12-20-(24)-KV-HXLP-DSTA---pdic01114

download 12-20-(24)-KV-HXLP-DSTA---pdic01114

of 2

Transcript of 12-20-(24)-KV-HXLP-DSTA---pdic01114

  • 7/29/2019 12-20-(24)-KV-HXLP-DSTA---pdic01114

    1/2www.pdic.com PDIC01114 | 10.08.04

    12/20 (24) KV HXLP-DSTA

    High Voltage Cross-Linked Polyethylene Three Cores Cable12/20 (24) KV, Copper Conductor with Double Steel Tape Armor

    Detail Descriptionor ConstructionConductor

    Compact round stranded copper

    Conductor Shield

    Semi-conducting tape and/or Semi-

    conducting cross-linked polyethylene

    Insulation

    Cross-linked polyethylene

    Insulation Shield

    Semi-conducting cross-linked polyethylene

    Shield

    Copper tape shield

    Filler

    Polypropylene (Nonhygroscopic material)

    Binding Tape

    Polyester and/or Spunbond tape

    Bedding

    Black polyethylene

    (Optional: Polyvinyl chloride)

    Armor

    Double steel tape

    SheathBlack polyethylene (ST 7)

    (Optional: Polyvinyl chloride)

    ApplicationPreferably used for urban networks. Exposed

    in aerial, direct burial, conduit, open tray and

    underground duct installation.

    Standards / Testing

    Specifications IEC 60502-2.

    Marking12/20 (24) KV HXLP-DSTA 3 X SIZE

    SQ.MM., PHELPS DODGE.

    InstallationHXLP-DSTA cable can be installed in

    aerial, direct burial, conduit, open tray and

    underground. It is recommended that theinstallation instructions indicated by the

    Local Electric Code, or any equivalent, be

    followed, so that the safe guarding of

    persons and the integrity of the product

    will not be affected by deficiencies in the

    installation.

    1

    Conductor

    PE Sheath

    Steel

    Wire

    Insulation

    Insulation

    Shield

    Bedding

    Conductor

    Shield

    Cooper Tape

    Binding Tape

    PP Filler

  • 7/29/2019 12-20-(24)-KV-HXLP-DSTA---pdic01114

    2/2www.pdic.com PDIC01114 | 10.08.04

    12/20 (24) KV HXLP-DSTA

    High Voltage Cross-Linked Polyethylene Three Cores Cable12/20 (24) KV, Copper Conductor with Double Steel Tape Armor

    2

    Nominal

    Sectional

    Area

    Minimum

    Number

    of Wires

    Diameter

    of

    Conductor

    (Approx)

    Thickness

    of Insulation

    Diameter

    Over

    Insulation

    (Approx)

    Thickness

    of Steel

    Tape

    Armor

    Diameter

    Over

    Armor

    (Approx)

    Thickness

    of Sheath

    Overall

    Diameter

    (Approx)

    Maximum

    DC.

    Resistance

    of Cdr.

    @ 20C

    Minimum

    Insulation

    Resistance

    @ 20C

    Ampacities

    Direct

    Burial in

    Ground

    @ 30C

    Ambient**

    Allowable

    Ampacities

    in Free Air

    @ 40C

    Ambient

    Cable

    Weight

    (Approx)

    Standard

    Packing

    mm mm mm mm mm mm mm mm / km M - km A A kg / km m / reel

    35 7 6.9 5.5 18.7 2x0.5 51.3 2.7 58 0.524 1417 160 175 3934 500

    50 7 8.0 5.5 19.8 2x0.5 53.8 2.8 61 0.387 1297 190 205 4500 500

    70 18 9.7 5.5 21.5 2x0.5 57.5 3 65 0.268 1146 230 255 5438 500

    95 18 11.4 5.5 23.2 2x0.5 61.3 3.1 69 0.193 1031 275 305 6510 250

    120 18 12.9 5.5 25.0 2x0.5 65.2 3.2 73 0.153 929 310 350 7558 250

    150 18 14.2 5.5 26.2 2x0.5 69.1 3.3 77 0.124 870 345 390 8745 250

    185 34 16.0 5.5 28.1 2x0.5 73.2 3.4 81 0.0991 795 385 445 10181 250

    240 34 18.4 5.5 30.5 2x0.8 79.8 3.6 88 0.0754 716 435 510 13166 250

    300 34 20.5 5.5 32.8 2x0.8 84.9 3.8 94 0.0601 652 480 575 15479 250

    400 55 23.4 5.5 36.2 2x0.8 92.6 4.0 102 0.0470 578 530 645 18735 250

    **Depth of Laying in Ground 1 m, Rho = 1.2 C-m/watt