functioning in the Automatic operating mode.The Manual key with integrated red LED lights up

    when the Relay for Voltage Control & Transformer Monitoring is

    functioning in the manual mode.

    The arrow keys Raise and Lower

    can be used to manually select the taps of the transformer.

    Prerequisite: The LOCAL key (red)

    is activated.

    All remote control commands via binary inputs or a serial

    connection are suppressed when in the LOCAL setting.

    Remote control is only possible in the REMOTE mode (green).

  • 8/21/2019 A-eberle Relay Reg Da

    49/31649

    REG-DA

    REG-DA operating manual

    The REG-DA Relay for Voltage Control & Transformer

    Monitoring was designed in such a way that all of the display

    elements of the transformer control panel (Manual/Auto and

    Local/Remote) have to be green when the operatingpersonnel leave the control room.

    The ACK key is currently still out of operation.

    In the future, this key will be able to be used to acknowledge

    process signals and/or fault signals which the Relay for Voltage

    Control & Transformer Monitoring generates itself and indicates

    in the display.

    Parameterisation panel

    The keys in the parameterisation panel can be used to manually

    parameterise the REG-DA Relay for Voltage Control &

    Transformer Monitoring.

    The Menu key is used to switch between the various

    operating modes and to select a specific parameterization

    menu (SETUP 1 ... SETUP 6)

    The Return key is used to confirm a specific

    parameter in the SETUP menus.

    NoteChanges to the parameterisation which are important

    for operation can only be carried out in the manual

    operating mode.

    The Esc key is used to exit any menu. The user can

    move the cursor within the parameterisation menus using the

    and keys.

    Function keys

    The function keys, F1 to F5 , are

    implemented as so-called softkeys.

    The function of the keys is context-controlled and depends on

    the corresponding menu.

  • 8/21/2019 A-eberle Relay Reg Da

    50/31650

    REG-DA

    REG-DA operating manual

    4.1.1 Display

    LCD display

    LCD Display Recorder Mode

    Address at bus (station identification) Relay name Time

    Setpoint value inSetpoint value in

    regulative deviation

    Backwards high-speed switching is indicated by

  • 8/21/2019 A-eberle Relay Reg Da

    51/31651

    REG-DA

    REG-DA operating manual

    4.2 Operating principle

    The operation of the REG-DA Relay for Voltage Control &

    Transformer Monitoring is completely menu-guided and theprinciple is the same for each item in the SETUP menu.

    The following operating principle applies for setting or changing

    the regulation parameters:

    MANUAL OPERATING MODEchanges the operating mode to

    manual operation

    MENU displays the list of operating modes

    MENU selects the SETUP menu item

    MENU can be used to scroll through the pages of

    the SETUP menu selection until the required parameter

    appears on the display.

    Select a parameter via the corresponding function key

    (F1 ... F5).

    Set the value of the parameter via the function keys.

    F1 increases the value in large steps

    F2 increases the value in small steps

    F4 increases the value in small steps

    F5 decreases the value in large steps

    F3 has a special function in some of the SETUP

    menus.

    After entering a value, the changed value is confirmed by

    pressing RETURN .

    If the entry is protected with a password, enter the

    password (see "Password request" on page 95).

    Return or leave the SETUP menus

    ESC (CANCEL)

    The SETUP menus will be automatically exited if no key ispressed for approx. 15 seconds.

  • 8/21/2019 A-eberle Relay Reg Da

    52/31652

    REG-DA

    REG-DA operating manual

    The REG-DA Relay for Voltage Control & Transformer

    Monitoring can be switched back to the automatic

    operating mode using AUTO once the required

    parameters are entered, checked and individually

    confirmed by pressing the RETURN key.

    4.3 Selecting the display mode

    The display modes of the REG-DA Relay for Voltage Control &

    Transformer Monitoring can be selected after pressing the

    MENU key.

    The following modes are available:

    Regulator Mode

    Measurement transducer mode

    Recorder mode

    Statistics mode (Monitor mode)

    ParaGramer mode

    Regulator Mode The F1 key is used to select the RegulatorMode.

    The display indicates the set setpoint

    value in V (kV) and as a percentage of

    the nominal voltage, the momentary

    actual value, the value of the

    permissible regulative deviation and the

    present tap-changer position of the

    tap-changing transformer.

    The present deviation of the setpoint is

    also indicated on a scale (by an

    analogue pointer) with a bandwidth of 10%.

    The colour of the scales pointer changes from transparent

    to black if the specified permissible regulative deviation is

    overshot or undershot.

  • 8/21/2019 A-eberle Relay Reg Da

    53/31653

    REG-DA

    REG-DA operating manual

    If required, the present value of the current may also be

    displayed.

    Note If Actual Value is displayed in capital letters, i.e.

    ACTUAL VALUE, then the MEASUREMENT VALUE

    SIMULATION is active!

    (see Page 146).

    Measurement

    transducer

    mode

    The F2 key is used to select the Measurement

    Transducer Mode.

    When the Relay for Voltage Control & Transformer Monitoring

    carries out measurements in the Aron circuit (feature M2), a

    second measurement transducer screen can be selected todisplay the measured values of the three-phase current

    networks loaded according to the requirements of the user.

    NoteIn the measurement transducer mode, only the reactive

    current I sinof each transformer will be displayed.However, it is not possible to determine on the basis of

    this display which share of the current pertains to the

    load and which pertains to the reactive current.

    The second measurement transducer screen can be selected

    by pressing either the or key.

  • 8/21/2019 A-eberle Relay Reg Da

    54/31654

    REG-DA

    REG-DA operating manual

    The third transducer screen may be selected by pressing either

    the or key.

    If the device is switched in parallel, it is advantageous to display

    the circulating reactive current as well.

    The circulating current Icirc provides information about the

    share of the current that is circulating in the parallel-switched

    transformers and not taken up by the load.

    The quasi-analogue scale illustrates the relationship between

    the circulating reactive current Icirc and the permissible

    circulating reactive current perm. Icirc.

    If the permissible Icirc is 50 A, the circulating reactive current

    Icirc is actually -100 A and the value -2 is shown on the scale.

    If the circulating current becomes zero, the quotient will also

    become zero and the pointer will be positioned in the middle of

    the scale.

    However, generally speaking, this ideal situation can in practice

    only then be reached when the parallel-switched transformers

    exhibit the same electrical features.

    Recorder mode The F3 key is used to select the RecorderMode.

    As standard, every Relay for Voltage

    Control & Transformer Monitoring is

    equipped with a DEMO recorder

    (feature: DEMO in the lower left corner

    of the grid).

    Above the grid, the set permissibleregulative deviation is displayed by

    means of two black arrows. In this

    manner, the recorder display is capable

  • 8/21/2019 A-eberle Relay Reg Da

    55/31655

    REG-DA

    REG-DA operating manual

    of supplying all of the information needed for operating the

    Relay for Voltage Control & Transformer Monitoring (see "LCD

    Display Recorder Mode" on page 50).

    In addition to the value of the present voltage and the tap-

    changer position (in the lower left-hand corner), the display also

    indicates the permissible regulative deviation (black arrows

    above the grid) and the change of the voltage over a period of

    time (past values).

    Within the grid, the present voltage is the value which intersects

    the lower line of the two parallel border lines at the top of the

    grid.

    Independent of the selected feedrate speed (F4), the memorystores values at a constant rate of 1 second.

    Each 1 second value is composed of 10 100ms values.

    Seven scale divisions are available in total on the display. Thus,

    a maximum time range of 7 x 10 minutes (70 minutes) may be

    shown on the screen.

    The shortest time range with the biggest optical resolution is 7

    x 14 seconds (98 seconds).

    Apart from the voltage, the recorder can also record the currentand the angle . The tap-changer position and the setpointvalue with tolerance band are always recorded as well.

    In the second recorder menu (F3-F3), the desired mode can be

    selected via the menu item Number of channels (F4). It is

    possible to change modes at any time without loss of data.

    Displaying the recorder data

    In the first recorder menu (F3), the menu item Dual Display (F4)

    can be used to switch the recorder display between the one-

    channel display of U and the two-channel display. The leftchannel is always reserved for the control voltage U. The Relay

    for Voltage Control & Transformer Monitoring offers a selection

    of measurement quantities for the second channel (see 2nd

    recorder menu).

    The time axis is the same for both curves. Only the resolution of

    the left channel can be changed using the dx (F5 key); the

    scale of the second channel remains the same.

  • 8/21/2019 A-eberle Relay Reg Da

    56/31656

    REG-DA

    REG-DA operating manual

    Derived variables from the recorder data

    In the first recorder menu (F3,F3), the

    menu item MMU display (F5) can be

    used to switch the display of variables

    derived from the present cursor value

    (at the very top) on and off.

    I and S are displayed as numeric values

    if only two recorder channels (U + I)

    have been selected (second recorder

    menu (F3, F3, F4)).

    If all three recorder channels (U + I + ) are activated, then I, ,P and Q will be displayed as numeric values.

    It is also possible to search for an event in the second recordermenu. If both the date and the time of a certain event are

    known, a specific day and time can be selected in the Time

    Search submenu.

    After returning to the recorder main menu (by pressing F3 or

    Enter), the recorder lists the selected time and displays all of the

    electrical measurement values as well as the corresponding

    tap-changes.

    Statistics mode The F4 key is used to select the StatisticsMode.

    The total number of tap-changes made

    since the counter was last set to zero is

    shown on the display. Thus tap-

    changes made under load and tap-

    changes made with a load of less than

    5% of the nominal current In(1 A or 5 A)

    are distinguishable.

    Changes made under load areadditionally displayed for each tap-

    change.

    NoteIf the tap-changer is working under load (I > 0.05 In), adouble arrow >> indicates the present tap-changer

    position.

    If the load condition is not fulfilled, the present tap-

    changer position will be indicated by a single arrow >.

    In conjunction with the recorder, the statistics mode provides

    valuable information regarding the controlled system.

  • 8/21/2019 A-eberle Relay Reg Da

    57/31657

    REG-DA

    REG-DA operating manual

    The parameters Time factor and Permissible regulative

    deviation can be used to reach an optimum between the

    voltage stability and the number of tap-changes. However, this

    relation cannot be calculated mathematically as it is subject tothe individual conditions at the respective feeding point.

    ParaGramer F5 selects ParaGramer mode.

    The ParaGramer is a tool used for

    automatically preparing parallel

    connections and for the one-line

    display of the switching status.

    The artificial word ParaGramer is

    derived from the terms

    parallel and one-line diagram.

    The ParaGramer displays the switching

    status of the individual transformers in one-line graphics and

    can be loaded by pressing the F5 key in the main menu.

    The function is activated by feeding a complete busbar replica

    (positions of the circuit breakers, disconnectors, bus ties and

    bus couplings) into each Relay for Voltage Control &

    Transformer Monitoring by means of binary inputs.

    On the basis of the switching statuses, the system can

    independently recognise which transformer should work in

    parallel operation with which other transformer(s) on a busbar.

    The system treats busbars connected via bus couplings as one

    single busbar.

    As shown in the graphic, both transformers T1 and T3 are

    working on busbar a, whereas transformer T2 is feeding on

    busbar b.

    If special crosslinks are needed

    between the busbars, we recommend

    that you contact the headquarters of

    our company A. Eberle GmbH & Co.

    KG for assistance, since it is not

    possible to describe all the options in

    this operating manual.

    The crosslinks feature is depicted in

    the graphic. With its assistance, two

    busbars may be coupled crosswise.

    Crosslink

  • 8/21/2019 A-eberle Relay Reg Da

    58/31658

    REG-DA

    REG-DA operating manual

    Setup menus MENU selects the SETUP men 1

    4.4 Lamp check

    Press the F5 key to check the functions of the light-

    emitting diodes on the front panel. Select F5 .

    NoteThis check can only be carried out in the Regulator

    Mode or Statistics Mode.

    4.5 Resetting fault signals

    To reset fault signals that occur, the operating mode must be

    changed from AUTOMATIC to MANUAL and then back to

    AUTOMATIC again.

    4.6 Operating the recorder

    F1 and F2 allow access to historical values.

    The time and date corresponding to a particular event can be

    found by setting the voltage-time diagram back to the time-

    reference line (beginning of the grid at the top) using the F1

    and F2 keys. The time, date, voltage value and

    tap-changer position can then be read below the grid.

    If historical data is displayed, the term HIST appears in the

    lower left-hand corner of the grid. Display of past measurement

    values may be aborted at any time by pressing the ESC

    (CANCEL) key.

    Press F3 to go to the recorder 1 menu. The scroll

    displacement for searching using the F1 and

    Time reference line

  • 8/21/2019 A-eberle Relay Reg Da

    59/31659

    REG-DA

    REG-DA operating manual

    F2 keys (in recorder mode) can be set using the scroll

    menu item. This helps to speed up the search procedure. It is

    also possible to switch back and forth between Dual Display

    and MMU display in the Recorder -1 menu.

    Pressing the F3 key in the Recorder -1 menu will take

    you to the Recorder -2 menu. In this menu a specific search

    date and time can be set under the menu item Time Search.

    The type of display (U, U+I, U+I+Phi, U+U2, U+OilT, U+WndT)

    can be selected under the menu item Channel Display.

    The time-line diagram for the selected point in time appears

    after returning to the recorder mode again by pressing F3

    .The Recorder 1 and Recorder 2 menus display the present

    memory capacity status in % as well as in days.

  • 8/21/2019 A-eberle Relay Reg Da

    60/31660

    REG-DA

    REG-DA operating manual

    The feedrate speed can be selected by pressing the F4

    key. Four different times can be selected: 14 s, 1 min, 5 min, 10

    min.

  • 8/21/2019 A-eberle Relay Reg Da

    61/31661

    REG-DA

    REG-DA operating manual

    The dt values refer to the time which must pass before a scale

    section (division) is recorded.

    The scale of the 1st channel can be changed using the

    F5 dx key.

    An extension of WinREG permits the data to be read out.

    The data may be archived on the PC from firmware version 1.78

    onwards.

    The evaluation program can also generate data records that

    can be read by MS EXCEL.

    Note

    If the note DEMO appears in the lower left-handcorner of the grid of the regular recorder display, the

    recorder is operating in demo mode. In this operating

    mode, the recorder only records the measured values

    for a period of 4 - 6 hours. After this period, the older

    values are replaced by the new ones.

    dT = 14sdT = 1m

    dT = 5mdT = 10m

    1 division

  • 8/21/2019 A-eberle Relay Reg Da

    62/31662

    REG-DA

    REG-DA operating manual

  • 8/21/2019 A-eberle Relay Reg Da

    63/31663

    REG-DA

    REG-DA operating manual

    5 Commissioning

    The REG-DA Relay for Voltage Control & Transformer

    Monitoring is a complex device with many functions.

    This variety of functions necessitates a comprehensive

    operating manual.

    It was considered whether it was better to fill the individual

    screenshots with all the theoretical information, or whether it is

    better to separate the two parts by summarising the

    background information and guiding the reader through the

    individual screens.

    We finally decided to offer two separate parts with the

    corresponding cross-references.

    However, in order to make it as easy as possible to start the

    parameterisation without constantly having to jump between

    two sections, we have inserted a commissioning section which

    enables a standard voltage regulation to be carried out step-by-step.

    Thus we based the description on the most important functions

    of voltage regulation.

    A summary of the limit values with a short explanation and links

    to the appropriate chapters can be found on Page 85

    Whilst the parameterisation can be implemented using the

    WinREG parameterisation program, this chapter only deals withparameterisation using the device keypad.

    The parameters that are particularly important for voltage

    regulation will be briefly mentioned in seven steps and the

    parameterisation explained.

    Further settings that are required in special cases can be found

    in chapter 7.

    After applying the operating voltage, the

    REG-DA will indicate that it is in regulator mode.

    Other modes, such as measurement transducer mode,

    recorder mode, statistics mode and ParaGramer mode, can be

    selected at any time.

  • 8/21/2019 A-eberle Relay Reg Da

    64/31664

    REG-DA

    REG-DA operating manual

    Therefore it is important to realise that all modes run parallel to

    each other in the background. If one selects the recorder mode

    (for example), the regulating tasks and all the other

    parameterised task settings will also naturally be processed.

    Press MENU and then use the keys

    F2 ... F5 to select the desired mode.

    The individual operating modes are briefly described below.

    In total, six SETUPs are designed for the parameterisation.

    You can scroll through the individual SETUPs in the following

    manner:

    Starting at the main menu (regulator, measurement transducer,

    recorder, statistics or ParaGramer), press MENU to enterSETUP 1.

    Repeatedly pressing the MENU key selects SETUP 2 to SETUP

    6.

    If you are already in one of the SETUPs, you can reach all the

    other menus by pressing the and keys.

    Caution!

    Please observe the Warnings and Notes on Page 9without fail!

  • 8/21/2019 A-eberle Relay Reg Da

    65/31665

    REG-DA

    REG-DA operating manual

    5.1 Regulator mode

    After the auxiliary voltage is applied, the Relay for Voltage

    Control & Transformer Monitoring indicates that it is in regulator

    mode.

    The important parameters for assessing a regulation situation

    are shown in this display mode.The tap-changer position and the present regulative deviation

    are shown in addition to the actual voltage value. The present

    regulative deviation is shown in quasi-analogue form.

    If the pointer is at 0 the actual value is the same as the

    setpoint value. If the regulative deviation is within the tolerance

    range the pointer is transparent. If the regulative deviation is

    outside the permissible regulative deviation the pointer changes

    to black.

    In this way one can judge the present condition of the controlled

    system at a glance.

    An alternative display with additional information the compactdisplay can be selected using the F1 key.

    In addition to the actual value and the tap-changer position, the

    setpoint value in V (kV) and % as well as the permissible

    regulative deviation in % are shown in this display.

    If you