technical data
SplitSky Air
EEDE05-1/1
air cond
itioning
systems
Zandvoordestraat 300
B - 8400 Ostend Belgium
www.daikineurope.com
Specifications are subject to change without prior notice
Het ISO14001 assures an effective environmental management system in order to help protect human health and the environment from potential impact of our activities, products and services and to assist in maintaining and improving the quality of the environment.
Daikin units comply with the European regulations that guarantee the safety of the product.
Daikin Europe N.V. is approved by LRQA for its Quality Management System in accordance with the ISO9001 standard. ISO9001 pertains to quality assurance regarding design, development, manufacturing as well as to services related to the product.
Daikin Europe N.V. participates in the Eurovent Certification Programme for Air Conditioners (AC), Liquid Chilling Packages (LCP) and Fan Coil Units (FC); the certified data of certified models are listed in the Eurovent Directory.
Split - Sky Air
EED
E05-
1/1
- 03/
2005
Prin
ted
in B
elgi
um b
y G
oeki
nt G
raph
ics
technical data
SplitSky Air
EEDE05-1/1
air conditioning systems
• Split Sky Air • Outdoor Units 4
• Outdoor Units • R-22 • R-C
TABLE OF CONTENTSR-C
1 Features. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
2 Specifications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Technical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Electrical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
3 Electrical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
4 Capacity tables. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Capacity tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
5 Dimensional drawing & centre of gravity. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Dimensional drawing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
6 Piping diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
7 Wiring diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Wiring diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
8 Sound data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Sound pressure spectrum . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
9 Operation range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
• Outdoor Units • R-22 • R-C
5
11
tdoo lit C22
Ou Sp R- R- 1 Features• Outdoor units for pair application
• Daikin outdoor units are neat and sturdy and can be mounted easily on a roof or terrace or simply placed against an outside wall.
• Outdoor units are fitted with a rotary compressor, renowned for low noise and high energy efficiency
• Split Sky Air • Outdoor Units
12
• Outdoor Units • R-22 • R-C
2 Specifications
2-1 TECHNICAL SPECIFICATIONS R25CV1A9 R35CV1A9 R50CV1A9 R60CV1A9
Casing Colour Ivory White
Dimensions Packing Height mm 599 599 732 732
Width mm 797 797 955 955
Depth mm 310 310 390 390
Unit Height mm 560 560 685 685
Width mm 695 695 800 800
Depth mm 265 265 300 300
Weight Machine Weight kg 27 33 49 61
Gross Weight kg 30 35 54 66
Heat Exchanger Dimensions Length mm 630 608 758 758
Nr of Rows 1 2 2 2
Fin Pitch mm 1.50 1.80 1.60 2.00
Nr of Passes 2 1.5 2 2
Nr of Stages 24 24 28 28
Tube type Hi-Xa(8)
Fin Type HL fin HL fin FL fin FL fin
Fan Type Propeller
Quantity 1 1 1 1
Air Flow Rate (nominal)
Cooling m3/min 29.0 27.0 40.5 40.5
Motor Quantity 1 1 1 1
Model KF-220-25L-1 KF-220-25L-1 53A-22 53A-22
Motor Speed (nominal at 230V)
Cooling rpm 720 710 855 855
Fan Motor Output W 25 25 53 53
Compressor Quantity 1 1 1 1
Motor Model RC30BV1R2T RC46AV1TRT RC60V1TNRT NH41VMDT
Type Hermetically sealed rotary compressor
Motor Output
W 700 1100 1500 2200
Operation Range Cooling Min °CDB 19.4 19.4 19.4 19.4
Max °CDB 46.0 46.0 46.0 46.0
Sound Level (nominal)
Cooling Sound Pressure
dBA 47.0 48.0 54.0 54.0
Refrigerant Type R22
Charge kg 0.76 0.95 1.35 1.70
Refrigerant Oil Type Suniso 4GSID Suniso 4GSID Suniso 4GSID MS-32
Charged Volume l 0.4 0.5 0.9 1.2
Piping connections
Liquid (OD) Diameter (OD)
mm 6.35 6.35 6.35 6.35
Gas Diameter (OD)
mm 9.5 12.7 15.9 15.9
Drain Diameter (OD)
mm 18 18 18 18
Piping Length Maximum m 25 25 30 30
Additional Refrigerant Charge kg/m 0.02/>10
Max. internunit level difference m 15.0 15.0 15.0 15.0
Heat Insulation Both liquid and gas pipes
• Split Sky Air • Outdoor Units 6
• Outdoor Units • R-22 • R-C
7
12
2-2 ELECTRICAL SPECIFICATIONS R25CV1A9 R35CV1A9 R50CV1A9 R60CV1A9
Power Supply Name V1 V1 V1 V1
Phase 1 1 1 1
Frequency Hz 50 50 50 50
Voltage V 220-240
Current Nominal running current (RLA)
Cooling (A) A 3.78 5.38 7.12 10.70
Starting current (cooling/heating)
A 20.0 27.0 33.5 58.0
Voltage range Minimum V 207 207 207 207
Maximum V 253 253 253 253
Wiring connections
For Power Supply Quantity 3 3 3 3
For connection with indoor
Quantity 4 4 4 4
Remark included earth wiring
Power Supply Intake Outdoor unit only
NOTES
1 Nominal cooling capacities are based on : indoor temperature : 27°CDB, 19°CWB, outdoor temperature : 35°CDB, equivalent refrigerant piping : 7.5m, level difference : 0m.
2 Sound levels are measured in an anechoic room
3 Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to sound level drawings of this chapter.
4 The sound power level is an absolute value indicating the power which a sound source generates
• Split Sky Air • Outdoor Units
13
• Outdoor Units • R-22 • R-C
3 Electrical data
3D045936A
SYMBOLS
MCA: Min. Circuit Amps
TOCA: Total Over-current Amps
MFA: Max. Fuse Amps (see note 7)
LRA: Locked rotor Amps
RLA: Rated Load Amps
OFM: Outdoor Fan Motor
IFM: Indoor Fan Motor
FLA: Full Load Amps
kW: Fan Motor Rated Output
NOTES
1 RLA based on the following conditions:Indoor temp. 27°CDB/19°CWBOutdoor temp. 35°CDB
2 TOCA means the total value of each OC set.
3 Voltage range: units are suitable for use on electrical systems where the voltage supplied to the unit terminals is not below or above the listed range limits.
4 Maximum allowable voltage unbalance between phases is 2%.
5 Select wire size based on the larger value of MCA or TOCA.
6 Instead of fuse, use circuit breaker.
7 MCA/MFAMCA = 1.25 x RLA + all FLAMFA 2.25 x RLA + all FLA(next lower standard fuse rating Min. 15A)
8 Overcurrent relay trips when TOCA exceeds indicated value for more than 5 seconds within 16 seconds at 25 °C.
9 If TOCA exceeds indicated value, overcurrent relay trips when compressor head temperature greater than 1,00 °C.
10 For more details concerning conditional connections, see http://www.daikineurope.com/extranet, select “Daikin Documentation” and select “conditional connection”, “the requested product type” and “English” from the drop down lists, click the search button. Finally, click on the document title of your choice.
Unit combination Power supply Compressor OFM IFM
Indoor unit Outdoor unit Hz-Volts Voltage range MCA TOCA MFA LRA RLA kW FLA kW FLA
FT25CV1A9 R25CV1A9
50-220Max. 50Hz - 264VMin. 50Hz - 198V 8.71 17.5 (note 8)
6.7 (note 9) 15
26.0 3.47
0.025 0.33 0.018 0.2850-230 27.0 3.51
50-240 28.0 3.60
FT35CV1A9 R35CV1A9
50-220Max. 50Hz - 264VMin. 50Hz - 198V 12.1 / 15
26.0 5.09
0.025 0.33 0.018 0.2850-230 27.0 5.11
50-240 28.0 5.12
• Split Sky Air • Outdoor Units 8
• Outdoor Units • R-22 • R-C
9
13
3 Electrical data
3D040942B
SYMBOLS
MCA: Min. Circuit Amps
MFA: Max. Fuse Amps (see note 7)
LRA: Locked rotor Amps
RLA: Rated Load Amps
OFM: Outdoor Fan Motor
IFM: Indoor Fan Motor
FLA: Full Load Amps
kW: Fan Motor Rated Output
NOTES
1 RLA based on the following conditions:Indoor temp. 27°CDB/19°CWBOutdoor temp. 35°CDB
2 Maximum allowable voltage unbalance between phases is 2%.
3 Select wire size based on the larger value of MCA or TOCA.
4 Instead of fuse, use circuit breaker.
5 MCA/MFAMCA = 1.25 x RLA + all FLAMFA 2.25 x RLA + all FLA(next lower standard fuse rating Min. 15A)
6 For more details concerning conditional connections, see http://www.daikineurope.com/extranet, select “Daikin Documentation” and select “conditional connection”, “the requested product type” and “English” from the drop down lists, click the search button. Finally, click on the document title of your choice.
Unit combination Power supply Compressor OFM IFM
Indoor unit Outdoor unit Hz-Volts Voltage range MCA MFA LRA RLA kW FLA kW FLA
FT50CV1A9 R50CV1A9
50-220Max. 50Hz - 264VMin. 50Hz - 198V 9.7 15
32.0 7.17
0.053 0.53 0.043
0.20
50-230 33.5 6.88 0.19
50-240 35.0 6.49 0.18
FT60CV1A9 R60CV1A9
50-220Max. 50Hz - 264VMin. 50Hz - 198V 14.3 25
55.0 10.87
0.053 0.53 0.043
0.20
50-230 57.5 10.38 0.19
50-240 60.0 9.89 0.18
• Split Sky Air • Outdoor Units
14
• Outdoor Units • R-22 • R-C
4 Capacity tables
4 - 1 Capacity tables
FT25CV1A9 + R25CV1A9
3D045935
Cooling capacity (50 Hz, 220-240 V)
SYMBOLS
AFR: Air flow rate [m3/min.]BF: Bypass factorEWB: Entering wet bulb temp. [°CWB]EDB: Entering dry bulb temp. [°CDB]TC: Total capacity cooling [kW]SHC: Sensible heat capacity [kW]PI: Power input [kW]
NOTES
1 Ratings shown are net capacities which include a deduction for indoor fan motor heat.
2 shows nominal (rated) capacities and power input.
3 TC, PI and SHC must be calculated by interpolation using the figures in the above tables. (Figures out of the tables should not be used for calculation).
4 SHC is based on each EWB and EDB.SHC* = SHC correction for other dry bulb.
= 0.02 x AFR [m3/min.] x (1-BF) x (DB*-EDB)Add SHC* to SHC.
5 Capacities are based on the folowing conditions.Corresponding refrigerant piping length: 5m(7.5m at [AS/NZS3823.1])Level difference: 0m
6 Air flow rate (AFR) and Bypass factor (BF) are tabulated below.
7 Add the following corrections to power input at [230V, 240V] as shown below.
Indoor Outdoor temperature (°CDB)EWB(°C)
EDB(°C)
20 25 30 32 35 40 46TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
14.0 20.0 2.70 1.81 0.47 2.55 1.74 0.56 2.40 1.67 0.66 2.34 1.65 0.70 2.25 1.60 0.75 2.10 1.53 0.85 1.92 1.45 0.9616.0 22.0 2.81 1.85 0.49 2.71 1.78 0.59 2.56 1.71 0.68 2.50 1.68 0.72 2.41 1.64 0.78 2.26 1.57 0.87 2.08 1.48 0.9918.0 25.0 3.01 1.88 0.52 2.86 1.81 0.61 2.71 1.74 0.71 2.65 1.71 0.75 2.56 1.67 0.80 2.41 1.60 0.90 2.23 1.52 1.0119.0 27.0 3.09 1.90 0.53 2.94 1.83 0.63 2.79 1.76 0.72 2.73 1.73 0.76 2.64 1.69 0.817 2.49 1.62 0.91 2.31 1.54 1.0322.0 30.0 3.32 1.95 0.57 3.17 1.88 0.67 3.02 1.81 0.76 2.96 1.78 0.80 2.87 1.74 0.86 2.72 1.67 0.95 2.54 1.59 1.0724.0 32.0 3.48 1.98 0.60 3.33 1.91 0.69 3.18 1.84 0.79 3.12 1.82 0.83 3.03 1.77 0.88 2.88 1.70 0.98 2.70 1.62 1.09
FTAFR 8.3BF 0.33
Voltage PI [kW]230 V +0.026240 V +0.051
• Split Sky Air • Outdoor Units 10
• Outdoor Units • R-22 • R-C
11
14
4 Capacity tables
4 - 1 Capacity tables
FT35CV1A9 + R35CV1A9
3D045937
Cooling capacity (50 Hz, 220-240 V)
SYMBOLS
AFR: Air flow rate [m3/min.]
BF: Bypass factor
EWB: Entering wet bulb temp. [°CWB]
EDB: Entering dry bulb temp. [°CDB]
TC: Total capacity cooling [kW]
SHC: Sensible heat capacity [kW]
PI: Power input [kW]
NOTES
1 Ratings shown are net capacities which include a deduction for indoor fan motor heat.
2 shows nominal (rated) capacities and power input.
3 TC, PI and SHC must be calculated by interpolation using the figures in the above tables. (Figures out of the tables should not be used for calculation).
4 SHC is based on each EWB and EDB.SHC* = SHC correction for other dry bulb.
= 0.02 x AFR [m3/min.] x (1-BF) x (DB*-EDB)Add SHC* to SHC.
5 Capacities are based on the folowing conditions.Corresponding refrigerant piping length: 5m(7.5m at [AS/NZS3823.1])Level difference: 0m
6 Air flow rate (AFR) and Bypass factor (BF) are tabulated below.
7 Add the following corrections to power input at [230V, 240V] as shown below.
Indoor Outdoor temperature (°CDB)
EWB(°C)
EDB(°C)
20 25 30 32 35 40 46TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
14.0 20.0 3.58 2.34 0.79 3.43 2.27 0.88 3.28 2.20 0.98 3.22 2.17 1.01 3.13 2.13 1.07 2.98 2.06 1.17 2.80 1.98 1.2816.0 22.0 3.74 2.38 0.81 3.59 2.31 0.91 3.44 2.24 1.00 3.38 2.21 1.04 3.29 2.17 1.10 3.14 2.10 1.19 2.96 2.01 1.3118.0 25.0 3.89 2.41 0.84 3.74 2.34 0.93 3.59 2.27 1.03 3.53 2.24 1.07 3.44 2.20 1.12 3.29 2.13 1.22 3.11 2.05 1.3319.0 27.0 3.97 2.43 0.85 3.82 2.36 0.95 3.67 2.29 1.04 3.61 2.26 1.08 3.52 2.22 1.135 3.37 2.15 1.23 3.19 2.06 1.3422.0 30.0 4.20 2.48 0.89 4.05 2.41 0.98 3.90 2.34 1.08 3.84 2.31 1.12 3.75 2.27 1.17 3.60 2.20 1.27 3.42 2.11 1.3824.0 32.0 4.36 2.51 0.92 4.21 2.44 1.01 4.06 2.37 1.11 4.00 2.34 1.14 3.91 2.30 1.20 3.76 2.23 1.30 3.58 2.15 1.41
FTAFR 8.4BF 0.24
Voltage PI [kW]230 V +0.035240 V +0.065
• Split Sky Air • Outdoor Units
14
• Outdoor Units • R-22 • R-C
4 Capacity tables
4 - 1 Capacity tables
FT50CV1A9 + R50CV1A9
3D045959
Cooling capacity (50 Hz, 220-240 V)
SYMBOLS
AFR: Air flow rate [m3/min.]
BF: Bypass factor
EWB: Entering wet bulb temp. [°CWB]
EDB: Entering dry bulb temp. [°CDB]
TC: Total capacity cooling [kW]
SHC: Sensible heat capacity [kW]
PI: Power input [kW]
NOTES
1 Ratings shown are net capacities which include a deduction for indoor fan motor heat.
2 shows nominal (rated) capacities and power input.
3 TC, PI and SHC must be calculated by interpolation using the figures in the above tables. (Figures out of the tables should not be used for calculation).
4 SHC is based on each EWB and EDB.SHC* = SHC correction for other dry bulb.
= 0.02 x AFR [m3/min.] x (1-BF) x (DB*-EDB)Add SHC* to SHC.
5 Capacities are based on the folowing conditions.Corresponding refrigerant piping length: 5m(7.5m at [AS/NZS3823.1])Level difference: 0m
6 Air flow rate (AFR) and Bypass factor (BF) are tabulated below.
7 Add the following corrections to power input at[AS/NZS3823.1] as shown below.
Indoor Outdoor temperature (°CDB)
EWB (°C)
EDB (°C)
20 25 30 32 35 40 46TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
14.0 20.0 5.36 3.67 1.25 5.21 3.60 1.35 5.06 3.53 1.44 5.00 3.50 1.48 4.91 3.46 1.54 4.76 3.39 1.63 4.58 3.30 1.74
16.0 22.0 5.52 3.70 1.28 5.37 3.63 1.37 5.22 3.56 1.47 5.16 3.53 1.50 5.07 3.49 1.56 4.92 3.42 1.66 4.74 3.34 1.7718.0 25.0 5.67 3.73 1.30 5.52 3.66 1.40 5.37 3.59 1.49 5.31 3.57 1.53 5.22 3.52 1.59 5.07 3.45 1.68 4.89 3.37 1.80
19.0 27.0 5.75 3.75 1.32 5.60 3.68 1.41 5.45 3.61 1.51 5.39 3.58 1.54 5.30 3.54 1.80 5.15 3.47 1.70 4.97 3.39 1.81
22.0 30.0 5.98 3.80 1.35 5.83 3.73 1.45 5.68 3.66 1.54 5.62 3.63 1.58 5.53 3.59 1.64 5.38 3.52 1.73 5.20 3.44 1.8524.0 32.0 6.14 3.84 1.38 5.99 3.77 1.48 5.84 3.70 1.57 5.78 3.67 1.61 5.69 3.63 1.67 5.54 3.56 1.76 5.36 3.47 1.87
FTAFR 16.2
BF 0.27
Voltage PI [kW]
230 V +0.05
• Split Sky Air • Outdoor Units 12
• Outdoor Units • R-22 • R-C
13
14
4 Capacity tables
4 - 1 Capacity tables
FT60CV1A9 + R60CV1A9
3D045960
Cooling capacity (50 Hz, 220-240 V)
SYMBOLS
AFR: Air flow rate [m3/min.]
BF: Bypass factor
EWB: Entering wet bulb temp. [°CWB]
EDB: Entering dry bulb temp. [°CDB]
TC: Total capacity cooling [kW]
SHC: Sensible heat capacity [kW]
PI: Power input [kW]
NOTES
1 Ratings shown are net capacities which include a deduction for indoor fan motor heat.
2 shows nominal (rated) capacities and power input.
3 TC, PI and SHC must be calculated by interpolation using the figures in the above tables. (Figures out of the tables should not be used for calculation).
4 SHC is based on each EWB and EDB.SHC* = SHC correction for other dry bulb.
= 0.02 x AFR [m3/min.] x (1-BF) x (DB*-EDB)Add SHC* to SHC.
5 Capacities are based on the folowing conditions.Corresponding refrigerant piping length: 5m(7.5m at [AS/NZS3823.1])Level difference: 0m
6 Air flow rate (AFR) and Bypass factor (BF) are tabulated below.
7 Add the following corrections to power input at[AS/NZS3823.1] as shown below.
Indoor Outdoor temperature (°CDB)
EWB(°C)
EDB(°C)
20 25 30 32 35 40 46TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
14.0 20.0 6.66 4.40 2.04 6.51 4.33 2.14 3.36 4.26 2.23 6.30 4.23 2.27 6.21 4.19 2.33 6.06 4.12 2.42 5.88 4.17 2.5316.0 22.0 6.82 4.43 2.07 6.67 4.36 2.16 6.52 4.29 2.26 6.46 4.26 2.29 6.37 4.22 2.35 6.22 4.15 2.45 6.04 4.20 2.5618.0 25.0 6.97 4.47 2.09 6.82 4.40 2.19 6.67 4.33 2.28 6.61 4.30 2.32 6.52 4.26 2.38 6.37 4.19 2.47 6.19 4.24 2.5919.0 27.0 7.05 4.48 2.11 6.90 4.41 2.20 6.75 4.34 2.30 6.69 4.32 2.33 6.60 4.27 2.39 6.45 4.20 2.49 6.27 4.25 2.6022.0 30.0 7.28 4.53 2.14 7.13 4.46 2.24 6.98 4.39 2.33 6.92 4.37 2.37 6.83 4.32 2.43 6.68 4.25 2.52 6.50 4.31 2.6424.0 32.0 7.44 4.57 2.17 7.29 4.50 2.27 7.14 4.43 2.36 7.08 4.40 2.40 6.99 4.36 2.46 6.84 4.29 2.55 6.66 4.34 2.66
FTAFR 17.5BF 0.23
Voltage PI [kW]230 V +0.07
• Split Sky Air • Outdoor Units
15
• Outdoor Units • R-22 • R-C
5 Dimensional drawing & centre of gravity
5 - 1 Dimensional drawing
R25,35CV1A9
3D028041A
MINIMUM SPACE FOR AIR PASSAGE
Name plate
Wall height on air outlet side is less than 1200
Terminal strip with earth terminalWiring inlet
Drain outlet(I.D. ø 15.9 hose for connection)
4-holes for anchor bolts(M8 or M10)
Service port
Gas stop valve:Model R25: 9.5 CuT
Model R35: 12.7 CuTLiquid stop valveø 6.4 CuTIN CASE OF
REMOVING STOP VALVE COVER
• Split Sky Air • Outdoor Units 14
• Outdoor Units • R-22 • R-C
15
15
5 Dimensional drawing & centre of gravity
5 - 1 Dimensional drawing
R50,60CV1A9
3D004856G
MINIMUM SPACE FOR AIR PASSAGE
Name plate
Earth terminal (M4) Terminal cover
Holes for anchor bolts(M8 or M10) 2-drain outlet
Power intake
Liquid stop valve
Gas pipe(ø 15.9 CuT)
Liquid pipe(ø 6.4 CuT)
Gas stop valve
Service port
Outdoor air thermostat
H A
1000 300
> 1000 600
• Split Sky Air • Outdoor Units
16
• Outdoor Units • R-22 • R-C
6 Piping diagram
R25CV1A9
3D020878D
Field piping(6.4 CuT)
Outdoor unit
9.5 CuT
Heat exchanger
Capillary tube
Propellor fan
Accumulator
7.9 CuT
Field piping(9.5 CuT)
7.9 CuT
7.9 CuT7.9 CuT
7.9 CuT
7.9 CuT6.4 CuT
Compressor
7.9 CuT
9.5 CuT
7.9
CuT
9.5
CuT
Gas stop valve with service port
Liquid stop valve7.9 CuT
• Split Sky Air • Outdoor Units 16
• Outdoor Units • R-22 • R-C
17
16
6 Piping diagram
R35CV1A9
3D020877C
Field piping(6.4 CuT)
Outdoor unit
12.7 CuT
Heat exchanger
Capillary tube
Propellor fan
Accumulator
7.9 CuT
Field piping(12.7 CuT)
7.9 CuT
7.9 CuT7.9 CuT
7.9 CuT
7.9 CuT 6.4 CuT
Compressor
7.9 CuT
12.7 CuT
7.9
CuT
9.5
CuT
Gas stop valve with service port
Liquid stop valve
• Split Sky Air • Outdoor Units
16
• Outdoor Units • R-22 • R-C
6 Piping diagram
R50,60CV1A9
DW521-856J
Field piping(6.4 CuT)
Outdoor unit
Heat exchanger
Capillary tube
Propellor fan
Accumulator
Field pipingsee note 1
Compressor
Gas stop valve with service port
Liquid stop valve
NOTE
1 Field piping specifications are as shown below.
Model name A
R50R60 15.9 CuT
• Split Sky Air • Outdoor Units 18
• Outdoor Units • R-22 • R-C
19
17
7 Wiring diagram
7 - 1 Wiring diagram
R25CV1A9
3D024713B
Power supply~50 Hz220V-240V
To indoor unit
LEGEND
C11R, C12R Running capacitorK1M Compressor relayL LiveN NeutralM1C Compressor motorTFU Thermal fuseF1U FuseM1F Fan motorQ1CL Overcurrent overload
protectorX1M, X2M Terminal strip
Protective earth
NOTES
1 Wiring diagram nameplate size: width 110 x length 70.2 Nameplate material: wood free tack paper.3 Coat the reverse side with pressure sensitive adhesive4 Refer to AS(Y)303002 unless otherwise specified.5 This drawing was drawn on CAD system.6 Make a slit on separate liner in vertical direction.
• Split Sky Air • Outdoor Units
17
• Outdoor Units • R-22 • R-C
7 Wiring diagram
7 - 1 Wiring diagram
R35CV1A9
3D024714B
Power supply~50 Hz220V-240V
To indoor unit
LEGEND
C11R, C12R Running capacitorK1M Compressor relayL LiveN NeutralM1C Compressor motorF1U FuseM1F Fan motorQ1L Overlead protectorX1M, X2M Terminal stripTFU Thermal fuse
Protective earth
NOTES
1 Wiring diagram nameplate size: width 110 x length 70.2 Nameplate material: wood free tack paper.3 Coat the reverse side with pressure sensitive adhesive4 Refer to AS(Y)303002 unless otherwise specified.5 This drawing was drawn on CAD system.6 Make a slit on separate liner in vertical direction.
• Split Sky Air • Outdoor Units 20
• Outdoor Units • R-22 • R-C
21
17
7 Wiring diagram
7 - 1 Wiring diagram
R50CV1A9
3D045730
Power supply~50 Hz220V-240V
indoor Field wiring
outdoor
LEGEND
C11R, C12R Running capacitorF1S Surge arresterF1U FuseK1M Compressor relayL LiveM1C Compressor motorM1F Fan motorN NeutralQ1L Overload protectorX11A ConnectorX1M Terminal strip
Protective earth
NOTES
1 Refer to the nameplate for the power requirements.2 Wiring diagram nameplate size: width 110 x length 70.3 Nameplate material: wood free tack paper.4 Coat the reverse side with pressure sensitive adhesive.5 Refer to AS(Y)303002 unless otherwise specified.6 This drawing was drawn on CAD system.7 Make a slit on separate liner in vertical direction.
• Split Sky Air • Outdoor Units
17
• Outdoor Units • R-22 • R-C
7 Wiring diagram
7 - 1 Wiring diagram
R60CV1A9
3D045733
Power supply~50 Hz220V-240V
indoor Field wiring
outdoor
LEGEND
C11R, C12R Running capacitorF1S Surge arresterF1U FuseK1M Compressor relayL LiveM1C Compressor motorM1F Fan motorN NeutralS1T ThermostatX11A ConnectorX1M Terminal strip
Protective earth
NOTES
1 Refer to the nameplate for the power requirements.2 Wiring diagram nameplate size: width 110 x length 70.3 Nameplate material: wood free tack paper.4 Coat the reverse side with pressure sensitive adhesive.5 Refer to AS(Y)303002 unless otherwise specified.6 This drawing was drawn on CAD system.7 Make a slit on separate liner in vertical direction.
• Split Sky Air • Outdoor Units 22
• Outdoor Units • R-22 • R-C
23
18
8 Sound data
8 - 1 Sound pressure spectrum
R25CV1A9
4D029157A
Octave band center frequency (Hz)
Octa
ve b
and
soun
d pr
essu
re le
vel (
dB) (
0 dB
= 0
.000
2 μb
ar)
Location of microphone
NOTES
1 Measurement was taken in an anechoic room.2 The operation noise measuring method is in accordance
with JISC9612.3 Operating conditions:
Power source = 220-240 V, 50 Hzo------o H (A = 48) and o- - - -o L (A = 46)
4 Operation noise differs with operation and ambient conditions.
Approximate threshold hearing for continuous noise
R35CV1A9
4D000697C
Octave band center frequency (Hz)
Octa
ve b
and
soun
d pr
essu
re le
vel (
dB) (
0 dB
= 0
.000
2 μb
ar)
Location of microphone
NOTES
1 Measurement was taken in an anechoic room.2 The operation noise measuring method is in accordance
with JISC9612.3 Operating conditions:
Power source = 220-230V (L) or 240 V (H), 50 Hzo------o H (A = 49) and o- - - -o L (A = 48)
4 Operation noise differs with operation and ambient conditions.
Approximate threshold hearing for continuous noise
R50,60CV1A9
DW527-217F
Octave band center frequency (Hz)
Octa
ve b
and
soun
d pr
essu
re le
vel (
dB) (
0 dB
= 0
.000
2 μb
ar)
Location of microphone
NOTES
1 Measurement was taken in an anechoic room.2 The operation noise measuring method is in accordance
with JISC9612.3 Operating conditions:
Power source = 220-230V (L) or 240 V (H), 50 Hzo------o H (A = 55) and o- - - -o L (A = 54)
4 Operation noise differs with operation and ambient conditions.
Approximate threshold hearing for continuous noise
• Split Sky Air • Outdoor Units
19
• Outdoor Units • R-22 • R-C
9 Operation range
R25,35,50,60CV1A9
4D000888K
Outd
oor t
emp.
(°CD
B)
Indoor temp. (°CWB)
Cont
inuo
us o
pera
ton
Pull)
dow
n pe
riod
NOTES
The graph is based on the following conditions:
1 Equivalent piping length: 5m
2 Level difference: 0m
3 Air flow rate: high
• Split Sky Air • Outdoor Units 24
• Outdoor Units • R-22 • R-C
25
19
• Split Sky Air • Outdoor Units