l Beginning with DeltaV v10.3.1, the system counts a maximum of 1 DST per FOUNDATION fieldbus (Ff) device referenced in the DeltaV control strategy.– Multiplexed function blocks will require only 1 DST.– A Ff device with one/multiple function blocks referenced in
one/multiple DeltaV control modules will require only 1 DST.– Existing DeltaV Ff customers will have their available DST
counts incremented when migrating to v10.3.1.
1 DST!1 DST! 1 DST!1 DST!
SS--series hardware in v11series hardware in v11SS--series hardware in v11series hardware in v11
New H1 with Integrated Segment PowerNew H1 with Integrated Segment PowerNew H1 with Integrated Segment PowerNew H1 with Integrated Segment Power
Foundation FieldBusFoundation FieldBusFoundation FieldBusFoundation FieldBusl Simplified installation
– Eliminate segment Power design and hardware– Use standard Bulk 24 VDC power to H1 Card– Redundant Power with Redundant H1 Cards– Reduced footprint– Simplified segment wiring– Enhanced segment diagnostics
Foundation FieldbusFoundation FieldbusFoundation FieldbusFoundation FieldbusBEFORE NOW
DeltaV makes Fieldbus Easy
- 2 powered H1 segments- Isolated power- 450 mA per segment - Fully redundant
Simplified H1 Segment installationSimplified H1 Segment installationSimplified H1 Segment installationSimplified H1 Segment installationl Both H1 and H1 with integrated power are
available with S-series I/O– Use Integrated power H1 card for safe area
installations of FF devices.– Use IS barrier on segment trunk with integrated power
H1– Implement FISCO and FINICO with non-powered H1
and proven in use solutions.
l Both H1 and integrated power H1 have the same functional capacity:– 2 segments per card– 16 devices per segment (total 32)– Execute DeltaV function blocks within Macro cycle
H1 Card with Integrated Power serves Zone 2 H1 Card with Integrated Power serves Zone 2 Devices (Ex Devices (Ex nLnL) via Segment Protector) via Segment ProtectorH1 Card with Integrated Power serves Zone 2 H1 Card with Integrated Power serves Zone 2 Devices (Ex Devices (Ex nLnL) via Segment Protector) via Segment Protector
Trunk 28-30 VDC 400 mA max.Ex nA
Spurs Ex nL Spurs Ex nL
Terminator switchbuilt in
H1 Card with Integrated Power serves Zone 2 H1 Card with Integrated Power serves Zone 2 Devices (Ex Devices (Ex nLnL) via Segment Protector) via Segment ProtectorH1 Card with Integrated Power serves Zone 2 H1 Card with Integrated Power serves Zone 2 Devices (Ex Devices (Ex nLnL) via Segment Protector) via Segment Protector
H1 Card with Integrated Power serves Zone 1 H1 Card with Integrated Power serves Zone 1 and Zone 0 Devices (Ex and Zone 0 Devices (Ex iaia) via Field Barriers) via Field BarriersH1 Card with Integrated Power serves Zone 1 H1 Card with Integrated Power serves Zone 1 and Zone 0 Devices (Ex and Zone 0 Devices (Ex iaia) via Field Barriers) via Field Barriers
Trunk 28-30 VDC 400 mA max.Ex e
Spurs Ex ia Spurs Ex ia
Terminator switchbuilt in Exe Parts are all Covered
H1 Card with Integrated Power serves Zone 1 H1 Card with Integrated Power serves Zone 1 and Zone 0 Devices (Ex and Zone 0 Devices (Ex iaia) via Field Barriers) via Field BarriersH1 Card with Integrated Power serves Zone 1 H1 Card with Integrated Power serves Zone 1 and Zone 0 Devices (Ex and Zone 0 Devices (Ex iaia) via Field Barriers) via Field Barriers