Cooling:Best Practices and Economizers
Cooling:Best Practices and Economizers
1
Randall Poet
A C Systems
![Page 2: 1 Randall Poet A C Systems. Server Load = CRAC Capacity Server Airflow = CRAC Airflow 2.](https://reader035.fdocuments.us/reader035/viewer/2022062518/56649e0f5503460f94af9319/html5/thumbnails/2.jpg)
Server Load = CRAC Capacity Server Airflow = CRAC Airflow
2
Ideal Situation
![Page 3: 1 Randall Poet A C Systems. Server Load = CRAC Capacity Server Airflow = CRAC Airflow 2.](https://reader035.fdocuments.us/reader035/viewer/2022062518/56649e0f5503460f94af9319/html5/thumbnails/3.jpg)
The Conventional Approach – Base CaseRaise the Return / Supply Air TempContain the Cold Aisle Add Intelligent ControlThe Set-upSummary
3
Agenda
![Page 4: 1 Randall Poet A C Systems. Server Load = CRAC Capacity Server Airflow = CRAC Airflow 2.](https://reader035.fdocuments.us/reader035/viewer/2022062518/56649e0f5503460f94af9319/html5/thumbnails/4.jpg)
Hot aisle / Cold aisle Blanking panels in racks Blanking panels between racks Blanking Panels between racks and floor Cable cut-outs covered Relatively clean underfloor area Proper location of CRAC units Vapor barrier around space
4
Start with Best Practices
![Page 5: 1 Randall Poet A C Systems. Server Load = CRAC Capacity Server Airflow = CRAC Airflow 2.](https://reader035.fdocuments.us/reader035/viewer/2022062518/56649e0f5503460f94af9319/html5/thumbnails/5.jpg)
20 Racks◦ 8 kW each◦ 35F delta T
5
Base Case – 75F Return Air Control 4 CRACs (N+1)
54 kW each 21F delta T design
![Page 6: 1 Randall Poet A C Systems. Server Load = CRAC Capacity Server Airflow = CRAC Airflow 2.](https://reader035.fdocuments.us/reader035/viewer/2022062518/56649e0f5503460f94af9319/html5/thumbnails/6.jpg)
20 Racks◦ 8 kW each◦ 35F delta T
6
Base Case – 75F Return Air Control 3 CRACs
Running 54 kW each 21F delta T design
![Page 7: 1 Randall Poet A C Systems. Server Load = CRAC Capacity Server Airflow = CRAC Airflow 2.](https://reader035.fdocuments.us/reader035/viewer/2022062518/56649e0f5503460f94af9319/html5/thumbnails/7.jpg)
Unit Airflow – 24,000 CFM Rack Airflow – 14,600 CFM Bypass Airflow – 9,400 CFM
7
Base Case Operating Scenario
75F
89F
54F
54F
CFM 100%
![Page 8: 1 Randall Poet A C Systems. Server Load = CRAC Capacity Server Airflow = CRAC Airflow 2.](https://reader035.fdocuments.us/reader035/viewer/2022062518/56649e0f5503460f94af9319/html5/thumbnails/8.jpg)
8
The Airflow Pattern
![Page 9: 1 Randall Poet A C Systems. Server Load = CRAC Capacity Server Airflow = CRAC Airflow 2.](https://reader035.fdocuments.us/reader035/viewer/2022062518/56649e0f5503460f94af9319/html5/thumbnails/9.jpg)
9
Typical Air Cooled DXEnergy Consumption
Evap Fan MotorCompressors
Condenser Fan Motors
![Page 10: 1 Randall Poet A C Systems. Server Load = CRAC Capacity Server Airflow = CRAC Airflow 2.](https://reader035.fdocuments.us/reader035/viewer/2022062518/56649e0f5503460f94af9319/html5/thumbnails/10.jpg)
Compressors run at full capacity Fans run at full speed
10
Typical Energy Consumption
Evap Fan MotorCompressors
Condenser Fan Motors
System kW 75F RA
Compressors 35.4
Evap Fans 8.7
Condenser Fans
5.4
Total 49.5
![Page 11: 1 Randall Poet A C Systems. Server Load = CRAC Capacity Server Airflow = CRAC Airflow 2.](https://reader035.fdocuments.us/reader035/viewer/2022062518/56649e0f5503460f94af9319/html5/thumbnails/11.jpg)
The Conventional Approach – Base CaseRaise the Return / Supply Air TempContain the Cold Aisle Add Intelligent ControlThe Set-upSummary
11
Agenda
![Page 12: 1 Randall Poet A C Systems. Server Load = CRAC Capacity Server Airflow = CRAC Airflow 2.](https://reader035.fdocuments.us/reader035/viewer/2022062518/56649e0f5503460f94af9319/html5/thumbnails/12.jpg)
Unit Airflow – 24,000 CFM Rack Airflow – 14,600 CFM Bypass Airflow – 9,400 CFM
12
New Operating Scenario85F
99F
64F
64F
CFM 100%
![Page 13: 1 Randall Poet A C Systems. Server Load = CRAC Capacity Server Airflow = CRAC Airflow 2.](https://reader035.fdocuments.us/reader035/viewer/2022062518/56649e0f5503460f94af9319/html5/thumbnails/13.jpg)
13
Increased Capacity at Full Airflow
![Page 14: 1 Randall Poet A C Systems. Server Load = CRAC Capacity Server Airflow = CRAC Airflow 2.](https://reader035.fdocuments.us/reader035/viewer/2022062518/56649e0f5503460f94af9319/html5/thumbnails/14.jpg)
14
Increased Capacity at Full Airflow
![Page 15: 1 Randall Poet A C Systems. Server Load = CRAC Capacity Server Airflow = CRAC Airflow 2.](https://reader035.fdocuments.us/reader035/viewer/2022062518/56649e0f5503460f94af9319/html5/thumbnails/15.jpg)
Compressors run at reduced capacity or unloaded Fan motors run at full speed
15
Operating Systems Comparison
System kW 75F RA 85F RA
Compressors 35.4 24.9
Evap Fans 8.7 8.7
Condenser Fans 5.4 5.4
Total 49.5 39.0
Base 78.8%
![Page 16: 1 Randall Poet A C Systems. Server Load = CRAC Capacity Server Airflow = CRAC Airflow 2.](https://reader035.fdocuments.us/reader035/viewer/2022062518/56649e0f5503460f94af9319/html5/thumbnails/16.jpg)
Sanity Check –100 dF OAT, 6400’ ASL
16
![Page 17: 1 Randall Poet A C Systems. Server Load = CRAC Capacity Server Airflow = CRAC Airflow 2.](https://reader035.fdocuments.us/reader035/viewer/2022062518/56649e0f5503460f94af9319/html5/thumbnails/17.jpg)
Sanity Check
17
![Page 18: 1 Randall Poet A C Systems. Server Load = CRAC Capacity Server Airflow = CRAC Airflow 2.](https://reader035.fdocuments.us/reader035/viewer/2022062518/56649e0f5503460f94af9319/html5/thumbnails/18.jpg)
The Conventional Approach – Base CaseRaise the Return / Supply Air TempContain the Cold Aisle Add Intelligent ControlThe Set-upSummary
18
Agenda
![Page 19: 1 Randall Poet A C Systems. Server Load = CRAC Capacity Server Airflow = CRAC Airflow 2.](https://reader035.fdocuments.us/reader035/viewer/2022062518/56649e0f5503460f94af9319/html5/thumbnails/19.jpg)
Unit Airflow – 21,600 CFM Rack Airflow – 15,800 CFM Bypass Airflow – 5,800 CFM
19
Contain the Cold Aisle85F
94F
62F
62F
CFM 90%
![Page 20: 1 Randall Poet A C Systems. Server Load = CRAC Capacity Server Airflow = CRAC Airflow 2.](https://reader035.fdocuments.us/reader035/viewer/2022062518/56649e0f5503460f94af9319/html5/thumbnails/20.jpg)
At the higher RA temperature, the contained system has very similar operating costs as the non-contained
Fan motors run at full speed but at a reduced CFM and HP due to the higher static pressure
Compressors run at reduced capacity or unloaded but slightly higher than the non-contained
20
Operating Systems ComparisonSystem kW 75F RA 85F RA 85F RA
Contained
Compressors 35.4 24.9 25.8
Evap Fans 8.7 8.7 7.5
Condenser Fans
5.4 5.4 5.4
Total 49.5 39.0 38.7
Base 78.8% 78.2%
![Page 21: 1 Randall Poet A C Systems. Server Load = CRAC Capacity Server Airflow = CRAC Airflow 2.](https://reader035.fdocuments.us/reader035/viewer/2022062518/56649e0f5503460f94af9319/html5/thumbnails/21.jpg)
21
Why use Containment??
System operating costs are similarContainment partitions and doors cost $$
![Page 22: 1 Randall Poet A C Systems. Server Load = CRAC Capacity Server Airflow = CRAC Airflow 2.](https://reader035.fdocuments.us/reader035/viewer/2022062518/56649e0f5503460f94af9319/html5/thumbnails/22.jpg)
22
Hot Spots in Racks due toWrap-Around
![Page 23: 1 Randall Poet A C Systems. Server Load = CRAC Capacity Server Airflow = CRAC Airflow 2.](https://reader035.fdocuments.us/reader035/viewer/2022062518/56649e0f5503460f94af9319/html5/thumbnails/23.jpg)
23
No Leakage into the Cold AIsle
![Page 24: 1 Randall Poet A C Systems. Server Load = CRAC Capacity Server Airflow = CRAC Airflow 2.](https://reader035.fdocuments.us/reader035/viewer/2022062518/56649e0f5503460f94af9319/html5/thumbnails/24.jpg)
24
Higher Temperatures without Containment
![Page 25: 1 Randall Poet A C Systems. Server Load = CRAC Capacity Server Airflow = CRAC Airflow 2.](https://reader035.fdocuments.us/reader035/viewer/2022062518/56649e0f5503460f94af9319/html5/thumbnails/25.jpg)
25
Containment of Cold Aisle
![Page 26: 1 Randall Poet A C Systems. Server Load = CRAC Capacity Server Airflow = CRAC Airflow 2.](https://reader035.fdocuments.us/reader035/viewer/2022062518/56649e0f5503460f94af9319/html5/thumbnails/26.jpg)
Issues to Consider Fire Detection / Suppression
◦ Wide variation between municipalities◦ If local Fire Inspector involved early, typically goes
well Curtains usually eliminate this issue
Installation◦ Will be site specificy
Irregular row length/height, gaps, etc.◦ Site conditions critical, one size does NOT fit all
![Page 27: 1 Randall Poet A C Systems. Server Load = CRAC Capacity Server Airflow = CRAC Airflow 2.](https://reader035.fdocuments.us/reader035/viewer/2022062518/56649e0f5503460f94af9319/html5/thumbnails/27.jpg)
Issues To Consider ADA
◦ CAC space is for Service Personnel (Section 4.1.1) What about cooling for components in rest
of room?◦ Best solution today may be ducted return from hot
aisle◦ Perf tiles near other equipment requiring cooling
(eg. UPS) 85⁰ Room temperature?
![Page 28: 1 Randall Poet A C Systems. Server Load = CRAC Capacity Server Airflow = CRAC Airflow 2.](https://reader035.fdocuments.us/reader035/viewer/2022062518/56649e0f5503460f94af9319/html5/thumbnails/28.jpg)
HAC vs CAC Main Purpose of Cooling in Data Center?
◦ Cool the equipment Data Centers commonly on raised floor
◦ CAC allows current investment to be used HAC typically requires in row cooling
◦ So, refrigerant or chilled water and condensate intermingled with IT equipment and racks
Which aisle does majority of work take place in?◦ CAC hot aisle likely in 85⁰F range
Can use perf tiles in other space◦ HAC hot aisle likely in 100⁰F range
![Page 29: 1 Randall Poet A C Systems. Server Load = CRAC Capacity Server Airflow = CRAC Airflow 2.](https://reader035.fdocuments.us/reader035/viewer/2022062518/56649e0f5503460f94af9319/html5/thumbnails/29.jpg)
The Conventional Approach – Base CaseRaise the Return / Supply Air TempContain the Cold Aisle Add Intelligent ControlThe Set-upSummary
29
Agenda
![Page 30: 1 Randall Poet A C Systems. Server Load = CRAC Capacity Server Airflow = CRAC Airflow 2.](https://reader035.fdocuments.us/reader035/viewer/2022062518/56649e0f5503460f94af9319/html5/thumbnails/30.jpg)
Unit Airflow – 16,800 CFM Rack Airflow – 14,600 CFM Bypass Airflow – 2,200 CFM
30
Closer to Matching the Load to the Cooling
92F
97F
62F
62F
CFM 70%
Variable Capacity Compressors
Variable Speed Fans Intelligent Control
![Page 31: 1 Randall Poet A C Systems. Server Load = CRAC Capacity Server Airflow = CRAC Airflow 2.](https://reader035.fdocuments.us/reader035/viewer/2022062518/56649e0f5503460f94af9319/html5/thumbnails/31.jpg)
The airflows and capacities/loads are more closely matched
Fan motors run at reduced speed, CFM and HP based on the demand in the contained area
Compressors run at reduced capacity or unloaded but slightly higher than the non-contained
31
Operating Systems ComparisonSystem kW 75F RA 85F RA 85F RA
Contained92F RA Contained
& Controlled
Compressors 35.4 24.9 25.8 25.5
Evap Fans 8.7 8.7 7.5 3.0
Condenser Fans 5.4 5.4 5.4 5.4
Total 49.5 39.0 38.7 33.9
Base 78.8% 78.2% 68.5%
![Page 32: 1 Randall Poet A C Systems. Server Load = CRAC Capacity Server Airflow = CRAC Airflow 2.](https://reader035.fdocuments.us/reader035/viewer/2022062518/56649e0f5503460f94af9319/html5/thumbnails/32.jpg)
The Conventional Approach – Base CaseRaise the Return / Supply Air TempContain the Cold Aisle Add Intelligent Control (Creating SmartAisle)The Set-upSummary
32
Agenda
![Page 33: 1 Randall Poet A C Systems. Server Load = CRAC Capacity Server Airflow = CRAC Airflow 2.](https://reader035.fdocuments.us/reader035/viewer/2022062518/56649e0f5503460f94af9319/html5/thumbnails/33.jpg)
33
Sensor Location• Server centric solution, meaning that it focuses on the inlet
temperature to the servers• Self adapting to environment changes due to server utilization,
equipment location changes and outside variables• Can adapt to situations with no containment, end containment, and
full containment
![Page 34: 1 Randall Poet A C Systems. Server Load = CRAC Capacity Server Airflow = CRAC Airflow 2.](https://reader035.fdocuments.us/reader035/viewer/2022062518/56649e0f5503460f94af9319/html5/thumbnails/34.jpg)
Rack Sensors• Rack Sensors without doors
can be mounted on the frame of the racks.
• Temperature differences were within .5°F
![Page 35: 1 Randall Poet A C Systems. Server Load = CRAC Capacity Server Airflow = CRAC Airflow 2.](https://reader035.fdocuments.us/reader035/viewer/2022062518/56649e0f5503460f94af9319/html5/thumbnails/35.jpg)
Cold Aisle Sensors• Sensors can also be mounted at the top
of cold aisles when rack mounting is unavailable
![Page 36: 1 Randall Poet A C Systems. Server Load = CRAC Capacity Server Airflow = CRAC Airflow 2.](https://reader035.fdocuments.us/reader035/viewer/2022062518/56649e0f5503460f94af9319/html5/thumbnails/36.jpg)
36
Supply Compensation
• Compensation is the magical link between controlling sensors• The controller evaluates the Rack Sensors and Fan Speed• If the fan is operating at 100% and remains above the cold
aisle set point• Then the supply temperature set point will slowly lower to
drive the correct cold aisle temperature
Lower Supply
Fan Speed100%
![Page 37: 1 Randall Poet A C Systems. Server Load = CRAC Capacity Server Airflow = CRAC Airflow 2.](https://reader035.fdocuments.us/reader035/viewer/2022062518/56649e0f5503460f94af9319/html5/thumbnails/37.jpg)
CW Valve Open %
100%90%80%70%60%50%40%30%20%10%0%
Fan Speed %
Controller and CRAC Operation
Incre
ase in
kW
Unit ON
IT Load IncreasesRack Temperature Sensor detects inlet rack temperature
Fan Speed IncreasesSo that cold aisle temperature is maintained at customer temperature Setpoint
Supply TemperatureThe increase in fan speed will result in a warmer supply air temperature which is detected by the supply air sensor that will increase cooling to maintain supply air setpoint
Cold Aisle ContainmentiCOM will automatically adjust to changes that result in a temperature increase or decrease
![Page 38: 1 Randall Poet A C Systems. Server Load = CRAC Capacity Server Airflow = CRAC Airflow 2.](https://reader035.fdocuments.us/reader035/viewer/2022062518/56649e0f5503460f94af9319/html5/thumbnails/38.jpg)
38
Controller and CRAC Operation• Advanced freeze protection routine
• Allow all units to reduce fan speed to 60%• Fan speed and compressor capacity (or CW valve) managed for
best unit efficiency and performance• Multiple remote sensors
• Controller can use averaged and maximum/minimum values to individually control multiple CRAC systems
• CRAC systems work as a team• All remote sensors used• Increase capacity of other applicable adjacent units if one is at
maximum and unable to handle the load• Automatically adjust for units not in service
![Page 39: 1 Randall Poet A C Systems. Server Load = CRAC Capacity Server Airflow = CRAC Airflow 2.](https://reader035.fdocuments.us/reader035/viewer/2022062518/56649e0f5503460f94af9319/html5/thumbnails/39.jpg)
The Conventional Approach – Base CaseRaise the Return / Supply Air TempContain the Cold Aisle Add Intelligent ControlThe Set-upSummary
39
Agenda
![Page 40: 1 Randall Poet A C Systems. Server Load = CRAC Capacity Server Airflow = CRAC Airflow 2.](https://reader035.fdocuments.us/reader035/viewer/2022062518/56649e0f5503460f94af9319/html5/thumbnails/40.jpg)
Issues to Consider Fire Detection / Suppression
◦ Wide variation between municipalities◦ If local Fire Inspector involved early, typically goes
well Curtain eliminates this issue
Installation◦ Will be a local responsibility◦ You need to develop relationship with local Cable
Contractor or similar company for installation Irregular row length/height
◦ Site Survey critical◦ Most expensive component
![Page 41: 1 Randall Poet A C Systems. Server Load = CRAC Capacity Server Airflow = CRAC Airflow 2.](https://reader035.fdocuments.us/reader035/viewer/2022062518/56649e0f5503460f94af9319/html5/thumbnails/41.jpg)
Issues To Consider ADA
◦ Consultant raised issue at BAIS project◦ Successfully defended CAC space is for Service
Personnel (Section 4.1.1) What about cooling for components in rest
of room?◦ Best solution today is ducted return from hot aisle◦ perf tile by IT component
85⁰ Room temperature
![Page 42: 1 Randall Poet A C Systems. Server Load = CRAC Capacity Server Airflow = CRAC Airflow 2.](https://reader035.fdocuments.us/reader035/viewer/2022062518/56649e0f5503460f94af9319/html5/thumbnails/42.jpg)
Issues To Consider Purpose of Cooling in Data Center?
◦ Control equipment inlet temps Data Centers often on raised floor
◦ CAC allows current investment to be used Which aisle does majority of work take place
in?◦ CAC hot aisle likely in 85⁰F range
Could use perf tile in other space◦ HAC hot aisle likely in 100⁰F range
![Page 43: 1 Randall Poet A C Systems. Server Load = CRAC Capacity Server Airflow = CRAC Airflow 2.](https://reader035.fdocuments.us/reader035/viewer/2022062518/56649e0f5503460f94af9319/html5/thumbnails/43.jpg)
Best practices are a must if improved efficiency is a goal
Running warmer temperatures in the space will improve the cooling system operating efficiency
Containment improves the availability of the servers by eliminating hot spots
Intelligently controlling fan speed and compressor capacity “balances” the system to operate at it’s most efficient level
43
Summary
![Page 44: 1 Randall Poet A C Systems. Server Load = CRAC Capacity Server Airflow = CRAC Airflow 2.](https://reader035.fdocuments.us/reader035/viewer/2022062518/56649e0f5503460f94af9319/html5/thumbnails/44.jpg)
Summary Efficiency is the story, not containment Containment can be done in several ways,
none necessarily fit all situations Each critical space is unique and merits
individual planning Dynamic Control is (currently )the final
element
![Page 45: 1 Randall Poet A C Systems. Server Load = CRAC Capacity Server Airflow = CRAC Airflow 2.](https://reader035.fdocuments.us/reader035/viewer/2022062518/56649e0f5503460f94af9319/html5/thumbnails/45.jpg)
…Shifting on to Economizers and Equipment Considerations…
45
![Page 46: 1 Randall Poet A C Systems. Server Load = CRAC Capacity Server Airflow = CRAC Airflow 2.](https://reader035.fdocuments.us/reader035/viewer/2022062518/56649e0f5503460f94af9319/html5/thumbnails/46.jpg)
90.1 Economizer Map
![Page 47: 1 Randall Poet A C Systems. Server Load = CRAC Capacity Server Airflow = CRAC Airflow 2.](https://reader035.fdocuments.us/reader035/viewer/2022062518/56649e0f5503460f94af9319/html5/thumbnails/47.jpg)
Definitions of Cooling Efficiency EER (Energy Efficiency Ratio)
◦ Total Cooling Capacity (BTUH)/Total power input (watts)
◦ Full-load value on 95F design day◦ Commercial return air conditions of 80F/50%
SCOP (Sensible Coefficient of Performance)◦ Sensible Cooling Capacity (kW)/Total power input
(kW)◦ Full-load value on 95F design day◦ Data Center return air conditions of 75F/45%
47
![Page 48: 1 Randall Poet A C Systems. Server Load = CRAC Capacity Server Airflow = CRAC Airflow 2.](https://reader035.fdocuments.us/reader035/viewer/2022062518/56649e0f5503460f94af9319/html5/thumbnails/48.jpg)
ASCOP – Efficiency MetricAnnualized Sensible Coefficient of
Performance(location specific)
Bin efficiency x bin hours/total annual hours Factors hours at each efficiency operating
point Factors part-load efficiency Factors economizer hours
48
![Page 49: 1 Randall Poet A C Systems. Server Load = CRAC Capacity Server Airflow = CRAC Airflow 2.](https://reader035.fdocuments.us/reader035/viewer/2022062518/56649e0f5503460f94af9319/html5/thumbnails/49.jpg)
Single System –Outside Air Economizer
49
![Page 50: 1 Randall Poet A C Systems. Server Load = CRAC Capacity Server Airflow = CRAC Airflow 2.](https://reader035.fdocuments.us/reader035/viewer/2022062518/56649e0f5503460f94af9319/html5/thumbnails/50.jpg)
Large or Multiple Systems –Outside Air Economizer
50
![Page 51: 1 Randall Poet A C Systems. Server Load = CRAC Capacity Server Airflow = CRAC Airflow 2.](https://reader035.fdocuments.us/reader035/viewer/2022062518/56649e0f5503460f94af9319/html5/thumbnails/51.jpg)
Single System withGlycol Economizer
51
![Page 52: 1 Randall Poet A C Systems. Server Load = CRAC Capacity Server Airflow = CRAC Airflow 2.](https://reader035.fdocuments.us/reader035/viewer/2022062518/56649e0f5503460f94af9319/html5/thumbnails/52.jpg)
Precooler on Chilled Water System
52
![Page 53: 1 Randall Poet A C Systems. Server Load = CRAC Capacity Server Airflow = CRAC Airflow 2.](https://reader035.fdocuments.us/reader035/viewer/2022062518/56649e0f5503460f94af9319/html5/thumbnails/53.jpg)
Chilled Water withCooling Tower Economizer
53
![Page 54: 1 Randall Poet A C Systems. Server Load = CRAC Capacity Server Airflow = CRAC Airflow 2.](https://reader035.fdocuments.us/reader035/viewer/2022062518/56649e0f5503460f94af9319/html5/thumbnails/54.jpg)
What if we could do a refrigerant based economizer cycle?
54
![Page 55: 1 Randall Poet A C Systems. Server Load = CRAC Capacity Server Airflow = CRAC Airflow 2.](https://reader035.fdocuments.us/reader035/viewer/2022062518/56649e0f5503460f94af9319/html5/thumbnails/55.jpg)
Energy Consuming ComponentsAir-Cooled System
55
Compressor energy reduction is low-hanging fruit
![Page 56: 1 Randall Poet A C Systems. Server Load = CRAC Capacity Server Airflow = CRAC Airflow 2.](https://reader035.fdocuments.us/reader035/viewer/2022062518/56649e0f5503460f94af9319/html5/thumbnails/56.jpg)
Digital Scroll Technology Continuous variable capacity
compressor technology without inverter drive from 10% to 100% of capacity
In commercial use since 2004 Available in single compressor
and tandem compressor configurations
High reliability versus Inverter drive systems
No electrical harmonics introduced
56
![Page 57: 1 Randall Poet A C Systems. Server Load = CRAC Capacity Server Airflow = CRAC Airflow 2.](https://reader035.fdocuments.us/reader035/viewer/2022062518/56649e0f5503460f94af9319/html5/thumbnails/57.jpg)
EC fans in unit
57
![Page 58: 1 Randall Poet A C Systems. Server Load = CRAC Capacity Server Airflow = CRAC Airflow 2.](https://reader035.fdocuments.us/reader035/viewer/2022062518/56649e0f5503460f94af9319/html5/thumbnails/58.jpg)
EC fans in raised floor
58
![Page 59: 1 Randall Poet A C Systems. Server Load = CRAC Capacity Server Airflow = CRAC Airflow 2.](https://reader035.fdocuments.us/reader035/viewer/2022062518/56649e0f5503460f94af9319/html5/thumbnails/59.jpg)
EconoPhase Pumped Refrigerant Economizer
59
Condenser
Check Valve
Compressors ON
EvaporatorElectronic expansion
valve
Summer operation
Check Valve
Check Valve
Refrigerant
Pumps OFF
SolenoidValve
EconoPhase
Outdoor Ambient 95°F
KW @ 70% Load 24.1
Circuit 2
Circuit 1
![Page 60: 1 Randall Poet A C Systems. Server Load = CRAC Capacity Server Airflow = CRAC Airflow 2.](https://reader035.fdocuments.us/reader035/viewer/2022062518/56649e0f5503460f94af9319/html5/thumbnails/60.jpg)
EconoPhase – Partial Economization
60
Condenser
Check Valve
Compressor
EvaporatorElectronic expansion
valve
Fall / Evening operation
Check Valve
Check Valve
Refrigerant
Pump
SolenoidValve
EconoPhase
Outdoor Ambient 65°F
KW @ 70% Load 15.1
Circuit 2
Circuit 1
ON
OFF
OFF
ON
![Page 61: 1 Randall Poet A C Systems. Server Load = CRAC Capacity Server Airflow = CRAC Airflow 2.](https://reader035.fdocuments.us/reader035/viewer/2022062518/56649e0f5503460f94af9319/html5/thumbnails/61.jpg)
EconoPhase - Full Economization
61
Condenser
Check Valve
Compressor
EvaporatorElectronic expansion valve
Winter operation
Check Valve
Check Valve
Refrigerant
Pump
SolenoidValve
EconoPhase
Outdoor Ambient 25°F
KW @ 70% Load 3.7
Circuit 2
Circuit 1
ON
OFF
ON
OFF
![Page 62: 1 Randall Poet A C Systems. Server Load = CRAC Capacity Server Airflow = CRAC Airflow 2.](https://reader035.fdocuments.us/reader035/viewer/2022062518/56649e0f5503460f94af9319/html5/thumbnails/62.jpg)
Technology
Electronic Expansion Valve EC Plug FansTandem compressors w/ Digital Scroll New Evaporator Coil design
◦ Staged “A” Coil◦ Greater surface area
Microchannel Condenser◦ Indoor Unit Communicates to Condenser
Refrigerant Economizer
![Page 63: 1 Randall Poet A C Systems. Server Load = CRAC Capacity Server Airflow = CRAC Airflow 2.](https://reader035.fdocuments.us/reader035/viewer/2022062518/56649e0f5503460f94af9319/html5/thumbnails/63.jpg)
Advantages ofRefrigerant Economizer
No additional heat exchangers No dust or contamination concerns No need for added ductwork or structural
changes to building for economizer No dampers to maintain Quick changeover between compressor
mode and economizer mode No water usage No water freeze or coil freeze concerns
63
![Page 64: 1 Randall Poet A C Systems. Server Load = CRAC Capacity Server Airflow = CRAC Airflow 2.](https://reader035.fdocuments.us/reader035/viewer/2022062518/56649e0f5503460f94af9319/html5/thumbnails/64.jpg)
45F 55F 65F 75F 85F 95F1.8
2.3
2.8
3.3
3.8
4.3
4.8
5.3
5.8
6.3
6.8
Outdoor Ambient, F
Eff
icie
ncy
, S
CO
PLiebert DSE Full-Load Efficiency SCOP (kW/kW) @ 85F return air
Liebert DSE DA125A @ 50% load
ASHRAE 90.1 @ 75F
Efficiency Plateau
+92%
Liebert DSE DA125A @ 100%
load
+45%
+115%
Traditional Refrigeration
![Page 65: 1 Randall Poet A C Systems. Server Load = CRAC Capacity Server Airflow = CRAC Airflow 2.](https://reader035.fdocuments.us/reader035/viewer/2022062518/56649e0f5503460f94af9319/html5/thumbnails/65.jpg)
With Refrigerant Economizer Maximum capacity, max airflow
65
0 10 20 30 40 50 600
2
4
6
8
10
12
14
16
0
20
40
60
80
100
120
140
SC
OP
, kW
/kW
Se
ns
ible
kW
= Sensible Capacity, kW
= SCOP
Ambient, ºF
![Page 66: 1 Randall Poet A C Systems. Server Load = CRAC Capacity Server Airflow = CRAC Airflow 2.](https://reader035.fdocuments.us/reader035/viewer/2022062518/56649e0f5503460f94af9319/html5/thumbnails/66.jpg)
Designing for LEED
Energy efficiencyNo water use for coolingMERV 13 filtersNo outside air contaminationR-410A refrigerant/lower charge
Utility Rebates
66
![Page 67: 1 Randall Poet A C Systems. Server Load = CRAC Capacity Server Airflow = CRAC Airflow 2.](https://reader035.fdocuments.us/reader035/viewer/2022062518/56649e0f5503460f94af9319/html5/thumbnails/67.jpg)
Condenser Improvements
67
![Page 68: 1 Randall Poet A C Systems. Server Load = CRAC Capacity Server Airflow = CRAC Airflow 2.](https://reader035.fdocuments.us/reader035/viewer/2022062518/56649e0f5503460f94af9319/html5/thumbnails/68.jpg)
Air Cooled Condenser Improvements
Microchannel vs. Fin and Tube Variable Speed Fans Control Based on Refrigerant Pressure
68
![Page 69: 1 Randall Poet A C Systems. Server Load = CRAC Capacity Server Airflow = CRAC Airflow 2.](https://reader035.fdocuments.us/reader035/viewer/2022062518/56649e0f5503460f94af9319/html5/thumbnails/69.jpg)
Aluminum Fins & Tubes Developed & used in Automotive A/C for
25+yrs
69
Microchannel Coil
![Page 70: 1 Randall Poet A C Systems. Server Load = CRAC Capacity Server Airflow = CRAC Airflow 2.](https://reader035.fdocuments.us/reader035/viewer/2022062518/56649e0f5503460f94af9319/html5/thumbnails/70.jpg)
70
Microchannel Coil Advantage
1” Thin coil replaces 2” to 6” fin/tube coil◦ Lower airside ∆P◦ Reduced maximum fan wattage for heat transfer◦ Reduced refirgerant quantity
6”1”
![Page 71: 1 Randall Poet A C Systems. Server Load = CRAC Capacity Server Airflow = CRAC Airflow 2.](https://reader035.fdocuments.us/reader035/viewer/2022062518/56649e0f5503460f94af9319/html5/thumbnails/71.jpg)
EC Axial Fan Technology EC (Electronically Commutated) Motor
◦ Every fan/motor is designed for variable speed. Superior part load efficiency
◦ 3-Phase AC power feed, but efficiency of a DC motor
◦ 20% reduction of fan speed = 49% savings in energy
71
![Page 72: 1 Randall Poet A C Systems. Server Load = CRAC Capacity Server Airflow = CRAC Airflow 2.](https://reader035.fdocuments.us/reader035/viewer/2022062518/56649e0f5503460f94af9319/html5/thumbnails/72.jpg)
Sound Quiet fan blade design
72
![Page 73: 1 Randall Poet A C Systems. Server Load = CRAC Capacity Server Airflow = CRAC Airflow 2.](https://reader035.fdocuments.us/reader035/viewer/2022062518/56649e0f5503460f94af9319/html5/thumbnails/73.jpg)
Sound Level Factors & Options
Sound varies with fan speed Fan speed is proportional to % compressor
load and outdoor ambient temperature◦ Will you ever hear a lightly loaded system
condenser? Even more quiet options
◦ Upsizing condenser will keep fan speed in nearly “inaudible” range!
73
![Page 74: 1 Randall Poet A C Systems. Server Load = CRAC Capacity Server Airflow = CRAC Airflow 2.](https://reader035.fdocuments.us/reader035/viewer/2022062518/56649e0f5503460f94af9319/html5/thumbnails/74.jpg)
Why do they cool things with air, anyway??
74
![Page 75: 1 Randall Poet A C Systems. Server Load = CRAC Capacity Server Airflow = CRAC Airflow 2.](https://reader035.fdocuments.us/reader035/viewer/2022062518/56649e0f5503460f94af9319/html5/thumbnails/75.jpg)
75
Why indeed? How about pumped refrigerant?
Refrigerant piping anifold suppliespumped refrigerant
Cam levers activates engagement and disengagement of server
Refrigerant connection points at top of the rack on left side. All plumbing runs along left side.
![Page 76: 1 Randall Poet A C Systems. Server Load = CRAC Capacity Server Airflow = CRAC Airflow 2.](https://reader035.fdocuments.us/reader035/viewer/2022062518/56649e0f5503460f94af9319/html5/thumbnails/76.jpg)
Cooling Architecture
Each server is cooled by an individual cold plate◦ Cold plates and insertion mechanism is designed for use of standard 1U
servers Circulating refrigerant is the cooling medium
Rack
Server
Heat exchanger &
circulation unit
Cold PlateTo/From Chiller
Cold Plate Highly flexible Backed with pressure
plate Forms to the server lid
![Page 77: 1 Randall Poet A C Systems. Server Load = CRAC Capacity Server Airflow = CRAC Airflow 2.](https://reader035.fdocuments.us/reader035/viewer/2022062518/56649e0f5503460f94af9319/html5/thumbnails/77.jpg)
In-Rack Cooling withPumped Refrigerant
The rack is 45U tall by 800mm wide by 1200mm deep.
36 1U server slots with cold plate Three non-cooled server slots for
“cool” devices like switches, etc. Can be configured for a cooling
capacity of 20kW or 40kW.
![Page 78: 1 Randall Poet A C Systems. Server Load = CRAC Capacity Server Airflow = CRAC Airflow 2.](https://reader035.fdocuments.us/reader035/viewer/2022062518/56649e0f5503460f94af9319/html5/thumbnails/78.jpg)
78
Thank You.Questions?