1
MULTICONTROL-SAUTOFILL SOLO MCA
Ver. 1/2020-en0
WE SAY:!REFILL PLEASE
mult
ico
ntr
olauto
fill
MC
A
2
Make-up
Losses within the system are mostly unavoidable. To ensure a smooth operation refilling from
time to time is necessary.
heat resp.cool generator
symbolic illustration
V
12
PY5 P1
PM1PL1u Q1
M
10
1
11
MAG
”pressure controlled” operation
membraneexpansion vessel
load
multicontrolautofill solo -SMCAstorage tank -GMCA
13
heat resp.cool generator
2
3
symbolic illustration
V
PY5 P1
PM1PL1u Q1
M
10
1
11
12
”contact controlled” operation
load
multicontrolautofill solo -SMCAstorage tank -GMCA
13
1
multicontrolpressure maintenance
possible supply of multiplepressure maintenance devices
OPERATING PRINCIPLE
Operating principle
Legend
1 ... make-up pipe 11 ... optional circulation pipe2 ... expansion overflow pipe (from system return) 12 ... vessel overflow3 ... expansion pressure pipe (to system return) 13 ... connection for mediumOPTIONAL10 ... suction pipe recirculation collecting pipe
M1 ... make-up pump 1u ... vessel pressure transmitter bottomPLY5 ... switch mixer P1 ... system pressure transmitterQ1 ... water counter
3
OPERATING PRINCIPLE
Especially in air conditions, cold water systems, solar systems etc. a special medium mixture is
used whereby a simple refill of fresh water is not possible. Multicontrol autofill solo -S forMCA
automatic, amount controlled make-up of special media offers the possibility to refill a certain
amount media mixture out of a storage tank is required.
We recommend our multicontrol -G vessels as storage tanks, but they don‘t have to beMCA
used compulsively. On site already existing vessels can possibly be used as storage tanks,
because the needed vessel connection unit is always included in scope of delivery of the
control unit multicontrol autofill -S. With it the necessary level measurement in theMCA
storage tank as well as a permanent temperature measurement in the stored medium is
realised.
It is distinguished between the following operating modes:
� ”contact controlled” operation:
Thereby control of the -S for example is carried out by a multicotrol pressureMCA
maintenance device. If the level within the pressure less expansion vessel falls below a certain
minimum level an electric contact will request make-up. The make-up pump (M1) supplies
ready mixed system medium out of the storage tank (e.g. -G) to the expansion vessel asMCA
long as it is refilled up to a preset level.
On demand there is the possibility to supply several multicontrol pressure maintenance
devices with make-up medium by one multicontrol autofil device. Thereto a make-up module
is installed in every supplying pressure maintenance device and via a contact each of these
devices can request make-up from the -S.MCA
� ”pressure controlled” operation:
Pressure controlled make-up takes place into the closed system directly. The system pressure
is hold constant by a membrane expansion vessel ( ), nevertheless it can fall by possibleMAG
leaks. Assumed that the proper function of the is given, make-up can be necessary.MAG
Therefore the vessel pressure transmitter (P1) registers the actual pressure in the system and
compares it with the adjusted set point. Decreases the pressure below the set value the make-
up pump (M1) starts. It pumps medium from the storage tank directly into the system. As soon
as the set pressure is reached, the make-up pump (M1) stops.
The make-up amout is recorded by a water meter (Q1) and compared with the maximum
adjusted make-up amount. Is this amount exceeded the make-up stops and the make-up
operation is locked. Only after verification and disengaging by the system support engineers,
make-up can be activated again. Beside the amount controlled operating mode also a time
controlled operating mode is available, which is advantageous in case of known and regular
necessary make-up amounts.
4
OPERATING PRINCIPLE DETAILS/
Within the storage tank ( -G) a vessel pressure transmitter (Pl1u) for level measurement isMCA
arranged. Level measurement bases on pressure measurement of the medium in the storage
tank. Out of it the filling height (=vessel level) is determined (also not by weight measurement
of load cells at the vessel).
By undercutting a certain minimum vessel level make-up stops to protect the make-up pump
(M1) from running dry. Not before the storage tank ( -G) is filled again further make-up canMCA
take place.
The storage tank is operated as open vessel to avoid negative pressure or overpressure. All
connections are mounted on site, which implicates high flexibility because connection
positions at the storage tank can be adapted to local conditions.
Circulation function
A circulation function is also included and after proper piping to the storage tank it can be
activated in the settings. It offers the possibility to mix longer stored medium to antagonise
settling out different media components at the storage tank bottom.
Therefore in the working hydraulics an electromotive activated switch mixer (Y5) is built in
already. To start the circulation functon it is activated by the electronic control, either in
periodic intervals of directly before any make-up for an adjustment time, depending on the
requirements of our costumer. For this purpose the switch mixer (Y5) is carried out as three way
mixing valve that is adjusted in position ”make-up” by default and moves to position
”circulating” during the circulation process. Thereupon the make-up pump (M1) is activated
and circulates the medium via the switch mixer (Y5) from the tank connection unit back to the
storage tank. Though all parts of the medium are well mixed again and afterwards make-up
can take place.
Medium recirculation
For safety of financial reasons it can additionally be necessary to prevent a leakage of the
particular system medium (e.g. via safety valves,...) and collect it again. For this purpose at the
storage tank -G a connection for a collecting pipe for media recirculation is provided.MCA
5
D TAILE S
operator panel with four lines,illuminated plain text display
easily accessible cableglands, on requestmountable to the left side
enclosed electronic unit,optimally protected
always included four potentialfree contacts:- fault- warning- make-up in operation- device operation enabled
on-site connections, on requestconvertible (right or left side)
corrosion resistance: base andpiping made of stainless steel,brass/red brassmounting holes in the base
plate for fixing the device
transportable palletfor easy insertion
tank overflow incl.discharge hopper
tank emptying for anymaintenance
storage tank made ofhigh medium resistantsynthetic material
Details
torsion resistant lattice-workmade of zinc-plated steel tube
continuoustemperaturecontrol
connection forcirculation pipeconnection for medium
recirculation from systemsafety valve(s)
6
ACCESSORY
Accessory
Your great benefit:� From pioneer to number one: 45 years
experience in pressure maintenance
� Company owned costumer service for
technical service of your system throughout
the product‘s life
� Convenient complete solution for make-up
of special media from an external tank with
connection for a collecting pipe for medium
recirculation to the tank
� Special low-noise, self priming make-up
pump
make-up / degassing
multicontrol autofill vessel -GMCA
expansion modules / remote signalling
multicontrol expansion module
”analog signalling”
multicontrol expansion module
”binary signalling”
multicontrol expansion module
”binary signalling & remote reset”
multicontrol moduleSMS
multicontrol bus modules
connection accessory
multicontrol autofill connection set G
multicontrol autofill connection set _MC
general accessory
multicontrol metal housing
multicontrol contact temperature sensor
incl. strap (diameter 15-40mm)
multicontrol temperature sensor
cable 10m, incl. immersion sleeve G1/2", 10PN
collecting pan, 3 spacer
discharge hopper 50 with siphon
Further products of our multicontrol series:
� expansion and pressure maintenance device picocontrol kompakt PCK
� expansion and pressure maintenance device multicontrol kompakt MCK
� pressure maintenance device multicontrol modular MCM
� pressure maintenance device topcontrol modular TCM
� pressure maintenance device multicontrol cool MCC
For detailled information compare brochure ”multicontrol original accessory”.
7
1
10 11
1
TECHNICAL DATA
Positions 10, 11, 12, 13 on the storage tank -GMCAare adapted to local conditions on site!
MCA-S1-2.7 MCA-S1-5.2 MCA-G640 MCA-G1000
nominal content litre 640 1000
max. operating pressure unit ( )PN bar
max. upper working pressure bar 2,7 5,2
max. operating pressure vessel ( )PN bar
max. temp. at connection point °C
insertion tilted dimension mm 1005 1145
voltage V/Hz
max. electrical power kW 0,6 0,8
fuse protection A
dimensions A mm
B mm 800 1000
C mm 1005 1145
D mm
E mm
F mm
G mm
weight kg 49,5 52 50 63
connections 1 "
10 "
11 "
12"
13" - R 1
1 … make-up pipe 10 … suction pipe 11 … optional circulation pipe 12 … vessel overflow
13 … optional connection for medium recirculation collecting pipe
Technical changes reserved!
Rp 1 R 1
Rp 1 R 1
- Geberit 50DN
445 -
1150 -
Rp 3/4 -
830
470 -
405 -
10 -
150 1200
225
70
1220
230/50 -
-
10 -
-
- 0
type elko-mat eder multicontrol autofill
multicontrol autofill MCA storage tank -GMCA
-
Technical data
8
www.eder-heizung.at
BETTER HEATING. SAFE BET.
plant complexity(generating capacity,
static height,total content,
working pressure)
elko-mat eder controlpico PCK
elko-flex eder
elko-mat eder multicontrol MCK
elko-mat eder multicontrol MCM
elko-mat eder topcontrol TCM
ANTON EDER GMBHA-9909 Leisach 52Tel.: +43 (0) 4852 644 77Fax: +43 (0) 4852 644 77-20
branch A-5733 Bramberg | Weyerstraße 350 | Tel.: +43 (0) 6566 7366branch A-1230 Vienna | Gorskistraße 15 | Tel.: +43 (0) 1 985 37 30