WelcomeHerzlich WillkommenBienvenue
JUMO eTRON T
data sheet 70.1050
2PL 70 / © JUMO Klaus Otto
Digital thermostat JUMO eTRON T
programming
increase value,select picture status at release level
decrease value,select picture status at release level
status indication of relay outputLED K1
LC display 3-digit 9-segment display, 6 mm high, with symbols for °C and °F
Displays and controls
3PL 70 / © JUMO Klaus Otto
1 measurement input for resistance thermometer, thermocouple, current, voltage (different hardware versions)
1 relay (changeover contact)
configurable for heating and cooling function
indication of min- / max-alert
time delayed switch-on after power-on is adjustable
configuration via device or setup program
available with supply: AC 230V +10%/-15%, 48…63Hz ; AC/DC 20…53 V, 48…63Hz ; DC 12…24V +15%/-15%, AC 24V +15%/-15%, 48…63Hz
Functions
4PL 70 / © JUMO Klaus Otto
Dimensions and assembling
5PL 70 / © JUMO Klaus Otto
Block structure
JUM
O e
TR
ON
T
Setup interface
for configuration from PC
floating changeover contact 10A/250V
Output
LC display
3-digit display for representation of measurement and parameter
Measurement input group 2
thermocouples Fe-CuNi „J, L“ or NiCr-Ni „K“, configurable
Measurement input group 4
voltage 0…10 V
Measurement input group 3
current 0(4)…20mA
Measurement input group 1
Pt100, Pt1000 or KTY2X-6 in 2-wire circuit, configurable
Keys
3 keys for instrument operation
Supply
-AC 230V +10/-15%, 48…Hz-AC 115V +10/-15%, 48…63Hz-DC 12…24V +15/-15% AC 24V+15/-15%, 48…63Hz
LED indication
1 LED for the switching status of relay K1
or
or
or
6PL 70 / © JUMO Klaus Otto
Connection 701050
7PL 70 / © JUMO Klaus Otto
Operational concept
8PL 70 / © JUMO Klaus Otto
Operational concept
Assignment of user rights
9PL 70 / © JUMO Klaus Otto
Parameter chart
10PL 70 / © JUMO Klaus Otto
Setup program
11PL 70 / © JUMO Klaus Otto
Setup program
12PL 70 / © JUMO Klaus Otto
Order details
13PL 70 / © JUMO Klaus Otto
Main fields of application
• ventilation technology
• heating and air conditioning technology
• baking ovens and chip pans
• solar and heat pumps
• transformer and storage temperature control
14PL 70 / © JUMO Klaus Otto
General benefits
• 10A relay (changeover contact)
Replaces an additional auxiliary relay or a contactor in many applications.
• 3-digit LC display with special symbols °C and °F
Offers a clearly arranged display of process values and parameters.
• Setup program
For easy configuration and storage of device data.
• Customized linearization via tabular function in the setup program
Enables linearization via 20 supporting points by own specifications.