Forewarned is Forearmed… Online Dissolved Gas Analyzer
Analysis of the gases dissolved in power transformer oil is recognized as the most useful tool for early detection and diagnosis of incipient faults in transformers. In addition, water contamination deteriorates the performance of the oil as high moisture content increases the risk of corrosion and overheating. This is in particular when the water content reaches the saturation point of the oil and free water is formed.
Besides regular gas chromatographic analysis and off-line moisture analysis of the insulation oil of power transformers, online monitoring systems gain more and more importance worldwide.
REG-DGA HC 01+ - Composite Gas & Moisture-in-oil measurement
REG-DGA HC 03 - Individual measurement of Hydrogen (H2), Carbon Monoxide ( CO) & Moisture (H2O) Ea
rly
War
nin
g/A
larm
Ap
plic
atio
ns
REG-DGA HC 05 - Individual measurement of Hydrogen (H2), Carbon Monoxide ( CO), Ethylene (C2H4), Acetylene ( C2H2) & Moisture (H2O)
REG-DGA HC 08 - Individual measurement of Hydrogen (H2), Carbon Monoxide ( CO), Ethylene (C2H4), Acetylene ( C2H2), Methane ( CH4), Ethane ( C2H6), Carbon Dioxide (CO2)& Moisture (H2O)
Nu
rsin
g/In
ten
sive
Ca
re A
pp
licat
ion
s
REG - DGA
REG-DGA HC 01+
The REG-DGA HC 01+ is a permanently-installed composite gas-in-oil sensor
for the analysis of following dissolved key fault gases (TDCG = Total Dissolved
Combustible Gases):
Fault gas TDCG contribution
Hydrogen (H2) approx. 20 %
Carbon Monoxide (CO) approx. 30 %
Methane (CH4) < 5 %
Acetylene (C2H2) 100 %
Ethylene (C2H4) approx. 32 %
Ethane (C2H6) < 5 %
The integration of 6 relevant key gases into a total weighted gas
concentration and the measurement of Moisture in oil enables the HC 01+ to
react to most transformer faults and makes the device to a compact and cost
effective tool used in particular for early transformer fault detection and
preventative maintenance.
The HC 01+ is equipped with 2 analog 0/4 ... 20 mA outputs for the dissolved
composite gas-in-oil and moisture in oil analysis results and 4 digital relay
outputs (Hi-alarm, Hi-Hi-alarm, Moisture-alarm and system function alarm)
Key Advantages:
Composite measurement of Hydrogen (H2), Carbon Monoxide (CO), Methane (CH4), Acetylene (C2H2), Ethylene (C2H4) and Ethane (C2H6) & dissolved Moisture (H2O) in the transformer oil.
Relay outputs with light indicators showing potential alerts
Easy and fast installation without any operational interruption of the transformer
Compact and resistant design for long lasting usage
Communication interfaces ETHERNET 10/100Mbit/s (copperwired or fibre-optical) and CAN bus to support proprietary communication protocols and to be prepared for sub-station communication protocol MODBUS on TCP.
REG-DGA HC 03
The REG-DGA HC 03 is a preventive maintenance device that is permanently
mounted on the transformer. It measures continuously the most important
fault gases in a power transformer, Hydrogen (H2), Carbon Monoxide (CO)
and Moisture (H2O).
Additionally, it serves for recording the fault gas contents, allows alarm levels
to be set for each fault gas and moisture content and offers output interfaces
(4-20mA) individually for H2, CO and H2O content.
By online monitoring of the key fault gases like Hydrogen (H2), Carbon
Monoxide (CO) and Moisture (H2O), an additional potential of cost reductions
and safety improvements can be achieved.
Key Advantages:
Individual analysis of the dissolved gas contents hydrogen (H2) and carbon monoxide (CO)
Analysis of moisture (H2O) dissolved in transformer oil (both relative humidity in % and absolute humidity in ppm)
Simple, lightweight and easy-to-mount solution on any valve on the transformer (NPT 1½)
Installation on the operational transformer without any supply interruption
Sophisticated graphical-oriented software (on the device and via PC)
Various communication interfaces (RS 232, RS 485, MODBUS, integrated GSM- and analog modem)
Maintenance-free system
REG-DGA HC 05
The REG-DGA HC 05 is a permanently-installed multi-gas-in-oil analysis
system with transformer monitoring functions. It allows for the individual
measurement of moisture and the key gases namely Hydrogen (H2),
Carbon Monoxide (CO), Acetylene (C2H2) and Ethylene (C2H4) dissolved in
transformer oil.
As hydrogen (H2) is involved in nearly every fault of the insulation system
of power transformers and carbon monoxide (CO) is a sign of an
involvement of the cellulosic / paper insulation, the presence and
increase of acetylene (C2H2) and ethylene (C2H4) further classifies the
nature of a fault as overheating, partial discharge or high energy arcing.
Key Advantages:
Individual measurement of Hydrogen (H2), Carbon Monoxide (CO), Acetylene (C2H2) and Ethylene (C2H4)
Moisture-in-oil measurement
Communication interfaces ETHERNET 10/100 Mbit/s (copper-wired or fibre-optical) and RS 485 to support proprietary communication protocols and to be open / prepared for substation communication protocols IEC 61850, MODBUS, DNP 3 etc.
Optional on-board GSM and analog modems for remote communication
REG-DGA HC 08
The REG-DGA HC 08 is a permanently-installed multi-gas-in-oil analysis
system with transformer monitoring functions. It allows for the individual
measure-ment of moisture and the key gases namely Hydrogen (H2),
Carbon Monoxide (CO), Carbon Dioxide (CO2), Methane (CH4), Acetylene
(C2H2), Ethylene (C2H4) and Ethane (C2H6) dissolved in transformer oil.
As hydrogen (H2) is involved in nearly every fault of the insulation system
of power transformers and carbon monoxide (CO) is a sign of an
involvement of the cellulosic / paper insulation, the presence and
increase of acetylene (C2H2) and ethylene (C2H4) further classifies the
nature of a fault as overheating, partial discharge or high energy arcing.
Key Advantages:
Individual measurement of Hydrogen (H2), Carbon Monoxide (CO), Carbon Dioxide (CO2), Methane (CH4), Acetylene (C2H2), Ethylene (C2H4) and Ethane (C2H6)
Moisture-in-oil measurement
Communication interfaces ETHERNET 10/100 Mbit/s (both copper-wired/fibre-optical) and RS 485 to support proprietary communication protocols and to be open / prepared for substation communication protocols IEC 61850, MODBUS, DNP 3 etc.
Optional on-board GSM and analog modems for remote communication
PRODUCT REG-DGA HC 01+ REG-DGA HC 03 REG-DGA HC 05 REG-DGA HC 08
Dimensional Comparison (Approx. mm)
W 224 x H 195 x D 218 W 224 x H 224 x D 307.5 W 263 x H 263 x D 327.5 W 263 x H 263 x D 327.5
Weight (Approx.)
4 KG 7.5 KG 13.5 KG 15 KG
Gas-in-Oil Analysis
H2
CO
C2H2
C2H4
CH4
C2H6
(composite)
H2 (0 ppm … 2,000 ppm)
CO (0 ppm … 2,000 ppm)
(individual)
H2 (1 … 2,000 ppm)
CO (5 … 5000 ppm)
C2H2 (0.5 … 2,000 ppm)
C2H4 (0.5 … 2,000 ppm)
(individual)
H2 (1 … 2,000 ppm)
CO (5 … 5,000 ppm)
CO2 (25 … 5,000 ppm)
C2H2 (0.5 … 2,000 ppm)
C2H4 (0.5 … 2,000 ppm)
C2H6 (0.5 … 2,000 ppm)
CH4 (1 … 2,000 ppm)
(individual)
Oil Moisture (relative %, absolute ppm)
( 0 ppm ... 100 ppm) ( 0 ppm ... 100 ppm) (0 ppm … 100 ppm) (0 ppm ... 100 ppm)
Measurement Interval 20 min 20 min 20 min 40 min
Power Supply
120 V -20% +15% AC 50/60 Hz or 230 V -20% +15% AC 50/60 Hz or 120 V -20% +15% DC or 230 V -20% +15% DC
88 V … 276 V AC Optional: 88 V … 350 V DC
88 V … 276 V AC Optional: 88 V … 350 V DC
88 V … 276 V AC Optional: 88 V … 350 V DC
Operating Temperature:
Oil Temperature
Ambient Temperature
-20° C ... +105° C
-50° C ... +55° C
-20° C ... +105° C
-50° C ... +55° C
-20° C ... +105° C
-50° C ... +55° C
-20° C ... +105° C
-50° C ... +55° C
Oil Pressure 0 - 800 kpa 0 - 800 kpa 0 - 800 kpa 0 - 800 kpa
Power Consumption 250 VA max. 350 VA max. 350 VA max. 350 VA max.
Analog Outputs (4 - 20 mA)
2 (Standard) 4 (Standard) 5 (Standard) 8 (Standard)
Relay Outputs (220 V AC/DC, 2A, 60W)
4 (Standard) 4 (Standard) 5 (Standard) 8 (Standard)
Opto-coupler Outputs - 8 (Standard) 5 (Optional) 5 (Optional)
Analog Inputs - 8 (Standard) 10 (Optional) 10 (Optional)
Communication / Protocol Ethernet (Copper Wired / FO) for TCP (Proprietory Communication or MODBUS)
RS232 RS485 (Proprietory or MODBUS) Internal on-board modem
Ethernet (Copper Wired / FO) RS485 (Proprietory or MODBUS) On-board GSM / Analog Modem (Optional)
Ethernet (Copper Wired / FO) RS485 (Proprietory or MODBUS) On-board GSM / Analog Modem (Optional)