VER
IFIED SOLUTIONS
BY H ALTO N
2
Halton SAFE
Table of contents1 System description 3
2 User Accounts 4
3 Main menu 7
3.1 Main menu - Change language 8
3.2 Main menu - Login and user accounts 8
3.3 Main menu - System status 9
3.4 Main menu - Footer 10
3.5 Main menu - Link buttons 10
3.6 Main Menu - Reset all alarms! 10
4 Settings and Installing 11
4.1 Controller 12
4.1.1 Fans 14
4.1.2 Fire alarm 14
4.1.3 External alarms 15
4.1.4 Controller wiring 16
4.2 Unit 17
4.2.1 Unit installations 19
4.2.2 Unit wiring 20
4.2.3 Unit address table 21
4.3 Damper 22
4.3.1 Damper wiring 24
4.4 Smoke detectors 24
4.4.1 Smoke detector wiring 25
4.5 Understanding zones 29
5 Dampers state and control 30
5.1 Link information and control 31
5.2 Damper information and control 32
5.3 Smoke detector information and control 35
6 Test dampers 36
6.1 Test timetable 37
6.2 Test pages 38
6.3 Test reports 39
7 Alarm dist and handling 41
7.1 Alarm log 42
8 Appendices 43
Halton SAFE central unit cabling and connection diagram 44
SAFE LINK Link unit wiring diagram / dampers wiring 45
SAFE LINK Link unit wiring diagram / Smoke wiring 46
Halton SAFE Controller and units Modbus and power connections 47
Setting the Halton SAFE LINK bus addresses 48
Halton SAFE system operation chart 49
Halton SAFE commissioning protocol 50
3
1 System description 3
2 User Accounts 4
3 Main menu 7
3.1 Main menu - Change language 8
3.2 Main menu - Login and user accounts 8
3.3 Main menu - System status 9
3.4 Main menu - Footer 10
3.5 Main menu - Link buttons 10
3.6 Main Menu - Reset all alarms! 10
4 Settings and Installing 11
4.1 Controller 12
4.1.1 Fans 14
4.1.2 Fire alarm 14
4.1.3 External alarms 15
4.1.4 Controller wiring 16
4.2 Unit 17
4.2.1 Unit installations 19
4.2.2 Unit wiring 20
4.2.3 Unit address table 21
4.3 Damper 22
4.3.1 Damper wiring 24
4.4 Smoke detectors 24
4.4.1 Smoke detector wiring 25
4.5 Understanding zones 29
5 Dampers state and control 30
5.1 Link information and control 31
5.2 Damper information and control 32
5.3 Smoke detector information and control 35
6 Test dampers 36
6.1 Test timetable 37
6.2 Test pages 38
6.3 Test reports 39
7 Alarm dist and handling 41
7.1 Alarm log 42
8 Appendices 43
Halton SAFE central unit cabling and connection diagram 44
SAFE LINK Link unit wiring diagram / dampers wiring 45
SAFE LINK Link unit wiring diagram / Smoke wiring 46
Halton SAFE Controller and units Modbus and power connections 47
Setting the Halton SAFE LINK bus addresses 48
Halton SAFE system operation chart 49
Halton SAFE commissioning protocol 50
1 System descriptionHalton Safe fire damper control unit can control up to 200
fire dampers and smoke detectors.
Safe control unit is extended with link units where fire
dampers and smoke detectors can be connected.
1-4 fire dampers and smoke detectors can be connected to
one link unit that has its own logic program.
Fire dampers and smoke detectors can be grouped to up
to 15 different groups, which allow to close only the group
where fire is detected.
Every fire damper and link unit can also be set to operate as a
separate group.
Fire dampers can be tested automatically by user defined
week schedule. System will write a test report based on
performed test, showing the operation of each fire damper.
System can be set up, operated and viewed using 5.7”
graphic display. Optionally a laptop computer can be
connected to perform the same operations using a browser
interface.
Each Safe control link unit has independent program logic.
Control and link units communicate with each other by
Modbus RTU protocol.
Control unit can be equipped with a backup battery for alarm
transmission in case of a power outage.
4
Halton SAFE
2 User Accounts1. Lookup
Password: no password
Auto login user with minimum rights. Allowed to see the overall view of system.
5
2. Service
Password: 59812
Allowed to see alerts on systems and acknowledge them
3. Maintenance
Password: 48627
Allowed to see test reports, modify minimum settings of system and define test times.
6
Halton SAFE
4. OEM_INSTALLERPassword: 962458
Allowed modify all device settings of system. (units, dampers, smoke detectors, fans, ext. alarm).
5. OEM_MaintenancePassword: ***
OEM reseller account can access hidden menus and values to allow full support to system.
7
3 Main menuThe main menu opens automatically when the Halton
SAFE screen is touched. The main menu page provides a
basic menu that allows viewing the system in more detail.
This page also lists the current state of the general alarms
and fan controls.
Navigation on sub menus:
To return to the main menu, press the Main Menu key at the top.
The Dampers states and Dampers test pages also have page navigation buttons.
With link buttons section you can access to system sub menus.
The main menu provides access to the fire damper and
smoke detector states and test pages via the dampers
states and control and test dampers icons.
Access to the settings page requires higher level privileges
than the basic user ID.
8
Halton SAFE
3.1 Main menu - Change LanguageA pop-up menu appears for available languages.
Select desired language from list and press change
button.
No user ID is needed for viewing and monitoring the
Halton SAFE central unit. The user IDs for deployment
and maintenance personnel are listed in the deployment
protocol.
For login press the ”key hole button”.
Current user information indicates current user name.
Users are:
Viewing - for viewing and monitoring dampers and smoke
detectors.
Service - for viewing, monitoring and alarm handling of
dampers and smoke detectors.
Maintenance - for viewing, monitoring, alarm handling and
minor settings of dampers and smoke detectors.
Installer - for all settings. Group handling and installation
features. See more about accounts from user accounts.
3.2 Main menu - Login and User Accounts
9
3.3 Main menu - System Status
System status shows overall information about the system.
Information in status:
System Status - Alarm
Contains information about system fire alarm.
States: = normal, = Acknowledge alarm, indicator blinks when alarm is unacknowledged.
System Status- Test
Contains information about test state.
States: = Currently not testing, = Currently one or more Zones are testing.
Link Units - Faults
Contains information about units Faults if there are one or more units on fault state.
States: = normal, = Acknowledge Alarm, indicator blinks when alarm is unacknowledged.
Dampers - Alarm
Contains information about Dampers Alarm State
States: = normal, = Acknowledge Alarm, indicator blinks when alarm is unacknowledged.
Dampers - Control
Contains information about Dampers Control.
States:
= All Control Closed, = All Control Opened, = Opened and Closed Control, = No active Dampers.
Dampers - State
Contains information about Dampers State.
States:
= All Dampers Closed, = All Dampers On middle, = All Dampers Opened, = Opened and Closed Dampers,
= Opened, on middle and Closed Dampers, = On middle and closed dampers,
= Opened and on middle Dampers, = No active Dampers.
Smoke Detectors - Alarm
Contains information about system fire alarm.
States: = normal, = Acknowledge Alarm, indicator blinks when alarm is unacknowledged.
Smoke Detectors - Service
Contains information about system fire alarm.
States: = normal, = Acknowledge Alarm, indicator blinks when alarm is unacknowledged.
Smoke Detectors - Reseting
Contains information about
States: = normal, = 1 or more Link units is resetting smoke detectors.
Fan Controls - 1-3
Contains information about Fan Controls states
States: = Fan control is inactive, = Fan control is active.
10
Halton SAFE
3.4 Main menu - FooterFooter contains most basic information about Safe controller.
On Left - Manufacturer and product name.
On Middle - Controller main version, sub version and current user.
On Right - System date and time.
By pressing reset all button system will confirm your
request.
3.5 Main menu - Link ButtonsNavigate through link buttons section to access system
sub menus.
Dampers States and Control - Access dampers and
smoke detectors management pages.
See more from dampers states and control
Test Dampers - Access to dampers test settings and
control page’s. See more from test dampers
Settings - Access to SAFE devices settings. See more
from settings
Alarm list and handling - Access to alarm logs and alarm
handling. See more from alarm list and handling
3.6 Main Menu - Reset All Alarms!If there are one or more alarms in system you can
acknowledge all from controller’s front page.
NOTE!! Sufficient user privileges required to reset all
alarms.
NOTE!! Always make sure that there’s no fire or smoke
in the building (the alarm was caused by a fault or device
malfunction.)
Never reset alarms if the cause of alarms is unknown.
By pressing Yes-button system will acknowledge all alarms
in controller.
If there are still active alarms the system will notify about
the alarms on screen.
OR
If everything seems to be fine the system will start its Restore Sequence. NOTE!! The restore sequence will
take some time.
11
Settings are divided to 6 different sections.
1. Unit Settings, Assign units in to use.
2. Dampers Settings, Assign units’ dampers into use and select zones.
3. Smoke Detectors Settings, Assign units’ smoke detectors into use and select zones.
4. Fan Control Relay Settings, Assign how fan relays are affect by zone alarm and zone testing
5. External Fire Alarm Settings, Assign which zones common fire alarm affects when triggered.
6. External Zone Connections, Assign external alarm pins.
Restarting system:On Settings Main Screen is also
= This will Restart whole system. NOTICE!!, system will store all information in one hour loop.
Restart system will always store all information when its initiated. Settled information may be lost on that time window if
system lose its voltage support or other malfunction.
4 Settings and Installing
If there are still active alarms the system will notify about
the alarms on screen.
OR
If everything seems to be fine the system will start its Restore Sequence. NOTE!! The restore sequence will
take some time.
12
Halton SAFE
Safe controller’s operating voltage is 230 VAC. Controller
will be delivered with grounded socket connection
cord which also works as controller disconnect device.
NOTE!! Remove or further connect Extension cord only if
disconnect switch is nearby.
Safe controller consists from I/O and CPU unit (or as
screen unit), which are installed to control center cabinet.
CPU unit contains 5.7” touch screen display, which is
installed to cabinet’s front plate.
4.1 Controller
CPU-unit can be installed on top of or right next to the I/O-
unit. It can also be installed to a distance from I/O-cabinet
to different room space.
The white cover is installed with four screws after installing
cables to I/O unit. If CPU cabinet is installed on top of I/O
cabinet, CPU cabinet’s install plate needs to be installed
with I/O cabinet’s cover with these screws also.
Installation and featuresMany inputs and outputs can be set in to SAFE controller.
Controller’s relay outputs provide system state that can
be used to transfer alarms, for example into building
automation system.
Also fans’ control permits can be routed through controller,
which allows ventilation system to stop when system is
on alarm or test state. Relays connection information is
described below.
Point NameRelay moduleConnectors Numbers
Explanation, Relay is active when,
Run permission to Fan 1 A1,A2 One of assigned Fire zone alarms.
Run permission to Fan 2 A3,A4 One of assigned Fire zone alarms.
Run permission to Fan 3 A5,A6 One of assigned Fire zone alarms.
Common Fire Alarm A7,A8 Any of common alarm is active
Link units common fault Alarm B1,B2 Any of units don't have connection to controller
Dampers common
Alarm
B3,B4 Any of dampers is on Alarm or fault state.
Smoke detectors common service Alarm B5,B6 Any of smoke detectors has service alarm.
Smoke detectors common Alarm B7,B8 Any of smoke detectors has Alarm.
NOTE!! If fan supply voltage exceeds 50 volts the fan relay 3 can’t be used, due to risk of electric shock and system malfunction.
An alarm affecting the fire zones can also be set. Connection information is description below.
13
More about alarm and control handling in Fans settings, Fire alarm settings
and External alarm settings.
SAFE controllers cabling and wiring instructions are presented in controller wiring.
Point NameExternal Alarms Connectors Numbers
Explanation, External alarm that closes,
External Alarm 1 C1,I1 Fire Zone 1
External Alarm 2 C2,I2 Fire Zone 2
External Alarm 3 C3,I3 Fire Zone 3
External Alarm 4 C4,I4 Fire Zone 4
External Alarm 5 C5,I5 Fire Zone 5
External Alarm 6 C6,I6 Fire Zone 6
External Alarm 7 C7,I7 Fire Zone 7
External Alarm 8 C8,I8 Fire Zone 8
External Alarm 9 D1,J1 Fire Zone 9
External Alarm 10 D2,J2 Fire Zone 10
External Alarm 11 D3,J3 Fire Zone 11
External Alarm 12 D4,J4 Fire Zone 12
External Alarm 13 D5,J5 Fire Zone 13
External Alarm 14 D6,J6 Fire Zone 14
External Alarm 15 D7,J7 Fire Zone 15
External Fire Alarm E1,J8 All
14
Halton SAFE
Each fan control relay can be set to switch off when user defined fire zone is alerting or system is testing fire zones
dampers.
4.1.1 Fans
External fire alarm input can be set to affect defined fire zone.
When fire alarm is triggered, the system will cause same kind of function as zone alarm triggers to defined zones.
Connector pins can also be set to normally open or normally closed (default value is normally closed).
4.1.2 Fire Alarm
15
External zone alarm connector pins for each zone can be set to normally open or normally closed (default value is
normally open).
4.1.3 External Alarms
16
Halton SAFE
4.1.4 Controller Wiring
17
Up to 50 link units can be connected into system. Every unit must be activated after it has been connected into SAFE Controller. Each link unit has its own individual parameters.
Parameters:
4.2 Link Unit
- Type: Select unit type, see below selecting types.- Alarm: Unit fault.- Alarm type: Unit fault message: 1. Unit is not in use 2. Communicating, everything is fine with this unit and it is communicating with controller. 3. Bus fault, controller can’t connect with this unit. Usually wrong unit address or cabling issue. 4. Version mismatch, link unit version needs to match the controller.- Version: Current version of the unit.- Port: Modbus communication port number, default is 3.- Address: Modbus address of the unit, default address is unit number + 10, See more on unit installation.
18
Halton SAFE
Selecting and changing Type parameter:
1. Click a white value field on unit row.
Note - units number must match the address, see more on unit installation.
2. System will open type selection settings:
3. Select type:
4. Accept unit type change by pressing change or cancel change by pressing cancel.
Clearing Unit Fault alarm.Unit fault alarms can be acknowledged by pressing Unit FAULT button.
Available types
Type Explanation
Not In Use Defines to system that any unit is not connected
Link Defines to system that Link unit is on use
THC24-MOD Defines to system that THC24-MOD unit is on use
19
Up to 50 link units can be connected to the system.
Operating Voltage:System contains a power unit for link units. The power unit is a 260VA toroidal transformer, which transforms the line voltage into 24 AC voltage. Link unit uses 24VAC power, connected to Units connectors P1 and G0. Power supply can be chained to other units from same connectors.One transformer can be connected to up to 6 units depending dampers what are connected to link units.
4.2.1 Link Unit Installation
Recommended cable is MMJ 3x2.5 S between power supply and link units.
With 260VA you may connect maximum of 6 units per support line depending on the length and diameter of the support cable.
Data Bus:Units communicate with controller via Modbus RTU Bus. Modbus RTU need to be connected with bus topology.Data bus has to be chained from unit to unit.
Data Bus address selection:Each link unit is identified by bus address. Each link unit must have an individual bus address for controller to find all units.Unit address is defined by DIP switch on Units circuit board.See unit address table how DIP switches are set.
Switch Number 1 2 3 4 5 6
Selection Value 32 16 8 4 2 1
For example:
If DIPs number 2, 3 and 5 are switched ON, unit address is 16 + 8 + 2 = 26. The units is
therefore number 16.
Refer to units address table how each unit DIP switch is set.
Cable has to be shielded type twisted pair cable. e.g. cable is 2x2x0.5mm shielded twisted pair see example connection setup from unit wiring.
DIP switch is a binary selector; the address is the sum of values of the switches in ON position.Address must be between 11 and 60. Address 11 is Unit 1 and address 60 is Unit 50.
Address can be marked to link unit cover.
20
Halton SAFE
4.2.2 Link Unit Wiring
21
4.2.3 Link Unit Address Table Link Units devices bus address correspond to the DIP switch settings
Unit NumberDip 1
32
Dip 2
16
Dip3
8
Dip4
4
Dip5
2
Dip6
1
1 1 1 1
2 1 1
3 1 1 1
4 1 1 1
5 1 1 1 1
6 1
7 1 1
8 1 1
9 1 1 1
10 1 1
11 1 1 1
12 1 1 1
13 1 1 1 1
14 1 1
15 1 1 1
16 1 1 1
17 1 1 1 1
18 1 1 1
19 1 1 1 1
20 1 1 1 1
21 1 1 1 1 1
22 1
23 1 1
24 1 1
25 1 1 1
26 1 1
27 1 1 1
28 1 1 1
29 1 1 1 1
30 1 1
31 1 1 1
32 1 1 1
33 1 1 1 1
34 1 1 1
35 1 1 1 1
36 1 1 1 1
37 1 1 1 1 1
38 1 1
39 1 1 1
40 1 1 1
41 1 1 1 1
42 1 1 1
43 1 1 1 1
44 1 1 1 1
45 1 1 1 1 1
46 1 1 1
47 1 1 1 1
48 1 1 1 1
49 1 1 1 1 1
50 1 1 1 1
22
Halton SAFE
Up to 4 dampers can be connected to each link unit.
Each damper has individual parameters.
4.3 Dampers
Unit Parameters:- Unit Number and Type: Unit number and type can be changed.
Damper Parameters:- Location: Current location of dampers. Location text can contain any information about damper position or state. Location text will be shown on Alarms clear text and graphic displays.- Zone: Current zone of dampers. Refer to section understanding zones of this manual. When a damper sends an alarm it triggers alarm state to selected zone.
Changing Location:The location text can be changed as follows:
1. Click Location text.
2. select programming from pop-up menu.
23
3. A programming menu will appear for the text field to be selected. ( NOTICE: Also other parameters are visible but may not be changed.)
3. Modify desired text on the text field:
3. Press Change button from left side of the window to save changed text. (NOTE: Changes will not be saved unless you press Change button). If you don’t want to modify text go to next step.
4. Press Picture Open button, this will take you back.
Changing Zone And Type
1. Click Zone or Type value field.
2. Zone or type can be selected
3. Select desired value from list and press Change for saving selected state or press Cancel.
24
Halton SAFE
4.3.1 Damper Wiring
25
Up to 4 smoke detectors can be added to each link unit.
Each smoke detector has its own individual parameters, depending on Safe controller version.
4.4 Smoke Detectors
Unit Parameters:- Unit number and type: View unit number and type. Unit type can be changed.
Smoke detector parameters:- Location: Shows detector current Location text. Location text will be shown on alarms clear text and graphic displays.- Zone: Shows detector current zone. See more in understanding zones. When detector is alarming it triggers alarm state to selected zone.
26
Halton SAFE
Changing Location:Location text can be changed (sufficient user rights required).
1. Click Location text.
2. Select programming from pop-up menu.
3. Select Text field from the programming menu. ( NOTE: Other parameters are visible but may not be changed)
3. Change desired text into text field.
3. Press Change button from left side of the window to save changed text. (NOTE: changes will not be saved unless you press Change button).
4. Press Picture Open button to go back.
5. All done.
27
Changing zone and type
1. Click zone or type value field.
2. Zone or type can be selected
3. Select desired value from the list and press Change for saving or Cancel.
28
Halton SAFE
4.4.1 Smoke Detector Wiring
29
Each device must be added to one of the fire zones. Device can affect multiple fire zones or multiple fire zones can affect to device control.Fire zone connections are presented on each device setting page.
4.5 Understanding Zones
Available Fire Zones Fire Zone Name
Explanation: Determines that this device affects to,
ALL All others devices is system
Not in Use This device is not in use
Unit other devices inside unit
Single Device is just alarming device in system
Row Device will affect same units and same damper position as selected device. ( Special selection to smoke detectors )
Zones 1-15 all devices what is defined into same zone as selected devices zone.
With these zones system can be built with many different variations of fire zones
Zones
With zones you can group one or more devices into
department section or into fire zone. When one of the
devices sends an alarm inside of a zone, whole zone will
be triggered to alarm state.
Zones can be closed by external alarm, which can be
connected to controller.
All devices can be split into multiple groups. Zone
grouping is assigned into end device, like fire damper and
smoke detector.
See example picture how units, dampers and smoke
detectors can be assigned into example building
Example Picture
30
Halton SAFE
These pages contain information about control, status and alarms from dampers, smoke detectors and link. One page can contain 16 dampers and smoke detectors.States are displayed as table. Dampers and smoke detectors are grouped by Unit.
From left to right:
First is unit information and fault alarm.Second is damper control, status and alarm information. On the right side are smoke detector information, alarm and resetting button.
5 Dampers state and controlReading information:
• Unit number tells information about where dampers and smoke detectors are connected.
• Dampers position tells information about where it is physically connected.
• Smoke detectors position tells information about where it is physically connected.
See more information about how your system can be configured and how to find physical connections from settings section.
Dampers State And Control
31
c
All information is divided into units that contain dampers
and smoke detectors.
Information:
For units you can see only unit numbers on state and
control page.
Control:
Unit fault alarm button will appear on page when unit is in
fault state.
Unit fault will trigger when there are one or more
problems within units handling, see more in unit settings.
Press unit fault button to acknowledge fault alarm. Button
will stop flashing when alarm is acknowledged.
On unit fault state dampers will set to error state and
smoke detectors alarm is set to normal state. See more
about dampers or smoke detectors.
5.1 Link Information and control
32
Halton SAFE
5.2 Dampers Information and Control
Information:
- Position: Displays damper location in unit. This is physical connection between unit and damper. See more
from damper settings.
- Location: Displays assigned text from damper alarm.
- Control: Displays the status of current control. Status can be:
- Close: Damper is controlled to close
- Open: Damper is controlled to open
- Not In Use: Damper is not in use
- ERROR: There is an ERROR state, like unit fault.
- State: Displays the status of the damper limit switches. Status can be:
- Closed: Damper is closed
- OnMidd (On Middle): Damper is between limit switches.
- Opened: Damper is opened.
- Fault: Both limit switches are active. This will be identified as error state and alarm will be triggered.
- Alarm: Displays the status of the damper alarm. Status can be:
- Normal: Damper is functioning normally
- Alarm: Damper hasn’t reached the end or open switch in period of alarm time, when control state
is changed or damper has been closed by malfunction or fire fuse has been burnt.
Damper has 160 seconds time to open and 30 seconds time to close. Alarm box
text will blink if alarm is triggered.
Damper will not be opened until damper alarm is acknowledged.
- Fault: See above fault
33
Controlling manually by hand:Each damper can be opened or closed manually. Damper cannot be controlled by hand if damper is on alarm
state, not in use or on fault state.
NOTE!! If damper is left to hand value, damper test program will ignore this damper.
For security reasons hand value for damper is always disabled, if current damper or zone is on alarm state.
For changing control value by hand
Press dampers control box.
It will open a window where either open or close can be selected.
Select value from list and press change for hand value or cancel.
Hand status will be indicated with blue borders around the control box.
Hand Value
34
Halton SAFE
For changing control value from hand value back
to Auto value.
Press damper control box.
A window will be opened where either open or close can
be selected. Press auto button.
Blue borders will disappear around control box to indicate
auto status when damper is returned to auto value.
For Acknowledging Damper alarm:
Press damper Alarm box
It will open a window with multiple selections for alarm
box. Selections are:
- Alarm acknowledge: For clearing damper alarm
- OTHERS ARE NOT REQUIRED.
Alarm box text stops blinking and alarm is acknowledged
when alarm acknowledge is pressed. Damper will try to
open again after alarm is acknowledged.
If problem on damper is not solved then alarm will be
triggered again.
35
Information:
- Position: Displays smoke detector location in unit.
This is physical connection between unit and smoke
detector. See more from smoke detectors settings.
- Alarm: Displays the status of the smoke detector
alarm. Status can be:
- Normal: Smoke detector is functioning
normally
- Service: Smoke detector has triggered service
state
- Alarm: Smoke detector has triggered alarm
state
- Shortcut: Line between smoke detector and
unit is on shortcut
- Broken line: Line between smoke detector and
unit is not connected properly or 2.2kOhm end
resistor is not installed into smoke
detector.
- Reseting: Unit is resetting smoke
detectors. Reset function cuts current from
smoke detectors for 10 seconds.
NOTE!! Reset function will reset all smoke detectors
on this unit.
Controlling:After alarm is triggered on one of units smoke detectors,
reset SD button will appear. Pressing the button all units’
smoke detectors can be reset.
If alarm reappears, smoke detector is still dirty from
particles or dirt and it needs to be cleaned first.
5.3 Smoke Detector information and Control
36
Halton SAFE
6 Test DampersFrom this page you can test dampers programmatically.
Test can be initiated by pressing test all now button, by
timetable or pressing zone test buttons.
Test program:
Test program is split into same zones as dampers and
smoke detectors are assigned. When zone test program
is initiated, programs steps are:
1. Programs wait cancellation for 5 seconds if test is
initiated by accident
2. Program will initiate test to each damper
assigned to the zone currently being tested. If the zone
doesn’t have any dampers assigned then the test will
not be initiated.
3. Zone test is stopped after all dampers of the
zone have finished the test program.
4. The system writes test report to hard drive after
zone test is stopped.
NOTE: You may stop a started test program any time by
pressing zone test button when the button is green.
One damper test protocol:
Test protocol will run for all initiated dampers.
NOTE!! Test protocol will not test dampers that are in
hand state.
Sequence is:
1. Close damper manually with hand state.
2. Check that damper will reach the end state.
3. Open damper manually with hand state.
4. Check that damper will reach the open state!
5. Remove hand value.
6. Successful - damper has completed the test protocol.
Test Timetable:
Test can be assigned to start according to time schedule.
The test schedule can be viewed and changed by pressing
the clock symbol.
Test report:
Test reports are divided by zones. If zone test is run,
reports can be found under view test reports buttons.
Fan Control:
Fan controls are turned off on test program, if fan is
assigned stop by currently running zone test.
Test pages:
Each damper can be set to run its test program or stop
current test.
37
6.1 Test Timetable
With timetable you may schedule your test(s) to start at
specific time. Timetable is one week timetable with 6
events on each day.
On the left are days and on the table are those six events
for each day.
To save edited events press change button. Cancel button
will ignore all changes. You can copy one day events to
another by copy events button.
- Time can be changed by the keypad. To clear the event
press C- button below the keypad.
- Select zone to be tested. Selection “All” will test all the
zones at the same time.
Event will be confirmed by pressing change button over
editing section. Cancel button will cancel editing.
Changing timetable:
Change events by pressing the slot from table. The event
table will be sorted automatically after events have been
added, removed or modified.
Event editing window opens when a slot is selected.
Copy Events:
Select the time schedule source from the left side and
destination from the right side.
Save changes by pressing copy button. Cancel button will
cancel editing.
38
Halton SAFE
6.2 Test Pages
Dampers control, state and test status can be viewed
from the test pages. Dampers can also be tested
individually.
Note that testing damper individually will not write
anything to test reports.
Test status
Contains test information.
States:
Waiting - Damper is waiting indication to test,
Testing! - Running testing protocol
Test OK! - Test is passed
Fault - Damper failed the test and is set to alert state
Canceled - Test has been canceled for this damper
Not in use! - Damper is not in use.
Test now button
Indicates damper being tested when the button is green.
- Press button to start test for this damper. Testing can be
cancelled by pressing the button again.
39
6.3 Test Reports
Test reports from one zone can be viewed. Go to test
dampers main page to select zone. Three reports per day
are stored on disk. New report will always appear after
zone test has been ended.
Finding report:
Test reports can be searched using the year, month and
day selectors.
For example select day for desired report.
Number defines the order for the days reports; 0 is latest
and 2 is earliest.
After day and number selection press show report button
to view report.
40
Halton SAFE
Dampers are separated with ‘**********’ line.
First Line is displaying Damper point id and state of
damper test. States can be:
- Waiting: For some reason after test damper is still on
waiting state of test. It might be considered as fault state.
- TESTING: For some reason after test damper is still on
waiting state of test. It might be considered as fault state.
- Test Succeeded: Test sequence for damper has been
succeeded.
- Fault: Damper can’t be tested. Notation about Fault will
be written to Notice line.
- CANCELED: Damper test sequence has been canceled
by User.
- Not In Use: Damper is not in use.
Second line contains information about dampers close
and open times.
- Opentime: last open time, how much time damper
took from close position to open position. (Time can be
other than on test sequences)
- Closetime, last close time, how much time damper
took from open position to close position. (Time can be
other than on test sequences)
- Open timestamp: last time when damper reached
open position. Format is hhmmss, hours,
minutes, seconds. (Time can be other than on test
sequences)
- Close timestamp: last time when damper reached
to close position. Format is hhmmss, hours, minutes,
seconds. (Time can be other than on test sequences)
Third line includes additional information about the test,
usually in case of a fault state. Additional information can
be:
- NOTICE: Damper is still waiting for testing!
- NOTICE: Damper is still testing its self!
- NOTICE: Fault! Damper is on Alarm state!
- NOTICE: Fault! Damper is on Hand value!
- NOTICE: Fault! Damper is on UKNOWN STATUS!
Report:Report will show start and end time and all dampers that are connected to selected zone report.
41
This shows alarms, unacknowledged alarms, active
alarms and alarm log.
After resetting all alarms there might be a check for any
active alarms. Active alarm means that one of the alarms
hasn’t been able to recover from the alarm state, for
example there is still damper mismatch between control
and state or fire alarm is still on.
Alarms lists inspection:
Alarm lists are not sorted by units or dampers. They are
sorted by their point id. Point id is system’s identification
for alarms.
Reading point identification:
Point id is sectioned to two or three parts. Last sections
indicate the alarm type. Sections are separated with
underline ( _ ). By combining these sections you can find a
specific alarm.
First part - location identifier: indicates where
physical/programmatic alarm is located.
Locations are:
- EXTERNAL: external physical alarm to controller, see
more info on external alarms and fire alarm.
- UNIT01-50: programmatic alarm for units.
Second part - device identifier: indicates which device
is alarming.
- FD01-04: Damper alarms on unit. The number indicates
damper position in unit.
- SD01-04: Smoke detector alarms on unit. The number
indicates smoke detector position in unit
- UNIT: This is unit alarm on controller
Third part (Type Part) - type identifier of what specifies
the alarm.
- FAULT: This is unit’s fault alarm.
- ALARM: This is a damper conflict alarm or smoke
detector alarm.
- ALARM1-15: This is an external alarm. Number indicates
zone number.
- FIREALARM: This is controller’s fire alarm.
All alarms:
Shows list of all available alarms.
Unacknowledged alarms:
Shows list of alarms that haven’t been acknowledged.
Alarms can be in not active state.
Unacknowledged alarms:
Shows list of alarms that are acknowledged but they are
still active.
7 Alarm List and Handling
42
Halton SAFE
Alarms logs inspection:
To access the alarm log select alarm selection from the
drop down menu.
This shows date, time and state when one of the alarms
has occurred. See more in Alarm Log section.
7.1 Alarm Log
When alarm state changes it is stored in this log. Alarms
appear in chronological order and latest log entry is on top
of the list.
Sorting
You can sort the list by time, user or point name (Point id).
There’s also a selection to view or hide Point text (damper
or smoke detector location).
Data list
Each row represents one log entry.
One row indicates the time when entry has been made,
user name who changed it (if blank it is a system entry),
event where alarm state has been set, point name for
identification, general information about from where to
where point state has been set.
43
8 Appendices
Halton SAFE central unit cabling and connection diagram 44
SAFE LINK Link unit wiring diagram / damper wiring 45
SAFE LINK Link unit wiring diagram / smoke wiring 46
Halton SAFE controller and unit Modbus and power connections 47
Setting the Halton SAFE LINK bus addresses 48
Halton SAFE system operation chart 49
Halton SAFE commissioning protocol 50
APPENDIX 1: Halton SAFE central unit cabling and connection diagram
Halton SAFE Link unit wiring diagram / Damper wiring
Halton SAFE Link unit wiring diagram / smoke detector wiring
Halton SAFE controller and unit Modbus and power connections
LINKnro
DIP 132
DIP 216
DIP 38
DIP 44
DIP 52
DIP 61
1 1 1 1
2 1 1
3 1 1 1
4 1 1 1
5 1 1 1 1
6 1
7 1 1
8 1 1
9 1 1 1
10 1 1
11 1 1 1
12 1 1 1
13 1 1 1 1
14 1 1
15 1 1 1
16 1 1 1
17 1 1 1 1
18 1 1 1
19 1 1 1 1
20 1 1 1 1
21 1 1 1 1 1
22 1
23 1 1
24 1 1
25 1 1 1
26 1 1
27 1 1 1
28 1 1 1
29 1 1 1 1
30 1 1
31 1 1 1
32 1 1 1
33 1 1 1 1
34 1 1 1
35 1 1 1 1
36 1 1 1 1
37 1 1 1 1 1
38 1 1
39 1 1 1
40 1 1 1
41 1 1 1 1
42 1 1 1
43 1 1 1 1
44 1 1 1 1
45 1 1 1 1 1
46 1 1 1
47 1 1 1 1
48 1 1 1 1
49 1 1 1 1 1
50 1 1 1 1
1 = on blank = off
APPENDIX 3: DIP switch settings corresponding to the SAFE LINK control unit bus address
APPENDIX 4: Halton SAFE system operation chart
SAFE commissioning protocol
Date: ______/______/20______
Site:
Site address:
Adjustment chart ID:
Setting the timed test programme and fan groups:
Test start: Not used Internal clock External clock, from where: ______
Test day setting: MON. TUES. WED. THURS. FRI. SAT. SUN.
Fan group setting, example: All, Group1, etc.
FAN1 FAN2 FAN3
Test time setting, time:
Tester’s name:
Installation company:
Contact information:
Date and signature:
Page 1 (5)
Halton SAFE user identification codes:
LOOKUP
Viewing rights
List of the fire dampers
Alarm list
Control rights
List of the fire dampers
Manual drive on/off
Reset alarm
No password
SERVICE
Service personnel
Same rights as for LOOKUP
Additional rights
Test report
Fire damper testing
Password 20127
INSTALLER
Installation person
Same rights as for SERVICE
Additional rights
Making settings
From the Settings page
Password 01473
Alarms:
Shared fire damper alarm: Not used Shared alarm – where to?
Shared smoke detector alarm: Not used Shared alarm – where to?
Not used Shared alarm – where to?
Halton SAFE LINK shared alarm: Not used Shared alarm – where to?
External shared fire damper alarm: Not used Shared alarm – where to?
Inbound external fire alarm: Not used Shared alarm – where to?
Halton SAFE LINK test:Number Location Tested
OK/fault:Number Location Tested
OK/fault:01 2602 2703 2804 2905 3006 3107 3208 3309 3410 3511 3612 3713 3814 3915 4016 4117 4218 4319 4420 4521 4622 4723 4824 4925 50
Notes:
SAFE commissioning protocol
SAFE commissioning protocolPage 2 (5)
Fire damper and smoke detector test:Fire damper Smoke detector
ID Location Tested OK/fault:
ID Location Tested OK/fault:
PP01 SD01PP02 SD02PP03 SD03PP04 SD04PP05 SD05PP06 SD06PP07 SD07PP08 SD08PP09 SD09PP10 SD10PP11 SD11PP12 SD12PP13 SD13PP14 SD14PP15 SD15PP16 SD16PP17 SD17PP18 SD18PP19 SD19PP20 SD20PP21 SD21PP22 SD22PP23 SD23PP24 SD24PP25 SD25PP26 SD26PP27 SD27PP28 SD28PP29 SD29PP30 SD30PP31 SD31PP32 SD32PP33 SD33PP34 SD34PP35 SD35PP36 SD36PP37 SD37PP38 SD38PP39 SD39PP40 SD40PP41 SD41PP42 SD42PP43 SD43PP44 SD44PP45 SD45PP46 SD46PP47 SD47PP48 SD48PP49 SD49PP50 SD50
SAFE commissioning protocolPage 3 (5)
Fire damper and smoke detector test:Fire damper Smoke detector
ID Location Tested OK/fault:
ID Location Tested OK/fault:
PP51 SD51PP52 SD52PP53 SD53PP54 SD54PP55 SD55PP56 SD56PP57 SD57PP58 SD58PP59 SD59PP60 SD60PP61 SD61PP62 SD62PP63 SD63PP64 SD64PP65 SD65PP66 SD66PP67 SD67PP68 SD68PP69 SD69PP70 SD70PP71 SD71PP72 SD72PP73 SD73PP74 SD74PP75 SD75PP76 SD76PP77 SD77PP78 SD78PP79 SD79PP80 SD80PP81 SD81PP82 SD82PP83 SD83PP84 SD84PP85 SD85PP86 SD86PP87 SD87PP88 SD88PP89 SD89PP90 SD90PP91 SD91PP92 SD92PP93 SD93PP94 SD94PP95 SD95PP96 SD96PP97 SD97PP98 SD98PP99 SD99PP100 SD100
SAFE commissioning protocol Page 4 (5)
Fire damper and smoke detector test:Fire damper Smoke detector
ID Location Tested OK/fault:
ID Location Tested OK/fault:
PP101 SD101PP102 SD102PP103 SD103PP104 SD104PP105 SD105PP106 SD106PP107 SD107PP108 SD108PP109 SD109PP110 SD110PP111 SD111PP112 SD112PP113 SD113PP114 SD114PP115 SD115PP116 SD116PP117 SD117PP118 SD118PP119 SD119PP120 SD120PP121 SD121PP122 SD122PP123 SD123PP124 SD124PP125 SD125PP126 SD126PP127 SD127PP128 SD128PP129 SD129PP130 SD130PP131 SD131PP132 SD132PP133 SD133PP134 SD134PP135 SD135PP136 SD136PP137 SD137PP138 SD138PP139 SD139PP140 SD140PP141 SD141PP142 SD142PP143 SD143PP144 SD144PP145 SD145PP146 SD146PP147 SD147PP148 SD148PP149 SD149PP1 50 SD150
Fire damper and smoke detector test:Fire damper Smoke detector
ID Location Tested OK/fault:
ID Location Tested OK/fault:
PP151 SD151PP152 SD152PP153 SD153PP154 SD154PP155 SD155PP156 SD156PP157 SD157PP158 SD158PP159 SD159PP160 SD160PP161 SD161PP162 SD162PP163 SD163PP164 SD164PP165 SD165PP166 SD166PP167 SD167PP168 SD168PP169 SD169PP170 SD170PP171 SD171PP172 SD172PP173 SD173PP174 SD174PP175 SD175PP176 SD176PP177 SD177PP178 SD178PP179 SD179PP180 SD180PP181 SD181PP182 SD182PP183 SD183PP184 SD184PP185 SD185PP186 SD186PP187 SD187PP188 SD188PP189 SD189PP190 SD190PP191 SD191PP192 SD192PP193 SD193PP194 SD194PP195 SD195PP196 SD196PP197 SD197PP198 SD198PP199 SD199PP200 SD200
SAFE commissioning protocolPage 5 (5)
www.halton.com