A AMPERE
A/C AIR CONDITIONING
AF AMPERE FRAME
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AHU AIR HANDLING UNIT
AT AMPERE TRIP
AWG AMERICAN WIRE GAUGE
BG BELOW GRADE
BLDG BUILDING
BRKR BREAKER
C CONDUIT
CB CIRCUIT BREAKER
CCT CIRCUIT
DISC SW DISCONNECT SWITCH
DWG DRAWING
EC EMPTY CONDUIT
EF EXHAUSTFANEMT ELECTRICAL METALLIC TUBING
EQUIP EQUIPMENT
ETR EXISTING TO REMAIN
EWC ELECTRIC WATER COOLER
EWH
ELECTRIC WATER HEATER
EXIST EXISTING
FACP FIRE ALARM CONTROL PANEL
FCU FAN COIL UNIT
FLA FULL LOAD AMPS
GFI GROUND FAULT INTERRUPTER
GND GROUND
GRS GALVANIZED RIGID STEEL
HH HANDHOLE
HP HORSEPOWER
KAIC THOUSAND AMP INTERRUPTING
CAPACITY, RMS SYMMETRICAL
KCMIL
KILOWATT HOURKWH
THOUSAND CIRCULAR MILS
KVA KILOVOLT AMPERE
MCB MAIN CIRCUITBREAKERMH MANHOLE
MLO MAIN LUG ONLY
MT MOUNT
MTD MOUNTED
MTG HT MOUNTING HEIGHT
N/C NORMALLY CLOSED
NF NON-FUSED
N/O NORMALLY OPEN
NESC NATIONAL ELECTRICAL
NEU NEUTRAL
NIC NOT IN CONTRACT
P POLE
PH PHASEPNL PANEL
PVC POLY VINYL CHLORIDE
QTY QUANTITY
RECEPT RECEPTACLE
REQ'D REQUIRED
SF SUPPLY FANS/N SOLID NEUTRAL
SW SWITCHTEL TELEPHONE
TV TELEVISION
UNIT HEATERUG UNDERGROUNDUON UNLESS OTHERWISE NOTED
V VOLTSW
WATER HEATERWHWIRE
WP INDICATES WEATHERPROOFEQUIPMENTXFMR TRANSFORMER
SAFETY CODE
FC FOOTCANDLE
DT DRY TYPE
MSB MAIN SWITCHBOARD
NEC NATIONAL ELECTRICAL CODE
TGB TELECOMMUNICATIONSGROUND BUS/BAR
TMGB TELECOMMUNICATIONSMAIN GROUND BUS/BAR
LAN LOCAL AREA NETWORK
LTG LIGHTING
UP UNDERGROUND POWER
SPD SURGE PROTECTIVE DEVICE
MSGB MAIN SYSTEM GROUNDBUS/BAR
LED RECESSED OR PENDANT FIXTURE. SEE LIGHTIG FIXTURESCHEDULE FOR DETAILS.
LED DOWNLIGHT ( INDICATES BRACKET, WALL MOUNTED FIXTURES).
EXIT LIGHTING FIXTURE. ARROW, WHEN USED, INDICATES DIRECTION.(INDICATES BRACKET, WALL MOUNTED FIXTURES). FILLED IN QUADRANT(s) OF SYMBOL INDICATES NUMBER AND ORIENTATION OF ILLUMINATEDFACES. (SEE LEGEND NOTE 3)
0-10V DIMMABLE WALL SWITCH, 20A, 120/277V. MOUNT 48" AFF TOCENTER UON.
DUPLEX CONVENIENCE RECEPTACLE, 20 A, 125 VAC, MOUNT +18" AFFUON. "WP" INDICATES WEATHERPROOF OUTLET.
RECEPTACLE AS NOTED ABOVE BUT, MOUNT 48" AFF OR 6" ABOVEBACKSPLASH OR COUNTER TOP WHERE COUNTER IS INDICATED.
FLUSH FLOOR MOUNTED SIX PORT VOICE/DATA/EXPANSIONOUTLET
DESCRIPTIONSYMBOL
LIGHTINGPROVIDE
LIGHTING CONTACTOR
POWER DEVICES
NEMA L14-30R RECEPTACLE. MOUNT AT 18" AFF.
TELECOMMUNICATION & SPECIAL SYSTEMS
EQUIPMENT CONNECTIONS
EQUIPMENT CONNECTION AS NOTED IN EQUIPMENTCONNECTION SCHEDULE.
JUNCTION BOX
DESCRIPTIONSYMBOL
DISTRIBUTION
PANELBOARD - 208Y/120V
DRY TYPE TRANSFORMER, SIZE AS INDICATED.
PANELBOARD - 480Y/277V
WIRE, CONDUIT AND RACEWAY
BRANCH CIRCUIT OR FEEDER WIRING IN CONDUIT INDICATES 2#12 CONDUCTORS & 1 #12 GND. IN 3/4" CONDUIT UON. CONDUITLARGER THAN 3/4" & WIRE LARGER THAN #12 SHALL BE ASINDICATED. (SEE LEGEND NOTE 1)
INDICATES A CONDUIT RUN CONCEALED IN CEILING, WALL, FLOOR,OR ABOVE SUSPENDED CEILING UON.
HOMERUNS TO PANEL. PANEL AND CIRCUIT DESIGNATIONSAS INDICATED.
CONDUIT TURNED DOWN
CONDUIT TURNED UP
CABLE TRAY, SIZE AND TYPE AS INDICATED.
L2A-1,3
GENERAL
NOTE REFERENCE - TYPICALLY LOCATED ON SAME SHEETWHERE SYMBOL IS USED.
THREE-WAY SWITCH, 20 A, 120/277 V. MOUNT 48" AFF TO CENTER UON.
EQUIPMENT TAG - SEE EQUIPMENT SCHEDULE SHEET EP701.
QUADRUPLEX CONVENIENCE RECEPTACLE MOUNTED IN TWO-GANG OUTLET BOX - EACH RATED 20A, 125 VOLTS WITH SINGLECOVER PLATE, MOUNT 18" AFF, UON.
LIGHTING FIXTURE TYPE, SEE LIGHTING FIXTURE SCHEDULE ONSHEET EL601.
A
EMERGENCY LIGHTING FIXTURE. POWERED FROM LIFE-SAFETYSYSTEM.
0-10V DIMMABLE, DUAL TECHNOLOGY OCCUPANCY SWITCH.MOUNT 48" AFF TO CENTER UON.
LOW VOLTAGE ROOM CONTROLLER, BASIS OF DESIGN HUBBELLBUILDING AUTOMATION NXRC-2RD-UNV
PHOTO-ELECTRIC SWITCH
TIME SWITCH
SIX PORT VOICE/DATA/EXPANSION. SEE DETAIL C1 AND F1 ON SHEETFY501. MOUNT 18" AFF UON
MAGNETIC MOTOR CONTROLLER (CONTROLLER FURNISHEDWITH EQUIPMENT).
MOTOR RATED SWITCH
DISCONNECT SWITCH. SIZE AS NOTED ON DRAWINGS
DISCONNECT SWITCH PROVIDED INTEGRAL WITH EQUIPMENT.
POINT OF CONNECTION NEW-TO-EXISTING (SEE LEGEND NOTE2).
POINT OF DEMOLITION
ROOM NUMBER.
D
OS
3
P
C
RC
T/S
E
J
M
T
1
101
XXX
OR
VARIABLE FREQUENCY CONNECTIONVFC
SWITCH WITH PILOT LIGHT, MOUNT 48" AFF UON.P
PROVIDE
CROSS HATCHING INDICATES REMOVE INDICATED DEVICE ORCIRCUIT.
EXISTING
L2A-1,3
T
EXISTING
XXX FEEDER DESIGNATION. FOR FEEDER SCHEDULE, SEE SHEETEP701.
SINGLE PORT CABLE TELEVISION OUTLET. MOUNT 72" AFF UON.TV
INDICATES GROUND FAULT CIRCUIT INTERUPTING RECEPTACLE.
LOW VOLTAGE CEILING MOUNTED DUAL TECHNOLOGYOCCUPANCY SENSOR, BASIS OF DESIGN HUBBELL BUILDINGAUTOMATION NXOS-OMDT2. REFER TO LIGHTING CONTROL RSERDIAGRAM ON EL601 AND LIGHTING SCHEDULE ON EL101 AND EL102.
PHOTOELECTRIC SMOKE DETECTOR, CEILING MOUNTED.SD
FIRE PROTECTION
NURSE STATION DOME LIGHT, SWITCHED BY PULL STATION INRESPECTIVE TOILET ROOM. MOUNT CENTERED ABOVE RESPECTIVEENTRANCE(S).
S PUBLIC ADDRESS (PA) SPEAKER, CEILING MOUNTED, SQUARE TYPE.
N
F FIRE ALARM PULL SWITCH STATION, WALL MOUNT 48" AFF UON.
FIRE ALARM STROBE WITH SPEAKER, WALL MOUNT 80" AFF UON.F
KP CARD READER ACCESS CONTROL DEVICE WITH KEYPAD. MOUNT48" AFF UON.
SECURITY MOTION DETECTOR, CEILING MOUNTED UON.M
CCTV SECURITY CAMERA. CEILING MOUNT FOR INTERIOR UON.WALL MOUNT FOR EXTERIOR UON.
SINGLE POLE SWITCH, 20A, 120/277V. MOUNT 48" AFF TO CENTER UON.
OR INDICATES TAMPER RESISTANT RECEPTACLE.
OR INDICATES GROUND FAULT CIRCUIT INTERUPTING RECEPTACLEAND ABOVE COUNTER MOUNTED.
FIRE ALARM PULL STROBE, WALL MOUNT 80" AFF UON.
LIGHTNING PROTECTION AND GROUNDING
AIR TERMINAL. SEE DETAILS 1 & 2, SHEET EP501.A
R ROOF CONDUCTOR. #2 AWG CU.
DDOWN CONDUCTOR. #2 AWG CU. SEE DETAILS 3, 4, & 5, SHEETEP501.
GGROUND CONDUCTOR. MATCH EXISTING GROUND RING. NOTE: IFNO PREVIOUS GROUND RING, PROVIDE MINIMUM #2/0 AWG CU.
GROUND ROD. SEE DETAILS 4 - 7, SHEET EP501.
GROUND ROD INSPECTION PIT. SEE DETAIL 8, SHEET EP501.
WIDE ANGLE LENS EXTERIOR CCTV SECURITY CAMERA.
LOW VOLTAGE CEILING MOUNTED DAYLIGHT SENSOR, BASISOF DESIGN HUBBELL BUILDING AUTOMATION NXDS. SENSORSHALL ONLY DIM FIXTURE NEAREST WINDOW(S).
DS
OS
LOW VOLTAGE ROOM CONTROLLER, BASIS OF DESIGNHUBBELL BUILDING AUTOMATION NXRC-1R-UNV
RCP
CR CARD READER ACCESS CONTROL DEVICE. MOUNT 48" AFF UON.
NURSE CALL PULL STATION. CONNECT TO RESPECTIVE DOMELIGHT AND SPEAKER AS A STAND ALONE UNIT. INSTALL WITHIN48" AFF WHERE CORD HANGS 4" AFF. INSTALL WITHIN 12" FROMTOILET.
N
SINGLE PORT DATA OUTLET FOR DDC, MOUNT AT 48" AFF.DDC
thre
e in
ches
= o
ne fo
ot6"
Department ofVeterans Affairs
one
and
one
half
inch
es =
one
foot
6"on
e in
ch =
one
foot
thre
e qu
arte
rs in
ch =
one
foot
one
half
inch
= o
ne fo
ot0
thre
e ei
ghth
s in
ch =
one
foot
0on
e qu
arte
r in
ch =
one
foot
0on
e ei
ghth
inch
= o
ne fo
ot0
10
6"0
26"
02
44
48
48
16
VA FORM 08-6231
Revisions:
1 2 3 4 5 6 7 8 9
Date:
CONSULTANTS: ARCHITECT/ENGINEERS:
590 MEANS ST NW ATLANTA, GA 30318
Drawing Title:
Approved Project Director:
Project Title:
Location:
Date: Checked: Drawn:
Drawing Number:
Building Number:
Project Number:
Dwg. of
OFFICE OFCONSTRUCTIONAND FACILITIESMANAGEMENT
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
BID DOCUMENTS
ELECTRICAL LEGEND CONSTRUCT DOM CLINIC
AND CLC ADMINISTRATION
ADDITION
MARTINSBURG, WV
E001
613-121
June 27, 2018 CEN SBC
LEGEND NOTES GENERAL NOTES
A. WIRING SHALL BE IN CONDUIT, MINIMUM SIZE THREE-QUARTER (3/4) INCHWITH LARGER SIZES AS INDICATED OR REQUIRED BY NEC.
B. WIRE AND CABLE SHALL BE #12 AWG MINIMUM.C. OPENINGS CREATED IN A FIRE OR SMOKE RATED WALL OR FLOOR BY
PROVISION OF ANY ELECTRICAL DEVICE OR CONDUIT, SHALL BE SEALEDAFTER THE WORK IS COMPLETED WITH A UL APPROVED FIRE/SMOKESEALANT APPROPRIATE TO RE-ESTABLISH THE PREVIOUS RATING OF THEWALL OR FLOOR. SEE ARCHITECTURAL PLANS FOR FIRE RATEDWALLS/FLOORS AND THEIR RATING.
1. WIRE AND CONDUIT FOR MOTOR AND EQUIPMENT LOADS SHALL BECONTINUOUS IN SIZE AND COUNT FROM SOURCE TO FINAL CONNECTION.SIZE AND COUNT SHALL BE AS INDICATED ON THE CIRCUIT HOMERUNUNLESS OTHERWISE NOTED.
2. WHERE A NEW-TO-EXISTING CONNECTION IS INDICATED, PROVIDEMATERIALS AND LABOR REQUIRED TO MAKE THE CONNECTION.
3. BRANCH CIRCUIT WIRING TO EXIT LIGHT FIXTURES AND TO THE BATTERYINVERTERS WITHIN FIXTURES WITH INTEGRAL BATTERY UNITS SHALL BEUNSWITCHED, CONNECTED AHEAD OF ANY CONTROL SWITCHES.
ELECTRICAL ABBREVIATIONSELECTRICAL LEGEND
501D & 502F
C-105
341 SQ. FT.
C-107
438 SQ. FT.
C-106
120 SQ. FT.
C-108
808 SQ. FT.
C-109
549 SQ. FT.
C-109A
132 SQ. FT.
C-110
181 SQ. FT.
CW-1
507 SQ. FT.
C-112
150 SQ. FT.
E-1
88 SQ. FT.
C-113
450 SQ. FT.
C-114
396 SQ. FT.
C-115
264 SQ. FT.
C-111
63 SQ. FT.
C-125
3,053 SQ. FT.
C-122
71 SQ. FT.
C-123
59 SQ. FT.
C-124
111 SQ. FT.
C-126
1688 SQ. FT.
C-127
623 SQ. FT.
C-128
660 SQ. FT.
CC-4
368 SQ. FT.
125 SQ. FT.
MEN'S LOCKER
WOMEN'S LOCKER
OFFICE
MECHANICAL ROOM
ELECTRIC ROOM
GENERATOR ROOM
STAIR # 1
WALKWAY
SERVICE ELEVATORLOBBY
ELEV.
SOILED UTILITY
PHARMACY
OFFICE
OXYGEN STORAGE
DINING
TOILET
ALCOVE
TOILET
RECREATION
RECREATIONEXAM
CORRIDOR
BIO
MED
233
ELEC R
OOM
235
STORAGE
239 SERVIC
E C
ORR.
SC-1
MULE S
TORAGE
238
UPDN.
D.F.
F.E.C.
F.E.C.
SDCO
10
11
1
2
3
4
5
6
9
8
7
5
12
13
5
thre
e in
ches
= o
ne fo
ot6"
Department ofVeterans Affairs
one
and
one
half
inch
es =
one
foot
6"on
e in
ch =
one
foot
thre
e qu
arte
rs in
ch =
one
foot
one
half
inch
= o
ne fo
ot0
thre
e ei
ghth
s in
ch =
one
foot
0on
e qu
arte
r in
ch =
one
foot
0on
e ei
ghth
inch
= o
ne fo
ot0
10
6"0
26"
02
44
48
48
16
VA FORM 08-6231
Revisions:
1 2 3 4 5 6 7 8 9
Date:
CONSULTANTS: ARCHITECT/ENGINEERS:
590 MEANS ST NW ATLANTA, GA 30318
Drawing Title:
Approved Project Director:
Project Title:
Location:
Date: Checked: Drawn:
Drawing Number:
Building Number:
Project Number:
Dwg. of
OFFICE OFCONSTRUCTIONAND FACILITIESMANAGEMENT
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
BID DOCUMENTS
ELECTRICAL DEMOLITION PLAN - CLC ADMIN CONSTRUCT DOM CLINIC
AND CLC ADMINISTRATION
ADDITION
MARTINSBURG, WV
ED101
613-121
June 27, 2018 CEN SBC
1/8" = 1'-0"1
ELECTRICAL DEMO PLAN - CLC ADMIN
GENERAL NOTES
KEY NOTES
GRAPHIC SCALE(S)
1/8" = 1' - 0"0 5' 10' 15' 30'
1 HAND HOLE SHALL BE REMOVED. RE-ROUTE EXISTINGBRANCH CIRCUITS SERVED FROM THIS JUNCTION.PROVIDE NEW IN GRADE SPLICE BOX(ES) WITH SCREW ONCOVER AS NECESSARY.
2 100 AMP PANEL "BLDG 501 ELECTRONIC MONITORINGPANEL" TO REMAIN. RE-FEED AS SHOWN ON EP101 FROMPANEL "EM-A" CURRENTLY SERVING THIS PANEL. THISPANEL IS SERVED FROM "EM-A" CIRCUIT 20,22,24 INBUILDING 501 ROOM C109.
3 LOAD CENTER AND FEEDER TO BE REMOVED.
4 FEEDER SERVING THE WOODEN SHED SHALL BEREMOVED TO JUST BEYOND THE NEW BUILDINGSEXTERIOR WALL. EXISTING CIRCUIT SHALL BEINTERCEPTED AND EXTENDED TO NEW PANEL AS SHOWNON NEW WORK PLAN EP101.
5 FEEDER SHALL BE REMOVED IN ITS ENTIRETY INCLUDINGHANDHOLE.
6 BRANCH CIRCUIT SERVING HVAC UNIT SHALL BEREMOVED BACK TO PANEL. SEE NOTE 3 FOR LOCATIONOF THIS PANEL.
7 WALL MOUNTED LIGHTING SERVING THIS AREA IS TO BEREMOVED BACK TO SERVING PANEL.
8 ACCESS CONTROL EQUIPMENT SERVING THIS DOORSHALL BE REMOVED.
9 STUBBED UP RECEPTACLE AT THIS LOCATION SHALL BEREMOVED. REMOVE BRANCH CIRCUITRY BACK TONEAREST REMAINING DEVICE. IF THERE ARERECEPTACLES DOWNSTREAM OF THIS DEVICE THEYSHALL BE RECONNECTED TO THE EXISTING CIRCUIT.
10 EXTERIOR WALL PACK AT THIS LOCATION SHALL BEREMOVED AND BRANCH CIRCUITRY SHALL BE REMOVEDBACK TO NEAREST REMAINING DEVICES.
11 REMOVE BRANCH CIRCUITRY SERVING FAN ABOVE DOOR.
12 EXISTING JUNCTION BOX TO BE REMOVED, ANDABANDONDED FEEDER ENDING IN THIS JUNCTION BOXSHALL BE REMOVED BACK TO SERVING PANEL.
13 EXISTING TELECOMMUNICATIONS MANHOLE TO HAVENEW COVER SELECTED BY ARCHITECT AND PROVIDED BYCONTRACTOR IN NEW CORRIDOR.
#
1. THIS PLAN SHOWS GENERALLY THE EXTENT OF DEMOLITIONTO BE PERFORMED. UNLESS NOTED OTHERWISE,DISCONNECT, REMOVE, AND HAUL OFF ALL ELECTRICALASSOCIATED WITH AREAS SHOWN. THIS SHALL INCLUDE,BUT NOT BE LIMITED TO: FIXTURES, WIRING DEVICES,PANELS, DISCONNECTS, ACCESSIBLE BOXES, CONDUITAND CONDUCTORS, ETC. WHERE BRANCH CIRCUITS AREBEING REMOVED, REMOVE BACK TO PANEL FEEDING ORCLOSEST JUNCTION BOX OF BRANCH CIRCUIT TO REMAIN.FIELD VERIFY AND COORDINATE EXISTING BRANCH CIRCUITSAND ELECTRICAL TO REMAIN IN ALL AREAS AND KEEP ACTIVETHROUGHOUT CONSTRUCTION. PROVIDE ALLAPPURTENANCES NECESSARY AND MAKE ALL CONNECTIONSAS REQUIRED. COORDINATE WITH ARCHITECTURALDRAWINGS FOR EXACT LIMITS OF CONSTRUCTION.
501
DNDNDN
DNCG CG
CG
CG
CG
CG
CGCGCG
CG
CG
CGCGCG
CG
CG
CGCG
CG
CG
CG
D
DDDDD
OS
D D
D
DD
OS
D D D
D
D
OS
OS
DD
OSOSOS OS
D D
OS
OS OS OS OS OS OS OS
OS
OS
OS
OS
OS
OS
OSOS
OS OS OS OS
OS OS
OS
OS
OS
OS
OS
OS
OS OS
OS
OS
OS
OS
OS
OS OS
OS
OS OS
OSOS
DS
DS
DS
DS DS DS DS
501D-100
501D-110 501D-108501D-113 501D-112501D-114501D-115
501D-107
501D-106
501D-109
501D-116
501D-111A
501D-111
501D-C2
501D-120
501D-128
501D-121
501D-103
501D-101
501D-122
501D-123501D-124501D-125501D-126
501D-102
501D-131
501D-130
501D-127501D-129A
501D-129
501D-C3
501D-C4
501D-104
501D-105
501D-136
501D-C1
501D-C5
501D-117501D-118501D-134501D-133501D-132
501D-135
501D-119
B
A1 A1 A1 A1A1
A1
A1
B
B
B
B
B
B
B
BB
B
BBBB
BB
B
B
B
BB B B B
B B B
A1
A1A1
A1
A1
A1 A1
A1
A1
A1
A1 A1
A1
A1 A1
A1A1 B
A2
A2
B
A1
A1
A1
A1
A1
A1A1
A1A1
A1
A1
A1BB B B B
A1
A1
A2 A2
A2A2
P1P1
P1
P1
P1
P1
P1
P1
P1P1
BBBB
B
BBBBBBB B B B
D1
B
D1
A1A1
P1
P1
P1
P1
A2
A2
B
BB
B
A1
A1
A1
A1
D1D1
D1D1
P2
A2
501D-HA-3
501D-HA-1
1
D1
A1
X1
X1
X1
X1
X1 X1 X1
X1
X1
X1
X1
X1
X1
X1X1
X1501C-125A
C
C.2
C.4
F
G
G.5
H
I
K
1 3 3.1 3.4 4 4.8 5 6 7 8 9 10 11 12
X1
501D-HA-5 (SC)
Z1
Z1
MOUNTAT 10'AFF
14' - 1 3/16"
501D-C4
A1
A1
4.5
RE
B
B.5
5.3 6.5 7.5 9.7 9.8 9.9 10.58.4
A
C
C.2
C.4
F
G
G.5
H
I
K
Z1
501D-HA-5 (SC)
Z1
Z1 Z1
Z1
B.5
TRUE
NORTH
PLAN
NORTH
TRUE
NORTH
PLAN
NORTH
thre
e in
ches
= o
ne fo
ot6"
Department ofVeterans Affairs
one
and
one
half
inch
es =
one
foot
6"on
e in
ch =
one
foot
thre
e qu
arte
rs in
ch =
one
foot
one
half
inch
= o
ne fo
ot0
thre
e ei
ghth
s in
ch =
one
foot
0on
e qu
arte
r in
ch =
one
foot
0on
e ei
ghth
inch
= o
ne fo
ot0
10
6"0
26"
02
44
48
48
16
VA FORM 08-6231
Revisions:
1 2 3 4 5 6 7 8 9
Date:
CONSULTANTS: ARCHITECT/ENGINEERS:
590 MEANS ST NW ATLANTA, GA 30318
Drawing Title:
Approved Project Director:
Project Title:
Location:
Date: Checked: Drawn:
Drawing Number:
Building Number:
Project Number:
Dwg. of
OFFICE OFCONSTRUCTIONAND FACILITIESMANAGEMENT
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
BID DOCUMENTS
FIRST FLOOR LIGHTING PLAN - CLC ADMIN CONSTRUCT DOM CLINIC
AND CLC ADMINISTRATION
ADDITION
MARTINSBURG, WV
EL101
613-121
June 27, 2018 CEN SBC
1/8" = 1'-0"1
FIRST FLOOR LIGHTING PLAN - CLC ADMIN
GENERAL NOTES
KEY NOTES
GRAPHIC SCALE(S)
1/8" = 1' - 0"0 5' 10' 15' 30'
CLC ROOM SCHEDULE - LIGHTING
NUMBER NAME
AVERAGE LIGHTLEVEL (FC)
UNIFORMITY RATIO(Max/Min)
ROOMCONTROLLER
# OF ROOMCONTROLLERS
TARGET DESIGN
501D-124 OFFICE/EXAM 50.0 48 2:1 YES 1
501D-125 OFFICE/EXAM 50.0 58 2:1 YES 1
501D-126 PROG. MAN. 50.0 56 2:1 YES 1
501D-127 BUS. MAN. 50.0 50 2:1 YES 1
501D-128 CUBICLES 15 59 2:1 YES 1
501D-129 AD. ASST. 50.0 41 2:1 YES 1
501D-129A STOR. 30 21 N/A NO
501D-130 SERV. CHIEF. 50.0 53 2:1 YES 1
501D-131 ENTRANCE 40.0 32 5:1 YES 1
501D-132 GUEST T. 15 46 2:1 NO
501D-133 STAFF T. 30 46 N/A NO
501D-134 HAC 10 46 N/A NO
501D-135 STOR. 30 20 N/A NO
501D-136 LANDING 15 34 4:1 NO
501D-C1 CORRIDOR 15 26 4:1 YES 1 - 1N
501D-C2 CORRIDOR 15 30 4:1 YES 1 - 1N
501D-C3 CORR. A 15 34 4:1 YES 1 - 1N
501D-C4 CORR. B 15 34 4:1 NO
501D-C5 CONNECTORRAMP
15 26 4:1 NO
CLC ROOM SCHEDULE - LIGHTING
NUMBER NAME
AVERAGE LIGHTLEVEL (FC)
UNIFORMITY RATIO(Max/Min)
ROOMCONTROLLER
# OF ROOMCONTROLLERS
TARGET DESIGN
501D-100 ENTRANCE 15.0 14 YES 1
501D-101 IT 50.0 (MIN) 35 NO
501D-102 MECHANICAL 19.0 (MIN) 44 NO
501D-103 STORAGE 20 33 N/A NO
501D-104 ELECTRICAL 50 84 NO
501D-105 CORR. 10.0 41 4:1 YES 2 - 1 N, 1 EM
501D-106 WAITING 30.0 31 5:1 YES 2 - 1 N, 1 EM
501D-107 ADMIN. SUPP. 50.0 51 2:1 YES 1
501D-108 N. CASE MAN. 50.0 54 2:1 YES 1
501D-109 OFF. / EX. 50.0 60 2:1 YES 1
501D-110 OFF. / EX. 50.0 47 2:1 YES 1
501D-111 OFF. / EX. 50.0 52 2:1 YES 1
501D-111A STOR. 30 25 N/A NO
501D-112 OFF. / EX. 50.0 47 2:1 YES 1
501D-113 N. CASE MAN. 50.0 54 2:1 YES 1
501D-114 PSYCHOL. 50.0 54 2:1 YES 1
501D-115 G. FELLOW 50.0 54 2:1 YES 1
501D-116 G. FELLOW 50.0 54 2:1 YES 1
501D-117 GUEST T. 15 46 2:1 NO
501D-118 STAFF T. 30 46 N/A NO
501D-119 STOR. 30 20 N/A NO
501D-120 COPY /WORKROOM
15 83 2:1 YES 2 - 1 N, 1 EM
501D-121 BREAK ROOM 50.0 61 2:1 YES 1
501D-122 CONFERENCEROOM
50 50 3:1 YES 2 - 1 N, 1 EM
501D-123 N. ADMIN. 50.0 53 2:1 YES 1
1 ROUTE 2#12,#12G,3/4" CONDUIT TO SPARE 20A/1PBREAKER IN PANEL "EM-A" IN ELECTIRCAL ROOM C-109.REFER TO EP101 FOR LOCATION OF PANEL.
#
501D
A. PROVIDE A UL924 DEVICE FOR EACH EMERGENCY LIGHTFIXTURE. REFER TO UL924 RELAY DETAIL ON EL601.
1/8" = 1'-0"2
EXTERIOR LIGHTING PLAN - CLC ADMIN
MA
TC
HLIN
E A
MA
TC
HLIN
E A
MA
TC
HLIN
E A
MA
TC
HLIN
E A
CG
CG
CG
CG
CG
CG
CG
CG
CG
CG
CG
CG
CG
CG
CG
CG
CG
CG
CG
CG
CG
CG
CG
CG
CG
CG
CG
CG
OS
DDD
D
DD
D
D
D
OS
DDDD
DDD
OS
D
D
OS
OS
OS
OSOS OSOS OS OS
OSOS
D
OSOS OS OS OS
OS
OS OS
OS
OS
OS
OS
OS
OS OS OS
OS
OS
D
OS
OS
OS
DS DS
DS DSDS
DSDS
DS
DS
DS
DS
502F-118
502F-116
502F-124502F-120
502F-114
502F-C1
502F-110
502F-101
502F-107
502F-106
502F-115 502F-117 502F-119 502F-121
502F-122
502F-123
502F-125
502F-127
502F-C2
502F-129502F-126
502F-128
502F-130
502F-111502F-109502F-108
502F-104
502F-102
502F-113502F-105
502F-112
502F-103
502F-100
502F-LS-1
502F-HA-1
502F-HA-3
B
BB
B
B
BB
D1
B
B
B
B
D2
D2
A1 A1
A1A1
A1A1
A1A1
B
A1
A1
A1
A1A1
A1A1
A1
A1
A1
A1
A1 A1
A1
A1
A1A1
A1A1
A1
A2
B
D2
D1
D1D1
A1
A2
A2
A1
A1
D1
D1
D2
D1D1
D1
D2 D2
D2 D2
A2
A2A2
A2 B
P1
P1
P1 P1P1
P1
P1
D1
D1
D1
D1
D1
D2
D1
D1
D1
D1
D1
D1
D1
D1
D1
D1
D1
P1
P1
A1
FF EE DD CC BB AA
20
21
21.4
22
23
X1
X1
X1
X1 X1
Z1
D2
Z1
Z1 Z1
Z1
Z1
Z1Z1
Z1
502F-HA-5
502F-105A
502F-107A
C
C
C
CC
C
TRUE
NORTH
PLAN
NORTH
thre
e in
ches
= o
ne fo
ot6"
Department ofVeterans Affairs
one
and
one
half
inch
es =
one
foot
6"on
e in
ch =
one
foot
thre
e qu
arte
rs in
ch =
one
foot
one
half
inch
= o
ne fo
ot0
thre
e ei
ghth
s in
ch =
one
foot
0on
e qu
arte
r in
ch =
one
foot
0on
e ei
ghth
inch
= o
ne fo
ot0
10
6"0
26"
02
44
48
48
16
VA FORM 08-6231
Revisions:
1 2 3 4 5 6 7 8 9
Date:
CONSULTANTS: ARCHITECT/ENGINEERS:
590 MEANS ST NW ATLANTA, GA 30318
Drawing Title:
Approved Project Director:
Project Title:
Location:
Date: Checked: Drawn:
Drawing Number:
Building Number:
Project Number:
Dwg. of
OFFICE OFCONSTRUCTIONAND FACILITIESMANAGEMENT
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
BID DOCUMENTS
FIRST FLOOR LIGHTING PLAN - DOM CLINIC CONSTRUCT DOM CLINIC
AND CLC ADMINISTRATION
ADDITION
MARTINSBURG, WV
EL102
613-121
June 27, 2018 CEN SBC
GENERAL NOTES
GRAPHIC SCALE(S)
1/8" = 1' - 0"0 5' 10' 15' 30'
1/8" = 1'-0"1
FIRST FLOOR LIGHTING PLAN - DOM CLINIC
DOM ROOM SCHEDULE - LIGHTING
NUMBER NAME
AVERAGE LIGHTLEVEL (FC)
UNIFORMITY
RATIO(Max/Min)
ROOMCONTROLLER
# OF ROOMCONTROLLERS
TARGET DESIGN
502F-100 LOBBY 40.0 45 5:1 YES 1 - 1N
502F-101 PAT. T. 15 16 2:1 NO
502F-102 CHECK IN 30.0 38 5:1 YES 2 - 1N, 1EM
502F-103 WAITING 20 45 5:1 NO
502F-104 TRIAGE 100 99 3:1 YES 2 - 1N, 1EM
502F-105 N. STATION 50.0 57 3:1 YES 2 - 1N, 1EM
502F-105A STOR. 50.0 57 NO
502F-106 MEDS 30 40 N/A YES 2 - 1N, 1EM
502F-107 N. STATION 50.0 52 3:1 YES 2 - 1N, 1EM
502F-107A STOR. 30 52 N/A NO
502F-108 N. ASSESS. 50.0 57 2:1 YES 1
502F-109 N. ASSESS. 50.0 57 2:1 YES 1
502F-110 VESTIBULE 20 32 5:1 YES 1
502F-111 SPEC. VEST. 20 24 5:1 NO
502F-112 SPEC. T. 30 29 N/A NO
502F-113 DOM SCREENINGCLERK
50.0 57 2:1 YES 1
502F-114 N. ASSESS. 50.0 55 2:1 YES 1
502F-115 DOM STAFFSCREENER
50.0 57 2:1 YES 1
502F-116 REC. THER. 50.0 55 2:1 YES 1
502F-117 DOM SUPV. SCREEN. 50.0 57 2:1 YES 1
502F-118 DIETICIAN 50.0 55 2:1 YES 1
502F-119 PEER SUPP. 50.0 57 2:1 YES 1
502F-120 IT 50.0 (MIN) 68 NO
502F-121 SOC. WORK. 50.0 57 2:1 YES 1
502F-122 HAC 10 43 N/A NO
502F-123 MANAGER 50.0 70 2:1 YES 1
502F-124 STAFF T. 30 28.4 N/A NO
502F-125 PSYCH. 50.0 54 2:1 YES 1
502F-126 PA OFFICE 50.0 54 2:1 YES 2 - 1N, 1EM
502F-127 PSYCH. 50.0 54 2:1 YES 1
502F-128 MECHANICAL 19.0 (MIN) 56 NO
502F-129 PSYCH. 50.0 54 2:1 YES 1
502F-130 ELECT 50 77 NO
502F-C1 CORR. A 15 25 4:1 YES 1 - 1N
502F-C2 CORR. B 15 25 4:1 NO
502F
1. PROVIDE A UL924 DEVICE FOR EACH EMERGENCY LIGHTFIXTURE. REFER TO UL924 RELAY DETAIL ON EL601.
SCALE: NONE
RC RC OS OS
A
DS
LIGHTING AND RECEPTACLE CONTROL RISER DIAGRAM
NOTES:
3
(TYPICAL FOR ALL SPACES)
(LIGHTING CONTROL RISER DIAGRAM ONLY)
1
2
EXACT NUMBER OF DEVICES SHOWN ON PLANS.
POWER CONNECTION TO LIGHT FIXTURE.
LIGHTING CIRCUIT SERVING SPACE.
CAT 6 CABLE.
LIGHTING CONTROL CABLE NOT SHOWN ON FLOOR PLANS.
TO NEXT OCCUPANCY SENSOR.
PROVIDE 2 IN/1 OUT CAT 6 ADAPTER AT EACH STUB OUT.
REFER TO ROOM SCHEDULE ON EACH LIGHTING SHEET FOR ROOMS THAT
REQUIRE ROOM CONTROLLERS.
3
2
5
4
1
4
4 7 7
5
6
5
6
7
8
4
8 8
UL 924 LISTED EMERGENCYLIGHTING RELAY
<EMERGENCY POWER
<UTILITY POWER
RED LIGHT
GREEN LIGHT
TOADDITIONALNORMALLIGHTING
BLACK (SENSING) REGULAR LINE HOT
REGULAR LINE NEUTRAL
ROOM SWITCH
NORMAL LIGHTING LOAD
TO 20 AMPNORMALPOWERCIRCUIT
1
2
3
RED
WHITE
6
BLUE
5
YELLOW
4
WHITE
X
BLUEEMERGENCY NEUTRAL
EMERGENCY HOT
EMERGENCY LIGHTING LOAD
EMERGENCYSWITCHING
TO 20 AMPEMERGENCY
POWERCIRCUIT
TOADDITIONALEMERGENCY LIGHTING
thre
e in
ches
= o
ne fo
ot6"
Department ofVeterans Affairs
one
and
one
half
inch
es =
one
foot
6"on
e in
ch =
one
foot
thre
e qu
arte
rs in
ch =
one
foot
one
half
inch
= o
ne fo
ot0
thre
e ei
ghth
s in
ch =
one
foot
0on
e qu
arte
r in
ch =
one
foot
0on
e ei
ghth
inch
= o
ne fo
ot0
10
6"0
26"
02
44
48
48
16
VA FORM 08-6231
Revisions:
1 2 3 4 5 6 7 8 9
Date:
CONSULTANTS: ARCHITECT/ENGINEERS:
590 MEANS ST NW ATLANTA, GA 30318
Drawing Title:
Approved Project Director:
Project Title:
Location:
Date: Checked: Drawn:
Drawing Number:
Building Number:
Project Number:
Dwg. of
OFFICE OFCONSTRUCTIONAND FACILITIESMANAGEMENT
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
BID DOCUMENTS
LIGHTING FIXTURE SCHEDULE AND DETAILS CONSTRUCT DOM CLINIC
AND CLC ADMINISTRATION
ADDITION
MARTINSBURG, WV
EL601
613-121
June 27, 2018 CEN SBC
LIGHTING FIXTURE SCHEDULE
TYPE DESCRIPTION MANUFACTURER MODEL NO.LAMPS
VOLTAGE WATTSMOUNTING
NOTESNO. TYPE TYPE HEIGHT
A1 RECESSED 2X4 LED CENTERANGLED PRISMATIC LENS,NOMINAL 5500 LUMENOUTPUT, 3500K CCT,ELECTRONIC DIMMABLEDRIVER
COLUMBIALIGHTING
OR APPROVEDEQUAL
LCAT24-35HLG-EDU 1 LED 277 V 48 W RECESSEDCEILING
A2 RECESSED 2X4 LED CENTERANGLED PRISMATIC LENS,NOMINAL 4800 LUMENOUTPUT, 3500K CCT,ELECTRONIC DIMMABLEDRIVER
COLUMBIALIGHTING
OR APPROVEDEQUAL
LCAT24-35MLG-EDU 1 LED 277 V 40 W RECESSEDCEILING
B RECESSED 2X2 LED CENTERANGLED PRISMATIC LENS,NOMINAL 2700 LUMENOUTPUT, 3500K CCT,ELECTRONIC DIMMABLEDRIVER
COLUMBIALIGHTING
OR APPROVEDEQUAL
LCAT22-35LWG-EDU 1 LED 277 V 23 W RECESSEDCEILING
C RECESSED 2X2 LED CENTERANGLED PRISMATIC LENS,NOMINAL 4398 LUMENOUTPUT, 3500K CCT,ELECTRONIC DIMMABLEDRIVER
COLUMBIALIGHITNG
LCAT22-35VLG-EDU 1 LED 277 V 39 W RECESSEDCEILING
D1 6" RECESSED DOWNLIGHT,FROSTED ACRYLIC LENS,NOMINAL 2000 LUMENOUTPUT, 3500K CCT,ELECTRONIC DIMMABLEDRIVER
PRESCOLITEOR APPROVED
EQUAL
LF6ML-6LFML30L35KDL 1 LED 277 V 36 W RECESSEDCEILING
D2 6" RECESSED DOWNLIGHT,FROSTED ACRYLIC LENS,NOMINAL 1300 LUMENOUTPUT, 3500K CCT,ELECTRONIC DIMMABLEDRIVER
PRESCOLITEOR APPROVED
EQUAL
LF6SL-6LFSL15L35KDL 1 LED 277 V 19 W RECESSEDCEILING
P1 1X4 PENDANT LED UTILITYCHANNEL, FROSTEDACRYLIC LENS, NOMINAL2500 LUMEN OUTPUT, 3500KCCT, ELECTRONIC DRIVER
COLUMBIALIGHTING
OR APPROVEDEQUAL
LCL4-35VL-EDU 1 LED 277 V 84 W PENDANT
P2 CIRCULAR 24" DIAMETERINDIRECT / DIRECT LEDPENDANT WITH OPENCENTER, EXTRUEDALUMINUN HOUSING WITHACRYLIC LENS, 3500K CCT,ELECTRONIC DIMMABLEDRIVER
OCLOR APPROVED
EQUAL
TW1-P1XX-24-MW-BAL-LED235K-UNV-DM1
1 LED 277 V 95 W PENDANT
X1 WALL MOUNT EXIT SIGN,THIN DIE-CAST ALUMINUMHOUSING, RED LETTERING,NUMBER OF DIRECTIONALCHEVRONS, FACES, ANDMOUNTING AS INDICATED ONPLANS, WHITE TRIM FINISH,ELECTRONIC DRIVER
DUAL LITEOR APPROVED
EQUAL
SE-R-BN LED 277 V 5 W UNIVERSAL
Z1 WALL MOUNTED FLOODLIGHT
HUBBELL WGH-225L-4K-U-L-PBT-234 1 LED 277 V 102 W SURFACE 9'
501D & 502F
12" = 1'-0"1
UL924 RELAY DETAIL
DNDNDN
DNCG CG
CG
CG
CG
CG
CGCGCG
CG
CG
CGCGCG
CG
CG
CGCG
CG
CG
CG
C-109
549 SQ. FT.
C-109A
132 SQ. FT.
C-110
181 SQ. FT.
CW-1
507 SQ. FT.
C-112
150 SQ. FT.
E-1
88 SQ. FT.
C-111
63 SQ. FT.
C-125
3,053 SQ. FT.
CC-4
368 SQ. FT.
ELECTRIC ROOM
GENERATOR ROOM
STAIR # 1
WALKWAY
SERVICE ELEVATORLOBBY
ELEV.
OXYGEN STORAGE
DINING
CORRIDOR
BIO
MED
233
ELEC R
OOM
235
SERVIC
E C
ORR.
SC-1
MULE S
TORAGE
238
UPDN.
F.E.C.
E VFC
E M E M
E M
E M E M
E M
E M
E M E M
E M
E M
E
E
E M
E M
J
E
E M E M E M
E M
E M
E E
E
E VFC E M
E M
E M
E M
E M
E M
E M
E M
E M
E M
E M
E M
E M
E M
E M
E M
E
E
E M
CG
E
M
E
M
501D-100
501D-110 501D-108501D-113
501D-112
501D-114501D-115
501D-107
501D-106
501D-109
501D-116
501D-111A
501D-111
501D-C2
501D-120
501D-128
501D-121
501D-103
501D-101
501D-122
501D-123501D-124
501D-125
501D-126
501D-102
501D-131
501D-130
501D-127
501D-129A
501D-129
501D-C3
501D-C4
501D-104
501D-105
501D-136
501D-C1
501D-C5
1
EP101
3
501C-125A
501D-117501D-118
501D-134501D-133
501D-132
501D-135501D-119
501D-LA1-17
501D-LA1-40
501D-LA1-12
501D-LA1-30
501D-LA1-31 501D-LA1-32
501D-LA1-33501D-LA1-34
501D-LA1-35
501D-LA1-36501D-LA1-37
501D-LA1-38501D-LA1-39
501D-LA1-29
501D-LA1-28
501D-LA1-11 501D-LA1-10
501D-LA1-9 501D-LA1-8 501D-LA1-7 501D-LA1-6 501D-LA1-5
501D-LA1-19
501D-LA1-4 501D-LA1-3
501D-LA1-14
501D-LA1-15501D-LA1-16
501D-LA1-21
501D-LA1-20
501D-LA1-18
501D-LA1-22501D-LA1-23
501D-LA1-24
501D-LA1-27
501D-LA1-26
501D-LA1-25
501D-LA1-2
501D-LT
501D-LT-1
501D-LT-2
501D-LT-3
501D-LT-4501D-LT-5,7,9
501D-LT-6,8,10
501D-LA1-41
KP-B-501
MDP-501EM-A
501D-LA1-1
2
101
303
304
501D-LA1-13
301 302
305
306
307
308
310311
309
401
512
C
C.2
C.4
F
G
G.5
H
I
K
1 3 3.1 3.4 4 4.8 5 6 7 8 9 10 11 12
414
4
4
4
4
5
6
7
501D-LA1-54
501D-LA1-44
501D-LA1-45
501D-LA1-46
490
502
491495 492 493
494
496 497
504
503
505
509
510
508
513
514
515
518
516
517
520
519
521
522
501D-LA1-48
8
540
541
546
548549
4.5
RE
B
B.5
5.3 6.5 7.5 9.7 9.8 9.9 10.58.4
A
501D-104
501D-LA1
501D-HA
501D-T-LA1
501D-T-LA2
501D-LA2501D-LA1-433
C
C.2
C.4
11 1210.5
TRUE
NORTH
PLAN
NORTH
488
535
thre
e in
ches
= o
ne fo
ot6"
Department ofVeterans Affairs
one
and
one
half
inch
es =
one
foot
6"on
e in
ch =
one
foot
thre
e qu
arte
rs in
ch =
one
foot
one
half
inch
= o
ne fo
ot0
thre
e ei
ghth
s in
ch =
one
foot
0on
e qu
arte
r in
ch =
one
foot
0on
e ei
ghth
inch
= o
ne fo
ot0
10
6"0
26"
02
44
48
48
16
VA FORM 08-6231
Revisions:
1 2 3 4 5 6 7 8 9
Date:
CONSULTANTS: ARCHITECT/ENGINEERS:
590 MEANS ST NW ATLANTA, GA 30318
Drawing Title:
Approved Project Director:
Project Title:
Location:
Date: Checked: Drawn:
Drawing Number:
Building Number:
Project Number:
Dwg. of
OFFICE OFCONSTRUCTIONAND FACILITIESMANAGEMENT
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
BID DOCUMENTS
FIRST FLOOR POWER PLAN - CLC ADMIN CONSTRUCT DOM CLINIC
AND CLC ADMINISTRATION
ADDITION
MARTINSBURG, WV
EP101
613-121
June 27, 2018 CEN SBC
1/8" = 1'-0"1
FIRST FLOOR POWER PLAN - CLC ADMIN
GENERAL NOTES
KEY NOTES
GRAPHIC SCALE(S)
1/8" = 1' - 0"0 5' 10' 15' 30'
1 ROUTE (2) 3" CONDUITS OVERHEAD TO EXISTING PANELMDP-501 IN ELECTRICAL RM. C109 FROM NEWELECTRICAL RM. 501D-104.
2 PROVIDE NEW 225A BREAKER IN PANEL MDP-501 TOSERVE NEW PANEL 501D-HA. REFER TO RISER DIAGRAMON EP701 FOR ADDITIONAL INFORMATION.
3 ELECTRICAL GROUNDING BAR. BOND TO MAINGROUNDING BAR IN ELECTRICAL RM. C-109 WITH #4CONDUCTOR. SEE DETAIL 9, SHEET EP501
4 MOUNT RECEPTACLE 6" BELOW SINK.
5 EXISTING PANEL "BLDG 501 ELECTRONIC MONITORINGPANEL".
6 ROUTE 4#3,#8G;1-1/4"C TO PANEL EM IN ROOM C109.
7 INTERCEPT EXISTING CIRCUIT SERVING WOODENPAVILION. PROVIDE IN GRADE SPLICE BOX WITH SCREWON COVER WHERE CIRCUIT IS INTERCEPTED.
8 POWER FOR AUTOMATIC DOOR OPENER.
1/4" = 1' - 0"0 5' 10' 15'1'
1/4" = 1'-0"3
FIRST FLOOR ENLARGED
POWER PLAN - ELECTRICAL RM. 501D-104 - CLC ADMIN
CLC ROOM SCHEDULE
NUMBER NAME
501D-123 N. ADMIN.
501D-124 OFFICE/EXAM
501D-125 OFFICE/EXAM
501D-126 PROG. MAN.
501D-127 BUS. MAN.
501D-128 CUBICLES
501D-129 AD. ASST.
501D-129A STOR.
501D-130 SERV. CHIEF.
501D-131 ENTRANCE
501D-132 GUEST T.
501D-133 STAFF T.
501D-134 HAC
501D-135 STOR.
501D-136 LANDING
501D-C1 CORRIDOR
501D-C2 CORRIDOR
501D-C3 CORR. A
501D-C4 CORR. B
501D-C5 CONNECTORRAMP
CLC ROOM SCHEDULE
NUMBER NAME
501D-100 ENTRANCE
501D-101 IT
501D-102 MECHANICAL
501D-103 STORAGE
501D-104 ELECTRICAL
501D-105 CORR.
501D-106 WAITING
501D-107 ADMIN. SUPP.
501D-108 N. CASE MAN.
501D-109 OFF. / EX.
501D-110 OFF. / EX.
501D-111 OFF. / EX.
501D-111A STOR.
501D-112 OFF. / EX.
501D-113 N. CASE MAN.
501D-114 PSYCHOL.
501D-115 G. FELLOW
501D-116 G. FELLOW
501D-117 GUEST T.
501D-118 STAFF T.
501D-119 STOR.
501D-120 COPY /WORKROOM
501D-121 BREAK ROOM
501D-122 CONFERENCEROOM
#
501D
1/8" = 1'-0"2
EXTERIOR POWER PLAN - CLC ADMIN
MA
TC
HLIN
E A
MA
TC
HLIN
E A
MA
TC
HLIN
E A
MA
TC
HLIN
E A
CG
CG
CG
CG
CG
CG
CG
CG
CG
CG
CG
CG
CG
CG
CG
CG
CG
CG
CG
CG
CG
CG
CG
CG
CG
CG
CG
CG
FLOOR DRAIN
FLO
OR
DR
AIN
CORRIDOR
CORRIDORCD-4
CORRIDOR
CD-3CORRIDOR
OFFICE
OFFICE
D-85OFFICE
D-92ACOPIER
D-92OFFICE
D-90OFFICE
D-91OFFICE
D-89OFFICE
D-88OFFICE
D-87OFFICE
D-86OFFICE
D-84OFFICE
D-83STORAGE
CD-1CORRIDOR
NEW ELECTRICFIRE PLACE
E-138BMECH. RM.
E-138AELEC. RM.
E-138CTELE. RM.
E-138EMERGENCYGENERATOR
RAISED SLAB (TYP.)
RAISED SLAB (TYP.)
E-116REC. RM.
E-116AVENDING
E-116BSTORAGE
E-118PRIVATE DINING
RAISED SLAB (TYP.)
R SD SLB (TYP .)
RSD SLB (TYP.)
AP
E.W
.C.
E VFCE VFC
E M
E M
E M
E M
E M
E M
E M
E M E M E M
E M
E
E M
E M
E E M
E ME ME M
E M
E ME M
E M
E M
E M
E M
E M
E M
E M
E
E M
E
E M
E VFC
E VFC
P.T.S.E-111
CLOSET& P.T.S.
E-123OFFICE
502F-105
502F-118502F-116
502F-124
502F-120
502F-114
502F-C1
502F-110
502F-101
502F-103
502F-107
502F-106
502F-113 502F-115 502F-117
502F-119
502F-121
502F-122
502F-123
502F-125
502F-127
502F-C2
502F-129502F-126
502F-128
502F-130
502F-111
502F-109
502F-108
502F-104502F-102
502F-100
EP102
3
1
502F-112
502F-LA1-13
502F-LA1-12
502F-LA1-14502F-LA1-15
502F-LA1-16
502F-LA1-19502F-LA1-18 (SC)
502F-LA1-11 502F-LA1-8 502F-LA1-9 502F-LA1-6
502F-LA1-5
502F-LA1-4
502F-LA1-3
502F-LA1-2
502F-LA1-7
502F-LA1-1
502F-LA1-10502F-LA1-17
502F-LA1-22
502F-LA1-30
502F-LA1-28
502F-LA1-27
502F-LA1-26502F-LA1-25
502F-LA1-24502F-LA1-23
502F-LT
502F-LT-3
502F-LT-5,7,9
502F-LT-4
502F-LT-6,8,10
502F-LT-2
502F-LT-1
MDP-502
EM-502
502F-LA1-18 (SC)
3
2
4
502F-LA1-29102
402
312
313
314
318 320
321
316
317
315
322
319
511
501
FF EE DD CC BB AA
20
21
21.4
22
23
6
6
6
6
6
6
502F-LA1-32 502F-LA1-33
502F-LA1-34
502F-LA1-20
502F-LA1-21
415
313
317
507
506
523
524
525
526527 528
529
530
531
532
533
502F-LA1-35
502F-LA1-36
7
536
537
544
MSP
552
553
8
8
502F-130
502F-HA
502F-LA1
502F-T-LA1
502F-LS
502F-LA1-31
502F-T-LA2
502F-LA2
20
21
5
TRUENORTH
PLANNORTH
CC
10
9
thre
e in
ches
= o
ne fo
ot6"
Department ofVeterans Affairs
one
and
one
half
inch
es =
one
foot
6"on
e in
ch =
one
foot
thre
e qu
arte
rs in
ch =
one
foot
one
half
inch
= o
ne fo
ot0
thre
e ei
ghth
s in
ch =
one
foot
0on
e qu
arte
r in
ch =
one
foot
0on
e ei
ghth
inch
= o
ne fo
ot0
10
6"0
26"
02
44
48
48
16
VA FORM 08-6231
Revisions:
1 2 3 4 5 6 7 8 9
Date:
CONSULTANTS: ARCHITECT/ENGINEERS:
590 MEANS ST NW ATLANTA, GA 30318
Drawing Title:
Approved Project Director:
Project Title:
Location:
Date: Checked: Drawn:
Drawing Number:
Building Number:
Project Number:
Dwg. of
OFFICE OFCONSTRUCTIONAND FACILITIESMANAGEMENT
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
BID DOCUMENTS
FIRST FLOOR POWER PLAN - DOM CLINIC CONSTRUCT DOM CLINIC
AND CLC ADMINISTRATION
ADDITION
MARTINSBURG, WV
EP102
613-121
June 27, 2018 CEN SBC
1/8" = 1'-0"1
FIRST FLOOR POWER PLAN - DOM CLINIC
KEY NOTES
GRAPHIC SCALE(S)
1/8" = 1' - 0"0 5' 10' 15' 30'
1/4" = 1' - 0"0 5' 10' 15'1'
1 ROUTE (2) 3" CONDUITS UNDERGROUND TO MAINELECTRICAL RM. E-138A FROM NEW ELECTRICAL RM.502F-130. ONE CONDUIT FOR FEEDER AND ONE SPARE.PROVIDE LB FITTING AS LOW AS POSSIBLE TO TURN INTOEXISTING ELECTRICAL ROOM E-138A. REFER TO RISERDIAGRAM ON EP701 FOR ADDITIONAL INFORMATION.
2 ROUTE (2) 1" CONDUITS UNDERGROUND TO MAINELECTRICAL RM. E-138A FROM NEW ELECTRICAL RM.502F-130. ONE CONDUIT FOR FEEDER AND ONE SPARE.PROVIDE LB FITTING AS LOW AS POSSIBLE TO TURN INTOEXISTING ELECTRICAL ROOM E-138A. REFER TO RISERDIAGRAM ON EP701 FOR ADDITIONAL INFORMATION.
3 REPLACE 200A SPARE BREAKER IN PANEL MDP-502 WITHNEW 225A BREAKERTO SERVE NEW PANEL 502F-HA.REFER TO RISER DIAGRAM ON EP701 FOR ADDITIONALINFORMATION.
4 PROVIDE NEW 50A BREAKER IN PANEL EM-502.TO SERVENEW PANEL 502F-LS. REFER TO RISER DIAGRAM ON EP701FOR ADDITIONAL INFORMATION.
5 ELECTRICAL GROUNDING BAR. BOUND TO MAINGROUNDING BAR IN ELECTRICAL RM. E-138A WITH #4CONDUCTOR. SEE DETAIL 9, SHEET EP501
6 MOUNT RECEPTACLE 6" BELOW SINK.
7 PROVIDE POWER TO ENTRY GATE AT ROADAPPROXIMATELY 100 FEET AWAY.
8 EXISTING PUMP AT THIS LOCATION TO BE REPLACED.REMOVE EXISTING DISCONNECT AND FEEDER BACK TOPANEL MSP. REPLACE EXISTING BREAKER IN PANEL MSPSERVING THIS PIECE OF EQUIPMENT WITH A NEW 50A/3PBREAKER. VERIFY BREAKER MANUFACTURER AND FRAMESIZE PRIOR TO ORDERING. PROVIDE 3#6, #10G; 1 1/4"CFROM NEW 50A/3P BREAKER IN PANEL MSP TO NEWCHILLED WATER PUMP.
9 PROVIDE 2#12,#12G,3/4"C. FROM RECEPTACLE TO NEAREST120V PANEL IN ROOM E-131 AND CONNECT TO SPARE20A1P BREAKER. ROOM E-131 IS APPROXIMATLEY 40 FEETAWAY FROM THIS SPACE.
10 PROVIDE ONE CAT 6 CALBE TO NEAREST PATCH PANEL INROOM E-112 AND TEST CABLE. ROOM E-112 ISAPPROXIMATLEY 130 FEET AWAY FROM THIS SPACE.
1/4" = 1'-0"3
ELECTRICAL RM. 502F-130 - DOM CLINIC
DOM ROOM SCHEDULE
NUMBER NAME
502F-115 DOM STAFFSCREENER
502F-116 REC. THER.
502F-117 DOM SUPV. SCREEN.
502F-118 DIETICIAN
502F-119 PEER SUPP.
502F-120 IT
502F-121 SOC. WORK.
502F-122 HAC
502F-123 MANAGER
502F-124 STAFF T.
502F-125 PSYCH.
502F-126 PA OFFICE
502F-127 PSYCH.
502F-128 MECHANICAL
502F-129 PSYCH.
502F-130 ELECT
502F-C1 CORR. A
502F-C2 CORR. B
DOM ROOM SCHEDULE
NUMBER NAME
502F-100 LOBBY
502F-101 PAT. T.
502F-102 CHECK IN
502F-103 WAITING
502F-104 TRIAGE
502F-105 N. STATION
502F-105A STOR.
502F-106 MEDS
502F-107 N. STATION
502F-107A STOR.
502F-108 N. ASSESS.
502F-109 N. ASSESS.
502F-110 VESTIBULE
502F-111 SPEC. VEST.
502F-112 SPEC. T.
502F-113 DOM SCREENINGCLERK
502F-114 N. ASSESS.
#
502F
1/4" = 1'-0"2
ELECTRICAL
CLOSET E111 - DOM CLINIC
C-109
549 SQ. FT.
C-110
181 SQ. FT.
CW-1
507 SQ. FT.
C-112
150 SQ. FT.
E-1
88 SQ. FT.
C-125
3,053 SQ. FT.
ELECTRIC ROOM
STAIR # 1
WALKWAY
SERVICE ELEVATORLOBBY
ELEV.
DINING
BIO
MED
233
SERVIC
E C
ORR.
SC-1
MULE S
TORAGE
238
E
A A
A
A
A
A
AA
A
AAAA
A
A A A AA
A A
AAA
A
A
A
A
A
A
A A A
A
A A
A
A A A A
A
J
EE E
CD-4CORRIDOR
CD-3CORRIDOR
D-90OFFICE
D-88OFFICE
D-86OFFICE
D-84OFFICE
D-83STORAGE
CD-1CORRIDOR
AP
A
A A
AA A A A A
A
AA A A A
A
A
A
A A A
A
AAA
AAA
601
C
C.2
C.4
F
G
G.5
H
I
K
1 3 3.1 3.4 4 4.8 5 6 7 8 9 10 11 12
G
R
G G
R R
G
G
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R R
R R
R
R
R
RR
R
RR
RRR
RR
R R R R
R
R RRRR
R
R
R
R R
G
G
G
G G
G
G
G
G
G
G
G
G
R
D
D
D
D
D
D
D
D
D D
D D D D D
D
D
R
G
G
R
RG
2
2
1
1
G3
1
1
2
2
3
G GG
G
500499498
4.5
RE
B
B.5
5.3 6.5 7.5 9.7 9.8 9.9 10.58.4
A
23
22
21.4
21
20
AABBCCDDEEFF
FF EE DD CC BB AA
20
21
21.4
22
23
DD
D D
D D D
DDD
DD
G
G
G
G
G G
G
G
GG
G
G
RR
R
R R
R
R R R R
R
R
R
RRRR
R
RRR
R
R
R R
R
R
R
R
R
R
R
R
1
2
G
3
1
G
G
R
R
2
TRUE
NORTH
PLAN
NORTH
TRUE
NORTH
PLAN
NORTH
thre
e in
ches
= o
ne fo
ot6"
Department ofVeterans Affairs
one
and
one
half
inch
es =
one
foot
6"on
e in
ch =
one
foot
thre
e qu
arte
rs in
ch =
one
foot
one
half
inch
= o
ne fo
ot0
thre
e ei
ghth
s in
ch =
one
foot
0on
e qu
arte
r in
ch =
one
foot
0on
e ei
ghth
inch
= o
ne fo
ot0
10
6"0
26"
02
44
48
48
16
VA FORM 08-6231
Revisions:
1 2 3 4 5 6 7 8 9
Date:
CONSULTANTS: ARCHITECT/ENGINEERS:
590 MEANS ST NW ATLANTA, GA 30318
Drawing Title:
Approved Project Director:
Project Title:
Location:
Date: Checked: Drawn:
Drawing Number:
Building Number:
Project Number:
Dwg. of
OFFICE OFCONSTRUCTIONAND FACILITIESMANAGEMENT
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
BID DOCUMENTS
ROOF POWER, LIGHTNING PROTECTION, AND
GROUNDING PLANS - CLC ADMIN AND DOM
CLINIC
CONSTRUCT DOM CLINIC
AND CLC ADMINISTRATION
ADDITION
MARTINSBURG, WV
EP103
613-121
June 27, 2018 CEN SBC
1/8" = 1'-0"1
ROOF POWER, LIGHTNING PROTECTION, AND GROUNDING - CLC ADMIN
1/8" = 1'-0"2
ROOF POWER, LIGHTNING PROTECTION, AND GROUNDING - DOM CLINIC
GENERAL NOTES
KEY NOTES
GRAPHIC SCALE(S)
1/8" = 1' - 0"0 5' 10' 15' 30'
#
501D & 502F
1 BOND GROUND RING TO EXISTING GROUND RING.
2 BOND ROOF CONDUCTOR GRID TO EXISTING BUILDINGLIGHTING PROTECTION.
3 PROVIDE GROUND CONNECTION TIE IF NO EXISTINGGROUND RING.
1. PROVIDE UL MASTER LABEL RE-CERTIFYING THIS BUILDING ADDITION INTOTHE MAIN BUILDING LIGHNING PROTECTION UL MASTER LABEL.
2. LOCATION OF AIR TERMINALS AS SHOWN IS DIAGRAMMATIC ONLY. ENSURETHAT TERMINALS ARE WITHIN 2'-0" OF OUTSIDE EDGE AND OUTSIDECORNERS, AND MAXIMUM SPACING DOES NOT EXCEED 20'-0";
3. MAINTAIN HORIZONTAL OR DOWNWARD COURSING OF MAIN CONDUCTORAND ENSURE THAT BENDS HAVE AT LEAST 8" RADIUS AND DO NOT EXCEED90o.
4. ATTACH EXPOSED ROOF, DOWN AND BONDING CONDUCTORS AT 3'-0" ONCENTER MAXIMUM. VERIFY COMPATIBILITY OF ADHESIVE ON MEMBRANEROOF APPLICATIONS WITHOUT VOIDING ROOF WARRANTY, PRIOR TOINSTALLATION.
5. BOND TO METALLIC WATER SERVICE AND OTHER METALLIC PIPINGSYSTEMS AS REQUIRED BY CODES.
6. INTERCONNECT LIGHTNING PROTECTION GROUND TO THE ELECTRICALAND OTHER BUILDING GROUND SYSTEMS AS REQUIRED BY CODE.
7. INSTALL TO ENSURE PROPER CODE COMPLIANCE AND SYSTEMCERTIFICATION.
8. MATERIAL TO BE UNDERWRITER'S LABORATORIES APPROVED WITHLABELS ON CONDUCTORS AT 10'-0" INTERVALS AND LABELS ON AIRTERMINALS.
9. COMPLETED INSTALLATION SHALL BEAR U.L. MASTER LABEL, WHICH SHALLBE SECURED BY SYSTEM INSTALLER PER UL96.
10. ON HINGED EXHAUST HOODS, CONDUCTORS SHALL BE ROUTED NEXT TOHINGES TO ALLOW OPENING OF EXHAUST HOODS WITHOUT REMOVINGLIGHTNING PROTECTION CONDUCTORS. ON EXHAUST FAN HOODS THATARE REMOVABLE, ROUTE CONDUCTORS TO ALLOW REMOVAL OF HOOD.
11. CONDUCTORS, BONDING PLATES AND AIR TERMINALS SHALL BEARRANGED SO THAT COVERS AND ACCESS TO EQUIPMENT SHALL NOT BERESTRICTED.
12. BOND ALL VENTS, DRAINS, PIPING AND METAL COMPONENTS TO THELIGHTNING PROTECTION SYSTEM.
13. THE LIGHTNING PROTECTION SYSTEM LAYOUT AS SHOWN IS INTENDED TODEPICT THE AREA OF COVERAGE, BUT IS NOT REPRESENTATIVE OF ALLCOMPONENTS REQUIRED. THE LIGHTNING PROTECTION SYSTEMDESIGNER/INSTALLER SHALL BE RESPONSIBLE FOR PROVIDING ACOMPLETE SYSTEM TO MEET UL96 AND NFPA 780 REQUIREMENTS.
14. REFER TO DETAILS ON THIS SHEET AND SHEET EP501.
DNDNDN
DNCG CG
CG
CG
CG
CG
CGCG
CG
FF
F
F
F
CR
E ME M
E
E
E E
C
C.2
C.4
F
G
G.5
H
I
K
1 3 3.1 3.4 4 4.8 5 6 7 8 9 10 11 12
501D-136
501D-C1
501D-C5
X1
X1
501D-HA-13
501D-LA1-56
1 2 3
1 2 3 1 2 3
1 2 3
1 2 3
1 2 3
1 2 3
1 2 3
1 2 31 2 3
1 2 3
1 2 3
4
560
559
562
558
561
563
P1 P1P1
P1 P1P1
P1 P1P1
P1 P1
P1
P1
P1
P1
P1
P1
P1
P1
P1
P1
P1
P1
P1
P1
P1
P1
P1
4.5
RE
B
B.5
5.3 6.5 7.5 9.7 9.8 9.9 10.58.4
A
thre
e in
ches
= o
ne fo
ot6"
Department ofVeterans Affairs
one
and
one
half
inch
es =
one
foot
6"on
e in
ch =
one
foot
thre
e qu
arte
rs in
ch =
one
foot
one
half
inch
= o
ne fo
ot0
thre
e ei
ghth
s in
ch =
one
foot
0on
e qu
arte
r in
ch =
one
foot
0on
e ei
ghth
inch
= o
ne fo
ot0
10
6"0
26"
02
44
48
48
16
VA FORM 08-6231
Revisions:
1 2 3 4 5 6 7 8 9
Date:
CONSULTANTS: ARCHITECT/ENGINEERS:
590 MEANS ST NW ATLANTA, GA 30318
Drawing Title:
Approved Project Director:
Project Title:
Location:
Date: Checked: Drawn:
Drawing Number:
Building Number:
Project Number:
Dwg. of
OFFICE OFCONSTRUCTIONAND FACILITIESMANAGEMENT
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
BID DOCUMENTS
FIRST FLOOR ELECTRICAL PLAN - CLC ADMIN -ALTERNATE NO. 5 - (BID ITEM NO. 6)
CONSTRUCT DOM CLINIC
AND CLC ADMINISTRATION
ADDITION
MARTINSBURG, WV
EP104
613-121
June 27, 2018 Checker Author
GENERAL NOTES
KEY NOTES
GRAPHIC SCALE(S)
1/8" = 1' - 0"0 5' 10' 15' 30'
#
A. PROVIDE A UL924 DEVICE FOR EACH EMERGENCY LIGHTFIXTURE. REFER TO UL924 RELAY DETAIL ON EL601.
1 SEE SHEET EL101 FOR LIGHTING WORK IN THIS AREA.
2 SEE SHEET EP103 FOR POWER WORK IN THIS AREA.
3 SEE SHEET EY101 FOR TELECOMMUNICATIONS WORK INTHIS AREA.
4 ROUTE 2#12,#12G,3/4" CONDUIT TO PANEL "EM-A" INELECTIRCAL ROOM C-109A. REFER TO EP101 FORLOCATION OF PANEL.
1/8" = 1'-0"1
FIRST FLOOR - CLC ADMIN - ALTERNATE NO. 5 (BID ALTERNATE NO. 6)
501D
GENTLY TAPEREDSOLID AIRTERMINAL
UNIVERSAL BASEMOUNTED WITHSTAINLESS STEELFASTENERS
CLASS I LIGHTNINGCONDUCTOR
CABLE CLIP WITHSTAINLESS STEELFASTENER - EVERY3" MAX.
AIR TERMINAL
FLAT SURFACE BASE
LIGHTNING CONDUCTOR
CADWELD "GR"
3/4" X 10'COPPERCLADGROUND ROD
CADWELD "VS"
28str X 14GaBARE Cu CONDUCTOR
1" SCHEDULE 80 PVC CONDUITBY ELECTRICAL CONTRACTOR
CLASS I COPPERLIGHTNINGCONDUCTOR
EXOTHERMIC CONNECTION
EXOTHERMIC CONNECTION
EXOTHERMIC CONNECTION
CLASS I COPPERLIGHTNINGCONDUCTOR
3/4" X 10' COPPERCLAD GROUND ROD
EXOTHERMIC WELD
28str X 14GaBARE Cu CONDUCTOR
THROUGHROOF ASSEMBLY
FINAL THRU-ROOFFLASHING BYROOFINGCONTRACTOR
GROUND
PULL SLOT(2 PLACES)
COVER27" DIA.
.36"
TOP OF COVER TOBE FLUSH WITHGRADE
GROUNDCONDUCTOR SIZEAS NOTED ONPLANS AND/ORSPECIFICATIONSCOPPER CLAD
GROUND ROD
CRUSHED ROCK
ERICO #T416A(INCLUDES COVER)
CADWELDCONNECTION
COVER MARKED"GROUND"
NOTES:1. TO IMPROVE SYSTEM RESISTANCE, ERICO®GEM MAY BE USED AS A BACKFILLMATERIAL IN AN AUGERED HOLE.
tm
CADWELD TYPE GT STONE BACKFILL IFIN A SUBSTATION
BAR COPPERCONDUCTOR TONEXT ROD (TYP)
EARTH BACKFILL
GROUND ROD
GEM FILLDIAMETERASSPECIFIEDORCALCULATED PER JOB
GROUND ROD
EXOTHERMIC WELD CONNECTION
LIGHTNING CONDUCTOR
LEGEND
1 - COPPER GROUND BAR, 1/4" X 4"X-", NEWTON INSTRUMENT CO. CAT. NO. B-6142. HOLE CENTERS TO MATCH NEMA DOUBLE LUG CONFIGURATION2 - INSULATORS, NEWTON INSTRUMENT CAT. NO. 3061-43 - 5/8" LOCKWASHERS, NEWTON INSTRUMENT CO. CAT. NO. 3015-84 - 5/8-11 X 1" H.H.C.S.BOLTS, NEWTON INSTRUMENT CO. CAT. NO. 3012-15 - APPLY COPPER NO-OX TO EXPOSED AREA OF GROUND BARS
3
42
1
1"
7/16"3/4"
2"
GRADE
WEATHERPROOFFLEXIBLE CONDUIT
MECHANICAL UNIT
COORDINATE LOCATION OFSTUB-UP WITH
CONDENSING UNITLOCATION
3"
MIN
IMU
M
CONCRETEPAD
12"
MIN
IMU
M
DISCONNECTSWITCH
CONDUIT ROUTEDTIGHT TO
STRUCTURE WITHSUPPORTS
TO MDP
thre
e in
ches
= o
ne fo
ot6"
Department ofVeterans Affairs
one
and
one
half
inch
es =
one
foot
6"on
e in
ch =
one
foot
thre
e qu
arte
rs in
ch =
one
foot
one
half
inch
= o
ne fo
ot0
thre
e ei
ghth
s in
ch =
one
foot
0on
e qu
arte
r in
ch =
one
foot
0on
e ei
ghth
inch
= o
ne fo
ot0
10
6"0
26"
02
44
48
48
16
VA FORM 08-6231
Revisions:
1 2 3 4 5 6 7 8 9
Date:
CONSULTANTS: ARCHITECT/ENGINEERS:
590 MEANS ST NW ATLANTA, GA 30318
Drawing Title:
Approved Project Director:
Project Title:
Location:
Date: Checked: Drawn:
Drawing Number:
Building Number:
Project Number:
Dwg. of
OFFICE OFCONSTRUCTIONAND FACILITIESMANAGEMENT
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
BID DOCUMENTS
ELECTRICAL DETAILS CONSTRUCT DOM CLINIC
AND CLC ADMINISTRATION
ADDITION
MARTINSBURG, WV
EP501
613-121
June 27, 2018 CEN SBC
NO SCALE1
AIR TERMINAL DETAILNO SCALE
2EXHUAST FAN LIGHTNING PROTECTION DETAIL
1 : 15
EXOTHERMIC WELD TO COLUMN DETAILNO SCALE
4GROUND ROD DETAIL
NO SCALE3
THROUGH ROOF DETAIL
NO SCALE8
GROUND ROD INSPECTION HOUSING DETAILNO SCALE
7GROUND ROUND BACKFILL DETAIL
NO SCALE6
GROUND ROD DETAIL
NO SCALE9
GROUND BAR DETAILNO SCALE
10CONDENSING UNIT CONNECTION DETAIL
NOTES(AIR TERMINAL DETAIL)A. REFER TO SPECIFICATIONS SECTION 26 41.00 FOR WHERE TO USE
COPPER OR ALUMINUM MATERIALS.
NOTES(EXHAUST FAN LIGHTNING PROTECTION DETAIL)A. REFER TO SPECIFICATIONS SECTION 26 41.00 FOR WHERE TO USE COPPER OR
ALUMINUM MATERIALS.
NEW PANEL 501D-HA SCHEDULE
CKT.
NO.135
791113
1517192123
25272931
33353739
41TOTAL AMPS (CONN. LOAD)TOTAL AMPS (FEEDTHRU)TOTAL AMPS (CONN. LOAD + FEED-THRU)PANELBOARD OPTIONS:
LOAD DESCRIPTIONLIGHTINGRECEPTACLESMECH EQUIP
ELECTRIC HEATMISCELLANEOUSELEVATORSHOW POWER
KITCHENAUDIO VISUALELECTRONICSDRYERS
TOTALS (CONN. KVA)TOTALS (CONN. KVA + 20%)TOTALS (CONN. AMPS)TOTALS (CONN. AMPS + 20%)
LOAD DESCRIPTIONLIGHTINGLIGHTINGLIGHTING
1-SH1
ALT LIGHTING
UH ALT
UH ALT
SPARESPARESPARE
SPARESPAREPANEL 501D-LA2FED VIA XFMR 501D-T-LA2 (75 KVA)
PANELCONN LOAD5.9
60.5
66.479.779.995.9
COND
SIZE3/43/43/4
3/4
3/4
*
*
1-1/2
KVAKVAKVA
KVAKVAKVAKVA
KVAKVAKVAKVA
KVAKVAKVA
AMPSAMPS
WIRE
SIZE3#123#123#12
4#12
3#12
*
*
1
SUBFEEDCONN LOAD
49.975.5
11.6
137.0164.4164.8197.8
BKR
TRIP202020
20
20
20
20
202020
2020125
A:A:A:
KVAKVAKVA
KVAKVAKVAKVA
KVAKVAKVAKVA
KVAKVAKVA
AMPSAMPS
AMPS6.97.92.6
11.911.911.94.0
13.013.013.013.013.0
13.0
96.089.5
87.0260.2
260.2
FEEDTHRUCONN LOAD
KVA1.92.20.7
3.33.33.31.1
3.63.63.63.63.6
3.6
26.624.8
24.1
KVAKVAKVA
KVAKVAKVAKVA
KVAKVAKVAKVA
KVAKVAKVA
AMPSAMPS
400 AMP BUS 300 AMP MCB 480Y/277 VOLTS 3PH, 4W, SN MIN. 35 KAIC SURFACE MOUNTED
PHA
BC
AB
CA
BC
AB
C
AB
CA
BC
AB
CB:B:B:
PANELBOARD NOTES:
* REFER TO MECHANICAL CONNECTION SCHEDULE ON EP701.** REFER TO FEEDER SCHEDULE ON EP701.
TOTALLOAD5.949.9136.0
11.6
203.5244.2244.7293.7
KVA1.31.31.3
0.10.10.13.6
3.63.63.63.63.6
1.01.01.0
22.319.6
21.1241.0
241.0
KVAKVAKVA
KVAKVAKVAKVA
KVAKVAKVAKVA
KVAKVAKVA
AMPSAMPS
AMPS4.84.84.8
0.50.50.513.0
13.013.013.013.013.0
3.63.63.6
80.570.8
76.2
D.F.MULT.
1.25NEC0.80
1.251.000.800.80
0.650.801.000.47
BKR
TRIP15
20
20
20
20
20
2020110
C:C:C:
TOTAL KVADEMAND7.430.0108.8
11.6
157.8189.4189.8227.8
WIRE
SIZE*
*
*
*
*
1
238.6
238.6
KVAKVAKVA
KVAKVAKVAKVA
KVAKVAKVAKVA
KVAKVAKVA
AMPSAMPS
COND
SIZE*
*
*
*
*
1-1/2
LOAD DESCRIPTIONAHU-1 (RM. 501D-102)
EF-3
UH ALT
UH ALT
1-RF-1
SPARE
SPARESPAREPANEL 501D-LA1FED VIA XFMR 501D-T-LA1 (75 KVA)
CKT.
NO.246
8101214
1618202224
26283032
34363840
42
NEW PANEL 501D-LA1 SCHEDULE
CKT.
NO.135
791113
1517192123
25272931
33353739
4143454749
51535557
59616365
676971
TOTAL AMPS (CONN. LOAD)TOTAL AMPS (FEEDTHRU)
TOTAL AMPS (CONN. LOAD + FEED-THRU)PANELBOARD OPTIONS:
LOAD DESCRIPTIONLIGHTING
RECEPTACLESMECH EQUIPELECTRIC HEATMISCELLANEOUS
ELEVATORSHOW POWERKITCHENAUDIO VISUALELECTRONICS
DRYERS
TOTALS (CONN. KVA)TOTALS (CONN. KVA + 20%)
TOTALS (CONN. AMPS)TOTALS (CONN. AMPS + 20%)
LOAD DESCRIPTIONRECEPTACLESRECEPTACLESRECEPTACLES
RECEPTACLESRECEPTACLESRECEPTACLESRECEPTACLES
RECEPTACLESRECEPTACLESRECEPTACLESRECEPTACLESRECEPTACLES
RECEPTACLESRECEPTACLESRECEPTACLESRECEPTACLES
RECEPTACLESRECEPTACLESRECEPTACLESRECEPTACLES
RECEPTACLESRECEPTACLESRECEPTACLESVEHICLE ENTRY GATE
VEHICLE ENTRY GATE
VEHICLE ENTRY GATE
SPARESPARESPARESPARE
SPARESPARESPARE
PANEL
CONN LOAD
31.2
11.6
42.851.4
118.9142.7
COND
SIZE3/43/43/4
3/43/43/43/4
3/43/43/43/43/4
3/43/43/43/4
3/43/43/43/4
3/43/43/4*
*
*
KVA
KVAKVAKVAKVA
KVAKVAKVAKVAKVA
KVAKVAKVAKVA
AMPSAMPS
WIRE
SIZE3#123#123#12
3#123#123#123#12
3#123#123#123#123#12
3#123#123#123#12
3#123#123#123#12
3#123#123#12
*
*
*
SUBFEED
CONN LOAD
18.7
18.722.5
52.062.4
BKR
TRIP202020
20202020
2020202020
20202020
20202020
20202020
20
20
20202020
202020A:A:
A:
KVA
KVAKVAKVAKVA
KVAKVAKVAKVAKVA
KVAKVAKVAKVA
AMPSAMPS
AMPS6.04.56.0
9.06.06.09.0
4.51.54.51.53.0
4.54.56.04.5
9.06.07.57.5
6.04.51.512.012.0
12.012.012.012.0
185.8
185.8
FEEDTHRU
CONN LOAD
KVA0.70.50.7
1.10.70.71.1
0.50.20.50.20.4
0.50.50.70.5
1.10.70.90.9
0.70.50.21.31.3
1.31.31.31.3
KVA
KVAKVAKVAKVA
KVAKVAKVAKVAKVA
KVAKVAKVAKVA
AMPSAMPS
225 AMP BUS 225 AMP MCB 208Y/120 VOLTS 3PH, 4W, SN MIN. 10 KAIC SURFACE MOUNTED
PHA
BC
AB
CA
BC
AB
C
AB
CA
BC
AB
CA
BC
A
BC
AB
CA
BC
AB
CB:B:
B:PANELBOARD NOTES:** REFER TO FEEDER SCHEDULE ON EP701.
TOTAL
LOAD
49.9
11.6
61.673.9
170.9205.0
KVA0.70.71.1
0.70.50.71.1
0.50.50.50.50.5
0.50.70.90.7
1.10.70.70.2
1.20.20.21.51.4
1.41.50.7
6.56.55.8
163.3
163.3
KVA
KVAKVAKVAKVA
KVAKVAKVAKVAKVA
KVAKVAKVAKVA
AMPSAMPS
AMPS6.06.09.0
6.04.56.09.0
4.54.54.54.54.5
4.56.07.56.0
9.06.06.01.5
10.01.51.512.512.0
12.012.56.0
54.054.048.0
D.F.
MULT.1.25
NEC0.801.251.00
0.800.800.650.801.00
0.47
BKR
TRIP202020
20202020
2020202020
20202020
20202020
2020202020
202020
20202020
100
C:C:
C:
TOTAL KVA
DEMAND
30.0
11.6
41.649.9
115.5138.6
WIRE
SIZE3#123#123#12
3#123#123#123#12
3#123#123#123#123#12
3#123#123#123#12
3#123#123#123#12
*3#123#123#12
*
3#123#12
175.8
175.8
KVA
KVAKVAKVAKVA
KVAKVAKVAKVAKVA
KVAKVAKVAKVA
AMPSAMPS
COND
SIZE3/43/43/4
3/43/43/43/4
3/43/43/43/43/4
3/43/43/43/4
3/43/43/43/4
*3/43/43/4*
3/43/4
LOAD DESCRIPTIONRECEPTACLESRECEPTACLESRECEPTACLES
RECEPTACLESRECEPTACLESRECEPTACLESRECEPTACLES
RECEPTACLESRECEPTACLESRECEPTACLESRECEPTACLESRECEPTACLES
RECEPTACLESRECEPTACLESRECEPTACLESRECEPTACLES
RECEPTACLESRECEPTACLESRECEPTACLESRECEPTACLES
LIFTRECEPTACLESRECEPTACLESRECEPTACLESVEHICLE ENTRY GATE
WOODEN PAVILIONALT RECEPTACLESSPARE
SPARESPARESPARESPARE
PANEL 501D-LT
CKT.
NO.246
8101214
1618202224
26283032
34363840
4244464850
52545658
60626466
687072
NEW PANEL 501D-LA2 SCHEDULE
CKT.
NO.135
79
1113
1517192123
25272931
33353739
4143454749
5153
TOTAL AMPS (CONN. LOAD)TOTAL AMPS (FEEDTHRU)
TOTAL AMPS (CONN. LOAD + FEED-THRU)PANELBOARD OPTIONS:
LOAD DESCRIPTIONLIGHTING
RECEPTACLESMECH EQUIPELECTRIC HEATMISCELLANEOUS
ELEVATORSHOW POWERKITCHENAUDIO VISUALELECTRONICS
DRYERS
TOTALS (CONN. KVA)TOTALS (CONN. KVA + 20%)
TOTALS (CONN. AMPS)TOTALS (CONN. AMPS + 20%)
LOAD DESCRIPTIONTANKLESS WATER HEATER
TANKLESS WATER HEATER
TANKLESS WATER HEATER
TANKLESS WATER HEATER
TANKLESS WATER HEATER
TANKLESS WATER HEATER
TANKLESS WATER HEATER
CU-7/AC-7
CU-4/AC-4
VAV'SCU-8/AC-8
UH-1SPARESPARE
SPARE
PANEL
CONN LOAD
75.5
75.590.6
209.5251.4
COND
SIZE*
*
*
*
*
*
*
*
*
**
*
KVA
KVAKVAKVAKVA
KVAKVAKVAKVAKVA
KVAKVAKVAKVA
AMPSAMPS
WIRE
SIZE*
*
*
*
*
*
*
*
*
**
*
SUBFEED
CONN LOAD
BKR
TRIP25
25
25
25
25
25
25
30
30
2030
202020
20
A:A:
A:
KVA
KVAKVAKVAKVA
KVAKVAKVAKVAKVA
KVAKVAKVAKVA
AMPSAMPS
AMPS16.816.816.8
16.816.816.816.8
16.816.816.816.816.8
16.816.825.025.0
25.025.010.07.5
7.50.8
221.6
221.6
FEEDTHRU
CONN LOAD
KVA1.81.81.8
1.81.81.81.8
1.81.81.81.81.8
1.81.82.62.6
2.62.61.20.9
0.90.1
KVA
KVAKVAKVAKVA
KVAKVAKVAKVAKVA
KVAKVAKVAKVA
AMPSAMPS
400 AMP BUS 300 AMP MCB 208Y/120 VOLTS 3PH, 4W, SN MIN. 10 KAIC SURFACE MOUNTED
PHA
BC
AB
CA
BC
AB
C
AB
CA
BC
AB
CA
BC
A
BC
B:B:
B:PANELBOARD NOTES:* REFER TO MECHANICAL CONNECTION SCHEDULE ON EP701.
TOTAL
LOAD
75.5
75.590.6
209.5251.4
KVA0.90.9
2.62.61.81.8
1.81.81.81.81.8
1.81.81.82.6
2.62.62.61.2
1.4
206.6
206.6
KVA
KVAKVAKVAKVA
KVAKVAKVAKVAKVA
KVAKVAKVAKVA
AMPSAMPS
AMPS8.68.6
25.025.016.816.8
16.816.816.816.816.8
16.816.816.825.0
25.025.025.010.0
11.7
D.F.
MULT.1.25
NEC0.801.251.00
0.800.800.650.801.00
0.47
BKR
TRIP15
20
30
25
25
25
25
25
30
30
20
202030
20
C:C:
C:
TOTAL KVA
DEMAND
60.4
60.472.5
167.6201.1
WIRE
SIZE*
*
*
*
*
*
*
*
*
*
12
200.8
200.8
KVA
KVAKVAKVAKVA
KVAKVAKVAKVAKVA
KVAKVAKVAKVA
AMPSAMPS
COND
SIZE*
*
*
*
*
*
*
*
*
*
3/4
LOAD DESCRIPTIONCU-2/AC-2
SPARE
CU-6/AC-6
TANKLESS WATER HEATER
TANKLESS WATER HEATER
TANKLESS WATER HEATER
TANKLESS WATER HEATER
TANKLESS WATER HEATER
CU-3/AC-3
CU-5/AC-5
PMP-1 & PMP-2
ALT EF'SSPARESPARE
SPARE
CKT.
NO.246
8101214
1618202224
26283032
34363840
4244464850
5254
NEW PANEL 501D-LT SCHEDULE
CKT.NO.
1
3579
11
13151719
2123
TOTAL AMPS (CONN. LOAD)TOTAL AMPS (FEEDTHRU)
TOTAL AMPS (CONN. LOAD + FEED-THRU)PANELBOARD OPTIONS:
LOAD DESCRIPTIONLIGHTING
RECEPTACLESMECH EQUIPELECTRIC HEATMISCELLANEOUSELEVATOR
SHOW POWERKITCHENAUDIO VISUALELECTRONICS
DRYERS
TOTALS (CONN. KVA)TOTALS (CONN. KVA + 20%)TOTALS (CONN. AMPS)
TOTALS (CONN. AMPS + 20%)
LOAD DESCRIPTIONRECEPTACLE
RECEPTACLERECEPTACLE
SPARE
SPARESPARESPARESPARE
SPARESPARE
PANELCONN LOAD
18.7
18.722.552.0
62.4
CONDSIZE3/4
3/43/4
KVA
KVAKVAKVAKVAKVA
KVAKVAKVAKVA
KVAKVAKVAKVA
AMPS
AMPS
WIRESIZE12
1210
SUBFEEDCONN LOAD
BKRTRIP
20
2030
20
20202020
2020A:A:
A:
KVA
KVAKVAKVAKVAKVA
KVAKVAKVAKVA
KVAKVAKVAKVA
AMPS
AMPS
AMPS3.0
3.024.024.024.0
54.0
54.0
FEEDTHRUCONN LOAD
KVA0.4
0.42.92.92.9
KVA
KVAKVAKVAKVAKVA
KVAKVAKVAKVA
KVAKVAKVAKVA
AMPS
AMPS
100 AMP BUS 100 AMP MCB 208Y/120 VOLTS 3PH, 4W, SN MIN. 10 KAIC SURFACE MOUNTED
PHA
BC
AB
C
AB
CA
BC
B:B:
B:PANELBOARD NOTES:
TOTALLOAD
18.7
18.722.552.0
62.4
KVA0.4
0.42.92.92.9
54.0
54.0
KVA
KVAKVAKVAKVAKVA
KVAKVAKVAKVA
KVAKVAKVAKVA
AMPS
AMPS
AMPS3.0
3.024.024.024.0
D.F.MULT.
1.25
NEC0.801.251.000.80
0.800.650.801.00
0.47
BKRTRIP
20
2030
20
20202020
2020C:C:
C:
TOTAL KVADEMAND
14.4
14.417.239.9
47.8
WIRESIZE
12
1210
48.0
48.0
KVA
KVAKVAKVAKVAKVA
KVAKVAKVAKVA
KVAKVAKVAKVA
AMPS
AMPS
CONDSIZE3/4
3/43/4
LOAD DESCRIPTIONRECEPTACLE
RECEPTACLERECEPTACLE
SPARE
SPARESPARESPARESPARE
SPARESPARE
CKT.NO.
2
468
1012
14161820
2224
thre
e in
ches
= o
ne fo
ot6"
Department ofVeterans Affairs
one
and
one
half
inch
es =
one
foot
6"on
e in
ch =
one
foot
thre
e qu
arte
rs in
ch =
one
foot
one
half
inch
= o
ne fo
ot0
thre
e ei
ghth
s in
ch =
one
foot
0on
e qu
arte
r in
ch =
one
foot
0on
e ei
ghth
inch
= o
ne fo
ot0
10
6"0
26"
02
44
48
48
16
VA FORM 08-6231
Revisions:
1 2 3 4 5 6 7 8 9
Date:
CONSULTANTS: ARCHITECT/ENGINEERS:
590 MEANS ST NW ATLANTA, GA 30318
Drawing Title:
Approved Project Director:
Project Title:
Location:
Date: Checked: Drawn:
Drawing Number:
Building Number:
Project Number:
Dwg. of
OFFICE OFCONSTRUCTIONAND FACILITIESMANAGEMENT
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
BID DOCUMENTS
ELECTRICAL SCHEDULES CONSTRUCT DOM CLINIC
AND CLC ADMINISTRATION
ADDITION
MARTINSBURG, WV
EP601
613-121
June 27, 2018 CEN SBC
501D & 502F
CLC ADMIN PANEL SCHEDULES
501D-HA
501D-LA1
501D-LA2
501D-LT
NEW PANEL 502F-HA SCHEDULE
CKT.
NO.135
791113
1517192123
25272931
33353739
41TOTAL AMPS (CONN. LOAD)TOTAL AMPS (FEEDTHRU)TOTAL AMPS (CONN. LOAD + FEED-THRU)PANELBOARD OPTIONS:
LOAD DESCRIPTIONLIGHTINGRECEPTACLESMECH EQUIP
ELECTRIC HEATMISCELLANEOUSELEVATORSHOW POWER
KITCHENAUDIO VISUALELECTRONICSDRYERS
TOTALS (CONN. KVA)TOTALS (CONN. KVA + 20%)TOTALS (CONN. AMPS)TOTALS (CONN. AMPS + 20%)
LOAD DESCRIPTIONLIGHTINGLIGHTINGLIGHTING
2-SH1
EF-4
SPARESPARESPARE
SPARESPARESPARESPARE
SPARESPAREPANEL 502F-LA2FED VIA XFMR 502F-T-LA2 (75 KVA)
PANELCONN LOAD3.8
48.2
52.062.462.575.0
COND
SIZE3/43/43/4
3/4
*
**
KVAKVAKVA
KVAKVAKVAKVA
KVAKVAKVAKVA
KVAKVAKVA
AMPSAMPS
WIRE
SIZE3#123#123#12
4#12
*
**
SUBFEEDCONN LOAD
43.946.9
5.0
95.7114.9115.1138.2
BKR
TRIP202020
20
20
202020
20202020
2020110
A:A:A:
KVAKVAKVA
KVAKVAKVAKVA
KVAKVAKVAKVA
KVAKVAKVA
AMPSAMPS
AMPS5.54.83.3
11.911.911.91.1
1.11.1
61.054.1
54.2184.2
184.2
FEEDTHRUCONN LOAD
KVA1.51.30.9
3.33.33.30.3
0.30.3
16.915.0
15.0
KVAKVAKVA
KVAKVAKVAKVA
KVAKVAKVAKVA
KVAKVAKVA
AMPSAMPS
225 AMP BUS 225 AMP MCB 480Y/277 VOLTS 3PH, 4W, SN MIN. 35 KAIC SURFACE MOUNTED
PHA
BC
AB
CA
BC
AB
C
AB
CA
BC
AB
CB:B:B:
PANELBOARD NOTES:
* REFER TO MECHANICAL CONNECTION SCHEDULE ON EP701.** REFER TO FEEDER SCHEDULE ON EP701.
TOTALLOAD3.843.995.1
5.0
147.7177.2177.7213.2
KVA3.13.13.1
9.49.49.4
16.516.5
15.8176.6
176.6
KVAKVAKVA
KVAKVAKVAKVA
KVAKVAKVAKVA
KVAKVAKVA
AMPSAMPS
AMPS11.011.011.0
34.034.034.0
59.759.7
57.0
D.F.MULT.
1.25NEC0.80
1.251.000.800.80
0.650.801.000.47
BKR
TRIP20
60
20
2020202020
20202020
2020110
C:C:C:
TOTAL KVADEMAND4.726.976.1
5.0
112.7135.2135.5162.7
WIRE
SIZE*
*
**
172.4
172.4
KVAKVAKVA
KVAKVAKVAKVA
KVAKVAKVAKVA
KVAKVAKVA
AMPSAMPS
COND
SIZE*
*
**
LOAD DESCRIPTIONAHU-2 (RM. 502F-128)
RF-2 (RM. 502F-128)
SPARE
SPARESPARESPARESPARESPARE
SPARESPARESPARESPARE
SPARESPAREPANEL 502F-LA1FED VIA XFMR 502F-T-LA2 (75 KVA)
CKT.
NO.246
8101214
1618202224
26283032
34363840
42
NEW PANEL 502F-LA1 SCHEDULE
CKT.
NO.135
791113
1517192123
25272931
33353739
4143454749
5153
TOTAL AMPS (CONN. LOAD)TOTAL AMPS (FEEDTHRU)
TOTAL AMPS (CONN. LOAD + FEED-THRU)PANELBOARD OPTIONS:
LOAD DESCRIPTIONLIGHTING
RECEPTACLESMECH EQUIPELECTRIC HEATMISCELLANEOUSELEVATOR
SHOW POWERKITCHENAUDIO VISUALELECTRONICS
DRYERS
TOTALS (CONN. KVA)TOTALS (CONN. KVA + 20%)
TOTALS (CONN. AMPS)TOTALS (CONN. AMPS + 20%)
LOAD DESCRIPTIONRECEPTACLESRECEPTACLESRECEPTACLES
RECEPTACLESRECEPTACLESRECEPTACLESRECEPTACLES
RECEPTACLESRECEPTACLESRECEPTACLESRECEPTACLESRECEPTACLES
RECEPTACLESRECEPTACLESRECEPTACLESRECEPTACLES
RECEPTACLESUC REFERIGERATORVEHICLE ENTRY GATE
SPARESPARESPARESPARESPARE
SPARESPARE
PANELCONN LOAD
25.1
5.0
30.136.2
83.7100.4
COND
SIZE3/43/43/4
3/43/43/43/4
3/43/43/43/43/4
3/43/43/4
3/4*
KVA
KVAKVAKVAKVAKVA
KVAKVAKVAKVA
KVAKVAKVAKVA
AMPSAMPS
WIRE
SIZE121212
12121212
1212121212
121212
12*
SUBFEEDCONN LOAD
18.7
18.722.5
52.062.4
BKR
TRIP202020
20202020
2020202020
20202020
202020
2020202020
2020A:A:
A:
KVA
KVAKVAKVAKVAKVA
KVAKVAKVAKVA
KVAKVAKVAKVA
AMPSAMPS
AMPS6.06.06.0
6.07.56.03.0
3.06.07.51.56.0
7.56.06.0
8.012.012.0
137.8
137.8
FEEDTHRUCONN LOAD
KVA0.70.70.7
0.70.90.70.4
0.40.70.90.20.7
0.90.70.7
1.01.31.3
KVA
KVAKVAKVAKVAKVA
KVAKVAKVAKVA
KVAKVAKVAKVA
AMPSAMPS
225 AMP BUS 225 AMP MCB 208Y/120 VOLTS 3PH, 4W, SN MIN. 10 KAIC SURFACE MOUNTED
PHA
BC
AB
CA
BC
AB
C
AB
CA
BC
AB
CA
BC
A
BC
B:B:
B:PANELBOARD NOTES:** REFER TO FEEDER SCHEDULE ON EP701.
TOTALLOAD
43.9
5.0
48.958.6
135.6162.7
KVA0.70.70.9
0.91.30.40.4
1.10.70.20.21.3
0.70.50.71.1
0.91.51.31.3
6.5
6.55.8
137.8
137.8
KVA
KVAKVAKVAKVAKVA
KVAKVAKVAKVA
KVAKVAKVAKVA
AMPSAMPS
AMPS6.06.07.5
7.510.53.03.0
9.06.01.51.510.5
6.04.56.09.0
7.512.512.012.0
54.0
54.048.0
D.F.MULT.
1.25
NEC0.801.251.000.80
0.800.650.801.00
0.47
BKR
TRIP202020
20202020
2020202020
20202020
20202020
20202020100
C:C:
C:
TOTAL KVADEMAND
26.9
5.0
31.938.3
88.6106.4
WIRE
SIZE121212
12121212
1212121212
12121212
1212*
**
131.5
131.5
KVA
KVAKVAKVAKVAKVA
KVAKVAKVAKVA
KVAKVAKVAKVA
AMPSAMPS
COND
SIZE3/43/43/4
3/43/43/43/4
3/43/43/43/43/4
3/43/43/43/4
3/43/4*
**
LOAD DESCRIPTIONRECEPTACLESRECEPTACLESRECEPTACLES
RECEPTACLESRECEPTACLESRECEPTACLESRECEPTACLES
RECEPTACLESRECEPTACLESRECEPTACLESRECEPTACLESRECEPTACLES
RECEPTACLESRECEPTACLESRECEPTACLESRECEPTACLES
RECEPTACLESTUBE STATIONVEHICLE ENTRY GATE
SPARESPARESPARESPAREPANEL 502F-LT
CKT.
NO.246
8101214
1618202224
26283032
34363840
4244464850
5254
NEW PANEL 502F-LA2 SCHEDULE
CKT.
NO.135
79
1113
1517192123
25272931
33353739
41TOTAL AMPS (CONN. LOAD)TOTAL AMPS (FEEDTHRU)TOTAL AMPS (CONN. LOAD + FEED-THRU)PANELBOARD OPTIONS:
LOAD DESCRIPTIONLIGHTINGRECEPTACLESMECH EQUIP
ELECTRIC HEATMISCELLANEOUSELEVATORSHOW POWER
KITCHENAUDIO VISUALELECTRONICSDRYERS
TOTALS (CONN. KVA)TOTALS (CONN. KVA + 20%)TOTALS (CONN. AMPS)TOTALS (CONN. AMPS + 20%)
LOAD DESCRIPTIONTANKLESS WATER HEATER
TANKLESS WATER HEATER
TANKLESS WATER HEATER
TANKLESS WATER HEATER
TANKLESS WATER HEATER
TANKLESS WATER HEATER
TANKLESS WATER HEATER
CU-9/AC-9
SPARE
SPARE
PANELCONN LOAD
46.9
46.956.2130.1156.1
COND
SIZE*
*
*
*
*
*
*
*
KVAKVAKVA
KVAKVAKVAKVA
KVAKVAKVAKVA
KVAKVAKVA
AMPSAMPS
WIRE
SIZE*
*
*
*
*
*
*
*
SUBFEEDCONN LOAD
BKR
TRIP25
25
25
25
25
25
25
30
20
30
A:A:A:
KVAKVAKVA
KVAKVAKVAKVA
KVAKVAKVAKVA
KVAKVAKVA
AMPSAMPS
AMPS16.816.816.8
16.816.816.816.8
16.816.816.816.816.8
16.816.88.78.7
140.8
140.8
FEEDTHRUCONN LOAD
KVA1.81.81.8
1.81.81.81.8
1.81.81.81.81.8
1.81.80.90.9
KVAKVAKVA
KVAKVAKVAKVA
KVAKVAKVAKVA
KVAKVAKVA
AMPSAMPS
225 AMP BUS 225 AMP MCB 208Y/120 VOLTS 3PH, 4W, SN MIN. 10 KAIC SURFACE MOUNTED
PHA
BC
AB
CA
BC
AB
C
AB
CA
BC
AB
CB:B:B:
PANELBOARD NOTES:
* REFER TO MECHANICAL CONNECTION SCHEDULE ON EP701.
TOTALLOAD
46.9
46.956.2130.1156.1
KVA0.90.91.8
1.81.81.81.8
1.81.81.81.81.8
1.10.10.1
124.8
124.8
KVAKVAKVA
KVAKVAKVAKVA
KVAKVAKVAKVA
KVAKVAKVA
AMPSAMPS
AMPS8.78.716.8
16.816.816.816.8
16.816.816.816.816.8
9.20.60.8
D.F.MULT.
1.25NEC0.80
1.251.000.800.80
0.650.801.000.47
BKR
TRIP15
25
25
25
25
25
20202130
30
C:C:C:
TOTAL KVADEMAND
37.5
37.545.0104.1124.9
WIRE
SIZE*
*
*
*
*
*
***
125.0
125.0
KVAKVAKVA
KVAKVAKVAKVA
KVAKVAKVAKVA
KVAKVAKVA
AMPSAMPS
COND
SIZE*
*
*
*
*
*
***
LOAD DESCRIPTIONCI-1/AC-1
TANKLESS WATER HEATER
TANKLESS WATER HEATER
TANKLESS WATER HEATER
TANKLESS WATER HEATER
TANKLESS WATER HEATER
VAV'SEF-2UH-2SPARE
SPARE
CKT.
NO.246
8101214
1618202224
26283032
34363840
42
NEW PANEL 502F-LT SCHEDULE
CKT.
NO.135
79
1113
1517192123
TOTAL AMPS (CONN. LOAD)TOTAL AMPS (FEEDTHRU)TOTAL AMPS (CONN. LOAD + FEED-THRU)PANELBOARD OPTIONS:
LOAD DESCRIPTIONLIGHTINGRECEPTACLESMECH EQUIP
ELECTRIC HEATMISCELLANEOUSELEVATORSHOW POWERKITCHEN
AUDIO VISUALELECTRONICSDRYERS
TOTALS (CONN. KVA)TOTALS (CONN. KVA + 20%)TOTALS (CONN. AMPS)TOTALS (CONN. AMPS + 20%)
LOAD DESCRIPTIONRECEPTACLERECEPTACLERECEPTACLE
SPARESPARE
SPARESPARESPARESPARESPARE
PANELCONN LOAD
18.7
18.722.552.062.4
COND
SIZE3/43/43/4
KVAKVAKVA
KVAKVAKVAKVAKVA
KVAKVAKVAKVA
KVAKVA
AMPSAMPS
WIRE
SIZE121210
SUBFEEDCONN LOAD
BKR
TRIP202030
2020
2020202020
A:A:A:
KVAKVAKVA
KVAKVAKVAKVAKVA
KVAKVAKVAKVA
KVAKVA
AMPSAMPS
AMPS3.03.0
24.0
24.024.0
54.0
54.0
FEEDTHRUCONN LOAD
KVA0.40.42.9
2.92.9
KVAKVAKVA
KVAKVAKVAKVAKVA
KVAKVAKVAKVA
KVAKVA
AMPSAMPS
100 AMP BUS 100 AMP MCB 208Y/120 VOLTS 3PH, 4W, SN MIN. 10 KAIC SURFACE MOUNTED
PHA
BC
AB
CA
BC
AB
C
B:B:B:
PANELBOARD NOTES:
TOTALLOAD
18.7
18.722.552.062.4
KVA0.40.42.9
2.92.9
54.0
54.0
KVAKVAKVA
KVAKVAKVAKVAKVA
KVAKVAKVAKVA
KVAKVA
AMPSAMPS
AMPS3.03.024.0
24.024.0
D.F.MULT.
1.25NEC0.80
1.251.000.800.800.65
0.801.000.47
BKR
TRIP202030
2020
2020202020
C:C:C:
TOTAL KVADEMAND
14.4
14.417.239.947.8
WIRE
SIZE121210
48.0
48.0
KVAKVAKVA
KVAKVAKVAKVAKVA
KVAKVAKVAKVA
KVAKVA
AMPSAMPS
COND
SIZE3/43/43/4
LOAD DESCRIPTIONRECEPTACLERECEPTACLERECEPTACLE
SPARESPARE
SPARESPARESPARESPARESPARE
CKT.
NO.246
8101214
1618202224
NEW PANEL 502F-LS SCHEDULE
CKT.
NO.135
79
111315
17192123
TOTAL AMPS (CONN. LOAD)TOTAL AMPS (FEEDTHRU)TOTAL AMPS (CONN. LOAD + FEED-THRU)PANELBOARD OPTIONS:
1.
LOAD DESCRIPTIONLIGHTINGRECEPTACLESMECH EQUIPELECTRIC HEAT
MISCELLANEOUSELEVATORSHOW POWERKITCHEN
AUDIO VISUALELECTRONICSDRYERS
TOTALS (CONN. KVA)TOTALS (CONN. KVA + 20%)TOTALS (CONN. AMPS)TOTALS (CONN. AMPS + 20%)
LOAD DESCRIPTIONLIGHTINGSPARESPARE
SPARESPARESPARESPARESPARE
SPARESPARESPARESPARE
PROVIDE EXTERNALLY MOUNTED SPD.
PANELCONN LOAD0.9
0.91.11.11.4
COND
SIZE3/4
KVAKVAKVAKVA
KVAKVAKVAKVA
KVAKVAKVAKVA
KVAKVA
AMPSAMPS
WIRE
SIZE3#12
SUBFEEDCONN LOAD
BKR
TRIP202020
2020202020
20202020
A:A:A:
KVAKVAKVAKVA
KVAKVAKVAKVA
KVAKVAKVAKVA
KVAKVA
AMPSAMPS
AMPS3.4
3.4
3.4
FEEDTHRUCONN LOAD
KVA0.9
KVAKVAKVAKVA
KVAKVAKVAKVA
KVAKVAKVAKVA
KVAKVA
AMPSAMPS
50 AMP BUS 50 AMP MCB 480Y/277 VOLTS 3PH, 4W, SN MIN. 14 KAIC SURFACE MOUNTED
PHA
BC
AB
CA
B
CA
BC
B:B:B:
PANELBOARD NOTES:
TOTALLOAD0.9
0.91.11.11.4
KVA
KVAKVAKVAKVA
KVAKVAKVAKVA
KVAKVAKVAKVA
KVAKVA
AMPSAMPS
AMPS
D.F.MULT.
1.25NEC0.801.25
1.000.800.800.65
0.801.000.47
BKR
TRIP202020
2020202020
20202020
C:C:C:
TOTAL KVADEMAND1.2
1.21.41.41.7
WIRE
SIZE
KVAKVAKVAKVA
KVAKVAKVAKVA
KVAKVAKVAKVA
KVAKVA
AMPSAMPS
COND
SIZE LOAD DESCRIPTIONSPARESPARESPARE
SPARESPARESPARESPARESPARE
SPARESPARESPARESPARE
CKT.
NO.246
810121416
18202224
thre
e in
ches
= o
ne fo
ot6"
Department ofVeterans Affairs
one
and
one
half
inch
es =
one
foot
6"on
e in
ch =
one
foot
thre
e qu
arte
rs in
ch =
one
foot
one
half
inch
= o
ne fo
ot0
thre
e ei
ghth
s in
ch =
one
foot
0on
e qu
arte
r in
ch =
one
foot
0on
e ei
ghth
inch
= o
ne fo
ot0
10
6"0
26"
02
44
48
48
16
VA FORM 08-6231
Revisions:
1 2 3 4 5 6 7 8 9
Date:
CONSULTANTS: ARCHITECT/ENGINEERS:
590 MEANS ST NW ATLANTA, GA 30318
Drawing Title:
Approved Project Director:
Project Title:
Location:
Date: Checked: Drawn:
Drawing Number:
Building Number:
Project Number:
Dwg. of
OFFICE OFCONSTRUCTIONAND FACILITIESMANAGEMENT
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
BID DOCUMENTS
ELECTRICAL SCHEDULES CONSTRUCT DOM CLINIC
AND CLC ADMINISTRATION
ADDITION
MARTINSBURG, WV
EP602
613-121
June 27, 2018 CEN SBC
501D & 502F
DOM CLINIC PANEL SCHEDULES
502F-LA2
502F-LT
502F-HA
502F-LA1
502F-LS
XFMR
"501D-T-LA1"
75KVAGRADE
EXISTING ELEC RM C-109A ELEC RM 501D-104
PANEL
501D-HA400 A
480 V
PANEL
501D-LA1225 A
208 V
XFMR
"501D-T-LA2"
75KVA
PANEL
501D-LA2400 A
208 V
PANEL
501D-LT100 A
208 V
TELECOM RM 501D-101
300Y
110D 125D
225Y 300Y
100Y
G75G75
1 2
PANEL
EM-A-501
250A
480V
EX PANEL
MDP-501
800A
480V
XFMR
"502F-T-LA1"
75KVAGRADE
EXISTING ELEC RM E-139A ELEC RM 502F-130
PANEL
502F-HA225 A
480 V
PANEL
502F-LA1225 A
208 V
XFMR
"502F-T-LA2"
75KVA
PANEL
502F-LA2225 A
208 V
PANEL
502F-LT100 A
208 V
TELECOM RM 502F-120
PANEL
502F-LS50 A
480 V110D 110D
225Y 225Y
225Y
100Y
50Y
G75 G75
3 4
PANEL
EM-A-502
250A
480V
EX PANEL
MDP-502
800A
480V
thre
e in
ches
= o
ne fo
ot6"
Department ofVeterans Affairs
one
and
one
half
inch
es =
one
foot
6"on
e in
ch =
one
foot
thre
e qu
arte
rs in
ch =
one
foot
one
half
inch
= o
ne fo
ot0
thre
e ei
ghth
s in
ch =
one
foot
0on
e qu
arte
r in
ch =
one
foot
0on
e ei
ghth
inch
= o
ne fo
ot0
10
6"0
26"
02
44
48
48
16
VA FORM 08-6231
Revisions:
1 2 3 4 5 6 7 8 9
Date:
CONSULTANTS: ARCHITECT/ENGINEERS:
590 MEANS ST NW ATLANTA, GA 30318
Drawing Title:
Approved Project Director:
Project Title:
Location:
Date: Checked: Drawn:
Drawing Number:
Building Number:
Project Number:
Dwg. of
OFFICE OFCONSTRUCTIONAND FACILITIESMANAGEMENT
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
BID DOCUMENTS
POWER RISER DIAGRAM AND MECHANICAL
CONNECTION SCHEDULE
CONSTRUCT DOM CLINIC
AND CLC ADMINISTRATION
ADDITION
MARTINSBURG, WV
EP701
613-121
June 27, 2018 CEN SBC
FEEDER SCHEDULE
DESIGNATION
NO.
OF
SETS
CONDUCTORS
CONDUIT NOTESPHASE NEUTRAL GROUND
50Y 1 3#6 #6 #10 1"
100Y 1 3#1 #1 #8 1-1/2"
110D 1 3#1/0 - #6 1-1/4"
125D 1 3#1/0 - #6 1-1/2"
225Y 1 3#4/0 #4/0 #2 3"
300Y 1 3#350
KCMILL
3"
GROUND CONDUCTOR SCHEDULE
DESIGNATION DESCRIPTION PVC CONDUIT
G75 #2 3/4" PVC
1 PROVIDE NEW 225A EATON BREAKER IN PANEL MDP-501. PANEL
IS A WESTINGHOUSE TYPE CDP, 480Y/277V,3PH,4W.
2 UTILIZE ONE SPARE 20A/1P BREAKERS FOR LIFE SAFETY
CONNECTIONS.
3 REPLACE 200A SPARE BREAKER IN PANEL MDP-502 WITH NEW
225A BREAKER. PANEL IS A WESTINGHOUSE UTILIZING TYPE JD
BREAKER WITH 35K RATING
4 PROVIDE NEW 50A EATON TYPE EHD3050L BREAKER IN PANEL
EM-502.
POWER RISER NOTES:
12" = 1'-0"1
CLC ADMINISTRATION POWER RISER DIAGRAM
12" = 1'-0"2
DOMICILIARY CLINIC POWER RISER DIAGRAM
501D & 502F
MECHANICAL EQUIPMENT CONNECTION SCHEDULEEQUIPME
NT
DEISGNA
TIONROOM
NUMBER DESCRIPTION
LOAD
RATING VOLTS
PHA
SE
DISCONNECT SWITCH
CONDUCTOR AND
CONDUIT
CIRCUIT
INFORMATION
REMARKS
NO. OF
POLES AMPS
FUS
E
NEM
AWIRE SIZE
CONDUI
T SIZE PANEL
CIRCUIT
NUMBER
101 501D-102 1-SF-1 5 HP 480 V 3 3 20 A 1 3#12, #12G 3/4" 501D-HA 2,4,6 UNIT TO BE SERVED BY A VARIABLE FREQUENCY DRIVE
102 502F-128 2-SF-1 7.5 HP 480 V 3 3 20 A 1 3#12, #12G 3/4" 502F-HA 2,4,6 UNIT TO BE SERVED BY A VARIABLE FREQUENCY DRIVE
301 501D-132 ELECTRIC TANKLESS WATER HEATER 3.5 KW 208 V 1 2 30 A 1 2#10,#10G 3/4" 501D-LA2 1,3 PROVIDE A NEMA 5-30R RECEPTACLE AND A CORD AND PLUG TO UNIT
302 501D-133 ELECTRIC TANKLESS WATER HEATER 3.5 KW 208 V 1 2 30 A 1 2#10,#10G 3/4" 501D-LA2 5,7 PROVIDE A NEMA 5-30R RECEPTACLE AND A CORD AND PLUG TO UNIT
303 501D-118 ELECTRIC TANKLESS WATER HEATER 3.5 KW 208 V 1 2 30 A 1 2#10,#10G 3/4" 501D-LA2 9,11 PROVIDE A NEMA 5-30R RECEPTACLE AND A CORD AND PLUG TO UNIT
304 501D-117 ELECTRIC TANKLESS WATER HEATER 3.5 KW 208 V 1 2 30 A 1 2#10,#10G 3/4" 501D-LA2 12,14 PROVIDE A NEMA 5-30R RECEPTACLE AND A CORD AND PLUG TO UNIT
305 501D-121 ELECTRIC TANKLESS WATER HEATER 3.5 KW 208 V 1 2 30 A 1 2#10,#10G 3/4" 501D-LA2 13,15 PROVIDE A NEMA 5-30R RECEPTACLE AND A CORD AND PLUG TO UNIT
306 501D-125 ELECTRIC TANKLESS WATER HEATER 3.5 KW 208 V 1 2 30 A 1 2#10,#10G 3/4" 501D-LA2 16,18 PROVIDE A NEMA 5-30R RECEPTACLE AND A CORD AND PLUG TO UNIT
307 501D-124 ELECTRIC TANKLESS WATER HEATER 3.5 KW 208 V 1 2 30 A 1 2#10,#10G 3/4" 501D-LA2 17,19 PROVIDE A NEMA 5-30R RECEPTACLE AND A CORD AND PLUG TO UNIT
308 501D-111 ELECTRIC TANKLESS WATER HEATER 3.5 KW 208 V 1 2 30 A 1 2#10,#10G 3/4" 501D-LA2 20,22 PROVIDE A NEMA 5-30R RECEPTACLE AND A CORD AND PLUG TO UNIT
309 501D-109 ELECTRIC TANKLESS WATER HEATER 3.5 KW 208 V 1 2 30 A 1 2#10,#10G 3/4" 501D-LA2 21,23 PROVIDE A NEMA 5-30R RECEPTACLE AND A CORD AND PLUG TO UNIT
310 501D-112 ELECTRIC TANKLESS WATER HEATER 3.5 KW 208 V 1 2 30 A 1 2#10,#10G 3/4" 501D-LA2 24,26 PROVIDE A NEMA 5-30R RECEPTACLE AND A CORD AND PLUG TO UNIT
311 501D-110 ELECTRIC TANKLESS WATER HEATER 3.5 KW 208 V 1 2 30 A 1 2#10,#10G 3/4" 501D-LA2 25,27 PROVIDE A NEMA 5-30R RECEPTACLE AND A CORD AND PLUG TO UNIT
312 502F-101 ELECTRIC TANKLESS WATER HEATER 3.5 KW 208 V 1 2 30 A 1 2#10,#10G 3/4" 502F-LA2 1,3 PROVIDE A NEMA 5-30R RECEPTACLE AND A CORD AND PLUG TO UNIT
313 502F-104 ELECTRIC TANKLESS WATER HEATER 3.5 KW 208 V 1 2 30 A 1 2#10,#10G 3/4" 502F-LA2 5,7 PROVIDE A NEMA 5-30R RECEPTACLE AND A CORD AND PLUG TO UNIT
314 502F-108 ELECTRIC TANKLESS WATER HEATER 3.5 KW 208 V 1 2 30 A 1 2#10,#10G 3/4" 502F-LA2 6,8 PROVIDE A NEMA 5-30R RECEPTACLE AND A CORD AND PLUG TO UNIT
315 502F-109 ELECTRIC TANKLESS WATER HEATER 3.5 KW 208 V 1 2 30 A 1 2#10,#10G 3/4" 502F-LA2 9,11 PROVIDE A NEMA 5-30R RECEPTACLE AND A CORD AND PLUG TO UNIT
316 502F-114 ELECTRIC TANKLESS WATER HEATER 3.5 KW 208 V 1 2 30 A 1 2#10,#10G 3/4" 502F-LA2 10,12 PROVIDE A NEMA 5-30R RECEPTACLE AND A CORD AND PLUG TO UNIT
317 502F-112 ELECTRIC TANKLESS WATER HEATER 3.5 KW 208 V 1 2 30 A 1 2#10,#10G 3/4" 502F-LA2 13,15 PROVIDE A NEMA 5-30R RECEPTACLE AND A CORD AND PLUG TO UNIT
318 502F-106 ELECTRIC TANKLESS WATER HEATER 3.5 KW 208 V 1 2 30 A 1 2#10,#10G 3/4" 502F-LA2 14,16 PROVIDE A NEMA 5-30R RECEPTACLE AND A CORD AND PLUG TO UNIT
319 502F-113 ELECTRIC TANKLESS WATER HEATER 3.5 KW 208 V 1 2 30 A 1 2#10,#10G 3/4" 502F-LA2 17,19 PROVIDE A NEMA 5-30R RECEPTACLE AND A CORD AND PLUG TO UNIT
320 502F-115 ELECTRIC TANKLESS WATER HEATER 3.5 KW 208 V 1 2 30 A 1 2#10,#10G 3/4" 502F-LA2 18,20 PROVIDE A NEMA 5-30R RECEPTACLE AND A CORD AND PLUG TO UNIT
321 502F-117 ELECTRIC TANKLESS WATER HEATER 3.5 KW 208 V 1 2 30 A 1 2#10,#10G 3/4" 502F-LA2 21,23 PROVIDE A NEMA 5-30R RECEPTACLE AND A CORD AND PLUG TO UNIT
322 502F-124 ELECTRIC TANKLESS WATER HEATER 3.5 KW 208 V 1 2 30 A 1 2#10,#10G 3/4" 502F-LA2 22,24 PROVIDE A NEMA 5-30R RECEPTACLE AND A CORD AND PLUG TO UNIT
401 501D-102 PMP-1 & PMP-2 .25 HP 120 V 1 1 20 A 1 2#12, #12G 3/4" 501D-LA2 40 UNIT TO BE SERVED BY A VARIABLE FREQUENCY DRIVE
402 502F-128 2-RF-1 2 HP 480 V 3 3 20 A 1 3#12, #12G 3/4" 502F-HA 8,10,12 UNIT TO BE SERVED BY A VARIABLE FREQUENCY DRIVE
414 501D-134 ELECTRIC TANKLESS WATER HEATER 3500KVA 208 V 1 2 30 A 1 2#10,#10G 3/4" 501D-LA2 28,30 PROVIDE A NEMA 5-30R RECEPTACLE AND A CORD AND PLUG TO UNIT
415 502F-122 ELECTRIC TANKLESS WATER HEATER 3500KVA 208 V 1 2 30 A 1 2#10,#10G 3/4" 502F-LA2 25,27 PROVIDE A NEMA 5-30R RECEPTACLE AND A CORD AND PLUG TO UNIT
488 EXTERIOR VEHICLE ENTRY GATE 2500 208 V 1 2 30 A 3R 2#10,#10G 3/4" 501D-LA1 47,49
490 501D-136 LIFT 1 A 120 V 1 1 20 A 1 2#12, #12G 3/4" 501D-LA1 42
491 5001D-C5 AC-3 2A 208 V 1 2 0 A 1 2#12, #12G 3/4" POWERED FROM EXTERIOR UNIT
492 5001D-C5 AC-4 2A 208 V 1 2 0 A 1 2#12, #12G 3/4" POWERED FROM EXTERIOR UNIT
493 5001D-C5 AC-6 2A 208 V 1 2 0 A 1 2#12, #12G 3/4" POWERED FROM EXTERIOR UNIT
494 501C-125A AC-5 2A 208 V 1 2 0 A 1 2#12, #12G 3/4" POWERED FROM EXTERIOR UNIT
495 5001D-C5 AC-7 2A 208 V 1 2 0 A 1 2#12, #12G 3/4" POWERED FROM EXTERIOR UNIT
496 EXTERIOR CU-6 25A 208 V 1 2 30 A 3R 3#10,#10G 3/4" 501D-LA2 8,10
497 EXTERIOR CU-7 25A 208 V 1 2 30 A 3R 3#10,#10G 3/4" 501D-LA2 29,31
498 ROOF CU-3 25A 208 V 1 2 30 A 3R 3#10,#10G 3/4" 501D-LA2 32,34
499 ROOF CU-4 25A 208 V 1 2 30 A 3R 3#10,#10G 3/4" 501D-LA2 33,35
500 ROOF CU-5 25A 208 V 1 2 30 A 3R 3#10,#10G 3/4" 501D-LA2 36,38
501 502F-120 AC-1 1 A 208 V 1 2 20 A 1 3#10,#10G 3/4" POWERED FROM EXTERIOR UNIT
502 501D-101 AC-2 1 A 208 V 1 2 20 A 1 3#10,#10G 3/4" POWERED FROM EXTERIOR UNIT
503 501D-102 EF-3 .5 HP 480 V 3 3 20 A 1 3#12, #12G 3/4" 501D-HA 8,10,12
504 501D-102 1-RF-1 2 HP 480 V 3 3 20 A 1 3#12, #12G 3/4" 501D-HA 26,28,30 UNIT TO BE SERVED BY A VARIABLE FREQUENCY DRIVE
505 501D-102 UH-1 1 A 120 V 1 1 20 A 1 2#12, #12G 3/4" 501D-LA2 43
506 502F-128 EF-4 .5 HP 480 V 3 3 20 A 1 3#12, #12G 3/4" 502F-HA 13,15,17
507 502F-128 UH-2 1 A 120 V 1 1 20 A 1 2#12, #12G 3/4" 502F-LA2 30
508 501D-108 VAV-1-03 1 A 120 V 1 1 20 A 1 2#12, #12G 3/4" 501D-LA2 37 PROVIDE LOCKABLE MOTOR RATED SWITCH MOUNTED ADJACENT TO UNIT
509 501D-C2 VAV-1-01 1 A 120 V 1 1 20 A 1 2#12, #12G 3/4" 501D-LA2 37 PROVIDE LOCKABLE MOTOR RATED SWITCH MOUNTED ADJACENT TO UNIT
510 501D-111 VAV-1-02 1 A 120 V 1 1 20 A 1 2#12, #12G 3/4" 501D-LA2 37 PROVIDE LOCKABLE MOTOR RATED SWITCH MOUNTED ADJACENT TO UNIT
511 EXTERIOR CU-1 1.8 KW 208 V 1 2 30 A 3R 3#10,#10G 3/4" 502F-LA2 2,4
512 EXTERIOR CU-2 1.8 KW 208 V 1 2 30 A 3R 2#10,#10G 3/4" 501D-LA2 2,4
513 501D-C2 VAV-1-11 1 A 120 V 1 1 20 A 1 2#12, #12G 3/4" 501D-LA2 37 PROVIDE LOCKABLE MOTOR RATED SWITCH MOUNTED ADJACENT TO UNIT
514 501D-114 VAV-1-04 1 A 120 V 1 1 20 A 1 2#12, #12G 3/4" 501D-LA2 37 PROVIDE LOCKABLE MOTOR RATED SWITCH MOUNTED ADJACENT TO UNIT
515 501D-122 VAV-1-05 1 A 120 V 1 1 20 A 1 2#12, #12G 3/4" 501D-LA2 37 PROVIDE LOCKABLE MOTOR RATED SWITCH MOUNTED ADJACENT TO UNIT
516 501D-124 VAV-1-12 1 A 120 V 1 1 20 A 1 2#12, #12G 3/4" 501D-LA2 37 PROVIDE LOCKABLE MOTOR RATED SWITCH MOUNTED ADJACENT TO UNIT
517 501D-125 VAV-1-08 1 A 120 V 1 1 20 A 1 2#12, #12G 3/4" 501D-LA2 37 PROVIDE LOCKABLE MOTOR RATED SWITCH MOUNTED ADJACENT TO UNIT
518 501D-121 VAV-1-13 1 A 120 V 1 1 20 A 1 2#12, #12G 3/4" 501D-LA2 37 PROVIDE LOCKABLE MOTOR RATED SWITCH MOUNTED ADJACENT TO UNIT
519 501D-C4 VAV-1-06 1 A 120 V 1 1 20 A 1 2#12, #12G 3/4" 501D-LA2 37 PROVIDE LOCKABLE MOTOR RATED SWITCH MOUNTED ADJACENT TO UNIT
520 501D-128 VAV-1-07 1 A 120 V 1 1 20 A 1 2#12, #12G 3/4" 501D-LA2 37 PROVIDE LOCKABLE MOTOR RATED SWITCH MOUNTED ADJACENT TO UNIT
521 501D-130 VAV-1-10 1 A 120 V 1 1 20 A 1 2#12, #12G 3/4" 501D-LA2 37 PROVIDE LOCKABLE MOTOR RATED SWITCH MOUNTED ADJACENT TO UNIT
522 501D-129 VAV-1-09 1 A 120 V 1 1 20 A 1 2#12, #12G 3/4" 501D-LA2 37 PROVIDE LOCKABLE MOTOR RATED SWITCH MOUNTED ADJACENT TO UNIT
523 502F-110 VAV-2-06 1 A 120 V 1 1 20 A 1 2#12, #12G 3/4" 502F-LA2 26 PROVIDE LOCKABLE MOTOR RATED SWITCH MOUNTED ADJACENT TO UNIT
524 502F-108 VAV-2-04 1 A 120 V 1 1 20 A 1 2#12, #12G 3/4" 502F-LA2 26 PROVIDE LOCKABLE MOTOR RATED SWITCH MOUNTED ADJACENT TO UNIT
525 502F-108 VAV-2-01 1 A 120 V 1 1 20 A 1 2#12, #12G 3/4" 502F-LA2 26 PROVIDE LOCKABLE MOTOR RATED SWITCH MOUNTED ADJACENT TO UNIT
526 502F-108 VAV-2-02 1 A 120 V 1 1 20 A 1 2#12, #12G 3/4" 502F-LA2 26 PROVIDE LOCKABLE MOTOR RATED SWITCH MOUNTED ADJACENT TO UNIT
527 502F-108 VAV-2-03 1 A 120 V 1 1 20 A 1 2#12, #12G 3/4" 502F-LA2 26 PROVIDE LOCKABLE MOTOR RATED SWITCH MOUNTED ADJACENT TO UNIT
528 502F-108 VAV-2-05 1 A 120 V 1 1 20 A 1 2#12, #12G 3/4" 502F-LA2 26 PROVIDE LOCKABLE MOTOR RATED SWITCH MOUNTED ADJACENT TO UNIT
529 502F-108 VAV-2-08 1 A 120 V 1 1 20 A 1 2#12, #12G 3/4" 502F-LA2 26 PROVIDE LOCKABLE MOTOR RATED SWITCH MOUNTED ADJACENT TO UNIT
530 502F-108 VAV-2-09 1 A 120 V 1 1 20 A 1 2#12, #12G 3/4" 502F-LA2 26 PROVIDE LOCKABLE MOTOR RATED SWITCH MOUNTED ADJACENT TO UNIT
531 502F-108 VAV-2-10 1 A 120 V 1 1 20 A 1 2#12, #12G 3/4" 502F-LA2 26 PROVIDE LOCKABLE MOTOR RATED SWITCH MOUNTED ADJACENT TO UNIT
532 502F-108 VAV-2-11 1 A 120 V 1 1 20 A 1 2#12, #12G 3/4" 502F-LA2 26 PROVIDE LOCKABLE MOTOR RATED SWITCH MOUNTED ADJACENT TO UNIT
533 502F-108 VAV-2-07 1 A 120 V 1 1 20 A 1 2#12, #12G 3/4" 502F-LA2 26 PROVIDE LOCKABLE MOTOR RATED SWITCH MOUNTED ADJACENT TO UNIT
535 EXTERIOR VEHICLE ENTRY GATE 2500 208 V 1 2 30 A 3R 2#10,#10G 3/4" 501D-LA1 50,52
536 EXTERIOR VEHICLE ENTRY GATE 2500 208 V 1 2 30 A 3R 2#10,#10G 3/4" 502F-LA1 37,39
537 EXTERIOR VEHICLE ENTRY GATE 2500 208 V 1 2 30 A 3R 2#10,#10G 3/4" 502F-LA1 38,40
540 501D-100 AUTOMATIC DOOR POWER 10 A 208 V 1 2 20 A 1 2#12, #12G 3/4" 501D-LA1 55,57
541 501D-100 AUTOMATIC DOOR POWER 10 A 208 V 1 2 20 A 1 2#12, #12G 3/4" 501D-LA1 51,53
544 502F-128 2-SH1 10 KW 480 V 3 3 20 A 1 3#12, #12G 3/4" 502F-HA 7,9,11
546 501D-102 1-SH1 10 KW 480 V 3 3 30 A 1 3#12, #12G 3/4" 501D-HA 7,9,11
547 502F-112 EF-2 120 V 1 1 20 A 1 2#12, #12G 3/4" 502F-LA2 28
548 EXTERIOR CU-9 1.8 KW 208 V 1 2 30 A 3R 2#10,#10G 3/4" 501D-LA2 39,41
549 501D-104 AC-8 1A 208 V 1 2 20 A 1 2#10,#10G 3/4" 501D-LA2 39,41 POWERED FROM EXTERIOR UNIT
550 EXTERIOR CU-9 1.8 KW 208 V 1 2 30 A 3R 2#10,#10G 3/4" 502F-LA2 29,31
551 502F-130 AC-9 1A 208 V 1 2 20 A 1 2#10,#10G 3/4" 502F-LA2 29,31 POWERED FROM EXTERIOR UNIT
552 E-138B CWP-1 25 HP 480 V 3 3 60 A 1 3#6,#10G 1" UNIT TO BE SERVED BY A VARIABLE FREQUENCY DRIVE. SEE NOTE 8 ON EP102.
553 E-138B CWP-2 25 HP 480 V 3 3 60 A 1 3#6,#10G 1" UNIT TO BE SERVED BY A VARIABLE FREQUENCY DRIVE. SEE NOTE 8 ON EP102.
558 Alternate
Area
EF-ALT 5.8A 120 V 1 1 20 A 12#12, #12G
3/4" 501D-LA2 42
559 Alternate
Area
EF-ALT 5.8A 120 V 1 1 20 A 12#12, #12G
3/4" 501D-LA2 42
560 Alternate
Area
UH Alt 13A 480 V 3 3 20 A 13#12, #12G
3/4" 501D-HA 21,23,25
561 Alternate
Area
UH Alt 13A 480 V 3 3 20 A 13#12, #12G
3/4" 501D-HA 15,17,19
562 Alternate
Area
UH Alt 13A 480 V 3 3 20 A 13#12, #12G
3/4" 501D-HA 20,22,24
563 Alternate
Area
UH Alt 13A 480 V 3 3 20 A 13#12, #12G
3/4" 501D-HA 14,16,18
601 ROOF EF-1 1/10 HP 120 V 1 1 30 A 3R 2#12, #12G 3/4" 501D-LA2 6
DNDNDN
DNCG CG
CG
CG
CG
CG
CGCGCG
CG
CG
CGCGCG
CG
CG
CGCG
CG
CG
CG
C-109
549 SQ. FT.
C-110
181 SQ. FT.
CW-1
507 SQ. FT.
C-112
150 SQ. FT.
E-1
88 SQ. FT.
63 SQ. FT.
C-125
3,053 SQ. FT.
ELECTRIC ROOM
STAIR # 1
WALKWAY
SERVICE ELEVATORLOBBY
ELEV.
DINING
BIOMED
233
SERVIC
E CORR.
SC-1
MULE STO
RAGE
238
S
S
S
S S
S S S
S
S
S
S
S
S
S
S
S
SSSSS SSS
NNNN
S
CR
CRN N N N
TV
KP
CR
SD
F
F
FF
F
F
F
F
F
F
F
F
FF
F
F
F
F
SD
TV
F
F
FF
F
F
F
F
F
FA
CP
FA
CP
CR
TV
TV
CR
LAUNDRY
124
BEDROOM
, RES
122
MEC
H R
OOM
135
REC
YC/TR
ASH
134
STAFF T
OILET
MED
SUPPLY
INTER
DISC
. OFFIC
E
132
BATH
, GEN
123A
COM
M C
LOSET
130
REC
STOR
131
STAIR
2
STRET
CHER
STORAGE
133
POLICE TA
CK R
OOM
136
SWITC
HGEAR
ROOM
143
STORAGE
137
VEST
IBULE
140(LOB02)
CORRID
OR
C-3
CORRID
OR
C-2
CORRID
OR
C-4
ELEV 2
BATH
, GEN
122A
BEDROOM
, RES
123
EMR
146
KP
501D-100
501D-110501D-108
501D-113501D-112
501D-114501D-115
501D-107
501D-106
501D-109
501D-116
501D-111A
501D-111
501D-C2
501D-120
501D-128501D-121
501D-103
501D-101
501D-122
501D-123501D-124501D-125501D-126
501D-102
501D-131
501D-130
501D-127
501D-129A
501D-129
501D-C3
501D-C4
501D-104
501D-105
501D-136
501D-C1
501D-C5
1
501D-117501D-118501D-134
501D-133501D-132
501D-119
501D-135
501C-125A
7
6
9
EY101
2
C
C.2
C.4
F
G
G.5
H
I
K
1 3 3.1 3.4 4
4.8 5 6 7 8 9 10 11 12
9
10
11
12
16
5
18
SEE TRANQ
UILITY BLDG. O
N THIS SHEET
MATCHLINE
EY101
22
SEE DELIVERY ENTRANCE FLOORPLAN ON THIS SHEET
23
24
25
25
26
26
MATCHLINE
EY101
3
33
3
2
DDC
4.5
RE
B
B.5
5.3 6.5 7.5 9.7 9.8 9.9 10.58.4
A
TRUE
NORTH
PLAN
NORTH
M
138
G.5
H
11 12
14
27
1. ALL TELECOMMUNICATIONS WORK IS TO BE PERFORMED PER THIS PROJECT'STELECOMMUNICATIONS SPECIFICATIONS, THE 2017 NEC, THE 2016 VATELECOMMUNICATIONS AND SPECIAL TELECOMMUNICATIONS SYSTEMS DESIGNMANUAL, AND THE 2016 VA OIT DESIGN GUIDE.
2. DEVICE LOCATIONS SHOWN ON PLAN ARE FOR REFERENCE.3. ACCESS CONTROL HAS M8/16 PANEL IN BIOMED ROOM IN DOM "A". CONTRACTOR
IS TO PROVIDE SIX (6) STRANDS OF MM FO CABLE WITH MEDIA CONVERTER ONEACH END TO "GA-127" IT CLOSET. VA WILL PROVIDE SWITCH. PROVIDE ALLCABLES AND CONNECTIONS TO M8/M16 PANEL.
4. ACCESS CONTROL IS TO BE FROM "SAFELOCK" SECURITY SYSTEM. CONTRACTORSHALL PROVIDE INSTALLATION WITH CAT-6 CABLE FROM HUBS TO BIOMED ROOMIN DOM "A". INSTALL ALL-WIRELESS HUBS. PROVIDE AND INSTALL SWITCH INBIOMED ROOM IN DOM "A". PROVIDE CAT-6 DROP FROM SWITCH IN DOM "A"ITCLOSET OF BIOMED ROOM TO EACH OFFICE. RUN CAT-6 FROM A-POD BIOMEDTO "E" POD BIOMED CLOSET. CONNECT ALL CAT-6 CABLES TO SWITCH IN DOM"A" CLOSET IN BIOMED ROOM FROM HUBS AND OFFICES. BIOMED TEAM WILLRELOCATE SERVER IN DOM "A" CLOSET PRIOR TO CONSTRUCTION. PROVIDESWITCH IN BIOMED DOM CLOSET "E", AND CONNECT TO SWITCH. CONTRACTORIS TO PROVIDE, INSTALL, AND PROGRAM CLIENT FOR DOM "A". CONTRACTOR ISTO SUPPLY SM FO CABLE FROM MECHANICAL ROOM "GA-104" TO "GA-127".
5. CATV CONTRACTOR IS TO RUN TWO (2) STRANDS OF SM FO CABLE FROM BIOMED"A" POD TO BIOMED "B" POD. RUN (24) STRANDS OF SM FO CABLE FROM BIOMEDROOM "E" POD TO BASEMENT "FIRE ALARM/MECHANICAL" ROOM. CONTRACTORSHALL SUPPLY AND MOUNT NECESSARY SM FO CABLE RINGS AND SPLICEBOXES. CONTRACTOR IS RESPONSIBLE FOR FUSION SPLICING ALL NECESSARYFIBERS. CONTRACTOR SHALL USE THE FO NODE TO SUPPLY 5 - 12 DBMV OFSIGNAL AT THE CATV TAPS. CATV PROVIDER IS DISH NETWORK WITH HEAD-ENDLOCATED ON 6TH FLOOR.
6. CCTV CAMERAS. INSTALL CAT-6 CABLE TO EACH CAMERA FROM NEAREST "OIT"CLOSET. CONTRACTOR TO PROVIDE, INSTALL AND PROGRAM VIDEO VIEWINGSTATION IN THE SECURITY OFFICE (LOCATED IN MAIN HOSPITAL).
7. PUBLIC ADDRESS (PA OR OVERHEAD PAGING). PROVIDE 2'X2' SQUARE CEILINGMOUNTED SPEAKER UNITS WITH INDIVIDUAL VOLUME CONTROL. BIOMED TEAMWILL UNINSTALL AND STOW ALL AFFECTED EXISTING CAMERAS,TELEVISIONS,AND BRACKETS PRIOR TO CONSTRUCTION.
8. NURSE CALL WILL CONSIST OF STAND ALONE UNITS AT EACH LOCATION ONPLANS. EACH NURSE CALL UNIT SHALL HAVE AN AUDIBLE TONE DEVICE, VISUALINDICATOR WITH A LIGHT SOURCE, AND A PULL STATION FOR TRIGGERING THEAUDIO-VISUAL ALARM.
4
15
17
MATCH
LINE
SEE CLC ADMIN. BLDG
. ON THIS SHEET
9
9
19 20
22
M
21
MATCHLINE
EY101
M
21
thre
e in
ches
= o
ne fo
ot6"
Department ofVeterans Affairs
one
and
one
half
inch
es =
one
foot
6"on
e in
ch =
one
foot
thre
e qu
arte
rs in
ch =
one
foot
one
half
inch
= o
ne fo
ot0
thre
e ei
ghth
s in
ch =
one
foot
0on
e qu
arte
r in
ch =
one
foot
0on
e ei
ghth
inch
= o
ne fo
ot0
10
6"0
26"
02
44
48
48
16
VA FORM 08-6231
Revisions:
1 2 3 4 5 6 7 8 9
Date:
CONSULTANTS: ARCHITECT/ENGINEERS:
590 MEANS ST NW ATLANTA, GA 30318
Drawing Title:
Approved Project Director:
Project Title:
Location:
Date: Checked: Drawn:
Drawing Number:
Building Number:
Project Number:
Dwg. of
OFFICE OFCONSTRUCTIONAND FACILITIESMANAGEMENT
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
BID DOCUMENTS
FIRST FLOOR TELECOMMUNICATIONS PLAN -
CLC ADMINISTRATION ADDITION
CONSTRUCT DOM CLINIC
AND CLC ADMINISTRATION
ADDITION
MARTINSBURG, WV
EY101
613-121
June 27, 2018 CEN HVB
1/8" = 1'-0"1
FIRST FLOOR TELECOMMUNICATIONS PLAN - CLC ADMININSTRATION ADDITION
GENERAL NOTES
KEY NOTES
GRAPHIC SCALE(S)
1/8" = 1' - 0"0 5' 10' 15' 30'
1/4" = 1' - 0"0 5' 10' 15'1'
1/4" = 1'-0"2
FIRST FLOOR IT RM. 501D-104 -
CLC ADMINISTRATION ADDITION -
ENLARGED TELECOMMUNICATIONS PLAN
1 BIOMED CABLING. PROVIDE FOUR (4) 1" INNERDUCTS WITH SM AND MM FO CABLESAS DESCRIBED IN GENERAL NOTES 3 AND 5. ROUTE INNERDUCTS OVERHEAD INCABLE BASKET TRAY FROM BIOMED ROOM GA-104 (IN BASEMENT LEVEL OFA-BUILDING) TO BIOMED ROOM 233 (IN TRANQUILITY BUILDING). SEE CLCADMINISTRATION TELECOMMUNICATIONS RISER DIAGRAM ON SHEET EY701.
2 PENETRATE BUILIDING TO TELECOMMUNICATIONS ROOM PER ALL APPLICABLECONSTRUCTION CODES.
3 PROVIDE DOOR ACCESS CONTROL RELEASE MECHANISM AND CIRCUITINTERFACED WITH FIRE ALARM.
4 PROVIDE SM AND MM FIBER IN 1" INNERDUCTS AS DESCRIBED IN GENERAL NOTES3 AND 5. ROUTE INNERDUCTS ABOVE CEILING IN BASKET TRAY FROMTELECOMMUNICATIONS ROOM 130 (IN FIRST LEVEL OF TRANQUILITY BLDG.) TODUCTBANK IN MECHANICAL ROOM (FIRST LEVEL TRANQUILITY BLDG. DIRECTLYBELOW BIOMED ROOM 233). ROUTE TO TELECOMMUNICATIONS ROOM 501D-101 INCLC ADMINISTRATION BUILDING. SEE NOTE 5. SEE RISER DIAGRAM ON SHEETEY701.
5 TELECOMMUNICATIONS CABLING. ROUTED THROUGH DUCTBANK IN BIOMED ROOM233 TO THE FLOOR LEVEL BELOW. CABLING ORIGINATES AT HEAD END EQUIPMENTIN TELECOMMUNICATIONS ROOM 130 OF TRANQUILITY BUILDING. SEE NOTE 4.
6 PROVIDE FIRE ALARM SUB CONTROL PANEL FED FROM ELEC RM C-109. SEE NOTE7.
7 EXISTING FIRE ALARM MAIN CONTROL PANEL, FEEDS PANEL IN ELEC RM 501D-101.SEE NOTE 6.
8 PROVIDE 19" TELECOMMUNICATIONS SERVER RACK. SEE FIGURES 6 AND 7 ONSHEET EY501.
9 PROVIDE (2) 4" RIGID CONDUIT SLEEVES THROUGH WALL ABOVE CEILING.
10 PROVIDE WIRE MESH TYPE BASKET TRAY FOR TELECOMMUNICATIONS AND BIOMEDCABLING FOR DEVICE DISTRIBUTION AND TRUNK LINES. WHERE NEW BASKETTRAY IS NEEDED, USE 12" WIDE BY 4" DEEP OR STANDARD SIZE AS REQUIRED TOACCOMODATE ALL CABLING AND CONDUITS.
11 CONNECTION TO BIOMED SYSTEM HEADEND EQUIPMENT FOR CCTV, PA, ACCESSCONTROL, AND CATV, LOCATED IN THIS ROOM. BIOMED HEAD END EQUIPMENTSUPPLYING THIS ROOM IS LOCATED IN BIOMED ROOM GA-104 OF MAIN HOSPITALA-BUILDING.
12 DATA AND VOICE HEADEND EQUIPMENT FOR DISTRIBUTION TO CLCADMINISTRATION BUILDING. TIE POINT FOR FIBER OPTIC CABLE FROM ROOM C-118
13 PROVIDE TELECOMMUNICATIONS GROUND BAR. BOND PER DETAIL 7 SHEET EY501.
14 PROVIDE 18-INCH LADDER TYPE CABLE TRAY, BOND TO TELECOMMUNICATIONSGROUND BAR USING #6 AWG GREEN WIRE, SEE RISER DETAIL ON SHEET EY701AREA A7.
15 TELECOMMUNICATIONS HEAD END EQUIPMENT AND CONNECTION POINT TOSERVICE TELECOMMUNICATIONS ROOM 501D-101 IN CLC ADMIN. BLDG.
16 FROM ROOM GA-104, APPROX. 500' DISTANCE TO MAIN HOSPITAL BUILDING "A"BASEMENT.
17 DUCT BANK FOR TELECOMMUNICATIONS WIRING ROUTING IS LOCATED IN THISROOM. ROUTE TELECOMMUNICATIONS CABLES FROM TELECOMMUNICATIONSROOM 130 IN THIS BUILDING AND LEVEL AND ROUTE UP TO BIOMED ROOM 233DIRECTLY ABOVE THIS ROOM.
18 DUCT BANK FOR TELECOMMUNICATIONS ROUTES THROUGH THIS ROOM FROM THEMECHANICAL ROOM DIRECTLY BELOW. SEE TRANQUILITY BUILDING FIRST LEVELFLOORPLAN ON THIS SHEET.
19 COLUMN-MOUNT CAMERA FACING INCOMMING TRAFFIC AT 48"AFF.
20 COLUMN-MOUNT KEYPAD READER AT 48" AFF.
21 MOUNT SENSOR TO DETECT INCOMING TRAFFIC. MOUNT ON COLUMN AT 39" AFF.
22 PROVIDE FOUR (4) 1-1/4" SCH. 40 CONDUIT UNDERGROUND. PROVIDE ONE (1) STUBUP AT TELECOMMUNICATIONS ROOM 501D-101 AND AT CAMERA POLE LOCATION.PROVIDE ONE (1) STUB UP AT CARD-READER LOCATION. PROVIDE ONE STUB-UP ATAUTOMATIC GATE LOCATION. PROVIDE ONE (1) STUB UP AT MOTION DETECTORLOCATION.
23 EXISTING MAN HOLE TO REMAIN.
24 TIE NEW BASKET TRAY TO EXISTING FOR TELECOMMUNICATIONS AND FIREPROTECTION CABLING.
25 PROVIDE TWO (2) 1 1/4" CONDUIT SLEEVES THRU WALL ABOVE CEILING.
26 PROVIDE TWO (2) 1 1/4" CONDUITS, ABOVE CEILING ADJACENT TO BASKET TRAY,FROM FIRE CONTROL PANEL IN ELECTRICAL ROOM C-109 TO FIRE CONTROL PANELIN ROOM 501D-104. PROVIDE FIRE ALARM WIRING POWER PER CLC ADMIN FIREALARM RISER DIAGRAM ON SHEET EY701.
27 3/4" THICK FIRE-RETARDANT TREATED 8' X 4' WOODEN BACKBOARD.
501D
1/8" = 1'-0"3
FIRST FLOOR TELECOMMUNICATIONS PLAN - TRANQUILITY BUILDING 1/8" = 1'-0"
4
DELIVERY ENTRANCE - TELECOMMUNICATIONS PLAN -
CLC ADMINISTRATION ADDITION
#
CLC ROOM SCHEDULE - TELECOMMUNICATIONS
NUMBER NAME
501D-124 OFFICE/EXAM
501D-125 OFFICE/EXAM
501D-126 PROG. MAN.
501D-127 BUS. MAN.
501D-128 CUBICLES
501D-129 AD. ASST.
501D-129A STOR.
501D-130 SERV. CHIEF.
501D-131 ENTRANCE
501D-132 GUEST T.
501D-133 STAFF T.
501D-134 HAC
501D-135 STOR.
501D-136 LANDING
501D-C1 CORRIDOR
501D-C2 CORRIDOR
501D-C3 CORR. A
501D-C4 CORR. B
501D-C5 CONNECTOR RAMP
CLC ROOM SCHEDULE - TELECOMMUNICATIONS
NUMBER NAME
501D-100 ENTRANCE
501D-101 IT
501D-102 MECHANICAL
501D-103 STORAGE
501D-104 ELECTRICAL
501D-105 CORR.
501D-106 WAITING
501D-107 ADMIN. SUPP.
501D-108 N. CASE MAN.
501D-109 OFF. / EX.
501D-110 OFF. / EX.
501D-111 OFF. / EX.
501D-111A STOR.
501D-112 OFF. / EX.
501D-113 N. CASE MAN.
501D-114 PSYCHOL.
501D-115 G. FELLOW
501D-116 G. FELLOW
501D-117 GUEST T.
501D-118 STAFF T.
501D-119 STOR.
501D-120 COPY / WORKROOM
501D-121 BREAK ROOM
501D-122 CONFERENCE ROOM
501D-123 N. ADMIN.
CG
CG
CG
CG
CG
CG
CG
CG
CG
CG
CG
CG
CG
CG
CG
CG
CG
CG
CG
CG
CG
CG
CG
CG
CG
CG
CG
CG
CD-3CORRIDOR
D-90OFFICE
D-88OFFICE
D-86OFFICE
D-84OFFICE
D-83STORAGE
CD-1CORRIDOR
AP
S
S
SSSS
CR
CR
CR
TV
TV
N
S
S
N
N
N
N
F
F
FF
F
F
SDSD
F
F
F
N
N
FACP
F
F
TV
F
S
KP
CR
CRCR
CR
N
KP
KP
M
MJ
N
KP
E-113HSKP.
E-112TELECOME-107
STORAGE
E-114MEN'S TOILET
E-115WOMEN'S TOILET
TELEPH
ONES
D-99COMMUNITY ROOM
CD-6CORRIDOR
D-100LAUNDRY
D-101STORAGE
D-102QUIET ROOM
LOUNGE D-170STORAGE
D-171KITCHENETTE
D-172TELE. RM.
D-173HSKP.
D-174ELEC. RM.
D-175OFFICE
D-176OFFICE
D-177OFFICE
D.F.
F.E.
E-138AELEC. RM.RAISED SLAB (TYP.)
FACP
502F-105
502F-118502F-116
502F-124
502F-120
502F-114
502F-C1
502F-110
502F-101502F-103
502F-107 502F-106
502F-113 502F-115 502F-117 502F-119 502F-121
502F-122
502F-123
502F-125
502F-127
502F-C2
502F-129502F-126502F-128
502F-130
502F-111
502F-109502F-108502F-104502F-102
502F-100
5
5
55
9
11
EY102
5
FF EE DD CC BB AA
20
21
21.4
22
23
12
19
20
23
MM
17
16
11
11
13
1
18
MATCHLINE
EY102
MATCHLINE
EY102
SEE ELECTRICAL ROOM E-138AFLOORPLAN ON THIS SHEET
SEE FIRST FLOORTELECOMMUNICATIONS PLAN
ON THIS SHEET
24
3
3
3
3
3
28
29
4
4
4
4
DDC
TRUENORTH
PLANNORTH
14
8
BB
21
21.4
21
M
1. ALL TELECOMMUNICATIONS WORK IS TO BE PERFORMED PER THIS PROJECT'STELECOMMUNICATIONS SPECIFICATIONS, THE 2017 NEC, THE 2016 VATELECOMMUNICATIONS AND SPECIAL TELECOMMUNICATIONS SYSTEMS DESIGNMANUAL, AND THE 2016 VA OIT DESIGN GUIDE.
2. DEVICE LOCATIONS SHOWN ON PLAN ARE FOR REFERENCE.3. ACCESS CONTROL HAS M8/16 PANEL IN BIOMED ROOM IN DOM "A". CONTRACTOR
IS TO PROVIDE SIX (6) STRANDS OF MM FO CABLE WITH MEDIA CONVERTER ONEACH END TO "GA-127" IT CLOSET. VA WILL PROVIDE SWITCH. PROVIDE ALLCABLES AND CONNECTIONS TO M8/M16 PANEL.
4. ACCESS CONTROL IS TO BE FROM "SAFELOCK" SECURITY SYSTEM.CONTRACTOR SHALL PROVIDE INSTALLATION WITH CAT-6 CABLE FROM HUBS TOBIOMED ROOM IN DOM "A". INSTALL ALL-WIRELESS HUBS. PROVIDE AND INSTALLSWITCH IN BIOMED ROOM IN DOM "A". PROVIDE CAT-6 DROP FROM SWITCH INDOM "A" ITCLOSET OF BIOMED ROOM TO EACH OFFICE. RUN CAT-6 FROM A-PODBIOMED TO "E" POD BIOMED CLOSET. CONNECT ALL CAT-6 CABLES TO SWITCHIN DOM "A" CLOSET IN BIOMED ROOM FROM HUBS AND OFFICES. BIOMED TEAMWILL RELOCATE SERVER IN DOM "A" CLOSET PRIOR TO CONSTRUCTION.PROVIDE SWITCH IN BIOMED DOM CLOSET "E", AND CONNECT TO SWITCH.CONTRACTOR IS TO PROVIDE, INSTALL, AND PROGRAM CLIENT FOR DOM "A".CONTRACTOR IS TO SUPPLY SM FO CABLE FROM MECHANICAL ROOM "GA-104"TO "GA-127".
5. CATV CONTRACTOR IS TO RUN TWO (2) STRANDS OF SM FO CABLE FROMBIOMED "A" POD TO BIOMED "B" POD. RUN (24) STRANDS OF SM FO CABLE FROMBIOMED ROOM "E" POD TO BASEMENT "FIRE ALARM/MECHANICAL" ROOM.CONTRACTOR SHALL SUPPLY AND MOUNT NECESSARY SM FO CABLE RINGS ANDSPLICE BOXES. CONTRACTOR IS RESPONSIBLE FOR FUSION SPLICING ALLNECESSARY FIBERS. CONTRACTOR SHALL USE THE FO NODE TO SUPPLY 5 - 12DBMV OF SIGNAL AT THE CATV TAPS. CATV PROVIDER IS DISH NETWORK WITHHEAD-END LOCATED ON 6TH FLOOR.
6. CCTV CAMERAS. INSTALL CAT-6 CABLE TO EACH CAMERA FROM NEAREST "OIT"CLOSET. CONTRACTOR TO PROVIDE, INSTALL AND PROGRAM VIDEO VIEWINGSTATION IN THE SECURITY OFFICE (LOCATED IN MAIN HOSPITAL).
7. PUBLIC ADDRESS (PA OR OVERHEAD PAGING). PROVIDE 2'X2' SQUARE CEILINGMOUNTED SPEAKER UNITS WITH INDIVIDUAL VOLUME CONTROL. BIOMED TEAMWILL UNINSTALL AND STOW ALL AFFECTED EXISTING CAMERAS,TELEVISIONS,AND BRACKETS PRIOR TO CONSTRUCTION.
8. NURSE CALL WILL CONSIST OF STAND ALONE UNITS AT EACH LOCATION ONPLANS. EACH NURSE CALL UNIT SHALL HAVE AN AUDIBLE TONE DEVICE, VISUALINDICATOR WITH A LIGHT SOURCE, AND A PULL STATION FOR TRIGGERING THEAUDIO-VISUAL ALARM.
10
18
MATCHLINE
EY102
27
15
11
13
MATCHLINE
EY102
7
MATCHLINE
EY102
SEE DOMICILIARY CLINIC ONTHIS SHEET
2
25
6
26
thre
e in
ches
= o
ne fo
ot6"
Department ofVeterans Affairs
one
and
one
half
inch
es =
one
foot
6"on
e in
ch =
one
foot
thre
e qu
arte
rs in
ch =
one
foot
one
half
inch
= o
ne fo
ot0
thre
e ei
ghth
s in
ch =
one
foot
0on
e qu
arte
r in
ch =
one
foot
0on
e ei
ghth
inch
= o
ne fo
ot0
10
6"0
26"
02
44
48
48
16
VA FORM 08-6231
Revisions:
1 2 3 4 5 6 7 8 9
Date:
CONSULTANTS: ARCHITECT/ENGINEERS:
590 MEANS ST NW ATLANTA, GA 30318
Drawing Title:
Approved Project Director:
Project Title:
Location:
Date: Checked: Drawn:
Drawing Number:
Building Number:
Project Number:
Dwg. of
OFFICE OFCONSTRUCTIONAND FACILITIESMANAGEMENT
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
BID DOCUMENTS
FIRST FLOOR TELECOMMUNICATIONS PLAN -
DOMICILIARY CLINIC
CONSTRUCT DOM CLINIC
AND CLC ADMINISTRATION
ADDITION
MARTINSBURG, WV
EY102
613-121
June 27, 2018 CEN HVB
1/8" = 1'-0"2
FIRST FLOOR TELECOMMUNICATIONS PLAN - DOMICILARY CLINIC
GENERAL NOTES
KEY NOTES
GRAPHIC SCALE(S)
1 BIOMED HEAD END EQUIPMENT LOCATION.
2 PROVIDE ONE (1) 1" CONDUIT UNDERGROUND TO STUB UP AT FIRE ALARMCONTROL PANEL LOCATION IN THIS ROOM. SEE NOTE 24.
3 DOOR ACCESS CONTROL SHALL BE PROVIDED WITH RELEASE MECHANISM ANDCIRCUIT INTERFACED WITH FIRE ALARM.
4 COLUMN-MOUNT AT 48" AFF.
5 INSTALL 3'-8" AFF.
6 PROVIDE 1" CONDUIT STUB UP TO 12" ABOVE FINISHED GRADE.
7 FIRE ALARM MAIN CONTROL PANEL. FEEDS SUB-PANEL IN ELEC RM 502F-130 OFNEW DOMICILIARY CLINIC
8 PROVIDE 19" TELECOMMUNICATIONS SERVER RACK. SEE DETAILS 6 AND 7 SHEETEY501.
9 PROVIDE FIRE ALARM SUB-PANEL FED FROM ELEC RM E-138A.
10 BIOMED ROOM TO PROVIDE HEAD-END EQUIPMENT CONNECTION POINT FOR PA,CCTV, ACCESS CONTROL & CATV.
11 PROVIDE (2) 4" RIGID CONDUITS SLEEVES THROUGH WALL ABOVE CEILING.
12 HEAD-END EQUIPMENT FOR VOICE AND DATA FOR DISTRIBUTION TO NEWDOMICILIARY CLINIC. FIBER CONNECTION POINT FOR VOICE AND DATA.CONNECTION POINT FOR ACCESS CONTROL AND CCTV TO PORT TO BIOMEDHEAD END EQUIPMENT IN ROOM 502-F130.
13 PROVIDE SM AND MM FO CABLE AS DESCRIBED IN GENERAL NOTES 3 AND 5.PROVIDE FO CABLES IN 1" INNERDUCTS FROM TELECOMMUNICATIONS ROOMD-172 TO TELECOMMUNICATIONS ROOM 502F-120. ROUTE ABOVE CEILING IN WIREBASKET TRAY. SEE RISER DIAGRAM ON SHEET EY701.
14 PROVIDE TELECOMMUNICATIONS GROUND BAR. BOND PER DETAIL 7 SHEETEY501.
15 HEADEND EQUIPMENT CONNECTION POINT FOR TELECOMMUNICATIONS. VOICECONNECTION VIA 110X PUNCHDOWN BLOCK.
16 TIE IN TO EXISTING PA SYSTEM DEVICE AND INSTALL AMPLIFIER(S) ASNECESSARY. TEST FOR DBA (SOUND) LOSS ON ALL INSTALLED DEVICES.
17 PROVIDE INTRUSION KEYPAD TIED INTO MOTION ALARM SYSTEM. KEYPADOPERATES INTRUSION ALARM SYSTEM.
18 PROVIDE SM AND MM FO CABLE AS DESCRIBED IN GENERAL NOTES 3 AND 5.PROVIDE FO CABLES IN 1" INNERDUCTS FROM BIOMED ROOM E-107 TO BIOMEDEQUIPMENT CONNECTION AREA IN ROOM 502F-120. ROUTE ABOVE CEILING INWIRE BASKET TRAY. SEE NOTES 1 AND 19. SEE RISER DIAGRAM ON SHEET EY701.
19 PROVIDE WIRE MESH TYPE BASKET TRAY, USE 12" WIDE X 4" DEEP OR STANDARDSIZE BASKET TRAY TO ACCOMMODATE ALL REQUIRED CABLES. CABLE TRAYROUTES ALL BIOMED AND TELECOMMUNICATIONS TRUNK AND DISTRIBUTIONWIRING.
20 PROVIDE DATA CONNECTION FOR FUTURE REGISTRATION KIOSK.
21 PROVIDE 18" LADDER TYPE CABLE TRAY, BOND PER DETAIL 7 ON SHEET EY501.
23 ALARM SPEAKER TO BE TRIGGERED BY MOTION DETECTORS IN THIS ROOM502F-106 AND OUTSIDE AREA 502-107 MOTION DETECTOR
24 PROVIDE ONE (1) 1" CONDUIT UNDERGROUND AND ADJACENT TO POWER DUCTBANK TO STUB UP AT FIRE ALARM CONTROL PANEL LOCATION IN ELECTRICALROOM 502F-130 IN CLC CLINIC. PROVIDE WIRING PER RESPECTIVE FIRE ALARMRISER ON SHEET EY701. SEE NOTE 2.
25 PROVIDE THRU-WALL RIGID CONDUIT SLEEVE AT 12" ABOVE FINISHED GRADE
26 PROVIDE 1" CONDUIT STUB UP TO ABOVE CEILING AND ROUTE TO FIRE ALARMCONTROL PANEL IN THIS ROOM E-138A
27 PROVIDE PHYSICAL BARRIER OR ENCLOSURE FOR TELECOMMUNICATIONSEQUIPMENT IN THIS ROOM.
28 PROVIDE ONE (1) 2" CONDUIT AT 18" BELOW GRADE TO FOLLOW ROUTE ASSHOWN. PROVIDE ENTRANCE TO BUILDING AND STUB-UP TO ABOVE CEILING.PROVIDE SIX (6) CAT-6 CABLES FROM TELECOM ROOM 502F-120 TO DEVICES(ALLOWING 2 SPARES) TO LIFT GATE(S). PROVIDE A PULL MEMBER IN CONDUIT.
29 LIFT GATE SHOWN FOR REFERENCE.
1/8" = 1' - 0"0 5' 10' 15' 30'
1/4" = 1' - 0"0 5' 10' 15'1'
DOM ROOM SCHEDULE
NUMBER NAME
502F-115 DOM STAFFSCREENER
502F-116 REC. THER.
502F-117 DOM SUPV. SCREEN.
502F-118 DIETICIAN
502F-119 PEER SUPP.
502F-120 IT
502F-121 SOC. WORK.
502F-122 HAC
502F-123 MANAGER
502F-124 STAFF T.
502F-125 PSYCH.
502F-126 PA OFFICE
502F-127 PSYCH.
502F-128 MECHANICAL
502F-129 PSYCH.
502F-130 ELECT
502F-C1 CORR. A
502F-C2 CORR. B
DOM ROOM SCHEDULE
NUMBER NAME
502F-100 LOBBY
502F-101 PAT. T.
502F-102 CHECK IN
502F-103 WAITING
502F-104 TRIAGE
502F-105 N. STATION
502F-105A STOR.
502F-106 MEDS
502F-107 N. STATION
502F-107A STOR.
502F-108 N. ASSESS.
502F-109 N. ASSESS.
502F-110 VESTIBULE
502F-111 SPEC. VEST.
502F-112 SPEC. T.
502F-113 DOM SCREENINGCLERK
502F-114 N. ASSESS.
1/4" = 1'-0"5
FIRST FLOOR TELECOMMUNICATIONS ROOM - DOMICILARY CLINIC
ENLARGED TELECOMMUNICATIONS PLAN
#
502F
1/8" = 1'-0"3
FIRST FLOOR BIOMED ROUTING PLAN - DOMICILARY CLINIC
1/8" = 1'-0"1
FIRST FLOOR TELECOMMUNICATIONS ROUTING PLAN - DOMICILARY CLINIC
1/8" = 1'-0"4
ELECTRICAL ROOM 138A - BUILDING E
(2) 1-1/4" CONDUITS STUBBEDINTO CEILING SPACE WITH LONGSWEEP ELBOWS, RUN CONDUITTO CABLE TRAY ROUTING TOTELECOM ROOM, UON. PROVIDEINSULATED THROAT BUSHING ATTHE END OF EACH CONDUIT
PROVIDE WITH FLUSHMOUNTED BOX, 4" X 4" X 2-1/8"DEEP.
PROVIDE SINGLE GANG TILECOVER, UON. COVER ALLOWS FORFUTURE EXPANSION BY REMOVALOF SINGLE GANG COVER ANDREPLACING WITH TWO GANGCOVER TO ACCOMODATE FUTUREADDITIONAL SERVICE AS REQUIRED
PROVIDE SINGLE GANGCOVERPLATE WITH SIX PORTS.ONE RJ-45 PORT FOR VOICE, ANDTHREE RJ-45 FOR CAT 6 DATA,ONE BLANK PORT IS FOREXPANSION.
THREE (4) BLUE DATA CAT 6CABLES, ONE (1) GRAY VOICE CAT 6CABLE
BLANK EXPANSIONPORT
RJ-45 8-PIN MODULAR JACK CAT 6GRAY FOR VOICE AND BLUE FOR DATA
TERMINATE AND LABELPORTS AS INDICATED
HIGH IMPACT COVER PLATE
VOICE DATA
DATA DATA
1 2 3 4 5 6 7 8
RJ-45 JACK POSITIONS
W-G
G
W-O
BL W-BL
O
W-BR
BR
PAIR 3
PAIR 2
PAIR 4PAIR 1
SPARE PORT
SPARE
UPS
AMP
MIX
S
S
S
S
D
D
F
IDENTIFICATION:
HORIZONTAL CABLE MANAGEMENT
FIBER OPTIC PATCH PANEL WITH SC CONNECTORS
48 PORT PATCH PANEL FOR DATA
48 PORT PATCH PANEL FOR DATA AS REQUIRED
UNUSED
VERTICALCABLE
MANAGEMENT
UNUSED
AUDIO / VISUAL MIXER AS REQUIRED
AUDIO / VISUIAL AMPLIFIER AS REQUIRED
UPS POWER SUPPLY
(TELECOMMUNICATIONS RACK DETAIL ONLY)
UNUSED
UNUSED
NOTES:
A. ALL COMPONENTS AND TERMINATIONS TO BEPERFORMED BY THE CONTRACTOR.
B. PROVIDE 48 PORT PATCH PANELS AS REQUIRED FORDROPS SHOWN PLUS 25% FOR FUTURE EXPANSION.
C. PROVIDE FLOOR MOUNTED TELECOMMUNICATIONS RACKCOMPLETE WITH WIRE MANAGEMENT AND POWER PLUGSTRIPS WITH 12' CORD MINIMUM
(TELECOMMUNICATIONS RACK DETAIL ONLY)
CAT-6 YELLOW 4-PAIR 24AWG UTP CABLE
ALL ADDED DEVICES TO MATCHEXISTING "IDENTIV" CARDREADER SYSTEM
NOTE: ACCESS CONTROL IS TOBE ON THE HIRSCH-VELOCITYNETWORK
FASTENERS SUPPLIED
DESCRIPTION
5/16"-18 X 4 1/2" H.H.C.S.
5/16"-18 X 1"
5/16"-18
5/16"
5/16"
H.H.M.S.
HEX NUT
FLAT WASHER
LOCK WASHER
20 5/16"
16"
3/8" - 16
7"
12 1/2"
15"
18 5/16"
12 - 24
1 1/4"MOUNTING SPACES
1/2"
5"
7' - 0"
CEILING-MOUNT INTERIORNETWORK CAMERA
CONNECTION TO CCTV HEADEND EQUIPMENTIN BIOMED ROOM 233 FOR CLC ADMIN. BLDG.OR ROOM E-107 FOR DOMICILIARY CLINIC.CAT-6 YELLOW CABLE IN 1-1/4" COUNDUIT.
EXTERIOR WIDE ANGLE LENS NETWORK CAMERA.POWER PER MANUFACTURER'SRECOMMENDATION.
5. 4" SQ. JUNCTION BOX
1 1/4" THRU-WALL RIGID CONDUIT SLEEVE
CAT-6 YELLOW JACKETED CABLEIN 1 -1/4" CONDUIT
CONNECTION TO CCTV HEADEND EQUIPMENTIN BIOMED ROOM 233 FOR CLC ADMIN. BLDG.
OR ROOM E-107 FOR DOMICILIARY CLINIC.
NOTE: CCTV CABLING IS TO BE ROUTED TO NEAREST VANETWORK PATCH PANEL
TYPICAL TELECOMMUNICATIONS ROOM
19" STANDARD TELE-COMMUNICATIONS RACK
TO TMGB
6 AWG
6 AWG
3/0 AWG
18" X 4" LADDER-TYPEBASKET TRAY
TELECOMMUNICATIONSCABLING
TGB
12" X 4" WIRE MESH TYPE BASKETTRAY
6 AWG
TO MSGB
3/0 AWG
thre
e in
ches
= o
ne fo
ot6"
Department ofVeterans Affairs
one
and
one
half
inch
es =
one
foot
6"on
e in
ch =
one
foot
thre
e qu
arte
rs in
ch =
one
foot
one
half
inch
= o
ne fo
ot0
thre
e ei
ghth
s in
ch =
one
foot
0on
e qu
arte
r in
ch =
one
foot
0on
e ei
ghth
inch
= o
ne fo
ot0
10
6"0
26"
02
44
48
48
16
VA FORM 08-6231
Revisions:
1 2 3 4 5 6 7 8 9
Date:
CONSULTANTS: ARCHITECT/ENGINEERS:
590 MEANS ST NW ATLANTA, GA 30318
Drawing Title:
Approved Project Director:
Project Title:
Location:
Date: Checked: Drawn:
Drawing Number:
Building Number:
Project Number:
Dwg. of
OFFICE OFCONSTRUCTIONAND FACILITIESMANAGEMENT
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
BID DOCUMENTS
TELECOMMUNICAITONS DETAILS CONSTRUCT DOM CLINIC
AND CLC ADMINISTRATION
ADDITION
MARTINSBURG, WV
EY501
613-121
June 27, 2018 CEN HVB
6" = 1'-0"1
TYPICAL TELECOM DEVICE CONNECTION DETAIL
12" = 1'-0"5
TYPICAL COMBINATION VOICE/DATA OUTLET DETAIL 1" = 1'-0"
6TYPICAL TELECOMMUNICATIONS RACK DETAIL
6" = 1'-0"2
TYPICAL SECURITY CARD READER DETAIL
6" = 1'-0"4
TYPICAL TELECOMMUNICATIONS EQUIPMENT RACK DETAIL 12" = 1'-0"
3TYPICAL INTERIOR / EXTERIOR SECURITY CAMERA DETAILS
501D & 502F
12" = 1'-0"7
TYPICAL TELECOMMUNICATIONS ROOM GROUNDING DETAIL
IT ROOM 502F-120TELECOM ROOMD-172 D-BLDG.
BIOMED SYSTEMS DISTRIBUTION FOR DOMICILARYCLINIC
E-107 BIOMEDROOM
S
CR
TV
TO BIOMEDSYSTEMS
EQUIPMENT
4 3
6 7
2
1
TYP.DOMICILARYCORRIDOR
DATA/VOICE ONLY DISTRIBUTION FOR DOMICILARY CLINIC
5
3
TYP. D-BLDG.CORRIDOR
TYP. DOMICILARYROOM
TYP. DOMICILARY ROOM
810 10
14
44
(TYP.)
FLOOR
1
4
TELECOM ROOM 501D-101TELECOM. ROOMC130 FIRST FLOORDEMENTIA BLDG.
DATA/VOICE ONLY DISTRIBUTION FOR CLC ADMIN. BLDG.
342
1
BIOMED ROOM 233SECOND FLOOR DEMENTIA
BLDG.
EXISTINGBIOMED
SYSTEMSHEADEND
EQUIPMENT
BIOMED SYSTEMS ONLY DISTRIBUTION FOR CLC ADMIN. BLDG.
S
CR
TV
3
714
44
BIOMED ROOM 233SECOND FLOORDEMENTIA BLDG.
4
TYP. CLC ADMIN. ROOMTYP. CLC ADMIN. ROOM
9
9
6
10
8
BIOMED ROOM GA-104MAIN HOSPITAL BASEMENT
FLOOR
BIOMEDSYSTEMSHEADEND
CONNECTIONPOINT
5
(TYP.)
4
TYP. CLC ADMIN.BLDG. CORRIDORS
3
DUCTBANK
FLOOR
1
7
WAITING AREA502F-103
LOBBY502F-100
18
15
16
GROUND LEVEL
TELECOM RM. 502F-120 INTERIOR EXTERIOR
IT ROOMENTRANCECORRIDOR
502F-C1
E. WALL N.E. WALL
4
7
N.E.CORRIDOR
501D-C1
S.W.CORRIDOR
501D-C5
11
12
13
GROUND LEVEL
TELECOMMUNICATIONSROOM 501D-104
INTERIOR CLC ADMIN. BLDG. EXTERIOR
S.E. CORRIDOR501D-C1
S.E.ENTRANCE501D-100
S.E. WALL
4
NORTH AREAS.W. EXIT
AREA501D-136
W. ENTRANCE501D-136
DELIVERY GATE
EXISTINGPUBLIC
ADDRESSAMPLIFIER
S S S S
CORRIDOR B 501D-C4-1 CORRIDOR A 501D - C3 CORRIDOR B 501D-C2-2BIOMED RM 233
S
FLOOR
S S S
14
S
CORRIDOR 501D-C2-1
S S S S S
CORRIDOR 501D-105 CORRIDOR 501D-C1
(TYP.)
PUBLICADDRESSAMPLIFIER
S S S S S
WAITING AREA 502F-103 CORRIDOR A 502F-C1 CORRIDOR B502F-C2BIOMED RM E-112/E-107
S
FLOOR
14
S S
(TYP.)
FIREALARM
CONTROLSUB-
PANEL
TO MASTER FIREALARM CONTROLPANEL ELEC RM
C-119
CORR. B 501D-C4-1 CORR. 501D-C2-1 CORR. 501D-C2-2
ELEC RM 501D-104
501D-106
F F FF F
CORR. 501D-C3
F F
501D-122
F
501D-103
F
CORR. 501D-C1
F
501D-102
F F
501D-100
F F
501D-131
F F
501D-136
F F
CORR. 501D-C5
F F
17(TYP.)
FIREALARM
CONTROLSUB-
PANEL
TO MASTER FIREALARM CONTROLPANEL ELEC RM
E-138A
CORR. 501F-C4 WEST 502F-107 502F-100
ELEC RM 502F-130
502F-103
F F FF
CORR. 501D-C3
F F
501D-122
F
501D-103
F
502F-130
F
CORR. 502F-C1 EAST
F
CORR. 502F-C2
F F
17(TYP.)
F
19
thre
e in
ches
= o
ne fo
ot6"
Department ofVeterans Affairs
one
and
one
half
inch
es =
one
foot
6"on
e in
ch =
one
foot
thre
e qu
arte
rs in
ch =
one
foot
one
half
inch
= o
ne fo
ot0
thre
e ei
ghth
s in
ch =
one
foot
0on
e qu
arte
r in
ch =
one
foot
0on
e ei
ghth
inch
= o
ne fo
ot0
10
6"0
26"
02
44
48
48
16
VA FORM 08-6231
Revisions:
1 2 3 4 5 6 7 8 9
Date:
CONSULTANTS: ARCHITECT/ENGINEERS:
590 MEANS ST NW ATLANTA, GA 30318
Drawing Title:
Approved Project Director:
Project Title:
Location:
Date: Checked: Drawn:
Drawing Number:
Building Number:
Project Number:
Dwg. of
OFFICE OFCONSTRUCTIONAND FACILITIESMANAGEMENT
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
BID DOCUMENTS
TELECOMMUNICATIONS RISER DIAGRAMS CONSTRUCT DOM CLINIC
AND CLC ADMINISTRATION
ADDITION
MARTINSBURG, WV
EY701
613-121
June 27, 2018 CEN HVB
6" = 1'-0"1
TELECOM RISER DIAGRAM - DOMICILARY CLINIC 6" = 1'-0"
2TELECOM RISER DIAGRAM - CLC ADMINISTRATION
KEY NOTES1 19" X 84" EQUIPMENT RACK. PROVIDE ONLY FOR NEW
TELECOMMUNICATIONS ROOM(S).
2 PROVIDE LADDER TYPE CABLE TRAY ABOVE EQUIPMENTRACK AS INDICATED ON ENLARGED TELECOM ROOM VIEWS,SEE EY101 AND EY102.
3 PROVIDE BASKET TYPE WIRE MESH CABLE TRAY ASINDICATED ON PLANS.
4 PROVIDE THROUGH WALL SLEEVE / CONDUITS ASINDICATED ON PLANS.
5 PROVIDE COUNDUIT AND CABLING AS INDICATED IN DETAIL 1ON SHEET EY501.
6 PROVIDE ONE (1) 3/4" CONDUIT WITH ONE (1) PURPLE CAT 6,24 AWG, 4 PAIR SOLID COPPER UTP CABLE.
7 SEE NOTE 6.
8 PROVIDE ONE (1) 3/4" CONDUIT WITH ONE (1) YELLOW CAT 6,24 AWG, 4 PAIR SOLID COPPER UTP CABLE.
9 PROVIDE CABLING AND CONDUITS AS INDICATED ON PLANS.
10 SEE NOTE 9.
11 CCTV PORTS IN PATCH PANEL IN TELECOMMUNICATIONSROOM 501D-101. CCTV HEAD END CONTROLLER CABINET ISLOCATED IN BIOMED ROOM GA104.
12 INPUT CONTROL FROM MASTER STATION IN BIOMED RM 233VIA JUNCTION BOX,
13 OUTPUT TO MASTER CONTROL MONITOR IN BIOMED RM 233VIA JUNCTION BOX.
14 PROVIDE ONE (1) 3/4" CONDUIT WITH 12AWG SOLID SPEAKERWIRE AS REQUIRED BY MANUFACTURER.
15 INPUT CONTROL FROM MASTER STA. IN BIOMED RME112/E107 VIA JUNCTION BOX
16 OUTPUT TO MASTER CONTROL MONITOR IN BIOMED RME112/E107 VIA JUNCTION BOX
17 PROVIDE ONE (1) 3/4" CONDUIT WITH 14AWG SOLID FIREALARM WIRE AS REQUIRED.
18 CCTV PORTS IN PATCH PANEL IN TELECOMMUNICATIONSROOM 502F-120. CCTV HEAD END CONTROLLER CABINET ISLOCATED IN BIOMED AREA IN ROOM 502F-130.
19 PROVIDE FIRE ALARM WIRE IN CONDUIT AS REQUIRED.
12" = 1'-0"3
CCTV RISER DIAGRAM - DOMICILARY CLINIC 12" = 1'-0"
4CCTV RISER DIAGRAM - CLC ADMINISTRATION
501D & 502F
#
12" = 1'-0"5
PA RISER DIAGRAM - CLC ADMINISTRATION
12" = 1'-0"6
PA RISER DIAGRAM - DOMICILARY CLINIC
12" = 1'-0"7
FIRE ALARM RISER - CLC ADMINISTRATION 12" = 1'-0"
8FIRE ALARM RISER - DOMICILIARY CLINIC