1 GE Consumer & Industrial Multilin Protection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc. 770 565-1556 [email protected]

Transcript of 1 GE Consumer & Industrial Multilin Protection Basics Presented by John S. Levine, P.E. Levine...

Page 1: 1 GE Consumer & Industrial Multilin Protection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc. 770 565-1556 John@L-3.com.

1GE Consumer & Industrial

Multilin

Protection Basics

Presented byJohn S. Levine, P.E.

Levine Lectronics and Lectric, Inc.770 565-1556

[email protected]

Page 2: 1 GE Consumer & Industrial Multilin Protection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc. 770 565-1556 John@L-3.com.

2GE Consumer & Industrial

Multilin

Protection Fundamentals

ByJohn Levine

Page 3: 1 GE Consumer & Industrial Multilin Protection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc. 770 565-1556 John@L-3.com.

3GE Consumer & Industrial

Multilin

Outline• Introductions

• Tools – Enervista Launchpad – On – Line Store – Demo Relays at Levine

• ANSI number

• Training CD’s

• Protection Fundamentals

Page 4: 1 GE Consumer & Industrial Multilin Protection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc. 770 565-1556 John@L-3.com.

4GE Consumer & Industrial

Multilin

Objective

• We are here to help make your job easier. This is very informal and designed around Applications. Please ask question. We are not here to “preach” to you.

• The knowledge base in the room varies greatly. If you have a question, there is a good chance there are 3 or 4 other people that have the same question. Please ask it.

Page 5: 1 GE Consumer & Industrial Multilin Protection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc. 770 565-1556 John@L-3.com.

5GE Consumer & Industrial

Multilin

Tools

Page 6: 1 GE Consumer & Industrial Multilin Protection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc. 770 565-1556 John@L-3.com.

6GE Consumer & Industrial

Multilin

Page 7: 1 GE Consumer & Industrial Multilin Protection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc. 770 565-1556 John@L-3.com.

7GE Consumer & Industrial

Multilin

Demo Relays at L-3

Page 8: 1 GE Consumer & Industrial Multilin Protection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc. 770 565-1556 John@L-3.com.

8GE Consumer & Industrial

Multilin

Relays at L-3

Page 9: 1 GE Consumer & Industrial Multilin Protection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc. 770 565-1556 John@L-3.com.

9GE Consumer & Industrial

Multilin

Page 10: 1 GE Consumer & Industrial Multilin Protection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc. 770 565-1556 John@L-3.com.

10GE Consumer & Industrial

Multilin

GE Multilin Training CD’s

Page 11: 1 GE Consumer & Industrial Multilin Protection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc. 770 565-1556 John@L-3.com.

11GE Consumer & Industrial

Multilin

ANSI Symbols

Page 12: 1 GE Consumer & Industrial Multilin Protection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc. 770 565-1556 John@L-3.com.

12GE Consumer & Industrial

Multilin

Conversion of Electro-Mechanical to Electronic sheet

Page 13: 1 GE Consumer & Industrial Multilin Protection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc. 770 565-1556 John@L-3.com.

13GE Consumer & Industrial

Multilin

PowerPoint presentations at:

http://l-3.com/private/ieee/

Page 14: 1 GE Consumer & Industrial Multilin Protection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc. 770 565-1556 John@L-3.com.

14GE Consumer & Industrial

Multilin

Protection Fundamentals

Page 15: 1 GE Consumer & Industrial Multilin Protection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc. 770 565-1556 John@L-3.com.

15GE Consumer & Industrial

Multilin

Desirable Protection Attributes

• Reliability: System operate properly– Security: Don’t trip when you shouldn’t– Dependability: Trip when you should

• Selectivity: Trip the minimal amount to clear the fault or abnormal operating condition

• Speed: Usually the faster the better in terms of minimizing equipment damage and maintaining system integrity

• Simplicity: KISS

• Economics: Don’t break the bank

Page 16: 1 GE Consumer & Industrial Multilin Protection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc. 770 565-1556 John@L-3.com.

16GE Consumer & Industrial

Multilin

Selection of protective relays requires compromises:

• Maximum and Reliable protection at minimum equipment cost

• High Sensitivity to faults and insensitivity to maximum load currents

• High-speed fault clearance with correct selectivity

• Selectivity in isolating small faulty area

• Ability to operate correctly under all predictable power system conditions

Art & Science of ProtectionArt & Science of Protection

Page 17: 1 GE Consumer & Industrial Multilin Protection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc. 770 565-1556 John@L-3.com.

17GE Consumer & Industrial

Multilin

• Cost of protective relays should be balanced against risks involved if protection is not sufficient and not enough redundancy.

• Primary objectives is to have faulted zone’s primary protection operate first, but if there are protective relays failures, some form of backup protection is provided.

• Backup protection is local (if local primary protection fails to clear fault) and remote (if remote protection fails to operate to clear fault)

Art & Science of ProtectionArt & Science of Protection

Page 18: 1 GE Consumer & Industrial Multilin Protection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc. 770 565-1556 John@L-3.com.

18GE Consumer & Industrial

Multilin

Primary Equipment & ComponentsPrimary Equipment & Components• Transformers - to step up or step down voltage level

• Breakers - to energize equipment and interrupt fault current

to isolate faulted equipment

• Insulators - to insulate equipment from ground and other

phases

• Isolators (switches) - to create a visible and permanent

isolation of primary equipment for maintenance purposes

and route power flow over certain buses.

• Bus - to allow multiple connections (feeders) to the same

source of power (transformer).

Page 19: 1 GE Consumer & Industrial Multilin Protection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc. 770 565-1556 John@L-3.com.

19GE Consumer & Industrial

Multilin

Primary Equipment & ComponentsPrimary Equipment & Components• Grounding - to operate and maintain equipment safely

• Arrester - to protect primary equipment of sudden

overvoltage (lightning strike).

• Switchgear – integrated components to switch, protect,

meter and control power flow

• Reactors - to limit fault current (series) or compensate for

charge current (shunt)

• VT and CT - to measure primary current and voltage and

supply scaled down values to P&C, metering, SCADA, etc.

• Regulators - voltage, current, VAR, phase angle, etc.

Page 20: 1 GE Consumer & Industrial Multilin Protection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc. 770 565-1556 John@L-3.com.

20GE Consumer & Industrial

Multilin

Types of ProtectionOvercurrent• Uses current to determine magnitude of fault– Simple– May employ definite time or inverse time curves– May be slow– Selectivity at the cost of speed (coordination stacks)– Inexpensive– May use various polarizing voltages or ground current

for directionality– Communication aided schemes make more selective

Page 21: 1 GE Consumer & Industrial Multilin Protection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc. 770 565-1556 John@L-3.com.

21GE Consumer & Industrial

Multilin

Instantaneous Overcurrent Protection (IOC) & Definite Time Overcurrent

t

I

CTI

50+2

50+2

CTI • Relay closest to fault operates first

• Relays closer to source operate slower

• Time between operating for same current is called CTI (Clearing Time Interval)

Distribution Substation

Page 22: 1 GE Consumer & Industrial Multilin Protection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc. 770 565-1556 John@L-3.com.

22GE Consumer & Industrial

Multilin

(TOC) Coordination

t

I

CTI

• Relay closest to fault operates first

• Relays closer to source operate slower

• Time between operating for same current is called CTI

Distribution Substation

Page 23: 1 GE Consumer & Industrial Multilin Protection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc. 770 565-1556 John@L-3.com.

23GE Consumer & Industrial

Multilin

• Selection of the curves uses what is termed as a “ time multiplier” or “time dial” to effectively shift the curve up or down on the time axis

• Operate region lies above selected curve, while no-operate region lies below it

• Inverse curves can approximate fuse curve shapes

Time Overcurrent Protection (TOC)

Page 24: 1 GE Consumer & Industrial Multilin Protection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc. 770 565-1556 John@L-3.com.

24GE Consumer & Industrial

Multilin

Multiples of pick-up

Time Overcurrent Protection(51, 51N, 51G)

Page 25: 1 GE Consumer & Industrial Multilin Protection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc. 770 565-1556 John@L-3.com.

26GE Consumer & Industrial

Multilin

Types of Protection

Differential– current in = current out– Simple– Very fast– Very defined clearing area– Expensive– Practical distance limitations

• Line differential systems overcome this using digital communications

Page 26: 1 GE Consumer & Industrial Multilin Protection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc. 770 565-1556 John@L-3.com.

27GE Consumer & Industrial

Multilin

Differential

• Note CT polarity dots

• This is a through-current representation

• Perfect waveforms, no saturation

I P

I S

I R-X

I P

I S

I R-Y

Relay

CT-X CT-Y

1 + (-1) = 0

+1

-1

0

Cur

rent

, pu

DIFF CURRENT

1 pu

Page 27: 1 GE Consumer & Industrial Multilin Protection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc. 770 565-1556 John@L-3.com.

28GE Consumer & Industrial

Multilin

Differential

• Note CT polarity dots

• This is an internal fault representation

• Perfect waveforms, no saturation

FaultI P

I S

I R-X

I P

I S

I R-Y

Relay

2 + (+2) = 4

+2

-2

0

Cu

rre

nt,

puX

2 pu 2 pu

CT-X CT-Y

DIFF CURRENT

Page 28: 1 GE Consumer & Industrial Multilin Protection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc. 770 565-1556 John@L-3.com.

29GE Consumer & Industrial

Multilin

Types of ProtectionVoltage• Uses voltage to infer fault or abnormal condition• May employ definite time or inverse time curves• May also be used for undervoltage load shedding

– Simple– May be slow– Selectivity at the cost of speed (coordination stacks)– Inexpensive

Page 29: 1 GE Consumer & Industrial Multilin Protection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc. 770 565-1556 John@L-3.com.

30GE Consumer & Industrial

Multilin

Types of ProtectionFrequency• Uses frequency of voltage to detect power

balance condition• May employ definite time or inverse time

curves• Used for load shedding & machinery

under/overspeed protection– Simple– May be slow– Selectivity at the cost of speed can be expensive

Page 30: 1 GE Consumer & Industrial Multilin Protection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc. 770 565-1556 John@L-3.com.

31GE Consumer & Industrial

Multilin

Types of ProtectionPower• Uses voltage and current to determine

power flow magnitude and direction• Typically definite time

– Complex– May be slow– Accuracy important for many applications – Can be expensive

Page 31: 1 GE Consumer & Industrial Multilin Protection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc. 770 565-1556 John@L-3.com.

32GE Consumer & Industrial

Multilin

Types of ProtectionDistance (Impedance)– Uses voltage and current to determine impedance of fault– Set on impedance [R-X] plane– Uses definite time – Impedance related to distance from relay– Complicated– Fast– Somewhat defined clearing area with reasonable

accuracy– Expensive– Communication aided schemes make more selective

Page 32: 1 GE Consumer & Industrial Multilin Protection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc. 770 565-1556 John@L-3.com.

33GE Consumer & Industrial

Multilin

Impedance• Relay in Zone 1 operates first• Time between Zones is called

CTI

Source

A B

21 21

T1

T2

ZA

ZB

R

X ZL

Page 33: 1 GE Consumer & Industrial Multilin Protection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc. 770 565-1556 John@L-3.com.

Generation-typically at 4-20kV

Transmission-typically at 230-765kV

Subtransmission-typically at 69-161kV

Receives power from transmission system and transforms into subtransmission level

Receives power from subtransmission system and transforms into primary feeder voltage

Distribution network-typically 2.4-69kV

Low voltage (service)-typically 120-600V

TypicalBulk

Power System

TypicalBulk

Power System

36GE Consumer & Industrial

Multilin

Page 34: 1 GE Consumer & Industrial Multilin Protection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc. 770 565-1556 John@L-3.com.

37GE Consumer & Industrial

Multilin

1. Generator or Generator-Transformer Units

2. Transformers

3. Buses

4. Lines (transmission and distribution)

5. Utilization equipment (motors, static loads, etc.)

6. Capacitor or reactor (when separately protected)

Unit Generator-Tx zoneBus zone

Line zone

Bus zone

Transformer zoneTransformer zone

Bus zone

Generator

~

XFMR Bus Line Bus XFMR Bus Motor

Motor zone

Protection Zones Protection Zones

Page 35: 1 GE Consumer & Industrial Multilin Protection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc. 770 565-1556 John@L-3.com.

38GE Consumer & Industrial

Multilin

1. Overlap is accomplished by the locations of CTs, the key source for protective relays.

2. In some cases a fault might involve a CT or a circuit breaker itself, which means it can not be cleared until adjacent breakers (local or remote) are opened.

Zone A Zone B

Relay Zone A

Relay Zone B

CTs are located at both sides of CB-fault between CTs is cleared from both remote sides

Zone A Zone B

Relay Zone A

Relay Zone B

CTs are located at one side of CB-fault between CTs is sensed by both relays, remote right side

operate only.

Zone OverlapZone Overlap

Page 36: 1 GE Consumer & Industrial Multilin Protection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc. 770 565-1556 John@L-3.com.

43GE Consumer & Industrial

Multilin

1. One-line diagram of the system or area involved

2. Impedances and connections of power equipment, system frequency, voltage level and phase sequence

3. Existing schemes

4. Operating procedures and practices affecting protection

5. Importance of protection required and maximum allowed clearance times

6. System fault studies

7. Maximum load and system swing limits

8. CTs and VTs locations, connections and ratios

9. Future expansion expectance

10.Any special considerations for application.

What Info is Required to Apply ProtectionWhat Info is Required to Apply Protection

Page 37: 1 GE Consumer & Industrial Multilin Protection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc. 770 565-1556 John@L-3.com.

C37.2: Device

Numbers

• Partial listing

44GE Consumer & Industrial

Multilin

Page 38: 1 GE Consumer & Industrial Multilin Protection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc. 770 565-1556 John@L-3.com.

45GE Consumer & Industrial

Multilin

One Line Diagram

• Non-dimensioned diagram showing how pieces of electrical equipment are connected

• Simplification of actual system

• Equipment is shown as boxes, circles and other simple graphic symbols

• Symbols should follow ANSI or IEC conventions

Page 39: 1 GE Consumer & Industrial Multilin Protection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc. 770 565-1556 John@L-3.com.

46GE Consumer & Industrial

Multilin

1-Line Symbols [1]

Page 40: 1 GE Consumer & Industrial Multilin Protection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc. 770 565-1556 John@L-3.com.

47GE Consumer & Industrial

Multilin

1-Line Symbols [2]

Page 41: 1 GE Consumer & Industrial Multilin Protection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc. 770 565-1556 John@L-3.com.

48GE Consumer & Industrial

Multilin

1-Line Symbols [3]

Page 42: 1 GE Consumer & Industrial Multilin Protection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc. 770 565-1556 John@L-3.com.

49GE Consumer & Industrial

Multilin

1-Line Symbols [4]

Page 43: 1 GE Consumer & Industrial Multilin Protection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc. 770 565-1556 John@L-3.com.

50GE Consumer & Industrial

Multilin

1-Line [1]

Page 44: 1 GE Consumer & Industrial Multilin Protection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc. 770 565-1556 John@L-3.com.

1-Line [2]

Page 45: 1 GE Consumer & Industrial Multilin Protection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc. 770 565-1556 John@L-3.com.

52GE Consumer & Industrial

Multilin

3-Line

Page 46: 1 GE Consumer & Industrial Multilin Protection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc. 770 565-1556 John@L-3.com.

55GE Consumer & Industrial

Multilin

CB Trip Circuit (Simplified)

Page 47: 1 GE Consumer & Industrial Multilin Protection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc. 770 565-1556 John@L-3.com.

58GE Consumer & Industrial

Multilin

Lock Out Relay

86b

PR

86b

Shown in RESET position

86TC 86a

Page 48: 1 GE Consumer & Industrial Multilin Protection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc. 770 565-1556 John@L-3.com.

59GE Consumer & Industrial

Multilin

CB Coil Circuit Monitoring:T with CB Closed; C with CB Opened

Coil Monitor Input

Trip/Close Contact

+

T/CCoil

-

52/aor

52/b

Breaker

Relay

52/a for trip circuit52/b for close circuit

Page 49: 1 GE Consumer & Industrial Multilin Protection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc. 770 565-1556 John@L-3.com.

60GE Consumer & Industrial

Multilin

CB Coil Circuit Monitoring:Both T&C Regardless of CB state

Breaker

Relay

Breaker

Relay

Page 50: 1 GE Consumer & Industrial Multilin Protection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc. 770 565-1556 John@L-3.com.

61GE Consumer & Industrial

Multilin

• Current transformers are used to step primary system currents to values usable by relays, meters, SCADA, transducers, etc.

• CT ratios are expressed as primary to secondary; 2000:5, 1200:5, 600:5, 300:5

• A 2000:5 CT has a “CTR” of 400

Current Transformers

Page 51: 1 GE Consumer & Industrial Multilin Protection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc. 770 565-1556 John@L-3.com.

62GE Consumer & Industrial

Multilin

• IEEE relay class is defined in terms of the voltage a CT can deliver at 20 times the nominal current rating without exceeding a 10% composite ratio error.

For example, a relay class of C100 on a 1200:5 CT means that the CT can develop 100 volts at 24,000 primary amps (1200*20) without exceeding a 10% ratio error. Maximum burden = 1 ohm.

100 V = 20 * 5 * (1ohm)

200 V = 20 * 5 * (2 ohms)

400 V = 20 * 5 * (4 ohms)

800 V = 20 * 5 * (8 ohms)

Standard IEEE CT Relay Accuracy

Page 52: 1 GE Consumer & Industrial Multilin Protection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc. 770 565-1556 John@L-3.com.

64GE Consumer & Industrial

Multilin

Application Burden Designation

Impedance (Ohms)

VA @ 5 amps

Power Factor

Metering B0.1 0.1 2.5 0.9B0.2 0.2 5 0.9B0.5 0.5 12.5 0.9B0.9 0.9 22.5 0.9B1.8 1.8 45 0.9

Relaying B1 1 25 0.5B2 2 50 0.5B4 4 100 0.5B8 8 200 0.5

Standard IEEE CT Burdens (5 Amp) (Per IEEE Std. C57.13-1993)

Page 53: 1 GE Consumer & Industrial Multilin Protection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc. 770 565-1556 John@L-3.com.

66GE Consumer & Industrial

Multilin

VVPP

VVSS

Relay

• Voltage (potential) transformers are used to isolate and step down and accurately reproduce the scaled voltage for the protective device or relay

• VT ratios are typically expressed as primary to secondary; 14400:120, 7200:120

• A 4160:120 VT has a “VTR” of 34.66

Voltage Transformers

Page 54: 1 GE Consumer & Industrial Multilin Protection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc. 770 565-1556 John@L-3.com.

67GE Consumer & Industrial

Multilin

Typical CT/VT Circuits

Courtesy of Blackburn, Protective Relay: Principles and Applications

Page 55: 1 GE Consumer & Industrial Multilin Protection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc. 770 565-1556 John@L-3.com.

68GE Consumer & Industrial

Multilin

CT/VT Circuit vs. Casing Ground

• Case ground made at IT location• Secondary circuit ground made at first point of

use

Case

Secondary Circuit

Page 56: 1 GE Consumer & Industrial Multilin Protection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc. 770 565-1556 John@L-3.com.

69GE Consumer & Industrial

Multilin

Equipment Grounding

– Prevents shock exposure of personnel– Provides current carrying capability for the

ground-fault current– Grounding includes design and construction of

substation ground mat and CT and VT safety grounding

Page 57: 1 GE Consumer & Industrial Multilin Protection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc. 770 565-1556 John@L-3.com.

70GE Consumer & Industrial

Multilin

System Grounding

– Limits overvoltages– Limits difference in electric potential through local

area conducting objects– Several methods

• Ungrounded• Reactance Coil Grounded • High Z Grounded• Low Z Grounded• Solidly Grounded

Page 58: 1 GE Consumer & Industrial Multilin Protection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc. 770 565-1556 John@L-3.com.

71GE Consumer & Industrial

Multilin

1. Ungrounded: There is no intentional ground applied to the system-however it’s grounded through natural capacitance. Found in 2.4-15kV systems.

2. Reactance Grounded: Total system capacitance is cancelled by equal inductance. This decreases the current at the fault and limits voltage across the arc at the fault to decrease damage.

X0 <= 10 * X1

System Grounding

Page 59: 1 GE Consumer & Industrial Multilin Protection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc. 770 565-1556 John@L-3.com.

72GE Consumer & Industrial

Multilin

3. High Resistance Grounded: Limits ground fault current to 10A-20A. Used to limit transient overvoltages due to arcing ground faults.

R0 <= X0C/3, X0C is capacitive zero sequence reactance

4. Low Resistance Grounded: To limit current to 25-400A

R0 >= 2X0

System Grounding

Page 60: 1 GE Consumer & Industrial Multilin Protection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc. 770 565-1556 John@L-3.com.

73GE Consumer & Industrial

Multilin

5. Solidly Grounded: There is a connection of transformer or generator neutral directly to station ground.

Effectively Grounded: R0 <= X1, X0 <= 3X1, where R is the system fault resistance

System Grounding

Page 61: 1 GE Consumer & Industrial Multilin Protection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc. 770 565-1556 John@L-3.com.

79GE Consumer & Industrial

Multilin

Basic Current Connections:How System is Grounded

Determines How Ground Fault is Detected

Medium/High Resistance

Ground

Low/No Resistance

Ground

Page 62: 1 GE Consumer & Industrial Multilin Protection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc. 770 565-1556 John@L-3.com.

80GE Consumer & Industrial

Multilin

Substation TypesSubstation Types

•Single Supply

•Multiple Supply

•Mobile Substations for emergencies

•Types are defined by number of

transformers, buses, breakers to

provide adequate service for

application

Page 63: 1 GE Consumer & Industrial Multilin Protection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc. 770 565-1556 John@L-3.com.

81GE Consumer & Industrial

Multilin

Industrial Substation Arrangements(Typical)

Page 64: 1 GE Consumer & Industrial Multilin Protection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc. 770 565-1556 John@L-3.com.

82GE Consumer & Industrial

Multilin

Industrial Substation Arrangements(Typical)

Page 65: 1 GE Consumer & Industrial Multilin Protection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc. 770 565-1556 John@L-3.com.

83GE Consumer & Industrial

Multilin

Utility Substation ArrangementsUtility Substation Arrangements

Single Bus, 1 Tx, Dual supply Single Bus, 2 Tx, Dual Supply

2-sections Bus with HS Tie-Breaker, 2 Tx, Dual Supply

(Typical)

Page 66: 1 GE Consumer & Industrial Multilin Protection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc. 770 565-1556 John@L-3.com.

84GE Consumer & Industrial

Multilin

Breaker-and-a-half –allows reduction of equipment cost by using 3 breakers for each 2 circuits. For load transfer and operation is simple, but relaying is complex as middle breaker is responsible to both circuits

Utility Substation ArrangementsUtility Substation Arrangements

Bus 1

Bus 2

Ring bus –advantage that one breaker per circuit. Also each outgoing circuit (Tx) has 2 sources of supply. Any breaker can be taken from service without disrupting others.

(Typical)

Page 67: 1 GE Consumer & Industrial Multilin Protection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc. 770 565-1556 John@L-3.com.

85GE Consumer & Industrial

Multilin

Double Bus: Upper Main and Transfer, bottom Double Main bus

Main bus

Aux. bus

Bus 1

Bus 2

Tie

b

rea

ker

Utility Substation ArrangementsUtility Substation ArrangementsUtility Substation ArrangementsUtility Substation Arrangements

Main

Reserve

Transfer

Main-Reserved and Transfer Bus: Allows maintenance of any bus and any breaker

(Typical)

Page 68: 1 GE Consumer & Industrial Multilin Protection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc. 770 565-1556 John@L-3.com.

86GE Consumer & Industrial

Multilin

Switchgear Defined• Assemblies containing electrical switching,

protection, metering and management devices• Used in three-phase, high-power industrial,

commercial and utility applications• Covers a variety of actual uses, including motor

control, distribution panels and outdoor switchyards

• The term "switchgear" is plural, even when referring to a single switchgear assembly (never say, "switchgears")

• May be a described in terms of use:– "the generator switchgear" – "the stamping line switchgear"

Page 69: 1 GE Consumer & Industrial Multilin Protection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc. 770 565-1556 John@L-3.com.

Switchgear Examples

Page 70: 1 GE Consumer & Industrial Multilin Protection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc. 770 565-1556 John@L-3.com.

94GE Consumer & Industrial

Multilin

A Good Day in System Protection……

– CTs and VTs bring electrical info to relays– Relays sense current and voltage and declare

fault– Relays send signals through control circuits to

circuit breakers– Circuit breaker(s) correctly trip

What Could Go Wrong Here????

Page 71: 1 GE Consumer & Industrial Multilin Protection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc. 770 565-1556 John@L-3.com.

95GE Consumer & Industrial

Multilin

A Bad Day in System Protection……

– CTs or VTs are shorted, opened, or their wiring is– Relays do not declare fault due to setting errors,

faulty relay, CT saturation– Control wires cut or batteries dead so no signal is

sent from relay to circuit breaker– Circuit breakers do not have power, burnt trip coil

or otherwise fail to trip

Protection Systems Typically are Designed for N-1

Page 72: 1 GE Consumer & Industrial Multilin Protection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc. 770 565-1556 John@L-3.com.

96GE Consumer & Industrial

Multilin

Protection Performance Statistics

• Correct and desired: 92.2%

• Correct but undesired: 5.3%

• Incorrect: 2.1%

• Fail to trip: 0.4%

Page 73: 1 GE Consumer & Industrial Multilin Protection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc. 770 565-1556 John@L-3.com.

97GE Consumer & Industrial

Multilin

Contribution to Faults

Page 74: 1 GE Consumer & Industrial Multilin Protection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc. 770 565-1556 John@L-3.com.

98GE Consumer & Industrial

Multilin

Fault Types (Shunt)

Page 75: 1 GE Consumer & Industrial Multilin Protection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc. 770 565-1556 John@L-3.com.

102GE Consumer & Industrial

Multilin

AC & DC Current Components of Fault Current

Page 76: 1 GE Consumer & Industrial Multilin Protection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc. 770 565-1556 John@L-3.com.

105GE Consumer & Industrial

Multilin

Useful Conversions

Page 77: 1 GE Consumer & Industrial Multilin Protection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc. 770 565-1556 John@L-3.com.

106GE Consumer & Industrial

Multilin

Per Unit System

Establish two base quantities:

Standard practice is to define– Base power – 3 phase– Base voltage – line to line

Other quantities derived with basic power equations

Page 78: 1 GE Consumer & Industrial Multilin Protection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc. 770 565-1556 John@L-3.com.

107GE Consumer & Industrial

Multilin

Per Unit Basics

Page 79: 1 GE Consumer & Industrial Multilin Protection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc. 770 565-1556 John@L-3.com.

108GE Consumer & Industrial

Multilin

Short Circuit CalculationsPer Unit System

Per Unit Value = Actual Quantity Base Quantity

Vpu = Vactual

Vbase

Ipu = Iactual

Ibase

Zpu = Zactual

Zbase

Page 80: 1 GE Consumer & Industrial Multilin Protection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc. 770 565-1556 John@L-3.com.

109GE Consumer & Industrial

Multilin

Short Circuit CalculationsPer Unit System

3 x kV L-L base

I base =x 1000MVAbase

Z base =kV2

L-L base

MVAbase

Page 81: 1 GE Consumer & Industrial Multilin Protection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc. 770 565-1556 John@L-3.com.

110GE Consumer & Industrial

Multilin

Short Circuit CalculationsPer Unit System – Base Conversion

Zpu = Zactual

Zbase Zbase = kV 2

base

MVAbase

Zpu1 = MVAbase1

kV 2base1

X Zactual

Zpu2 = MVAbase2

kV 2base2

X Zactual

Zpu2 =Zpu1 x kV 2base1 x MVAbase2

kV 2base2 MVAbase1

Page 82: 1 GE Consumer & Industrial Multilin Protection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc. 770 565-1556 John@L-3.com.

123GE Consumer & Industrial

Multilin

A Study of a Fault…….

Page 83: 1 GE Consumer & Industrial Multilin Protection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc. 770 565-1556 John@L-3.com.

125GE Consumer & Industrial

Multilin

Arc Flash Hazard

Page 84: 1 GE Consumer & Industrial Multilin Protection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc. 770 565-1556 John@L-3.com.

129GE Consumer & Industrial

Multilin

Protective Relaying Methods of Reducing Arc Flash Hazard

– Bus differential protection (this reduces the arc flash energy by reducing the clearing time

– Zone interlock schemes where bus relay selectively is allowed to trip or block depending on location of faults as identified from feeder relays

– Temporary setting changes to reduce clearing time during maintenance • Sacrifices coordination

– FlexCurve for improved coordination opportunities

– Employ 51VC/VR on feeders fed from small generation to improve sensitivity and coordination

– Employ UV light detectors with current disturbance detectors for selective gear tripping

Page 85: 1 GE Consumer & Industrial Multilin Protection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc. 770 565-1556 John@L-3.com.

Arc Flash Hazards

131GE Consumer & Industrial

Multilin

Page 86: 1 GE Consumer & Industrial Multilin Protection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc. 770 565-1556 John@L-3.com.

Arc Pressure Wave

132GE Consumer & Industrial

Multilin

Page 87: 1 GE Consumer & Industrial Multilin Protection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc. 770 565-1556 John@L-3.com.

136GE Consumer & Industrial

Multilin

Copy of this presentation are at:

www.L-3.com\private\IEEE

Page 88: 1 GE Consumer & Industrial Multilin Protection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc. 770 565-1556 John@L-3.com.

137GE Consumer & Industrial

Multilin

Protection Fundamentals

QUESTIONS?