HV Cable Jointing Nexans Euromold Elastimold HV Screened ......6/10 (12) kV 6.35/11 (12) kV 8.7/15...
Transcript of HV Cable Jointing Nexans Euromold Elastimold HV Screened ......6/10 (12) kV 6.35/11 (12) kV 8.7/15...
10
6/10 (12) kV6.35/11 (12) kV8.7/15 (17.5) kV
12/20 (24) kV12.7/22 (24) kV
18/30 (36) kV
Up to 36 kV - 630 A
440TBINTERFACE C
TEE CONNECTOR
Technical characteristics• The thick conductive EPDM
jacket provides a total safe totouch screen which ensuressafety for personnel.
• Each separable connector istested for AC withstand andpartial discharge prior toleaving the factory.
ApplicationSeparable tee shapeconnector (bolted type)designed to connect polymericinsulated cable to equipment(transformers, switch gear,motors, ...).Also connects cable to cablewhen using the appropriatemating parts.
DesignSeparable connectorcomprising:
1. Conductive EPDM insert.2. Conductive EPDM jacket.3. Insulating EPDM layer
moulded between the insertand the jacket.
4. Type C - 630 A interfaceas described by CENELECEN 50180 and 50181.
5. Conductor connector.6. Basic insulating plug (with
VD point).7. Cable reducer.8. Conductive rubber cap.9. Clamping screw.
10. Earthing lead.
The screen break designenables cable outer sheathtesting without removing ordismantling the connector.
Specifications andstandardsThe separable connector 440TBmeets the requirements ofCENELEC HD 629.1.
Separableconnector
type
VoltageUm(kV)
CurrentIr
(A)
Conductor size (mm2)
min. max.440TB/GK440TB/GM400TB/G
122436
630630630
185185185
630630630
400 mm
3
2
1
4
5
7
6 8
10
9
255 mm220 mm
11
Kit contentsThe complete (K)(M)440TB/Gtee connector kit comprises thefollowing components:
The kit also comprises lubricant, wipers,installation instructions and crimp chart.
Ordering instructionsTo order the tee connector,select the ordering part numberwhich gives you the bestcentring of your core insula-tion diameter and substitute Xusing table X, according to yourconductor size and type.Add a 'K' for use up to 24 kVand add an 'M' for use up to36 kV.
Orderingpart number
Dia. over core insulation (mm)
min. max.
440TB/G-22-X440TB/G-27-X440TB/G-32-X440TB/G-37-X440TB/G-43-X
23.528.534.039.045.5
31.037.542.548.556.0
Example:The copper wire screened cableis 36 kV, 240 mm2 strandedaluminium with a diameter overcore insulation of 37.0 mm.Order a M440TB/G-32-240(K)M-12-2 tee connector kit.
When installed on anappropriate equipment
bushing:1250 A continuously
For use withcopper tape
screened cables.Order: Kit MT.
+ + +
Connector housing(K)(M)440BT/G
Clampingscrew
400TCS
ConductorcontactTBC-X
Basicinsulating
plug +rubber cap
(K)(M)400BIPA
+
Cable reducer611CA-W
= (K)(M)440TB/G-W-Xconnector kit
Table W
Table X
Conductor size(mm2)
Aluminium conductor Copper conductor
DINhexagonal
Deepindent
DINhexagonal
185240300400500630
185(K)M-12-2240(K)M-12-2300(K)M-12-2400(K)M-12-2500(K)M-12-2
–
185KM-12-1240KM-12-1300KM-12-1400KM-12-1500KM-12-1630KM-12-1
185(K)M-11-2240(K)M-11-2300(K)M-11-2400(K)M-11-2500(K)M-11-2630(K)M-11-2
For use withother cable types.
Please contact ourrepresentative.
For outdoorapplications.
Order: +MWS.
Components can beordered individually.
For use in potentiallyexplosive atmospheres
(for 12 kV max.).Order: -/ATEX.