Daikin 8‐Zone Multi‐Split System
Key Points of the Installation Process
© 2012 Daikin ACSlide 2
• Installation Considerations
• Outdoor Unit
• Indoor Units & Controls
• Branch Provider Units
• 8‐Zone Selection Tool
• Refrigerant Piping
• REFNET Fittings
• Installation Examples
• Start Up Checklist
Topics
© 2012 Daikin AC
Installation Considerations
© 2012 Daikin ACSlide 4
Tools & Support
8‐Zone Selection Tool
Manuals
Daikin eQuip App
Product Catalog
© 2012 Daikin ACSlide 5
Daikin Tools for Install
© 2012 Daikin ACSlide 6
750 – 1000 PSI
Additional Tools for Install• Metric tools (hex key set and socket set) are required when
installing or servicing Daikin RLC units• Nitrogen regulator capable of measuring up to 700 plus PSI is
necessary for installing Daikin RLC units
Metric Hex Key Set
Metric Socket Set
© 2012 Daikin ACSlide 7
• Compatible with all HFC Refrigerants• Excellent anti‐wear properties• Better solubility with process fluids• Superior Resistance to Cap tube blockage• Better lubricity• Optimal for non‐drier systems• Very Hygroscopic but with no hydrolysis• Moisture easily removed
PolyVinylEther Oil (PVE)
PVE w/ drier
PVE w/o drier
© 2012 Daikin ACSlide 8
• Label the indoor units A, B, C, D, etc. as appropriate
• Daikin does not have preference regarding install order
• Important for wiring and piping
• Piping and wiring must match
• If the system is piped A, B, & C then it MUST be wired A to A, B to B, and C to C, etc.
Multi‐Split Installation
© 2012 Daikin ACSlide 9
System Layout
© 2012 Daikin AC
Outdoor Unit
RMXS48LVJU
© 2012 Daikin ACSlide 11
RMXS Features
• Design flexibility with the ability to connect from 2 zones to 8‐Zones on a
single system
• Ability to connect up to 50% to 130% of indoor unit capacity
• Long piping lengths for indoor installation flexibility
• Slim design for a space saving and
unobtrusive look to the home exterior
© 2012 Daikin ACSlide 12
RMXS Features
• Max Cooling Capacity – 48,000 Btu/h
(Heating 54,000 Btu/h)
• Up to 18.8 SEER (HSPF 11.3)
• Connects to CTXS, FTXS, FDXS, CDXS,
and FFQ indoor units
• 130% Connection Ratio
• 440 feet total pipe length
• Sound Levels ‐ 57 to 58 dBA
• Operating Range
• Cooling 23° to 115° F
• Heating 5 ° to 75° F
© 2012 Daikin ACSlide 13
RMXS Dimensions
• Unit should be placed where there is proper support for the weight of the condenser
• Raise unit up for snow and drainage of water during defrost where conditions require
• Securely fasten unit to withstand high winds and earthquake
• Unit must be installed level
• Area must have adequate ventilation
• Area must have adequate clearance for the unit
53”
4”
Min. 4” clearance on inlet side, to wall.
Refrigerant piping can be run through front, bottom, side or rear of cabinet
35 7/16”
© 2012 Daikin ACSlide 14
RMXS Clearances
© 2012 Daikin AC
Indoor Units & ControlsCTXS, FTXS, CDXS, FDXS, & FFQDaikin ENVi (DACA‐TS1‐1), Navigation Remote Controller (BRC1E72), Wireless Remote Controller (ARC452), & Wired Remote Controller (BRC944B)
© 2012 Daikin ACSlide 16
Wall Mount
• Auto‐swing mechanism ensures efficient air distribution via louvers that automatically close when the unit is turned off
• Wide air discharge outlet distributes a comfortable airflow throughout the entire space
• Horizontal louvers and front panel can be easily removed for cleaning• Undisturbed comfort with indoor operating sound levels as low as 22 dB(A)
Available Models
FTXS FTXS15LVJU FTXS18LVJU FTXS24LVJU
CTXS CTXS07LVJU CTXS09HVJU CTXS12HVJU
© 2012 Daikin ACSlide 17
Concealed Slim Duct
• Slim low profile design, only 7 7/8” in height • Rear or bottom return • Mold proof washable resin filter included• Wireless Receiver with 60” cable
• 10 ft. (DACA‐ARCW901P10) & 25 ft. (DACA‐ARCW901P25) receiver cable extension accessory options available NOTE: When used on RXS09&12 DAVJU
units, SEER rating is 13
FDXS_LVJU / CDXS_LVJU
Available Models
FDXS FDXS09LVJU FDXS12 LVJU
CDXS CDXS15LVJU CDXS18LVJU CDXS24LVJU
© 2012 Daikin ACSlide 18
FFQ_LVJU 2’ x 2’ Ceiling Cassette
• Enhanced comfort with uniform airflow and temperature distribution
• Draught free protection with horizontal air discharge
• Simple installation with an easy‐to‐fit decoration panel that blends with any interior
design
• Easy maintenance with an easy‐to‐clean grille and washable long life filter
FFQ_LVJU
Available Models
FFQ FFQ09LVJU FFQ12LVJU FFQ15LVJU FFQ18LVJU
© 2012 Daikin ACSlide 19
Condensate Drain Installation ‐FFQ_LVJU 2’ x 2’
Raising section must be run with ¾” condensate pipe
© 2012 Daikin ACSlide 20
Indoor Unit Piping Connections
Piping Connections (Flared)
CTXS07 CTXS09 CTXS12 FTXS15 FTXS18 FTXS24
CTXS/FTXS
Liquid (O.D.)Inches
1/4
Gas(O.D.)Inches
3/8 3/8 3/8 1/2 1/2 5/8
CDXS/FDXS
‐‐ FDXS09 FDXS12 CDXS15 CDXS18 CDXS24
Liquid (O.D.)Inches
1/4
Gas(O.D.)Inches
‐‐ 3/8 3/8 1/2 1/2 5/8
FFQ
‐‐ FFQ09 FFQ12 FFQ15 FFQ18 ‐‐
Liquid (O.D.)Inches
‐‐ 1/4 ‐‐
Gas(O.D.)Inches
‐‐ 3/8 3/8 1/2 1/2 ‐‐
© 2012 Daikin ACSlide 21
Individual Zone ControlDaikin’s 8‐Zone Multi‐Split system offers consistent temperature throughout the home with the ability to independently control up to eight individual rooms on a single system.
Using the following Remote Controllers*:• Daikin ENVi (DACA‐TS1‐1)• Navigation Remote Controller (BRC1E72)• Wireless Remote Controller (ARC452)• Wired Remote Controller (BRC944B)• Wireless Remote Controller Kit (BRC7E830)*RC selection is dependent on indoor unit installed.
BRC1E72Navigation Remote
FFQ OnlyBRC944Wired Option
Not available for FFQ
ARC452Wireless
DACA‐TS1‐1Daikin ENVi OptionNot available for FFQ
BRC7E830Wireless KitFFQ Only
© 2012 Daikin ACSlide 22
Daikin ENVi (DACA‐TS1‐1)Compatible with CTXS/FTXS and CDXS/FDXS
Key Features and Functions:• Cool, Heat, and Auto modes with dual set‐points • Weekly scheduling for residential use• Setback control• Optimum start • Hold, Quick save, and Vacation settings• Fan On/Auto, Fan speed, and Louver direction• Error code with plain text explanation• Wi‐Fi enabled – accessible through PC web, Smart
phone/Tablet• Dealer Web Portal – Alert Email and Trend Graph
Display• Room temperature/relative humidity display• Outdoor temperature and weather forecast
Other• Backlit• Fahrenheit/Celsius selectable• Current operation status• Room temperature sensor• Relay for AUX heater connection (manually switch over
from HP to AUX is required by user)
© 2012 Daikin ACSlide 23
Navigation Remote Controller (BRC1E72)
Key Features and Functions:• Configurable display – Standard, Detailed, and Simple • Dual or single Cool and Heat set‐points for occupied periods• Setback set‐points for unoccupied periods • Unwanted buttons/operation modes can be disabled • Power off eliminates set‐point and mode adjustment –
configurable • Set‐point range limitation• Individual button prohibits• Automatic adjustment for Daylight Savings Time (DST)
Schedule• Weekly schedule – 7 day, weekday plus Saturday and
Sunday (5 + 1 + 1), weekday plus weekend (5 + 2) and Everyday (1)
• Allows programming up to 5 events per day with Cool and Heat or single set‐points
• Setback configuration with Cool and Heat set‐points
Display• Detailed display mode• Standard display mode• Simple display mode (new)• Face decal option to eliminate unnecessary buttons
with optional face plate
Available for FFQ Only, must be purchased separately
© 2012 Daikin ACSlide 24
Wireless Remote Controller (ARC452)
Compatible with CDXS/FDXS and CTXS/FTXS
Key Features and Functions:
• Swing Function
• Mode Selection (Auto, Dry, Cool, Heat, Fan)
• Powerful Function
• Intelligent Eye (wall mount units only)
• Quiet Operation
• On/Off Timer
• Self‐Diagnosis with Digital Display
• Night Set Mode
© 2012 Daikin ACSlide 25
Wired Remote Controller (BRC944B)
Compatible with all indoor units except FFQ
Key Features and Functions:
• Built in one time or daily timer functionality
with up to 2 timer actions per day
• LCD lets you display set point temperature in
1°F or 1°C units
• Selectable auto / cool / heat / dry / fan
operation modes with adjustable temperature
and airflow rates
• Approximately two hour battery backup
• Controller can be used in conjunction with the
factory supplied standard wireless remote
controller
© 2012 Daikin ACSlide 26
Handheld Wireless Remote Controller
BRC7E830 Option
Wireless Remote Controllers are provided as “kits”
Temperature is setpoint display
Wireless Controllers only communicate with the fan coil when they are pointed at the receiver and a button is pressed
Listen for a “Beep” or “Beep Beep” for confirmation
Available for FFQ Only, must be purchased separately
© 2012 Daikin AC
Branch Provider Units (BP)
© 2012 Daikin ACSlide 28
BP Unit Exploded View
Liquid Line Connection
Gas Line Connection
© 2012 Daikin ACSlide 29
Allow for Service Clearance
Allow at least 8” of clearance above BP unit to allow for service.
Removing the BP unit cover is necessary for servicing the unit. Do not install BP unit flush against a ceiling or other obstruction.
Install using All thread or similar suspension method.
To service:
• Remove the 4 screws on the bottom
of the unit
• Remove the 4 screws that secure the
electrical wiring box cover
• Remove the 4 screws that secure the
electrical wiring box to the BP unit
• Lift the BP box unit
• Lift the top half of the thermal
insulation molding
© 2012 Daikin ACSlide 30
Internal Piping DiagramThe inlet piping to the BPMKS Unit is encapsulated in thermal insulation molding. The lines entering the BP unit are separate Gas and Liquid Lines as indicated in the following internal piping diagram.
© 2012 Daikin ACSlide 31
Specifications
• Flare nut connections
• Choice of 2‐zone or 3‐zone
BP units to match the system
selection to individual
requirements
Model Name BPMKS048A2U BPMKS049A3UPower Supply Single phase 60Hz 208/230VPower Consumption W 10.0 10.0Minimum Circuit Amps (MCA) A 15.0 15.0Running Current A 0.05 0.05Sound Pressure - (Cooling/Heating) dB(A) 32/32 32/32Number of Connectable Indoor Units 1 to 2 1 to 3Min. Connection Combination 7,000 7,000Max. Connection Combination 48,000 62,000Piping Connections (O.D.)
LiquidOutdoor Unit Side in. Ø 3/8 x 1Indoor Unit Side in. Ø 1/4 x 2 Ø 1/4 x 3
GasOutdoor Unit Side in. Ø 5/8 x 1Indoor Unit Side in. Ø 5/8 x 2 Ø 5/8 x 3
Drain in. Not requiredReducer pc. 1 (Ø 3/8 → Ø 1/4)
pc. 4 (Ø 5/8 → Ø 1/2)pc. 3 (Ø 5/8 → Ø 3/8)
Dimensions (H x W x D) in. 7-1/16 x 11-9/16 x 13-3/4Net Weight lbs. 18.0 20.0
© 2012 Daikin ACSlide 32
InstallationThe BP unit is for indoor use and should be installed above a ceiling or behind a wall in accordance with the following conditions. The unit must be:
• Fully supported in a location with little or no vibration
• Easily accessible with adequate space for servicing or repairs
• Placed within distance of allowable pipe length
• Located away from items producing heat or steam (gas)
• Located in a well‐ventilated area; not installed in a location that is hot
or humid for long periods of time (DB temp of 140° or above)
• Not installed near bedrooms due to possible audible sounds of
refrigerant flow through the piping
© 2012 Daikin ACSlide 33
Installation Restrictions & Clearances
Unit: inch (mm)
Access PanelProvide an access panel for servicing and maintenance.
© 2012 Daikin ACSlide 34
Ceiling Suspended Installation1. Fix the furnished (B)
washer retaining flange with two (C) screws. (4 locations in total)
2. Unit must be suspended using an all‐thread bolt and hexnut and washers.
3. Insure that the unit is level, tighten the hexnut.
The BP Unit must be installed Level. Allow at least 8” of service clearance above the BP unit.
© 2012 Daikin ACSlide 35
Wall Mounted Installation
CAUTION• Be sure to install the unit with
the top surface up.• Do not install near bedrooms.
The sound of refrigerant flowing through the piping may sometimes be audible.
The BP Unit must be installed Level. Allow at least 8” of service clearance above the BP unit.
© 2012 Daikin ACSlide 36
Electrical Box LocationThe mounting location for the Electrical Box can be modified to better reflect the needs of the installation.
Electrical Box as Shipped Electrical Box when Relocated
© 2012 Daikin ACSlide 37
Relocating Electrical BoxProcedures for Changing Location of E‐Box
1. Remove screws and pull off electrical wiring box cover.
2. Remove 4 screws shown in the figure, remove the printed circuit board.
© 2012 Daikin ACSlide 38
3. Remove the binding band (A) which holds the wires.
4. Remove the printed circuit board, and reattach as shown in the figure.
Relocating Electrical Box
© 2012 Daikin ACSlide 39
5. Reattach the binding band to position (B).
6. Attach printed circuit board and electrical wiring box cover to other side and secure with screws.
Relocating Electrical Box
© 2012 Daikin ACSlide 40
Blanking Off PortsThe Branch Provider Units are shipped with each port blanked off.
To access a port for use:• Remove the flare nut• Remove the blank
Any port that will not be in use should remain blanked off.
Note: A minimum of two indoor units must be installed per 8‐Zone system.
The indoor units can each be connected to separate Branch Provider units to allow for future expansion of the system.
© 2012 Daikin AC
8‐Zone Selection Tool
© 2012 Daikin ACSlide 42
8‐Zone Selection Tool
© 2012 Daikin ACSlide 43
Selection Flow Chart
© 2012 Daikin ACSlide 44
Selection Tool Report
© 2012 Daikin AC
Electrical Wiring
© 2012 Daikin ACSlide 46
Electrical WiringThe outdoor unit and branch provider (BP) units operate from separate 208/230V single‐phase power supplies, eliminating the need of power supply between them. Therefore, wiring size from the outdoor unit to the branch provider (BP) units can be reduced and ease installation.
DIII‐net transmission line4‐wire transmission and power supplyPower Supply
Max Wiring Length between units 656 ft.Total System Wiring Length 984 ft.
AWG 18‐16
Always follow local codes
© 2012 Daikin ACSlide 47
Detailed View of BP Wiring
3 Zone BP unit shown Always follow local codes
© 2012 Daikin ACSlide 48
Detailed View of BP Unit PCB
L1, L2, & GRD From 208/230V Electrical Supply (AWG 16‐14)
2 Zone BP unit shown
F1 & F2 Transmission wire to other BP unit or Outdoor Unit (Sheathed 2‐strand AWG 18‐16)
Always follow local codes
≤ 33 ft. use AWG 16‐14> 33 ft. use AWG 14
Inter‐unit wiring to Zone A (1,2,3 & Grd)Inter‐unit wiring to Zone B (1,2,3 & Grd)
© 2012 Daikin ACSlide 49
BP Unit Installation ‐ Electrical Conduit
Always follow local codes
L1 & L2 From 208/230V Electrical Supply (AWG 16‐14)
MOCP = 15
© 2012 Daikin ACSlide 50
Electrical Wiring ConnectionsConnection Example of Total System Wiring
Dedicated circuit not required for individual BP units
Always follow local codes
© 2012 Daikin AC
Refrigerant Piping
© 2012 Daikin ACSlide 52
Install Guidelines
• When connecting a pipe to the unit body or
removing it, be sure to use a back up wrench
and torque wrench.
• For the work dimension and the tightening
torque of the flare section, see this table.
• When connecting a flare nut, apply oil to the
flare section (only the OUTER surface), and
screw the nut three or four times initially by
hand.
• Be sure to use the flare nuts included with
the condenser or fan coil.
Pipe Size Tightening Torque1/4 " 10.4 ‐ 12.7 ft lbf3/8 " 24.1 ‐ 29.4 ft lbf1/2 " 36.5 ‐ 44.5 ft lbf5/8 " 45.6 ‐ 55.6 ft lbf3/4 " 71.7 ‐ 87.5 ft lbf
Back up Wrench
Torque Wrench
Flare Nut
Piping union
© 2012 Daikin ACSlide 53
• Keep refrigerant piping clean and sealed during installation
• Use Nitrogen purge during brazing process• Refrigerant piping must be properly insulated
• Recommended ¾” wall insulation• Liquid and Gas pipes must be individually insulated• All Flare nut connections must be insulated
• Refrigerant piping must be properly supported• Follow local code requirements for piping support locations
• Support piping within 12” of BP Box and Fan Coil unit• Keep track of each refrigerant circuit during installation
• Total refrigerant piping length cannot exceed 440 ft (135 m)
• Measure liquid lines as they are installed• Avoid crossing refrigerant lines during installation
Installation Procedures
© 2012 Daikin ACSlide 54
Insulation Requirements• The Liquid and Gas piping must be
completely insulated• Recommended wall thickness – 3/4”• All flare connections must be insulated
Indoor Unit Installation Kit
© 2012 Daikin ACSlide 55
Piping Rule #1
Total piping length between outdoor unit and BP units ≤ 180 ft
a b c
d e
a + b + c + d + e ≤ 180
© 2012 Daikin ACSlide 56
Piping Rule #2
Total piping length between BP units and indoor units ≤ 262 ft
f
f + g + h + i + j + k + l ≤ 262
g
hi
jk l
© 2012 Daikin ACSlide 57
Piping Rule #3
f, g, h, i, j, k, l ≤ 49
Total piping length between a BP unit and connected indoor unit ≤ 49 ft
f
g
h
hi j k l
© 2012 Daikin ACSlide 58
Piping Rule #4
Total allowable height between outdoor and indoor units ≤ 98 ft
H1≤ 98
H1
© 2012 Daikin ACSlide 59
Piping Rule #5
Total allowable height between outdoor unit and BP units ≤ 98 ft
H2≤ 98
H2
© 2012 Daikin ACSlide 60
Piping Rule #6
Total allowable height between BP units ≤ 49 ft
H3≤ 49
H3
© 2012 Daikin ACSlide 61
Piping Rule #7
Total allowable height between indoor units ≤ 49 ft
H4≤ 49
H4
© 2012 Daikin ACSlide 62
Piping Rule #8
Minimum allowable piping length between outdoor unit and first REFNET ≥ 16.4 ft
m
m ≥ 16.4
© 2012 Daikin ACSlide 63
Piping Rule #9
Maximum piping length from first REFNET to furthest indoor unit ≤ 131 ft
n
n ≤ 131
REFNET kits are recommended to be set as near as possible to the BP units. This run is recommended to be as short as possible.
© 2012 Daikin ACSlide 64
System Example
8‐Zone Multi Plus System ExampleFrom Selection Tool
© 2012 Daikin ACSlide 65
Pipe Size SelectionGas Liquid
Between outdoor unit and first REFNET 3/4 " 3/8 "
Between 1st REFNET and 2nd REFNET 5/8 " 3/8 "
Between REFNET and BP unit (Total Connected indoor unit capacity ≤ 17,000 Btu/h) 1/2 " 1/4 "
Between REFNET and BP unit (Total Connected indoor unit capacity ≥ 17,000 Btu/h) 5/8 " 3/8 "
© 2012 Daikin ACSlide 66
Calculate Additional Refrigerant
R =Total Length (ft) ofliquid piping size at
3/8 in. ODx 0.036 lb/ft X
Total length (ft) of liquid piping size at
¼ in. ODX 0.015 lb/ft
Example for refrigerant branch using REFNET joint (unit: OD inch x ft)
R = [(a+b+d+e) x 0.036] + [(c+f+g+h+i+j+k=L)] x 0.015 = [128 x 0.036] + [234 x 0.15] = 8.118 lb or 8.1 lb
a: 3/8 x 32 d: 3/8 x 32 g: 1/4 x 32 j: 1/4 x 32
b: 3/8 x 32 e: 3/8 x 32 h: 1/4 x 32 k: 1/4 x 32
c: 3/8 x 32 f: 1/4 x 32 i: 1/4 x 32 L: 1/4 x 32
© 2012 Daikin AC
REFNET Fittings
© 2012 Daikin ACSlide 68
REFNET “Y” Branch – Gas & Liquid Kit
KHRP26A22T
REFNET Components
© 2012 Daikin ACSlide 69
• REFNET Y Joints to be installed: straight up - straight down –level (+/- 30°)
• Each REFNET included in the branch kit is labeled to identify circuit:
• Liquid – Gas
REFNET “Y” Joint Installation
© 2012 Daikin ACSlide 70
REFNET “Y” ‐ Position vs. Flow Demonstration
© 2012 Daikin ACSlide 71
Refrigerant Flow Demonstration
© 2012 Daikin ACSlide 72
Pipe Flaring
Proper deburring is critical for a successful flare fitting
© 2012 Daikin ACSlide 73
“B” depth for all other sizes
DACA‐FSG‐1
Piping Flaring
A
Dimension “B” Requirement
Pipe Size Dimension
1/4” 1 mm
3/8” 2 mm
1/2” 2 mm
5/8” 2 mm
3/4” 2 mm
B
FlaringBlock
Dimension “A” requirement
Pipe Size Dimension
1/4” 9.1mm
3/8” 13.2mm
1/2” 16.6mm
5/8” 19.7mm
3/4” 24.0mm
Go / No Go“B” depth for ¼” pipe
© 2012 Daikin ACSlide 74
Brazing
• Tape in Schrader Fitting
• Set Nitrogen regulator to 1.5 – 3 PSIG
• Leave other end of pipe open
Dry Nitrogen MUST be used during all brazing (Pressure regulated to 1.5 to 3 PSIG) to prevent oxidation formation
© 2012 Daikin AC
Installation Examples
© 2012 Daikin ACSlide 76
Outdoor Unit Installed
Proper installation• Outdoor Unit is installed level• Shipping brackets have been
removed• All refrigerant piping is installed• Pressure tested to 550 psi for 24
hours• Triple evacuation of refrigerant
system, final evacuation to 500 microns or below and held for 1 hour
• Additional charge calculated by liquid line sizes and length
• Unit charged with R‐410A in liquid state
© 2012 Daikin ACSlide 77
Branch Provider Unit Installed
Proper installation
• BP Unit is installed level and
with proper clearance
• High and low voltage wiring
properly terminated
• Refrigerant piping properly
insulated
Note: flare nuts insulated after
photo
© 2012 Daikin ACSlide 78
REFNET Installed Level
Proper installation
• REFNET fittings are installed level
• All refrigerant piping is insulated
© 2012 Daikin ACSlide 79
Refrigerant Piping InstalledProper installation
• Refrigerant piping is insulated
• Brackets are installed outside of
insulation allowing for
expansion of line set
• BP unit power disconnect
installed
© 2012 Daikin ACSlide 80
What NOT to do
Improper Installation
BP unit installed flush with ceiling. BP units must be installed with adequate service
clearance. Allow at least 8” of clearance above the BP unit.
© 2012 Daikin ACSlide 81
What NOT to do
Improper Installation
BP unit installed at 30+ degree angle (BP units must be installed level).
© 2012 Daikin AC
Start Up Checklist
© 2012 Daikin ACSlide 83
Compressor shipping brackets removed
Stop Valves securely closed & field refrigerant piping pressure tested to 550 psi for 24
hours min.
Triple evacuate to 500 microns or less
All liquid lines are measured, “Additional Refrigerant Charge” is calculated and
weighed into the system, breaking the final vacuum
Stop Valves opened
All control wiring is installed and properly connected at each terminal block to BP
units
All condensate drain piping is connected, including fan coil tie‐in, and insulated as
required
Refrigerant lines are completely insulated including flare nut connections at Indoor
Units and BP units
Start Up Checklist
© 2012 Daikin ACSlide 84
Start Up Checklist All applicable ductwork is connected and air filters installed
Line Voltage is checked and verified to be within specified range for all system
components
Power up BP units
Power up outdoor unit to energize crankcase heaters (minimum 6 hrs) Initialization
sequence starts and the system addresses are set – Setup Navigation Remote
Controllers (for FFQ)
System refrigerant charge – Additional Refrigerant Charge mode
Test Operation
Remaining System Field Settings
Verify system operation in Cool & Heat mode as outside ambient temperature
conditions allow (heat mode is prohibited above 75.2°F outside air temperature)
© 2012 Daikin ACSlide 85
Operating TestFollow the “Operating Test” as described in the installation manual of the outdoor unit. If BP unit does not operate normally during the test run, the error can be checked on the remote controller display for the indoor unit.
Simple diagnosis can be done using the LEDs on the BP unit’s circuit board.For details, see the label on the inside of the BP unit’s electrical wiring unit cover.
*DO NOT perform any other procedures during Operating Test*Operating Test CANNOT be performed during: initialization, additional charge, or recovering mode
Error Codes displayed on the remote controller
Code Nonconformity during installation Remedial action
A9 Electric expansion valve connector not connected (BP unit)
Please contact your dealer
E2 Printed circuit board faulty (BP unit)
J0 Liquid and gas thermistor faulty (BP unit)
U4 Transmission error between BP unit and indoor unit
Correctly connect the inter connections between BP unit and indoor unit
U9 Transmission error between outdoor unit and BP unit
Correctly connect the inter connections between outdoor unit and BP unit
© 2012 Daikin ACSlide 86
Operating Test
Power On – Check Operation
Insure all thermisters and transducers are in place
Power ON outdoor unit for 6 hours (crank case heater)
Power ON branch port units
Open Service Valves
Perform check operation
Press/Hold BS4 (Test) button for 5 seconds
© 2012 Daikin ACSlide 87
Operating Test
Temperature Control – Check Operation
Makes sure the indoor and outdoor units are operating normally
Run each indoor unit one at a time and make sure the outdoor unit is also
running
Check to see if cold (or hot) air is coming out of the indoor unit
Press the fan direction and fan strength buttons on the indoor unit to see
if they operate properly
© 2012 Daikin ACSlide 88
• Outdoor Unit
• Indoor Units & Controls
• Branch Provider Units
• 8‐Zone Selection Tool
• Refrigerant Piping
• REFNET Fittings
• Installation Examples
• Start Up Checklist
Topics Recap