Electrical Notes & Articles _ Sharing Abstracts,Notes on Various Electrical Engineering Topics
description
Transcript of Electrical Notes & Articles _ Sharing Abstracts,Notes on Various Electrical Engineering Topics
-
ElectricalNotes&Articles
SharingAbstracts,NotesonvariousElectricalEngineeringTopics.
SelectionofSurgeProtectiveDevice(SPD)(Part3)
JULY6,2015 2COMMENTS(HTTPS://ELECTRICALNOTES.WORDPRESS.COM/2015/07/06/SELECTIONOFSURGEPROTECTIVEDEVICESPDPART3/#COMMENTS)
i4Votes
TypeofSPD:
Type1SPD:
Protectionfor:TransientOvervoltagesduetoDirectLightningStrokesLocation:Itisinstalledatanylocationbetweenthesecondaryoftheutilityservicetransformerandtheserviceentranceprimarydisconnection
Itisinstalledinthemainelectricalswitchboardwhenthebuildingisequippedwithalightningprotectionsystem.Itprotectsagainstexternalsurgescausedbylightningorutilitycapacitorbankswitching.Thesedevicestodischargingaveryhighlightningcurrentfromearthtothepowerdistributionsystem.
-
Currentratings:10Kato35Ka10/350swaveform.
RequiredDedicatedFuse/CircuitBreakerforSPD:NoRiskFactor:VerystrongriskArea
Type2SPD:
Protectionfor:TransientOvervoltagesduetoSwitchingandIndirectLightningStroke.Location:Itisinstalledinthemaindistributionswitchboard.
Itisdesignedtodischargethecurrentsgeneratedbyindirectlightningstrokesandcausinginducedorconductedovervoltageonthepowerdistributionnetwork.Itprotectsagainstresiduallightningenergy,motordrivensurgesandotherinternallygeneratedsurges.
Currentratings:5Kato200Ka8/20swaveform.RequiredDedicatedFuse/CircuitBreakerforSPD:MayorMayNot
RiskFactor:CommonriskArea
Type3SPD:
Protectionfor:SensitiveLoads.ItisinstalledasasupplementtoType2devicesandtoreducetheovervoltageattheterminalsofsensitiveequipment.Theircurrentdischargecapacityisverylimited.Asaconsequencetheycannotbeusedalone.Installedatminimumconductorlengthof10meters(30feet)fromtheelectricalservicepaneltothepointofutilizationProvidespointofuseprotection,easilyreplaceableanditprovidesthelastlineofdefenseagainstalightningstrike.RiskFactor:Verystrong&commonriskArea
ConnectionofSPDinDistributionBox.
Incommonmode:PhasetoearthorneutraltoearthIndifferentialmode:Phasetophaseorphasetoneutral
-
(https://electricalnotes.files.wordpress.com/2015/07/0.png)
FactorseffectonSPDPerformance:
(1)LocationofSurgeProtectionDevice:
LightningprotectionshouldbeinstalledonaoverallviewpointofProtection.Forlargeindustrialplants,datacenters,hospitals,ariskassessmentmethodmustbeusedtoguideinchoosingoptimaldistance.Inothercaseslikehousing,offices,buildingsWherethereisnotorlesssensitiveindustrialrisks,wemayadoptfollowingprincipletoselectSPD.Type2surgeprotectivedeviceshouldbeinstalledintheelectricalinstallationsincomingMainswitchboard.Ifthedistancebetweenthatsurgeprotectivedeviceandtheequipmenttobeprotectedismorethan30meters,thanadditionalsurgeprotectivedevice(Type2orType3)shouldbeinstalledneartheequipment.
-
(https://electricalnotes.files.wordpress.com/2015/07/1.png)
Whenthebuildingisequippedwithalightningprotectionsystem,aType1surgeprotectivedevicemustbeinstalledattheincomingMainSwitchBoard.ThereexistsurgeprotectivedevicescombiningType1andType2inthesameenclosure.
(https://electricalnotes.files.wordpress.com/2015/07/2.png)
TheLightningrodshavetobelocatedonthehighestpointsofthestructure,takingintoaccountthelocationofthegrounding,andthatthepathofthedownconductorsareasshortandstraightaspossible.
(2)SizeofDownConductor:
Lightningisaphenomenonthatgeneratesahighfrequencyvoltage.Thelengthofthecablesmustbetakenintoaccountincasesofhighfrequency.Thedownconductorsmaybetapes,strandedwireorsolidround.Theminimumcrosssectionmustbe1meterofcablecrossedbyalightningcurrentgeneratesanovervoltageof1,000V.MandatoryinStandardIEC603645534:L(lengthofcables)
-
(4)NumberofDownConductor
Atleastonedownconductorforeverylightningrod.Aminimumoftwodownconductorwhen,(1)ThehorizontalProjectionlengthoftheconductorexceedsitsverticalprojectionlength.(2)Theheightofthestructureisgreaterthan28meter.Equipotentialbondingwillbemadebetweentheconductorsatgroundlevelandevery20meters.AccordingtoUNE21186:(1)Eachlightningrodshallbegroundedbytwodownconductor.(2)Itwillbenecessary4downconductorsonbuildingshigherthan60meters.(3)Itshouldbeplacedwheneverpossibleinthe4cornersofthebuilding.
(5)PathofDownConductor
Thedownconductorrouteswilltheshortestpath,straightanddirecttogrounding.Weshouldavoidingelevationsabove40cmwithslopeequaltoorgreaterthan45.Theradiiofcurvesshallnotbelessthan20cmanddirectionchangeslessthan90.Theroutewillbechosensoastoavoidproximitytoelectricalconduits,telephone,dataanditscrossingwiththem.Inanycase,whenwecannotavoidanintersectionconduitsmustbeplacedinsideametallicshieldthatextended1mtoeachsideofthecrossing,andtheshieldshouldbindtothedownconductor.
(6)SafetyDistance:
AccordingCTESU8:Safetydistance(m)=0.1xLL=verticaldistancefromthepointwhereitisconsideredtheproximitytothegroundingofthemetalmassSafetydistancetooutdoorgaspipelines5m.AccordingtoUNE21186:Safetydistancefor1noofdownconductor(m)=0.16xLSafetydistancefor2Noofdownconductors(m)=0.08xLSafetydistancefor4Noofdownconductors(m)=0.04xLL=lengthofthedownconductorfromthepointwhereitisconsideredtheseparationdistancetothepointwhereislocatedthenearestequipotentialpoint.
-
(7)Earthing:
Therewillbe1groundingsystemforeachdownconductor.
(8)LightingCounter:
Thelightningcountermustbeinstalledoverthemoredirectdownconductor,abovethejointcontrol,andinallcases,about2metersabovetheground.
(9)SizeofSurgeProtectionDevice:
Atype2surgeprotectivedevicedependsmainlyontheexposurezone(moderate,medium,high).Type2SPDhasdischargecapacity(Imax)of20kA,40kA,65kA(8/20s).Type1SPDhasminimumdischargecapacity(Imax)of12.5kA(10/350).Highervaluesmayberequiredbytheriskassessmentwhenitsrequired.Forresidentialorlightcommerciallocations:asurgecurrentratingof20kAto70kA(8/20s)perphaseshouldbesufficient.InstallationsinForhighlightningareas:SPDswithhighersurgecurrentratingsof40kAto120kA,toprovidealongerservicelifeandhigherreliability.
FILEDUNDERUNCATEGORIZED
SelectionofSurgeProtectiveDevice(SPD)(Part2)
JUNE7,2015 6COMMENTS(HTTPS://ELECTRICALNOTES.WORDPRESS.COM/2015/06/07/SELECTIONOFSURGEPROTECTIVEDEVICESPDPART2/#COMMENTS)
-
i11Votes
SizeofSurgeProtectionDevice(SPD)dependsuponLocationofPanel:
Panellocationwithintheelectricalsystemismoreimportantthanthepanelssize.Thelocationofthepanelwithinthefacilityismuchmoreimportant.IEEEC62.41.2definesthetypesofexpectedsurgeswithinafacilityas:CategoryC:ServiceEntrance,moresevereenvironment:10kV,10kAsurgeCategoryB:Downstreammorethan30feetfromcategoryC,lesssevereenvironment:6kV,3kAsurgeCategoryA:Furtherdownstream,morethan60feetfromcategoryC,leastsevereenvironment:6kV,0.5kAsurgeWhenselectingtheappropriatekAratingforanSPD.CategoryC:100kAto200kAperphaseCategoryB:50kAto100kAperphaseCategoryA:50kAto100kAperphase
LargeSizeofSurgeProtectionDevice(SPD)doesnotgivebetterProtection:
MostSPDsuseametaloxidevaristor(MOV)asthemainlimitingdevice.IfanMOVisratedfor10kAandhavinga10kAsurge,itwoulduse100%ofitscapacity.ThesurgewilldegradetheMOValittlebit.Nowifweuse20KASPDsothisSPDhastwo10kAMOVsinparallel.TheMOVswillequallysplitthe10kAsurge,soeachwouldtake5kA.Inthiscase,eachMOVhaveonlyused50%oftheircapacitywhichdegradestheMOVmuchlessthan10KASPDAgainItistotallymisleadingthattwoparallelpath(in20KASPD)absorbsurgefasterorbetterthansinglepathSPD(like10KASPD)ofsamerating.ThemainpurposeofhavingMOVsinparallelistoincreasethelongevityorLifeoftheSPD.Again,Itisneedtoclearthatitissubjectiveandatsomepointweareonlyaddingcostby
-
incorporatingmoreMOVsandreceivinglittlebenefit.LargerkAratingsareforredundancy&longerlifeonly.
SPDcannotgive100%ProtectionagainstAllTypesofelectricaldisturbance
ThereisamisconceptionaboutSPDsisthattheyaredesignedtoprotectagainstallElectricalproblems.SPDisnotdesignedtoprotectagainstexcessivevoltageatthefundamentalpowerfrequency.Itisdesigntogiveprotectionagainstsurges(bydirectlightingorvoltagesurgesinlineatremotelocation).SPDcannotgiveProtectionagainstPoorPowerQuality(Harmonics)SomeSPDscontainfilteringtoremovehighfrequencynoise(50kHzto250kHz),ButSPDcannotfilterharmonicloads(3rdthrough50thharmonicequals180to3000Hz).SPDcannotgiveProtectionagainstUnderVoltage.SPDcannotgiveprotectionagainstundervoltageproblems.SPDcannotgiveProtectionagainstdirectlightingStrikes.AnSPDcannotpreventdamagecausedbyadirectlightningstrike.AdirectlightningstrikecausesinducedsurgesonthepowerlinethatarereducedbytheSPDButSPDcannotProtectagainstLightingStrikesnearSPDLocation.SPDcannotgiveprotectionagainsttemporaryovervoltage.Temporaryovervoltageiscausedbyaseverefaultintheutilitypowerorduetoproblemswiththeground(poorornonexistentNGbond).TemporaryovervoltageoccurswhentheVoltageexceedsthenominalvoltageforashortduration(millisecondtoafewminutes).Ifthevoltageexceeds25%ofthenominalsystemvoltage,theSPDandotherloadsmaybecomedamaged.
SelectionofSurgeProtectiondevice(SPD):
TheSize,performanceandspecificationofSPDdependonfollowingcharacteristics
CurrentcharacteristicofSPD
I:SurgeCurrentRating(KA),In:NominalDischargeCurrent(In),Imax:MaximumdischargeCurrent(Imax)
-
ShortCircuitCurrentRating(SCCR).
VoltagecharacteristicofSPD
Uc:MaximumContinuousOperatingVoltage(MCOV),Up:VoltageProtectionRating(VPR)orsurgevoltagerating(SVR)orClampingVoltage.TOV:TemporaryOverVoltage.
(1)SurgeCurrentRatings(I):
ThepeaksurgecurrentratingsofSPDaregenerallybasedonthesumofLineneutralandLinegroundcurrent.Apeakampereratingperphase.(I.e.LN100kA,LG100kAprovides200kA/phase).OtherSpecificationlikeMCOV,VPR,InandSCCRthathaveclearlydefinedtestcriteria,butforSurgeCurrentthereisnospecifiedTestCriteriaorindustrystandardhencedifferentSPDmanufacturerstocreatetheirowndefinitionsofpeakamperesurgecurrentratings.PleasenotethatselectionofHigherSurgeCurrentRatingsdontalwaysgivesBetterProtectionbutitisprovidelonerlife.IEEEClearlystatesthatTheselectionofasurgecurrentratingforanSPDshouldbematchedtotheexpectedsurgeenvironmentandtheexpectedordesiredusefullifeofthedevice.SelectionofSurgeRatingforanSPDdependsonThelocationoftheSPDwithintheelectricaldistribution&environmentalsurroundingsconditionofSite.FollowingsurgecurrentratingsbasedonSPDlocationwithintheelectricaldistribution.
SurgecurrentratingsbasedonSPDlocation
Location SurgeCurrent
ServiceEntranceLocations 240kA
DistributionLocations 120KAto160kA
BranchLocations 50KAto120kA
(2)Nominaldischargecurrentrating(In):
TheNominalDischargeCurrentisthepeakvalueofsurgecurrentconductedthroughtheSPD.Ithas8/20sImpulsecurrentWaveform.TheSPDmustfunctionafter15appliedsurges.
-
NominaldischargeCurrentshowsdurabilityofSPD.Thehighestnominaldischargecurrentratingis20kA.Example:calculateInforMaximumpeakcurrent(SurgeCurrent):I=200kA(themaximumlevelofnaturallightningwhere5%ofstrikesarebiggerthan100kA)Assumethatforperfectcurrentsharing50%togroundand50%totheelectricalnetworkNetworkconfigurationis3Phases+Neutral(n=4)In=SurgeCurrentXCurrentpathtoGround(%)/NoofPath=200x0.5/4=25kATheNominaldischargecurrentvalues,witha8/20swaveshapeasperUL1449areType1SPD(In)=10KAor20kAType2SPD(In)=3KA,5KA,10KAor20kATheNominaldischargecurrentvalueasperIEEEC62.41is200Ato10KA.TheNominaldischargecurrentvalueasperNFPAis20KA
(3)Maximumdischargecurrent(lmax):
ThemaximumsurgecurrentbetweenanyonephaseandneutralthattheSPDcanwithstandforasinglestrikeof8/20sor10/350scurrentiscalledMaximumdischargecurrentofSPD.Thisisthemaximumvalueofasurgecurrentthatcanbedivertedbythesurgeprotectivedevice.currentsurgeshavetwodifferentwaveshapesLightningcurrentsisalongwaveshape(10/350s)whichrepresentsdirectlightningstrike.Shortwaveshape(8/20s)whichrepresentsaindirectstrike;lmaxisthemaximumvalueofashortwaveshapecurrentandlimpisthevalueofalongwaveshapecurrent;thevaluelmaxorlimphastobeadaptedtotheexpectedvalueofthepossiblelightningcurrents.Imax>In
(4)Shortcircuitcurrentrating(SCCR):
Maximumsymmetricalfaultcurrent,atratedvoltage,thattheSPDcanwithstandwithoutsustainingdamageiscalledSCCRofSPD.Everyelectricalsystemhasanavailableshortcircuitcurrent.Thisistheamountofcurrentthatcanbedeliveredbythesystemataparticularpointinashortcircuitsituation.SCCRshoesthatMeasureofhowmuchcurrenttheelectricalutilitycansupplyduringafaultcondition.SCCRisnotasurgeratingbutitisthemaximumallowablecurrentaSPDcaninterruptintheeventofafailure.NECArticle285.6saysthattheSPDtobeinstalledwheretheavailablefaultcurrentislessthantheSCCRratingoftheSPDunit.
-
Typicalavailableshortcircuitcurrents
Load shortcircuitcurrentsofSPD
Residential 5KAto10kA
Smallcommercial 14KAto42kA
Largecommercial/industrial 42kAto65kA
Largeindustrial/utility/downtowninlargecities 100kAto200kA
Atasubpanel 120kAto160kAprovidesgoodprotectionandlife
PointofuseSPDs80kAto100kAperformwell
(5)CalculatingMaximumContinuousOperatingVoltage(MCOVorUc):
WhenSurgeProtectorareinstalledtoprotectsystemsfromlightningorswitchingsurges,itshouldbeinstalledbetweenthephaseandearth.HenceMCOVoftheinstalledarrestermustbeequalorhighertothecontinuousvoltagebetweenthephaseandearth.Onthreephasesystems,thelinetogroundvoltageisequaltothephasetophasevoltagedividedby1.73Forexample:ona440kVtransmissionsystem,thenominalsystemphasetophasevoltageis440kVthereforethelinetoearthvoltagewouldbe440/1.73=254kV.Sinceallsystemshavesomeregulationerror.Iftheregulationis10%,thenthelinetogroundvoltagecouldbe254x1.10=280kV.TheMCOVorUcoranarresterforthissystemataminimumshouldbe280kV.
TypicalMCOVs
System MCOV
120Vsystem 150VMCOV
240Vsystem 320VMCOV
480Vsystem 550VMCOV
SelectingSPDwithtoolowofavoltageratingwillresultinSPDfailureSelectingSPDwithtoohighofavoltageratingwillresultinreducedprotection
-
(6)CalculatingLinetoGroundVoltage:
ThemaximumrmsvoltagethatcanbeappliedtoeachmodeoftheSPDiscalledMCOVWhenathreephasepowersystemhaveafaultbetweenoneofthePhasetoearth,theVoltageoftwohealthyphasestogroundincrease.SinceArrestorismostlyconnectbetweenPhaseandEarthhenceVoltageacrossLAterminalsalsoIncrease.Thisincreaseinvoltagewillremainacrossthearresteruntilasystembreakeroperatesandbreaksorinterruptsthefault.Thisisaverysignificanteventinthelifeofanarresterandmustbeaccountedforduringthevoltageratingselectionofanarrester.Therearesomerulesofthumbandgraphsthatcanbeused,butthesearequitcrudeanddifficultatbesttouse.AnnexCofIEEEstandardC62.22andAnnexAofIEC600995coverthissubject.Fordistributionsystemswherethesystemandtransformerimpedancesarerelativelyunknown,aworstcasescenarioisusedforeachtypeofsystem.Thevoltageriseduringafaultinthesecasesisdeterminedbymultiplyingthelinetogroundvoltageby
TypeofSystem GroundFaultFactor
SolidlyGrounded4wiresystems 1.25
Unigrounded3wiresystems 1.4
Impedancegroundedsystems 1.73
IsolatedGroundSystemsandDeltaSystems 1.73
Forexample:Ina440kVmultigroundedsystem,themaximumcontinuouslinetogroundvoltage=PhasetoPhaseVoltage/1.73=440/1.73=254kV.Thevoltageduringagroundfaultontheunfaultedphasescanreach254x1.25or=318kVrms.Thisisthevoltageanarresterwillseeacrossitsterminalsforaslongasthefaultexists.
(7)Voltageprotectionlevel(UPatIn):
ThisisthemaximumvoltageacrosstheterminalsoftheSPDwhenitisactive.ThisvoltageisreachedwhenthecurrentflowingintheSPDisequaltoNominaldischargecurrent(In).Thevoltageprotectionlevelmustbebelowtheovervoltagewithstandcapabilityoftheloads.Intheeventoflightningstrokes,thevoltageacrosstheterminalsoftheSPDgenerallyremainslessthanUp.WhiledivertingthesurgecurrenttothegroundVoltageProtectionLevel(Up)mustnotexceed
-
thevoltagewithstandvalueoftheequipmentconnecteddownstream.SuppressedVoltageRating(SVR)waspartofanearlierversionofUL1449EditionandisnolongerusedintheUL1449standard.TheSVRwasreplacedbyVPR.
(8)TemporaryOverVoltage(TOV):
ItisusedtodescribetemporarySurgewhichcanariseasafaultoffaultswithinmedium&Lowvoltage.UTov=1.45XUo,whereUo=NominalLinetoearthVoltage.For230/440VSystemUTov=1.45X230=333.33Volt
FILEDUNDERUNCATEGORIZED
SelectionofSurgeProtectiveDevice(SPD)(Part1)
MAY30,2015 9COMMENTS(HTTPS://ELECTRICALNOTES.WORDPRESS.COM/2015/05/30/SELECTIONOFSURGEPROTECTIVEDEVICESPDPART1/#COMMENTS)
i6Votes
Introduction:
AdevicewhichdivertsorlimitssurgecurrentiscalledSurgeprotectivedevices(SPD).SPDprotectelectricalequipmentagainstovervoltagescausedbylightningorSwitching.Itiswiredinparalleltotheequipmentwhichisneededtobeprotected.OncethesurgevoltageexceedsSPDsratingitstartstoconductenergydirectlytotheelectrical
-
groundingsystem.AnSPDhasaverylowresistanceduringthistimeandgivelowresistancepaththeenergytoground.Oncethesurgeisoveritgiveshighresistancepathtocurrent.SPDispreviouslyknownasTransientVoltageSurgeSuppressors(TVS)orSecondarySurgeArresters.Underwriterlaboratories,UL1449ListedSPDsarenowdesignatedaseitherType1,Type2orType3andintendedforuseonACpowersystemsratedLessthan1000vrms
Principle:
SPDisusedtolimittransientovervoltagesofatmosphericorSwitchingSurgeandgivespathtotheexcessivecurrenttoearthhencelimittheovervoltagetoavaluethatisnothazardousfortheelectricalinstallation.
CausesofSurges:
(1)ExternalSurge:lightningstrikes:DirectStroke,IndirectStroke(2)InternalSurge:SwitchingSurge:Switchingon/offofinductiveloads.Trippedcircuitbreakersandfuses.Shortcircuits.Malfunctionscausedbythepowercompany.InsulationFailures:ArcingGround:Ignitionandinterruptiontoelectricarc.
DifferencebetweenSurgearrestor(LightingArrestor)andSurgeSuppressor:
SurgearrestersandSurgeSuppressorbothareusedtoprotectequipmentfromsurges.But,thereisconfusionbetweentheapplicationofsurgearrestors/Lightingarrestorandsurgesuppressors.Themaindifferencesbetweenalightningarresterandasurgearresterareitsfaultclearingtimeanditsposition
-
Botharedoingthesamejob,butstillbotharenotsame.
LightingArrestor/SurgeArrestor:
SurgeArrestersarewidelyalsoknownLightningarresters.SurgearrestersaredevicesinstalledonOverheadlines,substationsetctoavoidaLightingsurgeandotherSurgesofanadditionalcurrent/voltage/chargeduetovariousfaultsoccurring.Inthepastyearwhennonlinear/solidstatedevices(computers,PLCanddrives)werenotused.TheElectricalLoadismostlyLinearLoad.Utilitycompaniesandenduserswereconcernedwithhowtoprotectelectricaldistributionsystemsfromlightningsurgestoensurethatvoltagesurgesdidnotexceedthebasicinsulationlevel(BIL)oftheconductorwires,transformersandotherequipment.HenceSurgearrestors/Lightingarrestorsweredevelopedforuseinlow,mediumandhighvoltageapplicationsatvariouspointsinthetransmissionanddistributionsystem.SurgeArrestorprovidelowresistancepathbetweenthephaseconductorandground.LAdidnotconcernwiththeloadsifitclearedwithinafewcycles.Arrestorsarestillusedintheelectricalindustryprimarilyalongthetransmissionlinesandupstreamofafacilitysserviceentrance.Arrestorsareavailableinvariousclassesdependingupontheirwithstandcapability(e.g.,stationvs.distributionclass).Attheserviceentrancelocationonlowvoltagesystems(600Vandbelow),Lightningarrestorsweredesignedtoprotecttheelectricaldistributionsystemandnotthesensitivesolidstateequipment.Economically,surgearrestersarebetterthansurgeDifferentsurgearrestersareavailablebasedontheirwithstandingcapability.Themainproblemwiththemisthattheyaredesignedforprotectinglargeelectricaldistributionsystemsfromlightningsurges,andnotforsensitivesolidstateequipment.Applications:Thesurgearresterisbesttoprotectinsulationoftransformers,panelboards,andwirings.However,itdoesntworkwellforsolidstatecomponents.
SurgeSuppressor/SurgeProtector(calledTVSS):
Intodayswemostlyusesolidstate(nonlinear)loadslikeelectronicequipment,drives,PLCs,computers,electronicballasts,telecommunicationequipment.NonLinearisabout70%ofutilityloads.Thesolidstatecomponentswillbedamagedbythesurges.UsingSurgesuppressorsattheserviceentranceandkeybranchpanels,thesurgewillbeeffectivelyreducedtounder100V.IfaTVSSandlightningarrestorarebothusedataserviceentranceswitchboard,theTVSSwillturnonearlierandshuntmostofthesurgecurrent.Manywatertreatmentplants,telecommunicationfacilities,hospitals,schoolsandheavyindustrialplantsutilizeTVSSsinsteadofsurgearrestorstoprovideprotectionagainsttheeffectsoflightning,utilityswitching,switchingelectricmotors.Applications:Theyareusedinwatertreatmentplants,hospitals,schools,andtelecommunicationfacilities.
-
SizeofSurgeProtectionDevice(SPD)doesnotdependonPanelSize:
ThekAratingofanSPD(surgerating)isoneofthemostmisleadingterms.Wenormallyuse50KASPDtoprotect50KApanel.ThekAratingofthesurgearrestershasnothingtodowiththefaultcurrentratingofelectricaldistributionboard.Wecanfita40kAsurgearresterinadomesticboardwithafaultcurrentratingoflessthan5kAWhenasurgeentersapanel,itdoesnotknowthesizeofthepanel.SoItistotallymiscalculationforuse50KASPDfor50KAPanelThereisanormalPracticethatlargerpanelsneedlargerSPD,butsurgesareindifferenttopanelsize.Thelargestsurgethatcanenterabuildingswiringis10kA,asexplainedintheIEEEC62.41standard.SowhywouldweneedaSPDratedfor100KAor200kA.
FILEDUNDERUNCATEGORIZED
VariousRoutineTestofPowerTransformer(Part4)
APRIL13,2015 13COMMENTS(HTTPS://ELECTRICALNOTES.WORDPRESS.COM/2015/04/13/VARIOUSROUTINETESTOFPOWERTRANSFORMERPART4/#COMMENTS)
i9Votes
(9)MagneticBalanceTest
-
TestPurpose:
Magneticbalancetestoftransformerisconductedonlyonthreephasetransformerstochecktheimbalanceinthemagneticcircuit.
TestInstrument:
Multimeter.MillAmmeter
TestCircuitDiagram:
(https://electricalnotes.files.wordpress.com/2014/09/untitled10.png)
TestProcedure:
Firstkeepthetapchangeroftransformerinnormalposition.Nowdisconnectthetransformerneutralfromground.Thenapplysinglephase230VACsupplyacrossoneoftheHVwindingterminalsandneutralterminal.MeasurethevoltageintwootherHVterminalsinrespectofneutralterminal.Repeatthetestforeachofthethreephases.Incaseofautotransformer,magneticbalancetestoftransformershouldberepeatedforIVwindingalso.Therearethreelimbssidebysideinacoreoftransformer.Onephasewindingiswoundinonelimb.Thevoltageinducedindifferentphasesdependsupontherespectivepositionofthelimbinthecore.Thevoltageinducedindifferentphasesoftransformerinrespecttoneutralterminalsgiveninthetablebelow.415V,TwophasesupplyistobeappliedtoanytwophasesterminalsonHVsideofPowertransformerandvoltagesinothertwophasecombinationaretobemeasuredwithLTopen.SumoftheResultanttwovaluesshallbeequaltothevoltageapplied.
-
AppliedVoltage(415V) MeasuredVoltage(V1)
MeasuredVoltage(V2) Result
RY YB BR V=V1+V2
YB RY BR V=V1+V2
BR YB RY V=V1+V2
(10)HighVoltagetestsonHV&LVWinding:
TestPurpose:
TocheckstheinsulationpropertybetweenPrimarytoearth,SecondarytoearthandbetweenPrimary&Secondary.
TestInstrument:
HighVoltagetester(100KV&3KV)
TestCircuitDiagram:
(https://electricalnotes.files.wordpress.com/2014/09/untitled11.png)TestProcedure:
HVhighvoltagetest:LVwindingconnectedtogetherandearthed.HVwindingconnectedtogetherandgivenFollowingHVSupplyfor1minute.
-
LVhighVoltagetest:HVwindingconnectedtogetherandearthed.LVwindingconnectedtogetherandgivenFollowingHVSupplyfor1minute.433VWinding=3KVHighVoltage11KVWinding=28KVHighVoltage22KVWinding=50KVHighVoltage33KVWinding=70KVHighVoltage.
(11)DielectricalTest:
TestPurpose:
TochecktheabilityofmaininsulationtoearthandbetweenwindingTocheckstheinsulationpropertybetweenPrimarytoearth,SecondarytoearthandbetweenPrimary&Secondary.
TestInstruments:
3PhaseVariableVoltage&FrequencySource.AutoTransformer.
TestProcedure:
ThefollowingDielectrictestsareperformedinordertomeetthetransformerinsulationstrengthexpectations.Switchingimpulsetest:toconfirmtheinsulationofthetransformerterminalsandwindingstotheearthedpartsandotherwindings,andtoconfirmtheinsulationstrengthinthewindingsandthroughthewindings.Lightningimpulsetest:toconfirmthetransformerinsulationstrengthincaseofalightninghittingtheconnectionterminalsSeparatesourceACwithstandvoltagetest:toconfirmtheinsulationstrengthofthetransformerlineandneutralconnectionterminalsandtheconnectedwindingstotheearthedpartsandotherwindings.InducedACvoltagetest(shortdurationACSDandlongdurationACLD):toconfirmtheinsulationstrengthofthetransformerconnectionterminalsandtheconnectedwindingstotheearthedpartsandotherwindings,bothbetweenthephasesandthroughthewinding.Partialdischargemeasurement:toconfirmthepartialdischargebelowadeterminedlevelpropertyofthetransformerinsulationstructureunderoperatingconditions.
MethodNo1(separatesourcevoltagewithstandtest)
-
(https://electricalnotes.files.wordpress.com/2014/09/untitled12.png)
Alltheterminalsofthewindingundertestshouldbeconnectedtogetherandthevoltageshouldbeapplied.Thesecondarywindingsofbushingtypecurrenttransformersshouldbeconnectedtogetherandearthed.Thecurrentshouldbestableduringtestandnosurgesshouldoccur.Asinglephasepowerfrequencyvoltageofshapeapproximatelysinusoidalisappliedfor60secondstotheterminalsofthewindingundertest.Thetestshallbeperformedonallthewindingsonebyone.Thetestissuccessfulifnobreakdowninthedielectricoftheinsulationoccursduringtest.DuringtheSeparatesourceACwithstandvoltagetest,thefrequencyofthetestvoltageshouldbeequaltothetransformersratedfrequencyorshouldbenotlessthan80%ofthisfrequency.Inthisway,60Hztransformerscanalsobetestedat50Hz.Theshapeofthevoltageshouldbesinglephaseandsinusoidalasfaraspossible.Thistestisappliedtothestarpoint(neutralpoint)ofuniforminsulatedwindingsandgradual(nonuniform)insulationwindings.Everypointofthewindingwhichtestvoltagehasbeenappliedisacceptedtobetestedwiththisvoltage.Thetestvoltageismeasuredwiththehelpofavoltagedivider.Thetestvoltageshouldbereadfromvoltmeteraspeakvaluedividedby2.Testperiodis1minute.
MethodNo2(Inducedsourcevoltagewithstandtest)
-
(https://electricalnotes.files.wordpress.com/2014/09/untitled13.png)
TheaimofthistestistochecktheinsulationbothbetweenphasesandbetweenturnsofthewindingsandalsotheinsulationbetweentheinputterminalsofthegradedinsulationwindingsandearthDuringtest,normallythetestvoltageisappliedtothelowvoltagewinding.MeanwhileHVwindingsshouldbekeepingopenandearthedfromacommonpoint.Sincethetestvoltagewillbemuchhigherthanthetransformersratedvoltage,thetestfrequencyshouldnotbelessthantwicetheratedfrequencyvalue,inordertoavoidoversaturationofthetransformercore.Thetestshallstartwithavoltagelowerthan1/3thefulltestvoltageanditshallbequicklyincreaseduptodesiredvalue.ThetestvoltagecaneitherbemeasuredonavoltagedividerconnectedtotheHVterminaloronavoltagetransformerandvoltmeterwhichhavebeensettogetherwiththisvoltagedividerattheLVside.Anothermethodistomeasurethetestvoltagewithapeakvaluemeasuringinstrumentatthemeasuringtapendofthecapacitortypebushing(ifany).Testperiodwhichshouldnotbelessthan15seconds.Itiscalculatedaccording,Testperiod=120secondsx(Ratedfrequency/Testfrequency)Thedurationofthetestshallbe60second.Thetestisacceptedtobesuccessfulifnosurges,voltagecollapsesorextremeincreasesinthecurrenthaveoccurred.
AcceptanceCriteria:
Thetestissuccessfulifnobreakdownoccursatfulltestvoltageduringtest.
MethodNo3LightingImpulseTest:
AllthedielectrictestschecktheinsulationleveloftheTransformer.Impulsegeneratorisusedtoproducethespecifiedvoltageimpulsewaveof1.2/50microsecondswaveOneimpulseofareducedvoltagebetween50to75%ofthefulltestvoltageandsubsequentthreeimpulsesatfullvoltage.Forathreephasetransformer,impulseiscarriedoutonallthreephasesinsuccession.Thevoltageisappliedoneachofthelineterminalinsuccession,keepingtheotherterminalsearthed.Thecurrentandvoltagewaveshapesarerecordedontheoscilloscopeandanydistortioninthewaveshapeisthecriteriaforfailure.
FILEDUNDERUNCATEGORIZED
VariousRoutineTestofPowerTransformer(Part3)
-
MARCH5,2015 10COMMENTS(HTTPS://ELECTRICALNOTES.WORDPRESS.COM/2015/03/05/VARIOUSROUTINETESTOFPOWERTRANSFORMERPART3/#COMMENTS)
i11Votes
(5)ShortCircuitTest
TestPurpose:
ThevalueoftheshortcircuitimpedanceZ%andtheload(copper)losses(I2R)areobtained.Thistestshouldbeperformedbeforetheimpulsetestifthelaterwillbeperformedasaroutinetestinordertoavoidreadingserrors
TestInstrument:
MeggerorMultimeter.CT,PT
TestProcedure:
SuitableLowVoltage(3phase415V,50Hz)willbeappliedtotheterminalsofonewinding(usuallytheH.V.)withtheotherwindingshortcircuitedwith50sq.mm.Coppercable.(UsuallytheL.V.)Theappliedvoltageisadjustedtopasstheneededcurrentintheprimary/secondary.Inordertosimulateconditionsnearesttofullload,itiscustomarytopass100%,50%oratleast25%offullloadcurrent.Voltagetobeincreasedgraduallytillthecurrentintheenergizedwindingreachestherequiredvalue(50%to100%ratedcurrent).Measurethe3Phaselinecurrentsatalltapposition.IfthetapswitchisanOffCircuittapswitch,thesupplyhastobedisconnectedbeforechangingthetap.Aconsistenttrendintheincreaseordecreaseofcurrent,asthecasemaybe,confirmsthehealthinessofthetransformer.Iftransformerisequippedwithatapchanger,tappingregulationsareapplied.(1)Iftappingrangewithin5%andratedpowerlessthan2500kAV,loadlossguaranteerefer
-
totheprincipaltaponly.(2)Iftappingrangeexceeds5%orratedpowerabove2500kAV,itshallbestatedforwhichtappingbesidetheprincipaltaptheloadlosseswillbeguaranteedbythemanufacturer.ThreephaseLTsupplyisappliedonHVsideofpowertransformeratnormaltapwithratedcurrentonHVsideandcurrentsmeasuredinallthephasesonHVsideandphases&neutralonLVsidevaluesnoted.Readingstobetakenasquicklyaspossibleasthewindingswarmupandthewindingresistanceincreases.Hence,thelossesvaluewillincreaseaccordingly.Usingappropriateinstruments(conventionalthreewattmetermethodordigitalwattmeterwithammeters&voltmeters)measurementsofvoltage,currentsandpowercanberecorded.
(https://electricalnotes.files.wordpress.com/2014/09/untitled6.png)
ShortCircuitTest(WithoutusingCT,PT)ToavoidCTsandPTs,thismethodcanbeusedatcurrentlevelsof2to5Aandmeasurementofloadlossesisdoneatthiscondition.Thismeasuredloadlossisthenextrapolatedtoactualloadcurrentstoobtainloadlossesattheoperatingcurrent.Example:11kV/433V,1000kVAtransformerwith5%impedance,thevoltagetobeappliedonH.V.sideduringloadtestisestimatedbelow.V.sidefullloadcurrent(I1)=(KVAx1000/1.732xLineVoltage)V.sidefullloadcurrent(I1)=(10001000/1.73211000)=52.5AmpLinetolinevoltagetobeappliedonH.Vsideforgetting5AonH.V.side,LinetolinevoltagetobeappliedonH.VsideVisc=(LineVoltagex1000xZx5/0.866xI1x100)LinetolinevoltagetobeappliedonH.VsideVisc=(11x1000x5xx/x0.86652.5100)=60.5volts.SincethecurrentdrawnonH.V.sideisonlyabout5Ainthistest,CTscanbeavoidedandhencephaseangleerrorisnotapplicable.
-
(https://electricalnotes.files.wordpress.com/2014/09/untitled7.png)
ShortCircuitTest(WithusingCT,PT)
(https://electricalnotes.files.wordpress.com/2014/09/untitled8.png)AcceptanceCriteria:
Measuredimpedancetobewithinguaranteedvalueandnameplatevalue.Loadlossestobewithinguaranteedvalues.
Testcandetect:
Windingdeformation.Deviationinnameplatevalue.
(6)OpenCircuit/NoLoadTest
TestPurpose:
Inthistest,thevalueofNoLoadpower(Po)&theNoLoadcurrent(Io)aremeasuredatratedvoltage&frequency.
TestInstruments:
-
Wattmeters.Ammeter,VoltmeterorPoweranalyses
TestProcedure:
Testisperformedatratedfrequency.ThreephaseLTVoltageof415VappliedonHVsideofPowertransformerkeepingLTopenTwovoltmetersareconnectedtotheenergizedwinding,oneismeasuringthevoltagemeanvalueandtheotherisfortheVoltageR.M.Svalue.Voltageappliedtowinding(usuallytoH.V.windings).Itwillbeinarangefrom90%ofwindingratedvoltageto110%ofthesameinsteps,eachof5%(i.e.fora33/11kVtransformer,appliedvoltagevalueswillbe29.7kV,31.35kV,36.3kV)Readingsofwattmeters,Voltmeters&AmmetersarerecordedtoobtainthevaluesofV(r.m.s),Vmean,PoandIoateachvoltagestep.Testresultsareconsideredsatisfactoryifthereadingsofthetwoareequalwithin3%.Ifitsmorethan3%,thevalidityofthetestissubjectedtoagreement.Measuredvalueofpowerlossiscorrectedaccordingtothefollowingformula:Pc=Pm(1+d)D=(VmeanVr.m.s)/VmeanMeasurethelossinallthethreephaseswiththehelpof3wattmetermethod.Totalnoloadlossorironlossofthetrf=W1+W2+W3
TestCaution:
Thistestshouldbeperformedbeforetheimpulsetestifthelaterwillbeperformedasaroutinetestinordertoavoidreadingserrors
AcceptanceCriteria:
NoLoadlossestobewithinguaranteedvalues.
(7)Continuitytest:
PurposeofTest:
Toknowthecontinuityofwindingsofthetransformer.
TestInstruments:
MeggerorMultimeter.
TestProcedure:
-
CheckContinuityofTransformerbyusingmultimeterorbyMeggerbetweenfollowingTerminals
Transformer PP PP PP Result
HVSide RY YB BR ZeroMegaohmorcontinuity
LVSide ry yb br ZeroMegaohmorcontinuityTestcandetect:
Opencircuit/looseconnectionofwinding
(8)MagneticCurrentTest
TestPurpose:
Magnetizingcurrenttestoftransformerlocatesthedefectsinthemagneticcorestructure,shiftingofwindings,failureinturntoturninsulationorproblemintapchangers.Theseconditionschangetheeffectivereluctanceofthemagneticcircuit,thusaffectingtheelectriccurrentrequiredtoestablishfluxinthecore.
TestInstrument:
Multimeter.MillAmmeter
TestCircuitDiagram:
(https://electricalnotes.files.wordpress.com/2014/09/untitled9.png)
ThreephasesLTVoltageof415VappliedonHVsideofPowertransformerandcurrentsaretobemeasuredwithmillammeter.Thevalueshallbe=(1to2percentofratedfullloadcurrentofTC/HTKV)XVoltage
-
Applied
TestProcedure:
FirstofallkeepthetapchangerinthelowestpositionandopenallIV&LVterminals.Thenapplythreephase415Vsupplyonthelineterminalsforthreephasetransformersandsinglephase230Vsupplyonsinglephasetransformers.Measurethesupplyvoltageandelectriccurrentineachphase.Nowrepeatthemagnetizingcurrenttestoftransformertestwithkeepingtapchangerinnormalposition.Andrepeatthetestwithkeepingthetapathighestposition.Generallytherearetwosimilarhigherreadingsontwoouterlimbphasesontransformercoreandonelowerreadingonthecenterlimbphase,incaseofthreephasetransformers.Anagreementtowithin30%ofthemeasuredexcitingcurrentwiththeprevioustestisusuallyconsideredsatisfactory.Ifthemeasuredexcitingcurrentvalueis50timeshigherthanthevaluemeasuredduringfactorytest,thereislikelihoodofafaultinthewindingwhichneedsfurtheranalysis.
TestCaution:
ThismagnetizingcurrenttestoftransformeristobecarriedoutbeforeDCresistancemeasurement.
FILEDUNDERUNCATEGORIZED
VariousRoutineTestofPowerTransformer(Part2)
MARCH1,2015 3COMMENTS(HTTPS://ELECTRICALNOTES.WORDPRESS.COM/2015/03/01/VARIOUSROUTINETESTOFPOWERTRANSFORMERPART2/#COMMENTS)
i7Votes
-
(3)TurnsRatio/VoltageRatioTest:
TestPurpose:
TurnsRatioTest/VoltageRatioTestaredoneinTransformertofindoutOpenCircuitedturns,ShortCircuitedturnsinTransformerwinding.Thevoltageratioisequaltotheturnsratioinatransformer(V1/V2=N1/N2).Usingthisprinciple,theturnsratioismeasuredwiththehelpofaturnsratiometer.Ifitiscorrect,thenthevoltageratioisassumedtobecorrectThistestshouldbemadeforanynewhighvoltagepowertransformeratthetimeitisbeinginstalled.WithuseofTurnsRatiometer(TTR),turnsRatiobetweenHV&LVwindingsatvarioustapstobemeasured&recorded.TheturnsratioismeasureoftheRMSvoltageappliedtotheprimaryterminalstotheRMSVoltagemeasuredatthesecondaryterminals.R=Np/NsWhere,R=VoltageratioNp=Numberofturnsatprimarywinding.Ns=NumberofturnsatsecondaryWinding.Thevoltageratioshallbemeasuredoneachtappinginthenoloadcondition.
TestInstruments:
TurnsRatiometer(TTR)toenergiesthetransformerfromalowvoltagesupplyandmeasuretheHVandLVvoltages.WheatstoneBridgeCircuit
MethodNo1TurnsRatioTesting:
TestProcedure:
TransformerTurnsRatioMeter(TTR):TransformerratiotestcanbedonebyTransformerTurnsRatio(TTR)Meter.Ithasinbuiltpowersupply,withthevoltagescommonlyusedbeingverylow,suchas8,10Vand50Hz.TheHVandLVwindingsofonephaseofatransformer(i.e.RY&rn)areconnectedtotheinstrument,andtheinternalbridgeelementsarevariedtoproduceanullindicationonthedetector.Valuesarerecordedateachtapincaseoftappedwindingsandthencomparedtocalculated
-
ratioatthesametap.Theratiometergivesaccuracyof0.1percentoveraratiorangeupto1110:1.Theratiometerisusedinabridgecircuitwherethevoltagesofthewindingsofthetransformerundertestarebalancedagainstthevoltagesdevelopedacrossthefixedandvariableresistorsoftheratiometer.Adjustmentofthecalibratedvariableresistoruntilzerodeflectionisobtainedonthegalvanometerthengivestheratiotounityofthetransformerwindingsfromtheratiooftheresistors.BridgeCircuit:
(https://electricalnotes.files.wordpress.com/2014/09/untitled4.png)
Aphasevoltageisappliedtotheoneofthewindingsbymeansofabridgecircuitandtheratioofinducedvoltageismeasuredatthebridge.Theaccuracyofthemeasuringinstrumentis