ELECTRICAL LEGEND

14
SHEET DRAWING DATE PROJECT PROJECT LICENSE NUMBER: ________ EXPIRATION DATE: __________ SEAL: ALL DRAWINGS ARE PROTECTED BY FEDERAL COPYRIGHT BY MANNS WOODWARD STUDIOS, INC. AND CAN NOT BE REPRODUCED OR MODIFIED IN ANY MANNER WITHOUT WRITTEN PERMISSION. DOCUMENTS MAY NOT BE USED IN PART OR WHOLE TO DEVELOP THE DESIGN OF ANOTHER BUILDING WITHOUT EXPRESS WRITTEN PERMISSION BY MANNS WOODWARD STUDIOS. (P) 410-344-1460 (F) 443-403-2460 (E) [email protected] WWW.MWSARCH.COM S T U D I O S 10839-D PHILADELPHIA RD WHITE MARSH, MD 21162 ARCHITECTURE + MASTER PLANNING 8/14/2018 1:09:44 PM BALTIMORE CITY ANIMAL SERVICES BUILDING 2490 GILES ROAD, BALTIMORE, 21225 NO. DESCRIPTION DATE 03-15-2019 17-023 100% CD I HEREBY CERTIFY THAT THESE DOCUMENTS WERE PREPARED OR APPROVED BY ME, AND THAT I AM A DULY LICENSED PROFESSIONAL ENGINEER UNDER THE LAWS OF THE STATE OF MARYLAND. CONSULTANT: Engineering Infrastructure Solutions C.C. Johnson & Malhotra, P.C. 400 East Pratt Street, Suite 604 Baltimore, MD 21202 (P) 410-461-9920 | (F) (667)239-3534 | (E) [email protected] CCJM ELECTRICAL - NOTES, ABBREVIATIONS & LEGEND E001 FUSE , JUNCTION BOX CIRCUIT BREAKER SWITCH AND FUSE FUSED SWITCH GENERATOR MOTOR CONNECTION SAFETY SWITCH NONFUSED, SIZE AS INDICATED ELECTRICAL DEVICE AS INDICATED COMBINATION TYPE MOTOR STARTER, SIZE AS INDICATED SAFETY SWITCH FUSED, SIZE AS INDICATED DUPLEX RECEPTACLE 3 M WP RECEPTACLE WITH IN-USE BUBBLE COVER QUAD RECEPTACLE GFCI DUPLEX RECEPTACLE SPECIAL RECEPTACLE, SIZE AND TYPE AS NOTED , TS FS , , FIRE ALARM TAMPER SWITCH CONNECTION FIRE ALARM SYSTEM, VISUAL LIGHT/STROBE; WALL MTD (OR "C"-CEILING) FIRE ALARM SYSTEM FLOW SWITCH CONNECTION FIRE ALARM SYSTEM HEAT DETECTOR FIRE ALARM SYSTEM MANUAL PULL STATION FIRE ALARM SYSTEM SMOKE DETECTOR FIRE ALARM SYSTEM DUCT SMOKE DETECTOR DUPLEX RECEPTACLE FOR ELECTRIC WATER COOLER 480 VOLT PANELBOARD FIRE ALARM CONTROL PANEL FIRE ALARM ANNUNCIATOR PANEL FIXTURE SCHEDULE a 3 3 INDICATES CIRCUIT NUMBER 3 INDICATES CIRCUIT NUMBER A INDICATES TYPE OF LIGHTING FIXTURE REFER TO INDICATES SPECIAL / KEYED NOTE. UNLESS OTHERWISE A a 3 , 3 R-2,4 HOME RUN TO PANELBOARD UNLESS OTHERWISE NOTED. R INDICATES THE PANEL DISTRIBUTION EQUIPMENT AS INDICATED. 2,4 NUMBERS INDICATE SOPN NUMBER FOR PANEL DRAWING ON WHICH IT APPEARS. ELECTRICAL GENERAL NOTE APPLY TO ALL DRAWINGS, EGN-x NOTED, SPECIAL / KEYED NOTE APPLIES ONLY TO THE EGN-1 REFER TO ARCHITECTURAL DRAWINGS FOR EXACT LOCATIONS OF CEILING MOUNTED LIGHTING FIXTURES, ETC. EGN-2 REFER TO MECHANICAL/PLUMBING DRAWINGS FOR EXACT LOCATIONS OF MECHANICAL/PLUMBING EQUIPMENT AND DEVICES. EGN-3 REFER TO ARCHITECTURAL DRAWINGS FOR BUILDING WALL, CEILING, FLOOR, ROOF AND OTHER TYPES OF CONSTRUCTION. EGN-4 UNLESS OTHERWISE NOTED, ALL WORK IN FINISHED OCCUPIED AREAS SHALL BE CONCEALED ABOVE CEILING, IN WALL AND/OR IN CHASES. EGN-5 ALL MATERIAL AND EQUIPMENT SHALL BE U.L. LISTED AS SUITABLE FOR THE LOCATION AND ENVIRONMENT FOR WHICH IT IS USED AND SHALL MEET OWNER'S FACILITY DESIGN STANDARDS. EGN-6 ALL WORK SHALL BE DONE IN ACCORDANCE WITH THE 2014 EDITION OF NEC AND ALL OTHER APPLICABLE CODES. EGN-7 ALL EQUIPMENT AND WIRING THAT MAY REQUIRE SERVICING SHALL BE COMPLETELY ACCESSIBLE UPON COMPLETION OF PROJECT. JUNCTION BOXES AND PULL BOXES SHALL BE INSTALLED WHEREVER REQUIRED FOR A COMPLETE INSTALLATION OF BUILDING ELECTRICAL SYSTEMS. SIZE IN ACCORDANCE WITH NEC. EGN-8 BALANCE THE PANELBOARD LOADS ON EACH PHASE UNDER NORMAL OPERATING CONDITIONS, WITHIN 20% PLUS/MINUS TOLERANCE. CIRCUIT NUMBERS ARE FOR IDENTIFICATION PURPOSES ONLY. CORRECTLY SPACE THE CIRCUITS IN THE PANEL AND BALANCE THE LOAD ON THE PHASES UNDER NORMAL OPERATING CONDITIONS. UPDATE ALL PANEL DIRECTORIES TO INCLUDE EXISTING AND NEW CIRCUITS INFORMATION. EGN-9 COORDINATE WITH ALL OTHER TRADES/CONTRACTORS FOR A COMPLETE INSTALLATION OF WORK. EGN-10 THOROUGHLY EXAMINE THE PREMISES AND OBSERVE ALL FIELD CONDITIONS UNDER WHICH THE WORK SHALL BE PERFORMED. VERIFY LOCATION AND DIMENSIONS OF ALL EQUIPMENT WITH OTHER TRADES AND OWNER, REQUIRING ELECTRICAL CONNECTIONS, BEFORE ANY ROUGH-IN. ANY DIFFICULTIES IN COMPLYING WITH THE DRAWINGS AND SPECIFICATIONS SHALL BE BROUGHT TO THE ATTENTION OF ARCHITECT AND ENGINEER BEFORE BIDDING. EGN-11 PROVIDE GROUNDING CONNECTIONS FOR ALL ENCLOSURES, DEVICES AND EQUIPMENT PERMANENTLY AND EFFECTIVELY IN ACCORDANCE WITH NEC AND PROJECT SPECIFICATIONS. PROVIDE GROUNDING CONDUCTOR WITH EACH BRANCH CIRCUIT AND FEEDER. EGN-12 PROVIDE FIRE-STOPPING FOR EACH PENETRATION THROUGH FIRE RATED WALLS, FIRE RATED CEILINGS AND FIRE RATED FLOORS. EGN-13 UNLESS OTHERWISE NOTED, ALL WIRING CONDUCTORS SHALL BE COPPER, TYPE THWN/THHN INSULATION, RATED FOR 90 DEGREE C. AND IN METALLIC RACEWAYS. ARMORED CABLE WIRING SHALL NOT BE PERMITTED. REFER TO SPECIFICATIONS. EGN-14 DRAWINGS ARE DIAGRAMMATIC AND ARE INTENDED TO INDICATE THE GENERAL ARRANGEMENT. THEY ARE NOT INTENDED TO SHOW ALL DETAILS OF CONSTRUCTION OR EXACT LOCATIONS OF THE WORK. EGN-15 ALL OVERCURRENT PROTECTION DEVICES USED FOR MECHANICAL EQUIPMENT PROTECTION SHALL BE HACR RATED. CONTRACTOR SHALL VERIFY WIRE SIZES, CIRCUIT BREAKER AND FUSE RATINGS FOR ALL HVAC EQUIPMENT, AND BRING TO THE ATTENTION OF THE ARCHITECT/ ENGINEER ANY DISCREPANCIES AFFECTING THE WORK PRIOR TO PROCEEDING. EGN-16 THE CONTRACTOR SHALL RESTORE ALL AREAS AND SYSTEMS DISTURBED BY THEIR WORK TO ITS ORIGINAL CONDITIONS AND TO THE COMPLETE SATISFACTION OF ARCHITECT AND OWNER. EGN-17 VERIFY THAT ALL DOOR SWINGS ARE CORRECT BEFORE INSTALLING LIGHT SWITCH(ES). EGN-18 THE CORRECT NUMBER OF WIRES MAY NOT BE INDICATED FOR ALL CIRCUITS, ONLY THOSE WHERE CLARIFICATION IS NECESSARY. PROVIDE ALL WIRES NECESSARY FOR THE PROPER FUNCTION OF THE SYSTEM WHETHER INDICATED ON DRAWINGS OR NOT. NEUTRAL WIRES SHALL NOT BE SHARED. EGN-19 OPENINGS IN EXISTING BUILDING STRUCTURE FOR PASSAGE OF CONDUITS/CABLES SHALL NOT BE CUT UNTIL THE CONTRACTOR HAS ASKED FOR AND RECEIVED WRITTEN APPROVAL FROM THE OWNER. EGN-20 CONDUCTORS SHALL BE INSTALLED CONTINUOUS BETWEEN DEVICES, WITH SPLICES LOCATED ONLY IN JUNCTION BOXES OR IN CABINETS. CONDUCTORS SHALL BE OF SUFFICIENT LENGTH TO REACH THE FARTHEST TERMINAL IN PANELS. EGN-21 ALL RECEPTACLE/LIGHT SWITCH COVER PLATES SHALL BE LABELED WITH THE PANEL AND CIRCUIT NUMBER SERVING THE RECEPTACLE/LIGHT SWITCH. LETTERING SHALL BE A MINIMUM OF 1/8" IN HEIGHT. PROVIDE MACHINE PRINTED LABELS. HANDWRITTEN LABELS ARE NOT ALLOWED. EGN-22 NO POWER AND/OR SYSTEMS SHALL BE INTERRUPTED BY THE CONTRACTOR FOR ANY PURPOSE WITHOUT PRIOR WRITTEN APPROVAL OF THE OWNER. ALL OUTAGES SHALL COMPLY WITH THE OWNER'S REQUIREMENTS. RESTORE ALL EXISTING TO REMAIN EQUIPMENT, SYSTEMS, OR DEVICES IF INTERRUPTED BY DEMOLISHED CIRCUITS IN THE AREA. EGN-23 ALL EMPTY RACEWAYS SHALL HAVE PULL WIRE AND TERMINATED ABOVE CEILING AT AN ACCESSIBLE LOCATION WHERE INDICATED. EGN-24 FOR ELECTRICAL EQUIPMENT THAT MAY NEED EXAMINATION, ADJUSTMENT, SERVICING, OR MAINTENANCE WHILE ENERGIZED INCLUDING BUT NOT LIMITED TO PANELBOARDS, SPACE EQUAL TO THE WIDTH AND DEPTH OF THE ELECTRICAL EQUIPMENT AND EXTENDING FROM THE FLOOR TO A STRUCTURAL CEILING, PLUS THE WORKING SPACE REQUIRED BY THE NEC, MUST BE DEDICATED TO THE ELECTRICAL INSTALLATION. NO PIPING, DUCTS, OR EQUIPMENT FOREIGN TO THE ELECTRICAL INSTALLATION MAY BE LOCATED IN THIS SPACE WITH THE EXCEPTION OF SUSPENDED CEILINGS WITH REMOVABLE PANELS. 208 VOLT PANELBOARD , E T UNDERGROUND COMMUNICATION LINES, AS NOTED TRANSFORMER, SIZE AS INDICATED UNDERGROUND ELECTRICAL LINES, AS NOTED CONDUIT, CONCEALED IN CEILING OR WALL OR CHASE , , LV LD TV SMOKE DETECTOR, SINGLE STATION GROUND ROD, COPPER WELD, 3/4" DIAMETER AND 10' LONG GROUNDING CABLE T DOWN CONDUCTOR WITH GROUND ROD LIGHTNING PROTECTION CABLE SYSTEM GROUND OR EQUIPMENT GROUND LP G RECEPTACLE WITH TOP OUTLET SWITCHED , WP GFI WC CROSS HATCH LINES INDICATE THE NUMBER OF CURRENT CARRYING CONDUCTORS CROSS HATCH LINES WITH DOT AT END INDICATES THE EQUIPMENT GROUNDING CONDUCTOR (GREEN WIRE) AND SHALL BE SIZED IN ACCORDANCE WITH NEC ARTICLE 250. GREEN GROUNDING WIRE SHALL BE PROVIDED WITH EACH CIRCUIT, AND/OR FEEDER. WHERE NO WIRES ARE INDICATED, PROVIDE 2 (TWO) CURRENT CARRYING # 12 AWG CONDUCTORS AND 1 (ONE) # 12 GROUND FOR BRANCH CIRCUIT WIRING IN MINIMUM 3/4" RACEWAY UNLESS OTHERWISE INDICATED IN THE SCHEDULES. SMOKE DETECTOR WITH HORN, SINGLE STATION a a INDICATES SWITCH LEG OR CONTROL ZONE FIRE ALARM SYSTEM HORN # # EQUIPMENT/DEVICE MOUNTING HEIGHT DUPLEX RECEPTACLE - CEILING , J J F OUTLET BOX FOR CARD READER CARD READER BY GC AND WIRING BY OWNER - PROVIDE OUTLET BOX WITH 1" RACEWAY, PULL WIRE AND TERMINATE AT AN ACCESSIBLE LOCATION 6" ABOVE CEILING DATA OUTLET. PROVIDE OUTLET BOX, TWO (2) RJ-45 JACKS AND COVER PLATE WITH 1-1/4" RACEWAY, PULL WIRE AND EXTEND 6" ABOVE CEILING. OWNER WILL PROVIDE TWO (2) - 4 PAIR CAT 6 CABLE AND EXTEND TO NEAREST IT ROOM. OWNER WILL TERMINATE CABLES ON BOTH ENDS. MH = 18" AFF, C = 9" ABOVE COUNTER MH TELEPHONE/DATA OUTLET. PROVIDE OUTLET BOX, TWO (2) RJ-45 JACKS & COVER PLATE WITH 1-1/4" RACEWAY, PULL WIRE AND EXTEND 6" ABOVE CEILING. OWNER WILL PROVIDE: DATA - ONE (1) - 4 PAIR CAT 6 (BLACK) & VOICE - ONE (1) 4 PAIR CAT 5E (WHITE) CABLES AND EXTEND TO NEAREST IT ROOM. OWNER WILL TERMINATE CABLES ON BOTH ENDS. MH = 18" AFF, C = 9" ABOVE COUNTER MH a INDICATES SWITCH LEG OR CONTROL ZONE USB WALL MOUNTED EMERGENCY LIGHTING L2 L3 FA1. PROVIDE FULL FIRE ALARM SYSTEM WITH MAIN FIRE ALARM CONTROL PANEL LOCATED IN IT ROOM OR AS DIRECTED BY OWNER (GAMEWELL FCI 7100 WITH SILENT KNIGHT 5129 4 CHANNEL COMMUNICATOR BY HONEYWELL). FA2. PROVIDE THE NEW FIRE ALARM SYSTEM FOR THE ENTIRE FACILITY TO COMPLY WITH NFPA 72, NFPA 70, AND TO MEET THE REQUIREMENTS OF THE AUTHORITIES HAVING JURISDICTION. FA3. MAINTAIN COMPLETE FIRE ALARM SYSTEM WITHIN AND ADJACENT OF WORK SPACES AS FULLY WORKING SYSTEM. FA4. THE CONTRACTOR SHALL BE RESPONSIBLE TO APPLY AND GET THE FIRE ALARM PERMIT FROM LOCAL AUTHORITY HAVING JURISDICTION. FA5. CONTRACTOR SHALL BE FULLY RESPONSIBLE TO PREPARE AND SUBMIT ALL DRAWINGS AND DOCUMENTATION AS REQUIRED BY LOCAL GOVERNMENT (AHJ) FOR FIRE ALARM SYSTEM PERMIT. ALL COSTS ASSOCIATED WITH PREPARING THE DRAWINGS AND OTHER DOCUMENTATION AND PERMIT FEES FOR PERMITS SHALL BE INCLUDED IN THE BASE BID. FA6. FACP SHALL HAVE MINIMUM 20% SPARE CAPACITY. PROVIDE BATTERY WITH SPARE CAPACITY, EXPANSION MODULES AND NOTIFICATION APPLIANCE CIRCUITS ACCORDINGLY. ALL COSTS OF ANY AND ALL FIRE ALARM SYSTEM FOR THIS PROJECT SHALL BE INCLUDED IN BASE BID. FA7. PROVIDE FIRE ALARM SYSTEM EQUIPMENT, DEVICES, ENGINEERING, PROGRAMMING, INSPECTIONS, AND TESTS FOR A FULLY WORKING SYSTEM ACCEPTABLE TO AHJ AND OWNER. FA8. ALL CIRCUITS SHALL BE CLASS A AND SHALL BE RUN IN MINIMUM 3/4" METAL RACEWAYS. LABEL EACH RACEWAY. ALL NEW RACEWAYS AND BACK BOXES SHALL BE CONCEALED. ANY SURFACE MOUNTED RACEWAYS SHALL BE PAINTED TO MATCH ADJACENT SURFACE. ALL NEW JUNCTION BOXES SHALL HAVE RED PAINTED COVER PLATES. ALL JUNCTION BOXES SHALL HAVE A PERMANENT, MACHINE PRINTED LABEL READING “FIRE ALARM CIRCUIT” ON THE INSIDE COVER. ALL FIRE ALARM CONDUIT SHALL BE RED OR MARKED WITH 3/4 INCH WIDE RED BANDS EVERY 10 FEET AND AT EACH SIDE OF FLOORS, WALLS, AND CEILINGS. FA9. ALL DRAWINGS ARE CONCEPTUAL IN NATURE. DRAWINGS DO NOT SHOW EXACT LOCATIONS OF COMPONENTS NOR DO THEY SHOW ALL REQUIRED COMPONENTS. PROVIDE ALL COMPONENTS NECESSARY FOR A PROPERLY INSTALLED, FULLY FUNCTIONAL SYSTEM IN ACCORDANCE WITH THE APPLICABLE CODES AND STANDARDS. FA10. DURING THE PROJECT MAINTAIN ALL FIRE ALARM SYSTEMS, CONDUIT, CIRCUITS, AND DEVICES IN OPERATIONAL CONDITION. DURING CONSTRUCTION, NO AREA OF THE BUILDING SHALL BE LEFT WITHOUT AN OPERATIONAL FIRE ALARM SYSTEM EXCEPT THE PROJECT AREAS. FA11. PROVIDE ANNUNCIATOR PANEL AND GRAPHICS TO REFLECT ALL COMPONENTS INCLUDING BUT NOT LIMITED TO NEW LED PILOT LIGHTS FOR WATER FLOW AND TAMPER SWITCHES. ELECTRICAL LEGEND NOTE: LEGENDS ARE GENERAL, NOT ALL SYMBOLS, ABBREVIATIONS, AND/OR DESIGNATIONS MAY APPEAR ON THE DRAWINGS. ANNOTATIONS AS/AF AMPERES SWITCH & FUSE RATING A, AMP AMPERES ABBREV ABBREVIATIONS AC ALTERNATING CURRENT, ARMORED CABLE ACU AIR CONDITIONING UNIT AF AMPERE FRAME AFF ABOVE FINISHED FLOOR AFG ABOVE FINISHED GRADE AHU AIR HANDLING UNIT AIC AMPERE INTERRUPTING CAPACITY ATC AUTOMATIC TEMPERATURE CONTROL ATS AUTOMATIC TRANSFER SWITCH AUX AUXILIARY AWG AMERICAN WIRE GAUGE BES BLDG ELECTRICAL SYSTEM BIL BASIC IMPLUSE LEVEL BLDG BUILDING BKBD BACKBOARD BRKR BREAKER C CONDUIT CB CIRCUIT BREAKER CCTV CLOSED CIRCUIT TELEVISION CKT CIRCUIT CR CARD READER CL CURRENT LIMITING CLG CEILING CPT CONTROL POWER TRANSFORMER CT CURRENT TRANSFORMER CUH CABINET UNIT HEATER CW COOL WHITE DGS DIESEL GENERATOR SET DIA DIAMETER DISC DISCONNECT DIST DISTRIBUTION DN DOWN DP DISTRIBUTION PANEL DVR DIGITAL VIDEO RECORDER DWG DRAWING E, EMERGENCY EBH ELECTRIC BASEBOARD HEATER EC EMPTY CONDUIT ECB ENCLOSED CIRCUIT BREAKER EF EXHAUST FAN EGS ELECTRIC GENERATOR SET EH ELECTRIC HEATER ELECT ELECTRICAL EMT ELECTRICAL METALLIC TUBING ENCL ENCLOSURE EQUIP EQUIPMENT ER EXISTING RELOCATED ETR EXISTING-TO-REMAIN EWC ELECTRIC WATER COOLER EWH ELECTRIC WATER HEATER EX EXISTING EXH EXHAUST F FUSED OR FUSIBLE FA FRAME AMPERE FAAP FIRE ALARM ANNUNCIATOR PANEL FACP FIRE ALARM CONTROL PANEL FADS FIRE ALARM AND DETECTION SYSTEM FBO FURNISHED BY OTHERS FCU FAN COIL UNIT FDR FEEDER FL, FLOOR FLUOR FLUORESCENT FSS FUSED SAFETY SWITCH FT, FOOT OR FEET FVNR FULL VOLTAGE NON REVERSING GFCI GROUND FAULT CURRENT INTERRUPTER GND GROUND GN GENERAL NOTE GRS GALVANIZED RIGID STEEL GWB GYPSUM WALL BOARD GW GROUND WIRE HC HANDICAP HD HEAVY DUTY HID, HIGH INTENSIFY DISCHARGE HOA HAND-OFF-AUTOMATIC HP, HORSE POWER HPS HIGH PRESSURE SODIUM HTR HEATER HV HIGH VOLTAGE HVAC HEATING, VENTILATING AND AIR CONDITIONING HZ HERTZ IE THAT IS IMC INTERMEDIATE METAL CONDUIT JB JUNCTION BOX KCMIL THOUSAND CIRCULAR MILLS KV, KILOVOLT KVA KILOVOLT-AMPERE KW KILOWATT KWH KILOWATT-HOUR LA LIGHTNING ARRESTOR LS LIMIT SWITCH LTG LIGHTING LV LOW VOLTAGE MAX, MAXIMUM MCB MAIN CIRCUIT BREAKER MCC MOTOR CONTROL CENTER MCP MOTOR CIRCUIT PROTECTOR MH MOUNTING HEIGHT MIN, MINIMUM ABBREVIATIONS MDP MAIN DISTRIBUTION PANEL MTD MOUNTED MLO MAIN LUGS ONLY MTG MOUNTING MUX MULTIPLEXER N NEUTRAL NC NORMALLY CLOSED NEC NATIONAL ELECTRICAL CODE NIC NOT-IN-CONTRACT NL NIGHT LIGHT NO NORMALLY OPEN NTS NOT TO SCALE NFSS NON FUSED SAFETY SWITCH OC ON CENTER OH OVERHEAD OL OVERLOAD P POLE OR POLES PF POWER FACTOR PH PHASE VT POTENTIAL TRANSFORMER PL PILOT LIGHT PNL PANELBOARD PVC POLYVINYL CHLORIDE R REMOVE RAF RETURN AIR FAN RECEPTACLE REQD REQUIRED RGS RIGID GALVANIZED STEEL RMS ROOT MEAN SQUARE RS RAPID START RVAT REDUCED VOLTAGE AUTOTRANSFORMER S/N SOLID NEUTRAL SD SMOKE DETECTOR SEC SECONDARY SFA SPRINKLER FLOW ALARM SMR SURFACE METAL RACEWAY SPEC SPECIFICATION ST SHUNT TRIP SS SUB STATION STR STARTER SW SWITCH SWBD SWITCHBOARD SWGR SWITCHGEAR SYS SYSTEM SYM SYMMETRICAL SOPN SPACE OR POLE NUMBER TA TRIP AMPERE TB TERMINAL BOX TC TIME CLOCK TD TIME DELAY TTB TELEPHONE TERMINAL BOARD/BLOCK TTC TELEPHONE TERMINAL CLOSET TYP TYPICAL TV TELEVISION UC UNDER COUNTER UG UNDERGROUND UH UNIT HEATER UOI UNLESS OTHERWISE INDICATED UON UNLESS OTHERWISE NOTED UL UNDERWRITER'S LABORATORY USB UNIVERSAL SERIAL BUS V VOLT (S) OR VOLTAGE VA VOLT AMPERE VFD VARIABLE FREQUENCY DRIVE W WIRE W/ WITH WP WEATHER PROOF, WORK PHONE WW WIREWAY XFMR TRANSFORMER PH PHASE ɸ # NUMBER C CENTER LINE @ AT # MOUNTING HEIGHTS SWITCHES, 48" RECEPTACLE-GENERAL 18" RECEPTACLE-SPECIAL 18" RECEPTACLE-SINGLE 18" RECEPTACLE-REST ROOM 9" ABOVE BASIN RECEPTACLE-COUNTER 8" ABOVE COUNTER RECEPTACLE- MONITOR (DISPLAY) 78" OR DIRECTED BY OWNER IN FIELD RECEPTACLE-EXTERIOR 30" CABLE TV OUTLET 78" UON TELEPHONE/DATA-GENERAL 18" TELEPHONE-WALL TYPE 54", (48" FOR ADA ACCESSIBLE) FIRE ALARM PULL STATION 48" FIRE ALARM AUDIO/VISUAL DEVICE 80" CARD READER 40" EXIT LIGHT WALL MOUNTED, 90" OR 12" ABOVE DOOR EXIT LIGHT CEILING MOUNTED 96" AFF SAFETY SWITCH, VFD, STARTER 72" TO HANDLE ENCLOSED CIRCUIT BREAKER 72" TO HANDLE PANELBOARD 72" TO TOP CB MANUAL MOTOR STARTER 48" PUSH BUTTON, 48" AUTOMATIC DOOR OPENER 36" EMERGENCY BATTERY UNIT - WALL 18" BELOW CEILING OR 8' AFF EXIT SIGN - WALL 6" ABOVE DOOR JAMB ,NO HIGHER THAN 8' AFF CONTACTOR 5' AFF DISCONNECT SWITCH 5' AFF PANELBOARD (6' TALL) TOP TRIM 6' AFF, OR FROM BOTTOM 6" AFF MOTION SENSOR - WALL 8' AFF OR MANUFACTURER SPECIFICATION CAMERA - WALL 7'-6" AFF INTERCOM STATION 48" AFF MONITOR - WALL 7'-6" AFF FIRE SYSTEM GENERAL NOTES LIGHTING SYMBOLS LED LIGHTING FIXTURE LED LIGHTING FIXTURE WITH BATTERY BACKUP WALL MOUNTED FIXTURE INDUSTRIAL TYPE LED FIXTURE INDUSTRIAL TYPE LED FIXTURE WITH BATTERY BACKUP CEILING MOUNTED DOWN LIGHT; NORMAL , WITH BATTERY BACKUP WALL MOUNTED LIGHTING FIXTURE WALL WASH/DOWN LIGHT, CEILING MOUNTED COVE FIXTURE. LENGTH AS SHOWN ON DRAWINGS TRACK LIGHT WITH FIXTURE FIRE ALARM SYMBOLS FIRE ALARM SYSTEM INDIVIDUAL HORN AND STROBE LIGHT EXIT LIGHT BACK MOUNTED & w/ DIRECTIONAL CHEVRON AS INDICATED LIGHTING / POWER CONTROLS SYMBOLS OS VS PS PP SINGLE POLE SWITCH THREE WAY SWITCH DOUBLE POLE DISCONNECT LOW VOLTAGE SWITCH LOW VOLTAGE DIMMER TWO BUTTON ENTRY ROOM CONTROL STATION (LIGHTING) THREE BUTTON ENTRY ROOM CONTROL STATION (LIGHTING) OCCUPANCY SENSOR CEILING, WALL VACANCY SENSOR PHOTO SENSOR POWER PACK TELEPHONE/DATA SYMBOLS POWER SYMBOLS C DUPLEX RECEPTACLE MOUNTED ABOVE COUNTER ABOVE BACKSPLASH DUPLEX RECEPTACLE WITH (2) UNIVERSAL SERIAL BUS PORTS CONDUIT CONCEALED IN FLOOR OR UNDERFLOOR OR UNDERGROUND ELECTRICAL GENERAL NOTES # FIRE ALARM BELL # FIRE ALARM BELL AND STROBE FIRE ALARM SYSTEM COMBINATION HORN AND STROBE LIGHT ASSEMBLY FIRE ALARM SYSTEM CARBON MONOXIDE DETECTOR, M.H. 54" AFF FIRE ALARM - MAGNETIC DOOR HOLDER CO M METER 1. UNLESS INDICATED OTHERWISE ON THE PLANS OR AS DIRECTED BY THE OWNER, CENTERLINE OF DEVICE SHALL BE AS INDICATED ABOVE. 2. WHERE MOUNTING HEIGHTS ARE NOT DETAILED OR DIMENSIONED, THE CONTRACTOR SHALL INSTALL SYSTEMS, MATERIALS, AND EQUIPMENT TO PROVIDE THE MAXIMUM HEADROOM POSSIBLE AND COMPLY WITH THE REQUIREMENTS OF EQUIPMENT MANUFACTURER, APPLICABLE CODES AND STANDARDS, AND AHJ REQUIREMENTS. WHERE EQUIPMENT IS INTENDED, SPECIFIED, OR NOTED TO BE MOUNTED OTHER THEN INDICATED ABOVE, MOUNT IN ACCORDANCE WITH THE MANUFACTURER'S RECOMMENDATIONS AND AS DIRECTED. NOT ALL EQUIPMENT INDICATED WITH MOUNTING HEIGHTS ARE SHOWN ON THESE CONTRACT DOCUMENTS. 3. COORDINATE EXACT LOCATIONS AND MOUNTING HEIGHTS IN THE FIELD BEFORE ANY CORE DRILLING, CUTTING, AND ROUGH-INS. G FLR WALL FLOOR MOUNTED TELEPHONE/DATA OUTLET. PROVIDE OUTLET BOX, TWO (2) RJ-45 JACKS & COVER PLATE WITH 1-1/4" RACEWAY, PULL WIRE AND EXTEND 6" ABOVE CEILING. OWNER WILL PROVIDE PROVIDE: DATA - ONE (1) - 4 PAIR CAT 6 (BLACK) & VOICE - ONE (1) 4 PAIR CAT 5E (WHITE) CABLES AND EXTEND TO NEAREST IT ROOM. OWNER WILL TERMINATE CABLES ON BOTH ENDS. MH = 18" AFF CR C PA C SECURITY SYSTEM SYMBOLS SA UNDER-COUNTER (SILENT 911 ALARM), FURNISHED AND INSTALLED BY OWNER - PROVIDE OUTLET BOX WITH 1" RACEWAY, PULL WIRE FROM 6" ABOVE ACCESSIBLE CEILING TO LOCATION UNDERNEATH DESK. PANIC ALARM BUTTON, FURNISHED AND INSTALLED BY OWNER - PROVIDE OUTLET BOX WITH 1" RACEWAY AND PULL WIRE AND TERMINATE AT AN ACCESSIBLE LOCATION 6" ABOVE CEILING PANIC ALARM STROBE, FURNISHED AND INSTALLED BY OWNER - PROVIDE OUTLET BOX WITH 1" RACEWAY AND PULL WIRE AND TERMINATE AT AN ACCESSIBLE LOCATION 6" ABOVE CEILING CEILING MOUNTED SECURITY CAMERA BY OWNER - PROVIDE JUNCTION BOX WITH 1" RACEWAY, PULL WIRE AND EXTEND 6" ABOVE CEILING. WALL MOUNTED SECURITY CAMERA BY OWNER - PROVIDE JUNCTION BOX WITH 1" RACEWAY, PULL WIRE AND EXTEND 6" ABOVE CEILING. PROVIDE 1-1/2" SLEEVE THROUGH THE WALL FOR LOW VOLTAGE WIRING. OUTLET BOX FOR CONNECTIONS TO HDTV AT MEETING ROOM, MOUNTED 60" AFF AND COORDINATED WITH ASSOCIATED RECEPTACLE DESIGNATED FOR TV. PROVIDE OUTLET BOX AND COVER PLATE FOR THE FOLLOWING AT THE LOCATION INDICATED: * FUTURE COAX CONNECTION. PROVIDE 1" RACEWAY WITH PULL WIRE TO 6" ABOVE CONCEALED, ACCESSIBLE CEILING * (2) RJ-45 JACKS. PROVIDE 1-1/4" RACEWAY AND PULL STRING TO 6" ABOVE CONCEALED, ACCESSIBLE CEILING. DL DAYLIGHT SENSOR PL PLUG LOAD CONTROLLER OS N CAT 5 CABLE (LIGHTING) WS1. WS2. WS3. PROVIDE 4 CIRCUIT FMC TO HARD-WIRED JUNCTION BOX/POWER IN-FEED. WS4. WS5. WS6. WS7. WS8. WS9. WS10. WORKSTATION NOTES FOR WALL FED POWER SOURCE, SURFACE OR FLUSH MOUNT JUNCTION BOX(S) AS CLOSE AS POSSIBLE TO THE FURNITURE'S POWER IN-FEED. POWER IN-FEED CORD AND CAP FURNISHED BY FURNITURE MANUFACTURE AND INSTALLED BY CONTRACTOR. FOR PROTECTION FROM DAMAGE, STRAP/SECURE IN-FEED CORD FIRMLY TO WALL AND FURNITURE AS DIRECTED BY THE FURNITURE MANUFACTURER. FOR WALL FED VOICE/DATA SERVICES, SURFACE OR FLUSH MOUNT JUNCTION BOX(S) AS CLOSE AS POSSIBLE TO THE FURNITURE'S BASE IN-FEED. PROVIDE GROMMET IN COVER PLATE TO PROTECT CABLES FROM DAMAGE. ROUTE CABLE THROUGH BASE OF WORKSTATION FURNITURE VIA HORIZONTAL CABLE SUPPORTS FURNISHED BY FURNITURE MANUFACTURER AND INSTALLED BY CONTRACTOR. CONCEAL CABLE IN FURNITURE. FOR VERTICAL STRAIN-RELIEF, FASTEN CABLE TO THE FURNITURE'S STRUCTURAL MEMBERS. THE WORKSTATION ELECTRICAL SYSTEM TO BE PROVIDED WILL UTILIZE A 3 UTILITY, 1 ISOLATED CIRCUIT, 8 WIRE SYSTEM WITH A COMMON (4) #12 LINE (2) #10 NEUTRAL AND (2) #12 GROUND. AT THE POINT OF TERMINATION FOR THE POWER IN-FEED CABLE, THE CONTRACTOR SHALL COMBINE THE NEUTRALS AND GROUNDS AS DIRECTED BY THE FURNITURE MANUFACTURER. PRIOR TO THE POINT OF TERMINATION, THE NEUTRALS AND GROUND SHALL REMAIN DEDICATED TO THE SPECIFIC CIRCUIT. FIRMLY ATTACH POWER IN-FEED CABLE AND FMC TO WALL JUNCTION BOX COVER VIA UL LISTED FITTINGS/CONNECTORS WITH INSULATED THROATS. DUPLEX RECEPTACLES WILL BE FURNISHED AND INSTALLED BY THE FURNITURE MANUFACTURER. VOICE/DATA CABLE AND OUTLETS PROVIDED IN BASE PATHWAY BY CONTRACTOR. INSTALL OUTLETS IN FURNITURE KNOCKOUTS IN THE LOCATION AS DIRECTED BY THE OWNER. PROVIDE 3 DATA AND 1 VOICE PORT PER OUTLET FOR EVERY SEAT AS SHOWN ON THE FURNITURE LAYOUT DRAWINGS. FURNITURE SHALL BE PROVIDED WITH METALLIC SEPARATION BETWEEN POWER WIRING AND VOICE/DATA CABLES. ALL JUNCTION BOXES SHALL BE MADE READILY ACCESSIBLE INCLUDING HARDWIRED JUNCTION BOXES FURNISHED BY THE MANUFACTURER. ALL POWER AND VOICE/DATA CABLING WORK WILL BE PERFORMED BY THE SYSTEM FURNITURE QUALIFIED INSTALLER. THE FURNITURE VENDOR WILL FURNISH AND INSTALL POWER IN-FEEDS (OR BASE FEEDS) AND RECEPTACLES (POWER OUTLETS). RECEPTACLES WILL BE CORCUITED/CONNECTED BY THE FURNITURE VENDOR AS SHOWN ON THE FLOOR PLANS WITH THE FINAL POWER IN-FEED SERVICE CONNECTION BY THIS CONTRACT. DATA AND VOICE PORTS (OUTLET JACKS) INCLUDING CABLING AND FINAL TERMINATIONS IN THE FURNITURE SHALL BE PROVIDED BY THE CONTRACTOR. CABLE COVER WILL BE FURNISHED AND INSTALLED BY MANUFACTURER / FURNITURE VENDOR. COORDINATE ROUTING OF CABLES WITH FURNITURE INSTALLER BEFORE PROCEEDING WITH ANY ROUGH-IN WORK. SEE FLOOR PLAN(S) FOR FURNITURE POWER AND VOICE/DATA SERVICE LOCATIONS. VERIFY LOCATION OF FURNITURE POWER IN-FEED POINT OF TERMINATION WITH THE WORKSTATION MANUFACTURER / FURNITURE VENDOR BEFORE PROCEEDING WITH ANY ROUGH-IN WORK. PROVIDE QUANTITY OF JUNCTION BOXES AS NECESSARY TO ACCOMMODATE THE POWER AND VOICE/DATA WIRING/CABLING NEEDS OF THE FURNITURE. NOT ALL SERVICE FEEDS/LOCATIONS MAY BE SHOWN. TO ACCOMMODATE CHANGES IN THE FINAL FURNITURE LAYOUT, INCREASE THE NUMBER OF SERVICE LOCATIONS SHOWN ON THE FLOOR PLANS BY ADDITIONAL 25 PERCENT. LIGHTNING PROTECTION CABLE LP POWER PACK PUSH PLATE FOR HANDICAPPED ACCESS DOOR PB PC PHOTOCELL PP REMOTE DIGITAL FIRE ALARM TRANSMITTER 110 110 THE NUMBER ADJACENT TO THE SYMBOL INDICATES PREFERRED CANDELA VALUE. STROBE SYMBOL WITHOUT IDENTIFICATION SHALL BE AS FOLLOWS: CORRIDORS/HALLWAYS - 30 CANDELA, ROOMS <= 2,000 SQFT - 75 CANDELA, ROOMS > 2,000 SQFT - 110 CANDELA. , , TV OUTLET BOX FOR CONNECTIONS TO HDTV AT MEETING ROOM, MOUNTED 60" AFF AND COORDINATED WITH ASSOCIATED RECEPTACLE DESIGNATED FOR TV. PROVIDE OUTLET BOX AND COVER PLATE FOR THE FOLLOWING AT THE LOCATION INDICATED: * FUTURE COAX CONNECTION. PROVIDE 1" RACEWAY WITH PULL WIRE TO 6" ABOVE CONCEALED, ACCESSIBLE CEILING * (2) RJ-45 JACKS. PROVIDE 1-1/4" RACEWAY AND PULL STRING TO 6" ABOVE CONCEALED, ACCESSIBLE CEILING. * (2) HDMI OUTPUT. PROVIDE CABLING IN 1-1/4" RACEWAY TO CORRESPONDING HDMI INPUTS W TV OUTLET BOX FOR CONNECTIONS TO HDTV AT MEETING ROOM, MOUNTED 6" ABOVE COUNTER. COORDINATE EXACT LOCATION WITH OWNER. PROVIDE OUTLET AND COVER PLATE FOR THE FOLLOWING AT THE LOCATION INDICATED: * - (1) HDMI INPUT. PROVIDE CABLING TO WALL MOUNTED WALL PLATE IN SAME ROOM. C TV FLOOR BOX MOUNTED CONNECTIONS TO HDTV AT MEETING ROOM. COORDINATE EXACT LOCATION WITH TELECOM FLOOR BOX AT SAME ROOM AND OWNER. PROVIDE OUTLET AND COVER PLATE FOR THE FOLLOWING AT THE LOCATION INDICATED: * (1) HDMI INPUT. PROVIDE CABLING TO WALL MOUNTED WALL PLATE IN SAME ROOM. F DATA OUTLET FOR SYSTEMS FURNITURE, BY OTHERS. SIZE JUNCTION BOX FOR SYSTEM FURNITURE FOR THE QUANTITY OF DEVICES AS SHOWN. COORDINATE ALL WORK WITH OWNER AND SYSTEMS FURNITURE SUPPLIER. F QUAD RECEPTACLE - C = 9" ABOVE COUNTER C

Transcript of ELECTRICAL LEGEND

Page 1: ELECTRICAL LEGEND

SHEET

DRAWING

DATE

PROJECT

PROJECT

LICENSE NUMBER: ________

EXPIRATION DATE: __________

SE

AL

:

ALL DRAWINGS ARE PROTECTED BY FEDERAL COPYRIGHT BY MANNS WOODWARD STUDIOS, INC. AND CAN NOT BE REPRODUCED OR MODIFIED IN ANY MANNER WITHOUT WRITTEN PERMISSION. DOCUMENTS MAY NOT BE USED IN PART OR WHOLE TO DEVELOP THE DESIGN OF ANOTHER BUILDING WITHOUT EXPRESS WRITTEN PERMISSION BY

MANNS WOODWARD STUDIOS.

(P) 410-344-1460(F) 443-403-2460(E) [email protected]

S T U D I O S

10839-D PHILADELPHIA RDWHITE MARSH, MD 21162

ARCHITECTURE + MASTER PLANNING

8/14/2018 1:09:44 P

M

BA

LT

IM

OR

E C

IT

Y A

NIM

AL

S

ER

VIC

ES

B

UIL

DIN

G

24

90

G

IL

ES

R

OA

D, B

AL

TIM

OR

E, 2

12

25

NO. DESCRIPTION DATE

03-15-2019

17-023

100% CD

I HEREBY CERTIFY THAT THESE

DOCUMENTS WERE PREPARED OR

APPROVED BY ME, AND THAT I AM A

DULY LICENSED PROFESSIONAL

ENGINEER UNDER THE LAWS OF

THE STATE OF MARYLAND.

CO

NS

UL

TA

NT

:

Eng

inee

ring

Infra

stru

ctur

e S

olut

ions

C.C

. Joh

nson

& M

alho

tra,

P.C

.

400

Eas

t Pra

tt S

treet

, Sui

te 6

04B

altim

ore,

MD

212

02(P

) 410

-461

-992

0 | (

F) (

667)

239-

3534

|(E

) BA

LTIM

OR

E@

CC

JM.C

OM

CC

JM

ELECTRICAL -

NOTES, ABBREVIATIONS

& LEGEND

E001

FUSE

,

JUNCTION BOX

CIRCUIT BREAKER

SWITCH AND FUSE

FUSED SWITCH

GENERATOR

MOTOR CONNECTION

SAFETY SWITCH NONFUSED, SIZE AS INDICATED

ELECTRICAL DEVICE AS INDICATED

COMBINATION TYPE MOTOR STARTER, SIZE AS INDICATED

SAFETY SWITCH FUSED, SIZE AS INDICATED

DUPLEX RECEPTACLE

3

M

WP RECEPTACLE WITH IN-USE BUBBLE COVER

QUAD RECEPTACLE

GFCI DUPLEX RECEPTACLE

SPECIAL RECEPTACLE, SIZE AND TYPE AS NOTED

,

TS

FS,

,

FIRE ALARM TAMPER SWITCH CONNECTION

FIRE ALARM SYSTEM, VISUAL LIGHT/STROBE; WALL MTD (OR "C"-CEILING)

FIRE ALARM SYSTEM FLOW SWITCH CONNECTION

FIRE ALARM SYSTEM HEAT DETECTOR

FIRE ALARM SYSTEM MANUAL PULL STATION

FIRE ALARM SYSTEM SMOKE DETECTOR

FIRE ALARM SYSTEM DUCT SMOKE DETECTOR

DUPLEX RECEPTACLE FOR ELECTRIC WATER COOLER

480 VOLT PANELBOARD

FIRE ALARM CONTROL PANEL

FIRE ALARM ANNUNCIATOR PANEL

FIXTURE SCHEDULE

a

3

3 INDICATES CIRCUIT NUMBER

3 INDICATES CIRCUIT NUMBER

A INDICATES TYPE OF LIGHTING FIXTURE REFER TO

INDICATES SPECIAL / KEYED NOTE. UNLESS OTHERWISE

A

a

3

,

3

R-2,4

HOME RUN TO PANELBOARD

UNLESS OTHERWISE NOTED.

R INDICATES THE PANEL

DISTRIBUTION EQUIPMENT AS INDICATED.

2,4 NUMBERS INDICATE SOPN NUMBER FOR PANEL

DRAWING ON WHICH IT APPEARS.

ELECTRICAL GENERAL NOTE APPLY TO ALL DRAWINGS,EGN-x

NOTED, SPECIAL / KEYED NOTE APPLIES ONLY TO THE

EGN-1 REFER TO ARCHITECTURAL DRAWINGS FOR EXACT LOCATIONS OF CEILING MOUNTED

LIGHTING FIXTURES, ETC.

EGN-2 REFER TO MECHANICAL/PLUMBING DRAWINGS FOR EXACT LOCATIONS OF

MECHANICAL/PLUMBING EQUIPMENT AND DEVICES.

EGN-3 REFER TO ARCHITECTURAL DRAWINGS FOR BUILDING WALL, CEILING, FLOOR, ROOF AND

OTHER TYPES OF CONSTRUCTION.

EGN-4 UNLESS OTHERWISE NOTED, ALL WORK IN FINISHED OCCUPIED AREAS SHALL BE

CONCEALED ABOVE CEILING, IN WALL AND/OR IN CHASES.

EGN-5 ALL MATERIAL AND EQUIPMENT SHALL BE U.L. LISTED AS SUITABLE FOR THE LOCATION

AND ENVIRONMENT FOR WHICH IT IS USED AND SHALL MEET OWNER'S FACILITY DESIGN

STANDARDS.

EGN-6 ALL WORK SHALL BE DONE IN ACCORDANCE WITH THE 2014 EDITION OF NEC AND ALL

OTHER APPLICABLE CODES.

EGN-7 ALL EQUIPMENT AND WIRING THAT MAY REQUIRE SERVICING SHALL BE COMPLETELY

ACCESSIBLE UPON COMPLETION OF PROJECT. JUNCTION BOXES AND PULL BOXES SHALL

BE INSTALLED WHEREVER REQUIRED FOR A COMPLETE INSTALLATION OF BUILDING

ELECTRICAL SYSTEMS. SIZE IN ACCORDANCE WITH NEC.

EGN-8 BALANCE THE PANELBOARD LOADS ON EACH PHASE UNDER NORMAL OPERATING

CONDITIONS, WITHIN 20% PLUS/MINUS TOLERANCE. CIRCUIT NUMBERS ARE FOR

IDENTIFICATION PURPOSES ONLY. CORRECTLY SPACE THE CIRCUITS IN THE PANEL AND

BALANCE THE LOAD ON THE PHASES UNDER NORMAL OPERATING CONDITIONS. UPDATE

ALL PANEL DIRECTORIES TO INCLUDE EXISTING AND NEW CIRCUITS INFORMATION.

EGN-9 COORDINATE WITH ALL OTHER TRADES/CONTRACTORS FOR A COMPLETE INSTALLATION

OF WORK.

EGN-10 THOROUGHLY EXAMINE THE PREMISES AND OBSERVE ALL FIELD CONDITIONS UNDER

WHICH THE WORK SHALL BE PERFORMED. VERIFY LOCATION AND DIMENSIONS OF ALL

EQUIPMENT WITH OTHER TRADES AND OWNER, REQUIRING ELECTRICAL CONNECTIONS,

BEFORE ANY ROUGH-IN. ANY DIFFICULTIES IN COMPLYING WITH THE DRAWINGS AND

SPECIFICATIONS SHALL BE BROUGHT TO THE ATTENTION OF ARCHITECT AND ENGINEER

BEFORE BIDDING.

EGN-11 PROVIDE GROUNDING CONNECTIONS FOR ALL ENCLOSURES, DEVICES AND EQUIPMENT

PERMANENTLY AND EFFECTIVELY IN ACCORDANCE WITH NEC AND PROJECT

SPECIFICATIONS. PROVIDE GROUNDING CONDUCTOR WITH EACH BRANCH CIRCUIT AND

FEEDER.

EGN-12 PROVIDE FIRE-STOPPING FOR EACH PENETRATION THROUGH FIRE RATED WALLS, FIRE

RATED CEILINGS AND FIRE RATED FLOORS.

EGN-13 UNLESS OTHERWISE NOTED, ALL WIRING CONDUCTORS SHALL BE COPPER, TYPE

THWN/THHN INSULATION, RATED FOR 90 DEGREE C. AND IN METALLIC RACEWAYS.

ARMORED CABLE WIRING SHALL NOT BE PERMITTED. REFER TO SPECIFICATIONS.

EGN-14 DRAWINGS ARE DIAGRAMMATIC AND ARE INTENDED TO INDICATE THE GENERAL

ARRANGEMENT. THEY ARE NOT INTENDED TO SHOW ALL DETAILS OF CONSTRUCTION OR

EXACT LOCATIONS OF THE WORK.

EGN-15 ALL OVERCURRENT PROTECTION DEVICES USED FOR MECHANICAL EQUIPMENT

PROTECTION SHALL BE HACR RATED. CONTRACTOR SHALL VERIFY WIRE SIZES, CIRCUIT

BREAKER AND FUSE RATINGS FOR ALL HVAC EQUIPMENT, AND BRING TO THE ATTENTION

OF THE ARCHITECT/ ENGINEER ANY DISCREPANCIES AFFECTING THE WORK PRIOR TO

PROCEEDING.

EGN-16 THE CONTRACTOR SHALL RESTORE ALL AREAS AND SYSTEMS DISTURBED BY THEIR

WORK TO ITS ORIGINAL CONDITIONS AND TO THE COMPLETE SATISFACTION OF

ARCHITECT AND OWNER.

EGN-17 VERIFY THAT ALL DOOR SWINGS ARE CORRECT BEFORE INSTALLING LIGHT SWITCH(ES).

EGN-18 THE CORRECT NUMBER OF WIRES MAY NOT BE INDICATED FOR ALL CIRCUITS, ONLY

THOSE WHERE CLARIFICATION IS NECESSARY. PROVIDE ALL WIRES NECESSARY FOR THE

PROPER FUNCTION OF THE SYSTEM WHETHER INDICATED ON DRAWINGS OR NOT.

NEUTRAL WIRES SHALL NOT BE SHARED.

EGN-19 OPENINGS IN EXISTING BUILDING STRUCTURE FOR PASSAGE OF CONDUITS/CABLES

SHALL NOT BE CUT UNTIL THE CONTRACTOR HAS ASKED FOR AND RECEIVED WRITTEN

APPROVAL FROM THE OWNER.

EGN-20 CONDUCTORS SHALL BE INSTALLED CONTINUOUS BETWEEN DEVICES, WITH SPLICES

LOCATED ONLY IN JUNCTION BOXES OR IN CABINETS. CONDUCTORS SHALL BE OF

SUFFICIENT LENGTH TO REACH THE FARTHEST TERMINAL IN PANELS.

EGN-21 ALL RECEPTACLE/LIGHT SWITCH COVER PLATES SHALL BE LABELED WITH THE PANEL AND

CIRCUIT NUMBER SERVING THE RECEPTACLE/LIGHT SWITCH. LETTERING SHALL BE A

MINIMUM OF 1/8" IN HEIGHT. PROVIDE MACHINE PRINTED LABELS. HANDWRITTEN LABELS

ARE NOT ALLOWED.

EGN-22 NO POWER AND/OR SYSTEMS SHALL BE INTERRUPTED BY THE CONTRACTOR FOR ANY

PURPOSE WITHOUT PRIOR WRITTEN APPROVAL OF THE OWNER. ALL OUTAGES SHALL

COMPLY WITH THE OWNER'S REQUIREMENTS. RESTORE ALL EXISTING TO REMAIN

EQUIPMENT, SYSTEMS, OR DEVICES IF INTERRUPTED BY DEMOLISHED CIRCUITS IN THE

AREA.

EGN-23 ALL EMPTY RACEWAYS SHALL HAVE PULL WIRE AND TERMINATED ABOVE CEILING AT AN

ACCESSIBLE LOCATION WHERE INDICATED.

EGN-24 FOR ELECTRICAL EQUIPMENT THAT MAY NEED EXAMINATION, ADJUSTMENT, SERVICING,

OR MAINTENANCE WHILE ENERGIZED INCLUDING BUT NOT LIMITED TO PANELBOARDS,

SPACE EQUAL TO THE WIDTH AND DEPTH OF THE ELECTRICAL EQUIPMENT AND

EXTENDING FROM THE FLOOR TO A STRUCTURAL CEILING, PLUS THE WORKING SPACE

REQUIRED BY THE NEC, MUST BE DEDICATED TO THE ELECTRICAL INSTALLATION. NO

PIPING, DUCTS, OR EQUIPMENT FOREIGN TO THE ELECTRICAL INSTALLATION MAY BE

LOCATED IN THIS SPACE WITH THE EXCEPTION OF SUSPENDED CEILINGS WITH

REMOVABLE PANELS.

208 VOLT PANELBOARD

,

E

T UNDERGROUND COMMUNICATION LINES, AS NOTED

TRANSFORMER, SIZE AS INDICATED

UNDERGROUND ELECTRICAL LINES, AS NOTED

CONDUIT, CONCEALED IN CEILING OR WALL OR CHASE

,

,

LV

LD

TV

SMOKE DETECTOR, SINGLE STATION

GROUND ROD, COPPER WELD, 3/4" DIAMETER AND 10' LONG

GROUNDING CABLE

T

DOWN CONDUCTOR WITH GROUND ROD

LIGHTNING PROTECTION CABLE

SYSTEM GROUND OR EQUIPMENT GROUND

LP

G

RECEPTACLE WITH TOP OUTLET SWITCHED

,

WP

GFI

WC

CROSS HATCH LINES INDICATE THE NUMBER OF CURRENT

CARRYING CONDUCTORS CROSS HATCH LINES WITH DOT AT END

INDICATES THE EQUIPMENT GROUNDING CONDUCTOR (GREEN

WIRE) AND SHALL BE SIZED IN ACCORDANCE WITH NEC ARTICLE

250. GREEN GROUNDING WIRE SHALL BE PROVIDED WITH EACH

CIRCUIT, AND/OR FEEDER. WHERE NO WIRES ARE INDICATED,

PROVIDE 2 (TWO) CURRENT CARRYING # 12 AWG CONDUCTORS

AND 1 (ONE) # 12 GROUND FOR BRANCH CIRCUIT WIRING IN

MINIMUM 3/4" RACEWAY UNLESS OTHERWISE INDICATED IN THE

SCHEDULES.

SMOKE DETECTOR WITH HORN, SINGLE STATION

a

a INDICATES SWITCH LEG OR CONTROL ZONE

FIRE ALARM SYSTEM HORN

# #

EQUIPMENT/DEVICE

MOUNTING HEIGHT

DUPLEX RECEPTACLE - CEILING

,

JJ

F

OUTLET BOX FOR CARD READER CARD READER BY GC AND WIRING BY OWNER -

PROVIDE OUTLET BOX WITH 1" RACEWAY, PULL WIRE AND TERMINATE AT AN

ACCESSIBLE LOCATION 6" ABOVE CEILING

DATA OUTLET. PROVIDE OUTLET BOX, TWO (2) RJ-45 JACKS AND COVER PLATE WITH

1-1/4" RACEWAY, PULL WIRE AND EXTEND 6" ABOVE CEILING. OWNER WILL PROVIDE

TWO (2) - 4 PAIR CAT 6 CABLE AND EXTEND TO NEAREST IT ROOM. OWNER WILL

TERMINATE CABLES ON BOTH ENDS. MH = 18" AFF, C = 9" ABOVE COUNTER MH

TELEPHONE/DATA OUTLET. PROVIDE OUTLET BOX, TWO (2) RJ-45 JACKS & COVER PLATE WITH1-1/4" RACEWAY, PULL WIRE AND EXTEND 6" ABOVE CEILING. OWNER WILL PROVIDE: DATA -ONE (1) - 4 PAIR CAT 6 (BLACK) & VOICE - ONE (1) 4 PAIR CAT 5E (WHITE) CABLES AND EXTEND TONEAREST IT ROOM. OWNER WILL TERMINATE CABLES ON BOTH ENDS. MH = 18" AFF, C = 9"ABOVE COUNTER MH

a INDICATES SWITCH LEG OR CONTROL ZONE

USB

WALL MOUNTED EMERGENCY LIGHTING

L2

L3

FA1. PROVIDE FULL FIRE ALARM SYSTEM WITH MAIN FIRE ALARM CONTROL PANEL LOCATED IN IT

ROOM OR AS DIRECTED BY OWNER (GAMEWELL FCI 7100 WITH SILENT KNIGHT 5129 4

CHANNEL COMMUNICATOR BY HONEYWELL).

FA2. PROVIDE THE NEW FIRE ALARM SYSTEM FOR THE ENTIRE FACILITY TO COMPLY WITH NFPA

72, NFPA 70, AND TO MEET THE REQUIREMENTS OF THE AUTHORITIES HAVING

JURISDICTION.

FA3. MAINTAIN COMPLETE FIRE ALARM SYSTEM WITHIN AND ADJACENT OF WORK SPACES AS

FULLY WORKING SYSTEM.

FA4. THE CONTRACTOR SHALL BE RESPONSIBLE TO APPLY AND GET THE FIRE ALARM PERMIT

FROM LOCAL AUTHORITY HAVING JURISDICTION.

FA5. CONTRACTOR SHALL BE FULLY RESPONSIBLE TO PREPARE AND SUBMIT ALL DRAWINGS AND

DOCUMENTATION AS REQUIRED BY LOCAL GOVERNMENT (AHJ) FOR FIRE ALARM SYSTEM

PERMIT. ALL COSTS ASSOCIATED WITH PREPARING THE DRAWINGS AND OTHER

DOCUMENTATION AND PERMIT FEES FOR PERMITS SHALL BE INCLUDED IN THE BASE BID.

FA6. FACP SHALL HAVE MINIMUM 20% SPARE CAPACITY. PROVIDE BATTERY WITH SPARE

CAPACITY, EXPANSION MODULES AND NOTIFICATION APPLIANCE CIRCUITS

ACCORDINGLY. ALL COSTS OF ANY AND ALL FIRE ALARM SYSTEM FOR THIS PROJECT SHALL

BE INCLUDED IN BASE BID.

FA7. PROVIDE FIRE ALARM SYSTEM EQUIPMENT, DEVICES, ENGINEERING, PROGRAMMING,

INSPECTIONS, AND TESTS FOR A FULLY WORKING SYSTEM ACCEPTABLE TO AHJ AND OWNER.

FA8. ALL CIRCUITS SHALL BE CLASS A AND SHALL BE RUN IN MINIMUM 3/4" METAL RACEWAYS.

LABEL EACH RACEWAY. ALL NEW RACEWAYS AND BACK BOXES SHALL BE CONCEALED. ANY

SURFACE MOUNTED RACEWAYS SHALL BE PAINTED TO MATCH ADJACENT SURFACE. ALL NEW

JUNCTION BOXES SHALL HAVE RED PAINTED COVER PLATES. ALL JUNCTION BOXES SHALL

HAVE A PERMANENT, MACHINE PRINTED LABEL READING “FIRE ALARM CIRCUIT” ON THE

INSIDE COVER. ALL FIRE ALARM CONDUIT SHALL BE RED OR MARKED WITH 3/4 INCH WIDE

RED BANDS EVERY 10 FEET AND AT EACH SIDE OF FLOORS, WALLS, AND CEILINGS.

FA9. ALL DRAWINGS ARE CONCEPTUAL IN NATURE. DRAWINGS DO NOT SHOW EXACT LOCATIONS

OF COMPONENTS NOR DO THEY SHOW ALL REQUIRED COMPONENTS. PROVIDE ALL

COMPONENTS NECESSARY FOR A PROPERLY INSTALLED, FULLY FUNCTIONAL SYSTEM IN

ACCORDANCE WITH THE APPLICABLE CODES AND STANDARDS.

FA10. DURING THE PROJECT MAINTAIN ALL FIRE ALARM SYSTEMS, CONDUIT, CIRCUITS, AND

DEVICES IN OPERATIONAL CONDITION. DURING CONSTRUCTION, NO AREA OF THE BUILDING

SHALL BE LEFT WITHOUT AN OPERATIONAL FIRE ALARM SYSTEM EXCEPT THE PROJECT

AREAS.

FA11. PROVIDE ANNUNCIATOR PANEL AND GRAPHICS TO REFLECT ALL COMPONENTS INCLUDING

BUT NOT LIMITED TO NEW LED PILOT LIGHTS FOR WATER FLOW AND TAMPER SWITCHES.

ELECTRICAL LEGEND

NOTE:

LEGENDS ARE GENERAL, NOT ALL SYMBOLS, ABBREVIATIONS, AND/OR

DESIGNATIONS MAY APPEAR ON THE DRAWINGS.

ANNOTATIONSAS/AF AMPERES SWITCH & FUSE RATING

A, AMP AMPERES

ABBREV ABBREVIATIONS

AC ALTERNATING CURRENT, ARMORED CABLE

ACU AIR CONDITIONING UNIT

AF AMPERE FRAME

AFF ABOVE FINISHED FLOOR

AFG ABOVE FINISHED GRADE

AHU AIR HANDLING UNIT

AIC AMPERE INTERRUPTING CAPACITY

ATC AUTOMATIC TEMPERATURE CONTROL

ATS AUTOMATIC TRANSFER SWITCH

AUX AUXILIARY

AWG AMERICAN WIRE GAUGE

BES BLDG ELECTRICAL SYSTEM

BIL BASIC IMPLUSE LEVEL

BLDG BUILDING

BKBD BACKBOARD

BRKR BREAKER

C CONDUIT

CB CIRCUIT BREAKER

CCTV CLOSED CIRCUIT TELEVISION

CKT CIRCUIT

CR CARD READER

CL CURRENT LIMITING

CLG CEILING

CPT CONTROL POWER TRANSFORMER

CT CURRENT TRANSFORMER

CUH CABINET UNIT HEATER

CW COOL WHITE

DGS DIESEL GENERATOR SET

DIA DIAMETER

DISC DISCONNECT

DIST DISTRIBUTION

DN DOWN

DP DISTRIBUTION PANEL

DVR DIGITAL VIDEO RECORDER

DWG DRAWING E, EMERGENCY

EBH ELECTRIC BASEBOARD HEATER

EC EMPTY CONDUIT

ECB ENCLOSED CIRCUIT BREAKER

EF EXHAUST FAN

EGS ELECTRIC GENERATOR SET

EH ELECTRIC HEATER

ELECT ELECTRICAL

EMT ELECTRICAL METALLIC TUBING

ENCL ENCLOSURE

EQUIP EQUIPMENT

ER EXISTING RELOCATED

ETR EXISTING-TO-REMAIN

EWC ELECTRIC WATER COOLER

EWH ELECTRIC WATER HEATER

EX EXISTING

EXH EXHAUST

F FUSED OR FUSIBLE

FA FRAME AMPERE

FAAP FIRE ALARM ANNUNCIATOR PANEL

FACP FIRE ALARM CONTROL PANEL

FADS FIRE ALARM AND DETECTION SYSTEM

FBO FURNISHED BY OTHERS

FCU FAN COIL UNIT

FDR FEEDER FL, FLOOR

FLUOR FLUORESCENT

FSS FUSED SAFETY SWITCH FT, FOOT OR FEET

FVNR FULL VOLTAGE NON REVERSING

GFCI GROUND FAULT CURRENT INTERRUPTER

GND GROUND

GN GENERAL NOTE

GRS GALVANIZED RIGID STEEL

GWB GYPSUM WALL BOARD

GW GROUND WIRE

HC HANDICAP

HD HEAVY DUTY HID, HIGH INTENSIFY DISCHARGE

HOA HAND-OFF-AUTOMATIC HP, HORSE POWER

HPS HIGH PRESSURE SODIUM

HTR HEATER

HV HIGH VOLTAGE

HVAC HEATING, VENTILATING AND AIR CONDITIONING

HZ HERTZ

IE THAT IS

IMC INTERMEDIATE METAL CONDUIT

JB JUNCTION BOX

KCMIL THOUSAND CIRCULAR MILLS KV, KILOVOLT

KVA KILOVOLT-AMPERE

KW KILOWATT

KWH KILOWATT-HOUR

LA LIGHTNING ARRESTOR

LS LIMIT SWITCH

LTG LIGHTING

LV LOW VOLTAGE MAX, MAXIMUM

MCB MAIN CIRCUIT BREAKER

MCC MOTOR CONTROL CENTER

MCP MOTOR CIRCUIT PROTECTOR

MH MOUNTING HEIGHT MIN, MINIMUM

ABBREVIATIONSMDP MAIN DISTRIBUTION PANEL

MTD MOUNTED

MLO MAIN LUGS ONLY

MTG MOUNTING

MUX MULTIPLEXER

N NEUTRAL

NC NORMALLY CLOSED

NEC NATIONAL ELECTRICAL CODE

NIC NOT-IN-CONTRACT

NL NIGHT LIGHT

NO NORMALLY OPEN

NTS NOT TO SCALE

NFSS NON FUSED SAFETY SWITCH

OC ON CENTER

OH OVERHEAD

OL OVERLOAD

P POLE OR POLES

PF POWER FACTOR

PH PHASE

VT POTENTIAL TRANSFORMER

PL PILOT LIGHT

PNL PANELBOARD

PVC POLYVINYL CHLORIDE

R REMOVE

RAF RETURN AIR FAN RECEPTACLE

REQD REQUIRED

RGS RIGID GALVANIZED STEEL

RMS ROOT MEAN SQUARE

RS RAPID START

RVAT REDUCED VOLTAGE AUTOTRANSFORMER

S/N SOLID NEUTRAL

SD SMOKE DETECTOR

SEC SECONDARY

SFA SPRINKLER FLOW ALARM

SMR SURFACE METAL RACEWAY

SPEC SPECIFICATION

ST SHUNT TRIP

SS SUB STATION

STR STARTER

SW SWITCH

SWBD SWITCHBOARD

SWGR SWITCHGEAR

SYS SYSTEM SYM SYMMETRICAL

SOPN SPACE OR POLE NUMBER

TA TRIP AMPERE

TB TERMINAL BOX

TC TIME CLOCK

TD TIME DELAY

TTB TELEPHONE TERMINAL BOARD/BLOCK

TTC TELEPHONE TERMINAL CLOSET

TYP TYPICAL TV TELEVISION

UC UNDER COUNTER

UG UNDERGROUND

UH UNIT HEATER

UOI UNLESS OTHERWISE INDICATED

UON UNLESS OTHERWISE NOTED

UL UNDERWRITER'S LABORATORY

USB UNIVERSAL SERIAL BUS

V VOLT (S) OR VOLTAGE

VA VOLT AMPERE

VFD VARIABLE FREQUENCY DRIVE

W WIRE W/ WITH

WP WEATHER PROOF, WORK PHONE

WW WIREWAY

XFMR TRANSFORMER

PH PHASE ɸ

# NUMBER

C CENTER LINE

@ AT

#

MOUNTING HEIGHTS

SWITCHES, 48"

RECEPTACLE-GENERAL 18"

RECEPTACLE-SPECIAL 18"

RECEPTACLE-SINGLE 18"

RECEPTACLE-REST ROOM 9" ABOVE BASIN

RECEPTACLE-COUNTER 8" ABOVE COUNTER

RECEPTACLE- MONITOR (DISPLAY) 78" OR DIRECTED BY OWNER IN FIELD

RECEPTACLE-EXTERIOR 30"

CABLE TV OUTLET 78" UON

TELEPHONE/DATA-GENERAL 18"

TELEPHONE-WALL TYPE 54", (48" FOR ADA ACCESSIBLE)

FIRE ALARM PULL STATION 48"

FIRE ALARM AUDIO/VISUAL DEVICE 80"

CARD READER 40"

EXIT LIGHT WALL MOUNTED, 90" OR 12" ABOVE DOOR

EXIT LIGHT CEILING MOUNTED 96" AFF

SAFETY SWITCH, VFD, STARTER 72" TO HANDLE

ENCLOSED CIRCUIT BREAKER 72" TO HANDLE

PANELBOARD 72" TO TOP CB

MANUAL MOTOR STARTER 48" PUSH BUTTON, 48"

AUTOMATIC DOOR OPENER 36"

EMERGENCY BATTERY UNIT - WALL 18" BELOW CEILING OR 8' AFF

EXIT SIGN - WALL 6" ABOVE DOOR JAMB ,NO HIGHER THAN 8' AFF

CONTACTOR 5' AFF

DISCONNECT SWITCH 5' AFF

PANELBOARD (6' TALL) TOP TRIM 6' AFF, OR FROM BOTTOM 6" AFF

MOTION SENSOR - WALL 8' AFF OR MANUFACTURER SPECIFICATION

CAMERA - WALL 7'-6" AFF

INTERCOM STATION 48" AFF

MONITOR - WALL 7'-6" AFF

FIRE SYSTEM GENERAL NOTES

LIGHTING SYMBOLSLED LIGHTING FIXTURE

LED LIGHTING FIXTURE WITH BATTERY BACKUP

WALL MOUNTED FIXTURE

INDUSTRIAL TYPE LED FIXTURE

INDUSTRIAL TYPE LED FIXTURE WITH BATTERY BACKUP

CEILING MOUNTED DOWN LIGHT; NORMAL ,

WITH BATTERY BACKUP

WALL MOUNTED LIGHTING FIXTURE

WALL WASH/DOWN LIGHT, CEILING MOUNTED

COVE FIXTURE. LENGTH AS SHOWN ON DRAWINGS

TRACK LIGHT WITH FIXTURE

FIRE ALARM SYMBOLS

FIRE ALARM SYSTEM INDIVIDUAL HORN AND STROBE LIGHT

EXIT LIGHT BACK MOUNTED & w/ DIRECTIONAL

CHEVRON AS INDICATED

LIGHTING / POWER CONTROLS SYMBOLS

OS

VS

PS

PP

SINGLE POLE SWITCH

THREE WAY SWITCH

DOUBLE POLE DISCONNECT

LOW VOLTAGE SWITCH

LOW VOLTAGE DIMMER

TWO BUTTON ENTRY ROOM CONTROL STATION (LIGHTING)

THREE BUTTON ENTRY ROOM CONTROL STATION (LIGHTING)

OCCUPANCY SENSOR CEILING, WALL

VACANCY SENSOR

PHOTO SENSOR

POWER PACK

TELEPHONE/DATA SYMBOLSPOWER SYMBOLS

C

DUPLEX RECEPTACLE MOUNTED ABOVE COUNTER

ABOVE BACKSPLASH

DUPLEX RECEPTACLE WITH (2) UNIVERSAL SERIAL

BUS PORTS

CONDUIT CONCEALED IN FLOOR OR UNDERFLOOR OR

UNDERGROUND

ELECTRICAL GENERAL NOTES

#

FIRE ALARM BELL

#

FIRE ALARM BELL AND STROBE

FIRE ALARM SYSTEM COMBINATION HORN AND STROBE LIGHT ASSEMBLY

FIRE ALARM SYSTEM CARBON MONOXIDE DETECTOR, M.H. 54" AFF

FIRE ALARM - MAGNETIC DOOR HOLDER

CO

MMETER

1. UNLESS INDICATED OTHERWISE ON THE PLANS OR AS DIRECTED BY THE OWNER, CENTERLINE OF

DEVICE SHALL BE AS INDICATED ABOVE.

2. WHERE MOUNTING HEIGHTS ARE NOT DETAILED OR DIMENSIONED, THE CONTRACTOR SHALL

INSTALL SYSTEMS, MATERIALS, AND EQUIPMENT TO PROVIDE THE MAXIMUM HEADROOM

POSSIBLE AND COMPLY WITH THE REQUIREMENTS OF EQUIPMENT MANUFACTURER, APPLICABLE

CODES AND STANDARDS, AND AHJ REQUIREMENTS. WHERE EQUIPMENT IS INTENDED, SPECIFIED,

OR NOTED TO BE MOUNTED OTHER THEN INDICATED ABOVE, MOUNT IN ACCORDANCE WITH THE

MANUFACTURER'S RECOMMENDATIONS AND AS DIRECTED. NOT ALL EQUIPMENT INDICATED WITH

MOUNTING HEIGHTS ARE SHOWN ON THESE CONTRACT DOCUMENTS.

3. COORDINATE EXACT LOCATIONS AND MOUNTING HEIGHTS IN THE FIELD BEFORE ANY CORE

DRILLING, CUTTING, AND ROUGH-INS.

G

FLR WALL

FLOOR MOUNTED TELEPHONE/DATA OUTLET. PROVIDE OUTLET BOX, TWO (2) RJ-45 JACKS &COVER PLATE WITH 1-1/4" RACEWAY, PULL WIRE AND EXTEND 6" ABOVE CEILING. OWNER WILLPROVIDE PROVIDE: DATA - ONE (1) - 4 PAIR CAT 6 (BLACK) & VOICE - ONE (1) 4 PAIR CAT 5E(WHITE) CABLES AND EXTEND TO NEAREST IT ROOM. OWNER WILL TERMINATE CABLES ONBOTH ENDS. MH = 18" AFF

CR

C

PA

C

SECURITY SYSTEM SYMBOLS

SA

UNDER-COUNTER (SILENT 911 ALARM), FURNISHED AND INSTALLED BY OWNER -

PROVIDE OUTLET BOX WITH 1" RACEWAY, PULL WIRE FROM 6" ABOVE ACCESSIBLE

CEILING TO LOCATION UNDERNEATH DESK.

PANIC ALARM BUTTON, FURNISHED AND INSTALLED BY OWNER - PROVIDE OUTLET

BOX WITH 1" RACEWAY AND PULL WIRE AND TERMINATE AT AN ACCESSIBLE

LOCATION 6" ABOVE CEILING

PANIC ALARM STROBE, FURNISHED AND INSTALLED BY OWNER - PROVIDE OUTLET

BOX WITH 1" RACEWAY AND PULL WIRE AND TERMINATE AT AN ACCESSIBLE

LOCATION 6" ABOVE CEILING

CEILING MOUNTED SECURITY CAMERA BY OWNER - PROVIDE JUNCTION BOX WITH

1" RACEWAY, PULL WIRE AND EXTEND 6" ABOVE CEILING.

WALL MOUNTED SECURITY CAMERA BY OWNER - PROVIDE JUNCTION BOX WITH 1"

RACEWAY, PULL WIRE AND EXTEND 6" ABOVE CEILING. PROVIDE 1-1/2" SLEEVE

THROUGH THE WALL FOR LOW VOLTAGE WIRING.

OUTLET BOX FOR CONNECTIONS TO HDTV AT MEETING ROOM, MOUNTED 60" AFF ANDCOORDINATED WITH ASSOCIATED RECEPTACLE DESIGNATED FOR TV. PROVIDE OUTLET BOXAND COVER PLATE FOR THE FOLLOWING AT THE LOCATION INDICATED:

* FUTURE COAX CONNECTION. PROVIDE 1" RACEWAY WITH PULL WIRE TO 6" ABOVECONCEALED, ACCESSIBLE CEILING

* (2) RJ-45 JACKS. PROVIDE 1-1/4" RACEWAY AND PULL STRING TO 6" ABOVE CONCEALED,ACCESSIBLE CEILING.

DLDAYLIGHT SENSOR

PL

PLUG LOAD CONTROLLER

OS

N

CAT 5 CABLE (LIGHTING)

WS1.

WS2.

WS3.PROVIDE 4 CIRCUIT FMC TO HARD-WIRED JUNCTION BOX/POWER IN-FEED.

WS4.

WS5.

WS6.

WS7.

WS8.

WS9.

WS10.

WORKSTATION NOTESFOR WALL FED POWER SOURCE, SURFACE OR FLUSH MOUNT JUNCTION BOX(S) AS

CLOSE AS POSSIBLE TO THE FURNITURE'S POWER IN-FEED. POWER IN-FEED CORD

AND CAP FURNISHED BY FURNITURE MANUFACTURE AND INSTALLED BY

CONTRACTOR. FOR PROTECTION FROM DAMAGE, STRAP/SECURE IN-FEED CORD

FIRMLY TO WALL AND FURNITURE AS DIRECTED BY THE FURNITURE

MANUFACTURER.

FOR WALL FED VOICE/DATA SERVICES, SURFACE OR FLUSH MOUNT JUNCTION

BOX(S) AS CLOSE AS POSSIBLE TO THE FURNITURE'S BASE IN-FEED. PROVIDE

GROMMET IN COVER PLATE TO PROTECT CABLES FROM DAMAGE. ROUTE CABLE

THROUGH BASE OF WORKSTATION FURNITURE VIA HORIZONTAL CABLE SUPPORTS

FURNISHED BY FURNITURE MANUFACTURER AND INSTALLED BY CONTRACTOR.

CONCEAL CABLE IN FURNITURE. FOR VERTICAL STRAIN-RELIEF, FASTEN CABLE TO

THE FURNITURE'S STRUCTURAL MEMBERS.

THE WORKSTATION ELECTRICAL SYSTEM TO BE PROVIDED WILL UTILIZE A 3 UTILITY,

1 ISOLATED CIRCUIT, 8 WIRE SYSTEM WITH A COMMON (4) #12 LINE (2) #10

NEUTRAL AND (2) #12 GROUND. AT THE POINT OF TERMINATION FOR THE POWER

IN-FEED CABLE, THE CONTRACTOR SHALL COMBINE THE NEUTRALS AND GROUNDS AS

DIRECTED BY THE FURNITURE MANUFACTURER. PRIOR TO THE POINT OF

TERMINATION, THE NEUTRALS AND GROUND SHALL REMAIN DEDICATED TO THE

SPECIFIC CIRCUIT.

FIRMLY ATTACH POWER IN-FEED CABLE AND FMC TO WALL JUNCTION BOX COVER VIA

UL LISTED FITTINGS/CONNECTORS WITH INSULATED THROATS.

DUPLEX RECEPTACLES WILL BE FURNISHED AND INSTALLED BY THE FURNITURE

MANUFACTURER.

VOICE/DATA CABLE AND OUTLETS PROVIDED IN BASE PATHWAY BY CONTRACTOR.

INSTALL OUTLETS IN FURNITURE KNOCKOUTS IN THE LOCATION AS DIRECTED BY THE

OWNER. PROVIDE 3 DATA AND 1 VOICE PORT PER OUTLET FOR EVERY SEAT AS SHOWN

ON THE FURNITURE LAYOUT DRAWINGS. FURNITURE SHALL BE PROVIDED WITH

METALLIC SEPARATION BETWEEN POWER WIRING AND VOICE/DATA CABLES.

ALL JUNCTION BOXES SHALL BE MADE READILY ACCESSIBLE INCLUDING HARDWIRED

JUNCTION BOXES FURNISHED BY THE MANUFACTURER.

ALL POWER AND VOICE/DATA CABLING WORK WILL BE PERFORMED BY THE SYSTEM

FURNITURE QUALIFIED INSTALLER. THE FURNITURE VENDOR WILL FURNISH AND INSTALL

POWER IN-FEEDS (OR BASE FEEDS) AND RECEPTACLES (POWER OUTLETS). RECEPTACLES

WILL BE CORCUITED/CONNECTED BY THE FURNITURE VENDOR AS SHOWN ON THE FLOOR

PLANS WITH THE FINAL POWER IN-FEED SERVICE CONNECTION BY THIS CONTRACT.

DATA AND VOICE PORTS (OUTLET JACKS) INCLUDING CABLING AND FINAL

TERMINATIONS IN THE FURNITURE SHALL BE PROVIDED BY THE CONTRACTOR. CABLE

COVER WILL BE FURNISHED AND INSTALLED BY MANUFACTURER / FURNITURE VENDOR.

COORDINATE ROUTING OF CABLES WITH FURNITURE INSTALLER BEFORE PROCEEDING

WITH ANY ROUGH-IN WORK.

SEE FLOOR PLAN(S) FOR FURNITURE POWER AND VOICE/DATA SERVICE LOCATIONS.

VERIFY LOCATION OF FURNITURE POWER IN-FEED POINT OF TERMINATION WITH THE

WORKSTATION MANUFACTURER / FURNITURE VENDOR BEFORE PROCEEDING WITH ANY

ROUGH-IN WORK. PROVIDE QUANTITY OF JUNCTION BOXES AS NECESSARY TO

ACCOMMODATE THE POWER AND VOICE/DATA WIRING/CABLING NEEDS OF THE

FURNITURE. NOT ALL SERVICE FEEDS/LOCATIONS MAY BE SHOWN. TO ACCOMMODATE

CHANGES IN THE FINAL FURNITURE LAYOUT, INCREASE THE NUMBER OF SERVICE

LOCATIONS SHOWN ON THE FLOOR PLANS BY ADDITIONAL 25 PERCENT.

LIGHTNING PROTECTION CABLELP

POWER PACK

PUSH PLATE FOR HANDICAPPED ACCESS DOOR

PB

PC

PHOTOCELL

PP

REMOTE DIGITAL FIRE ALARM TRANSMITTER

110

110

THE NUMBER ADJACENT TO THE SYMBOL INDICATES PREFERRED CANDELA

VALUE. STROBE SYMBOL WITHOUT IDENTIFICATION SHALL BE AS FOLLOWS:

CORRIDORS/HALLWAYS - 30 CANDELA, ROOMS <= 2,000 SQFT - 75 CANDELA,

ROOMS > 2,000 SQFT - 110 CANDELA.

,

,

TV

OUTLET BOX FOR CONNECTIONS TO HDTV AT MEETING ROOM, MOUNTED 60" AFF ANDCOORDINATED WITH ASSOCIATED RECEPTACLE DESIGNATED FOR TV. PROVIDE OUTLET BOXAND COVER PLATE FOR THE FOLLOWING AT THE LOCATION INDICATED:

* FUTURE COAX CONNECTION. PROVIDE 1" RACEWAY WITH PULL WIRE TO 6" ABOVECONCEALED, ACCESSIBLE CEILING

* (2) RJ-45 JACKS. PROVIDE 1-1/4" RACEWAY AND PULL STRING TO 6" ABOVE CONCEALED,ACCESSIBLE CEILING.

* (2) HDMI OUTPUT. PROVIDE CABLING IN 1-1/4" RACEWAY TO CORRESPONDING HDMIINPUTS

W

TV

OUTLET BOX FOR CONNECTIONS TO HDTV AT MEETING ROOM, MOUNTED 6" ABOVE COUNTER.COORDINATE EXACT LOCATION WITH OWNER. PROVIDE OUTLET AND COVER PLATE FOR THEFOLLOWING AT THE LOCATION INDICATED:

* - (1) HDMI INPUT. PROVIDE CABLING TO WALL MOUNTED WALL PLATE IN SAME ROOM.

C

TV

FLOOR BOX MOUNTED CONNECTIONS TO HDTV AT MEETING ROOM. COORDINATE EXACTLOCATION WITH TELECOM FLOOR BOX AT SAME ROOM AND OWNER. PROVIDE OUTLET ANDCOVER PLATE FOR THE FOLLOWING AT THE LOCATION INDICATED:

* (1) HDMI INPUT. PROVIDE CABLING TO WALL MOUNTED WALL PLATE IN SAME ROOM.

F

DATA OUTLET FOR SYSTEMS FURNITURE, BY OTHERS. SIZE JUNCTION BOX FOR SYSTEMFURNITURE FOR THE QUANTITY OF DEVICES AS SHOWN. COORDINATE ALL WORK WITH OWNERAND SYSTEMS FURNITURE SUPPLIER.

F

QUAD RECEPTACLE - C = 9" ABOVE COUNTER

C

AutoCAD SHX Text
P
AutoCAD SHX Text
FCP
AutoCAD SHX Text
FSA
AutoCAD SHX Text
RDAT
Page 2: ELECTRICAL LEGEND

15" SD8" SD

4" SD

6" SAN.

6" SAN.

6" SA

G

GGGGGGGG

GG

G G

6"W

4"W

6"W4"W

DR

D

JJ

E09

E11

E10E12E13

E14

E15

E16

SL1

SL1

SL1SL1SL1

SL1

SL1

SL1

OA

OA

OAOAOA

OA

OA

OA OA OA OA

E19

E20

PROPOSED FIRE AND DOMESTIC WATER INCOMING LOCATION

4' - 0"

4' -

0"

4' - 0"

4' -

0"

4' -

0"

4' - 0"

CR

PB

E60

E60

OA

SL1

OA

CLEARANCE (TYPICAL)

E37E38

E39

LP - 11

LP - 16

SERVER/DATA/TEL

125

ELECTRICAL202

LP - 16

LP - 16

LP - 16LP - 16LP - 16

LP - 16

LP - 16

LP - 16

E75

E75E76

EX

E83

E82

FOR INCOMING FIBER SERVICE. COORDINATE EXACT ROUTING AND LOCATIONWITH CIVIL DRAWINGS AND CITY.

OA

E92

E91

PP2-28,30,32

E92

SHEET NUMBER:

DRAWING TITLE:

DATE ISSUED:

PROJECT NUMBER:

PROJECT SET:

I HEREBY CERTIFY THAT THESE DOCUMENTS WERE PREPARED OR APPROVED BY ME, AND THAT I AM A

DULY LICENSED PROFESSIONAL ENGINEER UNDER THE LAWS OF THE

STATE OF MARYLAND. LICENSE NUMBER: #xxxxx

EXPIRATION DATE: mm-dd-yyyy

CO

NSU

LTAN

T:SE

AL

ALL DRAWINGS ARE PROTECTED BY FEDERAL COPYRIGHT BY MANNS WOODWARD STUDIOS, INC. AND CAN NOT BE REPRODUCED OR MODIFIED IN ANY MANNER WITHOUT WRITTEN PERMISSION. DOCUMENTS MAY NOT BE USED IN PART OR WHOLE TO DEVELOP THE DESIGN OF ANOTHER BUILDING WITHOUT EXPRESS WRITTEN PERMISSION BY MANNS WOODWARD STUDIOS.

(P) 410-344-1460(F) 443-403-2460(E) [email protected]

S T U D I O S10839-D PHILADELPHIA RDWHITE MARSH, MD 21162

ARCHITECTURE + MASTER PLANNING

Eng

inee

ring

Infra

stru

ctur

e S

olut

ions

C.C

. Joh

nson

& M

alho

tra,

P.C

.

400

Eas

t Pra

tt S

treet

, Sui

te 6

04B

altim

ore,

MD

212

02(P

) 410

-461

-992

0 | (

F) (

667)

239-

3534

| (E

) BA

LTIM

OR

E@

CC

JM.C

OM

CC

JM

3/15

/201

9 5:

02:1

1 PM

E100

BALT

IMO

RE C

ITY

ANIM

AL S

ERVI

CES

BUIL

DING

2490

GIL

ES R

OAD

, BAL

TIM

ORE

, 212

25

ELECTRICAL - SITE PLAN

03-15-2019

17-023

100% CD

1" = 20'-0"1SITE PLAN - ELECTRICAL REFERENCED NOTES - SITE PLAN

E09 UTILITY PRECAST CONCRETE PAD-MOUNTED FOR BGETRANSFORMER. COORDINATE WITH BGE FOR THEIRREQUIREMENTS.

E10 RELOCATE EXISTING 60KW DIESEL GENERATOR FROM EXISTINGFACILITY. COORDINATE RELOCATION OF EXISTING GENERATORWITH OWNER. PROVIDE WEATHERPROOF, LEVEL 2 SOUNDATTENUATION ENCLOSURE WITH ASSOCIATED COMPATIBLEANCILLARY SUPPORT SYSTEMS INCLUDING BUT NOT LIMITED TOBATTERY CHARGER, BLOCK HEATER, AND RECEPTACLES.

E11 LOCATION FOR FUTURE STANDBY GENERATOR (NOT INCONTRACT).

E12 PROVIDE 4-WAY 4" SECONDARY DUCTBANK FROM BGETRANSFORMER TO PIT UNDERNEATH SWITCHBOARD INELECTRICAL ROOM. REFER TO DUCT BANK DETAILS.

E13 PROVIDE 4-WAY 4" DUCTBANK FOR FUTURE STANDBYGENERATOR (GENERATOR NOT IN CONTRACT) FROMSWITCHBOARD TO GENERATOR DOCKING STATION. PROVIDEWEATHERPROOF JUNCTION BOX AT DOCKING STATION PADFOR NON-FEEDER TERMINATIONS.

E14 PROVIDE 2-WAY 4" DUCT BANK FOR 60 KW GENERATOR. REFERTO DETAILS. COORDINATE WITH MANUFACTURE FOR EXACTTERMINATION.

E15 PROVIDE 3-WAY 4" DUCT BANK FOR TELECOM AND CABLE TVWIRING. REFER TO DETAILS.

E16 EXISTING TO REMAIN CABLE TV DUCT BANK. PROVIDE PULL BOXFOR NEW DATA CABLE.

E19 PROVIDE 2-WAY 4" PRIMARY DUCT BANK FOR BGETRANSFORMER. REFER TO DETAILS. TERMINATE ATAPPROXIMATELY 36" AWAY FROM MANHOLE. COORDINATE WITHBGE FOR EXACT TERMINATION.

E20 COORDINATE CONNECTION TO BGE INCOMING SERVICE WITHBGE PRIOR TO COMMENCING WORK.

E37 12x12x12 JUNCTION BOX FOR POWER FOR GATE. PROVIDEBRANCH CIRCUIT AS INDICATED.

E38 12x12x12 JUNCTION BOX FOR TELECOM WIRING FOR GATE.PROVIDE 1" RACEWAY TO TELECOM ROOM.

E39 1" RACEWAY TO TEL/ELEC ROOME60 PROVIDE TIMECLOCK FOR EXTERIOR LIGHTING CONTROL, SEE

DETAIL ELECTRICAL DRAWING E600.E75 1" EMPTY CONDUIT WITH PULL STRING FOR COMMUNICATION

WIRING.E76 1" EMPTY CONDUIT WITH PULL STRING FOR CONNECTION TO

GENERATOR ANCILLARY SYSTEMS INCLUDING BUT NOT LIMITEDTO BATTERY CHARGER, BLOCK HEATER, AND RECEPTACLE.

E82 1" CONDUIT FOR CONNECTION TO RELOCATED EXISTINGGENERATOR ANCILLARY SYSTEMS, INCLUDING BATTERYCHARGER, BLOCK HEATER AND RECEPTACLE. COORDINATEWIRING WITH GENERATOR ENCLOSURE SUPPLIER.

E83 PAD MOUNTED GENERATOR DOCKING STATION, PROVIDECONCRETE PAD. COORDINATE EXACT LOCATION ANDORIENTATION WITH OWNER AND DOCKING STATION SUPPLIER.

E91 COORDINATE DUCT BANK FOR FIBER WIRING, COORDINATEWITH CIVIL DRAWINGS.

E92 ALL RECEPTACLES IN THIS LOCATION TO BE WEATHERPROOFRATED.

T P

A. CONTRACTOR TO OBTAIN ALL PERMITS/PERMISSIONSREQUIRED BY OTHERS ON PRIVATE PROPERTY. ALL MATERIALS USED SHALL CONFORM TO BGE SPECIFICATIONS. ALL WORK MUST BE DONE IN ACCORDANCE WITH BGE'S STANDARDS AND SPECIFICATIONS. THE CONTRACTOR SHALL PAY ANY AND ALL FEES FOR SERVICE.

B. WORK SHALL BE DONE IN A MANNER ACCEPTABLE TO BGE AND INSPECTED BY THEIR CONDUIT DEPARTMENT BEFORE ENCASEMENT OR BACKFILLING. (CONTRACTOR MUST FIRST SUBMIT A DRAWING OF THE FACILITIES TO BE BUILT FOR THEIR APPROVAL). CALL IN ADVANCE TO ARRANGE INSPECTION. CALL BETWEEN 7.00 - 9.00 A.M. OR 3.00 - 4.00 P.M.

C. ALL RACEWAYS FOR MEDIUM VOLTAGE CONDUCTORS SHALL BE 6 INCH CONCRETE ENCASED. CONDUIT ROUTING SHALL BE BUILT IN ACCORDANCE WITH BGE SPECIFICATIONS. COORDINATE WITH BGE. ALL SERVICE CONDUCTOR CONDUITS SHALL BE 4 INCH PVC SCHEDULE 40 CONCRETE ENCASED.

D. SWEEP BENDS SHALL COMPLY WITH BGE REQUIREMENTS.

E. NYLON PULL LINES SHALL BE INSTALLED IN EACH DUCT FOR FUTURE CABLE INSTALLATION.

F. NO MORE THAN 180° OF BENDS OF DUCT LINE IS ALLOWED.

G. DUCT BANKS MUST HAVE MINIMUM OF THREE FEET (3') OF COVER (TOP OF DUCT TO FINISHED GRADE).

H. CONDUIT SHALL BE ENCASED IN MINIMUM 3000 PSI CONCRETE WITH PEA GRAVEL. NO METALLIC MATERIALS (REBARS, HOLD DOWN WIRES, ETC.) SHALL BE PERMITTED IN SPACES BETWEEN EACH DUCT.

I. CONTRACTOR SHALL ROD ALL CONDUITS, CLEAR ANY OBSTRUCTIONS AND PROVIDE NYLON PULL LINES PRIOR TO THE INSTALLATION OF BGE CABLES.

J. FOR LOCATIONS OF UTILITIES, CALL 24 HOURS A DAY 1-800-257-7777, 48 HOURS IN ADVANCE OF ANY WORK IN THIS VICINITY.

K. ALL METERING CURRENT TRANSFORMER MOUNTING DIMENSIONS, DRILLINGS, SPACING AND STUDS MUST COMPLY WITH BGE SPECIFICATIONS. THE MINIMUM ACCEPTABLE DIMENSIONS, DRILLINGS, ETC. FOR BGE LINE CONNECTIONS TO C/T CABINETS/COMPARTMENTS (INCLUDING SAFETY BARRIER WHERE APPLICABLE).

L. BGE SHALL BE NOTIFIED 48 HOURS (2 WORKING DAYS) BEFORE POURING OF ANY CONCRETE AND/OR THE BACK FILLING OF ANY TRENCH TO MAKE ARRANGEMENTS FOR THE INSPECTION AND APPROVAL OF YOUR ON SITE SERVICE CONNECTION STRUCTURAL EQUIPMENT.

M. ALL OTHER UNDERGROUND UTILITIES IN THE VICINITY SHALL BE SHOWN BY THE CONTRACTOR. MAINTAIN THE MINIMUM HORIZONTAL AND VERTICAL CLEARANCES SET BY BGE. MAINTAIN 5'-0" MINIMUM (HORIZONTAL) AND 1'-0" (VERTICAL) CLEARANCE FROM ALL UNDERGROUND UTILITIES.

N. CALL BGE FOR BGE INSPECTIONS AND COORDINATION.

A. CONTRACTOR SHALL BE RESPONSIBLE TO CALL AND COORDINATE WITH BGE TO GET THE ELECTRICAL AND GAS SERVICES TO THE SITE.

B. CONTRACTOR SHALL BE RESPONSIBLE TO COORDINATE WITH BGE TO TERMINATE NEW RACEWAYS UNDER TRANSFORMER PAD.

C. CONTRACTOR SHALL COORDINATE WITH BGE TO PROVIDE THE PAD FOR TRANSFORMER. IF INSTALLED IN THE FIELD, ALL PADS SHALL MEET BGE REQUIREMENTS AND SHALL BE APPROVED BY BGE.

D. CONTRACTOR SHALL SUBMIT THE SHOP DRAWINGS FOR SERVICE INCOMING SWITCHBOARDS WITH INCOMING SECTION, AND DISTRIBUTION SECTIONS TO BGE FOR THEIR APPROVAL. CONTRACTOR SHALL NOT ORDER THE EQUIPMENT UNTIL WRITTEN APPROVAL BY BGE.

BGE PROPOSED CLASS OF SERVICE CONDITIONS

GENERAL NOTES:

25'-0

"2'-

0"6'-

0"

24"DIA.

LEVELING NUTS, SHIMS, ETC.

FINISHED GRADE

GROUND LUG

GROUNDING BUSHING

BASE COVER

3000 PSI CONCRETE USESONOTUBE TO FORM

UPPER PORTION OF BASE

POLE AS SPECIFIED

CIRCUIT CONDUCTORS AND CONDUITHANDHOLE-PROVIDE BUSSMAN TYPE HLR

IN-LINE TYPE FUSE WITHIN POLE. LOCATE SOFUSE IS ACCESSIBLE THROUGH HANDHOLE.

AMPACITY SHALL BE APPROPRIATE FORAPPLICATION

1/2" CHAMFER ON TOP OFEDGE IF CONCRETE BASE IS

RAISED

ANCHOR BOLTS SHALL BE ASRECOMMENDED BY

MANUFACTURER

#4 INSULATED COPPERGROUND IN CONDUIT

ATTACHED TO INTERNAL LUGWELDED TO INTERIOR OF

POLE

REBAR CAGE 4 #4 WITH#3 TIES AT 12" O.C.

CONDUIT(S) AS NOTEDPLAN

10'-0" LONG, 3/4" DIA.SOLID COPPER

GROUNDING ROD. LAIDHORIZONTALLY (AS DEEP

AS POSSIBLE) PER NECSTANDARDS.

EXPOSED PORTIONOF FOUNDATIONSHALL BE RUBBEDSMOOTH

3"

21.0"

6" 6"

3"

3" 3"

12"

3"

12"

WARNING ANDIDENTIFICATION TAPE

FINISHED GRADE

MIN.

36"

WASHEDGRAVEL FILL

4" MIN

.

2 WAY - 4 INCH DUCT BANK, TYPICALSCALE: NONE

PVC SCHEDULE 40 CONDUIT (TYP)

CONCRETE ENCASED (3000 PSI,RED COLOR)

COMPACTED BACKFILL

PARKING LOT LIGHTING POLE BASESCALE: NONE

4 WAY - 4 INCH DUCT BANKSCALE: NONE

3"

4"

3"

3" 3"

22"

3"

12"

WARNING ANDIDENTIFICATION TAPE

FINISHED GRADE

MIN.

36"

4" MIN.

PVC SCHEDULE 40 CONDUIT (TYP)

CONCRETE ENCASED (3000 PSI,RED COLOR)

COMPACTED BACKFILL

4"

4"4"

WASHEDGRAVEL FILL

3

8 9

12" DIA.

48" M

IN.

3" MIN.

36" M

IN. /

48" M

AX.

6" MIN.

1" C, TO GATE OPERATORCONTROL PANEL

NOTES:1. NEW CARD READER SHALL BE INSTALLED FOR GATE ENTRY/ACCES.

2. INCLUDE #12 AWG EQUIPMENT GROUND WIRE TO CARD READER.

3. VERIFY FINAL CARD READER UNIT ELEVATION WITH OWNER.

CURB LINE

3000 PSI CONCRETEUSE SONOTUBE TO FORMUPPER PORTION OF BASE

1/2" CHAMFERON TOP OF EDGE

ANCHOR BOLTS PERMANUFACTURERRECOMMENDATION (MIN. OF 4)

FINISHED GRADE

ADDITIONAL CONDUIT(S) TOPEDESTAL AS APPLICABLE

CARD READER OR OTHERACCESS CONTROL UNIT.INCLUDE HARDWARE FORPEDESTAL INSTALLATION

GOOSENECK PEDESTAL

CARD READER PEDESTAL DETAIL, TYPICALSCALE: NONE

2

EXISTING STREET LIGHTING TO REMAIN: SEE CIVIL DRAWING

3 WAY - 4 INCH AND 2 WAY - 1" DUCT BANK

3" 3" 3"

12"

MIN

.

3"

3"

28.0"

4" 4"

3"

WARNING ANDIDENTIFICATION TAPE

FINISHED GRADE

WASHED GRAVEL FILL

4"

SCALE: NONE

PVC SCHEDULE 40 CONDUIT (TYP)

CONCRETE ENCASED (3000 PSI,RED COLOR)

COMPACTED BACKFILL

7

4" 12"

MIN.

36"

3"

1"

1"

3"

11.0"

3"

3" 3"

12"

3"

12"

WARNING ANDIDENTIFICATION TAPE

FINISHED GRADE

MIN.

36"

4" MIN

.

PVC SCHEDULE 80 CONDUIT (TYP)FOR POWER

CONCRETE ENCASED (3000 PSI,RED COLOR)

COMPACTED BACKFILL

1" 1"

WASHEDGRAVEL FILL

2 WAY - 1 INCH DUCT BANK, TYPICALSCALE: NONE

5

1" CONDUIT FORSITE LIGHTING

1"

12"

WARNING ANDIDENTIFICATION TAPE

FINISHED GRADE

MIN.

36"

WASHEDGRAVEL FILL

4" MIN

.

CONDUIT DETAIL WITHOUT CONCRETE ENCASEMENT, TYPICALSCALE: NONE

PVC SCHEDULE 40 CONDUIT (TYP)

4

PVC SCHEDULE 80 CONDUIT (TYP)FOR POWER

3 WAY - 4 INCH

3" 3" 3"

12"

MIN

.

3"

3"

22.0"

4" 4"

3"

IDENTIFICATION TAPE

FINISHED GRADE

WASHED GRAVEL FILL

4"

SCALE: NONE

PVC SCHEDULE 40 CONDUIT (TYP)

CONCRETE ENCASED (3000 PSI,RED COLOR)

COMPACTED BACKFILL

6

2" 12"

MIN.

36"

3"

4"

NO. DESCRIPTION DATE

Page 3: ELECTRICAL LEGEND

LVLV

LVLV

LVLV

LV

LV LV LV LV LV LV LV LV LV LV LV LV LV

OS

OS

LV

OS

OSOSLV

OS

OS

OS

LV

LVLV

OS

OS

LV

LV

LVLV

LVLV

LV LVLV

LV

LV

LVLV

LV

LV LVLVLVLVLV

LV LV LV LV LV LV

LVLVLVLVLV

LV LV OS

OS OS OS

LV

LD

LVLV

LVLV

LV LV LV LD LD LD

LV

LV

LV

LV

3

OS OS

OS OS

OS

LD

LDLV

LV

LV

LV

LV

LV

LV

LV

LDLDLD

LD LD

LD

LV

LD

LD

LVLV

LV LV

LV LVLVLV

LV LV

3

DIR OF DEV117

ACCT115

HR MANAGER114

MARKETINGAND PRCOORD

113

DIR OF OPS112

EXEC ASST111

EXEC DIR110

VOLUNTEERMANAGER

109

OFFICEMANAGER

108

FRONT OFFICE106

CORRIDOR107

WATER120

COPY/ WORKROOM

119

VET TECHGROUP

121

VET GROUPOFFICE

122

GENERALSTORAGE

124

FILE ROOM123

SERVER/DATA/TEL

125

JAN129

TOILET130

TOILET131

MEETINGROOM

103

TOILET126

TOILET127

TOILET104

TOILET105

PUBLIC LOBBY101

OBEDIENCETRAINING

102

LOUNGE128

DOG & CATKITCHEN

147

DOG & CATFOOD & LITTER

STORAGE148

COMMERCIALLAUNDRY

149

CAT BITEQUARANTINE

150

CAT ISOLATION151

CATOBSERVATION

152

GROOMING143

REPTILE/WILDLIFE

142

SMALLMAMMALS

141

CAT ROOM144

CAT ROOM145

CAT ROOM146

CAT COMM133

CAT COMM134

CAT COMM135

CAT COMM136

GETACQUAINTED/

ADOPTIONCLASSROOM

137

SURRENDER/FOSTER EXAM

138

FOSTER/SURRENDER

LOBBY139

OPENWORKSTATIONS

118

DOG ROOM153

DOG ROOM154

DOG ROOM155

DOGOBSERVATION

156

DOGQUARANTINE

157

DOGISOLATION &

SICK158

ELECTRICAL202

T&S 3199

T&S 4201

WOMEN'SLOCKER ROOM

198

MEN'S LOCKERROOM

197

T&S 1195

T&S 2196

AC GARAGE193

AC SUPPLIES/EVIDENCE

192

AC RADIOLOCKER/

EQUIPMENT191

AC BREAKROOM

190OFFICE

187

DOG INTAKE175

CAT INTAKE176

CLEANING/EQUIPMENTSTORAGE

171

SURGERYCORRIDOR

159

VET OFFICE172

DOG EXAM173

CAT EXAM174

SURGERY170

TNR CATHOLDING

169

SURGERYPREP168

DOG HOLDING162

CAT HOLDING163

CATRECOVERY

164

DOGRECOVERY

(BEACH)165

DOGRECOVERY

166

OXYGENSTORAGE

167

SURRENDER/FOSTER EXAM

140

LAB/PHARMACY

177X-RAY RM

178

LAUNDRY &CLEANUP

179

MEDICALSTORAGE

180EUTHANASIA

181

TOILET183

TOILET184

CORRIDOR160

OFFICE188

OFFICE189

OPENWORKSTATIONS

185DIR AC

186

CORRIDOR132

SURGERYCORRIDOR

159

CORRIDOR132

A A

A A

A A

A A

AA

A A

A A

A A

A A

A A

A

A

A

A

A

A

A

A1

A A

A A

A A

A A

A A

A A

A A

A A

AA

A A A

A A

A

A1 A A

AAA

A A A

AAA

A1 A A

A

A1

A

A1

A1 A A A1 A A A A1 A A1 A A A A1 A A A A1

A1

A

A

A

A

A

A1

A

A

A

A1

A1AAAAAA1A1AAAA

A

A

A1

A

A A1 A A

A

A1

A

A A1

A

A

A

A1A

X X X X X X X X

X

X

X

XX

X

X

X

X

XX

X

X

X

X

A

A

A

A1

A1

A

A1 A1

A1A1

A A

AA

A AA

A

A1

A

AA

AA

A

A

A

A

A

A

A

A1

A1

A

A

A

A

A

A

AAA

A

A A

A

A

GL GL1

GL GL

GL GL

A1 A

A1 A

D D

A A

A A

A A

TRAPSTORAGE

194

DOG HOLDING161

LP - 14 LP - 14

LP - 14 LP - 14

LP - 14 LP - 14

LP - 14 LP - 14

LP - 14 LP - 14

LP - 14 LP - 14

LP - 14 LP - 14

LP - 14 LP - 14

LP - 14 LP - 14

LP - 14 LP - 14

LP - 14

LP - 14

LP - 14

LP - 14

LP - 14

LP - 14

LP - 14

LP - 15

LP - 10

LP - 10

LP - 10

LP - 10

LP - 10

LP - 10

LP - 10

LP - 19LP - 10LP - 10LP - 10LP - 15LP - 15LP - 15

LP - 15

LP - 15

LP - 15

LP - 10LP - 10 LP - 10

LP - 10

LP - 14

LP - 14

LP - 14

LP - 14 LP - 14

LP - 14LP - 14LP - 14

LP - 14 LP - 14

LP - 14LP - 14LP - 14

LP - 14 LP - 14

LP - 15

LP - 15

LP - 15

LP - 15 LP - 15 LP - 15

LP - 13 LP - 13

LP - 13 LP - 13

LP - 13 LP - 13

LP - 13LP - 13

LP - 13 LP - 13

LP - 13 LP - 13

LP - 13LP - 13

LP - 13 LP - 13 LP - 13 LP - 13

LP - 13LP - 13

LP - 13 LP - 13

LP - 13LP - 13 LP - 13

LP - 13

LP - 13

LP - 13

LP - 13

LP - 13

LP - 13

LP - 13LP - 13

LP - 13

LP - 15 LP - 15 LP - 15

LP - 15

LP - 15

LP - 15

LP - 15 LP - 15 LP - 15 LP - 15

LP - 15

LP - 15

LP - 15

LP - 15LP - 15 LP - 10 LP - 10 LP - 10 LP - 10 LP - 10

LP - 10

LP - 10

LP - 10LP - 10

LP - 10

LP - 10

LP - 10

LP - 10LP - 10

LP - 10

LP - 10

LP - 10

LP - 15

LP - 15

LP - 15

LP - 18 LP - 18

LP - 18 LP - 18

LP - 18 LP - 18

LP - 18LP - 18

LP - 18 LP - 18

LP - 18LP - 18

LP - 19

LP - 19

LP - 19

LP - 19

LP - 19 LP - 19

LP - 19

LP - 19

LP - 19

LP - 19

EL1 - 34

LP - 19

LP - 19LP - 19

LP - 19

LP - 19

LP - 19

LP - 19

LP - 19

LP - 19

LP - 19

LP - 19

LP - 19

LP - 6

LP - 6

LP - 6

LP - 6

LP - 6

LP - 6

LP - 6 LP - 6 LP - 7 LP - 7

LP - 7 LP - 7

LP - 7 LP - 7

LP - 7LP - 7

LP - 7 LP - 7

LP - 7LP - 7

LP - 13 LP - 13

GL GL

LP - 15

LP - 12

?

LP - 15

LP - 14

LP - 4

LP - 15

LP - 15

LP - 2 LP - 10

LP - 19

LP - 7

LP - 7

LP - 2LP - 17LP - 17LP - 9LP - 9LP - 12

LP - 10

LP - 10

PS PS PS1

PSPSPS

PS1 PS PS

PS PS

PS

PS1PSPS

AC

AC

MP8

XLP - 10

E24

E24

GL

GL

GL

LP - 7

LP - 7

LP - 10

MP81

MP8 MP8

LP - 4

LP - 4

LP - 4

LP - 4

TLEL1 - 40

OS

OS

OS OS OS OS OS OS OS OS OS OS OS OSOS

OS

OS

OS

OS

OS

OS

OS OS

OS

OS OS OS

OS

OS

OS

OS

OS

OS

OS

OS

OSOS

OS

OS

OS

OS

OS

OS

OS

VS

VS

OS

OS

E21

E21

E21

E21

E21

E21E21

E21E21E21E21E21

E21

E21

E21

E21

E21

E21

E21

E21

E21

E21

E21

E21

E21

E21

E21

E24

E24E24e e e

f f

f f

e,f e,f

LP - 7

LP - 7

GL

OS OS

OS

OS

OSOS

OS

OS

OS

OS

OS

OS OS

OS

OS

OS

OSOS

OS

D D1 D D1

D D D D D

D D D D D

D D D D D

DDD1DD

D1

D

D

D

D D D1

D

D

D

D1D D1D

DD

DD

D D

DD

D

D

D

D1 D1

D

D

D

D D

D

D

D

D D1

D

D

D

D1 D D

DD

D D

DD

D D1 D1

D

D

D

D D D

DD

DD

DD

D1D

D D D1 D D

DDDDD

D D D D D

DDDDD

D1 D D1 D D1 D1

D

D

D

D D D1

D

DD

DD

D1D D

D

D

D

D D

D

D

D

D1

A A

AA

A A A

A

A DC

DC

DC DC

DC

DC

DCDC

DC DC

DCDC

DC DCDC

DCDC

DC

DC DC

DCDCDCDC

DC DC

DC DC

DC DC

D12 D12

D12 D12

D12 D12

D12 D12

D12 D12

D12 D12

DR DR

DR DR DR

DR

DR DR

DRDR

DR DR

D12

D12

D12

DR DR

DRDR

AC AC

ACAC

AC AC

DR DR

DR DR

DR DR

DR DR

D

D

D D

D

D D

D

D D

D

D A

A

A

A

A

A

A

A

A

A

A1

A

A

A

A A

A

A A

A

A A

A

A

A

A

A A A

A A

A

A1

D12

D12

D12

D12

D12

D12

D

D

D

D

D D

D

D

D

D

DD D

DDD

LP - 12LP - 12

LP - 12LP - 12

LP - 12

LP - 12 LP - 12 LP - 12 LP - 12 LP - 12

LP - 12LP - 12LP - 12LP - 12LP - 12

LP - 12 LP - 12LP - 12 LP - 12

LP - 12

LP - 12

LP - 12LP - 12LP - 12LP - 12

LP - 12LP - 12

LP - 12LP - 12

LP - 12

LP - 12 LP - 12 LP - 12 LP - 12 LP - 12

LP - 12LP - 12LP - 12LP - 12LP - 12

LP - 12LP - 12

LP - 12LP - 12

LP - 12

LP - 12LP - 12LP - 12LP - 12

LP - 12

LP - 9LP - 9

LP - 9LP - 9

LP - 9

LP - 9LP - 9LP - 9LP - 9LP - 9

LP - 9 LP - 9 LP - 9 LP - 9 LP - 9

LP - 9LP - 9

LP - 9LP - 9

LP - 9

LP - 9

LP - 9 LP - 9 LP - 9 LP - 9

LP - 9LP - 9

LP - 9

LP - 9 LP - 9 LP - 9

LP - 9 LP - 9 LP - 9

LP - 9LP - 9

LP - 9

LP - 9

LP - 9 LP - 9

LP - 17LP - 17

LP - 17LP - 17

LP - 17

LP - 17LP - 17LP - 17LP - 17LP - 17

LP - 17 LP - 17LP - 17 LP - 17 LP - 17

LP - 17LP - 17

LP - 17LP - 17

LP - 17

LP - 17

LP - 17 LP - 17 LP - 17 LP - 17

LP - 17

LP - 17

LP - 17

LP - 17

LP - 17LP - 17

LP - 17

LP - 17LP - 17 LP - 17

LP - 17LP - 17

LP - 17

LP - 17LP - 17LP - 17LP - 17

LP - 17 LP - 17LP - 17 LP - 17

LP - 17LP - 17LP - 17LP - 17

WS1 WS1 WS1 WS1 WS1 WS1 WS1 WS1

WS1

WS1

WS1

WS1

WS1WS1

LP - 3 LP - 3 LP - 3 LP - 3 LP - 5 LP - 5 LP - 5 LP - 5

LP - 5

LP - 5

LP - 5

LP - 5

LP - 5LP - 5

SC2 SC2 SC2 SC2

SC1 SC1

SC1

A1 A1

SC1

LP - 18

LP - 18 LP - 18

LP - 18LP - 18 LP - 18

LP - 18

LP - 18 LP - 18

LP - 18

LP - 18 LP - 18

LP - 18

LP - 18

LP - 18

LP - 18

LP - 18

LP - 18LP - 18

LP - 18

LP - 18

LP - 18LP - 18

LP - 18

LP - 18

LP - 18LP - 18

LP - 18

LP - 18

LP - 18LP - 18LP - 18

LP - 18 LP - 18

LP - 18LP - 18

LP - 18 LP - 18

LP - 18 EL1 - 34 EL1 - 34 EL1 - 34

EL1 - 34EL1 - 34EL1 - 34

EL1 - 34 EL1 - 34 EL1 - 34

EL1 - 34EL1 - 34EL1 - 34

EL1 - 34 EL1 - 34 EL1 - 34

EL1 - 34EL1 - 34EL1 - 34

EL1 - 34

EL1 - 34

EL1 - 34

EL1 - 32

EL1 - 32 EL1 - 32

EL1 - 32 EL1 - 32

EL1 - 32

EL1 - 32EL1 - 32

EL1 - 32 EL1 - 32

EL1 - 32EL1 - 32

EL1 - 32 EL1 - 32 EL1 - 36 EL1 - 36

EL1 - 36EL1 - 36

EL1 - 36 EL1 - 36

EL1 - 36EL1 - 36

EL1 - 36 EL1 - 36

EL1 - 36EL1 - 36

EL1 - 36 EL1 - 36

EL1 - 32EL1 - 32EL1 - 34EL1 - 34

EL1 - 34

LP - 6 LP - 6

LP - 6LP - 6

LP - 6 LP - 6

LP - 6LP - 6

LP - 6 LP - 6

LP - 6 LP - 6 LP - 6

LP - 6LP - 6LP - 6

LP - 8

LP - 8

LP - 8 LP - 8

LP - 8

LP - 8 LP - 8

LP - 8

LP - 8 LP - 8

LP - 8

LP - 8 LP - 8

LP - 8

LP - 8 LP - 8

LP - 8

LP - 8 LP - 8

LP - 8

LP - 8 LP - 8

LP - 8

LP - 8 LP - 19 LP - 19

LP - 19 LP - 19

LP - 19 LP - 19 LP - 19

LP - 19

LP - 19 LP - 19

LP - 19

LP - 19 LP - 19

LP - 19

LP - 19

LP - 19 LP - 19

LP - 19 LP - 19

LP - 19

LP - 7 LP - 7

LP - 7LP - 7

LP - 7LP - 7

LP - 7LP - 7

DL

DL

OS

DL DLDL DL DL DL DL DL DL DLDL

DL DL DL DL DL DL DL DL DL DLDL

OS

OS

OSOS OS OS

OS

OS OS OS OS OS

DL DL DL

DL DL

LP - 14LP - 14LP - 14LP - 14

OS

E4001

E4002

E4011

E4004

E4012

E4006

OS

E4021

E4015

PP

PP

LP - 19

A

CORRIDOR160

EM

EM

X

E4023

E4025

OS

OS

OS

OS

OS

OS

OS

OS

OS

A1 A1

PC

DL

OS

OSX

LP - 10X

LP - 10LP - 15

X

LP - 15

LP - 15

X

LP - 7

LP - 7

GL

GL

XWL

LP - 19

CL

CL CL CL CL

CL CL

LP - 20

LP - 20 LP - 20 LP - 20 LP - 20

LP - 20 LP - 20 LP - 20CL

X

?

LP - 15X

LP - 10

LP - 10

X

XLP - 19X

LP - 14

X

X

LP - 15

LP - 15

LP - 4

LP - 4

EL1 - 32X

LP - 4LP - 4 LP - 4

LP - 4LP - 4LP - 4

LP - 4LP - 4LP - 4

LP - 4 LP - 4 LP - 4

LP - 4 LP - 4

LP - 4

LP - 15

GL1

E84

OA OALP-20 LP-20

SHEET NUMBER:

DRAWING TITLE:

DATE ISSUED:

PROJECT NUMBER:

PROJECT SET:

I HEREBY CERTIFY THAT THESE DOCUMENTS WERE PREPARED OR APPROVED BY ME, AND THAT I AM A

DULY LICENSED PROFESSIONAL ENGINEER UNDER THE LAWS OF THE

STATE OF MARYLAND. LICENSE NUMBER: #xxxxx

EXPIRATION DATE: mm-dd-yyyy

CO

NSU

LTAN

T:SE

AL

ALL DRAWINGS ARE PROTECTED BY FEDERAL COPYRIGHT BY MANNS WOODWARD STUDIOS, INC. AND CAN NOT BE REPRODUCED OR MODIFIED IN ANY MANNER WITHOUT WRITTEN PERMISSION. DOCUMENTS MAY NOT BE USED IN PART OR WHOLE TO DEVELOP THE DESIGN OF ANOTHER BUILDING WITHOUT EXPRESS WRITTEN PERMISSION BY MANNS WOODWARD STUDIOS.

(P) 410-344-1460(F) 443-403-2460(E) [email protected]

S T U D I O S10839-D PHILADELPHIA RDWHITE MARSH, MD 21162

ARCHITECTURE + MASTER PLANNING

Eng

inee

ring

Infra

stru

ctur

e S

olut

ions

C.C

. Joh

nson

& M

alho

tra,

P.C

.

400

Eas

t Pra

tt S

treet

, Sui

te 6

04B

altim

ore,

MD

212

02(P

) 410

-461

-992

0 | (

F) (

667)

239-

3534

| (E

) BA

LTIM

OR

E@

CC

JM.C

OM

CC

JM

3/15

/201

9 6:

04:3

9 PM

E101

BALT

IMO

RE C

ITY

ANIM

AL S

ERVI

CES

BUIL

DING

2490

GIL

ES R

OAD

, BAL

TIM

ORE

, 212

25

ELECTRICAL - FIRSTFLOOR PLAN - LIGHTING

03-15-2019

17-023

100% CD

1/8" = 1'-0"1ELECTRICAL - FIRST FLOOR PLAN - LIGHTING

T P

REFERENCED NOTES - LIGHTING NEW WORKE21 CONNECT ALL EXIT LIGHTS ON THE BRANCH CIRCUIT INDICATED AND UPSTREAM OF

SWITCH.E24 SEE ELECTRICAL DRAWING E402 - FIRST FLOOR POWER PLAN FOR ADDITIONAL

LIGHTING IN THIS AREA.E84 PROVIDE SWITCH FOR FREEZER LIGHTING CONTROL, COORDINATE WITH FREEZER

MANUFACTURER FOR SPECIFICATION PRIOR TO INSTALLATION.

DS

A. PROVIDE ALL ADDITIONAL ACCESSORIES FOR A COMPLETE AND FULLY FUNCTIONING LIGHTING CONTROL SYSTEM INCLUDING BUT NOT LIMITED TO THE FOLLOWING:- POWER PACKS- 0 - 10V LOW VOLTAGE WIRING/RACEWAY

B. SEE LIGHTING CONTROL DIAGRAMS ON SHEETS E400-E402 FOR ADDITIONAL INFORMATION.

C. FOR PANEL SCHEDULES, REFER TO DRAWINGS E-601 & E-602. FOR LIGHTING FIXTURE SCHEDULE, REFER TO E-602.

GENERAL NOTES

NO. DESCRIPTION DATE

Page 4: ELECTRICAL LEGEND

REF

REF

REF

REF

REF

FEC

FEC

FEC

FEC

FEC

FEC

FEC

FEC

FEC

FECFEC FEC

REF

REF

GFI

GFI

WPGFI

J

FF

FF

FF

FF

M

M

M

M

M

M

M

M

M

M

M

M

M M

M

M

M M

M

M

M

M

WPGFI

WP

GFI

WP

GFI

WP

GFI

GFI

M

M

M

M

M

M

M

M

M

J

J

J

J

J

J

J

J

J

J

M

JJ

J

J

J

J

J

J

J

GFI

GFI

GFI

GFI

GFI

GFI

J

J

J

J

J J

J

J

DIR OF DEV117

ACCT115

HR MANAGER114

MARKETINGAND PRCOORD

113

DIR OF OPS112

EXEC ASST111

EXEC DIR110

VOLUNTEERMANAGER

109

OFFICEMANAGER

108

FRONT OFFICE106

MEETINGROOM

103

CORRIDOR107

WATER120

COPY/ WORKROOM

119 VET TECHGROUP

121

FILE ROOM123

VET GROUPOFFICE

122

GENERALSTORAGE

124

TOILET131

TOILET130

JAN129

SERVER/DATA/TEL

125

TOILET127

TOILET126

TOILET104

TOILET105

LOUNGE128

PUBLIC LOBBY101

OBEDIENCETRAINING

102

CAT COMM133

CAT COMM134

CAT COMM135

CAT COMM136

GETACQUAINTED/

ADOPTIONCLASSROOM

137

SURRENDER/FOSTER EXAM

138

FOSTER/SURRENDER

LOBBY139

SURRENDER/FOSTER EXAM

140

LAB/PHARMACY

177X-RAY RM

178

LAUNDRY &CLEANUP

179MEDICALSTORAGE

180

EUTHANASIA181

TOILET183

TOILET184

OPENWORKSTATIONS

185DIR AC

186

OFFICE189

OFFICE188

OFFICE187

AC BREAKROOM

190

AC GARAGE193

AC RADIOLOCKER/

EQUIPMENT191

AC SUPPLIES/EVIDENCE

192

TRAPSTORAGE

194

T&S 1195

T&S 2196

MEN'S LOCKERROOM

197

WOMEN'SLOCKER ROOM

198

T&S 3199

T&S 4201

ELECTRICAL202

DOGISOLATION &

SICK158

DOGQUARANTINE

157DOG

OBSERVATION156

DOG ROOM155

DOG ROOM154DOG ROOM

153

OPENWORKSTATIONS

118

CORRIDOR132

DOG & CATKITCHEN

147

GROOMING143

REPTILE/WILDLIFE

142

SMALLMAMMALS

141

CAT ROOM144

CAT ROOM145

CAT ROOM146

DOG & CATFOOD & LITTER

STORAGE148

COMMERCIALLAUNDRY

149CAT BITE

QUARANTINE150

CAT ISOLATION151

CATOBSERVATION

152

DOG HOLDING162

CAT HOLDING163

CATRECOVERY

164

DOGRECOVERY

(BEACH)165

DOGRECOVERY

166

SURGERYPREP168

OXYGENSTORAGE

167

SURGERY170

TNR CATHOLDING

169

SURGERYCORRIDOR

159

CLEANING/EQUIPMENTSTORAGE

171

VET OFFICE172

DOG EXAM173

CAT EXAM174

DOG INTAKE175

CORRIDOR160

CAT INTAKE176

SURGERYCORRIDOR

159

GFI

GFI

GFI

GFI GFI

GFI

WP WP

WP WPRP1 - 1

RP1 - 1RP1 - 1

RP1 - 1

RP1 - 3

RP1 - 5

PP1 - 25 PP1 - 27EL1 - 15

PP1 - 29

RP1 - 20 RP1 - 12

RP1 - 12

PP1 - 31

RP1 - 25

RP1 - 25

RP1 - 25

RP1 - 25

RP1 - 21

RP1 - 25

RP1 - 20

RP1 - 8

RP1 - 8

RP1 - 8

EL1 - 17 EL1 - 17 EL1 - 17

EL1 - 17

RP1 - 18

RP1 - 18

RP1 - 16

RP1 - 16

RP1 - 7

RP1 - 7

RP1 - 21RP1 - 23

RP1 - 23

RP1 - 23

EL1 - 8

RP1 - 16 RP1 - 18

EL1 - 8

EL1 - 5RP1 - 24

RP1 - 14

RP1 - 24

RP1 - 24

EL1 - 3

EL1 - 1

RP1 - 14

RP2 - 16RP2 - 16

DOG HOLDING161

RP2 - 17RP2 - 17RP2 - 17RP2 - 17RP2 - 17RP2 - 1 RP2 - 1

RP2 - 1RP2 - 1

RP2 - 25

RP2 - 29

RP2 - 29

RP2 - 27

RP2 - 27

EL1 - 13

PP2 - 11

PP2 - 8 PP2 - 10

RP2 - 10 RP2 - 12

RP2 - 8

RP2 - 10 RP2 - 8

RP2 - 12RP2 - 12

RP2 - 5

RP2 - 5

RP2 - 18

EL1 - 7

EL1 - 9

RP2 - 13 RP2 - 13 RP2 - 13 RP2 - 13

RP2 - 2

RP2 - 39

RP2 - 39

RP2 - 39

RP2 - 39

RP2 - 39

RP2 - 37

RP2 - 37

RP2 - 37

RP2 - 37

PP2 - 12

RP2 - 34

RP2 - 36

RP2 - 36

RP2 - 34

RP2 - 32

RP2 - 34

RP2 - 32

RP2 - 30

RP2 - 32

RP2 - 30

RP2 - 28

RP2 - 30

RP2 - 28

RP2 - 26

RP2 - 28

RP2 - 26

RP2 - 24

RP2 - 26

RP2 - 22

RP2 - 20

RP2 - 22 RP2 - 20 RP2 - 22

RP2 - 18

RP2 - 25

RP2 - 33

RP2 - 33

RP2 - 33

RP2 - 41

RP1 - 15RP1 - 15 RP1 - 15

RP1 - 15

RP2 - 15RP2 - 15RP2 - 15

E01 E01 E01E01 E01

E05

E07

E07

E06

RP2 - 31

RP2 - 31

RP2 - 31

PNL ML1

PNL LP

PNL RP2

ML1 - 6,8 SSU-1-04ML1 - 13,15

BCU-01

ML1 - 6,8

SSU-1-06

ML1 - 6,8

SSU-1-08

ML1 - 13,15

BCU-03

ML1 - 10,12

SSU-1-07

ML1 - 10,12

SSU-1-05

ML1 - 2,4

SSU-1-01

SSU-1-03

ML1 - 2,4

ML1 - 10,12

SSU-1-09

SSU-2-01

ML1 - 18,20ML1 - 22,24

SSU-2-02SSU-2-03

ML1 - 18,20

ML1 - 22,24

SSU-2-04

ML1 - 22,24SSU-2-06

ML1 - 17,19

BCU-04ML1 - 17,19

BCU-02

SSU-2-09ML1 - 30,32

ML1 - 26,28

SSU-2-10

ML1 - 18,20SSU-2-05

ML1 - 2,4

SSU-1-10

PNL MH1

VAV-3-1VAV-3-2

VAV-3-3 VAV-4-1

VAV-4-3

VAV-4-4

VAV-4-2

DOAS-3-01

ML1 - 39

ML1 - 39

ML1 - 39

ML1 - 39

ML1 - 39

ML1 - 39

ML1 - 39

RP2 - 9 RP2 - 9 RP2 - 9RP2 - 9 RP2 - 11 RP2 - 11 RP2 - 11 RP2 - 11 RP1 - 13 RP1 - 13 RP1 - 13 RP1 - 13

RP2 - 33RP2 - 35

RP2 - 41

RP2 - 41

RP2 - 41

EL1 - 11

RP2 - 19

RP2 - 21

DWH-1

RP2 - 27

RP2 - 27

+60" AFF

+60" AFFRP2 - 45

PP2 - 9

PP2 - 18

PP2 - 16 RP2 - 29

RP2 - 31

RP2 - 7

RP2 - 6

PP2 - 14PP2 - 26RP2 - 29

RP1 - 17

RP2 - 4RP1 - 17

RP1 - 17

E01E01E01

E01E01

E01

RP2 - 3EL1 - 14

EL1 - 14

EL1 - 14

EL1 - 14

EL1 - 14

EL1 - 14

STORAGE182

EL1 - 16

EL1 - 16

EL1 - 16

EL1 - 16

EL1 - 16

EL1 - 16

EWH-1 EWH-1

EWH-1

EL1 - 29EL1 - 27

EL1 - 30

EL1 - 30

EL1 - 30

EL1 - 30

EL1 - 30

EL1 - 30

EL1 - 10

EL1 - 10

EL1 - 10

EL1 - 14

RP1 - 9 RP1 - 9

RP1 - 9

RP1 - 19

RP1 - 9

EL1 - 23

EL1 - 25 EL1 - 19 EL1 - 21

PP1 - 33RP1 - 22

RP1 - 11PP1 - 19

RP1 - 21

MH1 - 10MH1 - 6

RP1 - 4RP1 - 7 RP1 - 7

RP1 - 7

EL1 - 24

RP1 - 9

RP1 - 19

RP1 - 19

RP1 - 19

RP1 - 5

RP1 - 5

RP1 - 5

RP1 - 5

EWH-1MH1 - 2

EWH-1

EWH-1

MH1 - 12

RP1 - 2 RP1 - 2RP1 - 2

RP1 - 23

SSU-2-08

SSU-2-07

ML1 - 30,32

RP1 - 6

ML1 - 26,28

RP1 - 6

GFI

WP

WPWP

WPWPWPWPWPWPWP

WPWP

WPWPWPWPWPWP

GFI

GFI

WPWPWP

GFI

GFI

GFI

GFI

GFIGFIGFIGFI

MH1 - 4

EL1 - 22

EL1 - 22

MH1 - 8

MH1 - 14

MH1 - 16

RP2 - 6RP2 - 47

EHUH-1

EHUH-1

USBRP1 - 15EL1 - 12

EL1 - 12

EL1 - 12 EL1 - 20

EL1 - 20

EL1 - 20

RP2 - 36

EL1 - 2

EL1 - 2

EL1 - 6

EL1 - 6

EL1 - 4

EL1 - 4

DSSU-1

USB

USB

EWC-1RP2 - 24

RP2 - 20

RP2 - 24

EQ-38

EQ-42EQ-42

EQ-42EQ-42

EQ-53

EQ-41

EQ-48

EQ-27

EQ-30

EQ-29

EQ-30

EQ-29

EQ-28

EQ-48

EQ-48

EQ-58

EQ-58

EQ-51

E27

E28

E29

EQ-11

EQ-11

RP2 - 15

RP1 - 12

EL1 - 31

EL1 - 43,45EL1 - 47

PP2 - 20

WP

PL

PL

PL

PL

PL

PL

PL

PL

PL

PL

PL

PL

PL

PL

PL

PL

PL

PL

PL

PL

PL

PL

PL PL

PL

PL

PL

PL

PL

PL

PL

PL

PL

E32

E32

E32

E33

E33

E33

E33

E33

E33

E33

E33

E33

E34

E33E33E33

PL

E35

PL

PL

EQ-31-EC

E35

E33

E34

PL

E34

PL

PL

PL

PL

PL

PL

PL

E33

E33

E33

E33

E33

E33

ML1 - 37

E31

ML1 - 33

CP-1

HSB-13

E07

E07

E01

WP

RP2 - 13

RP2 - 18

EQ-31-CU

PP2 - 7

EHUH-2

MH1 - 18

E32

EQ-21

EQ-26

EQ-26

ML1 - 29,31

E64

ML1 - 25,27

CP-2ML1 - 35

EQ-20

E6002

EL1-19,21,23E70

WP WP

WP

WP

WP

WPWP

WPWP

WP

WP WP

EQ-44

EQ-44

EQ-44

EQ-44

EQ-44

EQ-44

RP2-46,48,50,52

RP2-38,40,42,44

PP2 - 1

PP2 - 2

PP2 - 3

PP2 - 4

PP2 - 5

PP2 - 6

PP1 - 21

E73

EL1 - 26GFI

RP1 - 3

RP1 - 3

RP2 - 25

EQ-3

RP2 - 31

RP2 - 14

RP2 - 14

RP2 - 14

RP2 - 25RP1 - 25

RP1 - 10

RP1 - 10

RP1 - 10

PP1 - 24,26

PP1 - 20,22

PNL PP2

EQ-52

PP1 - 23

PP2 - 22,24

PP2 - 19,21,23

PP2 - 13,15,17

RP2 - 25

MH1-22,24,26E78DAC-1EL1 - 42 EL1 - 44E80

E80

PP1 - 1

PP1 - 7

PP1 - 13

PP1 - 2

PP1 - 8

PP1 - 14

PP1 - 3,5

PP1 - 9,11

PP1 - 15,17

PP1 - 4,6

PP1 - 10,12

PP1 - 16,18

E81

EQ-38

RP2 - 29

USB

RP1 - 11

WP

GFI

RP2 - 29RP1 - 21

RP1 - 21

RP2 - 43

RP2 - 41

RP2 - 25

+60" AFF

DOAS-06

RP1 - 27

RP2 - 49

EL1 - 55,57

EL1 - 56,58

E64

E85

E85

E1022

EL1 - 38 EL1 - 38

EL1 - 59

E87

EL1 - 60

EL1 - 60

CRP2 - 69

E88

C

C

C

REPTILE/WILDLIFE

142

SMALLMAMMALS

141

RP2 - 19

RP2 - 19

+18"+18"+36"+36"+54"+54"

+18"

+18"

+36"

+36"

+54"

+54"

+18"

+18"

+36"

+36"

+54"

+54"

+18"+18"

+36"+36"+54"+54"

+18"+18"+36"+36"

+54" +54"

+18" +18"

+36"+36"+54"+54"

RP2 - 53

RP2 - 23RP2 - 21

RP2 - 56

RP2 - 55RP2 - 54

RP2 - 57

RP2 - 58

RP2 - 59

RP2 - 60

RP2 - 68

RP2 - 61

RP2 - 62RP2 - 63

RP2 - 64

RP2 - 65

RP2 - 66

RP2 - 67

E86

E86

SHEET NUMBER:

DRAWING TITLE:

DATE ISSUED:

PROJECT NUMBER:

PROJECT SET:

I HEREBY CERTIFY THAT THESE DOCUMENTS WERE PREPARED OR APPROVED BY ME, AND THAT I AM A

DULY LICENSED PROFESSIONAL ENGINEER UNDER THE LAWS OF THE

STATE OF MARYLAND. LICENSE NUMBER: #xxxxx

EXPIRATION DATE: mm-dd-yyyy

CO

NSU

LTAN

T:SE

AL

ALL DRAWINGS ARE PROTECTED BY FEDERAL COPYRIGHT BY MANNS WOODWARD STUDIOS, INC. AND CAN NOT BE REPRODUCED OR MODIFIED IN ANY MANNER WITHOUT WRITTEN PERMISSION. DOCUMENTS MAY NOT BE USED IN PART OR WHOLE TO DEVELOP THE DESIGN OF ANOTHER BUILDING WITHOUT EXPRESS WRITTEN PERMISSION BY MANNS WOODWARD STUDIOS.

(P) 410-344-1460(F) 443-403-2460(E) [email protected]

S T U D I O S10839-D PHILADELPHIA RDWHITE MARSH, MD 21162

ARCHITECTURE + MASTER PLANNING

Eng

inee

ring

Infra

stru

ctur

e S

olut

ions

C.C

. Joh

nson

& M

alho

tra,

P.C

.

400

Eas

t Pra

tt S

treet

, Sui

te 6

04B

altim

ore,

MD

212

02(P

) 410

-461

-992

0 | (

F) (

667)

239-

3534

| (E

) BA

LTIM

OR

E@

CC

JM.C

OM

CC

JM

3/15

/201

9 5:

02:4

0 PM

E102

BALT

IMO

RE C

ITY

ANIM

AL S

ERVI

CES

BUIL

DING

2490

GIL

ES R

OAD

, BAL

TIM

ORE

, 212

25

ELECTRICAL - FIRSTFLOOR PLAN - POWER

03-15-2019

17-023

100% CD

1/8" = 1'-0"1ELECTRICAL - FIRST FLOOR PLAN - POWER

T P

REFERENCED NOTES - POWERE64 PROVIDE 1" RACEWAY TO OUTDOOR UNIT FOR POWER CONTROL WIRING.E70 PROVIDE 60 AMP, 208V, 3POLE, NEMA 4 FSS @ 45A.E73 PROVIDE DEDICATED 1P-120V RECEPTACLE JOHNSON CONTROL DEVICE.E78 PROVIDE 480V, 3Ø, 30A DISCONNECT SWITCH FUSED AT 20A FOR DAC-1.E80 PROVIDE 120V, 1Ø, JUNCTION BOX FOR SIGNAGE, COORDINATE WITH ARCHITECTURAL

DRAWINGS PRIOR TO INSTALLATION.E81 PROVIDE (6) 120V, NEMA 5-20R AND (6) 208V, NEMA 6-15R RECEPTACLE(S) IN CLEANING

EQUIPMENT STORAGE. ALL RECEPTACLES IN THIS AREA SHALL BE GFCI UNLESS OTHERWISE NOTED. COORDINATE WITH CLEANING EQUIPMENT MANUFACTURER PRIOR TOINSTALLATION FOR INSTALLATION REQUIREMENTS.

E85 PROVIDE 2P, 208V RECEPTACLE, COORDINATE EXACT TYPE AND LOCATION WITHOWNER'S IT SUPPLIER.

E86 RECEPTACLES INSTALLED IN THIS AREA SHALL BE COORDINATED WITH OWNER'S REPPRIOR TO INSTALLATION FOR EXACT MOUNTING LOCATIONS.

E87 PROVIDE 120V JUNCTION BOX FOR HEAT TRACE.E88 PROVIDE CEILING MOUNTED RECEPTACLE IN THIS LOCATION FOR PROJECTOR FOR

FUTURE. (PROJECTOR NOT IN CONTRACT).

REFERENCED NOTES - POWERE32 PROVIDE PLUG LOAD CONTROLLER AND ALL ASSOCIATED WIRING/RACEWAY TO

CONTROL ONE CIRCUIT POWERING FURNITURE SYSTEM RECEPTACLES. PROVIDE ALLCONTROL WIRING TO OCCUPANCY SENSOR SERVING THIS ROOM/AREA CONTROLLEDRECEPTACLES. LOCATE THE CONTROLLER AT A FULLY ACCESSIBLE LOCATION ABOVECEILING.

E33 PROVIDE PLUG LOAD CONTROLLER AND ALL ASSOCIATED WIRING/RACEWAY TOCONTROL ONE RECEPTACLE PER EVERY 50 SQ. FT OF THE OFFICE. PROVIDE ALLCONTROL WIRING TO OCCUPANCY SENSOR SERVING THIS ROOM/AREA CONTROLLEDRECEPTACLES. LOCATE THE CONTROLLER AT A FULLY ACCESSIBLE LOCATION ABOVECEILING.

E34 PROVIDE PLUG LOAD CONTROLLER AND ALL ASSOCIATED WIRING/RACEWAY TOCONTROL ONE RECEPTACLE PER DATA OUTLET IN THE COPY ROOM. PROVIDE ALLCONTROL WIRING TO OCCUPANCY SENSOR SERVING THIS ROOM/AREA CONTROLLEDRECEPTACLES. LOCATE THE CONTROLLER AT A FULLY ACCESSIBLE LOCATION ABOVECEILING.

E35 PROVIDE PLUG LOAD CONTROLLER AND ALL ASSOCIATED WIRING/RACEWAY TOCONTROL ONE COUNTERTOP RECEPTACLE IN THE BREAK ROOM/LOUNGE. PROVIDE ALLCONTROL WIRING TO OCCUPANCY SENSOR SERVING THIS ROOM/AREA CONTROLLEDRECEPTACLES. LOCATE THE CONTROLLER AT A FULLY ACCESSIBLE LOCATION ABOVECEILING.

REFERENCED NOTES - POWERE01 INSTALL ELECTRICAL RECEPTACLES AT 36 INCHES ABOVE FINISHED IN THIS AREA

UNLESS NOTED OTHERWISE.E05 JUNCTION BOX FOR WALK-IN COOLER FREEZER, COORDINATE SPECIFICATIONS WITH

MANUFACTURER PRIOR TO INSTALLATION.E06 PROVIDE 480V, 3Ø, 60A DISCONNECT SWITCH FUSED AT 50A FOR ANALOG SYSTEM FOR

XRAY. PROVIDE 3#4 AWG + 1#8 G IN 1" RACEWAY TO SWITCHBOARD.E07 PROVIDE JUNCTION BOX WITH (4) #12 LINE, (2) #10 NEUTRAL AND (2) #12 GROUND FOR 8

WIRE SYSTEM FURNITURE IN THIS LOCATION. COORDINATE WITH MANUFACTURERPRIOR TO INSTALLATION.

E27 PROVIDE RECEPTACLE FOR SCAVENGING VACUUM PUMP, COORDINATE EXACT HEIGHTAND MOUNTING LOCATION WITH VACUUM PUMP SUPPLIER.

E28 PROVIDE 3-GANG JUNCTION BOX FLUSH WITH FINISHED WALL. COORDINATE EXACTLOCATION AND CONTROL WIRING WITH SCAVENGING ALARM PANEL SUPPLIER.

E29 PROVIDE 120V JUNCTION BOX FOR LIGHTING CIRCUIT IN WALKING FREEZER,COORDINATE SPECIFICATIONS WITH MANUFACTURER PRIOR TO INSTALLATION.

E31 PROVIDE JUNCTION BOX ABOVE CEILING WITH BRANCH CIRCUIT WIRING/RACEWAY ASINDICATED FOR LOW VOLTAGE FLUSH VALVES CONTROLS. PROVIDE ALL LOW VOLTAGEWIRING IN THE WALL TO THE PLUMBING DEVICES.

1/4" = 1'-0"2 PARTIAL FLOOR PLAN - REPTILE/WILDLIFE AND SMALL MAMMALS ROOMS

NO. DESCRIPTION DATE

Page 5: ELECTRICAL LEGEND

REF

REF

REF

REF

REF

FEC

FEC

FEC

FEC

FEC

FEC

FEC

FEC

FEC

FECFEC FEC

REF

REF

TVTV

J

J

J

J

TV

J

J

TV TV

CR CRCRCRCRCRCRCR

CR

CR

CR

CR

CR

CR

CR

CR

CR

CR

CR

CRCR

CR CRCR

CR

C C

C

C

C

C

C

C

C

C

C

C

C

C

C

C

C

C

C

C

C

CR

SASA

E22

E22

E22

+60" AFF

DOG ROOM153

DOG ROOM154

DOG ROOM155 DOG

OBSERVATION156

DOGQUARANTINE

157

DOGISOLATION &

SICK158

ELECTRICAL202

T&S 3199

T&S 4201

WOMEN'SLOCKER ROOM

198

MEN'S LOCKERROOM

197

T&S 1195

T&S 2196

TRAPSTORAGE

194CORRIDOR160

AC SUPPLIES/EVIDENCE

192

AC GARAGE193

DOG INTAKE175

AC RADIOLOCKER/

EQUIPMENT191

OFFICE189

OFFICE188

OFFICE187

AC BREAKROOM

190

CAT INTAKE176

CAT EXAM174

DOG EXAM173

VET OFFICE172

CLEANING/EQUIPMENTSTORAGE

171

SURGERYCORRIDOR

159

TNR CATHOLDING

169

SURGERY170

SURGERYPREP168

DOGRECOVERY

(BEACH)165

CATRECOVERY

164

CAT HOLDING163

DOG HOLDING161

DOG HOLDING162

CATOBSERVATION

152CAT ISOLATION

151

CAT BITEQUARANTINE

150

COMMERCIALLAUNDRY

149

DOG & CATFOOD & LITTER

STORAGE148

DOG & CATKITCHEN

147

GROOMING143

REPTILE/WILDLIFE

142

SMALLMAMMALS

141

CAT ROOM144

CAT ROOM145

CAT ROOM146

CORRIDOR132

CORRIDOR132

CORRIDOR107

GENERALSTORAGE

124

SERVER/DATA/TEL

125

TOILET131

TOILET130

JAN129

VET GROUPOFFICE

122

FILE ROOM123

VET TECHGROUP

121

COPY/ WORKROOM

119

WATER120

MEETINGROOM

103

TOILET126

TOILET127

TOILET104

TOILET105

LOUNGE128

PUBLIC LOBBY101

OBEDIENCETRAINING

102

CAT COMM133

CAT COMM134

CAT COMM135

CAT COMM136

GETACQUAINTED/

ADOPTIONCLASSROOM

137

SURRENDER/FOSTER EXAM

138

FOSTER/SURRENDER

LOBBY139

SURRENDER/FOSTER EXAM

140

LAB/PHARMACY

177

X-RAY RM178

LAUNDRY &CLEANUP

179MEDICALSTORAGE

180

STORAGE182

EUTHANASIA181

TOILET183

TOILET184

CORRIDOR160

OPENWORKSTATIONS

185DIR AC

186

FRONT OFFICE106

OFFICEMANAGER

108

VOLUNTEERMANAGER

109

EXEC DIR110

EXEC ASST111

DIR OF OPS112

MARKETINGAND PRCOORD

113

HR MANAGER114

ACCT115

DIR OF DEV117

OPENWORKSTATIONS

118

CORRIDOR107

P P P P P P P

P

PPP

P

P

P

3015 15

15 15

15 15

75

1515

15

15

3030

15 15

151530

15

15

15 15

15

15

15

7515

15

15

151515

3030303030

151515

1515

151515

1515

15

15151515

15

30

15

15

30

15

15

15

15

15

15

15

15

30

30

30

FSA

FCP

E22

C

CRCRCR

C

C

C C C

C

C

CC

C

C

C

C

C

C

C

C

C

CRCRCRCRCRCR

FS

FS

TSTS

TSFSTS

CO CO CO CO CO CO

CR

30

15

15

30

15

15

15

15

15

P

PA PA PA PA

PA

PA

PA PA PA PA PA PA

PA

PA

PA

PA

DOAS-04

DOAS-03

DOAS-01

DOAS-02

15151515151515151515

15

15

15

15

15

15

15

15

15

15

E7115

15

15

15

15

15

E72

E74

1515

1515

E77

DR DR

DR

DR

E79

E79

E79

C

E36

15

1515

110WP

F F F

FF F

F F F

FFF

FFF

FFF

F F F

W

CF

E89

E89

E90

C C C

C

C

C

C

C

E92 E92 E92 E92 E92 E92

SHEET NUMBER:

DRAWING TITLE:

DATE ISSUED:

PROJECT NUMBER:

PROJECT SET:

I HEREBY CERTIFY THAT THESE DOCUMENTS WERE PREPARED OR APPROVED BY ME, AND THAT I AM A

DULY LICENSED PROFESSIONAL ENGINEER UNDER THE LAWS OF THE

STATE OF MARYLAND. LICENSE NUMBER: #xxxxx

EXPIRATION DATE: mm-dd-yyyy

CO

NSU

LTAN

T:SE

AL

ALL DRAWINGS ARE PROTECTED BY FEDERAL COPYRIGHT BY MANNS WOODWARD STUDIOS, INC. AND CAN NOT BE REPRODUCED OR MODIFIED IN ANY MANNER WITHOUT WRITTEN PERMISSION. DOCUMENTS MAY NOT BE USED IN PART OR WHOLE TO DEVELOP THE DESIGN OF ANOTHER BUILDING WITHOUT EXPRESS WRITTEN PERMISSION BY MANNS WOODWARD STUDIOS.

(P) 410-344-1460(F) 443-403-2460(E) [email protected]

S T U D I O S10839-D PHILADELPHIA RDWHITE MARSH, MD 21162

ARCHITECTURE + MASTER PLANNING

Eng

inee

ring

Infra

stru

ctur

e S

olut

ions

C.C

. Joh

nson

& M

alho

tra,

P.C

.

400

Eas

t Pra

tt S

treet

, Sui

te 6

04B

altim

ore,

MD

212

02(P

) 410

-461

-992

0 | (

F) (

667)

239-

3534

| (E

) BA

LTIM

OR

E@

CC

JM.C

OM

CC

JM

3/15

/201

9 5:

04:5

6 PM

E103

BALT

IMO

RE C

ITY

ANIM

AL S

ERVI

CES

BUIL

DING

2490

GIL

ES R

OAD

, BAL

TIM

ORE

, 212

25

ELECTRICAL - FIRSTFLOOR PLAN - SYSTEMS

03-15-2019

17-023

100% CD

1/8" = 1'-0"1 ELECTRICAL - FIRST FLOOR PLAN - SYSTEMS

T P

REFERENCED NOTES - SYSTEMSE22 PROVIDE VOICE/DATA JUNCTION BOX FOR SYSTEM FURNITURE AT THIS LOCATION.

COORDINATE WITH OWNER AND SYSTEMS FURNITURE MANUFACTURER FOR SYSTEMFURNITURE POWER AND DATA REQUIREMENTS.

E36 PROVIDE DATA OUTLETS FOR HVAC CONTROL PANEL, COORDINATE WITH MECHANICALDRAWINGS FOR EXACT MOUNTING LOCATION.

E71 PROVIDE JUNCTION BOX FOR DOOR RELEASE BUTTON, COORDINATE EXACT MOUNTINGLOCATION WITH SECURITY CONTRACTOR.

E72 PROVIDE (2) 4" EMPTY CONDUITS WITH PULL STRING FOR TELECOM AND CABLE TVWIRING TO BE STUBBED UP IN THIS LOCATION.

E74 PROVIDE JUNCTION BOX IN THIS LOCATION FOR DOOR BUZZER.E77 PROVIDE 4' X 8', 3/4" PLYWOOD BOARD FOR TELEPHONE TERMINAL.E79 PROVIDE PUSH BUTTON FOR OVERHEAD DOORS AT THE LOCATION INDICATED.

COORDINATE PHOTOELECTRIC SENSOR AND TWO WIRE SAFETY EDGE WITH OVERHEADDOOR MANUFACTURER.

E89 UNDERGROUND CONDUIT FOR DATA CONNECTION. PROVIDE 1-1/4” EMPTY CONDUITWITH PULL STRING TO WALL AS INDICATED. TERMINATE CONDUIT 6” ABOVE ACCESSIBLECEILING. COORDINATE CONDUIT PATH WITH POWER CONDUIT IN SAME ROOM.

E90 UNDERGROUND CONDUIT FOR CARD READER DATA CONNECTION. PROVIDE 1-1/4”EMPTY CONDUIT WITH PULL STRING TO WALL AS INDICATED. TERMINATE CONDUIT 6” ATINSIDE OF THE BUILDING ABOVE ACCESSIBLE CEILING. COORDINATE EXACTTERMINATION LOCATION WITH OWNER SECURITY CONSULTANT.

E92 ALL RECEPTACLES IN THIS LOCATION TO BE WEATHERPROOF RATED.

NO. DESCRIPTION DATE1 Permit Comments 3.12.19

Page 6: ELECTRICAL LEGEND

G,WP

G,WP

G,WP

G,WP

G,WP

G,WPG,WP

G,WP

HPU-03

HPU-01

DOAS-03

DOAS-04

DOAS-02

HPU-02

HPU-04

ACU-1

MH1-26,28,30HSB-6

HSB-10

HSB-8

HSB-3

MH1-14,16,18

MH1-13,15,17

MH1-25,27,29

MH1-19,21,23 MH1-20,22,24EF-1 EF-2

EF-6

EF-5

EF-3

EF-4

ML1-11

ML1-10

ML1-4

ML1-3

ML1-1

EL1-31,33

EL1-30

DOAS-01

ML1-23

EF-7

WP

WPWP

WP

E56

E56

E56

E56

E62

E62

E62

E62

E66

E66

E66

E68

E68

E68

E68E67 E67

E69

E62E62

E62

RP1 - 29

RP1 - 29

E66

E66RP1 - 29

RP1 - 29

E66E66

RP2 - 51RP2 - 51

RP2 - 51

RP2 - 51E66

SHEET NUMBER:

DRAWING TITLE:

DATE ISSUED:

PROJECT NUMBER:

PROJECT SET:

I HEREBY CERTIFY THAT THESE DOCUMENTS WERE PREPARED OR APPROVED BY ME, AND THAT I AM A

DULY LICENSED PROFESSIONAL ENGINEER UNDER THE LAWS OF THE

STATE OF MARYLAND. LICENSE NUMBER: #xxxxx

EXPIRATION DATE: mm-dd-yyyy

CO

NSU

LTAN

T:SE

AL

ALL DRAWINGS ARE PROTECTED BY FEDERAL COPYRIGHT BY MANNS WOODWARD STUDIOS, INC. AND CAN NOT BE REPRODUCED OR MODIFIED IN ANY MANNER WITHOUT WRITTEN PERMISSION. DOCUMENTS MAY NOT BE USED IN PART OR WHOLE TO DEVELOP THE DESIGN OF ANOTHER BUILDING WITHOUT EXPRESS WRITTEN PERMISSION BY MANNS WOODWARD STUDIOS.

(P) 410-344-1460(F) 443-403-2460(E) [email protected]

S T U D I O S10839-D PHILADELPHIA RDWHITE MARSH, MD 21162

ARCHITECTURE + MASTER PLANNING

Eng

inee

ring

Infra

stru

ctur

e S

olut

ions

C.C

. Joh

nson

& M

alho

tra,

P.C

.

400

Eas

t Pra

tt S

treet

, Sui

te 6

04B

altim

ore,

MD

212

02(P

) 410

-461

-992

0 | (

F) (

667)

239-

3534

| (E

) BA

LTIM

OR

E@

CC

JM.C

OM

CC

JM

3/15

/201

9 5:

05:1

4 PM

E104

BALT

IMO

RE C

ITY

ANIM

AL S

ERVI

CES

BUIL

DING

2490

GIL

ES R

OAD

, BAL

TIM

ORE

, 212

25

ELECTRICAL - ROOFPLAN

03-15-2019

17-023

100% CD

1/8" = 1'-0"1ELECTRICAL - ROOF PLAN

T P

REFERENCED NOTES - LIGHTING NEW WORKE56 DOAS UNIT FURNISHED WITH WEATHER PROOF RECEPTACLE AND DISCONNECT

SWITCH, COORDINATE WITH DOAS UNIT MANUFACTURER FOR SPECIFICATION.E62 DISCONNECT AND SPEED CONTROL BY MANUFACTURER UNLESS OTHERWISE NOTED.E66 PROVIDE GFCI, WP RECEPTACLE WITH BRANCH CIRCUIT AS INDICATED. PROVIDE

INDEPENDENT SUPPORTS.E67 PROVIDE 60 AMP, 480V, 3POLE, NEMA 4 NFSS.E68 PROVIDE 30 AMP, 480V, 3POLE, NEMA 4 NFSS.E69 PROVIDE 30 AMP, 208V, 2POLE, NEMA 4 NFSS.

NO. DESCRIPTION DATE

Page 7: ELECTRICAL LEGEND

LV

LV

LVLV

LVLV

LD

LVLV

LVLV

LV

LV

LV

LVLV

a

a

a

a

d d d d d

b

b

b

b

c

c

c

c

e

e

e

e

e

e

e

e

a,b,c,d,e

DL DL

DLDL

PP

E21

DOG ROOM154

E57

E57

E57

N N N N

N N N N

NN N N

NNNN

NN N N

N

N

N

N

N

N

N

N

N

E51

E51 E51

E51

E52

E53

E55

D1 D D1 D D1

D D D D D

D D D D D

DDDDD

D D D1 D D PP

PP

EXEC DIR110

VOLUNTEERMANAGER

109

N

N

N

N

E52

E52

E53

E55

A A

AA

E55

N

N

N

N

E58

E58

DL

PP

NN

N

N

NN

N

N

NE52

E51

N

E53E55

DC DC

DCDC

DC DC

DCDC

E50

a a

b b

a a

b b

d d d

a a a

a a a

b b b

b b b

c c c c

OS

OS

OS

OS

E21

PP

E21

E57

OPENWORKSTATIONS

118

N

N

N N

N

N

N N

N

N

N N N N

NNN

N

N

N

N

N

N

N

E52E53

E54

E54

E55

A1 A A

AAA

A A A

AAA

A1 A A

SC2 SC2 SC2 SC2

E57

E54

E54

DOG ROOM

MODE 1

MODE 2

ON

GENERAL NOTES FOR STATIONS CONFIGURATION:

A. PROVIDE CUSTOM ENGRAVING AS DIRECTED BY OWNER ON EACH BUTTON OF EACHDEVICE TO MATCH THE FUNCTIONS OF THE SPACE. DEVICE LABELS SHOWN ARE GENERICIN NATURE AND DO NOT REPRESENT THE EXACT FINAL EXPECTED ENGRAVING.

B. MODE 1: ZONE(S) a,b,c,d,e at 100%C. MODE 2: ZONE(S) - a,b,c,d at 100% / ZONE e - OFF

F. DAYLIGHT SENSOR: UNLESS OTHERWISE INDICATED, TURN LIGHTS TURNS OFF ZONE e WHEN NATURAL LIGHT FROM SKY LIGHT HAS REQUIRED FC, AND DIM REMAINING ZONES AT50%.

OFF

MODE 3

MODE 4

DIM UP

DIM DN

D. MODE 3: ZONE(S) - a,b,c,d,e at 50% E. MODE 4: ZONE(S) - a,b,c,e OFF / ZONE d AT 50%

OPEN WORKSTATION

MODE 1

MODE 2

ON

GENERAL NOTES FOR STATIONS CONFIGURATION:

A. PROVIDE CUSTOM ENGRAVING AS DIRECTED BY OWNER ON EACH BUTTON OF EACHDEVICE TO MATCH THE FUNCTIONS OF THE SPACE. DEVICE LABELS SHOWN ARE GENERICIN NATURE AND DO NOT REPRESENT THE EXACT FINAL EXPECTED ENGRAVING.

B. MODE 1: ZONE(S) a,b,c at 100%C. MODE 2: ZONE(S) - a,c at 100% / ZONE b - OFF

OFF

MODE 3

MODE 4

DIM UP

DIM DN

D. MODE 3: ZONE(S) - b,c, at 100% / ZONE a - OFFE. MODE 4: ZONE(S) - c at 100% / ZONE a,b - OFF

F. DAYLIGHT SENSOR: UNLESS OTHERWISE INDICATED, TURN LIGHTS TURNS OFF ZONE d WHEN NATURAL LIGHT FROM SKY LIGHT HAS REQUIRED FC, AND DIM REMAINING ZONES AT50%.

CAT ROOM

ON/OFF

GENERAL NOTES FOR STATIONS CONFIGURATION:

A. PROVIDE CUSTOM ENGRAVING AS DIRECTED BY OWNER ON EACH BUTTON OF EACHDEVICE TO MATCH THE FUNCTIONS OF THE SPACE. DEVICE LABELS SHOWN ARE GENERICIN NATURE AND DO NOT REPRESENT THE EXACT FINAL EXPECTED ENGRAVING.

B. DAYLIGHT SENSOR: UNLESS OTHERWISE INDICATED, TURN LIGHTS TURNS OFF ZONE b

DIM UP/DNON/OFF

GENERAL NOTES FOR STATIONS CONFIGURATION:

A. PROVIDE CUSTOM ENGRAVING AS DIRECTED BY OWNER ON EACH BUTTON OF EACHDEVICE TO MATCH THE FUNCTIONS OF THE SPACE. DEVICE LABELS SHOWN ARE GENERICIN NATURE AND DO NOT REPRESENT THE EXACT FINAL EXPECTED ENGRAVING.

OFFICE

ON/OFF

SHEET NUMBER:

DRAWING TITLE:

DATE ISSUED:

PROJECT NUMBER:

PROJECT SET:

I HEREBY CERTIFY THAT THESE DOCUMENTS WERE PREPARED OR APPROVED BY ME, AND THAT I AM A

DULY LICENSED PROFESSIONAL ENGINEER UNDER THE LAWS OF THE

STATE OF MARYLAND. LICENSE NUMBER: #xxxxx

EXPIRATION DATE: mm-dd-yyyy

CO

NSU

LTAN

T:SE

AL

ALL DRAWINGS ARE PROTECTED BY FEDERAL COPYRIGHT BY MANNS WOODWARD STUDIOS, INC. AND CAN NOT BE REPRODUCED OR MODIFIED IN ANY MANNER WITHOUT WRITTEN PERMISSION. DOCUMENTS MAY NOT BE USED IN PART OR WHOLE TO DEVELOP THE DESIGN OF ANOTHER BUILDING WITHOUT EXPRESS WRITTEN PERMISSION BY MANNS WOODWARD STUDIOS.

(P) 410-344-1460(F) 443-403-2460(E) [email protected]

S T U D I O S10839-D PHILADELPHIA RDWHITE MARSH, MD 21162

ARCHITECTURE + MASTER PLANNING

Eng

inee

ring

Infra

stru

ctur

e S

olut

ions

C.C

. Joh

nson

& M

alho

tra,

P.C

.

400

Eas

t Pra

tt S

treet

, Sui

te 6

04B

altim

ore,

MD

212

02(P

) 410

-461

-992

0 | (

F) (

667)

239-

3534

| (E

) BA

LTIM

OR

E@

CC

JM.C

OM

CC

JM

3/15

/201

9 5:

05:2

2 PM

E400

BALT

IMO

RE C

ITY

ANIM

AL S

ERVI

CES

BUIL

DING

2490

GIL

ES R

OAD

, BAL

TIM

ORE

, 212

25

ELECTRICAL - ENLARGEDSCALE PLANS - LIGHTINGCONTROLS I

03-15-2019

17-023

100% CD

1/4" = 1'-0"1 ELECTRICAL - TYPICAL DOG ROOM - LIGHTING CONTROL1/4" = 1'-0"2 ELECTRICAL - TYPICAL OFFICE - LIGHTING CONTROL

1/4" = 1'-0"4ELECTRICAL - TYPICAL CAT ROOM - LIGHTING CONTROL

1/4" = 1'-0"6 ELECTRICAL - OPEN WORKSTATION - LIGHTING CONTROL

1/4" = 1'-0"7 SEQUENCE OF OPERATION - TYPICAL DOG ROOM

REFERENCED NOTES - LIGHTING NEW WORKE21 CONNECT ALL EXIT LIGHTS ON THE BRANCH CIRCUIT INDICATED AND UPSTREAM OF

SWITCH.E50 PROVIDE ON/OFF + DIMMING LOW VOLTAGE SWITCH LIGHTING CONTROL BY ACUITY

CONTROLS OR APPROVED EQUAL. SEE SEQUENCE OF OPERATION BELOW FORLIGHTING SCENE SCHEMATIC.

E51 PROVIDE DAYLIGHT HARVESTING PHOTOCELL LIGHTING CONTROL IN THIS AREA. SEESEQUENCE OF OPERATION BELOW FOR LIGHTING SCENE SCHEMATIC.

E52 PROVIDE DIMMING/RELAY POWER PACK BY ACUITY CONTROLS OR APPROVED EQUAL,LOCATED IN ACCESSIBLE CEILING SPACE OF ROOM NEAR ENTRY DOOR. SEE SEQUENCEOF OPERATION BELOW FOR LIGHTING SCENE SCHEMATIC.

E53 277V LIGHTING CIRCUIT FROM DIMMING/RELAY POWER PACK BY ACUITY CONTROLS ORAPPROVED EQUAL. REFER FOR ELECTRICAL DRAWING E101 FOR DESIGNATED LIGHTCIRCUITS.

E54 PROVIDE CEILING MOUNTED OCCUPANCY SENSOR SWITCH BY ACUITY CONTROLS ORAPPROVED EQUAL, IN THIS AREA. SEE SEQUENCE OF OPERATION BELOW FOR LIGHTINGSCENE SCHEMATIC.

E55 PROVIDE AND CONNECT CAT-5 NETWORK CABLE TO BRIDGE DEVICE BY ACUITYCONTROLS OR APPROVED EQUAL.

E57 PROVIDE NLIGHT ENABLED TOGGLE AND/OR RAISE/LOWER VOLTAGE SWITCH WITHUSER DEFINED LOCAL CONTROL OF A LIGHTING ZONE.

E58 PROVIDE WALL MOUNTED OCCUPANCY SENSOR SWITCH BY ACUITY CONTROLS ORAPPROVED EQUAL, IN THIS AREA. SEE SEQUENCE OF OPERATION BELOW FOR LIGHTINGSCENE SCHEMATIC.

1/4" = 1'-0"8 SEQUENCE OF OPERATION- OPEN WORKSTATION

1/4" = 1'-0"9SEQUENCE OF OPERATION - TYPICAL CAT ROOM

1/4" = 1'-0"10 SEQUENCE OF OPERATION - TYPICAL OFFICE

NO. DESCRIPTION DATE

Page 8: ELECTRICAL LEGEND

LD

LD

LDLV

OS

OS

LVLVDL

DL

PP

PP

E51 E51E21 E21

N

N

NN

N N N

N

N

N

N

N

N

N

N

N

N

N

N

N

E52

E52

PS

PS

PS PS PS

PS1

PSPSPS1

PS

PS

PS

PSPS1

PS

OBEDIENCETRAINING

102

PUBLIC LOBBY101

E53

E55E55

E21

A1 A

E50

E50

E50

E21

b b b

aa a

a

a a

a aa

b b

b

PP

PP

N

N

N

N

N

E52

E52

TOILET183

TOILET184

E58

E55

N

E55

A1

A1

E58

E53

N

GENERAL NOTES FOR STATIONS CONFIGURATION:

A. PROVIDE CUSTOM ENGRAVING AS DIRECTED BY OWNER ON EACH BUTTON OF EACHDEVICE TO MATCH THE FUNCTIONS OF THE SPACE. DEVICE LABELS SHOWN ARE GENERICIN NATURE AND DO NOT REPRESENT THE EXACT FINAL EXPECTED ENGRAVING.

RESTROOM

ON/OFF

CAT ROOM

ON/OFF

GENERAL NOTES FOR STATIONS CONFIGURATION:

A. PROVIDE CUSTOM ENGRAVING AS DIRECTED BY OWNER ON EACH BUTTON OF EACHDEVICE TO MATCH THE FUNCTIONS OF THE SPACE. DEVICE LABELS SHOWN ARE GENERICIN NATURE AND DO NOT REPRESENT THE EXACT FINAL EXPECTED ENGRAVING.

B. DAYLIGHT SENSOR: UNLESS OTHERWISE INDICATED, TURN LIGHTS TURNS OFF ZONE b

DIM UP/DNON/OFF

PP

PP

NN

NN

N

N

NN

NN N

NN

N N

N

N

N

DOG INTAKE175

CAT INTAKE176

E55

E53

E52

E52

D D

DD

D D

DD

D D

DDD

D D D

CAT INTAKE

ON/OFF

GENERAL NOTES FOR STATIONS CONFIGURATION:

A. PROVIDE CUSTOM ENGRAVING AS DIRECTED BY OWNER ON EACH BUTTON OF EACHDEVICE TO MATCH THE FUNCTIONS OF THE SPACE. DEVICE LABELS SHOWN ARE GENERICIN NATURE AND DO NOT REPRESENT THE EXACT FINAL EXPECTED ENGRAVING.

DIM UP/DNON/OFF

SHEET NUMBER:

DRAWING TITLE:

DATE ISSUED:

PROJECT NUMBER:

PROJECT SET:

I HEREBY CERTIFY THAT THESE DOCUMENTS WERE PREPARED OR APPROVED BY ME, AND THAT I AM A

DULY LICENSED PROFESSIONAL ENGINEER UNDER THE LAWS OF THE

STATE OF MARYLAND. LICENSE NUMBER: #xxxxx

EXPIRATION DATE: mm-dd-yyyy

CO

NSU

LTAN

T:SE

AL

ALL DRAWINGS ARE PROTECTED BY FEDERAL COPYRIGHT BY MANNS WOODWARD STUDIOS, INC. AND CAN NOT BE REPRODUCED OR MODIFIED IN ANY MANNER WITHOUT WRITTEN PERMISSION. DOCUMENTS MAY NOT BE USED IN PART OR WHOLE TO DEVELOP THE DESIGN OF ANOTHER BUILDING WITHOUT EXPRESS WRITTEN PERMISSION BY MANNS WOODWARD STUDIOS.

(P) 410-344-1460(F) 443-403-2460(E) [email protected]

S T U D I O S10839-D PHILADELPHIA RDWHITE MARSH, MD 21162

ARCHITECTURE + MASTER PLANNING

Eng

inee

ring

Infra

stru

ctur

e S

olut

ions

C.C

. Joh

nson

& M

alho

tra,

P.C

.

400

Eas

t Pra

tt S

treet

, Sui

te 6

04B

altim

ore,

MD

212

02(P

) 410

-461

-992

0 | (

F) (

667)

239-

3534

| (E

) BA

LTIM

OR

E@

CC

JM.C

OM

CC

JM

3/15

/201

9 5:

05:3

0 PM

E401

BALT

IMO

RE C

ITY

ANIM

AL S

ERVI

CES

BUIL

DING

2490

GIL

ES R

OAD

, BAL

TIM

ORE

, 212

25

ELECTRICAL - ENLARGEDSCALE PLANS - LIGHTINGCONTROLS II

03-15-2019

17-023

100% CD

REFERENCED NOTES - LIGHTING NEW WORKE21 CONNECT ALL EXIT LIGHTS ON THE BRANCH CIRCUIT INDICATED AND UPSTREAM OF

SWITCH.E50 PROVIDE ON/OFF + DIMMING LOW VOLTAGE SWITCH LIGHTING CONTROL BY ACUITY

CONTROLS OR APPROVED EQUAL. SEE SEQUENCE OF OPERATION BELOW FORLIGHTING SCENE SCHEMATIC.

E51 PROVIDE DAYLIGHT HARVESTING PHOTOCELL LIGHTING CONTROL IN THIS AREA. SEESEQUENCE OF OPERATION BELOW FOR LIGHTING SCENE SCHEMATIC.

E52 PROVIDE DIMMING/RELAY POWER PACK BY ACUITY CONTROLS OR APPROVED EQUAL,LOCATED IN ACCESSIBLE CEILING SPACE OF ROOM NEAR ENTRY DOOR. SEE SEQUENCEOF OPERATION BELOW FOR LIGHTING SCENE SCHEMATIC.

E53 277V LIGHTING CIRCUIT FROM DIMMING/RELAY POWER PACK BY ACUITY CONTROLS ORAPPROVED EQUAL. REFER FOR ELECTRICAL DRAWING E101 FOR DESIGNATED LIGHTCIRCUITS.

E55 PROVIDE AND CONNECT CAT-5 NETWORK CABLE TO BRIDGE DEVICE BY ACUITYCONTROLS OR APPROVED EQUAL.

E58 PROVIDE WALL MOUNTED OCCUPANCY SENSOR SWITCH BY ACUITY CONTROLS ORAPPROVED EQUAL, IN THIS AREA. SEE SEQUENCE OF OPERATION BELOW FOR LIGHTINGSCENE SCHEMATIC.

1/4" = 1'-0"1ELECTRICAL - PUBLIC LOBBY/OBEDIENCE TRAINING - LIGHTING CONTROLS

3/8" = 1'-0"2ELECTRICAL - TYPICAL RESTROOMS - LIGHTING CONTROL

1/4" = 1'-0"3 SEQUENCE OF OPERATION - RESTROOMS1/4" = 1'-0"4 SEQUENCE OF OPERATION - PUBLIC LOBBY/OBEDIENCE TRAINING

1/4" = 1'-0"5 ELECTRICAL - CAT INTAKE - LIGHTING CONTROL

1/4" = 1'-0"6 SEQUENCE OF OPERATION - CAT INTAKE

NO. DESCRIPTION DATE

Page 9: ELECTRICAL LEGEND

LV

LV

LVLV

LV

LV

LV

LV

LV

OS

LD LD

LV

LDLV

LV

LD

LD

PP

PP

PP

PP

PP

PP

PP

PP

N

N

NN

NN

N

N

NN

NN

N

N

N

N

N

N

NN

N N

N N

N N

N

N N

N N

N

N NNN

N

N

N

N

NN

N

N

NN

N

E21

E21

N

N

N

N

NN

N

N

N

N

DOG HOLDING161

DOG HOLDING162

DOGRECOVERY

166

DOGRECOVERY

(BEACH)165

CATRECOVERY

164

CAT HOLDING163

SURGERYPREP168

TNR CATHOLDING

169

SURGERY170

OXYGENSTORAGE

167

N N

N N

N

N

N

N

E55

E52

E53

E53E55

E52

E52

E55

E55

E55

E52

E55

D12 D12 D12

D12D12D12

D12 D12 D12

D12D12D12

D12 D12 D12

D12 D12 D12

D12

D12

D12

DR DR

DRDR

DR DR

DRDR

DRDR

DR

DR

DRDR

DR DR

AC

AC

AC AC

AC

AC

DRDR

DRDR

DRDR

DRDR

AC AC

AC

AC

E55

E55 E52

E52

E52

E52

GL

E59E59

E59

E59

E59

E59

N

E59

E59

E59

E59

E58

E50

E50

N

N

GENERAL NOTES FOR STATIONS CONFIGURATION:

A. PROVIDE CUSTOM ENGRAVING AS DIRECTED BY OWNER ON EACH BUTTON OF EACHDEVICE TO MATCH THE FUNCTIONS OF THE SPACE. DEVICE LABELS SHOWN ARE GENERICIN NATURE AND DO NOT REPRESENT THE EXACT FINAL EXPECTED ENGRAVING.

B. MODE 1: ZONE(S) a,b,c,d,e at 100%C. MODE 2: ZONE(S) - a,b,c,d at 100% / ZONE e - OFF

F. DAYLIGHT SENSOR: UNLESS OTHERWISE INDICATED, TURN LIGHTS TURNS OFF ZONE E WHEN NATURAL LIGHT FROM SKY LIGHT IS REQUIRED FC, AND DIM REMAINING ZONES AT50%.

D. MODE 3: ZONE(S) - a,b,c,d,e at 50% E. MODE 4: ZONE(S) - a,b,c,e OFF / ZONE d AT 50%

OFF

ON

ON/OFF

DIM UP/DNON/OFF

PP

N

NN

NN N

N N

N

N

A

A

A

A

A

A

A

A1

E53

E52 E55

E21

FRONT OFFICE106

E57

E57

GENERAL NOTES FOR STATIONS CONFIGURATION:

A. PROVIDE CUSTOM ENGRAVING AS DIRECTED BY OWNER ON EACH BUTTON OF EACHDEVICE TO MATCH THE FUNCTIONS OF THE SPACE. DEVICE LABELS SHOWN ARE GENERICIN NATURE AND DO NOT REPRESENT THE EXACT FINAL EXPECTED ENGRAVING.

B. MODE 1: ZONE(S) a,b,c,d,e at 100%C. MODE 2: ZONE(S) - a,b,c,d at 100% / ZONE e - OFF

F. DAYLIGHT SENSOR: UNLESS OTHERWISE INDICATED, TURN LIGHTS TURNS OFF ZONE E WHEN NATURAL LIGHT FROM SKY LIGHT IS REQUIRED FC, AND DIM REMAINING ZONES AT50%.

D. MODE 3: ZONE(S) - a,b,c,d,e at 50% E. MODE 4: ZONE(S) - a,b,c,e OFF / ZONE d AT 50%

ON/OFF

DIM UP/DNON/OFF

MEETINGROOM

103

MP8

MP8 MP81

MP8

PPN

N

N

N

N

N E55 E52

E53

E21

E50

OS

E54

E50

GENERAL NOTES FOR STATIONS CONFIGURATION:

A. PROVIDE CUSTOM ENGRAVING AS DIRECTED BY OWNER ON EACH BUTTON OF EACHDEVICE TO MATCH THE FUNCTIONS OF THE SPACE. DEVICE LABELS SHOWN ARE GENERICIN NATURE AND DO NOT REPRESENT THE EXACT FINAL EXPECTED ENGRAVING.

B. MODE 1: ZONE(S) a,b,c,d,e at 100%C. MODE 2: ZONE(S) - a,b,c,d at 100% / ZONE e - OFF

F. DAYLIGHT SENSOR: UNLESS OTHERWISE INDICATED, TURN LIGHTS TURNS OFF ZONE E WHEN NATURAL LIGHT FROM SKY LIGHT IS REQUIRED FC, AND DIM REMAINING ZONES AT50%.

D. MODE 3: ZONE(S) - a,b,c,d,e at 50% E. MODE 4: ZONE(S) - a,b,c,e OFF / ZONE d AT 50%

ON/OFF

DIM UP/DNON/OFF

SHEET NUMBER:

DRAWING TITLE:

DATE ISSUED:

PROJECT NUMBER:

PROJECT SET:

I HEREBY CERTIFY THAT THESE DOCUMENTS WERE PREPARED OR APPROVED BY ME, AND THAT I AM A

DULY LICENSED PROFESSIONAL ENGINEER UNDER THE LAWS OF THE

STATE OF MARYLAND. LICENSE NUMBER: #xxxxx

EXPIRATION DATE: mm-dd-yyyy

CO

NSU

LTAN

T:SE

AL

ALL DRAWINGS ARE PROTECTED BY FEDERAL COPYRIGHT BY MANNS WOODWARD STUDIOS, INC. AND CAN NOT BE REPRODUCED OR MODIFIED IN ANY MANNER WITHOUT WRITTEN PERMISSION. DOCUMENTS MAY NOT BE USED IN PART OR WHOLE TO DEVELOP THE DESIGN OF ANOTHER BUILDING WITHOUT EXPRESS WRITTEN PERMISSION BY MANNS WOODWARD STUDIOS.

(P) 410-344-1460(F) 443-403-2460(E) [email protected]

S T U D I O S10839-D PHILADELPHIA RDWHITE MARSH, MD 21162

ARCHITECTURE + MASTER PLANNING

Eng

inee

ring

Infra

stru

ctur

e S

olut

ions

C.C

. Joh

nson

& M

alho

tra,

P.C

.

400

Eas

t Pra

tt S

treet

, Sui

te 6

04B

altim

ore,

MD

212

02(P

) 410

-461

-992

0 | (

F) (

667)

239-

3534

| (E

) BA

LTIM

OR

E@

CC

JM.C

OM

CC

JM

3/15

/201

9 5:

05:3

8 PM

E402

BALT

IMO

RE C

ITY

ANIM

AL S

ERVI

CES

BUIL

DING

2490

GIL

ES R

OAD

, BAL

TIM

ORE

, 212

25

ELECTRICAL - ENLARGEDSCALE PLANS - LIGHTINGCONTROLS III

03-15-2019

17-023

100% CD

1/4" = 1'-0"1ELECTRICAL - SURGERY SUITE - LIGHTING CONTROLS

1/4" = 1'-0"2SEQUENCE OF OPERATION - SURGERY SUITE

REFERENCED NOTES - LIGHTING NEW WORKE21 CONNECT ALL EXIT LIGHTS ON THE BRANCH CIRCUIT INDICATED AND UPSTREAM OF

SWITCH.E50 PROVIDE ON/OFF + DIMMING LOW VOLTAGE SWITCH LIGHTING CONTROL BY ACUITY

CONTROLS OR APPROVED EQUAL. SEE SEQUENCE OF OPERATION BELOW FORLIGHTING SCENE SCHEMATIC.

E52 PROVIDE DIMMING/RELAY POWER PACK BY ACUITY CONTROLS OR APPROVED EQUAL,LOCATED IN ACCESSIBLE CEILING SPACE OF ROOM NEAR ENTRY DOOR. SEE SEQUENCEOF OPERATION BELOW FOR LIGHTING SCENE SCHEMATIC.

E53 277V LIGHTING CIRCUIT FROM DIMMING/RELAY POWER PACK BY ACUITY CONTROLS ORAPPROVED EQUAL. REFER FOR ELECTRICAL DRAWING E101 FOR DESIGNATED LIGHTCIRCUITS.

E54 PROVIDE CEILING MOUNTED OCCUPANCY SENSOR SWITCH BY ACUITY CONTROLS ORAPPROVED EQUAL, IN THIS AREA. SEE SEQUENCE OF OPERATION BELOW FOR LIGHTINGSCENE SCHEMATIC.

E55 PROVIDE AND CONNECT CAT-5 NETWORK CABLE TO BRIDGE DEVICE BY ACUITYCONTROLS OR APPROVED EQUAL.

E57 PROVIDE NLIGHT ENABLED TOGGLE AND/OR RAISE/LOWER VOLTAGE SWITCH WITHUSER DEFINED LOCAL CONTROL OF A LIGHTING ZONE.

E58 PROVIDE WALL MOUNTED OCCUPANCY SENSOR SWITCH BY ACUITY CONTROLS ORAPPROVED EQUAL, IN THIS AREA. SEE SEQUENCE OF OPERATION BELOW FOR LIGHTINGSCENE SCHEMATIC.

E59 PROVIDE ON/OFF LOW VOLTAGE SWITCH LIGHTING CONTROL BY ACUITY CONTROLS ORAPPROVED EQUAL. SEE SEQUENCE OF OPERATION BELOW FOR LIGHTING SCENESCHEMATIC.

1/4" = 1'-0"3ELECTRICAL - FRONT OFFICE - LIGHTING CONTROLS

1/4" = 1'-0"4SEQUENCE OF OPERATION - FRONT OFFICE

3/8" = 1'-0"5ELECTRICAL - MEETING ROOM - LIGHTING CONTROLS

1/4" = 1'-0"6SEQUENCE OF OPERATION - MEETING ROOM

NO. DESCRIPTION DATE

Page 10: ELECTRICAL LEGEND

TRANSFORMER SCHEDULE

ID TAG

PRIMARY SECONDARYSBJ GEC

(CU) NOTESVOLTAGEDISCONNECT

TYPE LOCATIONTRIP

RATING FEEDER (CU)CONDUIT

SIZE VOLTAGE DISCONNECT TYPE LOCATIONTRIP

RATING FEEDER (CU)CONDUIT

SIZE

T1 75 480VCIRCUIT

BREAKER SWITCHBOARD "HSB" 125A 3#1 + 1#6G 1-1/2" 120V/208Y CIRCUIT BREAKER PANEL "EL1" 300A 4 #350K + 1#3G 3" #2

T2

75

480VCIRCUIT

BREAKER SWITCHBOARD "HSB"

125A 3#1 + 1#6G 1-1/2"

120V/208Y CIRCUIT BREAKER PANEL "PP1" 400A

4 #350K + 1#3G 3" #2

T3 30 480VCIRCUIT

BREAKER SWITCHBOARD "HSB" 60A 3#6 + 1#8G 1" 120V/208Y CIRCUIT BREAKER PANEL "ML1" 100A 4#2 + 1#6G 1-1/2" #6

T4

112.5

480VCIRCUIT

BREAKER SWITCHBOARD "HSB"

175A 3#2/0 + 1#6G 2"

120V/208Y CIRCUIT BREAKER PANEL "RP1" 300A

4-500KCMIL +1#2G 4" #2/0

TYPE K-13

KVARATING

FEC

J

GRADE LEVEL

ROOF

ELECTRICAL ROOM

TG

G

FUTURE GENERATOR AND ASSOCIATED CONCRETE PAD,

BY OTHERS.

PAD-MOUNTED UTILITY TRANSFORMER

MEDIUM VOLTAGEPRIMARY

HOUSE SERVICE 1000A SWITCHBOARD (HSB)

M

M ATS

M

T1 T2 T3

E

L

N

EL1 (DOUBLE SECTION)

PP1 MH1 ML1 LPRP2 (DOUBLE SECTION)

300A 400A 100A200A 250A 100A

M M M M

DOAS-1 DOAS-2 DOAS-3 DOAS-4

30A

90A

80A

150A

50A

125A

125A

60

3#1/0 + 1#6G IN 2"C

3#1/0 + 1#6G IN 2"C3#3 + 1#8G IN 1"C3#3 + 1#8G IN 1"C

4#2 + 1#1G IN 1-1/2"C

4#350 KCMILS + 1#3G IN 3-1/2"C

DISCONNECT SWITCH T1, 200A, 3 POLE, FUSED @125A,

600 VAC, SN, NEMA 135 KAIC

#4/0 AWG GROUNDING ELECTRODE CONDUCTOR IN

3/4" C TO BUILDING STEEL, WATER SERVICE ENTRANCE

PIPING AND TO GROUND FIELD

4 WAY UTILITY SECONDARY LATERAL DUCTBANK (4-4" PVC

CONDUITS)

EXISTING 60KW 480/277 VAC , 2Ø, 4W DIESEL GENERATOR. PROVIDED BY

OWNER. PROVIDE SOUND ATTENUATION, WEATHER PROOF ENCLOSURE.

125A

#4/0

1000A

NEUTRAL BUS

1000ALSIG

3 SET OF (4-500KCMIL & #3/0G IN 4"C)

4#1 + 1#6G IN 4"C DUCTBANK

AUTOMATIC TRANSFER SWITCH 125A, 3 POLE, SN, 480 VAC,

35 KAIC, NEMA 1

4#1 + 1#6 IN 2"C

DISCONNECT SWITCH BY UNITMANUFACTURE, SEE HVAC

DRAWINGS

DISCONNECT SWITCH BY UNITMANUFACTURE, SEE HVAC

DRAWINGS

CONCRETE PAD

CONCRETE PAD CONCRETE PAD

CONCRETE PAD

CONCRETE PAD CONCRETE PAD

CONCRETE PAD

ATS-1

X-RAY

150A 250A

E.G. BUS

SERVICE BONDING JUMPER

#3/0 AWG GROUNDING ELECTRODE CONDUCTOR IN

3/4" C TO GROUND ROD BY BGE.

DISCONNECT T3, 100 A, 208V, 3P, 4W NEMA 1

1 2 3 4

100A

175A

5

4#350 KCMILS + 1#6G IN 3"C

200A

200A

SERVICE RATED 1000A ATS SECTION

GENERATOR INCOMING 1000A BREAKER SECTIONINCOMING SECTION

1000A MAIN CIRCUIT BREAKER AND METERING

CORRIDOR 132

TRANSFORMER GENERAL NOTES:1. UNLESS OTHERWISE NOTED, ALL TRANSFORMERS TO BE DRY-TYPE, DELTA-WYE TYPE TRANSFORMERS. SEE SPECIFICATION FOR ADDITIONAL DETAILS

2. PROVIDE CONCRETE PAD FOR TRANSFORMERS. SEE ARCHITECTURAL EQUIPMENT PAD DETAILS FOR ADDITIONAL INFORMATION.

3. SECONDARY OVERCURRENT PROTECTION DEVICE SHALL BE LOCATED SUCH THAT THE MAXIMUM LENGTH OF SECONDARY CONDUCTORS DOES NOT EXCEED 10 LINEAR FEET.

4. PROVIDE GROUNDING ELECTRICAL CONDUCTOR TO BUILDING PER NEC

T4RP1

300A

200A

PP2

200A

4#4/0 + 1#4G IN 2-1/2"C

4#1 + 1#6 IN 1-1/2"C

M

M

M

M

SPD

SERVER/DATA/TEL 125

4#1 + 1#6G IN 2"C

M

PAD MOUNTED GENERATOR DOCKING STATION, TRYSTAR

GDS-125P-LM-JK

ESTIMATE HANDHOLE

T1

PNL EL1

T2

RP1 - 27

PNL RP1

T3

MH1 - 18

EHUH-2HSB

ELECTRICAL202

DISCONNECT SWITCH T1

ATS-1DISCONNECT

SWITCH T3, 250A, 3P

PNL PP1

T4

15' - 8"

4' -

8"

0' - 6"

4' -

0"

3' - 6" 3' - 6" 2' - 0" 3' - 0" 3' - 0"

1' - 7"

1 2 3 4 5

15' - 0"

4' -

0"

3' -

0"

3' -

0"

3' -

5"

4' - 5 1/2" 4' - 4 1/2"

1' -

5"

NORTHFACE

CONNECT TO

PANEL "LP1"

277V, 20A CIRCUITA B C

LOADTO LIGHTING

ELECTRONIC ASTRONOMICALTIME CLOCK WITH MANUALOVERRIDE CAPABILITY

TIME CLOCK WITH 8 CIRCUITRELAY CONTROL. MOUNTEDINSIDE NEMA-4X, STAINLESS

STEEL, LOCKABLE ENCLOSURE.

PHOTO CELL

NOTES:1. ELECTRICAL CONTRACTOR SHALL PROGRAM THE TIME CLOCK BASED ON OWNER'S

DIRECTION. (INCLUDING INDIVIDUAL ZONES). THE PARKING LOT LIGHTS SHALL AUTOMATICALLY SWITCH-OFF FROM MIDNIGHT TO 6 AM, UNLESS DIRECTED OTHERWISE.

ON ROOFPC

CT

C

SHEET NUMBER:

DRAWING TITLE:

DATE ISSUED:

PROJECT NUMBER:

PROJECT SET:

I HEREBY CERTIFY THAT THESE DOCUMENTS WERE PREPARED OR APPROVED BY ME, AND THAT I AM A

DULY LICENSED PROFESSIONAL ENGINEER UNDER THE LAWS OF THE

STATE OF MARYLAND. LICENSE NUMBER: #xxxxx

EXPIRATION DATE: mm-dd-yyyy

CO

NSU

LTAN

T:SE

AL

ALL DRAWINGS ARE PROTECTED BY FEDERAL COPYRIGHT BY MANNS WOODWARD STUDIOS, INC. AND CAN NOT BE REPRODUCED OR MODIFIED IN ANY MANNER WITHOUT WRITTEN PERMISSION. DOCUMENTS MAY NOT BE USED IN PART OR WHOLE TO DEVELOP THE DESIGN OF ANOTHER BUILDING WITHOUT EXPRESS WRITTEN PERMISSION BY MANNS WOODWARD STUDIOS.

(P) 410-344-1460(F) 443-403-2460(E) [email protected]

S T U D I O S10839-D PHILADELPHIA RDWHITE MARSH, MD 21162

ARCHITECTURE + MASTER PLANNING

Eng

inee

ring

Infra

stru

ctur

e S

olut

ions

C.C

. Joh

nson

& M

alho

tra,

P.C

.

400

Eas

t Pra

tt S

treet

, Sui

te 6

04B

altim

ore,

MD

212

02(P

) 410

-461

-992

0 | (

F) (

667)

239-

3534

| (E

) BA

LTIM

OR

E@

CC

JM.C

OM

CC

JM

3/15

/201

9 5:

05:4

3 PM

E600

BALT

IMO

RE C

ITY

ANIM

AL S

ERVI

CES

BUIL

DING

2490

GIL

ES R

OAD

, BAL

TIM

ORE

, 212

25

ELECTRICAL - POWERRISER DIAGRAM

03-15-2019

17-023

100% CD

SCALE: NONE1ELECTRICAL RISER DIAGRAM

1/4" = 1'-0"2ELECTRICAL PARTIAL FLOOR PLAN - ELECTRICAL RM 202

SCALE: NONE3SWITCHBOARD HSB ELEVATION

SCALE: NONE4TIME-CLOCK SCHEMATIC

NO. DESCRIPTION DATE

Page 11: ELECTRICAL LEGEND

SHEET NUMBER:

DRAWING TITLE:

DATE ISSUED:

PROJECT NUMBER:

PROJECT SET:

I HEREBY CERTIFY THAT THESE DOCUMENTS WERE PREPARED OR APPROVED BY ME, AND THAT I AM A

DULY LICENSED PROFESSIONAL ENGINEER UNDER THE LAWS OF THE

STATE OF MARYLAND. LICENSE NUMBER: #xxxxx

EXPIRATION DATE: mm-dd-yyyy

CO

NSU

LTAN

T:SE

AL

ALL DRAWINGS ARE PROTECTED BY FEDERAL COPYRIGHT BY MANNS WOODWARD STUDIOS, INC. AND CAN NOT BE REPRODUCED OR MODIFIED IN ANY MANNER WITHOUT WRITTEN PERMISSION. DOCUMENTS MAY NOT BE USED IN PART OR WHOLE TO DEVELOP THE DESIGN OF ANOTHER BUILDING WITHOUT EXPRESS WRITTEN PERMISSION BY MANNS WOODWARD STUDIOS.

(P) 410-344-1460(F) 443-403-2460(E) [email protected]

S T U D I O S10839-D PHILADELPHIA RDWHITE MARSH, MD 21162

ARCHITECTURE + MASTER PLANNING

Eng

inee

ring

Infra

stru

ctur

e S

olut

ions

C.C

. Joh

nson

& M

alho

tra,

P.C

.

400

Eas

t Pra

tt S

treet

, Sui

te 6

04B

altim

ore,

MD

212

02(P

) 410

-461

-992

0 | (

F) (

667)

239-

3534

| (E

) BA

LTIM

OR

E@

CC

JM.C

OM

CC

JM

3/15

/201

9 5:

05:4

9 PM

E601

BALT

IMO

RE C

ITY

ANIM

AL S

ERVI

CES

BUIL

DING

2490

GIL

ES R

OAD

, BAL

TIM

ORE

, 212

25

ELECTRICAL -SCHEDULES I

03-15-2019

17-023

100% CD

1. DOUBLE SECTION PANELNotes:

Total Est. Demand: 87 AReceptacle 51470 VA 59.71% 30735 VA Total Conn.: 144 APower 0 VA 0.00% 0 VA Total Est. Demand: 31235 VAMotor 0 VA 0.00% 0 VA Total Conn. Load: 51970 VAHVAC 500 VA 100.00% 500 VALoad Classification Connected Load Demand Factor Estimated Demand Panel Totals

Legend:Total Amps: 148 A 143 A 142 ATotal Load: 17780 VA 17100 VA 17090 VA

83 SPACE -- -- -- 0 VA 0 VA -- -- -- -- 8481 SPACE -- -- -- 0 VA 0 VA -- -- -- -- 8279 SPACE -- -- -- 0 VA 0 VA 3 30 A SPD 8077 SPACE -- -- -- 0 VA 0 VA -- -- -- SPACE 7875 SPARE 20 A 1 0 VA 0 VA -- -- -- SPACE 7673 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 7471 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 7269 RECEP (REPTILE, MAMMALS) 2#12+1#12 G IN 3/4"C 20 A 1 180 VA 0 VA 1 20 A SPARE 7067 RECEP (REPTILE, MAMMALS) 2#12+1#12 G IN 3/4"C 20 A 1 720 VA 720 VA 1 20 A 2#12+1#12 G IN 3/4"C RECEP (REPTILE, MAMMALS) 6865 RECEP (REPTILE, MAMMALS) 2#12+1#12 G IN 3/4"C 20 A 1 720 VA 720 VA 1 20 A 2#12+1#12 G IN 3/4"C RECEP (REPTILE, MAMMALS) 6663 RECEP (REPTILE, MAMMALS) 2#12+1#12 G IN 3/4"C 20 A 1 720 VA 720 VA 1 20 A 2#12+1#12 G IN 3/4"C RECEP (REPTILE, MAMMALS) 6461 RECEP (REPTILE, MAMMALS) 2#12+1#12 G IN 3/4"C 20 A 1 720 VA 720 VA 1 20 A 2#12+1#12 G IN 3/4"C RECEP (REPTILE, MAMMALS) 6259 RECEP (REPTILE, MAMMALS) 2#12+1#12 G IN 3/4"C 20 A 1 720 VA 720 VA 1 20 A 2#12+1#12 G IN 3/4"C RECEP (REPTILE, MAMMALS) 6057 RECEP (REPTILE, MAMMALS) 2#12+1#12 G IN 3/4"C 20 A 1 720 VA 720 VA 1 20 A 2#12+1#12 G IN 3/4"C RECEP (REPTILE, MAMMALS) 5855 RECEP (REPTILE, MAMMALS) 2#12+1#12 G IN 3/4"C 20 A 1 720 VA 720 VA 1 20 A 2#12+1#12 G IN 3/4"C RECEP (REPTILE, MAMMALS) 5653 RECEP (REPTILE, MAMMALS) 2#12+1#12 G IN 3/4"C 20 A 1 720 VA 720 VA 1 20 A 2#12+1#12 G IN 3/4"C RECEP (REPTILE, MAMMALS) 5451 RECEP. (ROOF) 2#12+1#12 G IN 3/4"C 20 A 1 720 VA 800 VA 1 20 A SYSTEMS FURNITURE FEED 5249 RECEP (WATER 120) 2#12+1#12 G IN 3/4"C 20 A 1 500 VA 800 VA 1 20 A SYSTEMS FURNITURE FEED 5047 GFI (WATER 120) 2#12+1#12 G IN 3/4"C 20 A 1 180 VA 800 VA 1 20 A SYSTEMS FURNITURE FEED 4845 RECEP. TV (LOBBY 101) 2#12+1#12 G IN 3/4"C 20 A 1 180 VA 1600 VA 1 20 A SYSTEMS FURNITURE FEED 4643 RECEP. TV (LOBBY 101) 2#12+1#12 G IN 3/4"C 20 A 1 180 VA 800 VA 1 20 A SYSTEMS FURNITURE FEED 4441 RECEP. (LOBBY, OBEDIENCE) 2#12+1#12 G IN 3/4"C 20 A 1 900 VA 800 VA 1 20 A SYSTEMS FURNITURE FEED 4239 RECEP. (OFF 112, 113, 114, 115,... 2#12+1#12 G IN 3/4"C 20 A 1 900 VA 800 VA 1 20 A SYSTEMS FURNITURE FEED 4037 RECEP. (OFF 108, 109, 110, 111) 2#12+1#12 G IN 3/4"C 20 A 1 720 VA 800 VA 1 20 A SYSTEMS FURNITURE FEED 3835 EQ-16 MONITOR (MEETING 103) 2#12+1#12 G IN 3/4"C 20 A 1 400 VA 940 VA 1 20 A 2#12+1#12 G IN 3/4"C CPU, FLOOR (OFFICE 115, 117) 3633 RECEP. (MEETING 103) 2#12+1#12 G IN 3/4"C 20 A 1 940 VA 1080 VA 1 20 A 2#12+1#12 G IN 3/4"C CPU (OFFICES 114, 115) 3431 RECEP. (CORRIDOR) 2#12+1#12 G IN 3/4"C 20 A 1 900 VA 1080 VA 1 20 A 2#12+1#12 G IN 3/4"C CPU (OFFICE 112, 113, 114) 3229 RECEP. (CORRIDOR, STORAGE) 2#12+1#12 G IN 3/4"C 20 A 1 1190 VA 1080 VA 1 20 A 2#12+1#12 G IN 3/4"C CPU (OFFICE 111, 112, 113) 3027 RECEP. (CORRIDOR, STORAGE) 2#12+1#12 G IN 3/4"C 20 A 1 720 VA 1080 VA 1 20 A 2#12+1#12 G IN 3/4"C CPU (OFFICE 109, 110, 111) 2825 RECEP. (CORRIDOR, STORAGE) 2#12+1#12 G IN 3/4"C 20 A 1 1080 VA 1080 VA 1 20 A 2#12+1#12 G IN 3/4"C CPU (FRONT, OFFICE 108, 109) 2623 RECEP (REPTILE/WILDLIFE) 2#12+1#12 G IN 3/4"C 20 A 1 720 VA 1080 VA 1 20 A 2#12+1#12 G IN 3/4"C CPU (FRONT, OFFICE 108) 2421 RECEP. (GROOM, REPT, MAMLS) 2#12+1#12 G IN 3/4"C 20 A 1 900 VA 1080 VA 1 20 A 2#12+1#12 G IN 3/4"C CPU (FRONT OFFICE 106) 2219 GFI (GROOM, REPT, MAMLS) 2#12+1#12 G IN 3/4"C 20 A 1 540 VA 1080 VA 1 20 A 2#12+1#12 G IN 3/4"C CPU (FRONT OFFICE 106) 2017 GFI (CAT ROOM 144, 145, 146) 2#12+1#12 G IN 3/4"C 20 A 1 1080 VA 1080 VA 1 20 A 2#12+1#12 G IN 3/4"C CPU (MEETING, FRONT, OBEDI) 1815 GFI (CAT, LAUNDRY) 2#12+1#12 G IN 3/4"C 20 A 1 720 VA 720 VA 1 20 A 2#12+1#12 G IN 3/4"C CPU (ADOPTION, EXAM) 1613 GFI (OBEDIENCE, CAT COMM) 2#12+1#12 G IN 3/4"C 20 A 1 900 VA 1080 VA 1 20 A 2#12+1#12 G IN 3/4"C CPU (SURRENDER LOBBY 139) 1411 GFI (DOG ROOM 155, 156) 2#12+1#12 G IN 3/4"C 20 A 1 720 VA 1080 VA 1 20 A 2#12+1#12 G IN 3/4"C CPU (VET GROUP OFFICE) 129 GFI (DOG ROOM 153, 154) 2#12+1#12 G IN 3/4"C 20 A 1 720 VA 720 VA 1 20 A 2#12+1#12 G IN 3/4"C CPU (VET TECH GROUP 121) 107 GFI (LOUNGE 128) 2#12+1#12 G IN 3/4"C 20 A 1 180 VA 720 VA 1 20 A 2#12+1#12 G IN 3/4"C CPU (VET TECH GROUP 121) 85 GFI (TOILET 130, 131) 2#12+1#12 G IN 3/4"C 20 A 1 360 VA 360 VA 1 20 A 2#12+1#12 G IN 3/4"C PRINTER (VET TECH 121, 122) 63 GFI (DOG/CAT KITCHEN 147) 2#12+1#12 G IN 3/4"C 20 A 1 180 VA 180 VA 1 20 A 2#12+1#12 G IN 3/4"C PRINTER (SURRENDER LOBBY) 41 GFI (TOILET 104, 105, 126, 127) 2#12+1#12 G IN 3/4"C 20 A 1 720 VA 300 VA 1 20 A 2#12+1#12 G IN 3/4"C PRINTER (OFFICE 117) 2

CKT Circuit Description Wire Size Trip Poles A B C Poles Trip Wire Size Circuit Description CKT

1. SEE ARCHITECTURAL DRAWING A106 FOR EQUIPMENT SCHEDULE.Notes:

Enclosure: NEMA 1 Indoor MCB Rating: 200 AMounting: Surface Wires: 4 Mains Rating: 225 A

Supply From: RP1 Phases: 3 Mains Type: CIRCUIT BREAKERLocation: Volts: 120/208 Wye A.I.C. Rating: 10,000

Branch Panel: RP2

Notes:

Receptacle 83690 VA 55.97% 46845 VAPower 113177 VA 100.00% 113177 VA Total Est. Demand: 871 AOther 56183 VA 100.00% 56183 VA Total Conn.: 908 ALighting 25141 VA 125.00% 31427 VA Total Est. Demand: 724409 VAHVAC 475435 VA 100.00% 475435 VA Total Conn. Load: 754902 VAEquipment 0 VA 0.00% 0 VALoad Classification Connected Load Demand Factor Estimated Demand Panel Totals

Legend:Total Amps: 908 A

Total Conn. Load: 754902 VA2019181716151413 EQ-38 - X RAY 3 100 A 50 A 46403 VA PROVIDE METER CIRCUIT BREAKER12 SPD 3 -- 30 A 0 VA LOCATED OUTSIDE OF SWITCHBOARD11 TRANSFORMER T1 (BACK-UP POWER VIA ATS-1) 3 200 A 125 A 41653 VA10 DOAS-01 (ON ROOF) 3 100 A 90 A 68506 VA PROVIDE METER CIRCUIT BREAKER9 TRANSFORMER T4 3 200 A 175 A 72130 VA PROVIDE METER CIRCUIT BREAKER8 DOAS-02 (ON ROOF) 3 100 A 80 A 54123 VA PROVIDE METER CIRCUIT BREAKER7 TRANSFORMER T2 3 200 A 125 A 80776 VA PROVIDE METER CIRCUIT BREAKER6 DOAS-03 (ON ROOF) 3 200 A 150 A 123570 VA PROVIDE METER CIRCUIT BREAKER5 TRANSFORMER T3 3 200 A 125 A 17727 VA PROVIDE METER CIRCUIT BREAKER4 PANEL MH1 3 400 A 250 A 140435 VA PROVIDE METER CIRCUIT BREAKER3 DOAS-04 (ON ROOF) 3 200 A 150 A 123570 VA PROVIDE METER CIRCUIT BREAKER2 PANEL LP 3 100 A 100 A 23298 VA PROVIDE METER CIRCUIT BREAKER1 SPARE 3 -- 200 A 0 VA

CKT Circuit Description # of Poles Frame Size Trip Rating Load Remarks

1. SWITCHBOARD TO BE UTILITY SERVICE RATED AND SUITABLE FOR FUTURE RENEWABLE LOCAL POWER SOURCE.Notes:

Enclosure: NEMA 1 INDOOR MCB Rating: 1000 AMounting: FLOOR, FREE STANDING Wires: 4 Mains Rating: 1200 A

Supply From: Phases: 3 Mains Type: CIRCUIT BREAKERLocation: ELECTRICAL 202 Volts: 480/277 Wye A.I.C. Rating: 65,000

Switchboard: HSB

Notes:

Total Est. Demand: 141 AReceptacle 0 VA 0.00% 0 VA Total Conn.: 141 APower 50884 VA 100.00% 50884 VA Total Est. Demand: 50884 VALighting 0 VA 0.00% 0 VA Total Conn. Load: 50884 VAHVAC 0 VA 0.00% 0 VALoad Classification Connected Load Demand Factor Estimated Demand Panel Totals

Legend:Total Amps: 140 A 144 A 140 ATotal Load: 16840 VA 17264 VA 16780 VA

41 SPARE 20 A 1 0 VA 0 VA -- -- -- SPACE 4239 SPARE 20 A 1 0 VA 0 VA -- -- -- SPACE 4037 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 3835 -- -- -- -- 0 VA 0 VA 1 20 A SPARE 3633 SPARE 20 A 2 0 VA 0 VA 1 20 A SPARE 3431 -- -- -- -- 0 VA 0 VA 1 20 A RESERVED-GATE ENTRAPMENT 3229 SPARE 20 A 2 0 VA 0 VA 1 20 A RESERVED-GATE LOOP... 3027 -- -- -- -- 0 VA 648 VA 1 20 A RESERVED-GATE PEDESTAL 2825 SPARE 20 A 2 0 VA 180 VA 1 20 A 2#12+1#12 G IN 3/4"C EQ-38 ANIMAL SCALE 2623 -- -- -- -- 5452 VA 1700 VA -- -- -- -- 2421 -- -- -- -- 5452 VA 1700 VA 2 35 A 3#10+1#10 G IN 3/4"C EQ-20 STACKED WASHER DRYER 2219 EQ-26 DISHWASHER 2#6+1#10 G IN 1"C 60 A 3 5452 VA 500 VA 1 20 A 2#12+1#12 G IN 3/4"C FLUSH VALVE XFMR (TOILET) 2017 -- -- -- -- 5452 VA 180 VA 1 20 A 2#12+1#12 G IN 3/4"C EQ-8 COFFEE MAKER 1815 -- -- -- -- 5452 VA 180 VA 1 20 A 2#12+1#12 G IN 3/4"C EQ-9 MICROWAVE 1613 EQ-26 DISHWASHER 2#6+1#10 G IN 1"C 60 A 3 5452 VA 180 VA 1 20 A 2#12+1#12 G IN 3/4"C EQ-38 ANIMAL SCALE 1411 EQ-11 WATER COOLER 2#12+1#12 G IN 3/4"C 20 A 1 500 VA 1000 VA 1 20 A 2#12+1#12 G IN 3/4"C EQ-13 COPIER 129 EWC-1 2#12+1#12 G IN 3/4"C 20 A 1 336 VA 1000 VA 1 20 A 2#12+1#12 G IN 3/4"C EQ-13 COPIER 107 EQ-21 VENDING MACHINIE 2#12+1#12 G IN 3/4"C 20 A 1 500 VA 1000 VA 1 20 A 2#12+1#12 G IN 3/4"C EQ-13 COPIER 85 EQ-29 INDUSTRIAL WASHER 2#12+1#12 G IN 3/4"C 20 A 1 840 VA 1656 VA 1 20 A 2#12+1#12 G IN 3/4"C EQ-28 IN\DUSTRIAL DRYER 63 EQ-29 INDUSTRIAL WASHER 2#12+1#12 G IN 3/4"C 20 A 1 840 VA 1656 VA 1 20 A 2#12+1#12 G IN 3/4"C EQ-30 INDUSTRIAL DRYER 41 EQ-27 INDUSTRIAL WASHER 2#12+1#12 G IN 3/4"C 20 A 1 1920 VA 1656 VA 1 20 A 2#12+1#12 G IN 3/4"C EQ-30 INDUSTRIAL DRYER 2

CKT Circuit Description Wire Size Trip Poles A B C Poles Trip Wire Size Circuit Description CKT

1. SEE ARCHITECTURAL DRAWING A106 FOR EQUIPMENT SCHEDULE.Notes:

Enclosure: NEMA 1 Indoor MCB Rating: 200 AMounting: Surface Wires: 4 Mains Rating: 225 A

Supply From: PP1 Phases: 3 Mains Type: 200A MCBLocation: Volts: 120/208 Wye A.I.C. Rating: 10,000

Branch Panel: PP2

1. DOUBLE SECTION PANEL2. CIRCUITS ARE TO BE INDIVIDUALLY METERED. PROVIDE ALL ASSOCIATED EQUIPMENT, ACCESSORIES, SOFTWARE AND TRAINING FOR A COMPLETE AND FULLY FUNCTIONING METERING SYSTEM.

Notes:

Total Est. Demand: 115 AReceptacle 11880 VA 92.09% 10940 VA Total Conn.: 116 APower 21496 VA 100.00% 21496 VA Total Est. Demand: 41544 VAMotor 0 VA 0.00% 0 VA Total Conn. Load: 41653 VAHVAC 4956 VA 100.00% 4956 VALoad Classification Connected Load Demand Factor Estimated Demand Panel Totals

Legend:Total Amps: 137 A 125 A 93 ATotal Load: 15941 VA 14501 VA 11210 VA

83 SPACE -- -- -- 0 VA 0 VA -- -- -- SPACE 8481 SPACE -- -- -- 0 VA 0 VA -- -- -- SPACE 8279 SPACE -- -- -- 0 VA 0 VA -- -- -- SPACE 8077 SPACE -- -- -- 0 VA 0 VA -- -- -- SPACE 7875 SPACE -- -- -- 0 VA 0 VA -- -- -- SPACE 7673 SPACE -- -- -- 0 VA 0 VA -- -- -- SPACE 7471 SPACE -- -- -- 0 VA 0 VA -- -- -- SPACE 7269 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 7067 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 6865 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 6663 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 6461 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 6259 EQ-31 HEAT TRACE 2#12+1#12 G IN 3/4"C 20 A 1 100 VA 360 VA 1 20 A 2#12+1#12 G IN 3/4"C RECEP ( UNDER (COUNTER... 6057 -- -- -- -- 1560 VA 1560 VA -- -- -- -- 5855 L6-20R (SERVER 125) 2#12+1#12 G IN 3/4"C 20 A 2 1560 VA 1560 VA 2 20 A 2#12+1#12 G IN 3/4"C L6-20R (SERVER 125) 5653 -- -- -- -- 4080 VA 0 VA 1 20 A SPARE 5451 -- -- -- -- 4080 VA 0 VA 1 20 A SPARE 5249 EQ-31-CU 3#4+1#8 G IN 3/4"C 45 A 3 4080 VA 0 VA 1 20 A GENERATOR RECEPTACLE 5047 EQ-31 - WALK-IN FREEZER LTG 2#12+1#12 G IN 3/4"C 20 A 1 500 VA 0 VA 1 20 A GENERATOR BATTERY CHARGER 4845 -- -- -- -- 770 VA 0 VA 1 20 A GENERATOR BLOCK HEATER 4643 EQ-31-EC - WALKIN FREEZER... 2#12+1#12 G IN 3/4"C 20 A 2 770 VA 500 VA 1 20 A 2#12+1#12 G IN 3/4"C EXTERIOR SIGNAGE 4441 SPARE 20 A 1 0 VA 500 VA 1 20 A 2#12+1#12 G IN 3/4"C EXTERIOR SIGNAGE 4239 -- -- -- -- 1144 VA 45 VA 1 20 A 2#12+1#12 G IN 3/4"C LTG. LOBBY TRACK LIGHTING 4037 ACU-1 2#10+1#10 G IN 3/4"C 15 A 2 1144 VA 580 VA 1 20 A RECEP ( UNDER (COUNTER... 3835 EF-3 2#12+1#12 G IN 3/4"C 15 A 1 528 VA 448 VA 1 20 A 2#12+1#12 G IN 3/4"C LTG. (SURGERY, HOLDING) 3633 SPARE 20 A 1 0 VA 800 VA 1 20 A 2#12+1#12 G IN 3/4"C LTG. (DOG AND CAT HOLDING) 3431 EQ-51 - SCAVENGE ALARM PANEL 2#12+1#12 G IN 3/4"C 20 A 1 500 VA 512 VA 1 20 A 2#12+1#12 G IN 3/4"C LTG. (SURGERY PREP 168) 3229 EQ-48 AUTOCLAVE 2#12+1#12 G IN 3/4"C 20 A 1 180 VA 600 VA 1 20 A 2#12+1#12 G IN 3/4"C EQ-50 - SURGICAL LIGHT 3027 EQ-48 AUTOCLAVE 2#12+1#12 G IN 3/4"C 20 A 1 180 VA 0 VA 1 20 A SPARE 2825 EQ-42 BLOOD ANALYZER 2#12+1#12 G IN 3/4"C 20 A 1 180 VA 180 VA 1 20 A GFI (LAB 177) 2623 EQ-42 BLOOD ANALYZER 2#12+1#12 G IN 3/4"C 20 A 1 180 VA 180 VA 1 20 A 2#12+1#12 G IN 3/4"C GFI (CAT HOLDING) 2421 EQ-42 BLOOD ANALYZER 2#12+1#12 G IN 3/4"C 20 A 1 180 VA 360 VA 1 20 A 2#12+1#12 G IN 3/4"C GFI (DOG HOLDING 161, 162) 2219 EQ-42 BLOOD ANALYZER 2#12+1#12 G IN 3/4"C 20 A 1 180 VA 540 VA 1 20 A 2#12+1#12 G IN 3/4"C RECEP. (SURGERY 170) 2017 FRIDGE (OFFICE 186, 187, 188, 189) 2#12+1#12 G IN 3/4"C 20 A 1 720 VA 0 VA 1 20 A SPARE 1815 FRIDGE (AC BREAK 190) 2#12+1#12 G IN 3/4"C 20 A 1 400 VA 1080 VA 1 20 A 2#12+1#12 G IN 3/4"C RECEP. (CAT, SURGERY) 1613 FRIDGE (LOUNGE 128) 2#12+1#12 G IN 3/4"C 20 A 1 400 VA 1260 VA 1 20 A 2#12+1#12 G IN 3/4"C RECEP. (SURGERY SUITE) 1411 2 DOOR FREEZER (KITCHEN 147) 2#12+1#12 G IN 3/4"C 20 A 1 1416 VA 540 VA 1 20 A 2#12+1#12 G IN 3/4"C RECEP. (SURGERY 170) 129 FRIDGE (KITCHEN 147) 2#12+1#12 G IN 3/4"C 20 A 1 400 VA 1080 VA 1 20 A 2#12+1#12 G IN 3/4"C RECEP. (SURGERY PREP 168) 107 FRIDGE (KITCHEN 147) 2#12+1#12 G IN 3/4"C 20 A 1 400 VA 720 VA 1 20 A 2#12+1#12 G IN 3/4"C CPU (SURGERY PREP 168) 85 FRIDGE (MED STORAGE 180) 2#12+1#12 G IN 3/4"C 20 A 1 180 VA 720 VA 1 20 A 2#12+1#12 G IN 3/4"C RECEP. (SERVER 125) 63 FRIDGE (LAB 177) 2#12+1#12 G IN 3/4"C 20 A 1 180 VA 720 VA 1 20 A 2#12+1#12 G IN 3/4"C RECEP. (SERVER 125) 41 FRIDGE (SURGERY PREP 168) 2#12+1#12 G IN 3/4"C 20 A 1 180 VA 720 VA 1 20 A 2#12+1#12 G IN 3/4"C RECEP. (SERVER 125) 2

CKT Circuit Description Wire Size Trip Poles A B C Poles Trip Wire Size Circuit Description CKT

Notes:

Enclosure: NEMA 1 Indoor MCB Rating: 300 AMounting: Surface Wires: 4 Mains Rating: 400 A

Supply From: T1 Phases: 3 Mains Type: CIRCUIT BREAKERLocation: ELECTRICAL 202 Volts: 120/208 Wye A.I.C. Rating: 10,000

Branch Panel: EL1

Notes:

Total Est. Demand: 115 AReceptacle 71630 VA 56.98% 40815 VA Total Conn.: 200 APower 0 VA 0.00% 0 VA Total Est. Demand: 41315 VALighting 0 VA 0.00% 0 VA Total Conn. Load: 72130 VAHVAC 500 VA 100.00% 500 VALoad Classification Connected Load Demand Factor Estimated Demand Panel Totals

Legend:Total Amps: 209 A 194 A 200 ATotal Load: 24980 VA 23220 VA 23930 VA

41 - -- -- -- 0 VA 17090 VA -- -- -- -- 4239 - -- -- -- 0 VA 17100... -- -- -- -- 4037 RESERVED FOR RP2 BREAKER -- -- -- 0 VA 17780... 3 200 A PANEL RP2 3835 SPARE 20 A 1 0 VA 0 VA -- -- -- -- 3633 SPARE 20 A 1 0 VA 0 VA -- -- -- -- 3431 0 VA 3 30 A SPD 3229 GFI (ROOF) 20 A 1 720 VA 3027 RECEP. (ELECTRICAL 202) 2#12+1#12 G IN 3/4"C 20 A 1 360 VA 2825 RECEP. (CORRIDOR) 2#12+1#12 G IN 3/4"C 20 A 1 1080 VA 2623 RECEP. (CORRIDOR 160) 2#12+1#12 G IN 3/4"C 20 A 1 720 VA 1080 VA 1 20 A 2#12+1#12 G IN 3/4"C CPU (LAB, X-RAY, EUTHANASIA) 2421 RECEP. (CORRIDOR 159) 2#12+1#12 G IN 3/4"C 20 A 1 720 VA 360 VA 1 20 A 2#12+1#12 G IN 3/4"C CPU (X-RAY) 2219 RECEP. (DOG, CAT EXAM) 2#12+1#12 G IN 3/4"C 20 A 1 720 VA 720 VA 1 20 A 2#12+1#12 G IN 3/4"C CPU (CAT INTAKE 175, OFFICE... 2017 RECEP. (SURRENDER 139, 140) 2#12+1#12 G IN 3/4"C 20 A 1 540 VA 1080 VA 1 20 A 2#12+1#12 G IN 3/4"C CPU (VET OFFICE, EXAM) 1815 RECEP. (BREAK, OFFICES) 2#12+1#12 G IN 3/4"C 20 A 1 900 VA 1080 VA 1 20 A 2#12+1#12 G IN 3/4"C CPU (VET OFFICE, DOG INTAKE) 1613 GFI (OBSERV, QUARAN) 2#12+1#12 G IN 3/4"C 20 A 1 720 VA 720 VA 1 20 A 2#12+1#12 G IN 3/4"C CPU (SURRENDER, LAB 177) 1411 GFI (LAUNDRY 179) 2#12+1#12 G IN 3/4"C 20 A 1 360 VA 1080 VA 1 20 A 2#12+1#12 G IN 3/4"C CPU (OFFICES 186, 188, 189) 129 GFI (INTAKE, STOR, EUTHAN) 2#12+1#12 G IN 3/4"C 20 A 1 900 VA 1080 VA 1 20 A 2#12+1#12 G IN 3/4"C CPU (WORKSTATIONS 185) 107 GFI (INTAKE, TOILETS) 2#12+1#12 G IN 3/4"C 20 A 1 900 VA 1080 VA 1 20 A 2#12+1#12 G IN 3/4"C CPU (WORKSTATIONS 185) 85 GFI (GARAGE, AC STORAGE) 2#12+1#12 G IN 3/4"C 20 A 1 900 VA 360 VA 1 20 A 2#12+1#12 G IN 3/4"C PRINTER (WORKSTATION 185) 63 GFI (LOCKER ROOMS, TRAP) 2#12+1#12 G IN 3/4"C 20 A 1 540 VA 180 VA 1 20 A 2#12+1#12 G IN 3/4"C PRINTER (VET OFFICE 172) 41 GFI (TOILET & SHOWERS) 2#12+1#12 G IN 3/4"C 20 A 1 720 VA 540 VA 1 20 A 2#12+1#12 G IN 3/4"C PRINTER (OFFICES 187, 188, 189) 2

CKT Circuit Description Wire Size Trip Poles A B C Poles Trip Wire Size Circuit Description CKT

Notes:

Enclosure: NEMA 1 Indoor MCB Rating: 300 AMounting: Surface Wires: 4 Mains Rating: 400 A

Supply From: T4 Phases: 3 Mains Type: CIRCUIT BREAKERLocation: ELECTRICAL 202 Volts: 120/208 Wye A.I.C. Rating: 10,000

Branch Panel: RP1

Notes:

Total Est. Demand: 224 AReceptacle 180 VA 100.00% 180 VA Total Conn.: 224 APower 80596 VA 100.00% 80596 VA Total Est. Demand: 80776 VALighting 0 VA 0.00% 0 VA Total Conn. Load: 80776 VAHVAC 0 VA 0.00% 0 VALoad Classification Connected Load Demand Factor Estimated Demand Panel Totals

Legend:Total Amps: 211 A 235 A 234 ATotal Load: 25304 VA 27776 VA 27696 VA

41 - -- -- -- 0 VA 16780 VA -- -- -- -- 4239 - -- -- -- 0 VA 17264... -- -- -- -- 4037 RESERVED - PP2 BREAKER -- -- -- 0 VA 16840... 3 200 A 4#1 + 1#6G IN 2"C PANEL PP2 3835 SPARE 20 A 1 0 VA 3633 EQ-22 MICROSCOPES 2#12+1#12 G IN 3/4"C 20 A 1 180 VA 3431 EQ-13 COPIER (WORKSTATION... 2#12+1#12 G IN 3/4"C 20 A 1 1000 VA 3229 EQ-11 WATER COOLER 2#12+1#12 G IN 3/4"C 20 A 1 500 VA 3027 EQ-9 MICROWAVE 2#12+1#12 G IN 3/4"C 20 A 1 180 VA 2825 EQ-8 COFFEE MAKER 2#12+1#12 G IN 3/4"C 20 A 1 180 VA 552 VA -- -- -- -- 2623 EQ-52 SCAVENGE VAC PUMP 2#12+1#12 G IN 3/4"C 20 A 1 504 VA 552 VA 2 20 A 2#12+1#12 G IN 3/4"C OVERHEAD DOOR OPENER 2421 EQ-3 CHEST FREEZER 2#12+1#12 G IN 3/4"C 20 A 1 240 VA 552 VA -- -- -- -- 2219 EQ-48 AUTOCLAVE 2#12+1#12 G IN 3/4"C 20 A 1 180 VA 552 VA 2 20 A 2#12+1#12 G IN 3/4"C OVERHEAD DOOR OPENER 2017 -- -- -- -- 1560 VA 1560 VA -- -- -- -- 1815 EQ-58 POWER WASH 2#12+1#12 G IN 3/4"C 15 A 2 1560 VA 1560 VA 2 15 A 2#12+1#12 G IN 3/4"C EQ-58 POWER WASH 1613 EQ-58 POWER WASH 2#12+1#12 G IN 3/4"C 20 A 1 1000 VA 1000 VA 1 20 A 2#12+1#12 G IN 3/4"C EQ-58 POWER WASH 1411 -- -- -- -- 1560 VA 1560 VA -- -- -- -- 129 EQ-58 POWER WASH 2#12+1#12 G IN 3/4"C 15 A 2 1560 VA 1560 VA 2 15 A 2#12+1#12 G IN 3/4"C EQ-58 POWER WASH 107 EQ-58 POWER WASH 2#12+1#12 G IN 3/4"C 20 A 1 1000 VA 1000 VA 1 20 A 2#12+1#12 G IN 3/4"C EQ-58 POWER WASH 85 -- -- -- -- 1560 VA 1560 VA -- -- -- -- 63 EQ-58 POWER WASH 2#12+1#12 G IN 3/4"C 15 A 2 1560 VA 1560 VA 2 15 A 2#12+1#12 G IN 3/4"C EQ-58 POWER WASH 41 EQ-58 POWER WASH 2#12+1#12 G IN 3/4"C 20 A 1 1000 VA 1000 VA 1 20 A 2#12+1#12 G IN 3/4"C EQ-58 POWER WASH 2

CKT Circuit Description Wire Size Trip Poles A B C Poles Trip Wire Size Circuit Description CKT

Notes:

Enclosure: NEMA 1 Indoor MCB Rating: 400 AMounting: Surface Wires: 4 Mains Rating: 400 A

Supply From: T2 Phases: 3 Mains Type: MLOLocation: ELECTRICAL 202 Volts: 120/208 Wye A.I.C. Rating: 10,000

Branch Panel: PP1

SERVER /DATA/TEL 125 SERVER /DATA/TEL 125

NO. DESCRIPTION DATE

Page 12: ELECTRICAL LEGEND

SHEET NUMBER:

DRAWING TITLE:

DATE ISSUED:

PROJECT NUMBER:

PROJECT SET:

I HEREBY CERTIFY THAT THESE DOCUMENTS WERE PREPARED OR APPROVED BY ME, AND THAT I AM A

DULY LICENSED PROFESSIONAL ENGINEER UNDER THE LAWS OF THE

STATE OF MARYLAND. LICENSE NUMBER: #xxxxx

EXPIRATION DATE: mm-dd-yyyy

CO

NSU

LTAN

T:SE

AL

ALL DRAWINGS ARE PROTECTED BY FEDERAL COPYRIGHT BY MANNS WOODWARD STUDIOS, INC. AND CAN NOT BE REPRODUCED OR MODIFIED IN ANY MANNER WITHOUT WRITTEN PERMISSION. DOCUMENTS MAY NOT BE USED IN PART OR WHOLE TO DEVELOP THE DESIGN OF ANOTHER BUILDING WITHOUT EXPRESS WRITTEN PERMISSION BY MANNS WOODWARD STUDIOS.

(P) 410-344-1460(F) 443-403-2460(E) [email protected]

S T U D I O S10839-D PHILADELPHIA RDWHITE MARSH, MD 21162

ARCHITECTURE + MASTER PLANNING

Eng

inee

ring

Infra

stru

ctur

e S

olut

ions

C.C

. Joh

nson

& M

alho

tra,

P.C

.

400

Eas

t Pra

tt S

treet

, Sui

te 6

04B

altim

ore,

MD

212

02(P

) 410

-461

-992

0 | (

F) (

667)

239-

3534

| (E

) BA

LTIM

OR

E@

CC

JM.C

OM

CC

JM

3/15

/201

9 5:

05:5

5 PM

E602

BALT

IMO

RE C

ITY

ANIM

AL S

ERVI

CES

BUIL

DING

2490

GIL

ES R

OAD

, BAL

TIM

ORE

, 212

25

ELECTRICAL -SCHEDULES II

03-15-2019

17-023

100% CD

LIGHTING FIXTURE SCHEDULETYPE BASIS OF DESIGN LAMPS WATTS VOLTAGE MOUNTING MOUNTING HEIGHT DLC

APPROVED COMMENTSMANUFACTURER CATALOG NUMBER TYPE CRI EFFICACY

A LITHONIA LIGHTING 2ALL4 CTRF 60L EZ1 LP840 N80 LED 80 106 lm/W 55 W 120V (277V) RECESSED CEILING YesA1 LITHONIA LIGHTING 2ALL4 CTRF 60L EZ1 LP840-EL14L N80 LED 80 106 lm/W 55 W 120V (277V) RECESSED CEILING YesAC LITHONIA LIGHTING 2BLT4-TUWH-PROP-48L-MVOLT-NLT LED 80 121 lm/W 42 W 120V (277V) RECESSED CEILING YesCL LITHONIA LIGHTING WF6 LL LED 50K LED 80 80 lm/W 13 W 277V RECESSED CANOPY YesD LITHONIA LIGHTING 2WRTL G L48 5000LM OAW AFL MVOLT 40K 90CRI LED 90 124 lm/W 39 W 277V RECESSED CEILING YesD1 LITHONIA LIGHTING 2WRTL G L48 5000LM OAW AFL MVOLT 40K 90CRI PS1050 LED 90 124 lm/W 39 W 277V RECESSED CEILING Yes

D12 LITHONIA LIGHTING 2WRTL G L48 5000LM OAW AFL MVOLT 40K 90CRI LED 90 124 lm/W 39 W 120V (277V) RECESSED CEILING YesDC LITHONIA LIGHTING 2BLT4 TUWH PROR 33L SDSMT MVOLT NLT LED 82 132 lm/W 23 W 120V (277V) RECESSED CEILING YesDR LITHONIA LIGHTING EPANL 24 40LHE 40K LED 80 123 lm/W 31 W 120V RECESSED CEILING YesEM LITHONIA LIGHTING EU2 LED M12 LED 277V WALLGL LITHONIA LIGHTING VAP-4000LM-PCL-WD-MVOLT-40K-90 LED 90 136 lm/W 33 W 120V (277V) SURFACE CEILING YesGL1 LITHONIA LIGHTING VAP-4000LM-PCL-WD-MVOLT-40K-90-E15WCP LED 90 136 lm/W 33 W 120V (277V) SURFACE CEILING Yes

MP8 PEERLESS LIGHTING 10CRM4L-QS-LSL-MSL8-SBL- PROPL700LMF(INDIRECT)-90CRI-1000LMF-NLT-277 LED 90 115 lm/W 104 W 120V (277V) SUSPENDED 18 INCHES FIXED No

MP81 PEERLESS LIGHTING 10CRM4L-QS-LSL-MSL8-SBL- PROPL700LMF(INDIRECT)-90CRI-1000LMF-NLT-277-E10WLCP LED 90 115 lm/W 104 W 120V (277V) SUSPENDED 18 INCHES FIXED No

OA LITHONIA LIGHTING CSXW LED 30C 1000 50K TFTM LED 79 141 lm/W 110 W 277V SURFACE 15 FEET Yes TYPE IV, SHORT, BUG RATING:B2-U0-G2

PS PRUDENTIAL LIGHTING BTRI-33-LED4-90-MO-SAL-UNV-DM01-ENL-CA96 LED 80 120 lm/W 50 W 120V (277V) SUSPENDED CEILING YesPS1 PRUDENTIAL LIGHTING BTRI-33-LED4-90-MO-SAL-UNV-DM01-ENL-CA96-EML LED 80 120 lm/W 50 W 120V (277V) SUSPENDED CEILING YesSC1 LITHONIA LIGHTING LDN6 40/40 LO6AR LD MVOLT EZ1 NPS80EZ LED 80 91 lm/W 44 W 120V (277V) RECESSED CEILINGSC2 LITHONIA LIGHTING LDN6 27/40 LO6AR LSS LED 80 91 lm/W 44 W 120V (277V) RECESSED CEILING

SL1 LITHONIA LIGHTING DSX1 LED P6 50K T4M MVOLT HS LED 70 113 lm/W 104 W 277V POLE MOUNTED 25 FEET ABOVE FINISHEDGRADE No TYPE IV, SHORT, BUG RATING:

B1-U2-G2TL LITHONIA LIGHTING LTHBRSD BR20 LED 27K LED 120V TRACK SURFACE Yes 6' TRACK W/ 3 HEADS AT 8W EACH

WS1 LITHONIA LIGHTING VGO2C 25LED 3500K MVOLT LPI LED 120V (277V) WALL 74 INCHES ABOVE FINISHEDGRADE

X LITHONIA LIGHTING LRP 1/2 GMR 120/277 EL N80 LED 0 lm/W 12 W 120V (277V) VARIES

XWL LITHONIA LIGHTING WLTE W 1 LED 0 lm/W 12 W 120V (277V) VARIES No STANDARD TEMP RATING -4° TO122°F (-20°C TO 50°C)

Notes:

Total Est. Demand: 34 AReceptacle 0 VA 0.00% 0 VA Total Conn.: 27 APower 0 VA 0.00% 0 VA Total Est. Demand: 28451 VALighting 22760 VA 125.00% 28451 VA Total Conn. Load: 22760 VAHVAC 0 VA 0.00% 0 VALoad Classification Connected Load Demand Factor Estimated Demand Panel Totals

Legend:Total Amps: 29 A 27 A 29 ATotal Load: 7912 VA 7520 VA 7898 VA

41 SPACE -- -- -- 0 VA 0 VA -- -- -- SPACE 4239 SPACE -- -- -- 0 VA 0 VA -- -- -- SPACE 4037 SPACE -- -- -- 0 VA 0 VA -- -- -- SPACE 3835 SPACE -- -- -- 0 VA 0 VA -- -- -- SPACE 3633 SPACE -- -- -- 0 VA 0 VA -- -- -- SPACE 3431 SPACE -- -- -- 0 VA 0 VA -- -- -- SPACE 3229 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 3027 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 2825 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 2623 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 2421 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 2219 LIGHTING 2#12+1#12 G IN 3/4"C 20 A 1 2365 VA 104 VA 1 20 A 2#12+1#12 G IN 3/4"C LIGHTING (CANOPY) 2017 LIGHTING 2#12+1#12 G IN 3/4"C 20 A 1 1610 VA 2115 VA 1 20 A 2#12+1#12 G IN 3/4"C LIGHTING 1815 CORRIDOR LIGHTING 2#12+1#12 G IN 3/4"C 20 A 1 1605 VA 2493 VA 1 20 A 2#6+1#6 G IN 1"C SITE LIGHTING 1613 LIGHTING 2#12+1#12 G IN 3/4"C 20 A 1 1732 VA 2306 VA 1 20 A 2#12+1#12 G IN 3/4"C LIGHTING 1411 SITE LIGHTING 2#10+1#10 G IN 1"C 20 A 1 1400 VA 1610 VA 1 20 A 2#12+1#12 G IN 3/4"C DOG ROOM LIGHTING 129 LIGHTING 2#12+1#12 G IN 3/4"C 20 A 1 1290 VA 1541 VA 1 20 A 2#12+1#12 G IN 3/4"C CORRIDOR LIGHTING 107 LIGHTING 2#12+1#12 G IN 3/4"C 20 A 1 380 VA 1021 VA 1 20 A 2#12+1#12 G IN 3/4"C LIGHTING 85 LIGHTING 2#12+1#12 G IN 3/4"C 20 A 1 278 VA 952 VA 1 20 A 2#12+1#12 G IN 3/4"C LIGHTING 63 LIGHTING 2#12+1#12 G IN 3/4"C 20 A 1 111 VA 570 VA 1 20 A 2#12+1#12 G IN 3/4"C LOBBY/OBEDIENCE LTG 41 TIME-CLOCK 2#12+1#12 G IN 3/4"C 20 A 1 0 VA 10 VA 1 20 A 2#12+1#12 G IN 3/4"C EMERGENCY LIGHTING 2

CKT Circuit Description Wire Size Trip Poles A B C Poles Trip Wire Size Circuit Description CKT

Notes:

Enclosure: NEMA 1 Indoor MCB Rating: 100 AMounting: Surface Wires: 4 Mains Rating: 125 A

Supply From: HSB Phases: 3 Mains Type: CIRCUIT BREAKERLocation: Volts: 480/277 Wye A.I.C. Rating: 35,000

Branch Panel: LP

LIGHTING FIXTURE SCHEDULE NOTES:1. LISTED CATALOG NUMBER AND MANUFACTURER CONSTITUTES "BASIS OF DESIGN". LISTING OF ALTERNATE MANUFACTURER'S NAMES DOES NOT IMPLY ACCEPTANCE OF THEIR STANDARD PRODUCT. MANUFACTURERS ARE

RESPONSIBLE FOR PROVIDING FIXTURES THAT ARE EQUAL IN ALL RESPECTS TO THE "BASIS OF DESIGN" FIXTURES. "INTENT IS TO ALLOW FOR COMPETITIVELY BID LIGHTING PACKAGE, FOR FIXTURES WITH MULTIPLE NAMED MANUFACTURERS."

2. SUBSTITUTIONS OF FIXTURES ONLY ALLOWED WHEN APPROVED IN ADVANCE BEFORE SHOP DRAWINGS SUBMITTAL AND REQUEST FOR SUBSTITUTION IS SUBMITTED IN ACCORDANCE WITH SPECIFICATION REQUIREMENTS.

3. LIGHTING FIXTURES SUBMITTALS SHALL INCLUDE, AS A MINIMUM: A) FIXTURE TYPE (TO MATCH WITH SCHEDULE), DIMENSIONS AND FINISH. B) LAMP DATA/LED DATA FOR EACH TYPE OF FIXTURE INCLUDING: TYPE, QUANTITY, WATTAGE, AND PHOSPHOR COLOR. C) DRIVER FOR EACH FIXTURE TYPE AND FIXTURE VOLTAGE.

4. PROVIDE UNIVERSAL 120/277 VOLT, 0-10V DIMMING DRIVER FOR DIMMING TO 1% UNLESS OTHERWISE INDICATED.

5. VERIFY CEILING/WALL TRIM COMPATIBILITY PRIOR TO SUBMITTING THE FIXTURES. COLOR AND FIXTURE FINISHES AS SELECTED BY ARCHITECT WHETHER SHOWN OR NOT. PROVIDE ADAPTER AND ADDITIONAL MOUNTING EQUIPMENT AS REQUIRED TO MOUNT FIXTURE TO SURFACE.

6. PROVIDE LABOR AND EQUIPMENT FOR FOCUSING OF ADJUSTABLE FIXTURES AND PRESETTING OF LIGHTING CONTROL SYSTEMS. FOCUSING AND PRESETTING SHALL BE DONE IN THE PRESENCE OF THE OWNER AND ARCHITECT/ENGINEER.

7. PROVIDE ALL CONTROL WIRES FOR 0-10V DIMMING.

8. IF THE CONTRACTOR OPTS TO USE THE FIXTURE OF ALTERNATE MANUFACTURER (WHERE ACCEPTABLE), THE CONTRACTOR SHALL BE RESPONSIBLE TO PROVIDE POINT-TO-POINT CALCULATIONS FOR ALL AREAS AS DIRECTED BY THE ENGINEER AT THE TIME OF SUBSTITUTION REQUEST.

9. PROVIDE ALL CHANNELS, HANGERS, CABLES, SUPPORTS AND OTHER ACCESSORIES AS REQUIRED FOR SUSPENDED FIXTURES FOR COMPLETE WORKING SYSTEM WITHOUT ADDITIONAL COST TO OWNER.

10. ALL LIGHT FIXTURES ANNOTATION WITH A SUFFIX OF 1 SHALL BE HAVE INTEGRAL EMERGENCY BATTERY BALLAST AND CONNECT TO CIRCUIT AS INDICATED, UPSTREAM OF ASSOCIATED CONTROL SWITCH TO SERVE AS A NIGHT LIGHT. PROVIDE ALL WIRING/RACEWAY AS REQUIRED FOR COMPLETE WORKING SYSTEM.

11. IF MULTIPLE VOLTAGES ARE INDICATED, FIXTURE IS COMPATIBLE WITH MULTIPLE VOLTAGES. FIXTURE TO BE WIRED TO VOLTAGE INDICATED IN PARENTHESES ().

3.9 W

15 W

25 W22 lm/W

Notes:

Total Est. Demand: 49 AReceptacle 0 VA 0.00% 0 VA Total Conn.: 49 APower 0 VA 0.00% 0 VA Total Est. Demand: 17727 VALighting 0 VA 0.00% 0 VA Total Conn. Load: 17727 VAHVAC 14619 VA 100.00% 14619 VALoad Classification Connected Load Demand Factor Estimated Demand Panel Totals

Legend:Total Amps: 52 A 48 A 48 ATotal Load: 6264 VA 5715 VA 5748 VA

41 SPARE 20 A 1 0 VA 0 VA -- -- -- SPACE 4239 VAV CONTROL(S) 2#12+1#12 G IN 3/4"C 15 A 1 350 VA 0 VA -- -- -- SPACE 4037 DWH-1 2#12+1#12 G IN 3/4"C 15 A 1 600 VA 0 VA -- -- -- SPACE 3835 CP-2 2#10+1#10 G IN 3/4"C 15 A 1 1012 VA 0 VA 1 20 A SPARE 3633 CP-1 2#10+1#10 G IN 3/4"C 15 A 1 1012 VA 0 VA 1 20 A SPARE 3431 -- -- -- -- 435 VA 237 VA -- -- -- -- 3229 DOAS-06 2#12+1#12 G IN 3/4"C 15 A 2 435 VA 237 VA 2 15 A 2#12+1#12 G IN 3/4"C SSU-2-08, 2-09 3027 -- -- -- -- 435 VA 375 VA -- -- -- -- 2825 DOAS-05 2#12+1#12 G IN 3/4"C 15 A 2 435 VA 375 VA 2 15 A 2#12+1#12 G IN 3/4"C SSU-2-07, 2-10 2623 SPARE 20 A 1 0 VA 588 VA -- -- -- -- 2421 SPARE 20 A 1 0 VA 588 VA 2 15 A 2#12+1#12 G IN 3/4"C SSU-2-02, 2-04 ,2-06 2219 -- -- -- -- 232 VA 588 VA -- -- -- -- 2017 BCU-02, 04 2#12+1#12 G IN 3/4"C 15 A 2 232 VA 588 VA 2 15 A 2#12+1#12 G IN 3/4"C SSU-2-01, 2-03, 2-05 1815 -- -- -- -- 232 VA 0 VA 1 20 A SPARE 1613 BCU-01, 03 2#12+1#12 G IN 3/4"C 15 A 2 232 VA 0 VA 1 20 A SPARE 1411 EF-7 2#12+1#12 G IN 3/4"C 20 A 1 528 VA 798 VA -- -- -- -- 129 EF-6 2#12+1#12 G IN 3/4"C 15 A 1 360 VA 798 VA 2 15 A 2#12+1#12 G IN 3/4"C SSU-1-05, 1-07, 1-09 107 EF-4 2#12+1#12 G IN 3/4"C 15 A 1 528 VA 802 VA -- -- -- -- 85 EF-5 2#12+1#12 G IN 3/4"C 15 A 1 528 VA 802 VA 2 15 A 2#12+1#12 G IN 3/4"C SSU-1-04, 1-06 ,1-08 63 EF-2 2#12+1#12 G IN 3/4"C 15 A 1 125 VA 1440 VA -- -- -- -- 41 EF-1 2#12+1#12 G IN 3/4"C 15 A 1 360 VA 1440 VA 2 15 A 2#12+1#12 G IN 3/4"C SSU-1-01, 1-03, 1-10 2

CKT Circuit Description Wire Size Trip Poles A B C Poles Trip Wire Size Circuit Description CKT

Notes:

Enclosure: NEMA 1 Indoor MCB Rating: 100 AMounting: Surface Wires: 4 Mains Rating: 125 A

Supply From: T3 Phases: 3 Mains Type: CIRCUIT BREAKERLocation: CORRIDOR 132 Volts: 120/208 Wye A.I.C. Rating: 10,000

Branch Panel: ML1

Notes:

Total Est. Demand: 168 AReceptacle 0 VA 0.00% 0 VA Total Conn.: 168 APower 0 VA 0.00% 0 VA Total Est. Demand: 139715 VALighting 0 VA 0.00% 0 VA Total Conn. Load: 139715 VAHVAC 139715 VA 100.00% 139715 VALoad Classification Connected Load Demand Factor Estimated Demand Panel Totals

Legend:Total Amps: 176 A 176 A 159 ATotal Load: 48212 VA 48212 VA 44012 VA

41 SPACE -- -- -- 0 VA 0 VA -- -- -- SPACE 4239 SPACE -- -- -- 0 VA 0 VA -- -- -- SPACE 4037 SPACE -- -- -- 0 VA 0 VA -- -- -- SPACE 3835 -- -- -- -- 5272 VA 0 VA -- -- -- SPACE 3633 -- -- -- -- 5272 VA 0 VA -- -- -- SPACE 3431 HPU-04 3#10+1#10 G IN 3/4"C 30 A 3 5272 VA 0 VA -- -- -- SPACE 3229 -- -- -- -- 5272 VA 0 VA 1 20 A SPARE 3027 -- -- -- -- 5272 VA 0 VA 1 20 A SPARE 2825 HPU-03 3#10+1#10 G IN 3/4"C 30 A 3 5272 VA 0 VA 1 20 A SPARE 2623 -- -- -- -- 2742 VA 5155 VA -- -- -- -- 2421 -- -- -- -- 2742 VA 5155 VA -- -- -- -- 2219 HPU-02 (MODULE 2) 3#12+1#12 G IN 3/4"C 20 A 3 2742 VA 5155 VA 3 25 A 2#12+1#12 G IN 3/4"C DAC-1 AIR CURTAIN 2017 -- -- -- -- 3740 VA 3300 VA 1 20 A 2#12+1#12 G IN 3/4"C EHUH-2 (ELECTRICAL 202) 1815 -- -- -- -- 3740 VA 7500 VA 1 35 A 2#8+1#10 G IN 3/4"C EHUH-1 (AC GARAGE 193) 1613 HPU-02 (MODULE 1) 3#10+1#10 G IN 3/4"C 25 A 3 3740 VA 7500 VA 1 35 A 2#8+1#10 G IN 3/4"C EHUH-1 (AC GARAGE 193) 1411 -- -- -- -- 5983 VA 2409 VA 1 15 A 2#12+1#12 G IN 3/4"C EWH-1 (TRAP STORAGE 194) 129 -- -- -- -- 5983 VA 2409 VA 1 15 A 2#12+1#12 G IN 3/4"C EWH-1 (TOILET 184) 107 HPU-01 (MODULE 2) 3#8+1#10 G IN 3/4"C 35 A 3 5983 VA 2409 VA 1 15 A 2#12+1#12 G IN 3/4"C EWH-1 (CORRIDOR 160) 85 -- -- -- -- 7730 VA 2409 VA 1 15 A 2#12+1#12 G IN 3/4"C EWH-1 (CORRIDOR 160) 63 -- -- -- -- 7730 VA 2409 VA 1 15 A 2#12+1#12 G IN 3/4"C EWH-1 (WORKSTATIONS 118) 41 HPU-01 (MODULE 1) 3#8+1#10 G IN 3/4"C 50 A 3 7730 VA 2409 VA 1 15 A 2#12+1#12 G IN 3/4"C EWH-1 (WORKSTATIONS 185) 2

CKT Circuit Description Wire Size Trip Poles A B C Poles Trip Wire Size Circuit Description CKT

Notes:

Enclosure: NEMA 1 Indoor MCB Rating: 250 AMounting: Surface Wires: 4 Mains Rating: 400 A

Supply From: HSB Phases: 3 Mains Type: CIRCUIT BREAKERLocation: Volts: 480/277 Wye A.I.C. Rating: 35,000

Branch Panel: MH1CORRIDOR 132 CORRIDOR 132

NO. DESCRIPTION DATE

Page 13: ELECTRICAL LEGEND

0.1

0.1

0.1

0.1

0.1

0.1

0.1

0.1

0.1

0.1

0.1

0.1

0.1

0.1

0.1

0.1

0.1

0.1

0.1

0.1

0.1

0.1

0.1

0.1

0.1

0.1

0.1

0.1

0.1

0.2

0.2

0.1

0.3

0.3

5.3

5.3

4.5 4.5 4.5

5.5

4.6

1.0

1.6

1.9

2.1

2.4

2.6

2.8

3.0

3.1

3.1

3.0

3.0

2.9

2.8

2.6

2.2

2.1

1.9

1.9

2.1

3.8

4.8

3.4

2.8

3.5

4.2

3.8

3.1

2.6

3.2

4.6

3.4

1.8

1.5

1.8

2.4

3.3

4.0

3.7

2.9

2.5

3.2

3.2

2.9

1.3

0.6

0.4

0.4

0.4

1.0

1.4

1.8

2.0

2.2

2.5

2.7

2.9

3.1

3.2

3.2

3.2

3.1

3.0

2.7

2.5

2.3

2.2

2.3

2.8

3.8

4.3

3.7

3.9

4.5

5.0

4.1

3.5

3.8

4.6

4.0

3.2

2.8

2.7

3.5

4.4

4.9

3.9

3.2

3.2

3.3

2.7

1.6

0.9

0.5

0.4

0.3

0.9

1.3

1.7

1.9

2.1

2.4

2.7

3.0

3.2

3.3

3.4

3.4

3.3

3.1

2.9

2.8

2.7

2.8

3.0

3.2

3.4

3.4

3.4

3.5

3.9

4.5

4.2

3.9

3.8

4.1

4.4

4.5

4.1

3.7

3.5

3.6

4.0

4.6

4.2

3.5

3.1

2.8

2.7

2.4

1.9

1.4

0.9

0.6

0.4

0.9

1.2

1.6

1.8

2.1

2.4

2.7

3.0

3.3

3.6

3.7

3.8

3.7

3.6

3.4

3.2

3.0

3.0

3.0

2.9

2.8

2.7

2.8

3.0

3.2

3.5

3.6

3.7

3.7

3.7

3.8

3.8

3.6

3.5

3.5

3.6

3.8

3.8

3.5

3.4

2.7

2.2

2.0

1.8

1.6

1.3

1.0

0.7

0.5

0.8

1.1

1.5

1.7

2.0

2.4

2.7

2.9

3.4

3.6

3.8

4.0

4.0

3.8

3.5

3.3

3.1

2.9

2.8

2.7

2.5

2.5

2.7

2.7

3.1

3.3

3.5

3.5

4.1

3.6

3.5

3.5

3.5

3.5

3.7

3.7

3.8

3.7

3.4

3.0

3.0

2.1

1.7

1.5

1.3

1.1

0.9

0.7

0.6

0.8

1.0

1.3

1.6

1.9

2.2

2.5

2.8

3.2

3.6

4.0

4.3

4.3

4.1

3.7

3.2

3.0

2.7

2.6

2.5

2.3

2.7

2.3

2.4

2.5

2.7

2.9

3.1

3.3

3.6

3.6

3.6

3.6

4.0

3.6

3.6

3.5

3.2

2.9

2.6

2.3

2.1

1.7

1.4

1.2

1.0

0.9

0.7

0.5

0.7

1.0

1.2

1.5

1.8

2.0

2.2

2.6

2.8

3.3

3.7

4.0

4.1

3.9

3.4

3.0

2.8

2.5

2.4

2.3

2.3

2.1

2.1

2.2

2.3

2.5

2.7

3.0

3.2

3.5

3.8

4.1

4.1

3.9

3.9

3.8

3.5

3.1

2.8

2.5

2.2

1.8

1.5

1.5

1.1

1.0

0.8

0.7

0.5

0.7

0.9

1.2

1.4

1.6

1.8

2.0

2.3

2.7

3.2

3.9

4.5

4.6

4.2

3.6

2.9

2.6

2.3

2.3

2.2

2.0

1.9

2.0

2.0

2.1

2.4

2.6

2.9

3.1

3.4

3.7

3.9

4.1

4.1

4.0

3.8

3.5

3.1

2.7

2.4

2.1

1.7

1.4

1.2

1.1

0.9

0.8

0.6

0.5

0.6

0.8

1.0

1.2

1.4

1.7

1.8

2.1

2.4

2.8

3.4

3.9

4.0

3.7

3.1

2.6

2.3

2.1

1.9

1.8

1.7

1.6

1.6

1.7

1.8

2.1

2.4

2.6

2.8

3.3

3.6

3.9

4.2

4.4

4.2

3.9

3.4

3.0

2.5

2.2

2.0

1.6

1.3

1.1

0.9

0.9

0.7

0.6

0.5

0.3

0.5

0.6

0.7

0.8

0.9

0.9

1.2

1.6

1.7

1.9

2.1

1.2

1.9

1.7

1.6

1.5

1.1

0.9

1.0

1.1

1.2

1.3

1.4

1.6

1.8

2.1

2.3

2.6

2.8

3.2

3.7

4.1

4.2

4.0

3.6

3.0

2.7

2.3

2.1

1.8

1.5

1.3

1.1

0.9

0.8

0.7

0.6

0.5

0.2

0.3

0.3

0.3

0.3

0.3

0.5

0.8

0.8

1.0

1.1

1.2

1.0

1.2

1.0

0.9

0.9

0.8

0.7

0.7

0.8

0.9

1.1

1.2

1.4

1.7

1.9

2.0

2.3

2.7

3.1

3.7

4.3

4.6

4.2

3.6

2.9

2.5

2.1

1.9

1.7

1.5

1.2

1.0

0.8

0.7

0.6

0.5

0.4

0.2

0.2

0.2

0.3

0.4

0.5

0.5

0.6

0.7

0.8

0.8

0.8

0.7

0.7

0.6

0.6

0.6

0.6

0.7

0.8

0.9

1.0

1.2

1.5

1.7

1.8

2.1

2.4

2.8

3.4

3.9

4.1

3.8

3.2

2.7

2.3

2.0

1.7

1.5

1.2

1.0

0.8

0.7

0.5

0.4

0.4

0.3

0.2

0.2

0.2

0.2

0.3

0.3

0.4

0.4

0.5

0.2

0.2

0.2

0.2

0.2

0.3

0.3

0.3

0.2

0.2

0.2

0.2

0.2

0.3

0.2

0.2

0.2

0.2 0.2

0.8

1.1

1.2

1.3

1.3

1.3

1.3

1.3

1.3

1.3

1.3

1.4

1.4

1.3

1.3

1.2

1.3

0.7

1.1

1.3

1.3

1.3

1.3

1.3

1.3

1.2

1.2

1.2

1.2

1.1

1.1

1.0

1.0

1.1

0.7

1.2

1.4

1.5

1.5

1.5

1.5

1.4

1.3

1.2

1.1

1.1

1.0

0.9

0.8

0.9

0.9

0.8

1.5

1.7

1.7

1.8

1.8

1.8

1.6

1.5

1.4

1.3

1.1

0.9

0.7

0.6

0.7

0.9

0.7

1.6

1.8

1.9

2.0

2.1

2.1

1.9

1.8

1.6

1.4

1.2

1.0

0.7

0.5

0.5

0.5

0.9

1.8

2.0

2.1

2.3

2.4

2.3

2.2

2.0

1.8

1.6

1.4

1.0

0.7

0.5

0.4

0.3

1.3

2.1

2.3

2.5

2.7

2.7

2.6

2.5

2.2

2.0

1.8

1.6

1.1

0.7

0.4

0.3

0.3

1.5

2.4

2.7

2.7

3.0

3.1

3.0

2.7

2.5

2.2

1.9

1.7

1.2

0.7

0.4

1.7

3.0

3.4

3.2

3.5

3.3

3.3

2.8

2.6

2.3

2.0

1.8

1.5

0.7

0.3

1.9

3.6

4.0

3.7

3.9

3.6

3.4

3.0

2.7

2.4

2.1

1.9

1.7

1.0

0.3

1.1

3.9

3.9

4.1

3.7

3.4

3.0

2.8

2.4

2.2

2.0

1.9

1.2

0.3

2.0

3.8

4.3

3.9

4.1

3.7

3.5

3.0

2.9

2.5

2.2

2.0

1.9

1.6

0.3

1.8

3.3

3.7

3.5

3.8

3.6

3.5

3.0

2.8

2.9

2.4

2.1

2.0

1.9

0.3

1.6

2.8

3.1

3.1

3.4

3.4

3.3

3.0

2.9

2.8

3.2

2.5

2.3

2.2

0.3

1.5

2.4

2.6

2.7

3.0

3.1

3.1

2.9

2.8

2.9

2.9

2.8

2.7

2.9

1.8

1.1

2.1

2.3

2.5

2.7

2.8

2.8

2.7

2.7

2.8

3.1

3.1

3.4

3.7

2.8

0.9

1.9

2.1

2.2

2.4

2.6

2.6

2.6

2.6

2.7

3.1

3.4

3.9

4.4

3.5

0.8

1.8

2.0

2.1

2.3

2.4

2.4

2.4

2.5

2.6

3.1

3.4

4.1

4.4

3.3

0.8

1.6

1.9

2.0

2.1

2.2

2.2

2.2

2.3

2.5

2.9

3.3

3.4

4.1

2.5

0.8

1.4

1.7

1.8

1.9

1.9

2.0

2.1

2.1

2.4

2.6

2.7

3.0

3.3

1.7

0.8

1.3

1.6

1.7

1.8

1.8

1.9

2.0

2.1

2.2

2.6

2.5

2.6

2.9

2.2

0.8

1.3

1.6

1.7

1.7

1.8

1.9

2.0

2.0

2.4

2.2

2.5

2.6

2.7

2.0

0.8

1.3

1.7

1.7

1.8

1.9

1.9

2.0

2.2

2.1

2.2

2.5

2.7

2.5

2.1

1.6

0.8

0.8

1.4

1.8

1.8

1.9

2.0

2.0

2.2

2.1

2.2

2.2

2.5

3.2

2.5

2.2

2.1

1.4

0.8

1.6

1.9

2.0

2.1

2.2

2.3

2.3

2.3

2.3

2.3

2.6

3.0

3.4

2.6

3.0

2.2

0.8

1.8

2.0

2.2

2.3

2.5

2.5

2.4

2.4

2.4

2.4

2.6

2.9

2.6

3.1

4.0

2.9

0.9

1.9

2.1

2.3

2.5

2.7

2.7

2.6

2.6

2.5

2.5

2.6

2.8

2.6

3.4

4.3

3.3

1.2

2.1

2.4

2.6

2.8

2.9

2.9

2.8

2.7

2.6

2.5

2.5

2.6

2.3

2.8

3.6

2.6

1.5

2.4

2.7

2.8

3.1

3.2

3.2

3.0

2.8

2.7

2.5

2.4

2.3

2.1

2.3

2.6

1.7

1.7

2.9

3.3

3.3

3.6

3.5

3.5

3.1

2.9

2.7

2.5

2.3

2.5

1.9

1.9

1.8

1.1

1.9

3.5

3.9

3.7

4.0

3.7

3.6

3.1

2.9

2.6

2.4

2.6

2.0

1.8

1.8

1.5

0.7

2.1

3.9

4.0

4.2

3.8

3.6

3.1

2.9

2.6

2.5

2.2

1.9

1.8

1.9

1.4

0.6

1.6

4.0

4.0

4.2

3.8

3.5

3.0

2.8

2.6

2.4

2.1

1.9

1.9

2.1

1.1

0.5

2.0

3.6

4.0

3.7

4.0

3.7

3.5

3.0

2.8

2.7

2.4

2.1

1.9

1.9

2.2

1.1

0.4

1.8

3.0

3.4

3.3

3.6

3.4

3.4

3.0

2.8

2.5

2.6

2.2

1.9

1.9

2.0

1.2

0.6

1.6

2.5

2.7

2.8

3.1

3.2

3.1

2.9

2.7

2.5

2.4

2.4

2.0

1.8

1.9

1.5

0.7

1.3

2.2

2.4

2.6

2.8

2.8

2.8

2.7

2.5

2.5

2.3

2.3

2.1

1.8

1.8

1.7

0.9

1.0

1.9

2.1

2.3

2.4

2.6

2.6

2.5

2.4

2.3

2.2

2.2

2.5

2.0

2.1

2.1

1.5

0.8

1.8

2.0

2.1

2.3

2.4

2.4

2.3

2.2

2.2

2.1

2.2

2.4

3.2

2.6

3.1

2.3

0.8

1.6

1.9

2.0

2.1

2.1

2.1

2.1

2.1

2.0

2.0

2.1

2.4

2.5

3.1

4.0

3.0

0.8

1.4

1.7

1.8

1.8

1.9

1.9

1.9

1.9

1.9

1.9

2.0

2.4

2.5

3.6

4.3

3.3

0.7

1.2

1.5

1.6

1.7

1.7

1.8

1.8

1.8

1.8

1.8

2.0

2.3

2.2

2.7

3.5

2.6

0.7

1.2

1.5

1.6

1.6

1.7

1.7

1.8

1.8

1.8

1.8

1.9

2.1

2.0

2.2

2.6

1.7

0.7

1.1

1.5

1.5

1.6

1.6

1.7

1.8

1.8

1.8

1.8

1.9

2.2

1.9

1.9

1.8

1.1

0.7

1.1

1.5

1.5

1.6

1.6

1.7

1.8

1.8

1.8

1.8

2.2

1.8

1.8

1.9

1.6

0.7

0.7

1.2

1.5

1.6

1.6

1.7

1.7

1.8

1.8

1.8

2.0

1.9

1.8

1.9

2.1

1.4

0.6

0.7

1.4

1.7

1.8

1.8

1.9

1.9

1.9

1.9

2.0

2.0

1.9

1.9

2.0

2.3

1.3

0.5

0.7

1.6

1.8

1.9

2.0

2.1

2.1

2.1

2.0

2.2

2.1

2.0

2.0

2.1

2.4

1.3

0.5

0.6

1.7

1.9

2.1

2.2

2.4

2.4

2.3

2.3

2.2

2.3

2.1

2.0

2.0

2.2

1.5

0.7

0.9

1.8

2.1

2.3

2.4

2.6

2.6

2.5

2.4

2.4

2.3

2.6

2.1

1.9

1.9

1.6

0.7

1.3

2.1

2.4

2.6

2.8

2.9

2.8

2.7

2.6

2.5

2.4

2.3

2.6

2.0

1.9

1.8

1.2

1.4

2.5

2.8

2.9

3.1

3.2

3.2

2.9

2.7

2.6

2.4

2.3

2.3

2.1

2.3

2.6

1.7

1.5

3.0

3.5

3.4

3.7

3.5

3.4

3.0

2.8

2.5

2.4

2.3

2.5

2.3

2.8

3.5

2.7

1.8

3.6

4.1

3.8

4.0

3.7

3.5

3.0

2.8

2.5

2.3

2.3

2.5

2.5

3.3

4.3

3.4

1.1

2.0

4.4

3.9

4.2

3.8

3.5

3.0

2.7

2.5

2.3

2.2

2.4

2.4

3.0

4.0

3.0

1.8

3.7

4.2

3.8

4.1

3.7

3.5

3.0

2.7

2.5

2.2

2.2

2.3

2.9

2.5

3.0

2.2

1.6

3.2

3.7

3.5

3.8

3.5

3.5

3.0

2.7

2.4

2.2

2.1

2.5

1.9

2.1

2.1

1.6

1.5

2.7

3.0

3.1

3.3

3.3

3.3

2.9

2.7

2.5

2.3

2.2

1.9

1.7

1.8

1.8

1.1

1.5

2.3

2.6

2.8

3.0

3.2

3.1

2.9

2.7

2.5

2.4

2.3

1.9

1.8

1.9

1.8

1.0

1.2

2.1

2.4

2.6

2.8

3.0

3.0

2.9

2.7

2.6

2.7

2.4

2.1

2.0

2.2

1.8

1.2

1.0

2.0

2.3

2.5

2.7

3.0

3.1

3.0

2.9

2.9

2.7

2.6

2.4

2.3

2.4

1.8

1.4

1.0

1.9

2.2

2.4

2.7

2.9

3.0

3.0

3.0

3.0

2.9

2.8

2.7

2.6

2.5

1.9

1.6

0.6

0.8

1.1

1.2

1.1

1.1

1.3

1.5

1.3

1.0

2.8

2.6

2.0

1.4

1.0

2.9

2.9

2.2

1.4

1.0

1.3

1.9

2.0

1.4

1.0

1.1

1.3

1.8

1.4

1.2

1.4

1.9

2.1

1.6

2.1

2.3

2.7

2.6

1.9

1.8

3.4

3.6

3.4

2.4

2.1

4.0

4.2

3.7

2.6

2.2

4.4

4.5

3.6

2.7

2.2

4.3

4.2

3.4

2.5

2.6

2.2

2.4

2.9

2.3

1.7

1.0

1.8

2.7

2.1

1.5

0.8

1.7

2.7

2.0

1.5

0.8

1.6

2.6

2.0

1.5

1.4

1.8

2.7

2.2

1.7

3.0

3.4

3.2

2.4

2.5

5.4

5.1

3.7

2.9

2.2

5.1

5.0

4.0

2.8

2.4

3.6

3.9

3.5

2.6

2.3

2.3

2.7

2.7

2.2

2.0

1.4

1.8

2.3

2.1

2.5

1.0

1.2

2.2

1.9

1.6

0.8

1.6

2.5

2.0

1.5

1.4

2.3

3.0

2.1

1.5

3.2

3.5

3.2

2.2

1.5

3.3

3.2

3.0

2.2

1.6

1.9

2.4

2.7

2.2

1.9

2.1

2.6

2.8

2.3

1.9

3.1

3.5

3.4

2.4

2.2

4.9

4.7

4.0

2.7

2.3

5.2

3.8

3.1

2.2

4.0

4.1

3.2

2.3

1.9

1.7

2.1

2.5

2.1

1.7

0.9

1.4

2.3

1.9

1.5

0.8

1.6

2.6

2.0

1.5

1.6

2.4

3.0

2.1

1.5

3.5

3.5

3.1

2.2

1.5

2.8

2.9

2.8

2.1

1.6

1.6

2.0

2.4

2.0

1.7

1.9

2.4

2.5

2.1

1.8

2.8

3.1

3.0

2.4

2.0

4.1

3.7

3.5

2.4

2.0

3.2

3.7

3.3

2.3

1.9

3.8

4.0

3.1

2.1

1.6

4.0

3.7

2.7

1.8

1.4

1.9

2.3

2.2

1.5

1.1

0.9

1.6

1.9

1.3

0.9

1.0

1.6

1.8

1.3

0.9

2.7

2.5

1.8

1.3

0.8

2.7

2.3

1.5

1.1

0.8

0.9

1.0

0.9

0.9

0.7

0.2

0.4

0.5

0.6

0.5

0.3

0.3

0.4

0.4

2.4

2.9

3.3

3.2

2.8

2.4

2.0

1.7

1.6

1.6

1.5

1.4

1.4

1.5

1.6

1.7

1.8

2.0

2.2

2.4

2.6

2.6

1.2

1.7

1.3

3.0

3.6

4.0

3.9

3.5

2.9

2.4

2.2

2.0

2.0

1.9

1.8

1.7

1.8

2.0

2.0

2.1

2.3

2.6

3.0

3.6

3.9

3.8

3.4

2.7

2.1

1.6

1.1

0.7

0.6

3.2

3.8

4.1

4.1

3.7

3.1

2.7

2.4

2.2

2.1

2.0

1.9

1.8

1.9

2.1

2.2

2.3

2.6

2.8

3.3

3.9

4.4

4.4

3.8

3.1

2.5

2.2

2.0

1.8

1.5

1.2

1.0

0.9

0.9

0.8

3.2

3.7

4.0

4.0

3.7

3.2

2.8

2.5

2.3

2.2

2.1

1.9

1.9

2.0

2.3

2.4

2.5

2.8

3.1

3.5

3.9

4.0

3.9

3.5

3.2

2.7

2.4

2.1

2.0

1.9

1.7

1.6

1.5

1.5

1.6

1.6

1.6

1.6

1.8

1.7

3.2

3.5

3.7

3.7

3.5

3.3

3.0

2.7

2.5

2.3

2.2

2.0

1.9

2.1

2.3

2.5

2.7

3.0

3.2

3.5

3.9

4.0

4.0

3.7

3.2

2.8

2.5

2.2

2.1

1.9

1.8

1.7

1.7

1.8

1.9

2.0

2.0

2.2

2.5

2.9

3.4

3.5

3.4

2.7

2.0

3.1

3.3

3.4

3.4

3.3

3.2

2.9

2.6

2.5

2.3

2.1

2.0

1.9

2.1

2.3

2.5

2.7

2.9

3.3

3.4

3.6

3.7

3.7

3.5

3.2

2.9

2.5

2.3

2.2

1.9

1.8

1.7

1.8

1.9

2.1

2.2

2.3

2.6

2.8

3.4

4.0

4.3

4.1

3.6

2.9

2.4

2.0

1.6

1.3

1.0

2.8

2.9

2.9

2.9

3.0

2.9

2.7

2.5

2.4

2.2

2.0

1.9

1.9

2.0

2.2

2.4

2.6

2.8

3.0

3.1

3.2

3.3

3.4

3.4

3.2

2.8

2.6

2.4

2.2

2.0

1.8

1.8

1.8

2.0

2.2

2.3

2.4

2.8

3.0

3.4

3.8

4.1

4.2

3.8

3.2

2.6

2.2

2.0

1.9

1.7

1.4

1.2

1.1

1.0

0.9

0.8

2.4

2.4

2.5

2.5

2.5

2.5

2.4

2.3

2.2

2.0

1.9

1.8

1.8

1.9

2.1

2.3

2.5

2.6

2.7

2.8

2.8

2.9

2.9

3.0

2.9

2.7

2.5

2.3

2.1

1.9

1.8

1.8

1.9

2.0

2.3

2.5

2.6

3.0

3.3

3.7

4.1

4.2

4.1

3.6

3.1

2.7

2.5

2.2

2.1

1.9

1.8

1.7

1.6

1.6

1.6

1.7

1.7

1.6

1.7

1.8

1.8

2.1

2.1

2.1

2.2

2.2

2.2

2.2

2.1

2.0

1.9

1.8

1.7

1.7

1.8

2.0

2.2

2.4

2.5

2.5

2.5

2.6

2.7

2.7

2.7

2.6

2.5

2.4

2.2

2.0

1.9

1.8

1.8

1.9

2.1

2.3

2.5

2.7

3.0

3.3

3.6

3.8

3.9

3.9

3.7

3.2

2.9

2.5

2.3

2.2

2.0

1.8

1.8

1.8

1.8

1.9

2.0

2.0

2.1

2.4

2.7

3.1

3.5

1.9

3.0

2.3

1.7

1.7

1.8

1.8

1.8

1.9

1.9

1.9

1.9

1.8

1.7

1.6

1.5

1.6

1.7

1.9

2.1

2.2

2.2

2.2

2.3

2.3

2.4

2.5

2.5

2.5

2.4

2.2

2.1

1.9

1.8

1.7

1.7

1.8

2.0

2.2

2.4

2.7

2.9

3.3

3.5

3.6

3.7

3.6

3.4

3.3

2.9

2.7

2.5

2.3

2.1

1.9

1.8

1.8

1.9

2.0

2.1

2.2

2.4

2.7

3.0

3.6

4.2

4.2

3.8

3.2

2.5

2.1

1.6

1.3

1.0

0.7

1.4

1.4

1.4

1.5

1.5

1.5

1.6

1.6

1.5

1.5

1.4

1.3

1.4

1.5

1.7

1.9

2.0

2.0

2.0

2.0

2.1

2.1

2.2

2.3

2.3

2.2

2.1

1.9

1.8

1.7

1.6

1.7

1.8

2.0

2.2

2.3

2.6

2.8

2.9

3.0

3.1

3.2

3.3

3.3

3.1

2.8

2.7

2.6

2.3

2.1

1.9

1.9

1.9

2.0

2.1

2.3

2.4

2.6

2.8

3.2

3.5

3.8

4.1

4.0

3.4

2.7

2.2

1.9

1.6

1.5

1.1

1.1

1.0

1.0

1.1

1.1

1.2

1.2

1.2

1.2

1.2

1.1

1.1

1.1

1.2

1.4

1.6

1.7

1.7

1.7

1.7

1.8

1.9

1.9

2.0

2.0

2.0

1.9

1.8

1.6

1.6

1.6

1.6

1.7

1.9

2.1

2.3

2.4

2.6

2.7

2.8

2.9

3.0

3.0

3.0

2.9

2.7

2.7

2.5

2.3

2.1

2.0

2.0

2.0

2.1

2.3

2.4

2.6

2.8

3.1

3.5

3.9

4.1

4.1

3.8

3.2

2.6

2.4

2.0

1.7

1.5

1.2

0.7

0.7

0.7

0.7

0.7

0.7

0.8

0.8

0.8

0.8

0.8

0.8

0.8

1.0

1.2

1.4

1.4

1.4

1.4

1.5

1.5

1.6

1.6

1.7

1.8

1.7

1.7

1.6

1.5

1.5

1.5

1.6

1.7

1.8

2.0

2.2

2.3

2.4

2.5

2.6

2.7

2.8

2.8

2.9

2.8

2.8

2.6

2.5

2.3

2.2

2.1

2.1

2.1

2.1

2.3

2.5

2.7

2.9

3.2

3.4

3.6

3.8

3.8

3.6

3.3

2.8

2.4

2.0

1.8

1.5

1.2

1.4

1.5

1.6

1.9

1.9

2.1

2.2

2.3

2.4

2.4

2.5

2.6

2.7

2.8

2.9

2.9

2.6

2.5

2.3

2.2

2.2

2.1

2.1

2.2

2.3

2.5

2.8

2.8

3.1

3.3

3.4

3.5

3.5

3.3

3.1

2.8

2.4

2.1

1.8

1.5

1.2

1.3

1.4

1.6

2.1

1.9

2.1

2.2

2.3

2.4

2.5

2.6

2.8

2.6

2.6

2.6

2.9

2.6

2.5

2.4

2.4

2.3

2.3

2.4

2.6

2.5

2.6

2.7

2.8

2.9

2.9

2.9

3.0

3.0

2.9

2.6

2.3

2.1

1.8

1.5

1.1

1.1

1.2

1.3

1.5

1.8

2.1

2.4

2.6

2.7

2.7

3.2

2.5

2.5

2.5

2.5

2.6

2.7

2.7

2.9

2.9

2.9

2.7

3.1

2.5

2.4

2.5

2.6

2.7

2.7

2.7

2.6

2.6

2.6

2.5

2.3

2.1

1.9

1.6

1.3

1.0

1.1

1.2

1.3

1.4

1.7

2.0

2.4

2.6

2.6

2.5

2.4

2.4

2.5

2.6

2.7

2.7

2.7

2.8

3.3

3.1

3.0

2.9

2.6

2.5

2.5

2.5

2.6

2.5

2.4

2.3

2.3

2.3

2.3

2.2

2.1

1.9

1.7

1.5

1.2

0.9

1.2

1.4

1.5

1.6

1.8

2.3

2.8

3.4

3.1

2.6

2.4

2.4

2.7

2.9

2.9

2.7

2.6

2.9

3.3

3.8

3.7

3.2

2.9

2.6

2.6

2.6

2.5

2.3

2.0

1.9

1.9

1.9

2.0

2.0

1.9

1.7

1.5

1.3

1.1

0.4

0.5

0.8

1.2

1.4

1.6

2.5

3.4

4.2

3.9

2.9

2.0

1.6

1.7

1.7

1.8

1.8

1.9

2.8

3.7

4.4

3.4

2.6

2.2

2.1

1.9

1.6

1.4

1.4

1.5

1.6

1.7

1.7

1.7

1.7

1.6

1.4

1.2

1.0

0.4

0.5

0.7

1.1

1.7

2.6

3.3

2.9

2.2

1.4

1.0

0.8

0.8

0.8

0.9

1.3

1.9

2.8

3.6

3.3

2.6

1.8

1.4

1.1

1.0

1.0

1.0

1.1

1.3

1.4

1.4

1.4

1.5

1.5

1.4

1.2

1.0

Statistics

Description Symbol Avg Max Min Max/Min Avg/Min

Driving Area 2.3 fc 4.6 fc 0.3 fc 15.3:1 7.7:1Parking One 2.2 fc 4.5 fc 0.2 fc 22.5:1 11.0:1Parking Two 2.2 fc 5.3 fc 0.1 fc 53.0:1 22.0:1Rear Biulding 2.2 fc 5.5 fc 0.1 fc 55.0:1 22.0:1

SHEET NUMBER:

DRAWING TITLE:

DATE ISSUED:

PROJECT NUMBER:

PROJECT SET:

I HEREBY CERTIFY THAT THESE DOCUMENTS WERE PREPARED OR APPROVED BY ME, AND THAT I AM A

DULY LICENSED PROFESSIONAL ENGINEER UNDER THE LAWS OF THE

STATE OF MARYLAND. LICENSE NUMBER: #xxxxx

EXPIRATION DATE: mm-dd-yyyy

CO

NSU

LTAN

T:SE

AL

ALL DRAWINGS ARE PROTECTED BY FEDERAL COPYRIGHT BY MANNS WOODWARD STUDIOS, INC. AND CAN NOT BE REPRODUCED OR MODIFIED IN ANY MANNER WITHOUT WRITTEN PERMISSION. DOCUMENTS MAY NOT BE USED IN PART OR WHOLE TO DEVELOP THE DESIGN OF ANOTHER BUILDING WITHOUT EXPRESS WRITTEN PERMISSION BY MANNS WOODWARD STUDIOS.

(P) 410-344-1460(F) 443-403-2460(E) [email protected]

S T U D I O S10839-D PHILADELPHIA RDWHITE MARSH, MD 21162

ARCHITECTURE + MASTER PLANNING

Eng

inee

ring

Infra

stru

ctur

e S

olut

ions

C.C

. Joh

nson

& M

alho

tra,

P.C

.

400

Eas

t Pra

tt S

treet

, Sui

te 6

04B

altim

ore,

MD

212

02(P

) 410

-461

-992

0 | (

F) (

667)

239-

3534

| (E

) BA

LTIM

OR

E@

CC

JM.C

OM

CC

JM

3/15

/201

9 6:

04:5

4 PM

E700

BALT

IMO

RE C

ITY

ANIM

AL S

ERVI

CES

BUIL

DING

2490

GIL

ES R

OAD

, BAL

TIM

ORE

, 212

25

ELECTRICAL - SITEPHOTOMETRICS PLAN

03-15-2019

17-023

100% CD

NO. DESCRIPTION DATE

ELECTRICAL - SITE LIGHTING PHOTOMETRICS PLANSCALE: NONE

1

Page 14: ELECTRICAL LEGEND

20.7

27.6 34.2

32.3

30.2

24.2

36.9

29.3

33.2 57.8 55.7

15.3

40.9

0.0 0.0 0.0 0.0 0.0

46.8 55.5

49.1

37.6

59.3

51.4

28.9

34.8

29.7 29.7

32.8 32.8

38.5

59.5

59.5

48.0

15.2

15.1

48.0

59.4

57.8 58.2 58.2

58.8

79.5

47.2

60.4

75.2

56.8

56.8

102.8 101.9

29.3

29.3

29.3

51.4

51.4

42.9

42.9

82.0

134.3

134.3

79.4

70.6

117.8

108.5

56.8

57.7

56.6

58.0

48.6

59.7

59.7

130.3

23.8

29.4 29.4

106.2

21.3

28.1

36.6

44.9

49.6

48.9

45.8

44.3

46.6

51.7

55.3

55.1

51.6

49.8

51.3

51.8

54.0

52.1

48.0

45.4

46.7

49.8

50.5

46.1

38.2

29.9

21.4

28.6

37.6

46.4

51.3

50.6

47.2

45.6

47.9

52.8

57.8

55.8

54.0

53.3

53.7

56.2

54.3

49.8

47.0

48.4

51.9

52.6

48.1

39.5

30.8

26.5

33.8

40.9

44.9

44.7

42.3

41.2

43.3

46.7

50.6

57.9

56.0

54.8

45.5

48.7

50.7

49.0

45.5

43.5

44.5

46.8

47.2

43.5

36.5

29.4

37.0

49.6

50.6

42.8

36.8

49.7

47.1

41.4

52.4

52.2

45.6

51.3

53.6

47.3

48.4

50.4

45.5

44.8

46.0

42.8

44.1

44.7

41.5

47.4

47.8

43.4

51.9

52.1

46.6

52.8

53.1

47.3

50.5

50.7

45.5

46.4

46.6

42.7

45.1

45.3

41.3

47.7

47.8

41.9

52.1

52.3

52.9

53.0

44.0

49.8

49.8

43.9

45.4

45.5

41.1

43.6

43.6

39.8

45.8

45.8

33.9

48.9

48.9

37.8

48.3

48.2

41.6

42.8

42.7

37.9

34.0

33.8

30.9

25.9

25.6

23.4

27.7

28.6

35.5

37.3

35.0

43.6

46.4

42.8

48.9

52.2

47.8

49.3

52.8

48.3

47.1

49.4

46.3

44.7

47.2

44.1

46.0

48.7

45.4

49.7

52.9

48.7

51.8

55.2

50.7

49.9

53.1

48.9

45.5

48.0

44.8

40.7

42.7

40.3

40.4

42.3

40.0

43.7

46.0

43.1

49.1

52.2

48.2

52.6

56.1

51.6

52.1

55.5

51.1

48.8

51.7

48.1

46.6

49.2

46.0

48.0

50.7

47.4

51.7

55.0

50.8

54.1

53.1

52.9

56.3

51.9

48.4

51.3

47.8

46.2

48.7

45.7

47.0

49.8

46.5

51.2

54.7

50.6

53.2

57.0

52.5

52.5

56.1

51.8

47.9

50.8

47.4

45.4

48.0

45.0

45.8

48.6

45.3

49.0

52.3

48.3

49.7

53.3

49.1

46.2

49.4

45.5

38.8

40.8

38.4

30.7

32.0

30.6

44.8

47.8

44.3

50.3

53.7

49.6

51.8

55.1

50.9

49.3

52.1

48.5

46.5

48.8

46.0

47.1

49.4

46.5

50.6

53.3

49.7

54.5

57.9

53.5

54.0

57.3

53.0

50.6

53.4

49.9

48.3

50.6

47.7

48.0

50.8

47.4

51.6

54.4

50.8

54.2

57.4

53.2

54.7

58.1

53.7

51.2

54.0

50.4

48.2

50.5

47.6

47.2

49.5

46.7

50.5

53.3

49.8

54.9

53.9

54.7

58.1

53.7

51.3

54.1

50.5

48.3

50.7

47.8

48.5

50.8

47.9

51.8

54.6

51.0

54.9

53.9

54.7

58.0

53.6

51.3

54.1

50.5

47.5

49.8

46.9

48.1

49.6

47.4

50.6

53.3

49.8

54.5

57.8

53.5

53.8

57.0

52.7

50.7

53.5

49.9

46.8

49.1

46.3

46.4

48.6

45.8

48.8

51.5

48.0

51.0

54.2

49.9

49.4

52.2

48.4

42.6

45.0

42.0

34.5

35.9

45.9

49.5

45.8

50.6

54.8

50.5

51.6

55.2

51.5

49.1

52.2

48.8

46.7

49.2

46.3

47.7

50.1

47.0

51.3

54.4

50.5

54.4

57.9

53.5

54.3

57.8

53.4

50.4

53.3

49.6

47.8

50.2

47.1

48.5

50.9

47.8

52.2

54.6

51.5

55.1

54.5

53.9

57.5

53.2

50.4

53.4

49.8

47.5

49.9

47.0

48.1

50.6

47.6

51.6

54.7

51.0

54.6

58.3

54.0

54.1

57.7

53.6

50.7

53.7

50.2

47.7

50.3

47.2

48.3

50.9

47.8

51.9

54.9

51.4

54.7

58.4

54.2

54.2

57.8

53.7

50.8

53.9

50.2

48.0

50.4

47.5

48.4

50.9

47.8

51.5

55.0

51.1

54.5

58.3

54.1

53.9

57.6

53.5

50.3

53.3

49.9

47.4

49.9

47.0

47.9

50.5

47.5

51.3

54.5

51.0

54.0

57.9

53.8

53.5

57.3

53.3

50.0

53.0

49.6

47.7

49.9

47.3

47.9

50.5

47.5

51.4

54.6

50.9

53.8

57.6

53.3

53.1

56.8

52.7

49.5

52.5

49.0

46.3

48.8

45.8

46.3

48.8

45.8

48.6

51.7

48.1

50.5

54.1

50.0

47.6

50.9

47.1

40.7

43.1

40.4

32.7

33.7 31.4

30.5

37.6

40.3

38.6

44.8

48.8

46.4

48.7

53.5

50.8

48.8

53.2

50.7

46.1

49.7

47.6

45.3

48.5

46.6

46.9

51.1

48.9

50.6

55.1

52.4

53.1

58.0

55.2

51.3

55.9

53.2

47.5

51.0

48.9

45.6

48.7

46.8

48.5

52.2

50.0

51.9

56.6

53.9

52.4

57.2

54.4

51.5

56.1

53.4

47.6

51.2

49.0

46.4

49.6

47.6

48.3

51.9

49.7

51.8

56.5

53.7

52.1

56.8

54.1

50.5

54.8

52.2

47.3

50.8

50.2

46.9

54.0

53.5

45.0

53.2

64.8

67.2

69.5

66.1

58.7

49.4

60.4

69.4

72.2

78.7

73.1

63.7

47.8

58.1

67.9

73.3

74.5

65.3

52.7

68.5

62.0

48.7

53.2

53.8

46.3

49.5

48.1

48.5

52.1

49.8

52.1

56.7

53.9

53.8

58.7

55.7

51.7

56.2

53.5

48.4

52.0

49.8

47.0

50.2

48.2

48.4

52.0

49.8

52.3

56.9

54.1

52.7

57.4

54.6

51.7

56.2

53.5

48.2

51.7

49.5

46.2

49.4

47.4

47.9

51.5

49.2

51.8

56.4

53.6

53.2

58.3

55.3

51.1

54.9

52.2

46.6

50.0

47.9

45.1

48.0

46.1

46.3

49.8

47.6

49.1

53.5

50.8

49.4

54.1

51.3

42.8

48.6

51.6

50.1

47.0

46.1

49.1

52.9

54.2

51.9

48.4

47.0

50.0

53.1

54.9

51.9

48.8

46.9

49.2

52.9

54.2

51.8

48.1

46.6

48.3

50.9

49.9

45.1

37.3

45.4

50.2

47.6

45.6

52.2

55.1

53.4

49.6

48.8

52.0

56.5

58.1

55.4

51.1

49.5

52.9

56.7

58.7

55.3

51.5

49.4

52.1

56.5

57.9

55.3

50.9

49.2

51.3

54.4

53.5

48.1

39.2

39.1

42.2

40.4

42.8

48.6

51.6

50.0

47.0

46.1

49.0

52.8

54.2

51.9

48.4

47.0

49.9

53.0

54.8

51.9

48.7

46.9

49.2

52.9

54.2

51.7

48.1

46.6

48.3

50.7

49.9

45.0

37.2

29.2

32.2

33.3

33.0

32.4

32.6

34.0

35.6

35.7

34.3

33.5

33.6

34.4

35.6

35.6

34.4

33.6

33.5

34.2

35.3

35.2

33.8

32.4

32.4

32.9

33.2

31.7

28.5

24.3

32.3

35.9

37.0

36.7

35.9

36.2

37.9

39.5

39.6

38.2

36.9

37.0

38.4

39.7

39.8

38.3

36.9

36.8

38.1

39.5

39.3

37.7

36.0

35.5

36.1

36.6

34.9

31.0

26.2

34.2

38.1

39.4

39.0

38.1

38.5

40.2

41.8

42.0

40.6

39.4

39.1

40.6

42.1

42.2

40.9

39.3

39.2

40.4

41.8

41.9

40.2

38.3

37.7

38.4

38.9

36.9

32.8

27.5

35.3

39.5

40.9

40.6

39.8

40.3

42.0

43.5

43.7

42.3

41.0

41.1

42.3

43.8

44.0

42.4

41.0

41.0

42.3

43.7

43.5

41.8

39.7

39.4

40.0

40.3

38.2

34.0

28.5

36.2

40.5

42.0

41.7

40.9

41.3

43.1

45.0

45.1

43.5

42.0

42.3

43.8

45.3

45.4

43.8

42.0

42.2

43.6

45.0

44.8

43.0

41.0

40.6

41.2

41.4

39.3

34.9

29.2

36.9

41.3

42.8

42.4

41.7

42.1

44.0

45.9

46.0

44.5

43.1

43.1

44.7

46.2

46.3

44.7

43.1

43.0

44.4

45.8

45.7

43.8

41.8

41.2

41.8

42.1

39.9

35.5

29.7

37.1

41.6

43.1

42.8

42.2

42.6

44.5

46.2

46.3

44.9

43.4

43.4

44.9

46.5

46.6

45.0

43.5

43.3

44.7

46.2

45.9

44.1

42.1

41.5

42.0

42.5

40.1

35.6

29.9

37.2

41.6

43.1

42.9

42.2

42.7

44.5

46.2

46.5

45.1

43.7

43.7

45.2

46.8

46.8

45.3

43.4

43.6

45.0

46.4

46.2

44.4

42.4

41.9

42.4

42.5

40.3

35.8

29.9

37.5

41.9

43.6

43.4

42.7

43.2

45.0

46.6

46.8

45.3

43.8

43.8

45.3

46.9

47.0

45.4

43.8

43.7

45.0

46.5

46.5

44.7

42.6

42.1

42.6

42.7

40.6

36.0

30.2

37.6

42.1

43.8

43.5

42.8

43.3

45.1

46.8

47.0

45.5

44.0

44.0

45.5

47.1

45.6

44.0

43.8

45.2

46.7

46.5

44.7

42.6

41.9

42.5

42.8

40.7

36.1

30.2

37.5

42.0

43.6

43.4

42.7

43.2

45.1

46.6

46.8

45.3

43.9

43.9

45.4

47.0

47.0

45.5

44.0

44.0

45.4

46.8

46.5

44.7

42.5

42.1

42.6

42.8

40.6

36.1

30.2

37.3

41.7

43.2

43.0

42.2

42.8

44.6

46.2

46.6

45.1

43.6

43.6

45.1

46.8

46.8

45.3

43.8

43.7

45.0

46.4

46.2

44.4

42.4

41.8

42.3

42.4

40.4

35.9

30.1

37.2

41.6

43.2

42.9

42.5

42.7

44.6

46.4

46.5

45.0

43.6

43.6

45.1

46.6

46.7

45.1

43.6

43.5

44.9

46.3

46.0

44.2

42.2

41.6

42.1

42.3

40.3

35.7

30.0

36.9

41.3

42.9

42.8

41.8

42.3

44.2

45.8

46.1

44.6

43.0

43.0

44.6

46.3

46.3

44.7

42.9

43.1

44.5

45.9

45.7

43.9

41.9

41.3

41.9

42.1

40.0

35.5

29.7

36.3

40.6

42.2

41.9

41.1

41.6

43.4

45.0

45.1

43.7

42.3

42.4

43.7

45.3

45.4

43.8

42.3

42.2

43.6

45.1

44.9

43.1

41.1

40.5

41.1

41.4

39.4

34.9

29.3

35.4

39.5

41.0

40.7

39.9

40.4

42.1

43.8

43.8

42.5

41.0

41.1

42.6

43.9

44.1

42.4

40.8

40.7

42.4

43.8

43.5

41.8

39.9

39.4

39.9

40.2

38.3

34.0

28.5

34.2

38.2

39.6

39.2

38.4

38.8

40.5

42.1

42.3

40.9

39.5

39.4

40.9

42.2

42.3

40.8

39.2

39.1

40.4

41.8

41.8

40.1

38.2

37.6

38.4

38.8

37.1

33.0

27.7

32.3

36.0

37.6

37.1

36.3

36.7

38.0

39.5

39.7

38.1

36.7

36.7

38.4

39.9

39.9

38.5

36.6

36.9

38.2

39.6

39.4

37.8

36.0

35.6

36.2

36.6

35.0

31.2

26.2

29.4

32.5

33.9

33.6

32.9

33.2

34.4

35.7

35.8

34.8

33.6

33.6

34.8

35.7

35.7

34.6

33.4

33.2

34.3

35.4

35.3

34.0

32.5

32.0

32.5

32.8

31.8

28.6

37.3

42.7

45.0

42.6

43.0

50.7

54.1

50.9

43.2

46.6

55.9

60.1

56.3

47.1

46.8

56.2

56.5

47.3

43.4

51.3

54.8

51.5

43.7

37.9

43.5

45.9

43.4

37.5

56.4

61.0

62.3

57.1

50.7

49.5

47.4

45.7

45.5

47.0

49.4

50.6

49.2

47.8

47.0

48.1

50.1

51.1

50.1

48.2

47.0

47.7

49.4

50.1

48.8

46.5

45.2

45.4

46.2

45.5

42.0

36.4

60.7

63.0

68.4

63.7

55.9

53.9

51.1

49.5

49.3

50.6

53.3

55.1

54.0

51.9

50.5

52.2

54.6

54.9

53.8

51.6

50.5

51.6

54.1

55.0

53.5

51.0

49.4

49.6

50.5

49.7

45.5

39.3

62.7

71.1

69.7

63.3

58.1

56.9

54.2

51.7

51.5

53.6

56.2

57.6

56.3

54.1

53.1

54.6

56.9

58.5

57.3

55.0

53.8

55.0

57.0

57.9

56.4

53.6

51.7

51.9

52.9

52.4

48.0

41.3

63.9

72.5

70.9

63.1

59.0

58.4

55.6

53.1

52.9

54.8

57.7

59.1

58.3

56.1

54.7

56.0

58.9

59.7

58.6

56.2

55.1

56.1

58.6

59.5

58.0

55.2

53.6

53.8

54.7

53.7

49.2

42.3

64.2

72.0

72.2

67.0

60.6

59.2

56.2

54.2

54.1

56.0

59.0

60.5

59.2

56.9

55.9

57.5

59.8

61.3

60.1

57.7

56.5

57.6

59.5

60.4

58.8

55.9

54.3

54.9

55.8

54.8

49.6

42.6

64.1

67.1

73.6

69.3

60.9

59.2

56.3

54.3

54.2

56.1

59.0

60.5

59.2

57.0

56.0

57.3

59.9

60.9

60.1

57.7

56.2

57.9

59.7

60.6

59.1

56.4

54.8

54.4

55.3

54.7

50.1

42.7

65.4

74.3

72.9

66.3

60.2

58.6

55.9

54.0

53.8

55.8

58.7

60.1

58.9

56.7

55.6

57.0

59.4

60.6

59.4

57.0

55.8

56.9

58.6

59.5

57.9

55.1

53.6

53.6

54.6

53.5

49.1

42.5

66.3

73.1

64.1

58.7

57.2

54.3

52.3

52.2

54.1

56.9

58.3

57.2

54.9

53.9

55.2

57.6

58.8

57.6

55.3

54.1

55.2

57.1

57.9

56.2

53.5

51.9

52.3

53.3

52.3

48.0

41.1

64.1

71.7

71.1

64.6

57.3

54.7

51.9

49.9

49.7

51.5

54.3

55.7

54.5

52.4

51.4

52.7

55.0

56.2

55.0

52.7

51.6

52.7

54.5

55.4

53.9

51.2

49.7

50.0

51.1

50.3

46.1

39.7

62.3

64.5

69.7

63.8

53.9

50.6

48.0

46.2

46.0

47.7

50.1

51.4

50.4

48.5

47.6

48.7

50.9

51.6

50.5

48.5

47.5

48.8

50.4

51.2

49.8

47.2

46.0

46.0

47.1

46.4

42.8

36.9

62.2

69.7

66.1

57.0

46.1

44.0

42.3

40.9

40.8

42.2

44.2

45.2

44.5

43.0

42.3

43.2

44.9

45.4

44.6

43.0

42.2

43.3

44.5

45.1

44.0

42.0

40.7

41.1

41.7

41.1

38.1

33.3

61.7

68.4

63.5

38.7

36.7

36.6

35.6

35.1

35.3

36.3

37.5

38.2

37.9

37.0

36.6

37.2

38.2

38.7

38.2

37.3

36.8

37.2

38.1

38.4

37.7

36.4

35.5

35.2

35.4

34.6

32.3

57.8

62.2

51.2

52.6

49.2

47.2

45.4

47.3

40.6

41.6

47.4

50.5

50.4

47.2

41.4

34.0

47.0

53.3

52.9

45.8

36.9

46.3

52.6

56.0

55.9

52.1

45.2

36.6

40.1

45.7

48.6

48.5

45.5

40.0

67.8

75.8

80.0

80.1

75.8

68.0

58.2

80.7

90.3

95.8

95.7

89.9

79.1

65.9

86.0

96.7

102.6

96.1

84.0

69.1

81.3

90.9

96.5

96.3

90.4

79.3

65.7

68.6

76.7

81.0

80.9

76.4

68.3

68.8

75.9

79.7

79.2

74.4

66.0

80.4

90.2

95.3

94.7

88.2

76.9

63.3

85.3

96.3

101.3

94.2

81.6

66.8

80.5

90.3

95.3

94.7

88.3

77.1

63.8

68.9

75.9

79.7

79.2

74.4

66.3

56.5

15.5

17.9

19.9

21.4

22.3

22.9

23.2

23.2

23.0

22.5

21.6

20.1

18.4

17.0

20.1

22.7

24.4

25.7

26.3

26.7

26.8

26.4

25.7

24.6

23.1

20.7

17.9

21.2

24.1

26.2

27.6

28.4

28.7

28.7

28.5

27.7

26.5

24.6

22.0

18.2

21.5

24.6

26.8

28.1

29.0

29.0

28.3

27.0

25.0

22.3

18.1

21.6

24.6

26.7

28.0

28.9

29.2

29.0

28.3

27.0

25.0

22.3

17.8

21.2

24.1

26.1

27.4

28.2

28.6

28.7

28.3

27.7

26.5

24.6

22.0

16.8

19.8

22.4

24.3

25.4

26.1

26.5

26.5

26.3

25.7

24.6

23.0

20.6

17.6

19.6

21.0

22.1

22.7

22.9

23.0

22.8

22.3

21.5

20.1

18.4

45.4

51.0

46.3

46.3

51.0

45.3

45.2

50.9

51.2

46.1

46.2

51.3

50.9

45.1

41.0

45.2

45.5

41.6

41.7

45.6

45.3

34.7

36.4

34.8

35.0

36.5

34.5

38.4

40.8

38.7

38.9

40.8

38.2

40.2

40.5

40.8

40.0

38.9

41.4

39.1

39.4

41.3

38.6

35.4

37.3

35.5

35.7

37.2

35.2

51.7

57.2

59.7

61.8

63.3

64.0

63.2

61.8

60.1

57.1

51.0

59.0

66.1

69.7

71.4

73.4

74.4

73.3

71.5

69.6

65.9

58.5

63.4

71.5

75.5

77.6

79.7

80.3

79.6

77.6

75.4

71.3

62.4

63.8

71.9

75.9

78.8

80.9

80.4

78.2

76.0

72.2

63.2

62.5

70.3

73.8

76.5

78.5

79.0

78.4

76.4

74.2

69.3

61.3

59.4

66.1

70.0

71.6

73.9

74.8

73.7

71.3

69.2

65.3

58.0

54.2

60.6

63.3

65.4

66.5

67.9

66.3

64.5

62.7

59.3

53.3

48.1

52.9

55.4

56.5

58.2

58.8

57.6

56.7

54.8

51.8

61.9

65.0

66.3

64.4

59.7

74.4

78.8

80.1

77.3

70.9

83.4

90.6

92.9

89.8

80.8

89.6

100.6

104.9

102.4

89.9

101.6

116.6

117.5

115.4

109.3

71.6

83.0

92.3

98.8

103.1

105.9

107.6

108.6

109.6

112.8

124.5

125.7

125.7

124.2

121.5

117.8

104.3

99.8

95.5

88.8

79.7

68.1

56.1

77.1

90.6

101.7

109.2

114.3

117.4

119.3

121.1

122.8

127.0

131.7

132.2

131.7

130.6

128.9

125.7

118.1

112.5

106.5

98.3

86.9

73.3

59.4

80.0

94.3

106.3

114.3

119.9

123.3

125.6

127.4

128.8

132.2

134.0

132.2

131.5

128.9

124.9

118.2

112.0

103.0

90.8

76.1

61.0

79.5

93.7

105.7

113.6

119.3

122.7

124.9

126.4

128.1

130.0

131.4

130.9

130.7

129.1

128.6

126.3

123.4

117.9

111.5

102.6

90.6

75.9

60.9

76.0

89.0

99.8

107.0

112.2

115.3

117.3

118.7

120.2

122.0

122.0

121.9

121.4

120.9

119.9

117.8

115.3

111.0

105.2

96.8

86.0

72.6

58.8

69.8

80.5

89.1

95.4

99.8

102.4

104.1

105.6

107.2

107.8

107.9

107.8

107.3

106.8

106.1

104.4

102.1

98.8

93.9

86.9

77.9

67.2

56.5

60.8

60.8

56.3

56.8

67.3

73.7

73.4

66.6

60.2

72.2

79.1

71.4

57.3

68.0

74.5

74.3

67.5

49.8

57.6

62.1

62.0

57.4

40.1

40.4

38.1

45.9

50.7

51.3

47.1

53.7

60.6

61.5

55.5

58.8

67.2

68.3

61.0

60.6

69.5

62.9

59.2

67.5

68.5

61.3

54.2

61.3

62.1

55.9

46.6

51.5

52.0

47.7

38.1

40.7

41.0

38.6

68.3

75.4

80.9

84.5

86.4

87.1

86.8

85.3

82.1

77.6

70.9

62.5

66.7

78.3

87.6

94.6

99.0

101.4

102.2

101.8

100.1

96.3

90.5

81.8

70.8

71.8

85.5

96.7

104.5

109.8

112.3

113.2

112.7

110.8

106.6

99.8

89.6

76.7

74.1

88.7

100.4

108.7

114.4

116.9

117.3

115.2

110.8

103.7

92.8

79.1

73.1

87.7

98.8

107.1

112.0

114.8

115.8

115.2

113.5

109.0

102.0

91.4

77.9

69.0

81.6

91.8

99.1

103.8

106.1

107.0

106.5

104.6

100.8

94.4

85.1

72.9

62.5

72.8

80.7

86.6

90.3

92.4

93.1

92.8

91.2

87.9

82.7

75.2

65.7

63.1

68.1

71.8

74.4

76.0

77.0

77.4

77.2

76.5

75.5

73.7

70.5

66.0

59.9

52.1

73.3

79.8

84.4

87.6

89.6

90.8

91.2

91.0

90.1

89.1

86.9

82.9

77.1

69.0

58.6

80.7

88.6

93.9

97.5

99.8

101.1

101.6

101.3

100.5

99.3

96.9

92.3

85.4

75.9

63.7

84.4

92.9

98.8

102.7

105.1

106.5

107.1

106.8

105.9

104.6

101.9

96.9

89.6

79.3

66.3

85.3

93.9

99.9

103.9

106.4

107.9

108.2

107.2

105.8

103.1

97.9

90.5

80.1

66.9

84.3

92.8

98.6

102.5

104.9

106.4

106.9

106.6

105.7

104.4

101.7

96.7

89.4

79.2

66.2

80.4

88.2

93.5

97.1

99.4

100.7

101.2

100.9

100.1

98.9

96.4

91.8

85.0

75.5

63.4

72.7

79.1

83.6

86.5

88.6

89.8

90.1

90.0

89.3

88.2

86.0

82.1

76.3

68.3

57.9

62.5

67.3

70.8

73.4

74.8

75.8

76.3

76.1

75.5

74.6

72.7

69.5

65.1

58.9

32.4

32.2

39.5

45.7

47.6

46.2

43.7

44.2

47.1

49.9

48.1

45.6

45.7

46.0

48.9

51.7

51.9

48.9

45.9

45.4

47.3

49.6

48.0

43.0

34.5

43.4

50.8

52.9

50.7

47.5

47.7

51.2

54.8

54.5

51.1

48.3

48.7

52.6

56.6

53.1

49.2

48.5

51.5

54.5

53.1

47.1

33.8

42.1

49.1

51.1

49.1

46.1

46.3

49.6

53.1

53.1

50.0

47.0

47.1

50.7

54.4

54.7

51.3

47.6

47.0

49.7

52.4

51.0

45.3

42.7

48.8

50.6

48.7

46.4

46.8

50.2

53.8

53.7

50.5

47.4

47.9

50.8

53.9

53.6

50.1

46.7

46.5

49.1

51.5

49.6

44.1

36.4

45.6

52.5

54.2

51.9

48.9

49.6

53.4

57.6

57.5

53.7

49.9

50.5

54.1

57.4

53.3

49.2

49.1

52.4

55.3

53.5

47.2

34.9

42.9

48.9

50.6

48.7

46.4

46.7

50.1

53.7

53.7

50.5

47.4

47.8

50.8

53.8

53.5

50.1

46.7

46.6

49.2

51.6

49.8

44.1

29.8

37.7

45.2

49.5

49.1

46.4

45.3

47.4

51.2

52.8

51.1

47.2

45.2

46.3

49.1

49.5

45.2

37.6

30.9

39.7

48.4

53.2

52.7

49.2

47.8

50.2

54.8

54.6

50.0

47.7

49.1

52.6

53.2

48.3

39.5

30.8

29.8

37.6

45.2

49.5

49.1

46.3

45.2

47.2

51.1

52.7

51.0

47.2

45.1

46.2

49.1

49.4

45.1

37.5

40.6

47.7

50.4

49.2

46.5

46.4

49.3

53.0

53.8

51.6

47.7

47.0

49.6

53.2

54.1

51.3

47.5

46.5

48.6

51.3

51.0

46.8

34.0

43.0

51.0

54.2

52.5

49.1

48.9

52.4

56.8

57.7

55.0

50.4

49.6

52.7

57.0

54.7

50.2

49.0

51.7

55.1

55.1

50.2

40.7

47.7

50.5

49.3

46.5

46.4

49.3

53.0

53.9

51.6

47.8

47.1

49.7

53.3

54.2

51.4

47.5

46.5

48.7

51.4

51.1

46.8

43.2

43.4

39.5

43.2

48.5

43.5

43.0

48.3

48.4

43.3

38.9

42.9

42.9

39.0

52.3

57.1

58.7

57.6

54.4

68.5

76.2

78.9

78.2

73.5

84.7

96.4

100.3

99.7

92.9

79.6

63.2

96.0

110.1

115.3

114.2

106.3

89.9

70.4

103.1

118.3

123.9

122.8

114.4

96.7

74.7

107.0

121.8

128.0

127.3

118.5

99.2

76.9

108.5

123.6

129.7

119.4

100.7

78.0

107.7

123.6

129.8

128.6

119.1

100.5

77.9

106.1

121.6

127.6

126.4

117.2

98.7

76.6

101.1

115.2

120.8

119.7

111.3

93.9

73.2

90.4

102.5

107.1

106.3

99.1

84.3

66.9

74.3

82.7

86.4

85.7

80.2

69.9

57.5

57.6

63.0

65.3

64.8

61.3

55.7

16.8

18.3

18.9

19.5

19.6

19.0

18.2

17.0

15.3

18.1

19.7

20.4

21.1

21.1

20.5

19.8

18.7

16.3

19.1

20.8

21.5

22.5

22.5

21.8

20.9

19.7

17.3

19.9

21.6

22.3

23.4

23.5

22.7

21.8

20.4

17.6

20.1

21.8

22.7

23.7

23.2

22.1

20.7

17.6

19.9

21.6

22.4

23.4

23.5

22.8

21.8

20.4

17.6

19.2

20.9

21.6

22.6

22.7

22.0

20.9

19.7

17.3

18.2

19.8

20.5

21.3

21.3

20.7

19.9

18.7

16.4

16.9

18.4

19.0

19.6

19.6

19.1

18.3

17.0

16.8

17.9

18.2

19.1

20.7

20.6

20.4

21.1

20.8

20.7

20.6

19.3

18.7

18.0

16.8

15.4

15.9

18.3

19.6

19.7

21.0

22.9

22.8

22.4

23.5

22.8

22.9

22.9

21.0

20.4

19.7

18.2

16.2

16.8

19.7

21.1

21.3

22.8

24.9

24.9

24.5

26.0

24.8

24.9

24.8

22.6

21.8

21.1

19.5

17.0

17.7

20.9

22.5

22.6

24.4

26.6

26.5

26.2

28.0

26.6

26.3

26.4

24.0

23.0

22.3

20.7

17.8

18.2

21.4

23.2

23.4

25.2

27.8

27.5

27.1

29.0

27.7

27.3

27.5

25.1

23.8

23.0

21.2

18.4

18.3

21.8

23.5

23.7

25.5

28.3

28.0

27.6

28.0

28.0

28.1

25.3

24.3

23.5

21.6

18.5

18.3

21.8

23.5

23.7

25.5

28.3

27.9

27.6

28.0

27.9

28.0

25.3

24.3

23.5

21.4

18.4

18.2

21.4

23.2

23.4

25.2

27.7

27.4

27.1

28.9

27.7

27.3

27.5

25.0

23.9

22.9

21.1

18.3

17.7

20.8

22.4

22.5

24.2

26.5

26.4

26.1

27.9

26.5

26.2

26.3

23.9

22.9

22.2

20.6

17.8

16.8

19.7

21.1

21.3

22.7

24.8

24.8

24.3

25.8

24.5

24.7

24.7

22.5

21.6

21.1

19.5

16.9

16.1

18.3

19.6

19.8

21.0

22.7

22.7

22.4

23.3

22.6

22.8

22.6

21.0

20.2

19.6

18.1

16.1

55.1

60.1

64.0

66.5

68.1

68.6

68.8

68.9

68.2

67.5

67.1

65.9

64.8

63.5

61.2

58.1

54.0

48.4

66.7

74.3

79.7

82.9

84.7

85.0

85.0

84.5

83.3

82.4

81.5

80.3

79.0

77.3

74.5

70.7

65.0

57.1

76.7

86.7

93.5

97.2

98.7

98.6

97.8

96.4

94.7

93.2

92.2

90.5

89.0

86.9

84.0

79.5

72.5

62.9

82.5

93.8

101.1

104.8

105.8

104.3

102.0

99.3

96.6

94.4

93.0

90.9

89.1

87.1

84.0

79.4

72.5

62.8

84.2

95.8

102.8

106.0

102.2

97.5

92.9

88.6

85.7

82.9

80.8

79.2

77.2

74.4

70.5

64.6

56.6

84.1

95.5

102.1

104.4

102.8

96.6

88.9

82.1

74.2

68.6

66.8

65.6

64.4

62.8

60.6

57.6

53.5

82.5

93.4

99.5

100.9

97.7

89.7

78.4

77.1

86.5

91.8

92.5

88.1

79.0

65.0

67.2

74.5

78.3

78.3

74.5

66.0

56.7

Description Symbol Avg Max Min Max/Min Avg/Min

AC Garage 193 22.8 fc 29.4 fc 15.1 fc 1.9:1 1.5:1Calc Zone #21 47.9 fc 56.8 fc 28.9 fc 2.0:1 1.7:1Calc Zone #22 49.7 fc 57.7 fc 34.8 fc 1.7:1 1.4:1Calc Zone #23 45.9 fc 56.6 fc 29.7 fc 1.9:1 1.5:1Calc Zone #24 49.6 fc 58.0 fc 32.8 fc 1.8:1 1.5:1Cat Holding 163,164 32.9 fc 42.9 fc 0.0 fc N/A N/AClassroom 137 81.4 fc 102.8 fc 57.8 fc 1.8:1 1.4:1Corridor 107 45.3 fc 59.4 fc 20.7 fc 2.9:1 2.2:1Corridor 132 (North) 50.9 fc 58.8 fc 32.3 fc 1.8:1 1.6:1Corridor 132 (South) 47.4 fc 57.8 fc 27.6 fc 2.1:1 1.7:1Corridor 159 50.6 fc 58.2 fc 34.2 fc 1.7:1 1.5:1Corridor 160 51.5 fc 79.5 fc 30.2 fc 2.6:1 1.7:1Dog Holding 161,162 66.8 fc 82.0 fc 46.8 fc 1.8:1 1.4:1Dog Intake 175 86.6 fc 108.5 fc 51.4 fc 2.1:1 1.7:1Dog Room 153,154,155,157,158 40.5 fc 47.2 fc 24.2 fc 2.0:1 1.7:1

Statistics

Description Symbol Avg Max Min Max/Min Avg/Min

Electrical Closet 202 20.2 fc 23.8 fc 15.2 fc 1.6:1 1.3:1Foster Exam 138,140 80.2 fc 101.9 fc 55.7 fc 1.8:1 1.4:1Front Office 106 80.7 fc 106.2 fc 48.0 fc 2.2:1 1.7:1Locker Room 197,198 54.1 fc 70.6 fc 37.6 fc 1.9:1 1.4:1Meeting Room 103 94.3 fc 130.3 fc 48.0 fc 2.7:1 2.0:1Open Workstation 118 52.8 fc 75.2 fc 29.3 fc 2.6:1 1.8:1Sugery 170 92.6 fc 117.8 fc 59.3 fc 2.0:1 1.6:1Surgery Prep 168 103.8 fc 134.3 fc 55.5 fc 2.4:1 1.9:1T&S 199 43.4 fc 48.6 fc 38.5 fc 1.3:1 1.1:1T&S 199 (Shower) 59.6 fc 59.7 fc 59.5 fc 1.0:1 1.0:1Typical Cat Comm 133,134,135,136 46.7 fc 56.8 fc 33.2 fc 1.7:1 1.4:1Typical Cat Room 144,145,146 24.0 fc 29.3 fc 15.3 fc 1.9:1 1.6:1Typical Office 115,114,113,112,111,110,109,108 47.8 fc 60.4 fc 36.9 fc 1.6:1 1.3:1Typical Office 189,188,187 64.6 fc 79.4 fc 49.1 fc 1.6:1 1.3:1Typical Toilet Rooms 131,130,126,127,104,105,183,184,195,196,199,201 46.7 fc 51.4 fc 40.9 fc 1.3:1 1.1:1

Statistics

SHEET NUMBER:

DRAWING TITLE:

DATE ISSUED:

PROJECT NUMBER:

PROJECT SET:

I HEREBY CERTIFY THAT THESE DOCUMENTS WERE PREPARED OR APPROVED BY ME, AND THAT I AM A

DULY LICENSED PROFESSIONAL ENGINEER UNDER THE LAWS OF THE

STATE OF MARYLAND. LICENSE NUMBER: #xxxxx

EXPIRATION DATE: mm-dd-yyyy

CO

NSU

LTAN

T:SE

AL

ALL DRAWINGS ARE PROTECTED BY FEDERAL COPYRIGHT BY MANNS WOODWARD STUDIOS, INC. AND CAN NOT BE REPRODUCED OR MODIFIED IN ANY MANNER WITHOUT WRITTEN PERMISSION. DOCUMENTS MAY NOT BE USED IN PART OR WHOLE TO DEVELOP THE DESIGN OF ANOTHER BUILDING WITHOUT EXPRESS WRITTEN PERMISSION BY MANNS WOODWARD STUDIOS.

(P) 410-344-1460(F) 443-403-2460(E) [email protected]

S T U D I O S10839-D PHILADELPHIA RDWHITE MARSH, MD 21162

ARCHITECTURE + MASTER PLANNING

Eng

inee

ring

Infra

stru

ctur

e S

olut

ions

C.C

. Joh

nson

& M

alho

tra,

P.C

.

400

Eas

t Pra

tt S

treet

, Sui

te 6

04B

altim

ore,

MD

212

02(P

) 410

-461

-992

0 | (

F) (

667)

239-

3534

| (E

) BA

LTIM

OR

E@

CC

JM.C

OM

CC

JM

3/15

/201

9 6:

05:0

7 PM

E701

BALT

IMO

RE C

ITY

ANIM

AL S

ERVI

CES

BUIL

DING

2490

GIL

ES R

OAD

, BAL

TIM

ORE

, 212

25

ELECTRICAL - INTERIORPHOTOMETRICS PLAN

03-15-2019

17-023

100% CD

NO. DESCRIPTION DATE

ELECTRICAL - INTERIOR LIGHTING PHOTOMETRICS PLANSCALE: NONE

1