    REG-DA

    Voltage Regulator

    * surface-mounting housing

    * panel-mounting housing

    * DIN-rails mounting

    ApplicationAll measurement, control and regulation tasks of tap-chan-

    ging transformers can be executed using the new REG-DA

    voltage regulator.

    The REG-DA regulator features a world innovation as it is

    equipped with a high-capacity transformer monitoring function

    in accordance with CEI IEC 354 (VDE 0536). This function

    allows the operator to call up information about the hot-spottemperature and the lifetime consumption of the transformer

    at any time. If required, the regulator can even activate up to

    six cooling levels. The oil temperature can either be recorded

    directly (PT 100) or via a mA input.

    Apart from its basic function, every REG-DA voltage regu-

    lator can be used as a measurement transducer, recorder,

    statistical unit, paragramer and transformer monitor all at the

    same time. All important network measurement quantities are

    displayed in measurement transducer mode. The trends in the

    voltage that is to be regulated over time and a second, se-

    lectable, measurement quantity are shown in recorder mode.

    The statistical unit for the tap-change position offers a clear

    presentation of all switching operations of the tap changer.

    The paragramer provides a complete busbar simulation.

    Interconnection of multiple voltage regulators on a network

    enables the mutual exchange of data between regulators over

    long distances.Various communications methods can be used

    to transfer data.This allows monitoring of multiple transformers

    from a centralised control centre. Parallel connection of seve-

    ral transfomers can be very easily implemented this way.

    Application-specific tasks can be implemented via freely

    programmable inputs and outputs. The REG-DA regulator

    is able to communicate with a control centre via all common

    scada protocols.

    Characteristics of the REG-DA voltageregulator Large backlit LCD (128 x 128) with all important

    information (tap-change position, voltage, etc.)

    Measuring functions (U, I, P, Q, S, cos , , I sin , f )

    Recorder functions (2-channel chart recorder)

    Statistics function (records total number of switching

    operations, switching operations per tap)

    Event recorder (log book) Transformer monitoring functions incl. recording of

    the hot-spot temperature and lifetime consumption

    14 (26) freely programmable binary inputs

    9 (21) freely programmable binary outputs

    Freely programmable analogue inputs or outputs (mA)

    PT 100 - direct input for RTD Temp. probe (option)

    Input for tap-change potentiometer (200...20 kOhm

    total resistance, option)

    Control of triple-wound transformers

    Control of phase-shifting transformers

    Limit value monitoring for all measurement quantities

    4 freely programmable set-point values Rated values of U and I can be programmed

    WinREG software for setup,programming and display

    as well as for a PC-based archiving and evaluation of

    the recorder data

    REGSimTM simulation software for the simulation

    of any parallel operation, network and load situations

    Implementation of control tasks through ability to freely

    program

    RS485 peripheral bus (COM3) for additional interface

    modules (ANA-D, BIN-D)

    ParaGramer function for the display and automation of

    any parallel connections with up to ten transformers UL certification

    Serial and Ethernet Scada protocols supported:

    IEC 61850, IEC 60870-5-103, IEC 60870-5-101,

    DNP3:00, LONMark, SPABUS, MODBUS RTU

    IEC 61850Interface now available!

    GB

    A. Eberle GmbH & Co. KG

    Technical Data

  • 7/27/2019 A-eberle Dt Reg-da Gb

    2/20

    RS232

    RS232

    RS485

    Status

    E-LANRS485

    1

    2

    3

    4

    5

    6 7

    8

    9

    10

    11

    12

    13

    COM 1

    COM 2

    COM 3

    P

    LCD

    LED

    RAM

    ROM

    CLOCK

    SERVICE

    BLOCKED

    F33

    F22

    F11

    F44

    F55

    AUTOUTO REMOTEEMOTE

    LOCALOCAL

    ACKCK

    MENUENUESCSC

    REG-DAEG-DA a-eberle

    SERVICE

    BLOCKED

    F33

    F22

    F11

    F44

    F55

    AUTOUTO REMOTEEMOTE

    LOCALOCAL

    ACKCK

    MENUENUESCSC

    REG-DAEG-DA a-eberle

    Case differentia-

    tion

    REG-DA

    program

    Boundary conditions

    Parallel operationon one (several)

    busbar (s)

    I sin Identical transformers,equal or different tap

    change

    I sin (S) Transformers with diffe-

    rent powers, different orequal tap changes

    Master-

    slave

    Identical transformers,

    equal tap change

    Freely switched in

    parallel

    cos Any transformers, any

    tap changes

    Description

    Figure 1 Functions of the REG-DA regulator (maximum

    extension)

    1 3x current and 2x voltage transformers

    2 Analogue inputs

    3 Binary inputs

    4 Input for tap-changer display

    5 Auxiliary voltage

    6 Display and processing unit

    7 Analogue outputs

    8 Binary outputs

    9 E-LAN connection (2 x RS485 with repeater function)

    10 COM1, RS232

    11 COM2, RS232

    12 COM3, RS485

    13 Status indication (relay)

    Regulator modeThe regulator constantly compares the actual value and a

    fixed or load-dependent setpoint value and, depending on

    the deviation, determines the correcting variable for the tap

    changer of the transformer. The regulator parameters canbe optimally adjusted to the dynamic time behaviour of the

    network voltage, which allows for a high control quality at a

    low number of switching operations.

    Parallel connection of transformersAll regulators are able to control several transformers connec-

    ted in parallel to one busbar without any additional devices.

    Every regulator constantly indicates which reactive current

    I sin is being used.

    Various processes are available to control the transformers,

    and they are listed in Table 1 according to those that operatein parallel on a busbar and those that are simply freely swit-

    ched in parallel.

    An essential factor in this context is that no additional com-

    ponents are required as all function units required for parallel

    operation are accommodated within the regulators.

    Table 1 Parallel operation of transformers

    Measurement transducer modeThe values of all relevant variables of an equally or arbitrarily

    loaded three-conductor three-phase supply network are calcu-lated and displayed on the basis of the sampling values.

    In addition, a selection of up to seven measurement values

    can be output as a DC signal via the analogue outputs.

    Recorder modeThe change in the voltage over time and a second selectable

    measurement quantity are continuously shown on the display

    in the form of a line chart. The time grid for the recording is

    adjustable. The present tap position is recorded in addition

    to the measurement values. Therefore it is possible to review

    the voltage and the corresponding tap position at any timeduring the recording.The average recording time for voltages

    and tap changes is approximately six weeks.The stored values can be displayed with a time and date via

    the keyboard or the WinREG operating software.

    Furthermore, measurement values which are transferred to

    the regulator as mA signals from external sources can be

    displayed.

    Technical Data REG-DA

    A. Eberle GmbH & Co. KG 2

  • 7/27/2019 A-eberle Dt Reg-da Gb

    3/20

    Statistics modeIn the statistics mode, all switching operations of the tap

    changer are registered. A differentiation is made between

    switching operations under load and switching operationswithout load.

    ParaGramer modeThe PARAGRAMER is a support tool for the automatic pre-

    paration of parallel connections and the online display of the

    switching statuses.

    The artificial word PARAGRAMER is a combination of the two

    terms parallel and one-line diagram.

    The PARAGRAMER shows the switching status of the indi-

    vidual transformers in a one-line diagram.The function is activated by feeding each regulator with a

    complete busbar replica (position of circuit breakers, discon-

    nectors, bus ties and bus couplings).

    Based on the switching states of all regulators involved in

    the parallel connection, the system autonomously detectswhich transformer is to work with which other transformer(s)

    in parallel connection on a busbar.Busbars that are connected via bus coupling(s) are treated

    as one single busbar by the system.

    Transformer monitoring mode TMMIn the monitoring mode, the basic parameters of the transfor-

    mer are monitored. The oil temperature can also be recorded

    in addition to the tap changer statistics. In accordance with IEC

    354 (VDE 0536/3.77) the hot-spot temperature is determined

    on the basis of the oil temperature and the winding current and

    subsequently extrapolated to determine the residual lifetimeof the transformer.

    Fans can be set to one of six levels and an oil pump can be

    used to regulate the temperature. Furthermore, the oil levels

    can be monitored and the operating hours of the fans and the

    pumps can be counted.

    The regulator is equipped with a mA input as standard.

    The temperature can be received as a mA signal by an

    upstream temperature measurement transducer using this

    input.

    If other combinations are required, e.g. temperature as a direct

    PT 100 connection and hot-spot temperature as a mA output,

    the desired combination can be selected from the E and C

    groups of characteristics.

    Additionally, a record is kept for every single tap in tabular

    form. How many tap changes have been carried out during

    which time period and how often each tap has been selected

    can be checked using these data. This information can be

    used to optimise the regulator settings.

    The saved statistics values can be selected using the key-

    board or loaded and printed using WinREG.

    The figure shows the two transformers T1 and T3 working on

    busbar a, while transformer T2 feeds off busbar b.

    SERVICE

    BLOCKED

    F33

    F22

    F11

    F44F55

    AUTOUTO REMOTEEMOTE

    LOCALOCAL

    ACKCK

    MENUENUESCSC

    REG-DAEG-DA a-eberle

    SERVICE

    BLOCKED

    F33

    F22

    F11

    F44

    F55

    AUTOUTO REMOTEEMOTE

    LOCALOCAL

    ACKCK

    MENUENUESCSC

    REG-DAEG-DA a-eberle

    SERVICE

    BLOCKED

    F33

    F22

    F11

    F44F55

    AUTOUTO REMOTEEMOTE

    LOCALOCAL

    ACKCK

    MENUENUESCSC

    REG-DAEG-DA a-eberle

    SERVICE

    BLOCKED

    F33

    F22

    F11

    F44

    F55

    AUTOUTO REMOTEEMOTE

    LOCALOCAL

    ACKCK

    MENUENUESCSC

    REG-DAEG-DA a-eberle

    Technical Data REG-DA

    3 A. Eberle GmbH & Co. KG

  • 7/27/2019 A-eberle Dt Reg-da Gb

    4/20

    Technical characteristics,Regulations and standardsIEC 1010/ EN61010 (VDE 0411)

    CAN / CSA - C 22.2 No. 1010.1 - 92

    VDE 0110

    IEC 255 - 4

    DIN 43807

    EN 61326 - 1 / A1

    IEC 688 - 1

    IEC 529

    EN 50178 / VDE 0160 / 11.94 (currently draft)

    VDE0106 part 100

    Resistance input for tap-change

    potentiometer:REG-DA voltage regulators that are equipped with characteri-

    stics D2 or D3 have only 8 binary inputs as standard, but also

    have a resistance input that can transform the resistance ofthe tap-change potentiometer (200 when total resistance

    is 20 k) into tap-change positions.

    Pins 23 to 26 intended for connection to tap-change poten-

    tiometers.

    A current is connected via pins 23 and 26 and a resistance

    chain.

    The voltage drop that occurs per tap-change position can be

    measured via pins 24 and 25 (4-conductor circuit) or via pins

    23 and 25 (3-conductor circuit).The standard version is a 3-conductor circuit. If a 4-conductor

    measurement circuit is required, it can be achieved at any

    time by changing the switching settings of DIP switch S and

    the connection.

    The resistance measurement circuitry consists of a program-

    mable current source to feed the measurement resistanceand a voltage-measurement device to measure the voltage

    at the resistance.

    The measurement result is output with a resolution of 12 bits

    and a refresh rate of approx. 10 Hz (0.1 s).

    The measurement device has a broken-wire detection sys-

    tem.

    The parameters can be entered into an application menu

    using the keyboard (see operating manual).

    Analogue inputs (AE)Number Refer to the order details

    Input range X1X2 -20 mA020 mA

    X1 and X2 programmable

    Control limit 1.2 X2

    Voltage drop 1.5 VElectrical isolation Optocoupler

    Common mode rejection > 80 db

    Series mode rejection > 60 db / decade ex 10 Hz

    Overload capacity 50 mA constantly

    Error limit 0.5 %

    Temperature input PT 100Number Only one PT 100 input

    possible

    Connection 3-conductor circuit

    Current through sensor < 8 mA

    Line compensation No compensation required

    Transmission behaviour Linear

    AC voltage input (UE )Measurement voltage UE 60 ... 140 V (if three-phase

    voltage is connected)

    35 ... 80V (if a phase

    voltage is connected) The nominal value can be

    selected using software

    Curve shape Sinusoidal

    Frequency range 16....50....60....65 Hz

    Internal consumption U2 / 100 k

    Overload capacity 300 VAC constantly

    AC current input (IE)Measurement current In 1 A / 5 A

    (software-selectable)

    Curve shape Sinusoidal

    Frequency range 16....50....60....65 Hz

    Control range 0 ... In ... 2.1 In

    Internal consumption 0.5 VA

    Overload capacity 10 A constantly

    100 In for 1 sec

    30 In for 10 sec

    UL Certificate Number 050505 - E242284

    The regulator is equipped with an analogue input as stan-

    dard.

    The inputs can be continuously short-circuited or operated

    open. All inputs are galvanically isolated from all other cir-

    cuits.

    Technical Data REG-DA

    A. Eberle GmbH & Co. KG 4

  • 7/27/2019 A-eberle Dt Reg-da Gb

    5/20

    Binary outputs (BO)R1 ... R13 (... R19, ... R25)

    Max. switching frequency 1 Hz

    Electrical isolation Isolated from all device-internal potentials

    Contact load AC: 250 V, 5 A (cos = 1.0)

    AC: 250 V, 3 A (cos = 0.4)

    DC: 220 V, 55 W switchingcapacity

    DC: 110 VR1, R2 R3 ... R13,

    ...R19, ...R25

    Switch-on current: 20 A 10 A

    Holding current: 5 A 5 A

    Switch-off current: 0.4 A 0.4 A

    Number of switching operations 5105 electric

    Binary inputs (BI)Inputs E1 ... E16 (... E22, ... E28)

    Control signals Ust 48 V...230 Vin the AC/DC range

    Curve shape, permissible Rectangular, sinusoidal

    H level 48 VL level < 10 V

    Signal frequency DC ... 60 HzSwitching delay Selectable in the range

    1..999 s

    Input resistance 108 kElectrical isolation Optocoupler; groups of 4,

    each galvanically isolated

    from each other.

    Analogue outputs (AO)Number Refer to the order details

    Output range Y1 Y2 -20 mA020 mA

    Y1 and Y2 programmable

    Electrical isolation Optocoupler

    Load resistance 0 R 8 V /Y2Alternating component < 0.5 % of Y2

    The outputs can be constantly short-circuited or operated

    open. All output connections are galvanically isolated from

    all other circuits.

    Example circuit diagram of a binary input

    Limit value monitoringLimit value Programmable

    Response time Programmable

    Alarm display Programmable LED

    or programmable on LCD

    Display elementsThe regulator has 14 LEDs

    LED 1 : Normal operation Green

    LED 2 : Faulty operation Red

    LED 3 ... LED 10 : Freely programmable Yellow

    LED 11 ... LED 14 : Freely programmable Red

    The individual LEDs can be labelled yourself.

    However, if at the time of ordering you specify the labels you

    require, the labelling can be carried out in our factory.

    Technical Data REG-DA

    5 A. Eberle GmbH & Co. KG

  • 7/27/2019 A-eberle Dt Reg-da Gb

    6/20

    Test voltagesHous.COM 1

    UhCOM 2COM 3

    BO BI AI AO UE IE

    Housing / COM 1 Hous. - 2.2 0.35 1.35 1.35 0.35 0.35 1.35 1.35

    Auxiliary voltage Uh 2.2 - 3.7 2.9 2.9 3.7 3.7 2.6 2.6

    COM 2/3 / IEC / DNP.. COMs 0.35 3.7 - 2.3 2.3 0.5 0.5 2.8 2.8

    Binary outputs BO 2.0 2.9 2.3 - 2.0 2.3 2.3 2.6 2.6

    Binary inputs (250 V) BI 2.0 2.9 2.3 2.0 - 2.3 2.3 2.6 2.6

    Analogue inputs AI 0.35 3.7 0.5 2.3 2.3 - 0.5 2.8 2.8

    Analogue outputs AO 0.35 3.7 0.5 2.3 2.3 0.5 - 2.8 2.8

    Input voltage UE 1.35 2.6 2.8 2.6 2.6 2.8 2.8 - 2.2

    Input current IE 2.0 2.6 2.8 2.6 2.6 2.8 2.8 2.2 -

    III II

    Input circuits of the current and

    voltage transformers

    Auxiliary voltage

    Control circuits, analogue

    inputs, analogue outputs

    COMs, E-LAN

    50 V 150 V 230 V

    E-LAN,

    COM1...COM3,

    analogue inputs,

    analogue outputs,

    inputs 10...50 V

    Voltage inputs,

    current inputs

    Auxiliary voltage,

    binary inputs

    (E1...E16),

    relay outputs

    (R1...R13),

    status

    Measurement quantities (optionally as mA value)Voltages TRMS U12, U23, U31 ( 0.25 %)

    Current TRMS I1, I2 , I3 ( 0.25 %)

    Active power P ( 0.5 %)

    Reactive power Q ( 0.5 %)

    Apparent power S ( 0.5 %)

    Power factor cos ( 0.5 %)

    Phase angle ( 0.5 %)Reactive current I sin ( 1 %)

    Frequency f ( 0.05 %)

    Reference conditionsReference temperature 23C 1 K

    Input quantities UE = 60 ... 140 V

    IE = 0 ... 1A / 0 ... 5 A

    Auxiliary voltage H = Hn 1 %

    Frequency 50 Hz...60 Hz

    Curve shape Sinusoidal, form factor1.1107

    Load (only for characteristics E91..E99) Rn = 5 V / Y2 1 %

    Other IEC 688 - Part 1

    Transmission behaviour of the analogue

    outputsError limit 0.05% / 0.25% / 0.5% / 1%

    related to Y2 (see Meas-

    rement quantities)Measurement cycle time 10 ms

    Electrical safetyProtection class I

    Degree of pollution 2

    Overvoltage category II, III

    Operating voltages

    Notes: All test voltages are AC voltages in kV which may be applied for 1 minute.

    E-LAN, COM2, COM3 are tested against each other with 0.5 kV.

    EMC requirements EN 61326-1

    Device class AContinuous, non-monitored

    operation, in industrial

    applications and EN 61000-6-2

    and 61000-6-4

    Emitted interference

    Conducted EN 61326 Table 3 and

    and radiated EN 61000-6-4emission

    Harmonic currents EN 61000-3-2

    Voltage fluctuations EN 61000-3-3

    and flicker

    Immunity to interference EN 61326 Table A1 and

    EN 61000-6-2

    ESD IEC 61000-4-2

    8 kV / 15 kV contact / air

    Electromagnetic fields IEC 61000-4-380 2000 MHz: 10 V/m

    Fast transients IEC 61000-4-4 4kV / 2kV

    Surge voltages IEC 61000-4-5 4kV / 2kV

    Conducted IEC 61000-4-6HF signals 150 kHz 80 MHz: 10 V

    Magnetic fields with heavy IEC 61000-4-8

    electrical frequencies 100 A/m (50 Hz), continuous

    1000 A/m (50 Hz), 1 s

    Voltage dips IEC 61000-4-11

    30 % / 20 ms, 60 % / 1 s

    Interruptions to the voltage IEC 61000-4-11

    100 % / 5s

    Damped oscillations IEC 61000-4-12,

    Class 3, 2.5 kV

    Technical Data REG-DA

    A. Eberle GmbH & Co. KG 6

  • 7/27/2019 A-eberle Dt Reg-da Gb

    7/20

    Product Type Fibre Pmin

    [dBm]2)

    Pmax

    [dBm]2)

    Glass ST

    Glass SMA

    HFBR 2412 T

    HFBR 2402

    0 ... 5 MBd

    = 820 nm

    100/140 m

    NA=0.3

    -24.0 -10.0

    POF_ST HFBR 2515 B

    0 ... 10 MBd

    = 650 nm

    1 mm POF -20.0 0.0

    200m HCS -22.0 -2.0

    POF_SMA HFBR 2505 C

    0 ... 10 MBd

    = 650 nm

    1 mm POF -21.6 -2.0

    200m HCS -23.0 -3.4

    Product Type Fibre Pmin

    [dBm]

    1)

    Pmax

    [dBm]

    1)

    Glass ST

    Glass SMA

    HFBR 1414 T

    HFBR 1404

    = 820 nm

    50/125 m

    NA=0.2

    -19.8 -12.8

    62.5/125 m

    NA=0.275

    -16.0 -9.0

    100/140 mNA=0.3

    -10.5 -3.5

    200m HCS

    NA=0.37

    -6.2 +1.8

    POF_ST HFBR 1515B

    = 650 nm1 mm POF -7.5 -3.5

    200m HCS -18.0 -8.5

    POF_SMA HFBR 1505C

    = 650 nm

    1 mm POF -6.2 0.0

    200m HCS -16.9 -8.5

    Characteristic H0 H2

    AC (internal) - -

    AC 85 ... 264 V -

    DC 88 ... 280 V 18 ... 72 V

    Power input 15 VA 10 WattsFrequency 50 Hz -

    Microfuse T2 250 V T2 250 V

    Mechanical designHousing Sheet steel, RAL 7035 grey

    Height 288 mm

    Width 216 mm

    Total depth 114 mm

    Mounting depth 87 mm

    Weight 3 kg

    Housing doors With silica glassFront plate Plastic, RAL 7035 grey on

    aluminium support

    Control panel cutout

    Height 282 mm

    Width 210 mm

    Degree of protection IP 54Rain Test 3R UL50

    Power supply

    The following applies to all characteristics:

    Voltage dips at nominal voltage that last 50 ms cause neither

    a loss of data nor a malfunction.

    StorageDevice parameters Serial EEPROM with

    1000 k recording/reading

    cyclesRAM data Li battery laser-welded

    (recorder function

    characteristic S1)

    Environmental requirements

    Dry, cold IEC 60068-2-1, - 15 C / 16 h

    Dry, hot IEC 60068-2-2, + 65 C / 16 h

    Constant humid heat IEC 60068-2-78

    + 40 C / 93 % / 2 days

    Cyclical humid heat IEC 60068-2-30

    12+12 h, 6 cycles

    +55 C / 93 %

    Toppling IEC 60068-2-31

    100 mm drop, unwrapped

    Vibration IEC 60255-21-1, class 1

    Impact IEC 60255-21-2, class 1

    Resistance to earthquakes IEC 60255-21-3, class 1

    Electrical logical interface

    Logic level of receiving output: CMOS

    (Uhmin : > 0.9 V CC, Ulmax < 0.1 V CC @ Io = 1 mA)

    Logic level of transmitting input: CMOS

    (Uhmin : > 0.7 V CC, Ulmax < 0.3 V CC), Schmitt-Trigger

    1) TA = 0..70C, IF= 60 mA, measured after 1 m fibre optic cable.

    2) TA = 0..70C, VCC = 5 V 5%, output level LOW (active)

    Optical receiver

    Optical transmitter

    Optical interface

    The REG-DA Regulator can be equipped with a fibre optic

    interface.(ST or FSMA connectors).Both plastic and glass

    fibre are supported for Multimode transmission.

    Characteristics V13 to V19 give an overview of the variouspossibilities.

    Technical Data REG-DA

    7 A. Eberle GmbH & Co. KG

  • 7/27/2019 A-eberle Dt Reg-da Gb

    8/20

    F33

    F22

    F11

    F44

    F55

    AUTOUTO REMOTEEMOTE

    LOCALOCAL

    ACKCK

    MENUENUESCSC

    REG-DA

    SERVICE

    BLOCKED

    REGSys www.regsys.de

    12

    18 87 250

    281

    x

    209

    307

    Panel mountingRear view

    Cutout

    282 x 210 mm

    Panel

    Mechanical dimensions

    Mechanical dimensions, panel mounting

    Technical Data REG-DA

    A. Eberle GmbH & Co. KG 8

  • 7/27/2019 A-eberle Dt Reg-da Gb

    9/20

    Standard DIN- railRear viev

    mounting

    127

    65

    surface / wall-mountingRear view

    2

    52

    270

    200

    3

    28

    6.5

    5.5

    Mechanical dimensions, standard mounting rail assembly

    Mechanical dimensions, wall mounting

    Technical Data REG-DA

    9 A. Eberle GmbH & Co. KG

  • 7/27/2019 A-eberle Dt Reg-da Gb

    10/20

    Level III

    Level II

    Level I

    Furthermore, additional binary inputs and outputs as well

    as mA inputs and outputs can also be accommodated onLevel II.

    In total two spare slots are available and they can be equipped

    with the following modules:

    Module 1: 6 binary inputs, 48 V...250 V AC/DC

    Module 2: 6 relay outputs

    Module 3: 2 mA inputs

    Module 4: 2 mA outputs

    General information about the connec-

    tionsThe regulator is equipped with three circuit board / connection

    levels.

    The auxiliary voltage, input voltage and currents, as well as the

    relay outputs, binary inputs, etc. are connected to Level I.

    The hardware for all the instrumentation and control connec-

    tions is contained on Level II.The appropriate connection elements on Level II must be

    used for RS232 or RS485 connections.

    If an ethernet connection is used, the corresponding con-nection on Level II is also available (must be connected for

    IEC 61850 or IEC 60870-5-104!).

    For fibre optic cable connections ST or FSMA connectors are

    mounted directy on the flange plate.This provides acess forcable termination without having to open the Regulator.

    Level III contains the connections for the individual COMs,

    E-LAN, the analogue inputs and outputs as well as the PT 100direct connection / resistance input for the tap-change poten-

    tiometer of the motor drive / the tap-changer.

    Fibre optic cable connection (ST connection)

    Fibre optic cable connection (FSMA connection)

    Technical Data REG-DA

    A. Eberle GmbH & Co. KG 10

  • 7/27/2019 A-eberle Dt Reg-da Gb

    11/20

    65

    66

    68

    *

    No.

    LevelI

    Option M1* M2* Triple-wound transformer*

    2 Input voltageU1

    UL1U15 Input voltage UL2

    8 Input voltage - UL3 U210 Input voltage -

    1 kCurrent input I1

    3 l

    4 kCurrent input I26 l

    7 kCurrent input I39 l

    21 L / (+)UH = Auxiliary voltage

    22 L / (-)

    LevelIII

    63 mA input + A1

    64 mA input - A1

    61 mA input or output + A262 mA input or output - A2

    65 mA input or output + A3

    66 mA input or output - A3

    67 mA input or output + A4

    68 mA input or output - A4

    LevelI

    11 Binary input 1 Activity lamp

    12 Binary input 2 Freely programmable

    13 Binary input 3 Freely programmable

    14 Binary input 4 Freely programmable

    15 Binary input 1...4 GND

    16 Binary input 5 AUTO

    17 Binary input 6 MANUAL18 Binary input 7 Freely programmable

    19 Binary input 8 Freely programmable

    20 Binary input 5...8 GND

    23 Binary input 9 BCD 1

    24 Binary input 10 BCD 2

    25 Binary input 11 BCD 4

    26 Binary input 12 BCD 8

    27 Binary input 9...12 GND

    28 Binary input 13 BCD 10

    29 Binary input 14 BCD 20

    30 Binary input 15 BCD sgn.

    31 Binary input 16 Freely programmable

    32 Binary input 13...16 GND

    33Freely programmable R534

    35Freely programmable R4

    36

    37Freely programmable R3

    38

    39

    Lower R240

    41

    42

    43

    Raise R144

    45

    46

    Nr.

    Level

    I

    47 > I R1148 > U R1049 < U R950 Local R851 Remote R7

    52 TC error ** R653 GND R6...R1154 Closes if fault occurs

    R1355 Life contact (status)

    56 opens if fault occurs

    57 MANUAL

    R1258 MANUAL / AUTO

    59 AUTO

    LevelIII

    69 E-

    E-LAN (L)70 E+

    71 EA-

    72 EA+

    73 E-

    E-LAN (R)74 E+

    75 EA-

    76 EA+

    77 Tx+

    COM 3 (RS 485)78 Tx-

    79 Rx+

    80 Rx-

    81

    COM 2 (RS 232)

    82 TxD

    83 RxD

    84 RTS

    85 CTS

    86 GND

    LevelII

    IEC

    LON

    DNP 3.0

    ***

    SPA bus

    Modbus

    See Level II pin assignment for additional

    Level II connections (page 13)

    * Option M1

    Used for standard applications,

    balanced load (I1= I

    2= I

    3).

    Option M2

    Only used for unbalanced load (I1 I2 I3).

    Two different voltage inputs for U1 and U2 are required

    fortriple-wound transformer applications.

    ** TC = tap changer

    *** Please refer to the instrumentation and control

    connections listed in the operating manual.

    The assignment of pins 23 to 32 changes depending on

    D0/D1/D4 and D2/D3.

    Terminal assignment

    Technical Data REG-DA

    11 A. Eberle GmbH & Co. KG

  • 7/27/2019 A-eberle Dt Reg-da Gb

    12/20

    SERVICE

    BLOCKED

    F33

    F22

    F11

    F44

    F55

    AUTOUTO REMOTEEMOTE

    LOCALOCAL

    ACKCK

    MENUENUESCSC

    REG-DAEG-DA a-eberle

    Display-Mae67,8 x 67,8 mmX = 114,5Y = 88,5

    1 2 3 4 5 6 7 8 9 10

    33 3 4 35 3 6 37 3 8 39 4 0 41 4 2 43 4 4 45 46 47 4 8 49 5 0 51 5 2 53 54 5 5 56 5 7 58 5 9 60

    11 1 2 1 3 1 4 1 5 1 6 1 7 18 19 20

    2122

    2 3 2 4 2 5 2 6 2 7 2 8 29 30 31 32

    Binary inputs

    107108109110111 112113100101102103104105106 87 88 89 90 91 92 93 94

    1 56 9

    77 78 79 80 81 81 83 84 85 8661 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 COM 1

    Ethernet connection(IEC 61850, IEC 60870-5-104)

    Relay outputs

    Binary inputs

    Level III

    Level II

    Level I

    SERVICE

    BLOCKED

    F33

    F22

    F11

    F44

    F55

    AUTOUTO REMOTEEMOTE

    LOCALOCAL

    ACKCK

    MENUENUESCSC

    REG-DAEG-DA a-eberle

    Display-Mae67,8 x 67,8 mmX = 114,5Y = 88,5

    1 2 3 4 5 6 7 8 9 10

    33 3 4 35 3 6 37 3 8 39 4 0 41 4 2 43 4 4 45 4 6 47 4 8 49 5 0 51 5 2 53 5 4 55 5 6 57 5 8 59 6 0

    11 12 13 14 15 16 1 7 1 8 1 9 2 0

    2122 ON

    1 2

    23 24 25 2 6

    107108109110111112 113100101102103104105106 87 88 89 90 91 92 93 94

    1 56 9

    77 78 79 80 81 81 83 84 85 8661 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 COM 1

    Ethernet(IEC 61850, IEC 60870-5-104)

    connection

    Relay outputs

    Binary inputs

    Tap-changepotentiometer input

    Level III

    Level II

    Level I

    Location of the connection terminals,

    Characteristics D0, D1, D4

    Location of the connection terminals,

    Characteristics D2, D3

    Technical Data REG-DA

    A. Eberle GmbH & Co. KG 12

  • 7/27/2019 A-eberle Dt Reg-da Gb

    13/20

    Level II pin assignmentCharacteristics C01 ... C09

    Characteristic C01

    6 additional binary inputs, 48 V ... 250 V AC/DC

    No.

    Module1

    100 Binary input E17

    101 Binary input E18102 Binary input E19

    103 Binary input E20

    104 Binary input E21

    105 Binary input E22

    106 GND E17 ... E22

    Characteristic C0212 additional binary inputs, 48 V ... 250 V AC/DC

    No.

    Module

    1

    100 Binary input E17

    101 Binary input E18

    102 Binary input E19103 Binary input E20

    104 Binary input E21

    105 Binary input E22

    106 GND E17 ... E22

    Module1

    107 Binary input E23

    108 Binary input E24

    109 Binary input E25

    110 Binary input E26

    111 Binary input E27

    112 Binary input E28

    113 GND E23 ... E28

    Characteristic C03

    6 additional relay outputs (NO contact)

    No.

    Modue2

    100 R14

    101 R15

    102 R16

    103 R17

    104 R18

    105 R19

    106 GND R14 ... R19

    Characteristic C0412 additional relay outputs (NO contact)

    No.

    Module2

    100 R14

    101 R15

    102 R16

    103 R17

    104 R18

    105 R19

    106 GND R14 ... R19

    Module2

    107 R20

    108 R21

    109 R22

    110 R23

    111 R24

    112 R25

    113 GND R20 ... R25

    Characteristic C05

    6 additional binary inputs, 48 V ... 250 V AC/DC and6 relay outputs (NO contact)

    No.

    Modu

    le1

    100 Binary input E17

    101 Binary input E18

    102 Binary input E19

    103 Binary input E20104 Binary input E21

    105 Binary input E22

    106 GND E17 ... E22

    Module2

    107 R14

    108 R15

    109 R16

    110 R17

    111 R18

    112 R19

    113 GND R14...R19

    Characteristic C074 additional analogue inputs

    No.

    Module

    3 100Analogue input

    +E10101 -

    102Analogue input

    +E11

    103 -

    Module3 104

    Analogue input+

    E12105 -

    106Analogue input

    +E13

    107 -

    Characteristic C062 additional analogue inputs

    No.

    Module3 100

    Analogue input+

    E10101 -

    102Analogue input

    +E11

    103 -

    Characteristic C094 additional analogue outputs

    No.

    Module4 100

    Analogue output+

    A10101 -

    102Analogue output

    +A11

    103 -

    Module4 104

    Analogue output+

    A12105 -

    106Analogue output

    +A13

    107 -

    Characteristic C082 additional analogue outputs

    No.

    Module4 100 Analogue output + A10

    101 -

    102Analogue output

    +A11

    103 -

    Technical Data REG-DA

    13 A. Eberle GmbH & Co. KG

  • 7/27/2019 A-eberle Dt Reg-da Gb

    14/20

    RS232

    COM

    1

    Terminalno.

    Level

    Level

    Level

    Level

    Legen

    d:

    optio

    nal

    E1...E4

    TCinop.

    progr.

    progr.

    progr.

    AUTO

    MANUAL

    progr.

    progr.

    E5...E8

    InputsE1...E8

    50...230V

    AC/DC

    11

    12

    13

    14

    15

    16

    17

    18

    19

    20

    E9...E12

    BCD1

    BCD10

    BCD20

    BCDsgn.

    progr.

    E13...E16

    Inp

    utsE9...E16

    50...230V

    AC/DC

    24

    2526

    27

    28

    29

    30

    31

    32

    BCD2

    BCD4BCD8

    GND

    E1

    E2

    E3

    E4

    E5

    E6

    E7

    E8

    GND

    GND

    E9

    E13

    E14

    E15

    E16

    GND

    E10

    E11E12

    )

    23

    LCD

    P

    LE

    D

    RAM/ROM

    128x128DOTS

    display

    Keyboard

    C

    LOCK

    U1

    2 5

    U

    U2

    8 10

    U

    I1

    1 3

    I

    I2

    4 6

    I

    I3

    7 9

    I

    L

    /(+)

    21

    22

    L

    /(-)

    CharacteristicM2

    CharacteristicM2

    UH

    )

    61

    2

    3

    4

    5

    7

    8

    9

    GND

    CTS

    TXD

    RTS

    RXD

    )))

    Analogueinputsandoutputs

    61

    62

    656

    6

    67

    68

    A2

    A3

    A4

    63

    64

    A1

    mAinput

    InputoroutputCharacteristiclE91...9

    9

    +

    )))

    Doublemodulel

    +

    +

    +

    -

    -

    -

    -

    mAinput

    Inputoroutput

    Inputoroutput

    Inputoroutput

    Inputoroutput

    Inputoroutput

    +

    +

    +

    +

    -

    -

    -

    -*

    R2

    R3

    progr.

    R4

    progr.

    R5

    343536373839404142434445

    R1

    46

    GND

    R6...R11

    R6

    TC

    fault

    R7

    Remote

    R8

    Local

    R9

    U

    R11

    >I

    52515049484753575859545556

    MANUAL

    Lifecontact

    (Status)

    progr.

    Relayoutputs48...250VAC/DC

    Relayoutputs48...250VAC/DC

    Lower

    Raise

    33

    )

    R12

    Closes

    MANUAL/AUTO

    R13

    Opens

    AUTO

    CTS

    RTSCOM2

    RS232

    COM3

    RS485

    85

    84

    86

    83

    82

    80

    79

    78

    77

    GND

    RxD

    TxD

    Rx-

    Rx+

    Tx-

    Tx+

    E+

    EA-

    EA+

    69

    70

    71

    72

    73

    74

    75

    76

    E-LAN

    L

    E-LAN

    R

    E-

    E+

    EA-

    EA+

    E-

    )))

    81

    IEC

    LON

    DNP3.0

    MODBUS

    FSMA

    ST

    IEC

    DNP3.0

    LON

    SPABUS

    ))

    100

    113

    ))

    Additional

    inputsandoutputs

    CharacteristicC01...C09

    (Seepinassignment

    onpage13)

    ))

    REG-DA block diagram

    *) The double module can either be a double-mA input or a double-mA output module.

    If direct temperature detection is required, the space is occupied by a PT 100 module.

    Technical Data REG-DA

    A. Eberle GmbH & Co. KG 14

  • 7/27/2019 A-eberle Dt Reg-da Gb

    15/20

  • 7/27/2019 A-eberle Dt Reg-da Gb

    16/20

    Parameterisation

    Recorder modeYT time grid 14 sec/div, 1 min/div,

    5 min/div,10 min/div,

    All measured values are stored in seconds, independent of

    the selected YT time grid (feed speed).

    The value every second represents the arithmetic average of

    the previous 10 measurement values generated in intervals

    of 100 ms.

    Memory behaviour Overwriting;

    with excess data FIFO overwriting

    (First In First Out)

    Storage time > 18.7 days worst case

    (voltage plus tap On average > 1 monthchange position)

    Measurement transducer modeMeasurement quantities Voltage Ueff

    on the display Current IeffActive power P

    Reactive power Q

    Apparent power S

    cos

    Reactive current I sin

    Frequency f

    Analogue output Max. three mA outputs

    (2.5, 5, 10, 20 mA bipolar)

    Refer to the list of characteri-stics

    Characteristic curve Linear, with corner

    Max. load RA max RA = 10 V/IANR

    Load

    IAN

    Nominal value of the outputcurrent

    REG-DA parameters (selection)

    WinREG parameterisation and configura-

    tion software

    WinReg was designed for the set up and programming of

    the REG-DA. WinREG can be operated in three different

    modes.

    In the Panel mode, up to six regulators can be simultaneously

    displayed and operated via the mouse.All settings which can be directly entered via the regulators

    membrane keypad can be carried out centrally with WinREG,

    provided that all regulators are connected to each other via

    E-LAN.

    This operating mode provides a considerably simplified and

    more transparent operation, particularly when the transformers

    are operated in parallel.

    If WinREG is used to change all the regulators on the trans-formers that are operating in parallel into the measurement

    transformer mode, all the circulating reactive currents of the

    transformers can be displayed on a PC monitor in real time.

    The Parameter mode allows for easy setup.Individual settings

    can be entered, stored for future use or transferred to a station

    using the clearly structured tab format.The Terminal-Mode provides the possibility of direct commu-nication with the system.

    Therefore, WinREG terminal is far easier to use than traditio-

    nal terminal programs and considerably simplifies the system

    programming.

    WinREG runs under Windows 95, 98, Windows 2000, NT

    or Windows XP and is also available in a modem enabled

    version for remote access.

    Parameters Setting rangePermissible regulative deviation 0.1 ... 10%

    Time factor 0.1 ... 30

    1st setpoint value 60.0 ... 140.0 V

    2nd setpoint value 60.0 ... 140.0 V

    3rd setpoint value 60.0 ... 140.0 V

    4th setpoint value 60.0 ... 140.0 V

    Time behaviour

    U t = const

    REG 5A/E

    LINEAR

    CONST

    Current influence

    Apparent current

    Active current

    Reactive current

    LDC

    Apparent current / active current

    Gradient

    Limitation

    0 ... 40 %

    0 ... 40 %

    LDC

    (Line-Drop Compensation)

    R : 0 ... 30

    X : 0 ... 30

    Undervoltage U 0 ... 25 %

    Overcurrent >I 0 ... 210 % (1A / 5A)

    Tripping 60 V ... 160 V

    High-speed forward switching 0 ... -35 %

    High-speed backward switching 0 ... 35 %

    Standstill -75 % ... 0 %Switching delay for U,

  • 7/27/2019 A-eberle Dt Reg-da Gb

    17/20

    CHARACTERISTIC CODE

    REG-DA voltage regulator

    Standard version, with double E-LAN interface,

    COM 2, COM 3 and a mA input channel e.g. to measure oil temperature

    or to measure tap-change position via resistance measurement transformer,

    with 16 binary inputs and 12 relay outputs plus status output

    Includes WinREG software to configure, program and display all regulator data. Includes

    connection cable.

    Note: Com 2 when no Scada connection is required.

    REG-DA

    Design: Panel-mounting or wall-mounting version (H x W x D) 307 x 250 x 102 mm

    with standard mounting rail adapter

    B0

    B1

    Power supply: External 85 V ... 110 V ... 264 V AC / 88 V ... 220 V ... 280 V DCExternal 18 V ... 60 V ... 72 V DC

    H0H2

    Input currents

    (can be altered later)

    IEN 1 A

    IEN 5 A

    F1

    F2

    Measurement transducer display functions for network quantities

    Three-conductor three-phase current with balanced load

    Three-conductor three-phase unbalanced loads

    Voltage measurement (upper voltage), current and voltage measurement (lower voltage)

    and other applications of the three current transformers and the two voltage transformers

    M1

    M2

    M3

    M9

    Recorder functions for network quantities with evaluation software without

    with

    S0

    S1

    Transformer monitoring without

    with

    T0

    T1Parallel operation without firmware for parallel operation

    with firmware for parallel operation

    K0

    K1

    Additional analogue inputs and outputs

    without

    with one PT 100 input

    with two mA inputs

    with two mA outputs

    with one PT 100 input and one mA output

    with two mA inputs and one mA output

    with three mA outputs

    Tap-change potentiometer input, total resistance 200 Ohm ... 2 kOhm

    Tap-change potentiometer input, total resistance >2 kOhm ... 20 kOhmother combinations of inputs and outputs

    Note for XE91...XE99:

    If known, please specify the scale!

    E.g.: 1 -100 ... 0 ... +100 MW E.g.: 2 0 ... 80 ... 120 V

    -20 ... 0 ... +20 mA 4 ... 16 ... 20 mA

    E.g.: 3 1 ... 19 taps E.g.:4 50 ... 140C

    0 ... 20 mA 4 ... 20 mA

    E00

    E91

    E92

    E93

    E94

    E95

    E96

    E97

    E98E99

    Binary inputs and tap-change potentiometer input

    Bi1...Bi16 48V...250V AC/DC

    Bi1...Bi8 48V...250V AC/DC and Bi9...Bi16 10V...48V AC/DC

    1 tap-change potentiometer input (total resistance 200...2 kOhm) and 8 binary inputs, 48V...250V AC/DC

    1 tap-change potentiometer input (total resistance >2...20 kOhm) and 8 binary inputs 10V...48V AC/DC

    Bi1...Bi16 10V...48V AC/DC

    D0

    D1

    D2

    D3

    D4

    Order details Only one code may be selected from codes with identical capital letters.

    If the digit 9 follows the capital letter in the code, additional information in text form is required.

    If only zeroes follow the capital letter in the code, they can be omitted from the code.

    X characteristics e.g. XE91 cannot be freely combined with all other characteristics. Please note the extra information in

    the text.

    Technical Data REG-DA

    17 A. Eberle GmbH & Co. KG

  • 7/27/2019 A-eberle Dt Reg-da Gb

    18/20

    Characteristic CODE

    REG-DA

    Level II: additional inputs and outputs

    without

    with 6 binary inputs 48 V...250 V AC/DC

    with 12 binary inputs 48 V...250 V AC/DC

    with 6 relay outputs

    with 12 relay outputs

    with 6 binary inputs and 6 relay outputs

    with 2 analogue inputs

    with 4 analogue inputs

    with 2 analogue outputs

    with 4 analogue outputs

    other combinations of 6 inputs, 6 outputs, 2 analogue inputs, 2 analogue outputs

    Note about C90: Two slots are normally available on Level II.

    Each terminal can be equipped with either 6 binary inputs, 6 binary outputs or

    an analogue module.Each analogue module has either 2 inputs or 2 outputs.

    The regulator can be equipped with 4 additional modules if no instrumentation and control

    connections (XW90, 91 or L1, L9) are used.

    C00

    C01

    C02

    C03

    C04

    C05

    C06

    C07

    C08

    C09

    C90

    Integrated instrumentation and control connections according to IEC61850 or IEC 60870- 5-104

    without

    IEC 60850 - 5 - 104 (extended with group of characteristics G)

    Note: please enter target system if to be connected according to IEC 60850-5-104

    IEC 61850 (extended with group of characteristics G)

    XW00

    XW90

    XW91

    Integrated instrumentation and control connections according to IEC 60870- 5-101/ ..-103, DNP

    without (extended with group of characteristics G)

    for the instrumentation and control connection of a REG-DA

    or the instrumentation and control connection of multiple systems (REG-D/DA/DP, etc.)Note: L9 can only be combined with characteristics XW90, Z15 to Z19 and Z91.

    L0

    L1

    L9

    Type of connection:

    Copper RS 232

    RS 485, 2-wire operation only

    V10

    V11

    Fibre optic cable with FSMA connection

    Glass fibre (wavelength 800...900 nm, range 2000 m)

    plastic (wavelength 620...680 nm, range 50 m)

    V13

    V15

    Fibre optic cable with ST connection

    Glass fibre (wavelength 800...900 nm, range 2000 m)

    plastic (wavelength 620...680 nm, range 50 m)

    V17

    V19

    Protokoll:

    IEC60870-5-103 for ABB

    IEC60870-5-103 for Areva

    IEC60870-5-103 for SAT

    IEC60870-5-103 f0r Siemens (LSA/SAS)

    IEC60870-5-103 f0r Sprecher Automation

    IEC60870-5-103 for other

    IEC60870-5-101 for ABB

    IEC60870-5-101 for IDS

    IEC60870-5-101 for SAT

    IEC60870-5-101 for Siemens (LSA/SAS)

    IEC60870-5-101 for other

    DNP 3.00

    LONMark

    SPABUS

    MODBUS RTU

    Z10

    Z11

    Z12

    Z13

    Z14

    Z90

    Z15

    Z17

    Z18

    Z19

    Z91

    Z20

    Z21

    Z22

    Z23

    Characteristics continued

    Technical Data REG-DA

    A. Eberle GmbH & Co. KG 18

  • 7/27/2019 A-eberle Dt Reg-da Gb

    19/20

    CHARACTERISTIC CODE

    REG-DA

    Operating manual German

    English

    French

    Spanish

    Italian

    Russian

    Other

    G1

    G2

    G3

    G4

    G5

    G6

    G9

    Display language German

    English

    French

    Spanish

    Italian

    Russian

    Other

    A1

    A2

    A3

    A4

    A5

    A6

    A9

    Additions to REG-DA CODE

    Profibus-DP interface module

    can be installed on standard mounting rails, without power supply for ext. Uh 24 V DC

    Dimensions: (120 x 75 x 27) mm

    incl. RS 485 interface and connection cable

    Profibus DP

    10MB/s TCP/IP adapter

    can be installed on standard mounting rails with power supply for Uh 230 V AC

    as 8TE plug-in module, 3HE with power supply: 85 V...110 V...264 V AC / 88 V...220 V...280 V DC

    as 8TE plug-in module, 3HE with power supply: 18 V...60 V...72 V DC

    100MB/s TCP/IP adapter

    TCP/IP Adapter

    A01

    A02

    A03

    A90Fibre optic cable module

    with ST connection (glass or plastic)

    with FSMA connection (glass or plastic)

    Modul 2

    A90

    A91

    Software for REG-DA CODE

    Collect / recorder module added to WinREG

    to read and display the REG-D/DA recorder data on CD-ROM WinREG

    REGSim (Windows 95, 98 and NT, XP, 2000)

    to simulate parallel operation of transformers on CD-ROM REGSim

    Continuation of characteristics

    Technical Data REG-DA

    19 A. Eberle GmbH & Co. KG

  • 7/27/2019 A-eberle Dt Reg-da Gb

    20/20

    Accessories Ident. No.

    Cable for PC connection (null modem cable) 582.020 8

    Cable for modem connection 582.2040

    1 pack of T2 L 250 V microfuses 582.1019

    Fibre optic cable coupler 111.9030.10

    DCF 77 radio clock 111.9024

    Modem for REG-Dx/EOR-D/PQI-D/MMU-D (standard version Uh: 230 V AC) 111.9030.02

    Modem for industrial applications Uh: 230 V AC 111.9030

    Analogue input module (2 inputs) 320.0004

    Analogue output module (2 outputs) 320.0003

    Analogue input module (1 input) 356.2009.00

    Analogue output module (1 output) 320.0007

    Input module for tap-change potentiometer total resistance 200 Ohm...2 kOhm 320.0002

    Input module for tap-change potentiometer total resistance >2 kOhm...20 kOhm 320.0002.1

    Additional input module for PT 100 according to DIN 43760 in 3-conductor circuit. 320.0005

    E- LAN Y-connection with booster REG-ST

    E- LAN PC adapter with booster REG-PC

    E- LAN PC adapter Y-connection with booster REG-ST3

    E- LAN booster (wide-range network) REG-B0

    REG-DA operating manual G1...G8 (please specify language) Gx

    Technical Data REG-DA

    presented by:A.Eberle GmbH & Co. KG