11MW BOM

4
BOM SL. No Item Technical Specification Make Unit Quantity 1 DC Capacity Watt 11000000 Module Capacity Watt 300 Inverter Output Power Watt 750000 2 Solar Modules-Crystalline Canadian Solar/CNPV Nos. 36666 3 Inverters-with Negative Grounding Kit TMEIC Nos. 14 4 Custom Made MW 11.0 5 Trinity/Hensel/Statcon or eq. Nos. 116 6 Cable Connectors (MC4 male & female) Lapp/Reputed or eq. Nos. 1924 7 POWER AND CONTROL CABLES:-ESTIMATION DC-LT Cables (i) 1CX4mmsq. (Solar)-Cu Advance Cables/KEI/Polycab or eq Mtrs 154000 (ii) 1CX120 mmsq.(SCB to Inverter)-Al Mtrs 24200 (iii) 1CX300mmsq. (Inverter to Transformer)-Al Mtrs 3360 Crystalline silicon power module with OC Voltage~37.7 V, Isc~8.5 Amp, Vmp~30.9V, Imp~8.1 Amp MPPT Controler inverter 750 kW with associated control and protection devices integrated to convert DC Power into 3 Phase AC voltage, along with grid synchronizing facility - voltages 380 Volt AC(+15% to -10%) 3 Phase 50 Hz, Peak Effficiency > 98%, THD Module Mounting Structures - Pre/Post Galvanized and support pads complete with module mounting assembly. Module Mounting Structures - Pre/Post Galvanized. Design as per IS code of wind speed of that perticular area. Electro galvanized nuts and bolt. Design life should be more than 25 Years and minimum yield strength of 340 MPA. 16 Channel String Combiner Boxes and terminal lugs for 4 Sq.mm solar cable Outdoor installation, UV resistant, glass fibre reinfiorsed plastic, self extinguishing, halogen free, IP-55 or Higher (IEC 60529), Voltage grade 650V with earthing stud with self locking door handle, for mounting on rail or cage clamp type suitable for conductor sizes 2.5,4,6,10,16,32,64,100,120,240 mm² cable inlet and outlet as per requirement. Facility for providing fuses for individual circuites, surge arresters & 1000V (IEC/CEI),600V (UL), With safety clip that requires a tool to unlock (NEC2008 compliant) Certified for applications with modules according to IEC 61730, Safety class II,Directive 2002/95/EC on the restriction of the use of certain hazardous substances in electrical and electronic equipment - with Minimal voltage drop, High current-carrying capacity,Minimal power loss, Minimal contact resistance,High durability contacts withstand up to 1 million mating cycles, Operating temperatures up to 350°C,higher temperatures permitted for short Single-pole, double insulated solar cable with fine- wire copper strand. TÜV certified according to the latest regulations. -40°C to +120°C (permanent) UV, ozone and hydrolysis-resistant. LT Power Cable will be 1.1 kV, Armoured or unarmoured, unearthed grade, double core/multi-core, stranded Al conductor as mentioned, XLPE insulated with PVC outer sheath made on PVC compound. Cable will be direct burried in case of Armoured cable and will be laid under HDPE pipes if unarmoured. All other details will be as Indian Standards .IEC Havelles/Advance/RPG/Polycab or eq. Havelles/Advance/RPG/Polycab or eq.

description

Bill of material

Transcript of 11MW BOM

Page 1: 11MW BOM

BOM SL. No Item Technical Specification Make Unit Quantity

1 DC Capacity Watt 11000000Module Capacity Watt 300Inverter Output Power Watt 750000

2 Solar Modules-Crystalline Canadian Solar/CNPV Nos. 36666

3 Inverters-with Negative Grounding Kit TMEIC Nos. 14

4 Custom Made MW 11.0

5 Trinity/Hensel/Statcon or eq. Nos. 116

6 Cable Connectors (MC4 male & female) Lapp/Reputed or eq. Nos. 1924

7 POWER AND CONTROL CABLES:-ESTIMATIONDC-LT Cables

(i) 1CX4mmsq. (Solar)-Cu Advance Cables/KEI/Polycab or eq Mtrs 154000

(ii) 1CX120 mmsq.(SCB to Inverter)-Al Havelles/Advance/RPG/Polycab or eq. Mtrs 24200

(iii) 1CX300mmsq. (Inverter to Transformer)-Al Havelles/Advance/RPG/Polycab or eq. Mtrs 3360

Crystalline silicon power module with OC Voltage~37.7 V, Isc~8.5 Amp, Vmp~30.9V, Imp~8.1 Amp

MPPT Controler inverter 750 kW with associated control and protection devices integrated to convert DC Power into 3 Phase AC voltage, along with grid synchronizing facility - voltages 380 Volt AC(+15% to -10%) 3 Phase 50 Hz, Peak Effficiency > 98%, THD < 3%

Module Mounting Structures - Pre/Post Galvanized and support pads complete with module mounting assembly.

Module Mounting Structures - Pre/Post Galvanized. Design as per IS code of wind speed of that perticular area. Electro galvanized nuts and bolt. Design life should be more than 25 Years and minimum yield strength of 340 MPA.

16 Channel String Combiner Boxes and terminal lugs for 4 Sq.mm solar cable

Outdoor installation, UV resistant, glass fibre reinfiorsed plastic, self extinguishing, halogen free, IP-55 or Higher (IEC 60529), Voltage grade 650V with earthing stud with self locking door handle, for mounting on rail or cage clamp type suitable for conductor sizes 2.5,4,6,10,16,32,64,100,120,240 mm² cable inlet and outlet as per requirement. Facility for providing fuses for individual circuites, surge arresters & blocking diodes as required

1000V (IEC/CEI),600V (UL), With safety clip that requires a tool to unlock (NEC2008 compliant) Certified for applications with modules according to IEC 61730, Safety class II,Directive 2002/95/EC on the restriction of the use of certain hazardous substances in electrical and electronic equipment -with Minimal voltage drop, High current-carrying capacity,Minimal power loss, Minimal contact resistance,High durability contacts withstand up to 1 million mating cycles, Operating temperatures up to 350°C,higher temperatures permitted for short periods

Single-pole, double insulated solar cable with fine-wire copper strand. TÜV certified according to the latest regulations. -40°C to +120°C (permanent) UV, ozone and hydrolysis-resistant.

LT Power Cable will be 1.1 kV, Armoured or unarmoured, unearthed grade, double core/multi-core, stranded Al conductor as mentioned, XLPE insulated with PVC outer sheath made on PVC compound. Cable will be direct burried in case of Armoured cable and will be laid under HDPE pipes if unarmoured. All other details will be as Indian Standards .IEC 60189: IS 694/ IS 1554/IS/IEC 69948

Page 2: 11MW BOM

SL. No Item Technical Specification Make Unit Quantity1 OIL FILLED POWER TRANSFORMERS:

Essennar/Voltamp/Tesla or eq. Nos.7

ii) Auxiliary Transformer Swastik/Uttam Nos. 1

2 Nos. 7

3 Standard Nos. 7

4 L&T/SKYTRON/Inaccess or Eq. MW 11

FOC Cable for SCADA Multimode and Single mode Fiber cable as per design requirement D-Link/Spiktel Mtrs 33005 POWER CABLES:-

A. LT Cables

Mtrs

Al Cable 3.5Cx50 sqmm Armoured (Aux Xmer to Inverter Room) Havelles/Polycab/RPG or eq. 2200Copper Cable 3Cx2.5sqmm Armoured Havelles/Polycab/RPG or eq. 1100Copper Cable 4Cx2.5sqmm Armoured Havelles/Polycab/RPG or eq. 1400Copper Cable 12Cx2.5sqmm Armoured (Control Cable) Havelles/Polycab/RPG or eq. 1750Copper Cable 4Cx6 sqmm Armoured Havelles/Polycab/RPG or eq. 1100B. HT CablesOverhead ACSR Conductor Standard Mtrs 700

Havelles/Polycab/RPG or eq. Mtrs 1400

6 Custom Made MW 11

7 33 KV Four Pole structure Disc Insulator, Isolator, Pin insulator, LA, CT-PT, Meter Custom Made Set 18 Custom Made Nos. 7

9 Plant Lighting System LED light 15Wp and cabling 2 Lights at Main gate and two at Inverter room Nos. 1010

Custom Made

MW 11

Danger boards as per IS 2551 33kVDanger boards as per IS 2551- 415VFirst aid box as per IS2 Nos. Shock treatment charts duly framed as per IS33kV grade hand gloves as per IS

11 ELECTRICAL ACCESSORIES :- MW 11(i) Control Terminal Clips on Type, Cable Glands Double crimping Custom Made LS 1(ii) Crimping Type Lugs U-Type, Ring Type, Pin Type for different cables Custom Made LS 1(iii) Armored cable end Termination Kits

Standard

LS 1

Raychem/3M Nos. 6

(iv) Conduits of different sizes Standard LS 112 DC/AC Area Work Complete Plant AC and DC work MW 11

i) .380/.380/33 KV800/800/1600 kVA ONAN, Dy11y11 Off -Load T/C, Z = 5 %, 3 Phase 50 Hz class A insulation, outdoor type for 50°C ambient complete with bushings and cable boxes, with cable terminations on both LT side and bare bushing on HT side.

ii) .380/33 KV800 kVA ONAN, Dy11 Off -Load T/C, Z = 5 %, 3 Phase 50 Hz class A insulation, outdoor type for 50°C ambient complete with bushings and cable boxes, with cable terminations on both LT side and bare bushing on HT side.

i) .380/.380/33 kV800/800/1600 kVA ONAN, Off -Load T/C, with cable terminations on LT side and bare bushing on HT side.

ii) .380/33 kV800 kVA ONAN, Off -Load T/C, with cable terminations on LT side and bare bushing on HT side.

33/.4 KV Aux. Transformer, 25 kVA, outdoor type with cable terminations on LT side and Bushing on HT Side.

33 kV VCB Panels for 33kv incoming/outgoing feeders with Control and Auxiliary cable and their end termination kits

For 33kV outgoing feeders, complete with Outdoor circuit breakers, CT-PT set, indication meters for current, voltage, power factor and energy, with outdoor C&R panel with protection relays for grid and internal faults, fully wired with annunciation and DC fail protection associated auxiliary contects and open close switches with earthing facility, having annunciation windows and hooter facility.

ABB/Schneider/Their approved System house

LA, Isolator and HG Fuse with supply and foundation of 2 Pole Structure

30 KA LA and 630 A Isolator and HG Fuse of suitable current rating mounted on lattice structure

SCADA SYSTEM to control and monitor complete plant parameters and operate the system from remote and Other Accessories

The system will be controlled from the main control room where all the data from different parts of the plant will be received, analyzed and action taken either manually or on auto as per the system design.The scada should have remote monitoring capability.

LT Power Cable will be 1.1 kV, Armoured, unearthed grade, double core/multi-core, stranded Cu/Al conductor as mentioned, XLPE insulated with PVC outer sheath made on PVC compound. All other details will be as Indian Standards .IEC 60189: IS 694/ IS 1554/IS/IEC 69948

33 kv, 3CX185mmsq -Al (Transformer to HT Panel & Power Evacuation)

Earthed grade, XLPE, Armoured ,Aluminium, 3 core, PVC outer sheath, self extinguishing type

EARTHING SYSTEM OF TOTAL PLANT including modules, structure, all electrical equipments, switch yard and Lightening Protection for the entire plant

Laying of GI Flat 50x8 mm, GI Flat 25x3 mm, GI Pipe in the entire plant for equipment earthing. Earth pits as per IS 3043. Providing Lightening arrestor poles, spikes and air termination rods of suitable height along with cables upto earthing points so as to cover the entire plant area.

SDB - 415 volt, 50 cycles for LT Distribution System with 1 Incomer and 3 outgoing feeder of Three Phase and 3 outgoing feeder of Single Phase

415 V LT SCB with 1 incomer from Auxiliary Transformer and 3 Nos. 3 Ph 415V outgoing feeders and 3 Nos. single Phase 220 V outgoing feeders.

Safety Items (Any other item as required for proper safety of a power plant as per statutory requirement to be included)

FIRE BUCKETS-12 Nos, 4.5 kg CO2 FIRE EXTINGUISHERS-6 Nos, FOAM FIRE EXTINGUISHERS -6 no.

2 Nos. 12mm thick 900 mm x 1800 mm rubber mats conforming to latest IS standards

Cable termination of Armored cables including supply of double compression brass cable glands with earth tags, crimping type tinned copper lugs,heat shrinkable cable sealing kits and consumables for the following size of cables.

For 33kV,3C x 185 sq mm,Unearthed grade AL XLPE with heat shrinkable sealing kits

Page 3: 11MW BOM

Civil Works (Annexure -II)SL. No Item Unit Quantity

1 Foundations and complete Civil Works for :-(i) Main Transformers Nos. 7(ii) Structure Foundation for LA and Isolator Nos. 7(iii) VCB Panels Nos. 7(iv) C&R Panel Nos. 7(v) Four Pole Structure Nos. 1(vi) Auxiliary Transformer Nos. 1(vii) Metering Cubical Foundation Nos. 1

2 Mod. Mounting Structures Foundation MW 113 Cable Trenches (Included In AC/DC Work)

(a) For HT Cable Mtrs 1400(b) For LT Cable Mtrs 88004 Nos. 4

5 Four Pole and Transformer Yard Fencing Nos. 5Note:

Inverter Room CFL, Micro filter, Duct outlet for hot air , switches, PVC conduit and necessary wiring from auxiliary supply point for local lighting etc

1) No peripheral roads.2) Only WBM roads upto inverter/control rooms.3) Minimum Drainage work as required to prevent water logging.