8 Zone Multi Split Key Pts Install PT RLC 1307 PP0 01A

89
© 2012 Daikin AC RESIDENTIAL | LIGHT COMMERCIAL | COMMERCIAL Daikin 8Zone MultiSplit System Key Points of the Installation Process

Transcript of 8 Zone Multi Split Key Pts Install PT RLC 1307 PP0 01A

Page 1: 8 Zone Multi Split Key Pts Install PT RLC 1307 PP0 01A

© 2012 Daikin AC

RESIDENTIAL | LIGHT COMMERCIAL | COMMERCIAL

Daikin 8‐Zone Multi‐Split System

Key Points of the Installation Process

Page 2: 8 Zone Multi Split Key Pts Install PT RLC 1307 PP0 01A

© 2012 Daikin ACSlide 2

• Installation Considerations

• Outdoor Unit

• Indoor Units & Controls

• Branch Provider Units

• 8‐Zone Selection Tool

• Refrigerant Piping

• REFNET Fittings

• Installation Examples

• Start Up Checklist

Topics

Page 3: 8 Zone Multi Split Key Pts Install PT RLC 1307 PP0 01A

© 2012 Daikin AC

Installation Considerations

Page 4: 8 Zone Multi Split Key Pts Install PT RLC 1307 PP0 01A

© 2012 Daikin ACSlide 4

Tools & Support

8‐Zone Selection Tool

Manuals

Daikin eQuip App

Product Catalog

Page 5: 8 Zone Multi Split Key Pts Install PT RLC 1307 PP0 01A

© 2012 Daikin ACSlide 5

Daikin Tools for Install

Page 6: 8 Zone Multi Split Key Pts Install PT RLC 1307 PP0 01A

© 2012 Daikin ACSlide 6

750 – 1000 PSI

Additional Tools for Install• Metric tools (hex key set and socket set) are required when 

installing or servicing Daikin RLC units• Nitrogen regulator capable of measuring up to 700 plus PSI is 

necessary for installing Daikin RLC units

Metric Hex Key Set

Metric Socket Set

Page 7: 8 Zone Multi Split Key Pts Install PT RLC 1307 PP0 01A

© 2012 Daikin ACSlide 7

• Compatible with all HFC Refrigerants• Excellent anti‐wear properties• Better solubility with process fluids• Superior Resistance to Cap tube blockage• Better lubricity• Optimal for non‐drier systems• Very Hygroscopic but with no hydrolysis• Moisture easily removed

PolyVinylEther Oil (PVE) 

PVE w/ drier

PVE w/o drier

Page 8: 8 Zone Multi Split Key Pts Install PT RLC 1307 PP0 01A

© 2012 Daikin ACSlide 8

• Label the indoor units A, B, C, D, etc. as appropriate

• Daikin does not have preference regarding install order

• Important for wiring and piping 

• Piping and wiring must match

• If the system is piped A, B, & C then it MUST be wired A to A, B to B, and C to C, etc.

Multi‐Split Installation

Page 9: 8 Zone Multi Split Key Pts Install PT RLC 1307 PP0 01A

© 2012 Daikin ACSlide 9

System Layout

Page 10: 8 Zone Multi Split Key Pts Install PT RLC 1307 PP0 01A

© 2012 Daikin AC

Outdoor Unit

RMXS48LVJU

Page 11: 8 Zone Multi Split Key Pts Install PT RLC 1307 PP0 01A

© 2012 Daikin ACSlide 11

RMXS Features

• Design flexibility with the ability to connect from 2 zones to 8‐Zones on a 

single system

• Ability to connect up to 50% to 130% of indoor unit capacity

• Long piping lengths for indoor installation flexibility

• Slim design for a space saving and 

unobtrusive look to the home exterior

Page 12: 8 Zone Multi Split Key Pts Install PT RLC 1307 PP0 01A

© 2012 Daikin ACSlide 12

RMXS Features

• Max Cooling Capacity – 48,000 Btu/h 

(Heating 54,000 Btu/h)

• Up to 18.8 SEER (HSPF 11.3)

• Connects to CTXS, FTXS, FDXS, CDXS, 

and FFQ indoor units

• 130% Connection Ratio

• 440 feet total pipe length

• Sound Levels ‐ 57 to 58 dBA

• Operating Range

• Cooling 23° to 115° F

• Heating 5 ° to 75° F

Page 13: 8 Zone Multi Split Key Pts Install PT RLC 1307 PP0 01A

© 2012 Daikin ACSlide 13

RMXS Dimensions

• Unit should be placed where there is proper support for the weight of the condenser

• Raise unit up for snow and drainage of water during defrost where conditions require

• Securely fasten unit to withstand high winds and earthquake

• Unit must be installed level

• Area must have adequate ventilation

• Area must have adequate clearance for the unit

53”

4”

Min. 4” clearance on inlet side, to wall. 

Refrigerant piping can be run through front, bottom, side or rear of cabinet

35 7/16”

Page 14: 8 Zone Multi Split Key Pts Install PT RLC 1307 PP0 01A

© 2012 Daikin ACSlide 14

RMXS Clearances

Page 15: 8 Zone Multi Split Key Pts Install PT RLC 1307 PP0 01A

© 2012 Daikin AC

Indoor Units & ControlsCTXS, FTXS, CDXS, FDXS, & FFQDaikin ENVi (DACA‐TS1‐1), Navigation Remote Controller (BRC1E72), Wireless Remote Controller (ARC452), & Wired Remote Controller (BRC944B)

Page 16: 8 Zone Multi Split Key Pts Install PT RLC 1307 PP0 01A

© 2012 Daikin ACSlide 16

Wall Mount

• Auto‐swing mechanism ensures efficient air distribution via louvers that automatically close when the unit is turned off

• Wide air discharge outlet distributes a comfortable airflow throughout the entire space

• Horizontal louvers and front panel can be easily removed for cleaning• Undisturbed comfort with indoor operating sound levels as low as 22 dB(A)

Available Models

FTXS FTXS15LVJU FTXS18LVJU FTXS24LVJU

CTXS CTXS07LVJU CTXS09HVJU CTXS12HVJU

Page 17: 8 Zone Multi Split Key Pts Install PT RLC 1307 PP0 01A

© 2012 Daikin ACSlide 17

Concealed Slim Duct

• Slim low profile design, only 7 7/8” in height • Rear or bottom return • Mold proof washable resin filter included• Wireless Receiver with 60” cable

• 10 ft. (DACA‐ARCW901P10) & 25 ft. (DACA‐ARCW901P25) receiver cable extension accessory options available NOTE: When used on RXS09&12 DAVJU

units, SEER rating is 13

FDXS_LVJU / CDXS_LVJU

Available Models

FDXS  FDXS09LVJU FDXS12 LVJU

CDXS CDXS15LVJU CDXS18LVJU CDXS24LVJU

Page 18: 8 Zone Multi Split Key Pts Install PT RLC 1307 PP0 01A

© 2012 Daikin ACSlide 18

FFQ_LVJU 2’ x 2’ Ceiling Cassette

• Enhanced comfort with uniform airflow and temperature distribution

• Draught free protection with horizontal air discharge

• Simple installation with an easy‐to‐fit decoration panel that blends with any interior 

design

• Easy maintenance with an easy‐to‐clean grille and washable long life filter

FFQ_LVJU

Available Models

FFQ FFQ09LVJU FFQ12LVJU FFQ15LVJU FFQ18LVJU

Page 19: 8 Zone Multi Split Key Pts Install PT RLC 1307 PP0 01A

© 2012 Daikin ACSlide 19

Condensate Drain Installation ‐FFQ_LVJU 2’ x 2’ 

Raising section must be run with ¾” condensate pipe

Page 20: 8 Zone Multi Split Key Pts Install PT RLC 1307 PP0 01A

© 2012 Daikin ACSlide 20

Indoor Unit Piping Connections

Piping Connections (Flared)

CTXS07 CTXS09 CTXS12 FTXS15 FTXS18 FTXS24

CTXS/FTXS

Liquid (O.D.)Inches

1/4

Gas(O.D.)Inches

3/8 3/8 3/8 1/2 1/2 5/8

CDXS/FDXS

‐‐ FDXS09 FDXS12 CDXS15 CDXS18 CDXS24

Liquid (O.D.)Inches

1/4

Gas(O.D.)Inches

‐‐ 3/8 3/8 1/2 1/2 5/8

FFQ

‐‐ FFQ09 FFQ12 FFQ15 FFQ18 ‐‐

Liquid (O.D.)Inches

‐‐ 1/4 ‐‐

Gas(O.D.)Inches

‐‐ 3/8 3/8 1/2 1/2 ‐‐

Page 21: 8 Zone Multi Split Key Pts Install PT RLC 1307 PP0 01A

© 2012 Daikin ACSlide 21

Individual Zone ControlDaikin’s 8‐Zone Multi‐Split system offers consistent temperature throughout the home with the ability to independently control up to eight individual rooms on a single system. 

Using the following Remote Controllers*:• Daikin ENVi (DACA‐TS1‐1)• Navigation Remote Controller (BRC1E72)• Wireless Remote Controller (ARC452)• Wired Remote Controller (BRC944B)• Wireless Remote Controller Kit (BRC7E830)*RC selection is dependent on indoor unit installed.

BRC1E72Navigation Remote 

FFQ OnlyBRC944Wired Option

Not available for FFQ

ARC452Wireless

DACA‐TS1‐1Daikin ENVi OptionNot available for FFQ

BRC7E830Wireless KitFFQ Only

Page 22: 8 Zone Multi Split Key Pts Install PT RLC 1307 PP0 01A

© 2012 Daikin ACSlide 22

Daikin ENVi (DACA‐TS1‐1)Compatible with CTXS/FTXS and CDXS/FDXS

Key Features and Functions:• Cool, Heat, and Auto modes with dual set‐points • Weekly scheduling for residential use• Setback control• Optimum start • Hold, Quick save, and Vacation settings• Fan On/Auto, Fan speed, and Louver direction• Error code with plain text explanation• Wi‐Fi enabled – accessible through PC web, Smart 

phone/Tablet• Dealer Web Portal – Alert Email and Trend Graph

Display• Room temperature/relative humidity display• Outdoor temperature and weather forecast

Other• Backlit• Fahrenheit/Celsius selectable• Current operation status• Room temperature sensor• Relay for AUX heater connection (manually switch over 

from HP to AUX is required by user)

Page 23: 8 Zone Multi Split Key Pts Install PT RLC 1307 PP0 01A

© 2012 Daikin ACSlide 23

Navigation Remote Controller (BRC1E72)

Key Features and Functions:• Configurable display – Standard, Detailed, and Simple • Dual or single Cool and Heat set‐points for occupied periods• Setback set‐points for unoccupied periods • Unwanted buttons/operation modes can be disabled • Power off eliminates set‐point and mode adjustment –

configurable • Set‐point range limitation• Individual button prohibits• Automatic adjustment for Daylight Savings Time (DST) 

Schedule• Weekly schedule – 7 day, weekday plus Saturday and 

Sunday (5 + 1 + 1), weekday plus weekend  (5 + 2) and Everyday (1) 

• Allows programming up to 5 events per day with Cool and Heat or single set‐points

• Setback configuration with Cool and Heat set‐points

Display• Detailed display mode• Standard display mode• Simple display mode (new)• Face decal option to eliminate unnecessary buttons

with optional face plate

Available for FFQ Only, must be purchased separately

Page 24: 8 Zone Multi Split Key Pts Install PT RLC 1307 PP0 01A

© 2012 Daikin ACSlide 24

Wireless Remote Controller (ARC452)

Compatible with CDXS/FDXS and CTXS/FTXS

Key Features and Functions:

• Swing Function

• Mode Selection (Auto, Dry, Cool, Heat, Fan)

• Powerful Function

• Intelligent Eye (wall mount units only)

• Quiet Operation

• On/Off Timer

• Self‐Diagnosis with Digital Display

• Night Set Mode

Page 25: 8 Zone Multi Split Key Pts Install PT RLC 1307 PP0 01A

© 2012 Daikin ACSlide 25

Wired Remote Controller (BRC944B)

Compatible with all indoor units except FFQ

Key Features and Functions:

• Built in one time or daily timer functionality 

with up to 2 timer actions per day

• LCD lets you display set point temperature in 

1°F or 1°C units

• Selectable auto / cool / heat / dry / fan 

operation modes with adjustable temperature 

and airflow rates

• Approximately two hour battery backup 

• Controller can be used in conjunction with the 

factory supplied standard wireless remote 

controller 

Page 26: 8 Zone Multi Split Key Pts Install PT RLC 1307 PP0 01A

© 2012 Daikin ACSlide 26

Handheld Wireless Remote Controller

BRC7E830 Option

Wireless Remote Controllers are provided as “kits”

Temperature is setpoint display

Wireless Controllers only communicate with the fan coil when they are pointed at the receiver and a button is pressed

Listen for a “Beep” or “Beep Beep” for confirmation

Available for FFQ Only, must be purchased separately

Page 27: 8 Zone Multi Split Key Pts Install PT RLC 1307 PP0 01A

© 2012 Daikin AC

Branch Provider Units (BP)

Page 28: 8 Zone Multi Split Key Pts Install PT RLC 1307 PP0 01A

© 2012 Daikin ACSlide 28

BP Unit Exploded View 

Liquid Line Connection

Gas Line Connection

Page 29: 8 Zone Multi Split Key Pts Install PT RLC 1307 PP0 01A

© 2012 Daikin ACSlide 29

Allow for Service Clearance

Allow at least 8” of clearance above BP unit to allow for service. 

Removing the BP unit cover is necessary for servicing the unit. Do not install BP unit flush against a ceiling or other obstruction.

Install using All thread or similar suspension method.

To service:

• Remove the 4 screws on the bottom 

of the unit

• Remove the 4 screws that secure the 

electrical wiring box cover

• Remove the 4 screws that secure the 

electrical wiring box to the BP unit

• Lift the BP box unit

• Lift the top half of the thermal 

insulation molding

Page 30: 8 Zone Multi Split Key Pts Install PT RLC 1307 PP0 01A

© 2012 Daikin ACSlide 30

Internal Piping DiagramThe inlet piping to the BPMKS Unit is encapsulated in thermal insulation molding.  The lines entering the BP unit are separate Gas and Liquid Lines as indicated in the following internal piping diagram.

Page 31: 8 Zone Multi Split Key Pts Install PT RLC 1307 PP0 01A

© 2012 Daikin ACSlide 31

Specifications

• Flare nut connections

• Choice of 2‐zone or 3‐zone 

BP units to match the system 

selection to individual 

requirements

Model Name BPMKS048A2U BPMKS049A3UPower Supply Single phase 60Hz 208/230VPower Consumption W 10.0 10.0Minimum Circuit Amps (MCA) A 15.0 15.0Running Current A 0.05 0.05Sound Pressure - (Cooling/Heating) dB(A) 32/32 32/32Number of Connectable Indoor Units 1 to 2 1 to 3Min. Connection Combination 7,000 7,000Max. Connection Combination 48,000 62,000Piping Connections (O.D.)

LiquidOutdoor Unit Side in. Ø 3/8 x 1Indoor Unit Side in. Ø 1/4 x 2 Ø 1/4 x 3

GasOutdoor Unit Side in. Ø 5/8 x 1Indoor Unit Side in. Ø 5/8 x 2 Ø 5/8 x 3

Drain in. Not requiredReducer pc. 1 (Ø 3/8 → Ø 1/4)

pc. 4 (Ø 5/8 → Ø 1/2)pc. 3 (Ø 5/8 → Ø 3/8)

Dimensions (H x W x D) in. 7-1/16 x 11-9/16 x 13-3/4Net Weight lbs. 18.0 20.0

Page 32: 8 Zone Multi Split Key Pts Install PT RLC 1307 PP0 01A

© 2012 Daikin ACSlide 32

InstallationThe BP unit is for indoor use and should be installed above a ceiling or behind a wall in accordance with the following conditions. The unit must be:

• Fully supported in a location with little or no vibration 

• Easily accessible with adequate space for servicing or repairs 

• Placed within distance of allowable pipe length

• Located away from items producing heat or steam (gas)

• Located in a well‐ventilated area; not installed in a location that is hot 

or humid for long periods of time (DB temp of 140° or above)

• Not installed near bedrooms due to possible audible sounds of 

refrigerant flow through the piping

Page 33: 8 Zone Multi Split Key Pts Install PT RLC 1307 PP0 01A

© 2012 Daikin ACSlide 33

Installation Restrictions & Clearances

Unit: inch (mm)

Access PanelProvide an access panel for servicing and maintenance.

Page 34: 8 Zone Multi Split Key Pts Install PT RLC 1307 PP0 01A

© 2012 Daikin ACSlide 34

Ceiling Suspended Installation1. Fix the furnished (B) 

washer retaining flange with two (C) screws. (4 locations in total)

2. Unit must be suspended using an all‐thread bolt and hexnut and washers.

3. Insure that the unit is level, tighten the hexnut.

The BP Unit must be installed Level. Allow at least 8” of service clearance above the BP unit.

Page 35: 8 Zone Multi Split Key Pts Install PT RLC 1307 PP0 01A

© 2012 Daikin ACSlide 35

Wall Mounted Installation

CAUTION• Be sure to install the unit with 

the top surface up.• Do not install near bedrooms. 

The sound of refrigerant flowing through the piping may sometimes be audible.

The BP Unit must be installed Level. Allow at least 8” of service clearance above the BP unit.

Page 36: 8 Zone Multi Split Key Pts Install PT RLC 1307 PP0 01A

© 2012 Daikin ACSlide 36

Electrical Box LocationThe mounting location for the Electrical Box can be modified to better reflect the needs of the installation. 

Electrical Box as Shipped Electrical Box when Relocated

Page 37: 8 Zone Multi Split Key Pts Install PT RLC 1307 PP0 01A

© 2012 Daikin ACSlide 37

Relocating Electrical BoxProcedures for Changing Location of E‐Box

1. Remove screws and pull off electrical wiring box cover.

2. Remove 4 screws shown in the figure, remove the printed circuit board.

Page 38: 8 Zone Multi Split Key Pts Install PT RLC 1307 PP0 01A

© 2012 Daikin ACSlide 38

3. Remove the binding band (A) which holds the wires.

4. Remove the printed circuit board, and reattach as shown in the figure.

Relocating Electrical Box

Page 39: 8 Zone Multi Split Key Pts Install PT RLC 1307 PP0 01A

© 2012 Daikin ACSlide 39

5. Reattach the binding band to position (B).

6. Attach printed circuit board and electrical wiring box cover to other side and secure with screws.

Relocating Electrical Box

Page 40: 8 Zone Multi Split Key Pts Install PT RLC 1307 PP0 01A

© 2012 Daikin ACSlide 40

Blanking Off PortsThe Branch Provider Units are shipped with each port blanked off. 

To access a port for use:• Remove the flare nut• Remove the blank

Any port that will not be in use should remain blanked off.

Note: A minimum of two indoor units must be installed per 8‐Zone system. 

The indoor units can each be connected to separate Branch Provider units to allow for future expansion of the system. 

Page 41: 8 Zone Multi Split Key Pts Install PT RLC 1307 PP0 01A

© 2012 Daikin AC

8‐Zone Selection Tool

Page 42: 8 Zone Multi Split Key Pts Install PT RLC 1307 PP0 01A

© 2012 Daikin ACSlide 42

8‐Zone Selection Tool

Page 43: 8 Zone Multi Split Key Pts Install PT RLC 1307 PP0 01A

© 2012 Daikin ACSlide 43

Selection Flow Chart

Page 44: 8 Zone Multi Split Key Pts Install PT RLC 1307 PP0 01A

© 2012 Daikin ACSlide 44

Selection Tool Report

Page 45: 8 Zone Multi Split Key Pts Install PT RLC 1307 PP0 01A

© 2012 Daikin AC

Electrical Wiring

Page 46: 8 Zone Multi Split Key Pts Install PT RLC 1307 PP0 01A

© 2012 Daikin ACSlide 46

Electrical WiringThe outdoor unit and branch provider (BP) units operate from separate 208/230V single‐phase power supplies, eliminating the need of power supply between them. Therefore, wiring size from the outdoor unit to the branch provider (BP) units can be reduced and ease installation.

DIII‐net transmission line4‐wire transmission and power supplyPower Supply

Max Wiring Length between units 656 ft.Total System Wiring Length 984 ft.

AWG 18‐16

Always follow local codes

Page 47: 8 Zone Multi Split Key Pts Install PT RLC 1307 PP0 01A

© 2012 Daikin ACSlide 47

Detailed View of BP Wiring 

3 Zone BP unit shown Always follow local codes

Page 48: 8 Zone Multi Split Key Pts Install PT RLC 1307 PP0 01A

© 2012 Daikin ACSlide 48

Detailed View of BP Unit PCB 

L1, L2, & GRD From 208/230V Electrical Supply (AWG 16‐14)

2 Zone BP unit shown

F1 & F2 Transmission wire to other BP unit or Outdoor Unit (Sheathed 2‐strand AWG 18‐16)

Always follow local codes

≤ 33 ft. use AWG 16‐14> 33 ft. use AWG 14

Inter‐unit wiring to Zone A (1,2,3 & Grd)Inter‐unit wiring to Zone B  (1,2,3 & Grd)

Page 49: 8 Zone Multi Split Key Pts Install PT RLC 1307 PP0 01A

© 2012 Daikin ACSlide 49

BP Unit Installation  ‐ Electrical Conduit

Always follow local codes

L1 & L2 From 208/230V Electrical Supply (AWG 16‐14)

MOCP = 15

Page 50: 8 Zone Multi Split Key Pts Install PT RLC 1307 PP0 01A

© 2012 Daikin ACSlide 50

Electrical Wiring ConnectionsConnection Example of Total System Wiring

Dedicated circuit not required for individual BP units

Always follow local codes

Page 51: 8 Zone Multi Split Key Pts Install PT RLC 1307 PP0 01A

© 2012 Daikin AC

Refrigerant Piping

Page 52: 8 Zone Multi Split Key Pts Install PT RLC 1307 PP0 01A

© 2012 Daikin ACSlide 52

Install Guidelines

• When connecting a pipe to the unit body or 

removing it, be sure to use a back up wrench 

and torque wrench. 

• For the work dimension and the tightening 

torque of the flare section, see this table.

• When connecting a flare nut, apply oil to the 

flare section (only the OUTER surface), and 

screw the nut three or four times initially by 

hand. 

• Be sure to use the flare nuts included with 

the condenser or fan coil.

Pipe Size Tightening Torque1/4 " 10.4 ‐ 12.7 ft lbf3/8 " 24.1 ‐ 29.4 ft lbf1/2 " 36.5 ‐ 44.5 ft lbf5/8 " 45.6 ‐ 55.6 ft lbf3/4 " 71.7 ‐ 87.5 ft lbf

Back up Wrench

Torque Wrench

Flare Nut

Piping union

Page 53: 8 Zone Multi Split Key Pts Install PT RLC 1307 PP0 01A

© 2012 Daikin ACSlide 53

• Keep refrigerant piping clean and sealed during installation

• Use Nitrogen purge during brazing process• Refrigerant piping must be properly insulated

• Recommended ¾” wall insulation• Liquid and Gas pipes must be individually insulated• All Flare nut connections must be insulated

• Refrigerant piping must be properly supported• Follow local code requirements for piping support locations

• Support piping within 12” of BP Box and Fan Coil unit• Keep track of each refrigerant circuit during installation

• Total refrigerant piping length cannot exceed 440 ft (135 m)

• Measure liquid lines as they are installed• Avoid crossing refrigerant lines during installation 

Installation Procedures

Page 54: 8 Zone Multi Split Key Pts Install PT RLC 1307 PP0 01A

© 2012 Daikin ACSlide 54

Insulation Requirements• The Liquid and Gas piping must be 

completely insulated• Recommended wall thickness – 3/4”• All flare connections must be insulated

Indoor Unit Installation Kit

Page 55: 8 Zone Multi Split Key Pts Install PT RLC 1307 PP0 01A

© 2012 Daikin ACSlide 55

Piping Rule #1

Total piping length between outdoor unit and BP units ≤ 180 ft

a b c

d e

a + b + c + d + e ≤ 180

Page 56: 8 Zone Multi Split Key Pts Install PT RLC 1307 PP0 01A

© 2012 Daikin ACSlide 56

Piping Rule #2

Total piping length between BP units and indoor units ≤ 262 ft

f

f + g + h + i + j + k + l ≤ 262

g

hi

jk l

Page 57: 8 Zone Multi Split Key Pts Install PT RLC 1307 PP0 01A

© 2012 Daikin ACSlide 57

Piping Rule #3

f, g, h, i, j, k, l ≤ 49

Total piping length between a BP unit and connected indoor unit ≤ 49 ft

f

g

h

hi j k l

Page 58: 8 Zone Multi Split Key Pts Install PT RLC 1307 PP0 01A

© 2012 Daikin ACSlide 58

Piping Rule #4

Total allowable height between outdoor and indoor units ≤ 98 ft

H1≤ 98

H1

Page 59: 8 Zone Multi Split Key Pts Install PT RLC 1307 PP0 01A

© 2012 Daikin ACSlide 59

Piping Rule #5

Total allowable height between outdoor unit and BP units ≤ 98 ft

H2≤ 98

H2

Page 60: 8 Zone Multi Split Key Pts Install PT RLC 1307 PP0 01A

© 2012 Daikin ACSlide 60

Piping Rule #6

Total allowable height between BP units ≤ 49 ft

H3≤ 49

H3

Page 61: 8 Zone Multi Split Key Pts Install PT RLC 1307 PP0 01A

© 2012 Daikin ACSlide 61

Piping Rule #7

Total allowable height between indoor units ≤ 49 ft

H4≤ 49

H4

Page 62: 8 Zone Multi Split Key Pts Install PT RLC 1307 PP0 01A

© 2012 Daikin ACSlide 62

Piping Rule #8

Minimum allowable piping length between outdoor unit and first REFNET ≥ 16.4 ft

m

m ≥ 16.4

Page 63: 8 Zone Multi Split Key Pts Install PT RLC 1307 PP0 01A

© 2012 Daikin ACSlide 63

Piping Rule #9

Maximum piping length from first REFNET to furthest indoor unit ≤ 131 ft

n

n ≤ 131

REFNET kits are recommended to be set as near as possible to the BP units. This run is recommended to be as short as possible.

Page 64: 8 Zone Multi Split Key Pts Install PT RLC 1307 PP0 01A

© 2012 Daikin ACSlide 64

System Example

8‐Zone Multi Plus System ExampleFrom Selection Tool

Page 65: 8 Zone Multi Split Key Pts Install PT RLC 1307 PP0 01A

© 2012 Daikin ACSlide 65

Pipe Size SelectionGas  Liquid 

Between outdoor unit and first REFNET 3/4  " 3/8 "

Between 1st REFNET and 2nd REFNET 5/8 " 3/8 "

Between REFNET and BP unit (Total Connected indoor unit capacity ≤ 17,000 Btu/h) 1/2 " 1/4 "

Between REFNET and BP unit (Total Connected indoor unit capacity ≥ 17,000 Btu/h) 5/8 " 3/8 "

Page 66: 8 Zone Multi Split Key Pts Install PT RLC 1307 PP0 01A

© 2012 Daikin ACSlide 66

Calculate Additional Refrigerant

R =Total Length (ft) ofliquid piping size at

3/8 in. ODx 0.036 lb/ft X

Total length (ft) of liquid piping size at

¼ in. ODX 0.015 lb/ft

Example for refrigerant branch using REFNET joint (unit: OD inch x ft)

R = [(a+b+d+e) x 0.036] + [(c+f+g+h+i+j+k=L)] x 0.015 = [128 x 0.036] + [234 x 0.15] = 8.118 lb or 8.1 lb

a:  3/8 x 32 d:  3/8 x 32 g:  1/4 x 32 j:  1/4 x 32

b: 3/8 x 32 e:  3/8 x 32 h:  1/4 x 32 k:  1/4 x 32

c: 3/8 x 32 f:  1/4 x 32 i:  1/4 x 32 L:  1/4 x 32

Page 67: 8 Zone Multi Split Key Pts Install PT RLC 1307 PP0 01A

© 2012 Daikin AC

REFNET Fittings

Page 68: 8 Zone Multi Split Key Pts Install PT RLC 1307 PP0 01A

© 2012 Daikin ACSlide 68

REFNET “Y” Branch – Gas & Liquid Kit

KHRP26A22T

REFNET Components

Page 69: 8 Zone Multi Split Key Pts Install PT RLC 1307 PP0 01A

© 2012 Daikin ACSlide 69

• REFNET Y Joints to be installed: straight up - straight down –level (+/- 30°)

• Each REFNET included in the branch kit is labeled to identify circuit:

• Liquid – Gas

REFNET “Y” Joint Installation

Page 70: 8 Zone Multi Split Key Pts Install PT RLC 1307 PP0 01A

© 2012 Daikin ACSlide 70

REFNET  “Y” ‐ Position vs. Flow Demonstration

Page 71: 8 Zone Multi Split Key Pts Install PT RLC 1307 PP0 01A

© 2012 Daikin ACSlide 71

Refrigerant Flow Demonstration

Page 72: 8 Zone Multi Split Key Pts Install PT RLC 1307 PP0 01A

© 2012 Daikin ACSlide 72

Pipe Flaring

Proper deburring is critical for a successful flare fitting 

Page 73: 8 Zone Multi Split Key Pts Install PT RLC 1307 PP0 01A

© 2012 Daikin ACSlide 73

“B” depth for all other sizes

DACA‐FSG‐1

Piping Flaring

A

Dimension “B” Requirement

Pipe Size Dimension

1/4” 1 mm

3/8” 2 mm

1/2” 2 mm

5/8” 2 mm

3/4” 2 mm

FlaringBlock

Dimension “A” requirement

Pipe Size Dimension

1/4” 9.1mm

3/8” 13.2mm

1/2” 16.6mm

5/8” 19.7mm

3/4” 24.0mm

Go / No Go“B” depth for ¼” pipe

Page 74: 8 Zone Multi Split Key Pts Install PT RLC 1307 PP0 01A

© 2012 Daikin ACSlide 74

Brazing

• Tape in Schrader Fitting

• Set Nitrogen regulator to 1.5 – 3 PSIG

• Leave other end of pipe open

Dry Nitrogen MUST be used during all brazing (Pressure regulated to 1.5 to 3 PSIG) to prevent oxidation formation

Page 75: 8 Zone Multi Split Key Pts Install PT RLC 1307 PP0 01A

© 2012 Daikin AC

Installation Examples

Page 76: 8 Zone Multi Split Key Pts Install PT RLC 1307 PP0 01A

© 2012 Daikin ACSlide 76

Outdoor Unit Installed

Proper installation• Outdoor Unit is installed level• Shipping brackets have been 

removed• All refrigerant piping is installed• Pressure tested to 550 psi for 24 

hours• Triple evacuation of refrigerant 

system, final evacuation to 500 microns or below and held for 1 hour

• Additional charge calculated by liquid line sizes and length

• Unit charged with R‐410A in liquid state

Page 77: 8 Zone Multi Split Key Pts Install PT RLC 1307 PP0 01A

© 2012 Daikin ACSlide 77

Branch Provider Unit Installed

Proper installation 

• BP Unit is installed level and 

with proper clearance

• High and low voltage wiring 

properly terminated

• Refrigerant piping properly 

insulated 

Note: flare nuts insulated after 

photo

Page 78: 8 Zone Multi Split Key Pts Install PT RLC 1307 PP0 01A

© 2012 Daikin ACSlide 78

REFNET Installed Level

Proper installation

• REFNET fittings are installed level

• All refrigerant piping is insulated 

Page 79: 8 Zone Multi Split Key Pts Install PT RLC 1307 PP0 01A

© 2012 Daikin ACSlide 79

Refrigerant Piping InstalledProper installation

• Refrigerant piping is insulated

• Brackets are installed outside of 

insulation allowing for 

expansion of line set

• BP unit power disconnect 

installed

Page 80: 8 Zone Multi Split Key Pts Install PT RLC 1307 PP0 01A

© 2012 Daikin ACSlide 80

What NOT to do

Improper Installation 

BP unit installed flush with ceiling. BP units must be installed with adequate service 

clearance. Allow at least 8” of clearance above the BP unit.

Page 81: 8 Zone Multi Split Key Pts Install PT RLC 1307 PP0 01A

© 2012 Daikin ACSlide 81

What NOT to do

Improper Installation 

BP unit installed at 30+ degree angle (BP units must be installed level). 

Page 82: 8 Zone Multi Split Key Pts Install PT RLC 1307 PP0 01A

© 2012 Daikin AC

Start Up Checklist

Page 83: 8 Zone Multi Split Key Pts Install PT RLC 1307 PP0 01A

© 2012 Daikin ACSlide 83

Compressor shipping brackets removed

Stop Valves securely closed & field refrigerant piping pressure tested to 550 psi for 24 

hours min.  

Triple evacuate to 500 microns or less

All liquid lines are measured, “Additional Refrigerant Charge” is calculated and 

weighed into the system,  breaking the final vacuum 

Stop Valves opened

All control wiring is installed and  properly connected at each terminal block to BP 

units

All condensate drain piping is connected, including fan coil tie‐in, and insulated as 

required

Refrigerant lines are completely insulated including flare nut connections at Indoor 

Units and BP units

Start Up Checklist

Page 84: 8 Zone Multi Split Key Pts Install PT RLC 1307 PP0 01A

© 2012 Daikin ACSlide 84

Start Up Checklist All applicable ductwork is connected and air filters installed

Line Voltage is checked and verified to be within specified range for  all system 

components

Power up BP units

Power up outdoor unit  to energize crankcase heaters (minimum 6 hrs)  Initialization 

sequence starts and the system addresses are set – Setup Navigation Remote 

Controllers (for FFQ)

System refrigerant charge – Additional Refrigerant Charge mode

Test Operation

Remaining System Field Settings

Verify system operation in Cool & Heat mode as outside ambient temperature 

conditions allow (heat mode is prohibited above 75.2°F outside air temperature)

Page 85: 8 Zone Multi Split Key Pts Install PT RLC 1307 PP0 01A

© 2012 Daikin ACSlide 85

Operating TestFollow the “Operating Test” as described in the installation manual of the outdoor unit. If BP unit does not operate normally during the test run, the error can be checked on the remote controller display for the indoor unit.

Simple diagnosis can be done using the LEDs on the BP unit’s circuit board.For details, see the label on the inside of the BP unit’s electrical wiring unit cover.

*DO NOT perform any other procedures during Operating Test*Operating Test CANNOT be performed during: initialization, additional charge, or recovering mode

Error Codes displayed on the remote controller

Code Nonconformity during installation Remedial action

A9 Electric expansion valve connector not connected (BP unit)

Please contact your dealer

E2 Printed circuit board faulty (BP unit)

J0 Liquid and gas thermistor faulty (BP unit)

U4 Transmission error between BP unit and indoor unit

Correctly connect the inter connections between BP unit and indoor unit

U9 Transmission error between outdoor unit and BP unit

Correctly connect the inter connections between outdoor unit and BP unit

Page 86: 8 Zone Multi Split Key Pts Install PT RLC 1307 PP0 01A

© 2012 Daikin ACSlide 86

Operating Test

Power On – Check Operation

Insure all thermisters and transducers are in place

Power ON outdoor unit for 6 hours (crank case heater)

Power ON branch port units

Open Service Valves

Perform check operation

Press/Hold BS4 (Test) button for 5 seconds

Page 87: 8 Zone Multi Split Key Pts Install PT RLC 1307 PP0 01A

© 2012 Daikin ACSlide 87

Operating Test

Temperature Control – Check Operation

Makes sure the indoor and outdoor units are operating normally

Run each indoor unit one at a time and make sure the outdoor unit is also 

running 

Check to see if cold (or hot) air is coming out of the indoor unit

Press the fan direction and fan strength buttons on the indoor unit to see 

if they operate properly

Page 88: 8 Zone Multi Split Key Pts Install PT RLC 1307 PP0 01A

© 2012 Daikin ACSlide 88

• Outdoor Unit

• Indoor Units & Controls

• Branch Provider Units

• 8‐Zone Selection Tool

• Refrigerant Piping

• REFNET Fittings

• Installation Examples

• Start Up Checklist

Topics Recap

Page 89: 8 Zone Multi Split Key Pts Install PT RLC 1307 PP0 01A

© 2012 Daikin AC

Thank YouPT‐RLC‐1207‐PP0‐01A