WelcomeHerzlich WillkommenBienvenue

JUMO eTRON T

data sheet 70.1050

Page 2: Welcome Herzlich Willkommen Bienvenue JUMO eTRON T data sheet 70.1050.

2PL 70 / © JUMO Klaus Otto

Digital thermostat JUMO eTRON T

programming

increase value,select picture status at release level

decrease value,select picture status at release level

status indication of relay outputLED K1

LC display 3-digit 9-segment display, 6 mm high, with symbols for °C and °F

Displays and controls

Page 3: Welcome Herzlich Willkommen Bienvenue JUMO eTRON T data sheet 70.1050.

3PL 70 / © JUMO Klaus Otto

1 measurement input for resistance thermometer, thermocouple, current, voltage (different hardware versions)

1 relay (changeover contact)

configurable for heating and cooling function

indication of min- / max-alert

time delayed switch-on after power-on is adjustable

configuration via device or setup program

available with supply: AC 230V +10%/-15%, 48…63Hz ; AC/DC 20…53 V, 48…63Hz ; DC 12…24V +15%/-15%, AC 24V +15%/-15%, 48…63Hz

Functions

Page 4: Welcome Herzlich Willkommen Bienvenue JUMO eTRON T data sheet 70.1050.

4PL 70 / © JUMO Klaus Otto

Dimensions and assembling

Page 5: Welcome Herzlich Willkommen Bienvenue JUMO eTRON T data sheet 70.1050.

5PL 70 / © JUMO Klaus Otto

Block structure

JUM

O e

TR

ON

T

Setup interface

for configuration from PC

floating changeover contact 10A/250V

Output

LC display

3-digit display for representation of measurement and parameter

Measurement input group 2

thermocouples Fe-CuNi „J, L“ or NiCr-Ni „K“, configurable

Measurement input group 4

voltage 0…10 V

Measurement input group 3

current 0(4)…20mA

Measurement input group 1

Pt100, Pt1000 or KTY2X-6 in 2-wire circuit, configurable

Keys

3 keys for instrument operation

Supply

-AC 230V +10/-15%, 48…Hz-AC 115V +10/-15%, 48…63Hz-DC 12…24V +15/-15% AC 24V+15/-15%, 48…63Hz

LED indication

1 LED for the switching status of relay K1

or

or

or

Page 6: Welcome Herzlich Willkommen Bienvenue JUMO eTRON T data sheet 70.1050.

6PL 70 / © JUMO Klaus Otto

Connection 701050

Page 7: Welcome Herzlich Willkommen Bienvenue JUMO eTRON T data sheet 70.1050.

7PL 70 / © JUMO Klaus Otto

Operational concept

Page 8: Welcome Herzlich Willkommen Bienvenue JUMO eTRON T data sheet 70.1050.

8PL 70 / © JUMO Klaus Otto

Operational concept

Assignment of user rights

Page 9: Welcome Herzlich Willkommen Bienvenue JUMO eTRON T data sheet 70.1050.

9PL 70 / © JUMO Klaus Otto

Parameter chart

Page 10: Welcome Herzlich Willkommen Bienvenue JUMO eTRON T data sheet 70.1050.

10PL 70 / © JUMO Klaus Otto

Setup program

Page 11: Welcome Herzlich Willkommen Bienvenue JUMO eTRON T data sheet 70.1050.

11PL 70 / © JUMO Klaus Otto

Setup program

Page 12: Welcome Herzlich Willkommen Bienvenue JUMO eTRON T data sheet 70.1050.

12PL 70 / © JUMO Klaus Otto

Order details

Page 13: Welcome Herzlich Willkommen Bienvenue JUMO eTRON T data sheet 70.1050.

13PL 70 / © JUMO Klaus Otto

Main fields of application

• ventilation technology

• heating and air conditioning technology

• baking ovens and chip pans

• solar and heat pumps

• transformer and storage temperature control

Page 14: Welcome Herzlich Willkommen Bienvenue JUMO eTRON T data sheet 70.1050.

14PL 70 / © JUMO Klaus Otto

General benefits

• 10A relay (changeover contact)

Replaces an additional auxiliary relay or a contactor in many applications.

• 3-digit LC display with special symbols °C and °F

Offers a clearly arranged display of process values and parameters.

• Setup program

For easy configuration and storage of device data.

• Customized linearization via tabular function in the setup program